Permit (262) ,,.
IIIIICITY OF TIGARD ELECTRICAL PERMIT
COMMUNITY DEVELOPMENT Permit#: ELC2016 00757
T i GARD 13125 SW Hall Blvd.,Tigard OR 97223 503.718.2439 Date Issued: 11/21/2016
Parcel: 2S101 DA00100
Jurisdiction: Tigard
Site address: 13010 SW 68TH PKWY
Project: Triangle Corporate Park I Subdivision: VARNS ACRES Lot: 9
Project Description: Building 1 -Roof mounted solar photovoltaic system,
Contractor: TICE ELECTRIC Owner: PACIFIC NW PROPERTIES LIMITED PA
5405 N LAGOON AVE. STERN FAMILY LIMITED PARTNERSHIP
PORTLAND, OR 97217 STERN, HELEN R REVOCABLE TRUST
6600 SW 105TH AVE#175
BEAVERTON, OR 97008
PHONE: 503-872-8230 PHONE: 503-626-3500
FAX: 971-230-3330
FEES
Quantity Description Date Amount
12 crt Branch Circuits wo/Purchase 10/28/2016 $137.80
Specifics: Service or Feeder
1 ea 15.01 to 25 kva 10/28/2016 $200.34
Type of Use: COM 75 ea Each additional kva over 25 10/28/2016 $556.50
Class of Work: ALT 224 Plan Review-Electrical 10/28/2016 $223.66
Type of Const: 107 12%State Surcharge- 10/28/2016 $107.36
Occupancy Grp: Electrical
Total $1,225.66
Required Items and Reports(Conditions)
This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other applicable law. All work will
be done in accordance with approved plans. This permit will expire if work is not started within 180 days of issuance, or if work is suspended for more the 180
days. ATTENTION: Oregon law requires you to folio -. [Ides adopted by the Oregon Utility Notification Center. Th• - rules are set forth in OAR
952-001-0010 through OAR 952-001-0090. Ya.•.y of the •les or direct questions to OUNC by calling 503. 32. -:7 or 1-=:
Electrical Permit Application i - FOR OFF►tF I SE()NI,l
'r� 4 Received 1 f / v Permit#: 4:-,Z630/(0 -79
J 7
City of Tigard Date/By: �G '�
lig a 13125 SW Hall Blvd.,Tigard,OR 97223 Plan Review / / Related Permit#:�f'�/� q��,_G%j
I Phone: 503.718.2439 Fax: 503.598.1960 ( 4 ?4\16 Date/By: /0 �7 /(/i iI Bf See Page 2 for
Inspection Line: 503.639.4175 +a C Ready Date y: Supplemental Information
T I G A R D g �e, Notified/Method: t`ty/9-7 /` r r ple
Internet: www.tigard-or.gov or.gov a e.kS�
11 i) r N 1
TYPE (•prON' Please check all that a 1 (submit 2 sets of plans w/items checked):
- ��� rel.' PPY
0 Addition/alterit? e �
®New constructionService or feeder 400 amps or more 0 Building over three stories.
❑Demolition 0 Other: where the available fault current 0 Marinas and boatyards.
TEGORY OF CONSTRUCTIONexceeds 10,000 amps at 150 volts or 0 Floating buildings.
CA
less to ground,or exceeds 14,000 0 Commercial-use agricultural
❑ 1-and 2-family dwelling ®Commercial/industrial ❑Accessory building apps for all other installations. buildings.
Master builder 0 Other: 0 Fire pump. 0 Installation of 150 KVA or
❑Multi-family 0 larger separately derived
,JOB SITE INFORMATION?AND LOCATION ❑Emergency system. g p y
❑Addition of new motor load of system.
Job#:80.7527 I Job site address:13010 SW 68th Parkway 100HP or more. occupancy.
❑Six or more residential units.
❑Health-care facilities. ❑Recreational vehicle parks.
City/State/ZIP:Tigard.OR 97223 0 Supply voltage for more than
0 Hazardous locations. 600 volts nominal.
Suite/bldg./apt.#: I Project name:Triangle 1 ❑Service or feeder 600 amps or more.
Cross street/directions to job site: .E SCHEDULE
Description I Qty. I Each I Total I `
New residential single-or multi-family dwelling unit.
Lot#: Includes attached garage.
Subdivision: 1,000 sq.ft.or less 168.54 4
Tax map/parcel#: Ea.add'I 500 sq.ft.or portion 33.92 1
DESCRIPTION OF WORK Limited energy,residential 7500 2
(with above sq.ft.)
ADDING SOLAR ARRAY ON ROOF Limited energy,multi-family 75.00 2
residential(with above sq.ft.)
