Report (10)
f tucci E , ' ' ,.�, _ � . Fire ProtectionWorldwide Products 5F? 2 9 7_(�1�, contacts wwwtyco-fire.com Series TY-FRB — 2.8, 5.6,`�and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General when exposed to corrosive atmo- spheres. Although corrosion-resistant Description coated sprinklers have passed the standard corrosion tests of the appli- , The TYCO Series TY-FRB, 2.8, 4.2, cable approval agencies,the testing is • _ 5.6,and 8.0 K-factor, Upright,Pendent, not representative of all possible cor- ` rosive atmospheres. Consequently, and Recessed Pendent Sprinklersli , I described in this data sheet are quick it is recommended that the end user b response, standard coverage, deco- e consulted with respect to the suit- k} t rative 3 mm glass bulb-type spray ability of these coatings for any given t. sprinklers designed for use in light or corrosive environment. The effects of ordinary hazard,commercial occupan- ambient temperature,concentration ofit chemicals, and gas/chemical velocity, cies such as banks, hotels, and shop- should ping malls. should be considered, as a minimum, along with the corrosive nature of the The recessed version of the Series chemical to which the sprinklers will be TY-FRB Pendent Sprinkler, where exposed. applicable, is intended for use in areas with a finished ceiling. This recessed An intermediate level of the Series TY-FRB Pendent Sprinklers is detailed pendent sprinkler uses one of the following: in Technical Data Sheet TFP356, and • Sprinkler Guards are detailed in Tech- A two-piece Style 10(1/2 inch NPT •) nical Data Sheet TFP780. or Style 40(3/4 inch NPT)Recessed Escutcheon with 1/2 inch (12,7 mm) "£ NOTICE of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment The Series TY-FRB, 2.8, 4.2, 5.6, and 8.0 K-factor, Upright, Pendent, ¢ 1 from the flush pendent position,or a • A two-piece Style 20(1/2 inch NPT) and Recessed Pendent Sprinklers - " described herein must be installed . or Style 30(3/4 inch NPT) Recessed and maintained in compliance with .. Escutcheon with 1/4 inch (6,4 mm) this document and with the applica- of recessed adjustment or upto 1/2 ble standards of the National Fire Pro- - . inch (12,7 mm) of total adjustment tection Association, in addition to the from the flush pendent position. standards of any authorities having The adjustment provided by the jurisdiction.Failure to do so may impair Recessed Escutcheon reduces the the performance of these devices. Sprinkler accuracy to which the fixed pipe drops The owner is responsible for maintain- to the sprinklers must be cut. in their fire Identification 9 protection system and Corrosion-resistant coatings, where devices in proper operating condition. applicable,are utilized to extend the life The installing contractor or sprinkler Number (SIN) of copper alloy sprinklers beyond that manufacturer should be contacted with which would otherwise be obtained any questions. TY1131 - Upright 2.8K,1/2"NPT TY1231 -Pendent 2.8K, 1/2"NPT I TY2131 - Upright 4.2K, 1/2"NPT I TY2231 - Pendent 4.2K, 1/2"NPT IMPORTANT .F--F.. F�2,-,AL, ,_,._ / TY3131 -Upright 5.6K, 1/2"NPT Always refer to Technical Data 1 TY3231 - Pendent 5.6K, 1/2""NPT Sheet TFP700 for the `INSTALLER OFFICE COPY TY4131 -Upright 8.0K,3/4"NPT WARNING"that provides cautions 1. TY4231 - Pendent 8.0K,3/4"NPT with respect to handling and instal- lation of sprinkler systems and com- I.3)7.� e-', i, /lc-444 ` "`4i TY4831 - Upright 8.0K, 1/2"NPT ponents. Improper handling and TY4931 - Pendent 8.0K, 1/2""NPT installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 NOVEMBER 2015 TFP171 TFP171 Page 2 of 10 .mi 1 - Frame 3 - Sealing 5 - Compression *Temperature rating ** Pipe thread connections per 2 - Button Assembly Screw is indicated on ISO 7-1 can be provided on ESCUTCHEON special request. PLATE SEATING 4 - Bulb 6 - Deflector* • • Deflector. q 7 - Bushing SURFACE 7 r i-via �� 1 7/16" ��1I A 3 (11,1 mm) �i� l r 2 NOMINAL 2-1/4" I MAKE IN (57,2 mm) 4 � 2 3/16" (556 mm) mm c' S . (39,7 ) IIC 1/2" NPT** WRENCH STYLE 10 or 20 p-7/8"(73,0 mm)DIA. FLATS RECESSED CROSS SECTION UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT FIGURE 1 QUICK RESPONSE SERIES TY-FRB K FRCTOUPRIGHT 1/21NCAND HNPPPENDENT(TY1231)SPRINKLERS 2.81 - Frame 3 - Sealing 5 - Compression *Temperature rating ** Pipe thread connections per 2 - Button Assembly Screw is indicated on ISO 7-1 can be provided on ESCUTCHEON Deflector. specialrequest.uest. PLATE SEATING 4 - Bulb 6 - Deflector* q SURFACE 1 y it*- zAa - 7/16" 1�1:'� ,F f/i 2 (NOMINAL 0j a , / 2-3/16" '- A r A (55,64 MAKE-IN mm) rr 2 3/16" 1-1/2" ilay---- 1 l (55,6 mm) i (38,1 mm) ice-5 1 .., . R' 1/2" NPT** WRENCH STYLE 10 or 20 -2-7/8"(73,0 mm)DIA. RECESSED FLATS UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB K RI GHT(TY Y21 1)AHNP PENDENT(TY2231)SPRINKLERS 4.2 1 - Frame 3 - Sealing 5 - Compression *Temperature rating ** Pipe thread connections per 2 - Button Assembly Screw is indicated on ISO 7-1 can be provided on ESCUTCHEON 4 Bulb 6 Deflector* Deflector. special request. PLATE SEATING SURFACE 1 iii7/16" iriliPm_ �r (11,1 mm) �4 � 2 i NOMINAL } 2 3/16" � MAKE-IN (55,6 mm) 4 , 2-3/16" ,,x�-1-/2" "ii ' 1 I (55,6 mm) I c$;1 mm) .P ` �5 �111 •-,_,�A"-. cif.- 6* 1/2" NPT** WRENCH STYLE 10 or 20 - 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UFR GHT(T Y3 INCH 1)ANP PENDENT(TY3231)SPRINKLERS TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Frame 3 ASealingssem 5 Compression Deflector. special request. PLATE SEATING 2 Button Assembly Screw SURFACE 4 - Bulb 6 - Deflector* 0 a 1 1/2" 04 (127mm) 'rte 3 NOMINAL ��- 77 `=� MAKE-IN (525-,57/1L) 8 7/16n 5 ) L �i 2 2-1/4° 0 1-9/16" (57,2 mm) IAllil I 4 (39,7 mm)1 111 0I -- 3/4"NPT** —'��-- ..z WRENCH STYLE 30 or 40 -W, �` 6* FLATS RECESSED 2-7/8"(73,0 mm)DIA. UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw —/ rr-r"- -�-�� 1 3 - Sealing 6 - Deflector* Assembly 7/16" �LL' 3 4 Bulb (11,1 mm)111114 2-1/4" Y NOMINAL (57,2 mm) , 2 `=, MAKE-IN * Temperature rating is 2-3/166 1-9/16" I 4 indicated on Deflector. (55,6 mm) (39,7 mm) _ -- ill ilICL_____________ 5 ** Pipe thread connections QW -,` * per ISO 7-1 can be 1/2"NPT** WRENCH 6 provided on special UPRIGHT FLATS request. PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT L' WRENCH RECESS WRENCH RECESS (END"A"USED FOR �AP 4.1.,ILL-Fil 1/2"NPT MODELS) r WRENCHRECESS 11 (END"B"USED FOR `� 3/4" NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER FIGURE 6 WRENCHING AREA W-TYPE 6 SPRINKLER FIGURE 7 WRENCH W--TYPE 7 RECESSED SPRINKLER WRENCH TFP171 Page 4 of 10 Do not attempt to compensate for Desi n insufficient adjustment in the Escutch- Dafa Criteria eon Plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Approvals The TYCO Series TY-FRB, 2.8, 4.2, UL and C-UL Listed 5.6,and 8.0 K-factor,Upright,Pendent, Series TY-FRB Upright and Pendent FM,LPCB,and NYC Approved and Recessed Pendent Sprinklers are Sprinklers Refer to Table A and B for complete intended for fire protection systems The Series TY-FRB Pendinstalled ent and approvalat information including corrosion- designed installation rdarulese with ognized by nhe stan- praccorrht danceers withust the efollowing resistant status. instructions. the applicable Listing or Approval Maximum Working Pressure agency (such as, UL Listing is based Step 1.Install Pendent sprinklers in the Refer to Table C. on the requirements of NFPA 13, and tep 1. P position. upright spthe rin- Discharge Coefficient FM Approval is based on the require- pendentpin the upright Install position. K=2.8 gpm/psis(40,3 Ipm/barY2) ments of FM's Loss Prevention DataWith K=4.2 Qpm/psi' (60.5lom/bar'") Sheets). Only the Style 10, 20, 30r Stepe2.edto the pipe threadsealant slant K= 5.6 gpm/psis(80,6 Ipm/bars) 40 Recessed Escutcheon, as app ico K=8.0 gpm/psis(115,2 Ipm/barlt) ble,is to be used for recessed pendent tighten the sprinkler into the sprinkler installations. Temperature Rating Step 3. Tighten the sprinkler into the Refer to Table A and B. Installation sprinkler fitting using only the W-Type Finishes6 Sprinkler Wrench(Figure 6).With ref- Sprinkler:Refer to Table D. The TYCO Series TY-FRB,2.8,4.2,5.6, erence to Figures 1 through 5, apply and 8.0 K-factor,Upright,Pendent,and the W Type 6 Sprinkler Wrench to the Recessed Escutcheon:Signal or Pure Recessed Pendent Sprinklers must sprinkler wrench flats. White,Jet Black,Chrome Plated,or be installed in accordance with this Natural Brass section. Series TY-FRB Recessed Pendent Sprinklers Physical Characteristics Bronze General Instructions The Series TY-FRB Recessed Pendent Frame Brass/Copper Do not install any bulb-type sprinkler Sprinklers must be installed in accor- Setton Sealing Assembly..Beryllium Nickel w/TEFLON if q bulb is crackedtthere ise a loss dance with the following instructions. Bulb Glass of liquid from the bulb.With the sprin- Compression Screw Bronze kler held horizontally,a small air bubble Step A.After installing the Style 10,20, Deflector Copper/Bronze Bushing(K=2.8) Bronze should be present.The diameter of the 30, or 40 Mounting Plate, as applica- air air bubble is approximately 1/16 inch ble,over the sprinkler threads and with Operation (1,6 mm)for the 135°F(57°C)and 3/32 pipe-thread sealant applied to the pipe inch(2,4 mm)for the 286°F(141°C)tem- threads,hand-tighten the sprinkler into The glass bulb contains a fluid that perature ratings. the sprinkler fitting. expands when exposed to heat.When A leak-tight 1/2 inch NPT sprinkler Step B. Tighten the sprinkler into the the rated temperature is reached, the joint should be obtained by applying a sprinkler fitting using only the W-Type fluid expands sufficiently to shatter the minimum to maximum torque of 7 to 7 Recessed Sprinkler Wrench (Figure glass bulb, allowing the sprinkler to 14 ft.-lbs. (9,5 to 19,0 Nm).A leak tight 7). With reference to Hissees d1Sprinkler, activate and water to flow. 3/4 inch NPT sprinkler joint should be apply the W Typ obtained with a torque of 10 to 20 ft.- Wrench to the sprinkler wrench flats. lbs. (13,4 to 26,8 Nm). Higher levels of Step C. After ceiling installation and torque can distort the sprinkler Inlet finishing, slide on the Style 10, 20, 30, with consequent leakage or impairment or 40 Closure over the Series TY-FRB of the sprinkler. Siler ad uthe Closure o MountingprnkPlatenpuntilsh its flange comesver the in contact with the ceiling. TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL I CHROME FACTOR COLOR BRASS PLATED I POLYESTER*** 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) and 175°F(79°C) Yellow UPRIGHT 1,2,3,4 (TY1131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red (TY1231)* 175°F(79°C) Yellow Figure 8 200°F(93°C) Green 135°F(57°C) Orange 1,2,4 RECESSED PENDENT 155°F(68°C) Red (TY1231)** 175°F(79°C) Yellow Figure 9 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) L 200°F(93°C) Green �] 286°F(141°C) Blue 135°F(57°C) Orange 4.2 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red (TY2231)* 1,2 Figure 10 175°F(79°C) Yellow 200°F(93°C) Green RECESSED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231)** 175°F(79°C) Yellow Figure 11 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 Page 6 of 10 SPRINKLER FINISH(See Note 8) I CHROME POLYESTER*** LEAD K BULB LIQUID NATURAL TYPE TEMPERATURE COLOR BRASS PLATED I COATED FACTOR 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY3231) and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5 UPRIGHT 200°F(93°C) Green (TY3131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red N/A 5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 1/2"NPT (TY3231)* Figure 12 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red N/A Figure PENDENT ) 175°F(79°C) Yellow 1,2,3,4,5 ( Figure 13 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT (TY4231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 8.0 PENDENT175°F 1,2,5 N/A 3/4"NPT (TY4231)* 175°F(79°C) Figure 14 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT175°F 1,2,3,5 N/A (TY4231)** 175°F(79°C) Figure 15 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY4931) 1,2,4,5,6 1,2,5 1/2"NPT and 175°F(79°C) Yellow UPRIGHT 200°F(93°C) Green (TY4831) 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377. 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K I TYPE NATURAL I CHROME FACTORBRASS PLATED I POLYESTER LEAD COATED PENDENT(TY1231) and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY1231) PENDENT(TY2231) and 4.2 UPRIGHT(TY2131) _____>.1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY2231) PENDENT(TY3231) and 5.6 UPRIGHT(TY3131) 250 PSI(17,2 BAR) 1/2"NPT OR 175 PSI(12,1 BAR) RECESSED (SEE NOTE 1) PENDENT(TY3231) PENDENT(TY4231) and 8.0 UPRIGHT(TY4131) 175 PSI 3/4"NPT 175 PSI(12,1 BAR) (12,1 BAR) RECESSED - PENDENT(TY4231) N/A g 0 PENDENT(TY4931) UPRIGHT(TY4831) 175 PSI(12,1 BAR) 1/2"NPT 175 PSI (12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Under- writers Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE Care and ihave not operatedcannotbe,should be replaced Care must be exercised to avoid Maintenance byf they completely cleaned damage to the sprinklers -before, wiping the sprinkler with a cloth or by during, and after installation. Sprin- klers brushing it with a soft bristle brush. klers dams ed bydropping, The TYCO Series TY-FRB must be Care must be exercised to avoid g striking, maintained and serviced in accordance damage to the sprinklers before, bereplaced. Also, replace any sage,or the like, prin- with this section. during, and after installation. Sprin- kler that has a crackebulb or thathasklers damaged by dropping, striking, lost liquid from its bulb. (Ref. Installa- Before closing a fire protection system main control valve for maintenance wrench twist/slippage,or the like,must tion Section). be replaced. Also, replace any sprin- Initial and frequent visual inspections of work on the fire protection system that it controls, obtain permission to kler that has a cracked bulb or that has random samples are recommended for shut down the affected fire protection lost liquid from its bulb. (Ref. Installa- corrosion-resistant sprinklers to verify the interitof the systems from the proper authorities tion Section.) and notify all personnel who may be The owner is responsible for the material of construction.)on-resistant Thereafter, affected by this action. inspection,testing,and maintenance of annual inspections per NFPA 25 should their fire protection system and devices suffice. Absence of the outer piece of an in compliance with this document, as Inspections of corrosion-resistant escutcheon, which is used to cover a clearance hole, can delay sprinkler well as with the applicable standards sprinklers are recommended at close operation in a fire situation. of the National Fire Protection Asso- range, instead of from the floor level ciwhich are found to the standardso .g., NFPA of 25), inaddition a dition to Sprinklerspng or exhibiting visible signsobe the having jurisdiction. Contactr the insides per NFPA.better I etermi en thet close exact range can determine the in eg- corrosion must be replaced. ing contractor or sprinkler manufac- rity ofhe condition andcorrosion-resistante sm i material, Automatic sprinklers must never be turer regarding any questions. rity the material, painted, plated, coated, or other- which can be affected by the corrosive wise altered after leavingthe factory. Automatic sprinkler systems are rec- conditions present. ected, tested, Modified sprinklers mustbereplaced. and maintained by a qommended to be ualified d Inspec- Sprinklers that have been exposed to tion Service in accordance with local corrosive products of combustion, but requirements and/or national codes. TFP171 Page 8 of 10 2-7/82-7/8" DIA. (73,0 DIA. (73,0 mm) (73,0 mm) 3/4" (19,1 mm) 1/2±1/8" 1/2"(12,7 mm) 5/8±1/4" 12,7±3,2 mm) 1/4" (6,4 mm) (159±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm) ( 2-1/4" DIA. f- (57,2 mm) 1MOUNTING FACE OF (57,2 mm) MOUNTING / FACE OF SPRINKLERPLATE SPRINKLER PLATE FITTING FITTING / 1/8" / 2 m - (3,2 mm) (3,2 mm) � 71-- ii T =-li f� T4_ PT/7i. r 7 1„ ��/ ING SII SOURFACE IN MOUNTING �■ ' SURFACE ��•�� if=��� 1-5/16"(33,3 mm) SERIES 1-5/16"(33,3 mm) CLOSURE SERIES CLOSURE TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16" (27,0 mm) FIGURE 8FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIE P 2RECESSED ESCUTCHEONCE 1/2 INCH TOTAL MENT STYLE 10 RECESSED ESCUTCHEON 2.8E 0FACTOR, 1/ ESCNPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8" DIA. - f-2(73,0 DIA. (73,0 mm) 1/2"(12,7 mm) mm) 3/4"(19,1 mm) 1/2±1/8" 5/8±1/4" 1/4" (6,4 mm) (15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 2 1/4" DIA. , 2-1/4" DIA. f- (57,2 mrn)IA / FACE OF (57,2 mm) 1 FACE OF MOUNTING PLATE MOUNTING SPRINKLER SPRINKLER PLATE FITTING FITTING 1/8" / 1 / - (3,2 mm) (3,2 mm) T M ��', PTi7 • G�_ '' "�� MOUNTING , 7-A pi_ r 7./ t \ . .a- L. .•WB/ 1i/ u, SURFACE . t , MOUNTING '111 - SURFACE 1 1/4"(31,8 mm) 1-1/4"(31,8 mm) SERIES CLOSURE SERIES CLOSURE TY-FRB 1"(25,4 mm) TY-FRB 3/4"(19,1 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE P 21/2 INCH RECESSED TOTAL ADJUSTMENT K- MENT STYLE RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 9 of 10 2-7/8"DIA. 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) (73,0 mm) (15,/8±1/6,4 mm) 1/2±1/8" 1/2"(12,7 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) 1 / (57,2 mm) SPRINKLER MOUNTING FACE OF MOUNTING FITTING PLATE SPRINKLER PLATE FITTING / 1/8" 2 m (3,2 mm) / 3 2 8" ) • Mil I T a1 �� 772 244 \ MOUNTING ,I' MOUNTINGS SURFACE SURFACE -_!''1,= i -+A ,- . CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm) FIGURE 12 FIGURE 13 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2-7/8" DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) MOUNTING (57,2 mm) / FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" (3,2 mm) (3,2 mm) T 7.111 / �� r.\ fMOUNTING �I� f MOUNTING ,� SURFACE SURFACE 1. . CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 14 FIGURE 15 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT 8.0 K-FACTOR,3/4 INCH NPT TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX I � SIN SPRINKLER TEMPERATURE FINISH RATINGS 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 1 155 155°F(68°C) POLYESTER(RAL9010) 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C) POLYESTER(RAL9003) 341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK 2 200 200°F(93°C) POLYESTER(RAL9005)2 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT(3/4"NPT) TY4131 NOTES: 1. Eastern Hemisphere sales only. 391 8.0K PENDENT(3/4"NPT) TY4231 2. Available in only 2.8K,4.2K,and 8.0K,155°F(68°C) and 200°F(93°C);requires lead time to manufacture. 360 8.0K UPRIGHT(1/2"NPT) TY4831" 361 8.0K PENDENT(1/2"NPT) TY4931" TABLE D SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for www.tyco-fire.com. availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright)Sprinkler(specify)temperature rating, (specify) finish or coating, P/N (specify from Table D) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify") finish, P/N(specify") Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 "Refer to Technical Data Sheet TFP770 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. vice TEFLON is trademark of The DuPont Corporation. Fire Protection Products 4 FireLock® V27, K5.6 Models V2709,V2710 ✓at 40.11 11® Standard Spray 40 Horizontal and Recessed Horizontal Sidewall Technical Specifications: Standard and Quick Response Models: V2709, V2710 Style: Horizontal Sidewall or Recessed r . . ' �. . Horizontal Sidewall 11 1s w r "� I{ 4� Nominal Orifice Size: l /13 mm il K Factor: 5.6 Imp./8.1 S.I.1 Nominal Thread Size: 1/2"/15 mm V2709/V2710 V2709/V2710 Standard Horizontal Recessed Horizontal Max. Working Pressure: Sidewall Sidewall • 175 psi/1200 kPa (FM) • 250 psi/1725 kPa (UL) Approvals/Listings: Factory Hydrostatic Test: 100% © 500 psi/3450 kPa cam ® (LPCBI a. ® Min. Operating Pressure: LISTED See Victaulic Publication 10.01 for more details. • 7 psi/48 kPa Temperature Rating: See chart on page 3 Product Description: 1 For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. These Model V27, standard spray horizontal sidewall sprinklers are designed for up to ordinary Hazard per NFPA 13, and can be used for standard or recessed installations. The design provides a crescent-shaped10 water discharge pattern for installation along a wall or under a beam or ceiling. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, 0 reducing assembly effort. This sprinkler is available in various temperature ratings (see chart on page 3) and finishes to meet many design requirements. The recessed pendent should be utilized with a Model V27 I1 recessed escutcheon which provides up to 3/4"/19 mm of e .-..� adjustments. � ��� .� Coverage 1 For coverage area and sprinkler placement, refer to NFPA 13 or applicable standard. Exaggerated for clarity Job/Owner 1111111111111111111111111111111111 -.■, Engineer System No. Location Spec Section IIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIIIIIIIIIIIIIIIIParagraph IIIIIIIIIIIIIIIIIIIII Contractor _.. Approved Submitted By IIIIIIIIIIIIIIIIIIIIIIIIII Date IIIIIIIIIIIIIIIIIIIIIIIIIIII DateIIIIIIIIIIIIIIIIIIIIIIII victaulic.com I Sprinklers I FireLock®I K5.6, V27 I Publication 40.11 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. 1 �CtauIic victaulic.com I Sprinklers I FireLock® I K5.6,V27 I Publication 40.11 Material Specifications: Accessories Horizontal Deflector: Commercial bronze per Installation Wrench: UNS C22000 — Open End: V27 Bulb: Glass with glycerin solution Recessed:V27-2 Bulb Nominal Diameter: Standard: 5.0 mm Sprinkler Finishes: I✓ Quick Response: 3.0 mm Plain Brass Load Screw: Low Silicon bronze per UNS C65100 Chrome plated Pip Cap: Low Silicon bronze per UNS C65100 ✓ White painted3 Spring: Beryllium nickel Flat black painted3 Seal: Teflon2 tape Custom painted3 Frame: Die cast brass 65-30 ❑ Proprietary Nickel/Teflon2 coating3 Lodgement Spring: Stainless steel per UNS S30200 VC-2504 155, 200, 286 SR Only: Wax3 For cabinets and other accessories refer to separate sheet. NOTE:Weather resistant recessed escutcheon available upon request. 2 Teflon is a registered trademark of Dupont Co. 3 UL Listed for corrosion resistance. ^UL Listed and FM Approved for corrosion resistance. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. \ICtaUliC victaulic.com 2 victaulic.com I Sprinklers I FireLock®I K5.6, V27 I Publication 40.11 Approvals/Listings: APPROVALS/LISTINGS Model V2709 V2709 Recessed V2710 V2710 Recessed V2710 Recessed Orifice Size(inches) Orifice Size(mm) 13 '/z. '/z" '13 /z„ Nominal K Factor Imperial 13 13 13 5.6 5.6 13 Nominal K Factor S.I.S 8.16 8.1 8.1 8.1 8.1 8.1 Response Standard 8 1 8.1 Standard Quick Quick Quick Deflector Type Horizontal Recessed Recessed Recessed Sidewall Horizontal Horizontal Horizontal Horizontal Sidewall* Sidewall Sidewall(up to Sidewall(up to Approved Temperature Ratings 1/2"adjustment) 3/4"adjustment) P/C° 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C cULus 175°F/79°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F/79°C 155°F/68°C 155°F/68°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 360°F/182°C 286°F/141°C 200°F/93°C 200°F/93°C 135°F/57°C 155"F/68°C 135°F/57°C 135°F/57°C FM 6 175°F/79°C 155°F/68°C 155°F/68°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F ° 155°F/68°C 200°F/93°C 286°F/141°C 175°F/79°C None 200°F/93°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C NYC/MEA 6#62-99 E 175°F/79°C 15S°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F/79°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 360°F/182°C 286°F/141°C 200°F/93°C 200°F/93°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C CSFM 6#7690-0531:112 175°F/79°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F/79°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 360°F/182°C 286°F/141°C 200°F/93°C 200°F/93°C 135°F/57°C LPCB 6104b/01 155°F/68°C 135°F/57°C 6104b/02 175°F/79°C 155°F/68°C 200°F/93°C None 175°F/79°C None None 286°F/141°C 200°F/93°C 360°F/182°C 286°F/141°C 135"F/57°C 155°F/68°C 135"F/57°C 135°F/57°C VNIIPO 175°F/79°C 155°F/68°C 155°F/68°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 286°F/141°C 175'F/79°C None 200°F/93°C 200°F/93°C 360°F/182°C 286°F/141°C CCCf ZSTBS 155°F/68°C None None None None 5 For K Factor when pressure is measured in Bar,multiply S.I.units by 10.0 6 Light Hazard ONLY Note:Listings and Approvals as of printing.All are approved open. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic CompanAll rights reserved. �CtaUlic' victaulic.com3y. victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.11 Dimensions: 3"/89 mm 1 21/4"/57 mm li♦ „6/ f' II— 5/16"/ IIS _ I�� 11 mm 11/a/ w!����® 8mm � -17.6111, .a in__ � 32 mm 1 �LM M�I i____. � ... Standard HSW—V2709,V2710 11/16"/ 17 mm 11/16" 11/16"/ ...--2 3/16"/ 43mm 30mm Sb mm�/ ��/ p farA�/ ij/ ��y 1 � Finished Ceiling Finished Ceiling 4-12"/102-305mm �� 4-12"/102-305 mm / Per NFPA Per NFPA ; —1- F � � -11111.it;J 2"/51 mm 23/8"/60 mm lig---11,\,,,.......,,,�il�f 2 in.mm 2 Mak Hole 215/16°/ ii:�I:i\i;! Min.Hole Max.Hole ,1 Min.Hole Max. 75 mm �'i �t. Finished Surface II is i 70 1 Finished Surface II -.1 f--Typical Wall _..1Fe-Typical Wall MAXIMUM EXTENSION MAXIMUM RECESS lh"Adjustment Recessed—V2709,V2710(drawing not to scale) 15 ____ z44 16 mss 7/16" 5/16" 23/16"/ 9/16"/t8 mm 37mm 37mm 56 mm ardrAr���tinne SPIMMITIBI I Finished Ceiling Finished Ceiling 4-12"/102-305 mm Per NFP 4-12" 05 mm l.Q Per NFPA Per NFPA � �� 'a '� 2"/51 mm 23/8"/60 mm J�r�hi� 2"/Strom 23/8:.Tiem 215/16"/ lc ��'1 iil,75 mm � I�il Min.Hole Max.Hole ..i p..; Mln.Hole Max.Hole I�� 00 Finished Surface I Finished Surface I 1..._ �f +--Typical Wall +l Typical Wall MAXIMUM EXTENSION MAXIMUM RECESS 3/4"Adjustment Recessed—V2709,V2710(drawing not to scale) • 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. CtcaUliC victaulic.com 4 Vv victaulic.com I Sprinklers I FireLocik_F:w:aiiirt,,,I,;I:,7,,e K5.6, V27 I Publication 40.11 Distribution Patterns: t," Models 209,V2710 K5.6 Standard Horizontal Sideland Recessed Horizontal Sidewall if Distribution trns__\ Trajectory t j I I I 3.0m ♦ i l• "� t2.4mIAd � i} n,. �.w..,� _,.� 7psi �.." ...Ii '` # 4 rI448kPa18m € I I 15 si1.2mE ., ! , �' i 103 kPa i m ,, I 2 I i ;l I i i : I i 30 psi I I ♦ I 207 kPa yty 0,6m 1,2m 1,8m 2.4m 30m 3.7m 43m 4.9m 55m 61m 6.72m 73m 79m Models V2709,V271O K5.6 Standard and Recessed Horizontal Sidewall Distribution Patterns-Plan View 28' 0.6m 1.2w 1.8m 2.4m 3.Om 3.7m 4.3m 4.9m 5.5w 6.1m 6.7m 7.3m 7.9m 8.5m r _ I i c � 0.6 m 1 ' a 1.2 m �.. a a • • 7psi �..�... _ _.._`� _.._ _ _ .._._ 48 kPa ♦' _ j 2.4 m _ •'� _ i 103 kPa ii 10' �Gr • '•�• 3.Om •.� • 30 psi 207 kPa iii • �� ••• 12' ■• y tz' 3.7m 14' . ___ •.♦i 4.3m 16' 4.9 m NOTES: A. Data shown is approximate and can vary due to differences in installation. B.These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic® victaulic.com I Sprinklers I FireLock® K5.6, V27 I Publication 40.11 i Ratings: Available Wrenches: All glass bulbs are rated for temperatures from -67°F V27-2 V27 (-55°C) to those shown in the table below. Recessed Open End Temperature-°F/°C No escutcheon '/ V Maximum With escutcheon Sprinkler Victaulic Nominal Ambient Glass Temperature Part Temperature Temperature Bulb Classification Identification Rating Allowed Color Ordinary A 135°F/57°C 100°F/38°C Orange ----> Ordinary C 155°F/68°C 100°F/38°C Red Intermediate E 175°F/79°C 150°F/65°C Yellow Intermediate F 200°F/93°C 150°F/65°C Green High J 286°F/141°C 225°F/107°C Blue Extra High 7 K 360°F/182°C 300°F/149°C Purple — M Open — No Bulb 7 Standard response only. • Always read and understand installation,care,and maintenance instructions, supplied with each box of sprin- t klers, before proceeding with installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install, remove,or adjust any Victaulic piping %Ii? products. • Installation rules,especially those governing obstruction,must be strictly followed. • Painting, plating,or any re-coating of sprinklers(other than that supplied by Victaulic) is not allowed. 0 Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pam- phlet that describes care and maintenance of sprinkler systems. In addition,the authority having jurisdiction may have additional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA,Telephone: r001-610-559-3300. rj1 InstallationNote Reference should always be made to the 1-40 Victaulic FireLock Automatic Sprinklers This product shall be manufactured by Victaulic or to Victaulic specifications.All products Installation and Maintenance Sheet for the product you are installing.This installation sheet to be installed in accordance with current Victaulic installation/assembly instructions. is included with each shipment of Victaulic products for complete installation and assembly equipmenreset rves ut hertige and ht to change wtngetprodurctuligc reserves t , designs and standard data,and is available in PDF format on our website at victaulic.com. WarrantyTrademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. \iiC'Caulic victaulic.com 6 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS V27, K4.9COBS Residential Pendent and Recessed Pendent SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS V2740 QUICK RESPONSE This Model V27 residential sprinkler is designed to meet the requirements of NFPA 13, 13D and 13R for residential use in a variety of room sizes, depending upon available operating pressure and room configuration.The design incorporates state-of-the-art, heat responsive, frangible glass bulb design(quick response)for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort.This sprinkler is available in various finishes to meet many design requirements. PENDENT (V2740) SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire,the ambient temperature rises causing the liquid in the bulb to expand.When the ambient temperature reaches the rated temperature of the sprinkler,the bulb shatters.As a result,the waterway is cleared of all sealing parts and water is discharged towards the deflector.The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire. • COVERAGE: Residential spray coverage up to 20 feet x 20 feet/6.1 m x 6.1 m room sizes per NFPA. TECHNICAL SPECIFICATIONS: Model:V2740 ACCESSORIES Style: Pendent and Recessed Pendent Installation Wrench: Nominal Orifice Size:%6"/12 mm • Open End:V27 K-Factor:4.9 Imp./7.1 Si."for room sizes up to • Recessed:V27-1 ,,....._.....,m0) 20'76.1 m Sprinkler Finishes: ��,., Nominal Thread Size:1/z" NPT/15mm • Plain brass Max.Working Pressure: 175psi/1200kPa • Chrome plated ` I� Factory Hydrostatic Test: 100%@ 500 psi/ • White painted*` \--. 3450kPa • Custom painted** 14�/� �� Min.Operating Pressure:7 psi/48kPa For escutcheons,cabinets and other accessories Temperature Rating:See chart on page 3 refer to separate sheet. /�,4 MATERIAL SPECIFICATIONS ^ For K-Factor when pressure is measured in Pendent Deflector: Bronze per UNS C51000 *Teflon is a registered trademark of Bulb Nominal Diameter: Dupont Co. u I • Quick Response:3.0mm **UL Listed for corrosion resistance in all Load Screw: Bronze per UNS C65100 configurations. Pip Cap: Bronze per UNS C65100 NOTE:Weather resistant recessed escutcheon �lo 10 0 4. Seal:Teflon*tape available upon request. 92 r► • Frame: Die cast brass 65-30 Exaggerated for clarity JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �CtaUliCm REV E 40.47 1 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.4/ V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE APPROVALS/LISTINGS Orifice Nominal Approved Temperature Ratings Model Size K-Factor Response Deflector Type F/C 1 Inches Imperial mm SI^ cULus V2740 7A6 4.9 Quick Pendent 155,175 12 7.1 J. 68,79 7/16 4.9 i Recessed Pendent 155,175 V2740 Quick ' * 12 7.1 ' Up to 1/2"Adjustment 68,79 7 4- > V2740 A6 4.9 Recessed Pendent 155,175 12 71 Quick Up to 3/4"Adjustment# 68,79 #Listings and approval as of printing. A For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. *For 12 x 12'to 20'x 20'rooms #For 12'x 12'to 18'x 18'rooms RATINGS All glass bulbs are rated for temperatures from—67°F/-55°C to those shown in table below. Temperature—"FIC Victaulic Sprinkler Temperature Part Nominal Temperature Maximum Ambient Classification Identification Rating Temperature Allowed Glass Bulb Color Ordinary C 155 100 Red 68 38 Intermediate EYellow ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style Temperature Rating K-Factor Thread Size Quantity Sprinkler Finish Escutcheon Finish Wrench Model Number www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40A7 2 REV E FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4V.4/ V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE WARNING A • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprinklers, before proceeding with installation of any sprinklers. • Always wear safety glasses and foot protection. • • Depressurize and drain the piping system before attempting to install, remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction, must be strictly followed. • Painting, plating, or any re-coating of sprinklers(other than that supplied by Victaulic) is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition,the authority having jurisdiction may have addi- tional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA,Telephone: 001-610-559-3300. AVAILABLE WRENCHES Sprinkler Type Open End Recessed V2740 Pendent V27 V27-2 V2740 Recessed Pendent V27-2 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RES . REV E Ictaulic' RESERVED 40.47 3 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.4/ V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE DIMENSIONS Standard Pendent—V2740 0..... 1 IS 23"/ la. 60 m 15/s°/ 41 mm F. ,3/467 j 30 mm Maximum Recess—le Adjustment Recessed—V2740(drawing not to scale) 2W/60 mm Max.Hole -W.r_ 2"/51 mm Min.Hole 1 __ 13A6/ ��� I 30 mm � -i■ I�� Typical Ceiling Tile ���� _,.at TypicalCeilingTile �.I. ` J�/ A '%6/ 7QY�I f } 17 mm ��I �C... :� ' 1%7 r 1 0 Finished Surface 3011mm Finished Surface 43 mm 'r� 1 MAXIMUM RECESS 2xAa'7 75 mm MAXIMUM EXTENSION Maximum Recess—3/4"Adjustment Recessed—V2740(drawing not to scale) 2W/60 mm Max.Hole 2"/51 mm Min.Hole~ 11 t l 1 1'A6'/ ���11f l l 1 'A6"/ En 37 m�I/l/L/�/I,��N�1`I yP al Ce ile 24 mm I�� Typical Ceiling Tile I 11 A T is fling i 18 mm 70101 :1--- --I---'1 u��� � � �6./ ,..�� f24 mmFinished Surface P,6"/ 4111 ii Finished Surface 43 mm MAXIMUM RECESS 2%"/ 75 mm MAXIMUM EXTENSION www.victaulic.com \iCtauliC VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV E 40.47 4 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 4V.4/ V271 K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE ROOM SIZE Victaulic V2740,4.9 K-Factor Pendent Sprinkler For Ceiling types refer to NFPA 13, 13R or 13D 2013 Editions Max. Ordinary Temp Intermediate Temp Coverage Rating Area' 15 Rating°C Rating Deflector to Installation 175'F/79'C CeilingMinimumai Flow'''' Pressure ' Floe' Type Spacing Ft.x Ft. GPM Flow`• Pressurece' PSI GPM m x m L/min bar L/min PSI 12 X 12 laarr Ft. 13 7.013 � 7.0m 3.7X37 492 048 ' 14 X 14 13 i. i. 49.2 0.48 7.0 ! 13 7.0 4.3 X 4.3 49.2 -__>. 16 X 16 7.0 1 49.2 7.0 3/a"recessed 3 70 13 Z0 Escutcheon(c) 8,0 4.9 X 4.9 49.24 4 0 48 49 2 0.48 13A6 to 4 inch or non-recessed 2.4 8 X 18 17 2 17 2 per NFPA 13,13R 155X5.5 643 0.83 64.3 0.83 or 13D 20 X20 20 16 7 20 16.7 6.1 X 6.1 75.7 1.15 75.7 1.15 (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)For NFPA 13 residential applications,the greater of 0.1gpm/ft2 over the design area of the flow in accordance with the criteria in the table must be used. (c) For 20 x 20 Coverage Area-%z'Maximum Recess www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV E �Ctaulic* 40.47 5 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4V.4/ V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE NOMINAL WETTING PATTERNS Model V2740 K4.9 residential pendent and recessed pendent(3/4) 13 GPM/49.2 LPM—16'x 16'/4.9 x 4.9m coverage area 2.4m =.....�_..-.....___«.M... ��..�....__� .✓" ,.-t 7 21m �' -t 1.2mt 3 i 1... i �_.M6 a 2 Q, 0.6m 4 186'2.42,1.8m 11m 1' 12m `""**.,.i 0.3m 2 �, ..�.OF OOM .x,.u...�,,.�..�...:,..:._.' . 0:62 „"w....,...., .:. .. .. 0' wM Model V2740 K4.9 residential pendent and recessed pendent(3/4') 17 GPM/64.3 LPM—18'x 1875.5 x 5.5m coverage area 2.4m .....w.� ,._.-x�..w,-.»... ..®,_» ,..,. 21 m 1.54 ..E :. 12m r r 4.., 4' 2 p t 06mr�.-. 8 b 2424m 186m 1101 0bm 1. .*�.- 4 18m 03m 12m CSO _".®.,.��.._. `�.'* 06.1 _...� ..-1__-....... _ ..._ See notes on next page. ✓ctaulilc www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV E 40.47 6 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4V.4/ V�7, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE NOMINAL WETTING PATTERNS Model V2740 K4.9 residential pendent and recessed pendent(/2') 20 GPM/75.7 LPM—20'x 2076.1 x 6.1 m coverage area 8' 78m1`- [ �,... _ 0.6m _..� -- ,�, "i0• 8 6 4 2, 0' fm_...„_..t ,.� ..:.N , I ' �'"® 6 24m 30m 24m 7.Sm 12m 06m I '""^ 031111 „,.1. 4 ibmum I 06m_ ' �......._ ... .. .,_ �OF'ROOM M.F NOTES: 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers. They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to the appropriate NFPA National Fire Code or the authority having jurisdiction for specific information regarding obstructions, spacing limitations and area of coverage requirements. Failure to follow these guidelines could adversely affect the perfor- mance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY ALL RIGHTS RESERVED. REV E �ctaulic' 40.47 7 FIRE PROTECTIONI?RQDUGJS-AUTOMATIC SPRINKLERS ,. Y27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com �CtaU�ilC: 40.47 4525 REV E UPDATED 04/2013 VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.47 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V27, K5.6 0 <> ® ILPcs, . ; VNIIPO Standard Spray; Upright, Pendent and Recessed Pendent SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS O MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE0 ,.. �' . These Model V27 standard spray sprinklers are designed to produce a hemispherical spray �` P p y pattern for standard commercial applications.They are ° available with either standard or quick response bulbs. The ' design incorporates , state-of-the-art, heat responsive,frangible glass bulb design(standard or quick response)for prompt, precise operation. d UPRIGHT PENDENT RECESSED The die cast frame is more streamlined and attractive than traditional sand cast (V2703 AND (V2707 AND PENDENT frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many v2704) v2706) (v2707 AND angles, reducing assembly effort. This sprinkler is available in various temperature v2706) ratings(see chart on page 2)and finishes to meet many design requirements. The recessed pendent should be utilized with a Model V27 recessed escutcheon which provides up to 3/4719 mm of adjustments. SPRINKLER OPERATION The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire,the ambient temperature rises causing the liquid in the bulb to expand. When the ambient tem- perature reaches the rated temperature of the sprinkler,the bulb shatters.As a result,the waterway is cleared of all sealing parts and water is discharged towards the deflector.The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire. COVERAGE For coverage area and sprinkler placement, refer to NFPA 13 standards. TECHNICAL SPECIFICATIONS Models/S.I.N.:V2703,V2704,V2707,V2708 Style: Pendent, Upright or Recessed Pendent ACCESSORIES • B Nominal Orifice Size: ' "/13 mm K-Factor:5.61mp./8.1 S.I.^ Installation Wrench: Nominal Thread Size: ' " NPT/15 mm • Open End:V27 Max. Working Pressure: • Recessed:V27-2 175 psi/1200kPa FM Global Finishes: 0250 psi/1725kPa UL • Plain brass Factory Hydrostatic Test: • Chrome plated �; 100%@ 500psi/3450kPa • White painted** \ Min.Operating Pressure:7psi/48kPa • Black painted** it i Temperature Rating:See charts on page 2&3. • Custom painted** • Proprietary nickel Teflon*coating** MATERIAL SPECIFICATIONS • For 155,200,and 286°F Standard Upright Deflector: Bronze per UNS C22000 Response Only,wax coated** Pendent Deflector: Bronze per UNS 051000 For cabinets and other accessories refer to Bulb:Glass with glycerin solution. �/ I Bulb Nominal Diameter: separate sheet. • Standard:5.0 mm NOTE:Weather resistant recessed escutcheons • available upon request. Quick Response:3.0 mm , Q Load Screw: Bronze per UNS C65100 A For K-Factor when pressure is measured in Pip Cap: Bronze per UNS 065100 Bar, multiply S.I. units by 10.0. Spring: Beryllium nickel * Teflon is a registered trademark of Dupont Co. Exaggerated for clarity Seal:Teflon*tape P **UL Listed for corrosion resistance in all Frame: Die cast brass 65-30 configurations. Lodgement Spring:Stainless steel per UNS S30200 JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Location Date Para Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I �ctaulic 40.10 1 4U. 10 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V27O7 STANDARD RESPONSE MODELS/S.I.N.V27O4 AND V27O8 QUICK RESPONSE Model T V2704 i 512708 512708_. . _u. V2707 APPROVALS/LISTINGS v27a3 v27o7 I ! � ,,/Zr ,/�" 13 y" /z �._ ._.®._. 13 � __.V- -__ 13 /z /z Orifice Size Gncbes) m._,— _ 13 i 13 �..-- c , -- � 13 Orrfrce Size(mm) 5.6 5.6 � 5.6 }.. Nominal'K Factor Imperial 5.6 5.6 _ — � 5. 81 i 81 8.1 i 8.1 81 Nominal K Factor S.I. Standard Quick Quick Quick lja Standard Standard _. .._._. Uri ht Pendent Response __. _ -_ ( Recessed Recessed t Pendent Pendent Upright upright Pendent � Deflector Type L +-- - up to 3/a'" up to N" Adjustment _ Model Approved Temperature Ratings F°IC by Agency$ - - 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155 F/68 155°F/68°C 155°F/68°C 155°F/68°C 105°F/93°C I 105°F/93°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C UL 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C ( 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 360°F/182°C 360°F/182°C _._..._ 135°F/57°C I 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 1350F/570C • 155°F/68°C 155°F/68°C 155°F/68"C 155°F/68°C ; 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C I 200°F/93°C 200°F/93°C 200°F/93°C I 200°F/93°C ULC 200°F/93°C ; 200°F/93°C 286°F/141°C 286°F/141 C 286°F/141 C 286°F/141°C 286 F/141°C 360°F/182°C 360 F/182°C E � — """ 1350F/57°C 135°F/57°C 1350F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 175°F/79°C 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C FM# ,, 200°F/93°C 200°F/93°C 175°F/79°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 200°F/93°C 286°F/141°C 286°F/141°C ' 360 F/182°C ! 360°F/182°C I - - °F/57 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C j 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C c 155°F/68°C 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C NYC/MEA#62-99-E 200°F/93°C 200:F/93°C 175°F/79°C 286°F/141°C 286F/141C ° °F/93°C 286°F/141°C 286°F/141°C 286°F/141°C 200°F/93°C ! 360°F/182°C 360°F/182°C 135F/57°C I 135°F/57°C I--- ° • 135°F/57°C i � 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C 155°F/68°C 155°F/68°C i 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C ! 175°F/79°C 175°F/79°C 175°F/79°C CSFM#7690-0531:112 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C I 360 F/182 286°F/141°C 286°F/141°C 286°F/141°C 360° 82°C °C F/1 E , 135°F/57°C 135°F/57°C 1 E, 155°F/68°C 135°F/57°C 155°F/68°C 135°F/57°C I • 175°F/79°C 175°F/79°C 175°F/79°C None None LPCB 200°F/93°C 105°F/79°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C v 286°F/141°C 360°F/182°C 135°F/57°C 135°F/57°C135°F/57°C 135°F/57°C j 135°F/57°C i 155°F/68°C 155°F/68°C • 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C VNIIPO 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 2000F/93°C 286°F/141°C 286°F/141°C 360°F/182°C• 360°F/182°C _... i ZSTZ ZSTX K-ZSTZ , K-ZSTX 155°F/68°C 155°F/68°C None 155°F/68°C i 155°F/68°C None CCC 200°F/93°C i 200°F/93°C 200°F/93°C I 200°F/93°C � • I E • i I 1 #Listings and Approvals as of printing.All are approved open,except for areas designated"No". ^For K Factor when pressure is measured in Bar,multiply S .units by 10.0 #FM Approved with 1/2"adjustment escutcheon only-quick response ✓ctauli www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I 40.10 2 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40. V V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE RATINGS All glass bulbs are rated for temperatures from-67°F/-55°C to those shown in table below. Victaulic Temperature-'F/°C Sprinkler Temperature Part Nominal Temperature Classification Identification Maximum Ambient --_. Rating Temperature Allowed Glass Bulb Color Ordinary A 135 100 57 38 Orange Ordinary C 155 100 68 Red 38 Intermediate E 175 150 79 fi5 Yellow Intermediate F 200 150 93. 65 Green High 286 225_ 141 107 Blue 300 Extra High# K 360 182 149 Open Purple _L - M No Bulb #Standard response only. All are approved open,except for areas designated"No". —150/65 if wax coated. ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style Temperature Rating K-Factor Thread Size Quantity Sprinkler Finish Escutcheon Finish Wrench Model Number • www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I 1Ctc1U�IC® 40.10 3 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4U. 1U V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE WARNING • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprinklers, before proceeding with installation of any sprinklers. c • Always wear safety glasses and foot protection. -‘1,?-..0 , • Depressurize and drain the piping system before attempting to install, remove,or adjust any Victaulic piping products. � • Installation rules,especially those governing obstruction, must be strictly followed. 0 • Painting, plating,or any re-coating of sprinklers(other than that sup- plied by Victaulic)is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association document NFPA 25 that describes care and maintenance — of sprinkler systems. In addition,the authority having jurisdiction may have additional maintenance,testing,and inspection requirements that rjmust be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA,Telephone: 001-610-559-3300. ht—V2703,V2704ri Upright pg DIMENSIONS Standard Pendent—V2707,V2708 Standard1 III— f 17A6"/ 37mm .1P-ril 60 mm 1s/e„/ 41 mm r 1 2/el 41 mm ' �_!_I —� 60 mm 1", 25 mm 'h"Adjustment Recessed—V2707,V2708(drawing not to scale) 2W/60 mm Max.Hole 2"/51 mm f Min.Hole ,,,,,,31 mm i + lll1��. 17 m gm - I MLI orti Typical Ceiling Tile ..I.'i1 Ul t ti* 15671n,16y ����� Finished Surface310 m 43 mm _i_ MAXIMUM RECESS 2.A6"/ 75 mm MAXIMUM EXTENSION • www.victaulic.com \iCtaulilC VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV 40.10 4 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 0 n . 1U 27, K5.6 TV Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE DIMENSIONS 3/4"Adjustment Recessed—V2707,V2708 (drawing not to scale) 2W/60 mm Max.Hole 2"/51 mm Min.Hole 24 mm 'A6"/ Fliti 1 1 7 18m Typical Ceiling Tile AWMI'NI,W 37rm Finished Surface 24mm MAXIMUM RECESS 2%"/ 75 mm MAXIMUM EXTENSION AVAILABLE WRENCHES Sprinkler Type V27-2 Recessed V27 Open End V2707,V2708 Pendent yes yes —1 V2707,V2708 Recessed Pendent yes V2703,V2704 Upright yes yes DISTRIBUTION PATTERNS Models/S.I.N.V2707,V2708 K5.6 standard pendent and recessed pendent distribution patterns—trajectory 410I ..... • i • 8 •� ♦♦4, i 2.4m • 44. I, �ti, ._........- _ ._.._. ... 1 e \. ♦♦♦ 6 I I 1. I ♦ I & I •` 1.8m i "_ # _ . , ...-.....€ ..,.,. ♦ E ..... .. .. _ • ♦ I 4 t I ♦ I ♦♦� 11.2m i I .. 44 • ♦ i ! k I ♦ r • 2 I ' I ♦♦ �. _ I 14 4 II 1 o • +♦ f • ........._....,,............. S ♦ t 2' 4 6 8 10,.,,. _ ,,2r.m.. M 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 7 psi • 15 psi ��. 48kPa •• •• 103 kPa 30 psi 207 kPa See notes on next page. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �I�^.taUIiC@ REV I 40.10 5 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS , . V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE DISTRIBUTION PATTERNS Models/S.I.N.V2703,V2704 K5.6 standard upright distribution patterns—trajectory 3.0m! • . i I 1 1 I ! "' .. ..`.1 1 ! 1 i1 2.4m ¢ •'• '4. . 1 I I 1r -r t .,.....1 t I ' ' � �� I k_ �.® $ _. a. —._ g ��,�.m5. .ly�' I Iq. � I I 4i 1.8m 1 ' I 1► 44. i I 1 1 4' I I t-,-------,----t------1y.----.4 1 ,.-., .. r. .�.-. ......._.