Renewable Energy El See Page 2
El'PROPERTY OWNER 0 TENANT Services or feeders installation,alteration,and/or relocation
200 amps or less
100.70 2
Name: 201 amps to 400 amps 133.56 2
Address: 401 amps to 600 amps 200.34 2
City/State/ZIP: 601 amps to 1,000 amps 301.04 2
Phone:( ) I Fax:( ) Over 1,000 amps or volts 552.26 2
Temporary services or feeders installation,alteration,and/or
Email: relocation
59.36 1
Owner installation:This installation is being made on property that I own which is not 200 amps or less 125.083 2
intended for sale,lease,rent,or exchange,according to ORS 447,449,670,and 701. 201 amps to 400 amps 168.54 2
Date: 401 amps to 599 amps
Owner signature: Branch circuits—new,alteration,or extension,per panel
❑ APPLICANT [" CO ACT PERSONA.Fee for branch circuits with
above service or feeder fee, 7.42 2
Business name:TICS ELECTRIC COMPANY each branch circuit
B.Fee for branch circuits without
Contact name:KEVIN SHANNON service or feeder fee,first 1 56.18 s(p<1 O 2
Address:5405 N LAGOON AVE branch circuit
Each add'1 branch circuit 1 1 7.42 457• L2_..2
City/State/ZIP:PORTLAND/OR/97217 Miscellaneous(service or feeder not included)
Phone:(503)341-7317 I ( )
Fax: : Each manufactured or modular 67.84 2
dwelling,service and/or feeder
Email:kevins@ticeelectric.com Reconnect only 67.84 2
CONTRACTOR Pump or irrigation circle 67.84 2
Sign or outline lighting 67.84 2
Business name:TICE ELECTRIC COMPANY Signal circuit(s)or limited-energy
0 See Page 2 2
Address:5405 N LAGOON AVE panel,alteration,or extension.
Each additional inspection over allowable in any of the above
City/State/ZIP:PORTLAND/OR/97217 Additional inspection(1 hr min) 66.25/hr
Phone:(503)872-8230 I
Fax:(971)230-3330 Investigation(1 hr mm) 90.00/hr
Industrial plant(1 hr min) 78.18/hr
Email:theresah@ticeelec.com Inspections for which no fee is 90.00/hr
specifically
Lic.: 166 Electrical Lic.: 26-126C Suprv.Lic.: 3940S listed(%hr min)
ELECTIRIC PERMIT FEES '
Suprv.Electrician signature,required: P / Subtotal: N.to
Date: 9/30/2016 0 Plan Review Required(25%of permit fee): 7 2 3.(p Ifr1
Print name: Bob Richardson State surcharge(12%of permit fee): -fi-� yJ •
TOTAL PERMIT FEE:
Authorized signature: I This permit application expires if a permit is not obtained within 180
Date: days after it has been accepted a iplete.
IPrint name: L s Number of inspections allowed per permit
I:\BuildingTermits\ELC PermitApp_ELR_ERE.doc Rev 06/17/2015
440-4615T(11/05/COM/WEB
Electrical Permit Application—City of Tigard
Page 2—Supplemental Information
Limited Energy Permit Fees: Renewable Energy Permit Fees:
RESIDENTIAL WORK ONLY: FEE SCHEDULE
Fee for all residential systems combined: $75.00 Description I Qty, I Each I Total' I *
Renewable electrical energy systems:
Check Type of Work Involved: 5 kva or less 100.70 2
5.01 to 15 kva 133.56 2
❑ Audio and Stereo Systems* 15.01 to 25 kva ' 200.34 2.6ENS'I 2
Wind generation systems in excess of 25 kva:
❑ Burglar Alarm 25.01 to 50 kva 301.04 2
❑ Garage Door Opener* 50.01 to 100 kva 552.26 2
>100 kva(fee in accordance 552.26 2
with OAR 918-309-0040)
n Heating, Ventilation and Air Conditioning Solar generation systems in excess of 25 kva:
System*
Each additional kva over 25 7 S 7.42 53-0.503
❑ Vacuum Systems* >100 kva—no additional charge 0.0 3
Each additional inspection over allowable in any of the above:
n Other: Each additional inspection is 66.25/hr 1
charged at an hourly(1 hr min)
Inspections for which no fee is 90.00/hr
specifically listed(%hr min)
COMMERCIAL WORK fl +1LY. ELECTRICAL PERMIT FEES
Fee for each commercial system: $75.00 Subtotal(Enter on Page 1): 17 t-b.a-y
* Number of inspections allowed per permit.