�„t, .,..,,,.,,,.. ,...I 1.2m I I ' F i N� 'i ♦4 I I s I'• .,... i 2' € 1 [ i \ I ♦`s I , r,,� I - . -yry . ,. ♦ . . i F 1 ., E 1 i i i 2 4' 6' 8' 10' 12' 14' 16' 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m 7 psi •" "' 15 psi � '• 30 psi 48 kPa 103 kPa 207 kPa NOTES: 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to the appropriate NFPA National Fire Code or the authority having jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements. Failure to follow these guidelines could adversely affect the perfor- mance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. • For complete contact information,visit www.victaulic.com 40.10 2544 REV I UPDATED 04/2012 ✓ctaulic VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.10 FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS V36 K5.6 0 ® c® Dry Type Standard Spray, Light Hazard LISTED Horizontal Sidewall and Recessed Horizontal Sidewall •V3609 STANDARD RESPONSE m, § . • r --414 tomoir V3610 QUICK RESPONSE • FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL • EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL • The V36 dry Sprinkler is used in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples. The Model V36 Dry Type Horizontal Sidewall Sprinkler utilizes a frangible glass bulb.At the bulb's rated temperature,the sprinkler opens releasing the bulb seat assembly,causing the inner tube assembly to move,allowing the spring assembly to pivot alongside the inner tube.At this time,water flows through the sprinkler and is distributed by the deflector, in an approved discharge pattern. The heart of the Model V36 sprinkler's proven actuating assembly is a hermetically sealed frangible glass bulb that contains a precisely measured amount of fluid.When heat is absorbed,the liquid within the bulb expands increasing the internal pressure.At the prescribed temperature the internal pressure within the bulb exceeds the strength of the glass causing the glass to shatter.This results in water discharge which is distributed in an approved pattern. COVERAGE: For coverage area and sprinkler placement, refer to NFPA 13 standards. JOB OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I �CtauIiC® 40.64 1 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.b4 V36, (5.6 ® c LISTED D • Dry Type Standard Spray, Light Hazard Horizontal Sidewall and :fi : Recessed Horizontal Sidewall I . .fel - t 1i: ono V3609 STANDARD RESPONSE V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL •/,. EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL TECHNICAL SPECIFICATIONS: :�. IiI • _l .-.ys�.yl..rss�.l..yysl�� Iii' I Exaggerated for clarity Models:V3610 and V3609 ACCESSORIES Style: Horizontal Sidewall and Recessed Installation Wrench: Model V36 Open End and Horizontal Sidewall Recessed Wrenches fit all V36 Series frames. Nominal Orifice Size: l /13mm Finishes: Orifice Insert:Stainless steel per UNS S30300 • Plain brass K-Factor: 5.6 Imp./8,1 S.I.^ • Chrome plated A Nominal Thread Size: 1" NPT/33.7mm • White Painted° Max.Working Pressure: 175 psi/1200kPa • Flat black painted A Factory Hydrostatic Test: 100%@ 500 psi/ • Custom painted A 3450kPa • Wax Min.Operating Pressure:7 psi/48kPa • Proprietary Nickel Teflon*Coated A Temperature Rating:See chart on page 3. For cabinets and other accessories refer to separate sheet. MATERIAL SPECIFICATIONS A For K-Factor when pressure is measured in Deflector: Brass per UNS C22000 or Stainless Bar, multiply S.I. units by 10.0. Steel per UNS S30400 * Teflon is a registered trademark of Dupont Co. Bulb:Glass with glycerin solution A UL Listed for corrosion resistance in all con- • Standard:5.0 mm figurations. • Quick Response:3.0 mm NOTES: Split Spacer:Stainless steel per UNS S30300 1.Weather resistant escutcheon available upon Load Screw: Brass per UNS C36000 request. Pip Cap:Stainless steel per UNS S30300 2.Only the Plain Brass and Nickel Teflon Spring Seal Assembly:Teflon*coated Beryllium finishes are FM approved. nickel alloy and Stainless steel per UNS S30300 Frame: Die cast brass Outer Tube:Galvanized steel pipe Inner Tube:Stainless steel per UNS S30400 Escutcheon: 1010-1018 mild steel and Stainless Steel Torsion Spring:Stainless Steel Wire www.victaulic.com '/ taUIiC VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I 40.64 2 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 4U.b4 V36, K5.6 0 it. co LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall i- V3609 STANDARD RESPONSE _...._.."........ .. , r1 .. . ..., .<;;;„, , .„.,,,,, ..„.. ____40 1 3 /I.±1., � V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL r EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL APPROVALS/LISTINGS Orifice Nominal Approved Temperature Ratings Model Size K-Factor Response Deflector Type "F/'C I Inches Imperial Standard mm Si.' or Quick UL* C-UL* FM V3610 /Z 5.6 Quick ; Horizontal Sidewall 1135,155,200,286 135,155,200,286'135,155,200,286 13 8.1 , 57,68,93,141 57,68,93,141 57,68,93,141 -f V3610 z 5.6 Quick Recessed Horizontal 135,155,200,286 135,155,200,286 135,155,200 13 8.1 i Sidewall i 57,68,93,141 57,68,93,141 , 57,68,93 V3609 /z 1 5.6 Standard Horizontal Sidewall 1 135,155,200,286 135,155,200,286'135, , ,155 200 286 13 8.1 57,68,93,141 ! 57,68,93,141 57,68,93,141 I +. V3609 Vz 5'6 , Standard Recessed Horizontal 135,155,200,286 135,155,200,286 135,155,200 13 8.1 Sidewall 1 57,68,93,141 57,68,93,141 57,68,93 *Listings and approval as of printing. A For K-Factor when pressure is measured in Bar,multiply S.I.units by 10. *Light Hazard Only-Listed for light hazard only with deflector from 4"-12"below the ceiling. **Approved for V3609 and V3610 up to 48"length. RATINGS All glass bulbs are rated for temperatures from-67°F/-55°C to those shown in table below. Temperature-`F/°C Sprinkler Temperature Nominal Temperature Maximum Ambient Classification Rating Temperature Allowed Glass Bulb Color Ordinary 135/155 ! 100 I 57/68 38 1 Orange/Red Intermediate 200 i 150 93 65 ' Green 286 High 141 225 Blue 107 • www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �CtaUI1C" REV I 40.64 3 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4U.b4 V36, K5.6 0 ® CO LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall "$�' :H . owl V3609 STANDARD RESPONSE V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL ! j A EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style Temperature Rating K-Factor Quantity Sprinkler Finish Escutcheon Style "A'Dimension-Distance from face of fitting to the finished ceiling line regardless of escutcheon used. AVAILABLE WRENCHES Model V36 Open End and Recessed Wrenches fit all V36 Series frames. www.victaulic.com �CtaU�iC� VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I 40.64 4 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4V•b4 V36, K5■6 FM c0 V LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall __ p e ry r V3609 STANDARD RESPONSE s ,I "' "I � ` � V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL Z., EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL WARNING • Always read and understand installation,care,and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation of any sprinklers. C • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install, remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction, must be strictly followed. • Painting, plating,or any re-coating of sprinklers(other than that 0sup- plied by Victaulic) is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler Isystems. In addition,the authority having jurisdiction may have addi- tional maintenance,testing,and inspection requirements that must be ry followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA,Telephone:001-610-559-3300. www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �CtaUIiC® REV I 40.64 5 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4U.b4' V36, K5.6 LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall andfru_ Recessed Horizontal Sidewall ., I l : V3609 STANDARD RESPONSE V3610 QUICK RESPONSE FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL 1111 m# EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL DIMENSIONS NOTE:The"A"dimension of a dry sprinkler,which extends into a freezer from a wet piping system, must take into account the wall or ceiling thickness of the freezer.See IMPORTANT INSTALLATION INFORMATION later in this document. Two Piece Escutcheon 1"NPT 1^SPT 11•Mr 1 ��10 Dia �_- in Dia 166"Min Dia ^ Tee wH in Wall 3Ola. Tee with sa}e oudetsize Hole in Wall as with same outlet size spunkier thread size Ø _4½M5t sprinkler size span 3^min IMPORTANTANTINSTALLATION 21/6" SNa F IMPORTANT INSTALLATIONent. FORMATION laterinthsdocument. Flush 1 Sleeve&skirt (Min.156") I"NPT I I <" I %I Li Tee with same outlet size 2Nd' as sprinkler thread size See IMPORTANT INSTALLATION INFORMATION later in this document. Plain Barrel • A.. (MIn.IY,) ,"NPT 4 PO"Min Dia. Wall Cup Hole In Wall Collar IIII; �� Die � 3�h'._M� Die. 21i16" Tee with same outlet size Piece s sprinkler thread size Two f 2"Mel Dia See IMPORTANT Escutcheon INSTALLATION Tee with same outlet size Hole In Wall as sprinkler thread size 156"Min INFORMATION later In \ See IMPORTANT INSTALLATION 266"Max. [his document. "A, I a"Min. INFORMATION later in this document. (MIn.1/) 51/4"Max. Extended Recessed DEFLECTOR TO CEILING DISTANCE 4—121102—305 MM FOR ALL CONFIGURATIONS SHOWN ABOVE. www.victaulic.com �CtaU�iC VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV 40.64 6 • FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 40.b4 V36, K5.6 0 ® c4 Dry Type Standard Spray, Light Hazard LISTED Horizontal Sidewall and Recessed Horizontal Sidewall V3609 STANDARD RESPONSE .Y"; 72,. _ V3610 QUICK RESPONSE FLUSH DRY RECESSEDS HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL SLEEVE&S SIDEWALL _ Fav 4171 EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS MODELS V3610,V3609 HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS-TRAJECTORY i I [ 1 13.0m 0� .� • ■""tib r�-I �,., - g., ,-1-- 8' 1 I .� f *♦ I i 2.4m I , tt _ .• w F ¢♦♦ 6 I •. 14 4 E I `I I I 144 1.2 m .n ,. r + I I ♦ I s I ♦ I I' .�H. 1 0.6m -��#.�.-.�m�.-fir I_ . � I I y I I € I I � I I I I I I I `• I. I 2' 4' 6' 8' 10' 12 14 ry 16' ra 18 20 22 24' 26' 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m 5.5m 6.1 m 6.7m 7.3m 7.9m 7psi -..mm.. 15 psi 48 kPa 103 kPa 20 psi 207 kPa MODELS V3610, V3609 HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS-PLAN VIEW 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 28' 0.6m 1.2m 1.8m 2.4m 3.0m 3.7m 4.3m 4.9m 5.5m 6.1 m 6.7m 7.3m 7.9m 8.5m Ii 1 I 1 I 0.6m w �., k ... . I I 1 >. 4I '. tinx._.. .., � i E I .w ,.. .... _..,_. ..1 44 I 1.2 m 6' 1.8m ��. I ♦€ 1 I I ? � I ��.. I � E � �.�.��r,t 8' I 1, I I ♦ I .,mm ' 12' I I r I ••I ! K I .. . € 3.7m ,. I I • �r��, ..w_ .Ar 1 I 14 ? ••h € •I e. , 16' • c 4.9 m 7 psi 15 psi 48 kPa 103 kPa 20 psi 207 kPa See notes on last page. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC ALL RIGHTS S RESERVED. REV I �CCaIU�iC® 40.64 7 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 4V.b4 V36, K5.6 LISTED • Dry Type Standard Spray, Light Hazard Horizontal Sidewall and ##h' —01 IrA Recessed Horizontal Sidewall 14.,.---. ,.. ; ., ,1 ti r.." f..:. V3609 STANDARD RESPONSE - , • 4w V3610 QUICK RESPONSE SLEEVE&SKIRT FLUSH DRY RECESSED HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL _ Iii; :- 7 EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL IMPORTANT INSTALLATION INFORMATION For detailed installation instructions,see publication 1-40. No. 1 Victaulic Model V36 Series Dry sprinklers should be installed in accordance with NFPA 13.These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible,the proper sprinkler wrench may be used with extreme care for lengths up to approximately 18". Excessive force may distort the frame thus destroying the unit. No. 2 Dry sprinklers MUST be installed only into the outlet of a cast or malleable iron tee. No.3 DO NOT install dry sprinklers into any couplings or threaded elbows. In addition, DO NOT install dry sprinklers into any fitting that interferes with thread penetration. NOTE:The end seal of the dry sprinkler MUST NOT bottom out in the fitting. NOTE:The"A" dimension of a dry sprinkler,which extends into a End Seal ,� HEATED SPACE freezer from a wet piping system, must take into account the wall or \�_ ceiling thickness of the freezer.The minimum length of the dry sprinkler -, ' g�!' should not be less than the lengths specified in the following table, plus t the thickness of the freezer's wall or ceiling( A"="C" +"D"). Refer to the drawing for a representation of the"A" dimension.DO NOT "C"Exposed Minimum Barrel Diameter of hole is dependent upon the attempt to modify dry sprinklers,since they are manufactured to this Length(Refer to Table) type of escutcheon selected.Space must be sealed to prevent condensation from specific"A"dimension. forming,per NFPA requirements. etemperature maintained between 40following°F/4°table C andisused 60°whF/16n°Cthe aroundambient the wet piping system.is A TheEXPOSED BARREL AMBIENT TEMPERATURE(°F/°C) See Note - -' _ _ Insulation Exposed Minimum Barrel Length "D„ -- - Ambient Temperature inches/mm _ - _ Exposed to Discharge601716:tEnd of Sprinkler 40°F/4`C 50°F/10°C -- - F/`C 0 0 I 0 ,',-',I,'',.;,', Wall or Ceiling of Freezer 40 0 0 0 4 'I iv 30 - 0 0 0 1 4 0 AO020 !emir 20 i 102 0 4401 COLD SPACE 10 2038 1 0 -12 25 0 0 Exaggerated for Clarity 0 12 3-18 305 76 0 4 1 TYPICAL SLEEVE AND SKIRT CONFIGURATION FOR EXAMPLE ONLY -10-23 14 14 102 25 1._. -20 14 6 356 152 76 4 -30 16 203 102 -34 406 18 -408 4203 102 -40 457 -50 20 10 _46 i 508 254 152 __... -60 20 10 -51 i 508 i 254 152 NOTE:Exposed minimum barrel lengths are inclusive up to 30-mph/48-kph wind velocities www.victaulic.com viCtaulic VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.CO 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV 40-64 8 FIRE PRpTECTION PRODUCTS—AUTOMATIC SPRINKLERS V36, K5.6 ® FM IJSTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and Recessed Horizontal Sidewall f V3609 STANDARD RESPONSE ir� V3610 QUICK RESPONSE • FLUSH DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL NOTES 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers. They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprin- kler spacing rules for installation. Refer to the appropriate NFPA National Fire Code and the Authority Having Jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. US&WORLD HEADQUARTERS CANADA CENTRAL AND SOUTH AMERICA P.O. Box 31 905-884-7444 1-610-559-3300 Easton, PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3608(fax) 4901 Kesslersville Road viccanada@victaulic.com vical@victaulic.com Easton, PA 18040 USA EUROPE ASIA PACIFIC 1-800-PICK-VIC(1-800-742-5842) 1-610-559-3300 32-9-381-15-00 86-21-54253300 1-610-250-8817(fax) 32-9-380-44-38(fax) 86-21-54253671 (fax) pickvic@victaulic.com viceuro@victaulic.be vicap@victaulic.com www.victaulic.com UNITED KINGDOM MIDDLE EAST 44(0) 1438310690 971-4-883-88-70 44(0) 1438310699(fax) 971-4-883-88-60(fax) viceuro@victaulic.be UPDATED 12/2009 40.64 3127 REV I VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �CtaUliCm 40.64 Bulletin 016 Rev.E Model DH56 HSW I� ® Model DH56 HSW Recessed eia Model DH56 HSW Concealed ig Quick Response, Extended Coverage Dry Sprinklers m For coverages up to 28 feet wide and 10 feet longm. 250 psi (17,2 bar) rated. Features: `11 ° wv . 1. Coverage for long and narrow spaces such as hall- NISI ways, corridors, decks and rooms up to 28 feet wide and 10 feet long.(') 2. Deflector to ceiling dimensions are: 4"(102mm)min.to 12"(305mm)max. DH56 HSW 3. Minimum spacing between sprinklers 13 feet(4m).(1" 4. Polyester Coated Corrosion Resistant Sprinklers(cULus) � �� 5. UL Listed for extended coverage, light hazard appli- •• 'e. ccations. `' 6. 5.6 K Factor. 7. Sprinkler is approved for 250 psi(17,2 bar)applications. ,- 8. Quick response performance. 9. 1" (13mm) adjustment of escutcheon and cover. 10.Concealed cover plate can prevent the sprinkler from being used for unintended purposes. No exposed DH56 HSW FP Recessed thermal element with the concealed version. 11.Push-on/thread-off sturdy convenient escutcheon for recessed and cover for concealed. ; 12.Factory assembled sprinkler&cup, shipped complete with bulb protector for concealed and FP recessed ver- : v sions. 13.Sprinkler&cup assembly and escutcheon or cover are separately packaged. 14.Cover finishes available in standard white paint, spe- cial bronze, black paint or flat white paint. DH56 HSW Concealed (1)See Fig. 7. with SWC coverplate Approval Organizations a fire the rising ambient temperature melts the solder and 1. Listed by Underwriters Laboratories Inc. and the cover plate is ejected away by springs exposing the UL certified for Canada(cULus) 3mm frangible glass bulb. The use of a 3mm bulb allows 2. NYC MEA 258-93-E quick response which enables the sprinkler to apply water to a fire sooner than standard response sprinklers of the Products Description same temperature rating. The Model DH56 are quick response extended coverage Model DH56 dry sprinklers are intended for use in dry sidewall dry sprinklers for use in light hazard applications. and preaction systems to protect areas subjected to freez- The Model DH56 dry sprinkler with SWC cover plate is a ing temperatures and unheated portions inside buildings. concealed sprinkler that uses Reliable's push on/thread off See Fig. 1 for guidelines on using dry sprinklers in wet sidewall cover.This sprinkler has the cup factory mounted systems. and is shipped with a bulb protector that protects the 3mm Environments wherein dry sprinklers are employed can frangible glass bulb during shipping and post installation be corrosive. For this reason, Model DH56 dry sprinklers finishing operations. The DH56 can be combined in the have a special wax fillet placed in the gap between the field with the FP or F2 Escutcheon to make a recessed cup that supports the bulb and the wrenching boss. This dry sprinkler. The SWC cover plate, FP and F2 recessed wax will not interfere with the operation of the sprinkler,and escutcheons have 1/2" adjustment. The SWC cover plate it prevents contaminants from entering the internal portion is attached with 135 & 165 degree solder. In the event of of the drop nipple. The wax must not be removed. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application DH56 HSW Concealed with SWC Cover Plate The Model DH56 is a horizontal sidewall dry sprinkler To install the DH56 HSW dry sprinkler with the SWC intended for installation in light hazard occupancies in ac- coverplate as a concealed sprinkler, cut a 21/8" diam- cordance with NFPA 13. These sprinklers are designed to eter hole into the wall as shown in Fig. 6. Temporari- provide fire protection in long and narrow spaces such as ly remove the plastic protective cap, and then use the hallways, corridors, decks and rooms up to 28 feet (8,5m) Model XLO2 wrench (see Fig. 2) to tighten the sprinkler wide and 10 feet(3m)long. They are rated for 250 psi(17,2 until it is secured in the sprinkler fitting. Note: The Model bar) and can be mounted between 4 and 12 inches (102 XLO2 wrench has a notch in it to accommodate the de- and 305mm)down from the ceiling. flector top. This wrench can only be inserted one way. Care must be taken not to damage the deflector during General Installation Instructions tightening.Apply a Teflon**based sealant to the sprinkler Model DH56 dry sprinklers must be installed only in stan- threads before installing in the sprinkler. Wrench only on dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) the square boss. DO NOT WRENCH ON ANY OTHER pipe tees in the horizontal position,even at branch line ends. PART OF THE SPRINKLER. It is recommended that the They should not be installed into elbows or pipe couplings sprinkler be protected during plastering and painting op- located on drop nipples to the sprinklers. For these and erations by reinstalling the plastic protective cap. Instal- other fittings including CPVC, the dry sprinkler should be lation is completed by removing the protective cap and installed into a fitting to allow protrusion into the fitting in ac- inserting the coverplate. Coverplate assemblies provide cordance with the diagrams. The "A" dimension of the dry 1/2" (13mm) of adjustment. Final adjustment is made by sprinkler, which extends into a freezing zone from wet pipe turning the coverplate clockwise until the skirt flange systems, should be selected to provide, as a minimum, the makes full contact with the wall surface. Cover removal specified lengths in inches shown in Fig. 1. requires turning in the counter-clockwise direction. Caution: Concealed coverplate assemblies are listed only for Do not install Model DH56 HSW Dry sprinklers into CPVC use with specific sprinklers. The use of any other con- adapter fittings or tees that have an internal obstruction. cealed wall sprinkler or the use of the SWC coverplate This will damage the sprinkler and/or the fitting. Refer to on any sprinkler with which it is not specifically listed will Fig. 8 void all guarantees, warranties, listings and approvals. DH56 HSW Note: DH56 and DH56 Recessed Sprinklers have or- To install the DH56 HSW dry sprinkler cut a 21/8" diameter ange bulb protectors to minimize bulb damage during hole in the wall as shown in Fig. 4. Use the Model G3 instal shipping, handling, and installation. REMOVE THIS PRO- lation wrench (see Fig. 3) to tighten the sprinkler until it is TECTION AT THE TIME THE SPRINKLER SYSTEM IS Remov- secured in the sprinkler fitting. Apply a Teflon* based seal- PLACED IN SERVICE FOR FIRE PROTECTION.ant to the sprinkler threads before installing in the sprinkler. al of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed Wrench only on the square boss. DO NOT WRENCH ON corn- to install sprinklers when covers are in place. REMOVE ANY OTHER PART OF THE SPRINKLER. Installation is pleted by removing the orange glass bulb-protector and as PROTECTORS BY UNDOING THE CLASP BY HAND. DO sembling the slip-on escutcheon to the sprinkler's can. NOT USE TOOLS TO REMOVE THE PROTECTORS. DH56 HSW Recessed with FP Escutcheon To install the DH56 HSW dry sprinkler with the FP Escutch- eon as a recessed sprinkler cut a 25/8" diameter hole in the wall as shown in Fig.5. Temporarily remove the plastic pro- tective cap, and then use the Model XLO2 wrench(see Fig. 2) to tighten the sprinkler until it is secured in the sprinkler fitting. Note: The Model XLO2 wrench has a notch in it to accommodate the deflector top. This wrench can only be inserted one way. Care must be taken not to damage the deflector during tightening. Apply a Teflon** based seal- ant to the sprinkler threads before installing in the sprinkler. Wrench only on the square boss. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. It is recommended that the sprinkler be protected during plastering and paint- ing operations by reinstalling the plastic protective cap. In- stallation is completed by removing the protective cap and inserting the push-on escutcheon. Turn clockwise to adjust the escutcheon against the wall. *DuPont Registered Trademark 2. • RECOMMENDED MINIMUM EXPOSED BARREL LENGTH BASED ON AMBIENT TEMPERATURE IN THE PROTECTED AREA (STANDARD DH56 HSW DRY SPRINKLER SHOWN) EXPOSED BARREL AMBIENT AMBIENT TEMPERATURE TEMPERATURE OF PROTECTED 40'F/4'C I 50'F/10'C I 60'F/16'C AREA* AT THE EXPOSED MINIMUM BARREL LENGTH** DISCHARGE END FACE OF TEE TO TOP OF CEILING) OF THE SPRINKLER ( IN. (MM) IN. (MM) IN. (MM) 40'F (4'C) 0 0 0 30'F(-VC) 0 0 0 20'F (-7C) 4 (101) 0 D •A" - 10'F (-1200) 8 (203) 1 (25.1) 0 DIMENSION CLEARANCE 12 (305) 3 (75) 0 MINIMUM HOLE 0'F (-1 8'C) EXPOSED .{ -10'F (-230C) 14 (356) 4 (101) 1 (25.1) BARREL LENGTH \. ESCUTCHEON -20'F(-29'0) 14(356) 6 (152) 3 (75) \ -30'F(-34'C) 16 (406) , 8 (203) 4 (101) -40'F(-40'0) 18 (457) 8 (203) 4 (101) (HEATED AREA) -50'F(-46'C) 20 (508) 10 (254) 6 (152) -60'F (-51'C) 20 (508) 10 (254) 6 (152) IA III * THE PROTECTED AREA REFERS TO THE AREA BELOW THE CEILING_ _ _ - - -—- �� DIA. —�Iii THE AMBIENT TEMPERATURE IS THE TEMPERATURE AT THE DISCHARGE 4i FOR OF THE SPRINEAER. �c,�� = III -zZ FOR PROTECTED AREA TEMPERATURES THAT OCCUR BETWEEN THE VALUES \J LISTED, USE THE NEXT COOLER TEMPERATURE. \ \ P **THE MIN. REQUIRED BARREL LENGTH IS NOT THE SAME AS THE 'A' DIMENSION. WET \ NOTE. EXPOSED MINIMUM BARREL LENGTHS ARE INCLUSIVE UP TO 30MPH \ (PROTECTED AREA) \ WIND VELOCITIES IN THE PROTECTED AREA V A� INSTALL 1 INCH NPT THREADED A A END OE DRY PENDENT SPRINKLER INTO THE 1 INCH NPT SIDE OUTLET OF A MALLEABLE IRON TEE FITTING WALL PER ANSI B 16.3 (CLASS 150) OR CAST IRON THREADED TEE FITTING PER ANSI 16.4(CLASS 125) ONLY INSULATED FREEZER OR COOLER STRUCTURE OR EXTERIOR FRAMING IF HUMIDITY AND TEMPERATURE DIFFERENTIAL CAUSES CONDENSATION DN THE EXPOSED DRY SPRINKLER, CONSIDER WRAPPING THE EXPOSED BARREL WITH INSULATION, FOAM INSULATING TAPE DR EQUIVALENT, SEAL THE CLEARANCE SPACE AROUND THE SPRINKLER TO AVOID LEAKAGE OF AIR INTO THE PROTECTED AREA AND CONSEQUENT FORMATION OF CONDENSATE AROUND THE FRAME, WHICH COULD INHIBIT OPERATION OR CAUSE PREMATURE OPERATION. SEE BELOW FOR RECOMMENDED METHODS. I RECOMMENDED DRY SPRINKLER SEAL ARRANGEMENTS (STANDARD DH56 HSW DRY SPRINKLER SHOWN) MINIMUM MINIMUM EXPOSED CLEARANCE EXNOSED BARREL HOLE BARREL LENGTH LENGTH (SEE ABOVE) (SEE ABOVE) INSIDE FACE fki IN COLD AREA DRY SPRINKLER INSIDE FACE DRY SPRINKLER N COLD AREA (HEATED AREA) I k (HEATED AREA) I, 7-ZR Tj {VIP _ _— �I6Ihl II1I111IIII — ''1�II il ',.‘2,‘,.„.1,4_10111111 'II61hu - -INNIn111 - 1 1 1 � SEAL— (PROTECTED AREA: DECKTITE FLASHING 1 RASCO #4003910 (RECOMMENDED) INSULATED FREEZER, OR COOLER STRUCTURE OR EXTERIOR FRAMING 016FG05A Fig. 1 3. Technical Data: rinkler Maintenance K Factor TemperaturetiModel DH56 Quick Response Dry Sprinklerssystemmaintained should bein Thread Rang Maximum Sp Size Ambient identification inspected quarterly and the sprinkler US Metric Sprinkler SWC Temperature Number accordance with NFPA 25. Do not remove the factory ap- Cover (SIN) plied thermally sensitive wax fillet between the bulb support- 155°F 135°F 100°F ing cup and the wrenching boss. Do not replace this wax with (68°C) (57°C) (38°C) a substitute substance. An alternate substance may interfere 5.6 80 1 175°F 165°F 150°F with proper operation of the sprinkler. Do not clean sprinklers (79°C) (74°C) (66°C) RA1664 with soap and water, ammonia or any other cleaning fluids. 200°F 165°F 150°F Remove dust by using a soft brush or gentle vacuuming. Re- (93°C) (74°C) (66°C) move any sprinkler which has been painted(other than factory applied)or damaged in any way. A stock of spare sprinklers Coverage Area should be maintained to allow quick replacement of dam- Maximum Coverage aged or operated sprinklers. Prior to installation, sprinklers Area Width x Length Flow Rate Pressure should be maintained in their original cartons and packaging ft x ft(m x m) gpm(L/min) Psi(bar) until used to minimize the potential for damage to sprinklers 28 x 8(8,5 x 2,4) 23(87,1) 16.9(1,2) that would cause improper operation or non-operation. 28 x 10(8,5 x 3) 28(106) 25(1,7) Model DH56 Quick Response Approval Type: Extended Coverage Horizontal • Quick Response, Extended Coverage. Sidewall Dry Sprinkler Specification • Approved for installation in accordance with NFPA 13 Sprinklers shall be a [quick response —cULus Listed] ex- for light hazard occupancies. tended coverage horizontal sidewall sprinkler for light hazard occupancies. Sprinklers to be of bronze frame construction Step 1 with a special deflector capable of providing a discharge over a coverage area of 28 ft. (8,5m) wide, and 10 ft. (3m) long <1, horizontal throw.Water seal assembly shall consist of a Teflon- coated Belleville spring washer. Installation shall permit sprin- kler deflectors to be positioned 4" (102mm) to 12" (305mm) Step 2 below the ceiling. Sprinklers shall have a nominal K-factor of 5.6 (80), and 1" NPT thread. Sprinkler temperature rating shall be [155°F(68° C)] and [200°F(93°C)]. Rated working ' pressure shall be 250 psi (17.2 bar). Standard finish: [whit r e][chrome][bronze][Special finish—specify]. Quick response + extended coverage horizontal sidewall dry sprinklers shall be Step 3 Reliable Model DH56,SIN RA1664(Bulletin 016). For recessed EC horizontal sidewall sprinklers: Replace �` "horizontal sidewall"with"recessed horizontal sidewall." Add: .r'" ` l (1)Recessed escutcheon assembly shall be a two-piece es- r{ 4F" cutcheon of push-on and thread off design with 'h" (13mm) it adjustment.Standard finish shall be chrome,white and brass. Quick response recessed horizontal sidewall sprinklers shall Fig.2-XL02 Wrench be Reliable Model DH56,SIN RA1664(Bulletin 016). For concealed EC horizontal sidewall sprinklers: Replace "horizontal sidewall" with "concealed horizontal sidewall." Add: Cover plate assembly shall consist of a brass cover ,. plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and A thread-off design allowing a '/2" (13mm) cover plate adjust- ment. Cover plate temperature rating shall be 135°F(57°C) for 155°F (68°C) dry sprinkler and 165°F (74°C) for 200°F (93°C) dry sprinkler. A bulb protector shall be provided and factory installed inside the sprinkler cup to protect the glass bulb from damage, which could occur during construction • Fig.3-G3 Wrench before the cover plate is installed.Standard cover plate finish: [white] [Custom Color— specify]. Quick response extended coverage concealed horizontal sidewall dry sprinklers shall be Reliable Model DH56, SIN RA1664(Bulletin 016). 4. DH56 HSW DRY SPRINKLER 1 1/2" [38.10mm] Total Adjustment Ceiling 1 ---------- O [ ;[ J 1 1/4" [31.75mm] 4" [101.60mm] Min. 2" [304.80mm] Max. Escutcheon Adjustment 1/4" [6.35mm] ]� Escutcheon Adjustment System Tee 1" NPT ' iT 1 15/16" ` fitil ' iii Illllll "` X:313-471\'‘\r v u�J � IrM1. 3" Dia. im I I IIIIIII1 [76.20mm] 2 1/8" Dia. iD [53.98mm] Bole in Wall --c 1/4"�_ 1/4" [6.35mm] Protrusion Sprinkler Can "A" Dimension Nominal Position Adjustment of Escutcheon Range + 1/4" [+6.35mm] oiersa3A — 1 1/4 [-31.75mm] Available "A" Dim. is 2" to 48" (51 mm to 1219mm) in 1/4" (6mm) increments Note: The Sprinkler Can protrudes 1/4"when escutcheon is in nominal position. Escutcheon adjustment provides + 14" (+6mm) to -11/4" (-32mm) "A" dimension adjustment range. Fig. 4 DH56 HSW RECESSED DRY SPRINKLER Ceiling LJ 1 1/4" Escutcheon N [31.75mm] 4" [101.6mm]Min. Cup o I 12" [304.8mm]Max.H System Tee I /2- 1' NPT WM ._ _ ( 1 d �� I 11IlIII, ` 3 7/32" Dia. II �� [8 .8m no] ME 2 5/8„ Dia. ]d [66.68mm] Io —Nominal Position Hole in Wall ' 3 I of Escutcheon 2 9/32" Dia. _j [___] [57 94i-m] 1/4" [6.35] Escutcheon Adjustment "A" Dimension [6 [12.7mm] Adjustment Range Escutcheon Adjustment 076FG028 ±5.35mm 1/4" [6.35] [ ] Escutcheon Adjustment Available "A" Dim. is 3-1/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments Note: Do not install the Model DH56 Dry EC Horizontal Recessed Sidewall Sprinkler in walls which have positive pressure in their side space. Fig. 5 5. D56 HSW CONCEALED DRY SPRINKLER Ce neg PUAN ON GOVS ,'N'T System Tee .��L TURN TO ADJUST UNTIL TIGHT A94I951 WALL 1"NPT !It 1 007.9 TO 304 Si war A.4 W rill _ I'1��lul' fi* 3 5/16" mist aroo-ee;o.,Eevotee A^ 2 9/3z" ��i��� ��� Ce4.14] Above inside Pee 1-5]94) OU_ i...,— -- — L \`— RECOMMENDED f� R Rata J 2 5DIA TER DIAMETER 3 1 9/16" L J r_ (39.69] J _ /16"(4�bmm �— Ad(us�e at Range Coverplate Ad�us(ment [+11.]mm—OmmJ Nominal Position of COVell,,, 0 I6FGO IA DIMENSIONS IN BRACKETS ARE IN MILLIMETERS(MM) Co erplafe4Atllustm, 1/2"(12.7] ADJUSTMENT Available "A" Dim. is 3-1/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments Fig. 6 N 72' ]4m] Minimum Spacing I 28' [8.5m] Maximum Spacing I \ MODEL DE56 DRY SPRINKLER \ ] r \ WALL F 0 ,/%i/j;; at-, //, , //,�„ , ; 4" [100mm] min.From Ceiling ] \ i 72" ]305mm] max.From Ceiling //////,--i///// , \\' 28' ]8.5m] 07682044 Fig. 7 6. . *CAUTION* DO NOT INSTALL MODEL F3, MODEL F3QR OR MODEL DH56 HSW DRY SPRINKLERS INTO CPVC ADAPTER FITTINGS OR TEES THAT HAVE AN INTERNAL OBSTRUCTION. THIS WILL DAMAGE THE SPRINKLER AND/OR THE FITTING. CPVC ADAPTER FITTINGS AND TEES WITH INTERNAL OBSTRUCTIONS ARE ALSO COMMONLY FOUND DURING THE RETROFITTING PROCESS OF RELIABLE'S OLDER MODEL G3 DRY SPRINKLERS. NO INTERNAL INTERNAL -OBSTRUCTION OBSTRUCTION 0 j -ini FEMALE FEMALE PIPE PIPE THREAD THREAD INCORRECT CORRECT CPVC ADAPTER CPVC ADAPTER FITTING OR TEE FITTING OR TEE RELIABLE MANUFACTURES A FULL-LINE OF MODEL F3-PL, MODEL F3QR-PL, AND MODEL DH56 HSW-PL DRY SPRINKLERS THAT HAVE A SHORTER INLET FOR THESE APPLICATIONS. SHORTERSal- - LONGER INLET NLET ,7.= MALE /4(� �� MALE /1.m".111. 1-11 PIPE / PIPE THREAD THREAD MODEL F3-PL, STANDARD MODEL F3QR-PL OR MODEL F3, MODEL DH56 HSW-PL MODEL F3QR OR DRY SPRINKLER MODEL DH56 HSW DRY SPRINKLER BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR I APPLICATION 076fg08 Fig.8 7. Ordering Information Installation Wrench Specify: Model XLO2 Sprinkler Wrench (Recessed &Concealed) 1. Sprinkler Type (select one): Model G3 Sprinkler Wrench (a)Model DH56 Dry EC HSW Note: A leak tight 1" NPT sprinkler joint can be obtained (b)Model DH56 Dry Recessed EC HSW/FP with a torque of 20-30 ft-lbs (27.1 - 40.7 N-m). Do not (c)Model DH56 Dry Concealed EC HSW tighten sprinklers over maximum recommended torque. 2. Sprinkler Temperature Rating. It may cause leakage or impairment of the sprinklers. 3. Sprinkler Finish. 4. Cover Plate/Escutcheon Finish. Escutcheon Data: 5. Length: "A" Dimension(face of tee to face of ceiling or FP cup/escutcheon assembly- 1/2"(13mm) adjustment wall) in 1/a" (6mm) increments. Finishes to Note: 1. The "A" dimension is based on a nominal) Standard Finishes 0) y gauged Sprinkler Escutcheon Cover Plate pipe thread "make-up" of 0.600" (15mm) per ANSI White Polyester(2) B2.1 [71/2 threads approximately]. /Chrome/Bronze White/Chrome White 2. All platings and paintings are decorative and intend- (1) Other colors and finishes are available. Consult factory for details. ed for interior use. (2)cULus Listed as Corrosion Resistant Sprinkler in standard Black or White. UL Listing Category Note:Paint or any other coatings applied over the factory finish will void Sprinklers, Automatic and Open. Quick Response Sprinklers. all approvals and warranties. The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured b IIeIiabIö The Reliable Automatic Sprinkler Co.,Inc. �SRecycled (800)431-1588 Sales Offices Nair Paper (800)848 6051 Sales Fax (914)829-2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A 05/10 P/N 9999970308 u SPEARS CPVC FIREFlameGSPRINKLERard ®PRODUCTS FG-2.0312 Complete System of Pipe, Fittings & Solvent Cement Corrosion Resistant • Superior Flow • Ease of Installation =' Spears® FlameGuard® CPVC Fire Sprinkler Products provide a cost .' , effective alternative to metal systems with advantages of high corrosion resistance, improved system hydraulics, ease of installation and quick + a tom" ;t4 I )I ifI assembly with readily available tools. CPVC Fire Sprinkler Systems are based on proven MC FIR!WIMP=PRODUCTS products that - 4111 • have been in continuous service for - over 40 years. Spears®FlameGuard° OH I _. products N. area roved by UL®, FM® _fy ski, P pp Global, LPCB and Certified by NSF W Illi # is ill,ro. International for potable water use. 111.111) Check local codes for restrictions and limitations. Corrosion Resistant CPVC Material Does Not Easy Installation for Lower Costs Sustain Biological Growth FlameGuard®CPVC system installations significantly Unlike metal systems, FlameGuard® CPVC products never reduce costs over conventional metal piping by virtually rust,scale or pit and do not sustain biological growth-a cause eliminating prefabrication. Systems can be fully installed of Microbiologically Influenced Corrosion(MIC)which can on site using solvent cement joining methods. destroy metal fire sprinkler systems from the inside out. UL° Listed for U.S. and Canada in NFPA 13, 13R& 13D Systems Superior Flow Characteristics for Lower FlameGuard® CPVC Fire Sprinkler Products are UL® Friction Losses listed for U.S. and Canada applications for Light Hazard The smooth-wall interior surfaces of FlameGuard® CPVC occupancies as defined in NFPA 13,Residential occupancies systems result in reduced friction loss over metal systems. up to and including 4-stories as defined in NFPA 13R, The design flow characteristics remain constant throughout and Residential occupancies for one and two family the life of the product because there is no interior corrosion dwellings and manufactured homes as defined in NFPA in the system due to microbiological activity. 13D. Consult Spears®FlameGuard®CPVC Fire Sprinkler Pressure Rated to 175 psi(1200kpa) @ 150°F Products Installation Instructions and NFPA Standards for (65°C) additional applications including air plenum,system risers, FlameGuard®CPVC Products are produced in combinations concealed, exposed, underground, combustable attic, of Schedule 40 and Schedule 80 Fitting configurations con- garage,basement and low pressure dry piping installations. forming to ASTM F 438 or F 439 standards and FlameGuard® Full Limited Lifetime Warranty SDR 13.5 CPVC Fire Sprinkler Pipe conforming to ASTM F FlameGuard® CPVC Fire Sprinkler Products carry a 442 standards. UL® Rated working pressure is 175 psi limited lifetime warranty against defects in material or (1200kpa)@ 150°F(65°C)(LPCB rated to 120°F)(49°C). workmanship. Consult Spears®warranty for additional details. PROGRESSIVE PRODUCTS FROM \°N°ERT FC9� � SPEARS®INNOVATION& d LPCB o oKAs NIC� -- TECHNOLOGY o a M^YKNT Visit our web site: www.spearsmfg.com 007 Spears® FlameGuard®. . . The Leader in Innovative CPVC Fire Sprinkler System Products Pioneer in Molded-in Metal Insert Head Adapters Spears® pioneered the development of the FlameGuard® molded-in-place metal thread insert for connection of sprinkler heads to CPVC fire sprinkler systems, plus Metal FIPT threaded female adapters for metal-to-plastic transitions. Developed the Special Reinforced (SR) Head Adapters Spears® FlameGuard® continuous improvement program developed the 411110 technology to produce a superior patented plastic threaded fitting - the Special Reinforced(SR)Design.This unique design incorporates a patented thermoplastic compression process that equalizes stresses generated by tapered thread joint make-up. All CPVC plastic body and threads provide a more uniform construction and improved corrosion resistance. Now, the Revolutionary TorqueSafeTM Gasket Sealed Head Adapter • Requires NO Thread Sealants • Eliminates Stress • Prevents Over Tightening • Provides Easy Frame Alignment Spears® revolutionary design features a special molded-in-place Brass Thread Insert fitted with an elastomer gasket seal at the base of the threads. The gasket seal allows a modified thread design that eliminates radial stress and associated problems typical with tapered thread joint make up. The insert is designed to rotate for easy sprinkler frame alignment without over tightening. Patent Pending. Full Assortment of Specialty Products & Fitting Configurations Spears® FlameGuard® provides the specialty fittings needed in today's fire sprinkler systems. Like the adjustable drop nipple for fine-tuning to finished ceiling height,and ringed head adapter for ease of locating during installation. Plus, Spears®FlameGuard®line offers a full assortment of CPVC fire sprinkler fitting configurations including Tees, Elbows, Flanges, Couplings, Caps, Male Adapters, Grooved Coupling Adapters and Unions, sizes 3/4" through 3"; with new 3/4" and 1" Repair Couplings. Complete Size Range of CPVC Pipe Spears®FlameGuard® CPVC Fire Sprinkler Pipe is available in sizes 3/4" to 3". Conforms to ASTM F 442 standard for SDR 13.5 CPVC pipe. Spears® Solvent Cements & Thread Sealant FlameGuard®products should be installed using Spears® FS-5 One-Step Solvent Cement. For threaded joints, use Spears® BLUE 75— Thread Sealant that has been tested for compatibility with FlameGuard® CPVC Fire Sprinkler Products. Spears® TorqueSafeTM Gasket Sealed Adapter requires no sealant. Consult sprinkler head manufacturer prior to use. Installation Training Available - Contact Spears® Technical Services for Details FlameGuard®Products must be installed in accordance with Spears®CPVC Fire Sprinkler Piping Products Installation Instructions,National Fire Protection Association Standards 13, 13R, 13D,and in accordance with local codes.Code requirements andfield conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. SPEARS® MANUFACTURING COMPANY �iPEARS �: CORPORATE OFFICE � 15853 Olden St., Sylmar, CA 91342• PO Box 9203, Sylmar, CA 91392 ALW(818)364-1611 •www.spearsmfg.com ©Copyright 2012 Spears®Manufacturing Company. All Rights Reserved.Printed in the United States of America 03/12. FG-2-0312 ( �Iiiiii i I '4bll Freer BOO SMARM•www.ptonaerplpe.tsotn , Scope Bending Test (Cold) . Covers black and hot-dipped galvanized furnace butt-welded For NPS 2"and under Degree of Bend Diameter of (continuous welded)Grade A pipe. Pipe Is intended Mandrel for mechanical and pressure applications and is acceptable Standard 90' 12 x outside pipe 1. diameter for ordinary uses In steam,water,gas and air lines. Pipe Close Coiling 90' 8 x outside pipe is suitable for welding,threading,grooving and bending. diameter Flattening Test Hot"Dipped Galvanized As a test for quality of the weld for pipe 2W NPS and larger, The average weight of zinc coating shall be not less than position the weld at 90'from the direction of force and flatten until the 1.8 oz.per sq.ft.of surface(inside and outside). OD Is%of the original outside diameter. No cracks shall occur along When galvanized pipe is bent or otherwise fabricated the inside or outside surface of the weld. • to a degree which causes zinc coating to stretch or compress beyond the limit of elasticity,some flaking bf the coating Frequency of Tests Tensile teats are required on each lot of 25 tats or fraction thereof I may occur, of pipe NPS 1W' and smaller and frau each bt of 50 tons or fraction Hydrostatic Testing thereof of pipe NPS 2 and larger. . Hydrostatic lest pressures for plain-end pipe are For NPS 2W and larger,a flattening test is also required on each lot of I Indicated below 50 tons. NPS Std.Weight Extra Strong . 36"through 1' 700 psi 850 psi Dimensions and Weights VW through 3" 1000 pal 1300 psi The dimensions and weights furnished under this specification are in • agreement with the standardized dimensions and weights specified in End Finish ASME B 38.10. . Plain End: Black Plain End NPS 1W and smaller.unless otherwise specified on order, PermlaeSate • end finish shall be at the option of the manufacturer. Variations Soh.40 Soh 80 • In Wall Nominal OD Weight Weight NPS 2"and larger,STD and XS weights:ends beveled Size Inches Wall LbJFt. Wall Lbs./Ft. Thickness y, .405 .068 .24 .095 .31 to angle of 30', h5°,-0'with a root face of *''/z". Minimum wall thick- 11 .540 .088 .43 .119 .54 3. .675 .091 .57 .128 .74 Threaded:To ANSi Standard B 1.20.1 ness at any point shall v, .840 .109 .85 .147 1.09 not be more than "/.• 1.060 .113 1.13 .154 1.48 1' 1.815 .133 1.68 178 2.17 Coupiings:To ASTM Standard A 885 12.5%under nominal 1Y; 1.680 .140 2.27 .191 3.00 1'h' 1.900 .145 2.72 .200 3.83 wail thickness 2" 2.375 .164 3.66 .218 5.03 Chemical Requirements specified. 2,4" 2.875 .203 5.80 278 7.57 9' 3.500 .216 7.58 S00 10.26 Composition,max.% Carbon Manganese Phosphorus i6ytlfur Permissible Variations in Outside Diameter .30 1.20 NPS 1'I:'and under: ±.016" *Copper *Nickel *Chromium *Molybdenum "Vanadium NPS 2"and over. *1% .40 .40 .40 .15 .08 "The combination of these five elements Permissible Variations Weight Per Foot shall not exceed 1.00%. Pipe shall not vary more than*10%from the standard specified. Tensile Requirements Product Marking Tensile Strength,min. 48,E psi Each length of pipe 1/1"NPS and larger is continuously stenciled to Yield Strength,min. 30,000 psi show the manufacturer,the grade of pipe(ASTM A53),the kind of pipe Elongation in 2" Refer to A53 Table X4.1 (F for continuous weld,A for Grade A),the size,XS for extra strong, and length. Legal Notice:This brochure is Intended for general information only. Pioneer makes no warranty or representation,expressed or implied,of any kind with respect to the inlormation contained herein and shall in no event assume liability or responsibility for any loss,damage or injury whatsoever resulting from the use of this information. in all cases,the customer is therefore requested to antis Information at its own risk and responsibility. North American Pipe&Steel Www.napsteel.corn NAPSteel FIRE SPRINKLER PIPE North American Pipe & Steel has been a trusted source for steel piping products since 1981. With strong ties to mills in the U.S. and abroad, we are certain to supply "What you need when you need it". Our fire sprinkler line of pipe is another example of our commitment to meeting the needs of our increasing customer base. NAP SuperFlow and NAP Schedule 10 Pipe is: �I✓ manufactured to ASTM A135,A795 and A53A. t.er UL listed and FM approved for fire sprinkler applications including roll grooved, plain end and welded joints. fully traceable. NAP SuperFiow - sal. 4 • , " X t " 3 t{t•_a''-'.:; x t 3 i 1+14)„ . � 1-1/4" 1.660 1.494 1.400 61 300 370/0.2 6 2" 2.375 2.185 2.320 37 300 358/0.30 3.500 yam, 3.320 3.280 19 305 0 1 27/0.09 NAP Schedule 10 ~' ^.�.,, ',. ,'; t..'':•d .':r1 : :. m 33^:"4 s ° . ,. + �y Y� tt .+��',Y«M 1 4 {� ,,. d {{ ... � F µF > + €X.,,?', A Eke ?^aF .tM; "��` t` �C^}" - ",':� .,"nzt A 1-1/4" 1.660 1.442 1.400 61 300 = l2 fou .. 6 _ ,* -:%;,4;„:„ -% ••bb ,yam q .',_ 2 2.375 2.157 2.320 37 300 ® 3.500 3.260 3.280 19 300 111111111111 NAP Super Flow Pipe and NAP Schedule 10 Pipe are manufactured by MS Pipe Co., LTD, South Korea Surrey, BC Longview,WA Auburn,WA Nampa, ID 11933 Tannery Road,V3V 3X1 7 International Way, 98632 3136 B Street NW, 98001 2114 Delta Drive, 83687 1-800-665-7473 1-877-735-0275 1-877-735-0275 1-877-735-0275 • 'breaded Fittings Ductile Iron 41/ .p � f' ° i K 4iiiii . , , , , , ,, . . , ,. . . Ductile Iron Threaded 'Fittings : , ,-, , i t i .,,- ., i 1't"-Yrt -z:n,-' ,'*-'-'-',,-,,,''',',.cl'Iti;,,i.ilkf'80Wfit:•,!!'If,''Ix-,, '.- , .. . ,... , .. . • . branded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 psi WSP • Ductile iron castings conform to ASTM A536 ®L US • Fitting dimensions conform to ASME B16.3 LISTED • Bushings and plugs conform to ASME B16.14 41/1:1 ' • All fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B1.20.1 • Independent lab verification that fittings meet applicable chemical &mechanical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 • ProPakTM Packaging fl ` ' i � � SIV,,ritjrt :s�al�ofi� � '��fir; 'ee'rre. ` .. es. .GJa$s• !;0 br de £ i 0 - ; _ -20 to 100 500 , 200 �'. :a.�,:,�: 480 3 *X4.r^.n 300 440 —1 400 �. - Mod 400 ,:-.54.14.04,4** Mj'R""'�+�,'' " tom, cif Ti':: 500 � . , 360 320 . ` if 1 �� "^tt 600 ` SCI ProPalinf System ¢ Ductile Iron Threaded Fittings - Class 300 UL/FM c13us 4;0' APPROVED LISTED Fig. 35E 3 90°Elbow p*, 1 35E 3004Mpg 100 200 0.2 .., 1 ♦♦� <.- ,",4, [��$€d::1,,,:.4::,p., f g..,ak a Y -1.50 \ •F `ii" r,rk•: t,''r� ,,f Ir,x- ir..1,. � yy. --" I e A01111111Cy 35E 3010 1 5p0+ 40 80 0.5 01 �'� _,A45,'',2'....-4%i41.' ,A x ",3< ..,FI,. '+. }}�'. (`': cap ,o r r"i$ .4 :-':i :1'''''-i:'49;2`' '',1,-..:::; t. '''1:-.+t 1-1/2 35E 3014 1.94 36 D 6.iiiiiiir-V-Nil ,,. via,.f0=4 ":: w;,{Mk a',z.. ,4° 2F*i€' "'°- '" 35E 3024 2.70 4 8 C I Fig. 35RE3 90°Reducing Elbow B , .ice r ij,'h'Ae!°rds est ia£z �t::s. a' :r.< Y ip ' s i M. ''• 3/4 x 1/2 35RE3006004 1.20 1.22 80 160 0.3 (--- �,.'' .' ., ,x -,.,,,v.`, - ,e� .<: �`, ": �"+,i', ', s,,,A'''"-": yr.'.004,10.4114,7.- Ms ,* �'.1:v." � . , 4,, I-- 1 x 3/4 35RE3010006 1.45 50 100 0.4milk 1 ���,_, A q .c L.i.';`:o- J «1 --,..4,,N.€� ,,,y;- ad- :.3r' .r ,--� .,, r ' >M•• •'�. � .. � 1-1/4x3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/2x1/2 35RE3014004 . .4.. ... . . . 1.75 " .30 60 0 6 ; y2`4 :::4 ::t':":,1,6.,- tY. � Fd6j , ,. ;u3ft"C9r i �,f. ';',-'„,'".4. -",-', i3: •:, ;z ; 1-1/2 x 1 35RE3014010 1 65 1.80 20 40 0.8 t4 ,,,-,:‘,--.#0,71 ;,,,.z,..1:-.;,':,7, 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 t.„•,,,-_.7 .-.-i;',".„?,P. n -;,: . ,, ..;+?° .,i 74a ..,,'t . A.„ '; ,,.:i t'r ,s • �,i 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 . - ,,' "' 1rr5 a4 a r4.47?.*: ` ' ,, . ` ":2‘''.;:, ', •''j* ;fi 1 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow ' `ice, , . 