(SEE OAR 918-309-0000)
Check Type of Work Involved:
❑ Audio and Stereo Systems
❑ Boiler Controls
❑ Clock Systems
❑ Data Telecommunication Installation
❑ Fire Alarm Installation
❑ HVAC
❑ Instrumentation
❑ Intercom and Paging Systems
❑ Landscape Irrigation Control*
n Medical
❑ Nurse Calls
n Outdoor Landscape Lighting*
❑ Protective Signaling
❑ Other:
Total number of commercial systems:
*No licenses are required. Licenses are required for all
other installations
I:\Building\Permits\ELC_PermitApp_ELR_ERE.doc Rev 06/17/2015
Electrical Permit Application FOR OFFICE I:SI a\1,‘
City of Tigard Datee Bed Permit#:
t
Phone: 503.718.2439 Fax: 503.598.1960 Date/B :
13125 SW Hall Blvd.,Tigard,OR 97223 Plan Review
Related Permit#:
Inspection Line: 503.639.4175 Ready Date/By: Juris: El See Page 2 for
T I G A R D Internet: www.tigard-or.gov Notified/Method: Supplemental Information
TYPE OF WORK PLAN REVIEW
❑New construction 0 Addition/alteration/replacement Please check all that apply(submit 2 sets of plans w/items checked):
0 Service or feeder 400 amps or more 0 Building over three stories.
❑Demolition 0 Other: where the available fault current 0 Marinas and boatyards.
CATEGORY OF CONSTRUCTION exceeds 10,000 amps at 150 volts or 0 Floating buildings.
❑ 1-and 2-family dwelling 0 Commercial/industrial 0 Accessory building less to ground,or exceeds 14,000 0 Commercial-use agricultural
amps for all other installations. buildings.
❑Multi-family 0 Master builder 0 Other: 0 Fire pump. 0 Installation of 150 KVA or
JOB SITE INFORMATION AND LOCATION 0 Emergency system. larger separately derived
❑Addition of new motor load of system.
Job#: Job site address: 100HP or more. ❑"A","E","1-2","1-3",
❑Six or more residential units. occupancy.
City/State/ZIP: ❑Health-care facilities. 0 Recreational vehicle parks.
0 Hazardous locations. 0 Supply voltage for more than
Suite/bldg./apt.#: Project name:
❑Service or feeder 600 amps or more. 600 volts nominal.
Cross street/directions to job site: FEE SCHEDULE
Description I Qty. I Each I Total I *
New residential single-or multi-family dwelling unit.
Subdivision: Lot#: Includes attached garage.
1,000 sq.ft.or less 168.54 4
Tax map/parcel#: Ea.add'I 500 sq.ft.or portion 33.92 1
DESCRIPTION OF WORK Limited energy,residential
75.00 2
(with above sq.ft.)
Limited energy,multi-family 75.00 2
residential(with above sq.ft.)
Renewable Energy 0 See Page 2
❑ PROPERTY OWNER I 0 '' NiENT" Services or feeders installation,alteration,and/or relocation
Name: 200 amps or less 100.70 2
201 amps to 400 amps 133.56 2
Address:
401 amps to 600 amps 200.34 2
City/State/ZIP: 601 amps to 1,000 amps 301.04 2
Phone:( ) Fax:( ) Over 1,000 amps or volts 552.26 2
Temporary services or feeders installation,alteration,and/or
Email: relocation
Owner installation:This installation is being made on property that I own which is not 200 amps or less 59.36 1
intended for sale,lease,rent,or exchange,according to ORS 447,449,670,and 701. 201 amps to 400 amps 125.08 2
Owner signature: Date: 401 amps to 599 amps 168.54 2
0 APPLICANT'' 0 CONTACT PERSON Branch circuits—new,alteration,or extension,per panel
A.Fee for branch circuits with
Business name: above service or feeder fee, 7 42 2
each branch circuit
Contact name: B.Fee for branch circuits without
service or feeder fee,first 56.18 2
Address: branch circuit
City/State/ZIP: Each add'l branch circuit 7.42 2
Miscellaneous(service or feeder not included)
Phone:( ) Fax: :( ) Each manufactured or modular 67.84 2
dwelling,service and/or feeder
Email: Reconnect only 67.84 2
CONTRACTOR Pump or irrigation circle 67.84 2
Business name: Sign or outline lighting 67.84 2
Signal circuit(s)or limited-energy ❑ See Page 2 2
Address: panel,alteration,or extension.
Each additional inspection over allowable in any of the above
City/State/ZIP: Additional inspection(1 hr min) 66.25/hr
Phone:( ) Fax:( ) Investigation(1 hr min) 90.00/hr
Industrial plant(1 hr min) 78.18/hr
Email: Inspections for which no fee is
90.00/hr
CCB Lic.: Electrical Lic.: Suprv.Lic.:
specifically listed('h hr min)
ELECTRICAL PERMIT FEES
Suprv.Electrician signature,required: Subtotal:
Print name: Date: 0 Plan Review Required(25%of permit fee):
State surcharge(12%of permit fee):
TOTAL PERMIT FEE:
Authorized signature:
This permit application expires if a permit is not obtained within 180
Print name: Date: days after it has been accepted as complete.