1 Ie t 4. \ 1/2 35F 3004 0.88 150 300 0.2„/�,�ii a `. �cc ;fie.4,,,,„',,,,,r''.,,,,,,,, , Z ,,ii,4. r' d•14" ,,*:,4.- .r'V i tt � ix 4 �' ��� 1 35F 3010 40 80 0.5 4$ 1 „,„.7!,.7.-1,,,,,, ,,,1.,,t4,,,„_,„,,,,,„ 20 40 1 0 35F 3024 1.95 4 2.7 Fig. 35T 3- Tee ''Sile I '' (, +° ` -` P-DclOat ti t o ' #1 `,; n � aA 1 �� \ { ' .°t4.," � f:.. 1/4. 4,:i" ;''t al.er'. a et . `" ' `IllINI` 1/2 35T 3004 1.13 80 160 0.3 1 35T 3010 1.50 25 50 0.7 �q Sn,M' �^ "� ,fix 4�.ti .t, ^�. � m d{ ~�;•,,..,. • Imo"-.---• I T`', . ''1 .. k_ 'tivv . :' 44,%, t1. „ '' ,.'24. :''4t,, 6 ,:4 .:'4» ' A iF q 1-1/2 35T 3014 1.94 10 20 1.5 2-1/2 35T 3024 2.70 4 8 4.3 201 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com c,1 ! . Ductile Iron Threaded Fittings - Class 300 UL/FM c (21us ® Fig. 35RT3-Reducing Tee LISTED o `ii.'` - ,: r! Ys rt, U iY ss� ,y 1fi.. "r 4� 'a-(p� l4::,,,j. �'.firrrf! 4 ,, iTa Yf.* gq 'P"'' a t''' Y 0�„ 13,t ����NJfM "• "�� C 3/4 x 1/2 35RT3006004 1.20 1.20 60 120 _0.4 1111111bh-- - 1x12x1 _ i / 35RT3010004010 1 50 1 36 1.50 30 60 0 6 " _\�,�„: .tet mQ . rpt r ; D E B E A 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1.45 70 0.6 1-1/4x1/2 35RT3012004 1.34?fir Ya '^7J�1 34 1.53 20 40 0.8 yl...b ° . ..s0.;:N ' Es' u, : "yw #' .::4;44: i�'<:� :i"- A.t�4 t'i T 1-1/4x3/4 ' i. 35RT3012006 1.45 1.45 1.62 15 30 0.9 ' k;:::: u,:. ; r � `nT?C x V4 i4.z ''SII a:- :' :,..',:.'4,:: -t k :,: .'° t L 1-1/4 x 1 35RT3012010 1.58 1.58 1.67 15 30 1.0 1-1/4 y�x 11 x 3/4 35RT3012010006}, 1.45 1.38 1.63 20 40 0.8 '••`.�$ZPIAZI Y:01. '�F"f'!�'1�zrs .a aHa` p v 11 y -sv w 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 1.56 1.88 24 48 1.1 1-1/2x3/4 35RT3014006 1.52 1.52 1.75 16 1.1 , e:a^ .,:•.14,4* ;„':e-C':-...'",;:',1714i1!:;,.d q <,. 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 ,.":`'s :;',A. M . - 'b »," Itli t.,. i lit,, f r:.r z s :' Y ?.. 1-1/2 x 1x 1/2 35RT3014010004 1.44 1.25 1.69 20 40 0.8 1 1/2 x 1 x 1 35RT3014010010 1.65 1.50 1.80 16 32 1.0 1-1/2 x 1x 1-1/2 35RT3014010014 1.94 1.80 1.94 12 24 1.3 4iii 0;„h4. t -,.fi ti ner Ojr e3.241 '-F 't,'':{>• 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 12 x 1-1/4 x 1 35RT3014012010 1.65 1.58 1.80 16 32 1.1 - z.„: 1-1/2 x 1 1/4 x 1 1/2 35RT3014012014 1.94 1.88 1.94 14 28 1.4ryP A" 2 x 3/4 35RT3020006 1.60 1.60 1.97 10 20 1.6 2 x 1 x 2 35RT3020010020 2.25 2.02 2.25 8 16 1.9 2 x 1-1/4 x 2 35RT3020012020 2.25 2.10 2.25 8 16 2.0 ,R 2 x 1-1/2 x 1/2 35RT3020014004 1.49 1.41 1.88 10 20 1.3 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 ':-:'1071V:444.,i'' 5 4 ' r t 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 � 1.88e ; Fig. 35BT3-Bull Head Tee .4,10:!.::,.t. n: 1 i ; ;: '` C ; l'i:Ok>.qq. ` wed t. l �� rarttin. -, in �n „Inilsr a e - • { In .." �," 3/4 x 1 35BT3006010 1.45 1.45 1.37 30 60 0.6 ii - ;-- ''''."11---i-1 x /2 35BT30100' 1 80 - o € w E aab � "1J4c * y Y/.,�� {�) �Y� ,,yam y lai.0 1-1/4x1-1/2Y 35BTT33� � 1.8 1.88 1.82 15 30 1.3 012014 1 8 1-1/2 x 1-1/4 x 2 35BT3014012020 2.16 2.10 2.02 10 20 1.8 ;;;i 110 , : -4gs401* .:.'-.:.474,e'''.:7,1',074-1 202 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com -; 1 Ductile Iron Threaded Fittings - Class 300 UL/FM c (2) us 44> APPROVED A Fig. 35CP3 Straight Coupling with Ribs s. LISTED "'3, rd �4�• ^d $� •S` N I 38.E '� q kil°:''''''::',: _ 35C13004 200 400 01 ^iiiiii'' �,:.,.;�Y 3, ::::' .?.. ��:15 :�o Ib� e�. , y17.:. lie '- ,,,,......e____. /�_///� 35CP3010 60 120 0.4 "tel' '�'.,,,,,.,,C.� 1„.„, ,':'W,, zs:„,,, . „,„ 4 t, +k ,::,„ ' a ��'€ ,,,,,,.,, . _r 1 1/2 35CP3014 2.19 50 �, 0 7 D .Sr' '� '- t� `,.<�`� *rl...:�74 T4• 4' Y�Pt� s'4,.��., .v'x'' k� l`i�iti1iiisy 35CP3024 3,00 9 ti Fig. 35RC3 —Hex Reducing Coupling „,4' , „..,:., tryfikinjA 4.r 1 x 1/2 35RC3010004 1.69 80 160 0 3 A k d C*a F y x€. 1 1/4 x 3/4 35RC3012006 2 06 40 80 0.6 ,,at .: .v�,"[i,c,,.A �xk:3,1:. 4Ai . ...„w.r ...KA e.4.. t • t:.l.... Wj r� Fig. 35HB3 —Hex Bushing R1 ,>I * :at intPht B , 35HB3010004 1.06 1.40 180 360 0.2 i' .1R1).11,:-');:'41.':t4OPY'''Iir:4;;;07 :4: ''`Z:5 14.,*(, !_., IA Itri*:: .'i:,,,:. °,:"*i.'',:, ..:',7-..., �! A 1-1/4 x 1 35HB3012010 1.19 1.80 90 180 0.2 1-1/2x1-1/4 35HB3014012ID" 1.95 �75 150 0.3 2 x 1-1/4 35HB3020012 1.38 2.55 40 80 0.6 �.1i1'` ;F",�'"�r.. ,;'..wt�'�`'):' '•�17��.��,git, idka,s' .���"� .a45 ,,r,?, im3i KAL4:M: Fig. 35SP3 —Square Head Plug al44. $ s y t „..� , 7 ��u f 335SP3004 0.94 600 1200 0.07It i� C Y r ,aa,,Y 'b : "c n 1•= "T' �, s a 1' c 4 '.„'F' S .�v;.: IL �i A 1 35SP3010 200 400 0.1 I �' I` I dI i< ` ar._yr. 1 *<:.� < ; F` ,`” : •:,,-'0 J, I?tom a 3 iiii§ .� i` ,.? •zs: ,e', ?,":. 1-1/2 35SP3014 1.44 80 160 0.4 Fig. 35U 3— Union with Brass Seat A , 4N'IS • ft-��r � ,I1 35U 3010 2.19 20 40€ 1i001,• ,,ms ,r .ey€' a „,,,,,,,,,,t.,...; "� z,/ r,, ." , r.7,L II ml 1-1/2 35U 30r1�4 �2j.6,2�� 10 20 1.7 ioi 203 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com Ductile Iron Threaded Fittings - Class 300 UL/FM cus APPROVED A A Fig. 35X 3 Cross LISTED 1 IA 1 35X 3010 1.50� t 40 20 0.9 II IA 1-1/2 35X3014 1.94 8 16 1.8 1© hr 0 U C Ii 1 . B B Fig. 351lX3 Reducing Cross � �1 D '' x. `i% ` � I I 1 1/4 x 1 35RX3012010 1.67 L, 1.58 15 30 1.2 " 2 x 1 35RX3020010 2.02 1.73 8 16 2.0 Fig. 35C 3-Cap • - 4 A 1/2 35C 3004 0.87 300 600 0.1 ,I - 1 350 3010 1.16 110 220 0.2 1-1/2 35C 3014 1.33 50 1000.5 2-1/2 35C 3024 1.70 18 36 1.6 Fig. 35BC3-Beam Clamp h A !� 3/8 35BC3003 0.75 100 200 0.3 t4riGCi 204 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • wwwsmithcooper.com FireLock® Fittings ✓ctaulic® 10.03 Material Specifications: Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. 1111 Fitting Coating: ❑ Orange enamel ❑ Red enamel in Europe, Middle East, Africa, and India ❑ Optional: Hot dipped galvanized Approvals/Listings: c 4L us 4J LPCB vas CSP LISTED Product Description: FireLock® products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees feature CAD- developed, hydrodynamic design, affording a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. Refer to the appropriate listing agency or approval body for pressure ratings. Pressure ratings vary by agency. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I FireLock® Fittings I Publication 10.03 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. 1 actauliic victaulic.com I FireLock° Fittings I Publication 10.03 Dimensions: I-CtoE1 C to _ _ _p_ CtoE fi / p p p T to. 461'' ,v0 0 ..p p C - .� i ;�°` `� oie to NO.001 o i -� NO.003 NO.002 No.006 No.001 No.003 No.002 No.006 90°Elbow 45°Elbow Straight Tee Cap p Actual Nominal Out aApprox. Approx. Approx. Approx. Weight Weight Weight Weight Size Diameter C to E Each C to E Each C to E Each C to E Each inches inches inches Lbs. inches Lbs. inches Lbs. inches Lbs. mm mm 1 Y4 1.660 mm kg mm kg mm kg mm kg 32 42.4 - - - - - - 0.82 0.3 1 Y2 1.900 - - - 21 0.1 40 48.3 - - - - - 0.4 - 2 211 0.2 2 2.375 2.751.7 2.00 1.8 2.75 2.4 0.88 0.6 50 60.3 70 I 0.8 51 0.8 I 70 I 1.1 I 22 0.3 2 Y 2.875 3.00 3.1 2.25 2.2 3.00 I 3.6 65 73.0 76 1.4 57 0.88 1.0 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 3.30 2.25 2.4 I 3.00 I 3.8 76.1 76 1.5 57 1.1 76.2 1.7 - - 3 3.500 3.38 I 4.0 2.50 3.1 1 3.38 5.3 80 88.9 86 1.8 64 0.88 1.2 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 108.0 102 2.6 76 2.3 102 3.4 - - 4 4.500 4.00 6.7 3.00 5.6 4.00 100 114.3 102 3.0 76 2.5 102 8.7 1.5 1.4 3. 5 5.563 4.88 12.6 3.2515.7 .0 1.1 125 141.3 124 8.3 1.00 4. 5.7 83 3.8 7.125 1. 9 1249 139.7 mm 5.500 4.88 12.4 3.25 8.2 4.88 15.4 139.7 124.0 5.6 82.6 3.7 124.0 6.9 - - 159 mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 158.8 140 5.7 89 4.2 140 8.0 - - 6 6.625 5.50 18.3 3.50 11.7 150 168.3 140 8.3 5.50 22.7 1.005.9 89 5.3 140 10.3 25 2.7 165.1 mm 6.500 5.43 17.6 3.50 11.4 5.50 22.0 165.1 139.7 7.9 88.9 5.2 139.7 9.9 - - 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.1312.7 200 219.1 173 11.6 108 9.3 176 17.6 2995.8 ' 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic' victaulic.com I FireLock® Fittings I Publication 10.03 Flow Data: Frictional Resistance Actual Equivalent Feet/meters of Straight Pipe' Nominal Outside No.002 Size Diameter Elbows Straight Tee inches inches No.001 No.003 mm mm 90°Elbow 45°Elbow Branch Run 1'/4 1.660 - - - - 32 42.4 - - - - 1' 1.900 - - - - 40 48.3 - - - - 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 0.5 2.6 1.1 21/2 2.875 4.3 2.2 10.8 4.3 65 73.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 108 mm 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 139.7mm 5.500 8.3 4.1 20.6 8.3 139.7 2.5 1.3 6.3 2.5 159mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.05.0 25.0 10.0 150 168.3 3.0 ( 1.5 7.6 3.0 165.1 mm 6.500 9.8 4.9 24.5 9.8 165.1 3.0 1.5 7.5 3.0 I 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 1 The flow data listed is based upon the pressure drop of Schedule 40 pipe. General Notes: NOTE: When assembling FireLock EZ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009N/009H couplings, use FireLock No. 006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the "QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H couplings. Installation Note Reference should always be made to the 1-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. \iiCtafLJliC victaulic.com 3 . Victaulic® FirelockTM Rigid Coupling Style 009N ✓ctauliic® 10.64 Or Patented 1.0 CERTIFICATION/LISTINGS 04 ® LPCB v C104-1a/36 2.0 PRODUCT DESCRIPTION • The FireLock EZTM Style 009N Installation-ReadyTM Rigid Coupling is for use in the fire protection market. • The coupling's unique design eliminates loose parts, promotes consistent installation and provides substantial gains in productivity. • IMPORTANT: FireLock EZTM Style 009N couplings are recommended for use ONLY on fire protection systems. 3.0 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) ❑ Orange enamel (North America, Asia Pacific) ❑ Red enamel (Europe) O Hot dipped galvanized Gasket: (specify choice') ❑ Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. System No. Location Spec Section Paragraph Submitted By Date Approved Date • • victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. 1 ✓ctauluc® • victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64• • 4.0 LISTINGS/APPROVAL 2 The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Nominal Size cULus FM Vds LPCB Sch.5 Sch. 10 Sch.40 Sch.5 Sch. 10 Sch.40 inches psi psi psi psi psi psi psi psi mm kPa kPa kPa kPa kPa kPa kPa kPa 11/4 232 365 365 175 363 363 363 363 32 1600 2517 2517 1205 2502 2502 2500 2500 11 232 365 365 175 363 363 363 363 40 1600 2517 2517 1205 2502 2502 2500 2500 2 363 365 365 175 363 363 363 363 50 2502 2517 2517 1205 2502 2502 2500 2500 2' N/A 365 365 175 363 363 363 363 65 2517 2517 1205 2502 2502 2500 2500 365 325024 363 363 76.1 mm N/A 25173 N/A N/A 25024 N/A 2500 2500 3 N/A 365 365 175 363 363 363 363 80 2517 2517 1205 2502 2502 2500 2500 4 N/A 365 365 175 363 363 363 363 100 2517 2517 1205 2502 2502 2500 2500 175 363 363 N/A N/A 108.0 mm N/A N/A N/A 1205 2502 2502 5290 365 N/A 363 363 232 N/A 125 N/A 2000 2517 2502 2502 1600 363 4 N/A N/A N/A 133.0 mm N/A N/A N/A N/A 25024 290 s 3634 232 N/A 139.7 mm N/A 2000 s N/A N/A 2502 4 N/A 1600 363 4 N/A N/A N/A 159.0 mm N/A N/A N/A N/A 2502 4 290 6 363 4 N/A N/A N/A 165.1 mm N/A 2000 6 N/A N/A 2502 4 6 290 365 N/A 363 363 232 N/A 150 N/A 2000 2517 2502 2502 1600 4 N/A N/A N/A 216.0 mm N/A N/A N/A N/A 2502 4 8 290 365 N/A 363 363 232 N/A 200 N/A 2000 2517 2502 2502 1600 2 Listed/Approved for wet and dry pipe systems(>—40°F/-40°C)for continuous use in freezing conditions,use of Style 005H Coupling with Silicone Gasket is recommended. Please see the Victaulic Installation Manual I-009N/009H for details concerning when supplemental lubrication is required. 3 cULus listed for DIN 2458 2.6 mm pipe wall. 4 FM approved for BS 1387 Medium 3.6 mm pipe wall. 5 cULus listed for EN 10220 4.0 mm pipe wall. 6 cULus listed for EN 10255 4.5 mm pipe wall. • • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com2 ✓ctaulilc victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • 4.1 LISTINGS/APPROVAL • Speciality Pipe Pipe Size Pipe Size IIICTEEZM Pipe Size Pressure Rating cULus FM cULus FM inches psi psi inches psi psi cULFM kPa kPa inches psi psi kPa kPa kPa kPa =ME 2300608 ®®® 2068 2517 300 365 300 365 MOM 2068 2517 DF ® 2068FF 1'/a 4 2517 300 365 2068 ®® 2517 DT 1'/a 2 300 365 FLF 2068 2517 1'/a 4 N/A 251 STMUM 5 365 175 175 2517 EF 11/4—4 1 06 1206 FLT 1'/a—2 N/A 365 2517 STF 11/4—4 N/A 365 300 365 2517 EL 1'/a—2 2 68 2517 FLTL 1'/a—2 N/A 365 2517 TF 2'/a—4 N/A 365 2517 ET40 1'/a—2 300 365 GL 1'/a—2 300 365 365 2068 2517 2068 2517 WLS 1'/a-2 300 2068 2517 EZF 3-4 300 365 MF 1'/a-4 300 365 2068 2517 2068 2517 WST 1'/a-2 N/A 365 ME 2517 NOTES300 rill 1'/a 2 2068 • BLT=BLT steel pipe manufactured by Allied Tube&Conduit Corp. • DF=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • DT=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • EF=EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL=EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40=Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF=EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT=EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF=Fire-Flo steel pipe manufactured by Youngstown Tube Co. • FLF=Fire-Line Flow steel pipe manufactured by Western International Forest Products Inc. • FLT=Fire-Line Threadable steel pipe manufactured by Western International Forest Products Inc. • FLTL=Fire-Line Threadable Light steel pipe manufactured by Western International Forest Products Inc. • GL=GL steel pipe manufactured by Wheatland Tube Co. • MF=Mega-Flow steel pipe manufactured by Wheatland Tube Co. • MT=Mega-Thread steel pipe manufactured by Wheatland Tube Co. • MLT=MLT steel pipe manufactured by Wheatland Tube Co • ST=STD wall pipe in accordance with ASTM A53. • STF=Steady Flow steel pipe manufactured by AMS Tube Corp. • TF=Tex-Flow steel pipe manufactured by Tex-Tube Co. • WLS=WLS steel pipe manufactured by Wheatland Tube Co. • WST=WST steel pipe manufactured by Wheatland Tube Company. • XL=XL steel pipe manufactured by Allied Tube&Conduit Corp. • • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulac® victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64• • 5.0 DIMENSIONS Style 009N Y ••-Z-. Y MZ mu .L ITT iiiii .3 �r_� lit Style 009N Pre-Assembled Style 009N Joint Assembled (Push On Condition) Dimensions Pre-assembled Approx. Actual Maximum Maximum Allow. (Push On Condition) Joint Assembled Weight Nominal Outside Working End Pipe End Bolt/Nut 9 Y Z Each Size Diameter Pressure 7 Load 7 Separation8 Size X V X inches inches psi lbs. inches inches inches inches inches inches inches lbs. mm mm kPa N mm No. mm mm mm mm mm mm kg 11/4 1.660 365 790 0.10 3/8x 2 3.13 5.00 2.75 5.00 2.00 1.4 32 42.4 2517 3514 2.54 2 M10 x 2 79 127 70 127 51 0.6 11/2 1.900 365 1035 0.10 3/8x 2 3.38 5.13 3.00 5.13 2.00 1.5 40 48.3 2517 4604 2.54 2 M10 x 2 86 130 76 130 51 2 2.375 365 1616 0.12 3/8 x21 4.00 5.63 3.50 5.63 2.00 0.91.9 50 60.3 2517 7193 3.05 2 M10 x 2'h 102 143 89 143 51 21/2 2.875 365 2370 0.12 3/8 x 2' 4.50 6.13 4.00 6.13 2.00 2.1 65 73.0 2517 10542 3.05 2 M10 x 21/2 114 156 102 156 51 1.0 3.000 365 2580 0.12 3/8 x 21/2 4.63 6.00 4.13 6.13 2.00 2.1 76.1 mm276.1 2517 11476 3.05 M10 x 21/2 118 152 105 156 51 1.0 3 3.500 365 3512 0.12 3/s x 21/2 5.13 6.75 4.63 6.75 2.00 2.3 .3 80 88.9 2517 15622 3.05 2 M10 x 2'h 130 171 117 171 51 4 4.500 365 5805 0.17 3/8 x 21/2 6.00 7.88 5.63 7.50 2.13 2.9 100 114.3 2517 25822 4.32 2 M10 x 2% 152 200 143 191 54 1.3 4.250 365 5175 0.17 3/8 x 21/2 5.63 7.38 5.38 7.38 2.13 3.1 108.0 mm2108.0 2517 23020 4.32 M10 x 21/2 152 1.87 137 187 54 1.4 5 5.563 365 8870 0.17 ' x 3 7.25 9.25 6.75 9.13 2.25 5.0 125 141.3 2000 39456 4.32 2 M12 x 3 184 235 171 232 57 2.3 5.250 365 7897 0.17 ' x 3 6.63 9.00 6.38 9.00 2.25 4.8 133.0 mm2133.0 2517 35106 4.32 M12 x 3 168 229 162 229 57 2.2 139.7 mm 5.500 365 8667 0.17 2 '/2 x 3 6.88 9.25 6.75 9.13 2.25 4.9 139.7 2517 38529 4.32 M12 x 3 175 235 171 232 57 2.2 6.250 365 11192 0.17 Y x 31/4 7.88 10.00 7.38 9.88 2.25 5.6 159.0 mm 159.0 2517 49753 4.32 2 M12 x 3'/a 200 254 187 251 57 2.5 6.500 365 12105 0.17 1 x 3'/a 8.00 10.25 7.75 10.13 2.25 6.0 165.1 mm 165.1 2517 53813 4.32 2 M12 x 3'/a 203 260 197 257 57 .7 6 6.625 365 12582 0.17 1/2 x 318.38 264 10.38 2008 10.13 6. 2.25 0 150 168.3 2000 44469 4.32 2 M12 x 3/a 216.0 mm 8.500 365 20712 0.17 2 5/9 x 4 10.63 13.25 10.25 10.13 2.63 11.4 216.0 2517 55968 4.32 M16 x 4 270 337 260 257 67 5.2 8 8.625 365 21326 0.17 5/9 x 4 10.88 13.38 10.25 13.13 2.50 11.4 200 219.1 1620 94863 4.32 2 M16 x 4 276 340 260 333 64 5.2 7 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.See the Listings/Approvals section of this publication for ratings on other pipe. 8 The allowable pipe separation dimension shown is for system layout purposes only.FireLock EZTM couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 9 Number of bolts required equals number of housing segments. NOTES • When assembling FireLock EZTM couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop.For FireLock EZTM Style 009N couplings,use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall not be used with Style 009N couplings.IMPORTANT:Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling.There is no interchanging of gaskets or housings between coupling styles. • Use Of Flushseal Gaskets For Dry Pipe Systems FireLock EZTm couplings are supplied with FireLock EZTM Grade"E"Type A gaskets.These gaskets include an integral pipe stop,that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems.It should be noted that standard Victaulic Flush-SeaITM gaskets are not compatible and cannot be used with the FireLock EZTM couplings. • • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. \CtauIiC victaulic.com 4 victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • 6.0 REFERENCE MATERIALS • Publication 05.01:Seal Selection Guide 1-009N/009H:Installation Instructions FireLock EZTM Rigid Coupling • • User Responsibility for Product Selection and Suitability Note Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications.All products Victaulic products for a particular end-use application,in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions. standards and project specifications,as well as Victaulic performance,maintenance, Victaulic reserves the right to change product specifications,designs and standard safety,and warning instructions.Nothing in this or any other document,nor any verbal equipment without notice and without incurring obligations. recommendation,advice,or opinion from any Victaulic employee,shall be deemed to alter,vary,supersede,or waive any provision of Victaulic Company's standard conditions Installation of sale,installation guide,or this disclaimer. Reference should always be made to the I-009N/I-009H Firelock EZ Rigid Coupling Installation Instructions for the product you are installing.Handbooks are included with Intellectual Property Rights each shipment of Victaulic products,providing complete installation and assembly data, No statement contained herein concerning a possible or suggested use of any material, and are available in PDF format on our website at www.victaulic.com. product,service,or design is intended,or should be constructed,to grant any license under any patent or other intellectual property right of Victaulic or any of its subsidiaries Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. or affiliates covering such use or design,or as a recommendation for the use of such material,product,service,or design in the infringement of any patent or other intellectual Trademarks property right.The terms"Patented"or"Patent Pending"refer to design or utility patents Victaulic,FireLock EZT^ Flush-SeaP"",and Installation-Ready'',are trademarks or or patent applications for articles and/or methods of use in the United States and/or other registered trademarks of Victaulic Company,and/or its affiliated entities,in the U.S.and/ countries. or other countries. • • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 4tauI,c* BARB°N STEEL PIPE—GROOVED CQIPLINGS .., 1_• , 1 i v � w,s L Reducing Coupling `Ous ® Vds 1 PCB SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 750 t - The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed to replace two couplings and a reducing fitting,the Style 750 features a special reducing 11111 Pite gasket for pressure responsive sealing.A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536,grade 65-45-12. Ductile iron conforming to ASTM A-395,grade 65-45-15, is available upon special request. Housing Coating: Orange enamel • Optional: Hot dipped galvanized and others Gasket: (Specify choice"): • Grade"E" EPDM (All other sizes) EPDM (Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. " Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional:Assembly Washer:Galvanized,carbon steel Bolts/Nuts: Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com jctauli VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV 1 06.08 1 CARBON STEEL PIPE-GROOVED COUPLINGS vo.va Reducing Coupling STYLE 750 DIMENSIONS Max.Work Allow.Pipe Bolt/Nut@ Size Pressure- Max.End Load - End Sep.tAt.Each Deflect.Fr.Ci No-Size Dimensions-Inches/mm Wgt.Eac Nominal Size Per Pipe Inch zmm psi Lbs. Cplg. In./Ft. kPa N Inches/mm Deg. mai/alInches x Lbs. 2 1 '> 350 Y Z kg 502 x 500 0-0.07 0.20 338 528 1.88 2.7 25 i 2410 2225 0-1.8 0 5T 17 2-3/8x2 85 134 48 12 11/2 350 I 1000 0-0.07 40 2410 4450 0-1.8 0 57 02017 2-3/8 x 2 338 528 188 2.0 21/2 85 134 48 10 2 500 2215 _..__. 65 x 50 3450 9850 0_�.g 0°-47' 0.16 2-3/8 x 2 4.00 5.93 1.88 3.1 _„,__ ._ _:._. 14 102 151 48 1.4 76.1 mm x 2 s 350 - 1550 0-0,070,16 . 50 2410 6900 0_1.8 0°-47' 2-Yz x 2'/a 14 111 168 48 21 4.38 6.63 188 4.6 3 2 350 1550 0-0.07 80 x 50 2410 0°-39' 0113 i 3 4.75 7.13 1.88 4.9 6900 0 1.8 2-/zx2/a : 121 181 48 2.2 21/2 500 3250 0-0.07 7.1 0.13 65 3450 14460 0-1.8 0°-39' 11 2-' x 2 3/ 4.75 7.13 1.88 43 _.. .....__ 121 181 350 48 2 0 889mm x 761 mm 2475 0-0.07 0.13 ._8 .__ 2410 11010 0-1.8 0°-39' 11 2-1/2x23/4 4.75 7.13 1.88 4.2 .,. 4 _.. .., 121 181 48 1.9 2 350 1550 100 x 50 2410 6900 p-3 2 1 19 �58 i 2-5/8 x 3Ya 625 8.90 2.25 8.1 2/z 350 159__ 226 57 3.7 2275 028 65 2410 10125 0 03.2 1° 19, 2-5/8x3Ya 625 890 225 8.6 25. 159 226 57 3.9 3 500 4810 0-0.13 80 3450 21400 0-3.2 1 9' 0.28 2-5/8 x 3 Ya 6 00 8 90 225 6.7 25 152 226 57 1143 mm x 767 mm 350 2475 0-0.13 3.0 2410 11014 19' 0.28 18.90 0-3.2 25 2-5/8x3/a 625 226 2.25 6.9 5 4 E 350 E 159... ! 226 57 3 x 5565 0-0.13 125 100 2410 i 24765 0-3.2 1 3 0192 2-3/4x 4 Ya 7 18 10.70 2.13 11.2 6 x 4 350 i 5565 0-0.13 }. 182 272 54 5.1 150 100 2410 24765 ' 0° 52 0.18 3 8.63 11.90 225 16.7 { 0-3.2 15 2-/ax4/a 181 302 57 7.6 5 350 8500 0-0,13 125 2410 37825 0.18 i 831 1190 225 12.9 0 3.2 0°-52 15 2-3/ax4Ya 211 302 57 5.9 165.1 mm x 4 350 5565 0-0.13 0.19 100 2410 24765 0 3.2 0 55 16 2-34x 4 Ya 8 63 11 90 225 5.2 8 6 _ ,_ 219 302 350 12060 57 � 69 0.13 . .. 200 x 150 2410 53645 0 0.1� 0° 38' 2-7/8 x 5 10 81 14.88 250 22.4 11 275 378 64 102 2191 mm x 1651 mm i 350 11610 0-0.13 0.13 2410 51645 0-3.2 0` 38 11 x 075 14.88 2.50 23.2 2 7/8 5 10 __ ....z 273 .._` 378 64 10.5 8 350 20450 0-0.13 0° 25' 0.9 13.12 1726 2.62 31.4 273 x 2791 i 2410 90970 0-3.2 8 2-1x 51/2 333 , 438 67 Style 750 Reducing couplings should not be used with end caps(#60)in systems where a vacuum may be developed,Contact Victaulic for details. 14.2 *Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 1 Yz times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 3/4-3 1/2"/20-90 mm;25%for 4'%100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. Y 1 Ii_fZ,; Y z- FZ-► isk. --Ai It ipralmaki..1114.......414. ,,,,.„i r_lit ...I NVila.... 1..__,,i www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ��'ta'1UIIC' 06.08 2 REV J CARBON STEEL PIPE-GROOVED COUPLINGS UO.V$ Reducing Coupling STYLE 750 FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables.All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Equiv.Pipe Size Length Size Length Nominal Nominal Size Sm.Dia. Size Sm.Dia. Inches/mm Feet/m Inches/mm Feet/m 2 1 5.9 12 2.7 50 x 25 1.8 25 x 50 08_. 1'h ` 2.0 11/2 2 1.9 40 ; 0.6 40 x S0 06.. _.. 21/2 2 1.9 2, 2'1 1.0 65 x 50 0.6 50 x 65 Y 0 3 761mm .0 761mm x 50 06 0.3 3 2 5.5 3 I 35 80 x 50: 17 80 1.1 21/2 3.8 4 3.0 65" 12 100 0.9 889m x__ 761 mm d 3.2 658 2'/z 80 O8 4 2 60 4 3.0 100 x 50 1.8 ! .._: 100 09 25 65 :: 1.8 761m x 889mm ` 0.8 3.. 6.0 3.0 1143 0.9 114.3 mm x 761 mm i 1 8 80 x 100 E 0.8 5 4 30 4 5 33 125 x 100 0.9 100 ... 1255__ _ 1 0 64 60 6 4.6 150 x' 100 1.8 150 I 1.4 5 _. ,U. 4.5 165.1 mm! 4.6 125 ' 1.4 14 165.1 mm 'x 4 60 5 x 6 23 100 1.8 125 150 07_ __._.. 86 73 6 x 8 60 200 x 150 1 22 150 200 .�._11 8 ,._,.. 73165.1mm x 2191mm I 5.4 219.1mm x 165.1 mm 22365 10 8 87 8 10 6.3 273 x 2191 265 2191 x 273 I 192 • www.victaulic.com ‘iiCtaulac' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. RFV .I CARBON STEEL PIPE-GROOVED COUPLINGS Reducing Coupling STYLE 750 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 06.08 1536REV J UPDATED 08/2012 ,L`taUIiL'® VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. V� 06.08 Victaulic® Flexible Coupling jtauIicr Style 75 06.05 • Victaulic RX roll sets must be used when grooving light-wall/thin-wall stainless steel pipe for use with Victaulic Couplings. VI Failure to use Victaulic RX roll sets when grooving V light-wall/thin-wall stainless steel pipe may cause joint failure, resulting in serious personal injury and/or Exaggerated for clarity property damage. Approvals/Listings ® @' LPCB 0 vds NOTICE • Victaulic RX grooving rolls must be ordered See Victaulic publication 10.01 for details separately. They are identified by a silver color and See Victaulic publication 02.06 for portable water approvals if applicable. the designation RX on the front of the roll sets. Product Description Style 75 is available where moderate pressures are expected or weight considerations are a factor. Up to 50% lighter in weight than the Style 77, the Style 75 coupling is recommended for service up to 500 psi/3450 kPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. The Victaulic standard flexible coupling offering for grade "EHP" or "T" gaskets is the Style 177 installation-ready flexible coupling. For all available sizes, the Style 177 is the standard flexible coupling Victaulic supplies in North America for piping systems using Grade "EHP" or "T" gaskets. Contact Victaulic for further details. Performance data presented in this document is based on use with standard wall, carbon steel pipe. For use with stainless steel pipe, please reference publication 17.09 for pressure ratings and end loads. When used on light wall stainless steel pipe, the Victaulic RX roll set must be used to roll groove the pipe. For further information regarding roll grooving stainless steel, refer to publication 17.01. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. 1 ictaulic® victaulic.com I Couplings I Flexible i Style 75 I Publication 06.05 Material Specifications Housing: Bolts/Nuts: Ductile iron conforming to ASTM A-536, grade 65-45-12. Heat-treated plated carbon steel, trackhead meeting the Ductile iron conforming to ASTM A-395, grade 65-45-15, physical and chemical requirements of ASTM A-449 and is available upon special request. physical requirements of ASTM A-183 Housing Coating: (specify choice) ❑ Standard: Orange enamel. ❑ Optional: Hot dipped galvanized and others. Gasket: (specify choice') NOTE:Additional gasket styles are available.Contact Victaulic for details. ❑ Grade "E" EPDM EPDM (Green stripe color code). Temperature range—30°F to +230°F/-34°C to +110°C. May be specified for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot+180°F/+82°C potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR PETROLEUM SERVICES. ❑ Grade "T" Nitrile Nitrile (Orange stripe color code). Temperature range 20°F to +180°F/29°C to +82°C. May be specified for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not compatible for hot water services over +150°F/+66°C or for hot dry air over+140°F/+60°C. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulicW • victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 Dimensions Style 75 I Y 1 [4-7 1 0 Ili :ff, 1111 Actual Maximum Maximum Allow. Dimensions Approx. Nominal Outside Working End Pipe End Deflection from Weight Size Diameter Pressure 2 Load 2 Separation3 Centerline3 Bolt/Nuta X Y Z Each Pipe inches inches psi lbs. inches Per Cplg. inches/ft. inches inches inches lbs. mm mm kPa N mm Degrees mm/m (No.)size inches mm mm mm kg 1 1.315 500 680 0-0.06203, 0.57 2_3/s x 2 2.38 4.27 1.77 1.3 25 33.4 3450 3025 0-1.6 48 61 108 45 0.6 11/4 1.660 500 1080 0-0.060.45 2.68 4.61 1.77 1.4 20-10' 2-3/8x 2 68 117 45 0.6 32 42.2 3450 4805 0-1.6 38 1 1 1.900 500 1420 0-0.0610-56' 0.40 2-3/8x 2 2.91 4.82 1.77 1.5 40 48.3 3450 6320 0-1.6 33 74 122 45 0.6 2 2.375 500 2215 0-0.0610-31' 0.32 2-3/8x 2 3.43 5.22 1.88 1.7 50 60.3 3450 9860 0-1.6 26 87 133 48 0.8 21 2.875 500 3245 0-0.061,-15' 0.26 2-3/13x 2 3.88 5.68 1.88 1.9 65 73.0 3450 14440 0-1.6 22 98 144 48 0.9 3.000 500 3535 0-0.060.26 4.00 5.90 1.88 1.9 76.1 mm 10-12' 2-3/8 x 2 102 150 48 0.9 76.1 3450 15730 0-1.6 22 3 3.500 500 4800 0-0.060.22 4.50 7.00 1.88 2.9 80 88.9 3450 21360 0-1.6 10-2' 18 2 1 x 2 3/a 114 178 48 1.3 3 1/2 4.000 500 6300 0-0.060.19 5.00 7.50 1.88 2.9 0°-54' 2-1/2 x 2 3/a 127 191 48 1.3 90 101.6 3450 28035 0-1.6 16 4 4.500 500 7950 0-0.130.34 5.80 8.03 2.13 4.1 1°-36' 2-1/2 x 2 3/a 147 204 54 1.9 100 114.3 3450 35380 0-3.2 28 108.0 mm 4.250 450 6380 0-0.130.35 5.55 7.79 2.13 3.7 1,-41' 2-12 x 70 108.0 3100 28395 0-3.2 29 141 198 54 1.7 41/2 5.000 450 8820 0-0.130.256.13 9.43 2.13 5.5 10-26' 21 2-3/8)(3 1/a 156 240 54 2.5 120 127.0 3100 39250 0-3.2 5 5.563 450 10935 0-0.130.27 6.88 10.07 2.13 5.8 10-18' 2-5/8x 31/a 175 256 54 2.6 125 141.3 3100 48660 0-3.2 23 133.0 mm 5.250 450 9735 0-0.13 0.28 6.55 9.37 2.13 6.0 1°-21' 2-16 x 82.5 133.0 3100 43325 0-3.2 24 166 238 54 2.7 5.500 450 10665 0-0.13 0.28 6.80 9.59 2.13 6.3 139.7mm 1°-18' 2-5/8x 31/a 173 244 54 2.9 139.7 3100 47460 0-3.2 24 6.000 450 12735 0-0.13 0.21 7.38 10.48 1.88 6.2 152.4mm 1°-12' 18 2-5/9x3 Y4 187 266 48 2.8 152.4 3100 56670 0-3.2 6 6.625 450 15525 0-0.130.23 8.00 11.07 2.13 7.0 150 168.3 3100 69085 0-3.2 10-5' 18 2-%x 3 1/a 203 281 54 3.2 6.250 450 13800 0-0.13 0.24 7.63 10.49 2.13 6.8 159.0 mm 1,-9' 2-16 x 82.5 194 266 54 3.1 159.0 3100 61405 0-3.2 20 8 8.625 450 26280 0-0.1300-50' 0.18 2-3/a x 41/a 10.34 13.97 2.13 12.4 200 219.1 3100 116945 0-3.2 14 263 355 59 5.6 2 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. 3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by: 50%for 3/4-3 1/2"/20-90 mm;25%for 4"/100 mm and larger. 4 Number of bolts required equals number of housing segments. General Notes Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. 3 ictaulic victaulic.com victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 Installation Note Reference should always be made to the 1-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic® ••••=immmimm•Eimi SAMMYS® hi I ltil YS® SIDEWINDER° FOR WOOD -Horizontal Application Application Product Features Not less than 2"nominal width •No pre-drilling required. (1-1/2")up to 3-112"pipe;not less than 3"(2-1/2")nominal width 4"&5"pipe •Quick to install using the Sammy k.�m 4---1 Floor Joist Nut Driver with an 18V cordless drill/driver. Minimum 2-1/2"from bottom for s branch lines.Minimum 3"from bot- tom for main lines.Exception:This •Saves time from traditional requirement shall not apply to 2"or methods. thicker nailing strips resting on top of steel beams. •Reduces installation costs. - •Made in the U.S.A. Composite I Truss Consult truss manufacturer for recommended installation point. 'Pre-drilling may be required for Model SWG 25-380.Tool available on page 11. 1 P; Watch a video demonstration at ° www.itwbuildex.corn Approvals Rod Part Model Screw Ultimate UL Test Box Case Size Number Descriptions Pullout(lbs) Load(lbs) Qty Qty HORIZONTAL MOUNT 1/4" 8019957 SWG 200 1/4 x 2" 1725 (Fir) 25 125 3/8" 8021957 SWG 20 1/4 x 2" 1725 (Fir) 1050 25 125 v 3/8" 8022925 SWG 25-380 3/8 x 2-1/2" 2249 (Fir) 1500 25 125 #14 SW Red ^s, -t!..:3(" .. it,''i* ;.,,`rt ,.:. y ?:Sliw.. 884 i .,. `.,4,77,f,,,;..„.. Nut Driver Part#8114910 •May require pre-drilling;consult joist manufacturer. SAMMYS SWIVEL HEADTM FOR WOOD - Swivel Application • Application Product Features 4 V/000 JOIST •Eliminates distortion of threaded rod. • •Accommodates up to 3%'x 12 pitch roof. +" •Allows 17°deflection from vertical. t •Saves time from traditional methods. •Reduces installation costs. N. 4,40 •Made in the INN .S.A. a ER goz MAXMAXANG E w 41109 Approvals Rod Part Model Screw Ultimate UL Test Load FM Test Min Box Case Size Number Descriptions Pullout(lbs) (lbs) Load(lbs) Thickness Qty Qty e. SWIVEL MOUNT r4#14 Black /,.<> 3/8" 8139957 SH GST 20 114 x 2 1257(Fir) 1050 1475 25 125 Nut Driver — fl„- 0, $10 -1;140144 1/4'1,.= 4;+ 0 .,- 47 4'.-' 1 5 Part#8113910 - e . .. .. ._.,. n... 1903 Dim.Lumber 1500 Q" 3/8" 8269957 SH-GST/CST 20 5116 x 1-314" 1406 @ 45°off vertical 1855°0° 45° 25 125 Dim.Lumber r 2 p x 1-3/4» 1 1 Ars a '1 - - *May require predrilling;consult joist manufactures S #14 SH Orange N, Nut Driver Part#8273910 • 5 To find a distributor near you.call 800-BUILDEX f• qtr �r .d 'r � . "�,; z# E 4 a �^ „„ s :t ri '^k f'' F1 �g Y �'it;: r't b x,x ,.: �, .=.sz, air'+ t i x�1r , u- t s[ "' -i` ,'"n.,rnamu:,^ , Ft ` . r 5 .SAMMYS° FOR WOOD - Vertical Application ApplicationProct Features Not less than Wood Flooring 2"nominal width •No pre-drilling required. 4_4(1-1/2..) 1 •Quick to install using the Sammy Not less than Nut Driver with an 18V cordless 3"nominal drill/driver. thickness(2-1/2") (depth or side Wood Joist of vertical member) •Saves time from traditional mam its methods. n Double Sheetrock = For vertical use- Ceiling •Reduces installation costs. install in center of lower face. Minimum 2"embedment into base •Made in the U.S.A. material for NFPA 13 compliance. Composite/Truss I Consult truss manufacturer for recommended installation point. y. • ) "Pre-drilling maybe required for GST , , 25-380.Tool seailable on page 11. g'. 1. 1 0 I r Watch a video demonstra6'on at www itwbuiidex.com Approvals Rod Part Model Screw UL Test FM Test Box Case Size Number Descriptions ut s) Load(lbs) Load(lbs) Qty Qty VERTICAL MQUNT 1/4" 8002957 GST 10004 1/4 x 1" 210 /1 "OB) 25 125 .,..,,,,, 670 /4Pl :,,.„,, i4 39a7 5 x :F:Ulllt:m:apa,,,y(t.: , p . r,..ois - .. 1/4 800497GST 300 1/4 x3 200 (Fir) 25125 ii7 8, q t .: e y r m x — I 3/8"o„ "i%:*„„.''''''./'fr''' 1 8008957 GST 20 1/4 x 2 1760 (Fir) 850: ' ' 1475 25" 125, v 009925 GST 25-380 318x2-1/2" 2113 (Ftr) 1500 2-:;4:7''''''r''11:0$2 :: 5 125 #14 Black % :, 1+ 7 c r Nut Driver °! ':".140:1, t4 .; 3/8 8069925 GST 30 SS 1/4 x 3 2060 (Fir) 25 125 Part#8113910 �. 1/2" 8013925 GST 2 1l4 x 2" 1760 (Fir) 25 125 b. i 1,_ 1/2" 8015925 GST 3 1/4 x 3" 2275 (Fir) 25 125 #14 SW Red Nut Driver Part#8114910 n . ye, SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. For the most up to date information,visit www.itwbuildex.com 4 AZ47g1§M P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 514 CPVC - COPPER #905 #906 STEEL . :OFFSET HANGER 404 3.00 1 I = = ...= NIMI=. SIZE-SYSTEM PIPE: 3/4"thru 2" O MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- Hanger/Restrainer CONUSED 203-EX 4231,EX 2551 M.1 PATENT-No.6,648,278. 11 % FUNCTION- Support horizontal piping: CPVC,Copper or Steel. l,.! Provides listed vertical/horizontal restraint and prevents upward movement of pipe from pendent sprinkler discharge. Stabilize vertical piping. -Hanger/ -\� , ... INSTALLATION- Per these instructions Restrainer I) `� Stabilize including NFPA 13, 13R, 13D and CPVC manufacturers instructions. 1111 Install on horizontal or vertical mounting surface. Snap over pipe then squeeze strap back allowing pipe to slide freely. =_ When #905 threads are exposed in wood,install#906 backing nut. = FASTENERS-UL Listed per NFPA 13 `Tl) WOOD- CPVC pipe-#905 screw-no pre-drill. Copper and Steel pipe-#14 SMS or 1/4"xl 1/2" lag screw- no pre-drill. Thru 5/8" gypsum board- 1/4"x 2"lag screw. STEEL-min. 18 GA.-CPVC,Copper and Steel pipe- 1/4" or#14 Tek Screw. o • CONCRETE: Required minimum load each fastener= 5(wt)+2501bs. 2 4 4 FEATURESo * 1 1/2" Offset-loose fit allows pipe to slide. 4 * Common center-line for 3/4" and 1". "� * Offset edge eliminates abrasion. *AFCON#905 screw included-5/16"hex head. ilf_f_�`' ORDERING-Part#and pipe size. v AFCON#906 backing nut sold separately. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT he liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCONproducts have been,or are used. i"�;:.CAD; 11/13 . P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 515 CPVC DOUBLE OFFSET HANGER Hanger/Restrainer 0 11.11= oa 1;1• SIZE-SYSTEM PIPE: 3/4"and 1" MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- usreo 203-EX 4231 PATENT-No.6,702,236 FUNCTION-Support horizontal CPVC pipe. Provides listed vertical/horizontal restraint and prevents / upward movement of pipe from pendent sprinkler discharge. / Hanger/Restrainer INSTALLATION- Per these instructions including NPFA 13, 13R / 13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. FASTENERS-UL Listed per NFPA 13. #904 screw in wood-no pre-drill. FEATURES 0* Double 1 1/2tt offset * Common center-line for 3/4" and 1". *Offset edge eliminates abrasion. *Required AFCON#904 screw included-3/8"hex head. ORDERING-Part#and pipe size. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON AFCON shall NOT he liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCONproducts have been,or are used. 11/13 Atz17 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 510 CPVC - COPPER - STEEL HANGER 510 Fastener o SIZE �im� 3/4 2.125 1 2.312 O 11/4 3.170 1 1/2 3.400 2 4.010 2 1/2 4.320 3 5.320 SIZE-SYSTEM PIPE: 3/4"thru 3" MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- / Os 203-EX 4231,EX 2551 LISTED FUNCTION-Supporthorizontal piping: CPVC,Copper or Steel. Size 3/4"-2"Prevents upward movement of pipe from pendent sprinkler discharge. Stabilize vertical piping. I INSTALLATION- Per these instructions 11111 M including NFPA 13, 13R, 13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. FASTENERS- UL Listed per NFPA 13 in WOOD: 3/4"-3"CPVC pipe-#905 screw-no pre-drill. 3/4"-3" Steel and Copper pipe-#14 x 1 1/2" SMS or Restraint 1/4"x11/2" lag bolt-no pre-drill. in STEEL-min. 18 GA. 3/4"-3"CPVC,Copper and Steel pipe- 1/4"or#14 Tek Screw. •',• I FEATURES ti,i * Offset edge eliminates abrasion. *Retainer dimples secure hanger to pipe during installation. Hanger a � Stabilize * Required AFCON#905 screw included-5/16"hex head. \. ORDERING-Part#and pipe size. / - �� CAN ALSO BE USED TO REPLACE- #500 Pipe Strap #520 Tin Strap Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including pails and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. not manufathe ctured following warranty restriction will sold by AFCON.AFCON shallly NOTbe Gable n deer anER- y stanNOwhat whatsoever for ny directfailure orindirect,tincidentalwhen or consequential damages of any kind,incl ding but noton with other products,parts or systems limited to loss of business or profit,when non-AFCON products have been,or are used. , 5/14 .`�. :gg0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 300 RING HANGER i 1 thru 4 inch pipe 1/2&3/4 inch pipe LISTED FOR STEEL/CPVC 5 thru 8 inch pipe NFPA 13 UL PIPE ROD 1 WT. 5 WT.+250 TEST LOAD 1 3/8 30.75 403.75 750 11/4 3/8 43.95 469.75 750 SIZE-ROD-3/8"or 1/2" 1 1/2 3/8 54.15 520.75 750 SIZE-SYSTEM PIPE- 1/2"thru 8" 2 3/818 76.95 634.75 750 MATERIAL-Carbon Steel,Mil.Galvanized to G-90 spec. 2 V2 3/8 162.30 841.75 850 05 LISTING/APPROVAL- 3 3/8 162.30 1061.50 1050 4 3/8 246.00 1480.00 1500 5 1/2 349.45 1996.75 2000 `us�TEO us 203-EX 2551 1"-8" 6 1/2 476.35 2631.75 2650 FM Approval guide-1"-8" 8 1/2 711.00 3805.00 4050 OSHPD OPA-0601 See Website. CONFORMS WITH:Federal Specification WW-H-171E,Type 10. Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10. MAXIMUM TEMPERATURE-650°F. FUNCTION-Pipe hanger component of an AFCON hanger. To support steel,CPVC or copper pipe. INSTALLATION-Per NFPA 13, 13R, 13D,these instructions and the CPVC or copper pipe manufacturers instructions. °"E A B FEATURES 8793 25259 T 11/4 2.1382 2.7850 * Sized and listed exclusively for use with#310 Surge Restrainer. 2 2.2673 2."'° * Band edge is offset for EASY pipe insertion. Aillik A B 2 2.6048 32516 * Custom fit swivel nut for better retention in ring. 2,/2 3.492° 44311 3 3.7845 4.4311 ORDERING-Part#,pipe size. 4' 4 4.3582 4.9992 8 7.5768 8.3190 8 7.5768 8.3290 11/09 � 's .a7g000 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 077 ATTACHMENT FITTING LOCKING 17/32" 17/32" v O --.Nro.... (9 ‘,,,,11., e at _ 0 ,- „,„, 9 077D DUCTILE BASE PLATE 077S STEEL BASE PLATE SIZE-BRACE PIPE: 1” and 1 1/4" Sch.40 MATERIAL-Carbon Steel,Ductile Iron or S.S.(Type 304). FINISH-Plain or E.G. LISTING/APPROVAL- c(DDS 203A-EX2625 © Approved FM Approved-1950 OSHPD See Website. LASTED FUNCTION- Structure attachment fitting of an AFCON sway brace assembly. c®ua Max. Horizontal Load Sway brace assemblies are intended to be installed in accordance with Size 1-1 1/4 I 2015 NFPA 13 and the manufacturer's installation instructions. INSTALLATION-Per these instructions including NFPA 13 or FM 2-8. Load rating-see chart. ASSEMBLY Combine with proper AFCON components-see disclaimer below. Insert brace pipe thru fitting near pivot bolt. Q Max.Horizontal Load Tighten set bolt until head contacts bracket. FEATURES 3044° 45-59°60-74° 75-90° * Swivel allows attachment at any angle. *Visual inspection,verifies proper installation. Size 1-1 1/4 630 870 1620 1810 *Larger fastener hole available.-Consult factory. ORDERING-Part#,size-brace pipe and finish. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 9/14 t , Ad7:?§§,§31 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 411 SWAY BRACE FITTING Part#077 *ft:-t 7 Part#078 •i "IrTAmpF-7, ii‘.,,,. C,coft, ,,,,,,,,,\I " SIZE-SYSTEM PIPE:Nominal Pipe Size ° Sch.40 Steel 1"- 12" 411�' '.t �� Sch. 10 Steel 1 1/4"- 12" i - Sch. 7 Steel 2"-6" MATERIAL-Carbon Steel or S.S.(Type 304) FINISH-Plain or E.G. PATENT-No.7,140,579 LISTING/APPROVAL OO Listed Max.Horizontal Load c �L us 203A-EX1"-10" I 2765 2625 © FM Approved-1950 12" 3740 Unit, APPROVED FUNCTION-Longitudinal fitting of an AFCON sway brace assembly. Sway brace assemblies are intended to be installed in accordance with NFPA 13 and the manufacturer's installation instructions. ©certified Max.ASD Horizontal Load INSTALLATION- Per these instructions System Including NFPA 13 or FM 2-8 NPS Sch. 30°44° 45°-59° 60°-74° 75°-90° Load rating-see chart. 1"-1 1/2" 10-40 420 510 570 2 -3" 7-40 860 1030 1150 ASSEMBLY-See drawing. a" 7-40 860 1030 1150 6" 7-40 Combine with proper AFCON components-see disclaimer below. 2220 11502 3040 6,. 7-ao 040 8" 10-40 1340 1620 1810 Align brace member parallel to face of 411 fastener flanges. 2220 3 Tighten 1/2"bolts until fastener flanges connect. FEATURES * Patented-design eliminates bending of fastener flanges during installation. * Patented-design prevents over tightening on system pipe. * Improved assembly-fastener flanges connect for superior strength. * Visual inspection-proper installation when 411 fastener flanges connect. ORDERING-Part#,size-system pipe and finish. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,pans or systems not manufactured or sold by AFCON AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCONproducts have been,or are used. 0::.,:. ';',', '' 5/14 ..47:grg§,aD P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 078 ATTACHMENT FITTING LOCKING t 41 ® Part#077 9/16 Dia. 1 i ii I 0 , �� `\ i 4441 ,•, \ Part#078 r41 01 %,iil .._ Part#410/411— SIZE-BRACE PIPE: 1"and 1 1/4" Sch.40 MATERIAL-Carbon Steel or S.S.(Type 304). ►: FINISH-Plain or E.G. J LISTING/APPROVAL- Oils 203A-EX 2625 FM FM Approved-1950 OSHPD See Website. usre° FUNCTION-Structure attachment fitting of an AFCON sway brace assembly. Common transition component with 411 sway brace fitting-see drawing Sway brace assemblies are intended to be installed in accordance with NFPA 13 and the manufacturer's installation instructions. INSTALLATION- Per these instructions 0 Max. Horizontal Load including NFPA 13 or FM 2-8. Load rating-see chart. 30°-44° 45°-59° 60°-89° 90° DO NOT BEND-If angle required use part 070,075,076 or 077. 1008 I 1425 I 1745 2015 ASSEMBLY Combine with proper AFCON components-see disclaimer below. Insert brace pipe thru fitting near pivot bolt. Load Tighten set bolt until head contacts bracket. 30°_44°Max.x. Horizontal9° zLoad FEATURES 430 I 620 I 760 I 940 *Visual inspection,verifies proper installation. *Bolt hole fits 410/411 sway brace fitting. ORDERING-Part#,size-brace pipe and finish. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. warrant ainst e re of its Be following warranty restriction will apply sold by AFCON.AFCON shall NOTb liable undeer any ER-AFCON will NOT for anyhdirectuor indirect,inc incideducts nn used in combination tal consequential damages of any kind,inc]ding but not systems limited to loss of business or profit,when non-AFCON products have been,or are used. CAD 4/14 . ° .` :,s . 7rffig'010 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 400 RISER CLAMP IRON PIPE ' ""- PIPE STOCK MAX.REC. le-- C .-.,Ic C ... 4 SIZE A B C SIZE LOAD LBS. I # 1 1/2" 10 3/8" 3/8" 1 1/2" 3/16"x1 1/4" 255 _itp_......s _ { HMI MI 2" 10 3/4" 3/8" 2" 3/16"x1 1/4" 255 2 1/2" 11" 3/8" 2 1/8" 1/4"x1 1/4" 390 l*1 I!{ �- 3" 12" 3/8" 3 1/4"x1 1/4" 530 3 1/2" 13" 1/2" 3 5/16" 1/4"x1 1/4" 670 B B 4" 13 1/2" 1/2" 3 3/8" 1/4"x1 1/4" 810 5" 14 1/2" 1/2" 4" 1/4"x1 1/2" 1160 6" 15 1/8" 1/2" 4 1/2" 1/4"x2" 1570 8" 18 1/2" 5/8" 5 13/16" 3/8x2" 2500 NOTE:MAXIMUM TEMPERATURE:650°F SIZE- 1/2 thru 20 inch pipe. ‘10 MATERIAL-Carbon Steel. FINISH-Plain,E.G.,H.D.G.and S.S. LISTING/APPROVAL- (4, Si,. EX 2551 11/2"-8"pipe. OSHPD OPA-0601 See Website. CONFORMS WITH: Federal Specification WW-H-171E,type 8,3/4 thru 20 inch,and " '" Manufacturers Standardization Society SP-69,type 8. FUNCTION-Used for supporting vertical piping. ORDERING-Part#,pipe size and finish. 1/08 IPS yCARBON STEEL PIPE FIRE PROTECTION PRODUCTS 0 . 4 FireLock® Zone Control Riser Module °` OD, SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS • SERIES 747M Designed for NFPA 13 commercial requirements,the Victaulic Series 747M Zone Control Riser Module features a cast body,and is compact and easy to install in zoned wet sprinkler systems. i The integrated module body consists of a shut off valve,test and drain valve combination and " different orifice sizes(K factors),a UL Listed and FM Approved Flow Switch,and a Pressure Gauge.The Series 747M FireLock Zone Control Riser Module is available in sizes from 1' through 6"/32mm-150mm with grooved ends on the main pipe for installation in the horizontal or vertical up-flow positions with UL Listed, FM Approved Victaulic grooved couplings. 11/4-2"modules have an NPT drain port.2' -6"modules have a grooved drain port. The Series 747M FireLock Zone Control Riser Module is FM Approved and UL and ULC Listed for working pressures up to 365psi/2517 kPa.An optional pressure relief valve kit is available STYLE 747M for all sizes.The Pressure Relief Valve is FM Approved and UL and ULC Listed for working PATENT PENDING pressures up to 175psi/1200kPa. DIMENSIONS Module Body Size 1 I Dimensions Inches/mm - gar-u --• „., __1' �� Aprx.Weight E a ACtaf s s Diemeter 1".Diameter n € + )i: E " * 1 $ : i �,��inches/MD' I4 a$f m 11.45 7 20 5 77 3.50 C 11) I 10 OS 7.48 2.54 �8 w 1 2a 1.6602.2I 5.2 ,Lir i 32 42.2 ; 33.4 290.8 182.9_' 146.5 1 88.9 255.3 190.0 64 5 6 9 D ® C F 1 Yz 1.900 1 11.45 7.32 1 5.77 3.50 10G5 7.48 2.54 15.5 40 1 48.3 4 33 4 290.8 185.9 146.5 88.9 255.3 190.0 645 7.0 ` ,� 2 I 2.375 1 11.45 I 7.55 5.77 3.50 ; 10.05 7.48 1 2.54 19.9 -,,„,_,_..,.. 