* Number of inspections allowed per permit.
I:\Building\Permits\ELC_PermitApp_ELR_ERE.doc Rev 06/17/2015 440-4615T(11/05/COM/WEB
,t14—F4:74:1* 41'4'''': *L''''''' ;444—**'
41::':IZrrt'*''irf:cilj'r':'e';f:7'Ziles*'clt :i':i''Ct'm";p':nA;r411 =
j
ji
09/29/16 PGE ,�
' CONTACT: Nick Rowley REA
PHONE: 541-754-2001 '
aka
CUSTOMER NAME: NWPE -Triangle Corparate Park I ''
ADDRESS: 13010 SW 68th Parkway Tigard Ore 97223
4
a.
SDPM/ENGR: Tod L. Shattuck
WR: M2174993 .
PHONE: 503-672-5466 '
3-PHASE SECONDARY LINE-LINE FAULT CURRENT (RMS)
rte;
TRANSFORMER DATA { }
PAD MOUNT? YES
'a XFMR Impedance(%): 5.32 % 3-PH SUBMERSII YES
+' TRANSFORMER SIZE: 1500 KVA
XFMR? NO I{,
Secondary VOLTAGE(L to L): 480 v WYE
OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY
Secondary Wire LENGTH: 85 Feet
WIRE SIZE
>" Number of SECONDARY RUNS: 8 Run(s)of: 1350 QX UG I
Secondary WIRE Resistance R: 0.0600 Ohms/1000' ri
k.','
Secondary WIRE Reactance X: 0.0330 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop)
Service Wire LENGTH: 1 Feet WIRE SIZE
Number of Service RUNS: 1 Run(s)of: I I f
Service WIRE Resistance R: 0.0180 Ohms/1000'
Service WIRE Reactance X: 0.0258 Ohms/1000' 9,
' MAXIMUM FAULT CURRENT*: 31,042 Amps
, ' *Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating.
Based on a panel size of: 1600amp Amps •,
' ' 'TOPPtnt T1s .a ei,ZtO and,0 19646"Print -Ph e Data ,
s al`- '- - -" "� a 4 `as �r ' r ,, vk.
f Portland General Electric Company
PN
'
09/29/16 ,!:*,':
GE .,�
f , CONTACT: Nick Rowley REA
N.
�v
PHONE: 541-754-2001
# CUSTOMER NAME: NWPE -Triangle Corparate Park I
T . ADDRESS: 13010 SW 68th Parkway Tigard Ore 97223
SDPM/ENGR: Tod L. Shattuck WR: M2174993
PHONE: 503-672-5466
' 3-PHASE SECONDARY LINE-LINE FAULT CURRENT(RMS)
,, °. TRANSFORMER DATA
' PAD MOUNT? YES .
XFMR Impedance (%): 5.32 % 3-PHSUBMERSIIYES
'
TRANSFORMER SIZE: 1500 KVA XFMR? NO
Secondary VOLTAGE(L to L): 480 v WYE OH BANK? NO
VAULT--> VAULT ( or Pole --> Pole) SECONDARY tl`
Secondary Wire LENGTH: 85 Feet WIRE SIZE
Number of SECONDARY RUNS: 8 Run(s)of: 1350 QX UG
Secondary WIRE Resistance R: 0.0600 Ohms/1000'
Secondary WIRE Reactance X: 0.0330 Ohms/1000'
VAULT ( or Pole) --> PANEL SECONDARY (or Svc Drop) {4
Service Wire LENGTH: 1 Feet WIRE SIZE
Number of Service RUNS: 1 Run(s)of: I I „
Service WIRE Resistance R: 0.0180 Ohms/1000'
Service WIRE Reactance X: 0.0258 Ohms/1000'
MAXIMUM FAULT CURRENT*: 31,042 Amps
: 'Maximum fault current based upon transformers/conductors sized for 100% of electrical panel rating. '
Based on a panel size of: 1600amp Amps
`�F nt ttu§Page:0 1 Qd c ise llnri a=p4psea` " °
13125 SW Hall Blvd.
Tigard, OR 97223
City of Tigard
Location:
13010 SW 68TH PKWY, TIGARD, OR, 97223
Record Type:
Commercial - Electrical
Inspection Type:
199 Electrical final
Result:
PASS- NoCofO
Comments:
Violation Summary:
Inspector
Tel: 503.718.2439
Inspection Date:
Record ID:
ELC2016-00757
Inspector:
Chip Barnett
Contractor