50 I 60 3 33 4 i 290.8 1 191.8 146 5 88.9 t 255.3 190.0 I 64 5 9.0 2 1 2.875 1 14 12.00 1 8.41 6.18 4.25 9.76 11 87 I 4 25 22.7 E G 65 l 73.0 42 I 305 ' 214 157 108 I 248 302 108 10.3- A 3 1 3.500 1 1/4 1 12.00 942 1 6.18 4.25 9.76 11.87 I 4.25 23.2 80 88 9 42 l 305 239 157 108 248 302 = 108 10.6._. PA-2732-50mm Nominal Sizes 4 4.500 2 I 12.00 9.90 ; 7.25 5.00 10.15 12.62 4.21 30.3 ' • 100 114.3 60 305 1 252 184 127 258 321 I 107 13.8 6 6 625 2 12.00 10.85 8.31 6.00 10.15 1 13.62 , 4.24 36.7 150 1 168.3 l 60 I 305 ' 276 211 154 1 258 346 l 107.7 16.7 B pe: Am Orifices 1 1 �q Nominal Size inches 1 f 0 y C 1.25 K5.6 Slit-z ''�„' 1.5 K5.6 r a ,J - F 2 K5.6 2.5 K5.6K6.9K8.0K11.2 3 K5.6 K6.9 K8.0 K11.2 E 4 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8 6 K5.6 K6.9 K8 0 K11.2 K14.0 K16.8 A 21/2-61/65.0-150 mm Nominal Sizes Drain Size Nominal Size Drain Type (Valves shown above in the"test"position. inches Shown with optional Pressure Relief Valve Kit installed) 125 i NPT 1 Hose Clamp 1.5 NPT 2 -1 NPT - 1I 2.5 Grooved 11 r/4_.._, Pressure Relief Valve 3 Grooved Barbed Fitting 4 Grooved 2" Hose Clamp 6 I Grooved I 2' Close Nipple ' ,"�- DrainTubing jie Elbow Barbed Fitting Optional Pressure Relief Valve Kit Detail •JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com jctaulic' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I 10.96 1 FIRE PROTECTION PRODUCTS DEVICES FireLock® Zone Control Riser Module SERIES 747M MATERIAL SPECIFICATIONS Module Body:Cast from ductile iron conforming to ASTM A-536,grade 65-45-12 with integral Victaulic grooved ends. Finish:orange enamel. Shut-off and Test/Drain Valve:Chrome plated brass ball,S 37700 brass clapper,416SS or 410SS shafts,Delrin orifice,virgin Teflon*,enhanced Teflon and EPDM rubber seals. *Teflon is a registered trademark of Dupont Coupling:Any UL Listed, FM Approved Victaulic IPS-sized coupling may also be used.Note: Couplings not included with product. Waterflow Detector:System Sensor Model WFD/WFDTH vane type waterflow detector with sealed retard,visual switch activation,and mechanical delay adjustment.Cover includes tamper resistant security screws and tool. Note: ULC models WFDA/WFDTHA include cover tamper switch. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. • NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. WARNING • This product must be installed by an experienced,trained installer, in accordance with the instructions provided with each valve.These instructions contain important information. Failure to follow these instructions may result in serious personal injury, - , property damage,or valve leakage. 111 If you need additional copies of this product literature or the valve installation instructions,or if you have any questions about the safe installation and use of this device,contact Victaulic Company,P.O. Box 31, Easton, PA 18044-0031 USA,Telephone:001-610-559-3300. For complete contact information,visit www.victaulic.com 10.96 3089 REV I UPDATED 7/2010 VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICt'a1UI1C® 10.96 FireLock® Check Valves ✓ctalulia° Series 717 & 717H 10.08 Grooved ends allow fast, easy installation with just two Victaulic couplings or the valve may be mounted to flanged (ANSI CL.150) equipment using either to Victaulic Style 741 Vic-Flange®or Style 744 FireLock r. U • flange adapters on either end. Series 717 Series 717 (21/2—3'/65—80 mm) (4—12/100—300 mm) k I Series 717H High Pressure Check Valve (2—3'/50—80 mm) Approvals/Listings: c0 us 411> Els LPCB LISTED See Victaulic Publication 10.01 for more details. The FireLock Series 717 Check Valve and Series 717H High Pressure Check Valves are CAD designed for hydrodynamic efficiency and available in 2"/50 mm —3'/80 mm (Series 717H) and 2 lh"/65 mm — 12"/300 mm (Series 717) sizes. Series 717H valves are cULus Listed and FM Approved for service up to 365 psi/2517 kPa. See chart below for approved services for the Series 717 valves. In both valve designs, the single-disc mechanism incorporates a spring-assisted feature for nonslamming operation. This spring-assisted, single-disc design achieves a leak-free seal with as little as 5ft/1.5m of head. Series 717 and 717H FireLock Check Valves can be installed either vertically (flow upwards only) or horizontally. A cast flow arrow indicator is provided to assist with proper valve orientation. Both valves include upstream and downstream pressure taps. Each valve is factory-tested to the rated working pressure. For systems requiring a Riser Check option, refer to publication 10.09. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date Check Valve I Firelock® I Series 717 & 717H I Publication 10.08 ✓ctaulic� victaulic.com 1 • Check Valve I Firelock® I Series 717 & 717H I Publication 10.08 Material Specifications: Spring: All sizes Type 302/403 Stainless Steel Housing: Shaft Plug: Ductile iron conforming to ASTM A-536, grade • Series 717H (2—3"/50—80 mm): Type 416 Stainless 65-45-12. Ductile iron conforming to ASTM A-395, Steel grade 65-45-15, is available upon special request. • Series 717 (2 '/z— 12765—300 mm): Carbon steel Body Coating: zinc plated Series 717H Body: Black Paint Pipe Plug: Series 717H Endface: Electroless Nickel • Series 717H (2—3750—80 mm): carbon steel zinc Series 717 (2 '/z—3"): PPS Coating Series 717 (4— 12"): Black Paint plated Body Seat: • Series 717 (4— 127100—300 mm): Carbon steel zinc plated Series 717H — Nitrile 0-ring installed into an electroless nickel plated endface Series 717 (2 l —3"): PPS Coated ductile iron Series 717 (4— 12"): Electroless Nickel plated Disc Seal or Coating: (specify choice') ❑ Grade "T" nitrile (Series 717H Only) Nitrile(Orange color code).Temperature range—20°F to +180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors, vegetable and mineral oils within the specified temperature range; except hot, dry air over+140°F/+60°C and water over+150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. ❑ Grade "E" EPDM (Series 717 Only) EPDM (green color code). Temperature range-30°F to +230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. NOT RECOMMENDED FOR PETROLUEM SERVICES. ' Services listed are General Service Recommendations only.It should be noted that there are services for which these gaskets are not recommended.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Discs: • Series 717H (2—3750—80 mm): CF8M Cast Stainless Steel • Series 717 (2 %z—3"): Aluminum bronze with elastomer seal • Series 717 (4— 127100—300 mm): Elastomer encapsulated disc with electroless nickel plated seat Shaft: • Series 717H (2—3750 -80 mm): Brass • Series 717 (2 %2—3"): Type 416 Stainless Steel • Series 717 (4— 127100—300 mm) Type 316 Stainless Steel victaulic.com 2 ✓ctaulic' Check Valve I Firelock!I Series 717 &717H I Publication 10.08 Approval/Listing: Approval/Listing Service Pressures Series 717H Size cULus FM LPCB Vds 2"/50 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 2W/65 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 76.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 3"/80 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 4"/100 mm n/a n/a n/a n/a n/a n/a I t n/a 5"/125 mm n/a I n/a n/a n/a I 139.7 mm n/a l 6"/150 mm I n/a n/a I n/a n/a 165.1 mm I n/a I n/a n/a n/a 8"/200 mm n/a n/a n/a n/a 10"/250 mm n/a n/a n/a n/a 12"/300 mm n/a n/a n/a n/a Approval/Listing Service Pressures Series 717 Size cULus FM LPCB Vds 2"/50 mm n/a n/a n/a n/a 2'/z''/65 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa n/a 76.1 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 3"/80 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 4"/100 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 5"/125 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa n/a 139.7 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 6"/150 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 165.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa n/a 8"/200 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 348 psi/2400 kPa up to 16bar/232 psi 10"/250 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a 12"/300 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a ✓ctaiulic victaulic.com 3 • Check Valve I Firelock° I Series 717 & 717H I Publication 10.08 Dimensions- Series 717: f A-> R � A "I:W 0 ;JillIID E -*I J k O F B� 410 c 10 '/z"NPT Upstream Drain J 0 '/z"NPT Downstream Drain Yz"NPT Upstream Drain �~ 0 2"NPT(Drain Optional) ®!z"NPT Downstream Drain Typical 2 'h-3"/65-80 mm Typical 4-8"/100-200 mm Typical 10-127250-300 mm Actual I Dimensions Nominal Outside E to E Approx. Size Diameter A BCDEWeight J K P R Each inches inches inches inches inches inches inches inches inches inches inches lbs. mm mm mm mm mm mm mm mm mm mm mm kg 2' 2.875 3.88 4.26 3.57 65 73.0 99 108 91 - - - - _ 3.6 76.1 mm 3.000 3.88 4.26 3.57 1.6 76.1 99 108 91 - - - _ 3.6 3 3.500 4.25 5.06 4.17 1.6 80 88.9 108 129 106 - - _ - 2.05 4 4.500 9.63 6.00 3.88 2.752.0 100 114.3 245 152 99 3.50951 1144.50 89 3.35 2.1 70 89 51 114 89 85 5 5.563 10.50 6.80 4.50 9. 125 141.3 267 173 114 - 106 55 5.884 4.08104 101 27.0 106 55 149 104 101 12.3 139'7 mm 5.5000 10.50 267 6.80 4.50 4.17- 173 114 106 55 1495.88 4.08104 3.980127.0 106 55 149 104 101 12.3 6 6.625 11.50 8.00 5.00 150 168.3 292 203 - 114 61 1696.67 4.73120 3.899 38.02 127 114 61 169 120 6.500 11.50 8.00 5.00 99 17.2 4.50 2.38 6.67 4 165.1 mm 165.1 292 .73 3.89 38.0 203 127 114 61.625 14.00 9.88 6.06 169 120 99 17 2 8 8 356.0 5.05 5.65 2.15 8.85 5.65 5.75 64.0 200 219.1 251 154 128 144 55 225 144 10 10.750 17.00 12.00 7.09 5.96 146 29.0 250 273.0 432 305 180 151 6.69 2.170 555 277 10.92 173 100.0 171 - 12 12.750 19.50 14.00 8.06 6.91 45.4 300 323.9 495 356 205 7 2.51 12.81 140.0 176 19944 64 925 196 - 63.5 Dimensions- Series 717H: A C II► . IDE Di Typical 2750 mm-3780 mm Dimensions Nominal E to E Approx. Size A BCD EJ K P Weight R Each inches inches inches inches inches inches inches inches inches inches lbs. mm mm mm mm mm mm mm mm mm mm kg 2 8.66 6.46 3.23 1.48 3.02 50 219.8 164.1 82.1 37.5 76.7 711.7 .0 - - 0 4.25 1 108.0 4..9 0.7 2'' 9.37 6.94 3.31 1.66 65 238.0 176.3 84.1 3.40 3.38 4.38 13.. 8 42.2 86.4 85.9 - - 9.37 6.94 3.31 1.66 111.3 6.3 76.1 mm 238.0 176.3 84.1 42.2 3.40 3.38 - 86.4 85.9 - 4.38 13.8 3 9.62 7.44 111.3 6.3 3 244.32189.04 3.53 1.91 3.65 3.38 48.592.7 85.9 - - 4.63 2 117.6 9..10 1 victaulic.com 4 Jctaulic' Check Valve I Firelock®-I Series 717 & 717H I Publication 10.08 Flow Characteristics The charts below express the flow of water at 60°F/16°C through valve. S717H/717HR � I i .'-------f-----t moil, 6 a , '.5, i t t \,, v , v s t I. , I t . 1, y„� P ^) 1 i 11 o —1\ti — _» . ._l 1.__ 1 �..1 __1=itit , 1 i N F i k C 3 .. . 6 100 1000 10 Flow—GPM 5717H/717HR 100.00- "d .-r� 747 L 1 ..... ., gip,.. , .1.�- ..`i"`..”}y".s F :" € - I '= 1 f Hit, I 1 1 E 44 44 1.a,,.., , . _y,::.zc ,. - i....,. — 1, l I 1 i [ I E �y ZZs 1 °I... 55 f �. . .i.1 CL ltt t x15J .. `v�, is I F F F ) �c ¢Q I 1 t ' IU I I 1 a qj ,t t1 - of o } 1 11 tai \ zt c 10.00 I t I I 1 �..,, .., � i � E��- ��.*tiF F ,"�"q, ro � it_�,° } � E 7 -'----'t----,—, ,s ...-. �.,4- io " " ,ti,. N Y I 1 ¢ 1t s' I i l.. 4 I I 1 1 Ii i i I i 1l i 3 , 1 i; i 1 Witt t t i .1; i I 100 I ; _�.�� 1.00 10 ? _ _. ...... 10000 l00000 1000 Flow Rate—Litres/min. • \iiCtauliC victaulic.com 5 • Check Valve I Firelock® I Series 717 & 717H I Publication 10.08 Flow Characteristics The charts below express the flow of water at 60°F/16°C through valve. to .• 5717/717R I. a , t 1.l . �F � 1.q ' 1 i t' l 1 1 6 I I F .I -�, Ate$ = F,.o "..MFF -IFF .00;11) .m..• ,,n. t r I -j 1 t o t �bh I E\1� `ypF \ �~ ,ti tii# 1 1 1 y 1 9► : § a f l a t rl ¢ io. a � is :. , t. � ..I � � l t , 1 I#F t 0.1 i /t i Islii 10 100 1000 0 .0 fn _1 0 10000 100000 Flow—GPM 5717/717R 10 ..,N. 1,„ f t ',..... .?. l..v.. e , �. . ..' ' g Ia r.. .. # I i' C ,.. .#... 1 1. I't ,,,, F FF ��q h' � f ' u, 1 I;r�bh # tet a l ^tih hF S 1, p 1 I r t 0 1 . r'5 b\ w " d I 3 i I I f.; .# I }.. 1 t ` 1" 1" I, 4. I. .., ,1 0.1 ' ` I 1 II I # 1 # . lo 100 I ;_. . # .a 1000 . ..- 10000 100000 Flow—GPM Installation Reference should always be made to the 1-100 Victaulic Field Installation Handbook for Note the product you are installing.Handbooks are included with each shipment of Victaulic tothis inprstallectd l e accordance with current by VictaulicVictaulic or to Victaulic installation/assemblyasbin tr Allct products products for complete installation and assembly data,and are available in PDF format Victaulic be installed intheight changeh p teo , esigns n instructions. on our website at www.victaulic.com. reserves the right to product specifications,designs and standard equipment without notice and without incurring obligations. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic and FireLock are registered trademarks of Victaulic Company. • 10.08 1479 Rev.R Updated 05/2014 ©2014 Victaulic Company.All rights reserved. ✓ctaulic® victaulic.com 6 • FireLock® Buterfly Valve ✓Ctaul;c Style 705 with Weatherproof Actuator 10.81 Material Specifications: Body: Ductile iron conforming to ASTM A-536, grade 65-45-12 End Face, 2 —6"150— 150 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Seal Retainer, 8— 12"/2O0 —300 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Approvals/Listings: Coating: Black alkyd enamel c 4i us 44:› vds LPCB Disc: Ductile iron conforming to ASTM A-536, grade LISTED #G410001 104j104 65-45-12, with electroless nickel coating conforming to See Victaulic Publication 10.01 for more details. ASTM B-733 Seat: Product Description: 0 Grade "E" EPDM The Series 705 Butterfly Valve features a weatherproof Stems: 416 stainless steel conforming to ASTM A 582 actuator housing Approved for indoor or outdoor use, a ductile iron body and disc with EPDM seats. Designed Stem Seal Cartridge: C36000 brass for fire protection services only. Victaulic FireLock Series 705 Butterfly Valve is cULus Listed, LPCB Listed, Bearings: Stainless Steel with TFE lining FM and VdS Approved for 300 psi/2068 kPa service. Contact Victaulic for details of agency approvals. Stem Seals: EPDM Stem Retaining Ring: Carbon steel Actuator: ❑ 2—8"/50—200mm: Brass or bronze traveling nut on a steel lead screw, in a ductile iron housing ❑ 10— 12"/250—300mm: Steel worm and cast iron quadrant gear, in a cast iron housing Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date • victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. 1 �CtauliC victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Approvals and Listings: Approval/Listing Service Pressures Series 705 Butterfly Valve Size cULus FM Vds LPCB 2750 mm up to 300psi/2068kPa n/a up to 300psi/2068kPa up to 300psi/2068kPa 2W/65 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 76.1 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 3"/80 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 4"/100 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 5"/125 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 139.7 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 6"/150 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 165.1 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 8"/200 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 10"/250 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 12"/300 mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2ictaulac® victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Dimensions: I I (dWiiii) i�7ill • 0H mI I , lir I� 1 WIi f Ile \ ! B e �� 1 FJ-' J G E A 4-D NOTE:OPTIONAL 1/2"/15MM TAP AVAILABLE. CONTACT VICTAULIC FOR DETAILS. Actual Dimensions Nominal Outside E to E Size Diameter A B C D E F G DIA H J inches inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm mm mm mm mm 2 2.375 4.25 2.28 6.41 _ - 4.00 4.22 4.50 2.12 60.3 60.3 108.0 57.9 162.8 101.6 107.2 114.3 53.8 21 2.875 3.77 2.28 7.54 _ _ 4.00 4.22 4.50 1.77 73 73.0 95.8 57.9 191.5 101.6 107.2 114.3 45.0 3.000 3.77 2.28 7.54 _ _ 4.00 4.22 4.50 1.77 76.1 mm 76.1 95.8 57.9 191.5 101.6 107.2 114.3 45.0 3 3.500 3.77 2.53 7.79 _ - 4.50 4.22 4.50 1.77 88.9 88.9 95.8 64.3 197.9 114.3 107.2 114.3 45.0 108 mm 4.250 4.63 2.88 8.81 550 4.22 4.50 2.20 - - 108.0 117.6 73.2 223.8 139.7 107.2 114.3 55.9 4 4.500 4.63 2.88 8.81 _ _ 5.50 4.22 4.50 2.20 114.3 114.3 117.6 73.2 223.8 139.7 107.2 114.3 55.9 133 mm 5.250 5.88 3.35 10.88 _ 6.56 6.19 6.30 2.58 133.0 149.4 85.1 276.4 166.6 157.2 160.0 65.5 139.7 mm 5.500 5.88 3.35 10.88 - _ 6.56 6.19 6.30 2.58 139.7 149.4 85.1 276.4 166.6 157.2 160.0 65.6 5 5.563 5.88 3.35 10.88 _ _ 6.56 6.19 6.30 2.58 141.3 141.3 149.4 85.1 276.4 166.6 157.2 160.0 65.5 159 mm 6.250 5.88 3.84 11.38 - 0.41 7.52 6.19 6.30 2.58 159.0 149.4 97.5 289.1 10.4 191.0 157.2 160.0 65.5 165.1 mm 6.500 5.88 3.84 11.38 - 0.41 7.52 6.19 6.30 2.58 165.1 149.4 97.5 289.1 10.4 191.0 157.2 160.0 65.5 6 6.625 5.88 3.84 11.38 _ 0.41 7.52 6.19 6.30 1.90 168.3 168.3 149.4 97.5 289.1 10.4 191.0 157.2 160.0 48.3 8 8.625 5.33 5.07 13.53 0.80 1.47 10.00 6.19 8.10 2.33 219.1 219.1 135.4 128.8 343.6 20.3 37.3 254.0 157.2 205.7 59.2 10 10.750 6.40 6.37 15.64 1.41 1.81 12.25 8.10 9.00 _ 273 273.0 162.6 161.8 397.3 35.8 46.0 311.2 205.7 228.6 12 12.750 6.50 7.36 16.64 2.30 2.80 14.25 8.10 9.00 - 323.9 323.9 165.1 186.9 422.7 58.4 71.1 362.0 205.7 228.6 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ictaulic® victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: The chart expresses the frictional resistance of Victaulic Series 705 Butterfly Valve in equivalent feet/ meters of straight pipe. Nominal Outside Equivalent Size Diameter mm mm Feet/m inches inches of pipe 2 2.375 6 50 60.3 1.8 2' 2.875 6 65 73.0 1.8 76.1 mm 3.000 6 76.1 1.8 3 3.500 7 80 88.9 2.1 4 4.500 8 100 114.3 2.4 108 mm 108 mm 8 2.4 5 5.563 12 125 141.3 3.7 133 mm 133 mm 12 3.7 139.7 mm 5.500 12 139.7 3.7 6 6.625 14 150 168.3 4.2 159mm 159mm 14 43 165.1 mm 6.500 14 165.1 4.2 8 8.625 16 200 219.1 4.9 10 10.750 18 250 273.0 5.5 12 12.750 19 300 323.9 5.8 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic' victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: • C,values for flow of water at+60°F/+16°C through a fully open valve are shown in the table below. For additional details, contact Victaulic. Formulas for lc values Formulas for C,values Where: AP=Q2/K„2 Where: AP=Q2/Cv2 Flow Factor Ks, Flow Coefficient C Q=K„x,/AP m3/hr Q=C xVAP Q(Flow) Q(Flow) GPM AP(Pressure) bar AP(Pressure Drop) psi Valve Size Full Open Valve Size Full Open Actual Actual Nominal Outside Nominal Outside Flow Coefficient Size Diameter Flow Coefficient Size Diammeteter inches inches K inches inches c mm mm mm mm 2 2.375 147 2 2.375 170 50 60.3 50 60.3 225 2' 2.875 2 Y� 2.875 260 65 65 73.0 73.0 3.000 3.000 260 76.1 225 76.1mm 76.1 76.1 mm 0 380 3 3.500 440 80 3 3.50.50 80 88.9 4 4.500 88.9 820 4 4.500 710 100 114.3 100 114.3 108mm 108mm 820 108mm 108mm 710 5 5.563 1040 5 5.563 1200 125 141.3 125 141.3 133mm 133mm 1200 133mm 133mm 1040 139.7 mm 5.500 1040 5.500 200 139.7 mm 139.7 139.7 1560 6 6.625 6 6.625 1800 150 168.3 150 168.3 159 mm 159 mm 1800 159 mm 159 mm 1560 165.1 mm 6.500 1560 6.500 1800 165. 165.1 mm 165.1 1 8 8.625 2940 8 8.625 3400 200 219.1 200 219.1 10 10.750 5020 10 10.750 5800 10 273.0 250 273.0 12 12.750 12.750 7790 30012 9000 300 323.9 323.9 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. Ct'dU�iC victaulic.com 5 VV victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Switch and Wiring: UL LINED ` JUNCTIONN B� 1. The supervisory switch contains two singlepole, CONDUIT '�� g double throw, pre-wired switches. /'- � .- /�'NPT 2. Switches are rated: i®i CONDUIT CONNECTORS 10 amps @ 125 or 250 VAC/60 Hz WIRE 0.50 amps @ 125 VDC 0.25 amps 250 VDC FIRE ALARM TEND-OF-LINE RESISTOR, CONTROL PANEL OR NEXT INDICATORO SUPERVISORY CIRCUIT 3. Switches supervise the valve in the "OPEN" position. NO COM SWITCH CONTACT RATING: _ 5. One switch has two#18 insulated wires per terminal, 10A AT , IME ' 2SUSOC. which permit complete supervision of leads (refer OUT0 SA AT 125 D 0.25 AT 250 VDC _ BELL , to diagrams and notes below). The second switch OR VOLTAGE SOURCE HORN has one#18 insulated wire per terminal. This double circuit provides flexibility to operate two electrical sw"`h':,lea°pertermina devices at separate locations, such as an indicating light and an audible alarm, in the area that the valve NOTE: The above diagram shows a connection between is installed. the common terminal (yellow—Si and yellow-with- 6. A#14 insulated ground lead (green) is provided. orange stripe—S2) and the normally closed terminal (blue—S1 and blue-with-orange stripe—S2). In this Switch #1 = S1 example, the indicator light and alarm will stay on until the valve is fully open. When the valve is fully open, the For connection to the supervisory circuit of a UL indicator light and alarm will go out. Cap off any unused Listed alarm control panel wires (e.g. brown with orange stripe). Switch #2 = S2 Only S1 (two leads per terminal) may be connected to Auxiliary switch that may be connected to auxiliary the fire alarm control panel. devices, per the authority having jurisdiction The connection of the alarm switch wiring shall be in Normally Closed: (2) Blue accordance with NFPA 72 and the auxiliary switch per s1 NFPA 70 (NEC). Common: (2) Yellow Normally Closed: Blue with Orange Stripe S2 Normally Open: Brown with Orange Stripe Common: Yellow with Orange Stripe Installation Reference should always be made to the 1-100 Victaulic Field Installation Handbook for Note the product you are installing.Handbooks are included with each shipment of Victaulic toThis installedpduct shall accordance manufactured wcurrent by Victaulic or to Victaulic specifications.selynsAll products products for complete installation and assembly data,and are available in PDF format Victaulic be inthe ight changeh p Victaulic einstallation/assembly designs an instructions. on our website at www.victaulic.com. reserves the right to product specifications,designs and standard equipment without notice and without incurring obligations. Warranty kRefer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic is a registered trademark of Victaulic Company. 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctaulicg FireLock NXTTM Dry Valve 4tauiicr Series 768 30.80 ty Patent Pending Certifications/Listings: c al us ® LPCB C( 104f/01 0832 MEA:248-98-E See Victaulic Publication 10.01 for more details. Product Description: The patent-pending Victaulic Series 768 FireLock NXT Dry Valve is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from dry-pipe sprinkler systems. 'see page 12 for European trim Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. 1 �CtauIict ' victau_lic,com I NXT Dry Valve I Series 768 I Publication 30.80 , Features: The low differential, unique latch and actuator design of the valve allows the valve to be reset without opening the valve. The low differential design is not subject to water columns. The valve allows the water to operate a water Clapper �_` motor alarm and/or electric pressure alarms, which ,�� ``•�� Latch continue until the flow of water stops. With the optional ��t� �� �;� accelerator, the valve can be configured to respond � 0 �� faster for use in larger systems, or where faster response .; �i times are required. ,•. Diaphragm The valve is rated to 300 psi/2065 kPa water working l�'J ������� Assembly .,.;!'� ,��� pressure and is factory tested hydrostatically to 600 psi/ ��� 4135 kPa for sizes 1 l/—8740—200 mm. VdS trim Clapper Seal ��/ configurations are approved to 16 BAR (see page 12). ,I ` Seat Required air pressure for all trim variations is 13 psi/ 90 kPa. The Series 768 is available grooved x grooved. Exaggerated for clarity Standard grooved dimensions conform to ANSI/AWWA Note:Valve is shown in the"set"position C606. The Victaulic Series 768 FireLock NXT Dry Valve is made of high-strength, low-weight ductile iron, and it offers easy access to all internal parts. All internal parts are replaceable. Maintenance and service can be performed without removing the valve from its installed position. The rubber clapper seal is replaced easily without removing the clapper from the valve. The valve is painted inside and out to increase corrosion resistance. The body is tapped for main drain and all available trim configurations. Installation Options The Victaulic Series 768 FireLock NXT Dry Valve is available bare, or in the following configurations: Pre-trimmed The pre-trimmed valve comes completely assembled with all necessary trim components. Vic-Quick Riser The Vic-Quick Riser comes completely pre-trimmed and includes a shut off valve (uses a Series 705W FireLock Butterfly valve— request publication 10.18; for 1 l and 2"/40 and 50 mm sizes, the Vic-Quick Riser comes with a Series 728 Ball Valve— request publication 10.17) for system shut off, pre-set pressure switches, and a drain kit for ease of installation. For complete Vic-Quick Riser information request publication 30.20. Series 745 FireLock Fire-Pac (Available in North America only) The Fire-Pac is a completely pre-assembled fire protection valve that provides maximum service in a minimal enclosed space. The unit includes a water supply shutoff valve, the sprinkler system fire protection valve, alarm line pressure switches, air supervisory pressure switches, supervisory pump switches, and digital pressure gauges that are easily viewed through a window in the cabinet door. For complete Fire-Pac information request publication 30.23. Optional accessories ship separately. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 2 NiCtaulic. victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Dimensions: The 4 Inch/114.3 Mm UI Listed, FM Approved Configuration Is Shown Below 11/2-2"/48.3-60.3 mm Configurations Contain 3/4"/19 mm Drain Valves. 2 Y2-3"/73.0-88.9 mm Configurations Contain 1 1/4"/31 mm Drain Valves. 4-8"/114.3-219.1 mm Configurations Contain 2"/50 mm Drain Valves. ItI a:oil n �zya E fa-MINAIIMaiii 1-111:7111,1 pri rr-i, ^ nMEOW r-1 I II -tlitifiton-c---1'-----fr , I I i i II�_�III � D *Di � �� � u-1 �Li iii� '-Im.����� it I 1r' I,------ 11 i �_-1111 �1�1� � ��.Ili _ �r r]T. 1\� ill ' '• ` �t��+ III rJl� III.o` •y.J = 6F jl� , - V A B i ill *Al �( BOJ �;� �� rrT it �I[COs-jam �,i��l��Ijj-•`J o l I,:.-JI i i iiiii010° 41'1'4' 1 LI-II 1 - __aI I :_ =:• � 10111Militilla mom� H '(----- K C *E1 Full Open Approx. Weight Each Dimensions Without With Actual Trim Trim Nominal aEl F G H J K Bl C D Dl E Size DiameterncheA Al B bs inches inches inches inches inchesnminches inchesmminches inches inches incmhms inches inches inches inches inches Ikgs lbs. mm mm mm mm 5.25 8.50 2125 3.04 9.17 6.98 43.0 1 Y2 1.900 9.00 16.35 27.25 39.50 13.75 16.00 - 133 . 05 9.50 539 77.21 232.91.116.989 16.77. 19.50 40 48.3 228.60 415.29 692 1003 349 40619.5 2 2.375 9.00 13.37 27.25 39.50 13.75 16.00 125 2150 9.50 41 21.25539 3.4 232.91.17177.29. 1j. 43.0 50 603 228.60 339.60 692 1003 349 406 a 02 18 7 29.5 2 2.875 12.61 16.50110 32.25144.25 1123 1342 16.00 406 1444 133 228 234 21.25 3.90 10.50 6.93 99 06 266.70 176 0 41.0 65.0 65 73.0 320.29 3.000 12.61 41910 38195 1123 1342 0 1406 0 1444 0 13355 92.2080 92.3245 2513.295 99 06 265.0 665 0 176 02 18.07 29.5 3 .5.1 320.29 133 228 234 539 99.06 266.70 176.02 18.7 29.5 3 3.500 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0 80 88.9 320.29 419.10 819 1123 342 406 444 95.0 4 4.503 519.8303.68 383.50 45.5050 1155 13810 15 75 400 20.50 5.25 9.00 520 133 228 12735 2533 158.75 244.34 8.46 26.07 43 0 100 114.14.3 381.781.7 6 6.500 16.00 55 0800 3863 1168 15.50 17.0043122.005585.25 8 50 133 215 1292 20.50 6.20 9.62 8.84 157 48 244.34 224.53 36.02 116.0 =I 52 6 165. 06 40 1.50 16.0 6 16.00 6 6.62568. 406.400 34.008611600 8 15.50 393 17.0043122.00 5.25 8.50 558 133 215 1292 2520 157.48 244.34 22453 36.02 152.6 1501 10.21 .0 517.50 560.07 8 8.62519.1 4 5 0 23 00 584.20 33.50 1155 16.75 425 20.0050825.25641158 222 12.75 323 1469 153 67 23876 259.33 122.055. 1718.6 200 219.1 444.5 NOTES: The"A"dimension coupling is not shown in order to clarify dimensional callouts. Components shown as dotted lines denote optional equipment. *Measurements denoted with an asterisk take optional equipment into account. Optional drain connection kit is shown for reference and takeout dimensions. reserved. �CtaU_ rights 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All ri g 3 __ victau lic•com . victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Performance: Hydraulic Friction Loss The chart below expresses the flow of water at 65°F/18°C through a full open valve. 6.0 5.0 .' 4.. - r „Y-: 4.0 4 '.M1'4‘ ! ri H y t.. F t ' F o s } a ',e, i.4,'ry\eh e o M� b\ �oF f a 0.9 Y ,_r p 0.8 r 1. r r- --i p,6 Y 1 F ( t {F d ; , 1 a t 1 i ;• I E f_ 0.2 r� }. , 1 I i 1 , t .. I 10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 20,000 800 3,000 8,000 FLOW RATE-GPM Frictional Resistance The chart below expresses the frictional resistance of Victaulic Series 768 FireLock NXT. Dry Valve in equivalent feet of straight pipe. Actual Equivalent Nominal Outside Length of Size Diameter Pipe inches inches feet mm mm meters 11/2 1.900 3.00 40 48.3 0.914 2 2.375 9.00 50 60.3 2.743 21/2 2.875 8.00 65 73.0 2.438 3.000 8.00 76.1 mm 76.1 2.439 3 3.500 17.00 80 88.9 5.182 ' 4 4.500 21.00 100 114.3 6.401 6.500 22.00 165.1 mm 165.1 6.706 6 6.625 22.00 150 168.3 6.706 8 8.625 50.00 200 219.1 15.240 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. �CtaU�iiC victaulic.com 4 victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Cv Values: Operation: - C,,values for flow of water at+60°F/+16°C through a fully The Series 768 Dry Valve contains a clapper, which has open valve are shown in the table below. a replaceable rubber seal. The clapper makes contact with the valve's seat ring, which has access Formulas for C,values Where: holes leading into an intermediate chamber in the valve. AP=Q2/C„2 Flow Coefficient c, The diaphragm contacts the latch, and the latch holds Q=cv x VAP Q(Flow) GPM the clapper closed. AP(Pressure Drop) psi In the closed position, the valve diaphragm is maintained in the extended position by the water supply pressure from upstream of the water supply control valve. The diaphragm latch holds the clapper in the closed position. The Series 776 Low Pressure Actuator (LPA) maintains Valve Size Full Open the water, and the system's air pressure controls the Actual LPA. Required air pressure is 13 psi/90 kPa. The design Nominal Outside of the 776 actuator does not require the traditional air Size Diameter Flow Coefficient cushion of 10—20 psi/69— 138 kPa. Excess air inches inches Kpressure above 13 psi/90 kPa will cause a delay in valve 1, 1.900 60 operation. 40 48.3 52.0 Once the system's air pressure reduces to the trip point, 50 2.375 950 the LPA opens and allows the water supply pressure in 2% 2.s75 180 the diaphragm to release (i.e. an open sprinkler). This 65 73.0 156.0 release allows the latch to move to its open position, 76.1 mm 56 7000.11 800 permitting the clapper to pivot freely, thus allowing water into the system. 3 3.500 200 80 88.9 173.0 Water enters the intermediate chamber of the valve 4 4.500 iso through the holes in the seat ring. The water flows from loo 11x.3 302.s the intermediate chamber to the alarm line, which 165.1 mm 6.500 1000 y 165.1 865.0 activates the system's alarms. The alarms continue to 6 6.625 1000 sound until the flow of water stops. 150 168.3 865.0 When the flow of water stops, the spring-assisted valve 28 00 219.1 1499.1 25 1500 clapper returns to the closed position. The valve acts as an alarm check valve until the system is back in service as a dry system, according to the proper procedure. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 5 ✓Ctaulic° ' victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 . Material Specifications: Body: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Clapper: Aluminum bronze UNS-C95500 Latch: Aluminum bronze UNS-C95500 Shaft: Stainless 17-4 Clapper Seal: Peroxide cured EPDM, ASTM D2000 Bushings/Seat 0-rings: Nitrile Springs: Stainless Steel (300 Series) Diaphragm: Peroxide cured EPDM with fabric reinforcement Bill of Materials 1 Valve Body 12 Cover Plate 2 Clapper 13 Cover Plate Gasket 3 Clapper Seal 14 Cover Plate Bolts" 4 Seal Ring 15 Latch 5 Seal Washer 16 Latch Spring 6 Seal Retaining Ring 17 Latch Spring Bushing and 0-ring(Qty.2) 7 Seal Assembly Bolt 18 Diaphragm 8 Bolt Seal 19 Diaphragm Cover 9 Clapper Spring 20 Diaphragm Cover Cap Screws(Qty.8) 10 Clapper Shaft 21 Latch Shaft 11 Clapper Shaft Bushing and 0-ring(Qty.2) 40 0 •(-'.,,:-.4 .,_ N. „ s„,_,_, (fito. LCD (4,4 4,0, . it i-k 4D i - °' ° 0 ..% -----1 -----......-- 4„,,,,,_ .. - vcip .1).-,-----'''..1,L111)1\ ° : 4.°7 > ' 0 (P'4P m .i, 0 O *NOTE:The 111-inch/48.3-mm and 2-inch/60.3-mm valve sizes contain washers under the heads of the cover plate bolts. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctaulic' victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Trim Package Details: • Air Compressor (See page 8 for more on the Victaulic Series 7C7 Compressor Package) Trim Packages: • Air Maintenance Trim Assembly NOTE: See page 11 for details of trim and page 12 for details of European trim. • Alarm Panels 1 Galvanized components. • Drain Connection Kit 2 Series 776 Low-Pressure Actuator—The Series 776 Low-Pressure Actuator is pneumatically actuated and requires only 13 psi/90 kPa minimum air Air Supply Requirements: pressure, regardless of the system supply pressure. This actuator allows the system to operate with a low The required air pressure for Series 768 FireLock NXT Dry Valves is 13 psi/90 kPa minimum, regardless of the air or gas pressure of 7 psi/48 kPa. system supply water pressure. Air pressures should be 3 All Required Pipe and Fittings. kept below 18 psi/124 kPa, unless a Series 746-LPA 4 All Standard Trim Accessories. Dry Accelerator is installed. Systems with air pressures higher than 18 psi/124 kPa may require the addition of a 5 All Required Gauges Series 746-LPA Dry Accelerator. Optional Trim Package: If multiple Series 768 FireLock NXT Dry Valves are 1 Black Trim for Foam Systems— If the valve is installed with a common air supply, isolate the systems with a spring-loaded, soft-seated ball check valve to intended for use in a foam system, black trim must be ordered, per NFPA requirements. Specify this ensure air integrity for each system. Good practice is requirement on the order. to include a ball valve for isolation and service of each individual system. The engineer/system designer is responsible for sizing Optional Accessories: the compressor so that the entire system is charged to • Series 746-LPA Dry Accelerator—The Series the required air pressure within 30 minutes. DO NOT 746-LPA Dry Accelerator is required when the oversize the compressor to provide more airflow. An Series 768 Dry Valve is installed in large systems to oversized compressor will slow down or possibly prevent improve response time. Request submittal 30.64. valve operation. If the compressor fills the system too fast, it may be • Series 760 Water Motor Alarm—The Series 760 necessary to restrict the air supply. Restricting the air Water Motor Alarm is a mechanical device that supply will ensure that air being exhausted from an open sounds when a sustained flow of water occurs (such sprinkler or manual release valve is not replaced by the as with an open sprinkler). Request submittal 30.32. air supply system as fast as it is being exhausted. • Series 75B Supplemental Alarm Device—The Series 75B Supplemental Alarm Device is designed to provide a continuous alarm for systems equipped with a mechanical device. Request submittal 30.33. • Series 75D Water Column Kit—The Series 75D Water Column Kit is designed to minimize residual water in the riser from collecting above the clapper. Request submittal 30.34. • Alarm Pressure Switch —Alarm Pressure Switches are designed to activate electrical alarms and control panels when a sustained flow of water occurs (such as with an open sprinkler). • Air Supervisory Pressure Switch—Air Pressure Supervisory Switches are used to monitor low system air pressure and are factory pre-set. • Air Supply System —The air supply system contains all components for establishing and maintaining air in the system. The compressor, low-pressure alarms, ball valves, and required trim are included in the air supply system. • 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. �CtaUlilC victaulic.com 7 victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Compressor Sizing: COMPRESSOR REQUIREMENTS 12 20 psi/138 kPa i I I 13 psi/90 kPa ` 10 i V -- W 00CC -- '' Ce i 00 I 00 ' w in m o w 5 m 0 0 0 0 0 0 0 SYSTEM CAPACITY(in gallons) Base or Riser-Mounted Compressors: Shop Air or Tank-Mounted Air Compressors: For base or riser-mounted compressors, the recom- In the event a compressor becomes inoperative, a mended air pressure of 13 psi/90 kPa is the "on" or properly sized tank-mounted air compressor provides "low" pressure setting for the compressor. The `off" the greatest protection for systems. or "high" pressure setting should be 18 psi/124 kPa. When shop air or a tank-mounted air compressor is Victaulic offers the Series 7C7 Compressor package used, the Series 757 Regulated AMTA must be installed. for FireLock NXT devices which is riser-mounted and The Series 757 Regulated AMTA provides proper air pre-set for the FireLock NXT pressure requirements as regulation from the air reservoir to the sprinkler system. stated above. For information on the Series 7C7 package, consult publication 30.22. The Series 7C7 For tank-mounted air compressors, the recommended Compressor package is only available in North America. air pressure of 13 psi/90 kPa should be used as the set point for the air regulator. The "on" pressure of the When a base or riser-mounted air compressor supplies compressor should be at least 5 psi/34 kPa above the air to a Series 768 FireLock NXT Dry Valve, it is not set point of the air regulator. necessary to install the Victaulic Series 757 Regulated Air Maintenance Trim Assembly (AMTA). In this case, the airline of the compressor connects to the trim at the fitting where the Series 757 Regulated AMTA is normally installed (refer to the applicable trim drawing). If the compressor is not equipped with a pressure switch, the Series 757P Air Maintenance Trim Assembly with Pressure Switch should be installed. For information on the Series 757 Regulated Air Maintenance Trim Assembly, see publication 30.35. For information on the Series 757P Air Maintenance Trim Assembly, see publication 30.36. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 8 i9tauliC® victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Series 757 Regulated Air . Maintenance Trim Assembly: • Victaulic recommends a maximum of two Series 768 FireLock NXT Dry Valves per Series 757 Regulated AMTA Bill of Materials I 1 1/2"13.2 mm Restrictor 2 Slow Fill Ball Valve(Normally Open) 3 Air Regulator 4 Strainer(100 Mesh) 0'?5' •• 5 Spring-Loaded,Soft-Seated /� Ball Check Valve 0 Nd �7 0 6 Fast Fill Ball Valve(Normally Closed) ui 0 �; © ,-,-1 0 'sig .0, 416 si✓1 0 Exaggerated for clarity Series 757P Air Maintenance Trim Assembly With Pressure Switch: • Victaulic recommends a maximum of two Series 768 FireLock NXT Dry Valves per Series 757P AMTA with Pressure Switch Bill of Materials 0 `.,, Item Qty. Description I \% 1 1 Restrictor(1h-inch NPT) # m 2 1 Strainer(1/cinch NPT) O - 3 1 Swing Check(1/2-inch NPT) 4 1 Slow-Fill Ball Valve T v p-c) (Normally Open) 5 1 Spring-Loaded,Soft-Seated Check Valveq9, rs1 9 6 1 Pressure Switch 7 2 Compression Fitting,Straight (1/4-inch NPT x 1/4-inch Tube) %4 0 8 1 Copper Tubing(1/4-inch OD) ® 1 q. 9 11 Close Nipple 1 lr (1h-inchNPT x 1.13) �� 0 10 1 Nipple(1/2-inch NPT x 4.00) 11 1 90°Female Elbow(1/2-inch NPT) % 12 4 Female Tee(Y-inch NPT) 13 3 Union(1h-inch NPT) k(Z21, 04.14 2 Reducing Bushing1s:G_ (1/2-inch NPTx 1/4-inch NPT) �' 4. 15 1 Fast Fill Ball ValveP.•• (Normally Closed) �`" 0 c 16 1 Pressure Switch Isolation Ball © 0 �' la, y- Valve(Normally Open- ' Lockable) / FROM V( COMPRESSOR ,4 TO SYSTEM Exaggerated for clarity 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 9ictaulic® victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Compressor Requirements: Remote System Test Valve Requirements Compressor Requirements and Settings for Series 768 The remote system test valve (inspector's test connection) FireLock NXT Dry Valves Installed with Series 746-LPA should contain a UL Listed and/or FM Approved valve Dry Accelerators (normally closed), which can be opened to simulate the Set the air regulator of the Series 757 Regulated AMTA operation of a sprinkler. to 13 psi/90 kPa. The remote system test valve (inspector's test connection) THE SERIES 757P AIR MAINTENANCE TRIM should be located at the most hydraulically ASSEMBLY WITH PRESSURE SWITCH MUST NOT BE demanding location in the release system. USED ON A SERIES 768 FIRELOCK NXT DRY VALVE NOTE: Multiple restrictions on the remote system test INSTALLED WITH A SERIES 746-LPA DRY valve (inspector's test connection) may slow the air ACCELERATOR. decay rate and cause the system to respond slower than required. When a Series 768 FireLock NXT Dry Valve is installed with a Series 746 LPA Dry Accelerator, the Series 757 The remote system test valve (inspector's test connection) Regulated AMTA must be used. NOTE: The use of an air should terminate with an orifice equal to the regulator with a base or risermounted compressor could smallest orifice in the releasing system. cause short cycling, resulting in premature wear of the The remote system test valve (inspector's test connection) compressor. is used to ensure that water reaches the most remote In the event a compressor becomes inoperative, a part of the system within 60 seconds. properly sized tank-mounted air compressor provides the greatest protection for systems installed with a Series 746-LPA Dry Accelerator. In this situation, air can be supplied continuously to the sprinkler system for an extended time period. NOTE: The Series 757 Regulated AMTA must be used with a tank-mounted air compressor or shop air system that continually supplies air to a Series 768 FireLock NXT Dry Valve installed with a Series 746-LPA Dry Accelerator. The air regulator of the Series 757 Regulated AMTA is a relief-type design. Any pressure in the system that is above the set point of the air regulator will be released. Therefore, charging the air regulator above the set point could cause premature operation of a valve installed with a Series 746-LPA Dry Accelerator. NOTE: The series 746-LPA should not be used above 30 psi. If higher pressures are required, the series 746 should be used. Settings for Air Supervisory Pressure Switches and Alarm Pressure Switches Air supervisory pressure switches are required for dry systems and must be set according to the following instructions. NOTE: Switches for Vic-Quick Risers are pre-set at the factory. Wire the air supervisory pressure switches to activate a low-pressure alarm signal. NOTE: In addition, the local authority having jurisdiction may require a high-pressure alarm. Contact the local authority having jurisdiction for this requirement. Set the air supervisory pressure switches to activate at 2—4 psi/14—28 kPa below the minimum air pressure required, but not lower than 10 psi/69 kPa. Wire the alarm pressure switch to activate a water flow alarm. Set the alarm pressure switch to activate on a pressure rise of 4—8 psi/28— 55 kPa. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 10 ictaulic@ victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Exploded View Drawing— • Trim Components ( c us ® Trim) LISTED Series 768 FireLock NXT Dry Valve (Optional Accessories Also Shown) Bill of Materials 1 Series 768 FireLock NXT Dry Valve 2 FireLock Rigid Coupling(Optional/ O Sold Separately-Comes Standard when VQR Assembly is Ordered) Va 3 Water Supply Main Control Valve From System / (Optional/Sold Separately-Comes AirFeea--Ak r.� ` 0 Standard when VQR Assembly is Ordered) _ 4 Drain Swing Check Valve - 5 Drip Cup with Cap ) 6 Alarm Pressure Switch(Optional/Soldr�i i-- Separately-Comes Standard when VQR �p ii Assembly is Ordered) ,e/ ® I/' Location 7 Series 729 Drip Check Valve 0 8 Diaphragm-Charge-Line Ball Valve i (Normally Open) -- — .i �1��; 9 3-in-1 Strainer/Check/Restrictor i h,��? i / i �.�� Assembly i I■lll i �;, 0 y 10 Series 760 Water Motor Alarm za '!i! t` (Optional/Sold Separately) 23 ' ,\ 1 01110. ��,'-� 11 Alarm Test Ball Valve m R 01 J ` 3 '• 12 Diaphragm-Charge-Line Pressure ) go i oDrip Cup Gauge(0-300 psi/0-2068 kPa/0-20.7 Bar) �� '1° �4 ToDnppCup Location `' �W41 ,_�� Location 13 Series 749 Auto Drain ®0' i . O O 14 Series 746-LPA Dry Accelerator \, O� Assembly(Optional/Sold Separately) =' 0 i r,'„ 15 Series 776 Low-Pressure Actuator �� t -w' To 16 Air Manifold System 17 Air Supervisory Pressure Switch Notet \,\ :; (Optional/Sold Separately-Comes I\- \• Standard when VQR Assembly is Ordered) m . ' \ \- 0 / 18 System Pressure Gauge . \\, \,, 011111*--,...m....-------...-, - BEY (0-80 psi/0-552 kPa/0-5.5 Bar with Retard) t� •,\ �� 19 Water Supply Main Drain Valve- ® O� 4�►��, \ I�t��� Flow Test (CO � ' ;R m 20 Water Supply Pressure Gauge ,f� \ \` (0-300 psi/0-2068 kPa/0-20.7 Bar) �.� ° �. „... / Imo' >>►./ 21 Drain Connection Kit(Optional/Sold ��`—\ � � F' F%i �'�' Separately-Comes Standard when VQR V ,11,•, p Assembly is Ordered) �- 1 \ r 22 Gauge Valve -� �i 23 System Main Drain Valve n .��`�� 24 Series 748 Ball Check Valve (� ® e1/ i u h f' 0 r 7411�.+, l ' ITo Drip Cup .• �__ __, -�1 Lootion From Water Supply Exaggerated for clarity Optional devices include the Series 75D Water Column Device Kit and the Series 75B Supplemental Alarm Kit. NOTE 1:Connection point for the Series 75D Water Column Device Kit. For installation of the Series 75B Supplemental Alarm Device,refer to the instructions supplied with the product. • 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 11 ictaulic victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Exploded View Drawing— Trim Components: (European Trim: cal us ® LPCB (( 0 of, MEA:248-98-E 104f/01 0832 Series 768 FireLock NXT Dry Valve (Optional Accessories Also Shown) Bill of Materials 1 Series 768 FireLock NXT Dry Valve O� 10 2 FireLock Rigid Coupling(Optional/Sold Separately–Comes Standard when VQR Assembly is Ordered) �✓V 0 From System `, I 3 Water Supply Main Control Valve(Optional/ Air Feed ( '.:1 0 Sold Separately–Comes Standard when VQR ':1 I Assembly is Ordered) 4 Drain Swing Check Valve m I I '/ 5 Drip Cup with Cap L J 6 Alarm Pressure Switch(Optional/Sold t4 Separately–Comes Standard when VQR I ,� Location ? r Assembly is Ordered) 'P 7 Series 729 Drip Check Valve 8 Diaphragm-Charge-Line Ball Valve rt." /- L� 'N (Normally Open) 1 ,,,, 9 3-in-1 Strainer/Check/Restrictor 4 f0 Assembly ® ® / ;1' © /� 10 Series 760 Water Motor Alarm J I �� I 3 TO Datsun ` (Optional/Sold Separately) "i♦ lino To Drip �oOn 11 Alarm Test Ball Valve ® o-�� �/•-V0• I , � I� Cal c°p ��yypp A -,%,,, !'� Location 12 Diaphragm-Charge-Line Pressure .. 01 Gauge(0–300 psi/0–2068 kPa/0–20.7 Bar) �``''' 6 �� �, 13 Series 749 Auto Drain �� t 14 Series 746-LPA Dry Accelerator Note 1 \ Syne" I �' ., / Assembly(Optional/Sold Separately) \ 15 Series 776 Low-Pressure Actuator ® \ t T ® �f...,X) 16 Air Manifold = 17 Air Supervisory Pressure Switch(Optional/Sold '�, 7 I \ �� # /� Separately–Comes Standard when VQR z) ©1 ,%1• \ IEl Assemblyis Ordered) ,..--›111okf 18 System Pressure Gauge fila? m 11111\` , »���'� (0–80 psi/0–552 kPa/O–5.5 Bar with Retard) V �- :cie—i 0 ``� �'c• t''',, �' II `•�t 19 Water Supply Main Drain Valve– I �/ 6'^'`` Flow Test 6 20 Water Supply Pressure Gauge I —_ ..4„ , 25 (0_300 psi/0–2068 kPa/0–20.7 Bar) L.- 21 Drain Connection Kit(Optional/Sold Separately–Comes Standard when VQR Oz I m'1, ToDrip I I Assembly is Ordered) cup s 22 Gauge Valve -� Location 23 System Main Drain Valve ♦i 6 24 Series 748 Ball Check Valve �Cv� ,� \ A25 Water Motor Alarm Shutoff Valve ® r ;/r, err/ J (Normally Open)* -11)c- 'Item 25,water motor alarm shutoff valve,can be closed to prevent water from flowing into the Series 760 Water Motor alarm during conditions that are not favorable for the alarm to sound(i.e during a trip test). From Water Supply • 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 12 ✓Ctaiulic' 4 victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 k • This product must be installed by an experienced,trained installer, in accordance with the instructions provided with each valve.These instructions contain important information. 4 Failure to follow these instructions may result in serious personal injury, property damage, or valve leakage. If you need additional copies of this product literature or the valve installation instructions, or if you have any questions about the safe installation and use of this device, contact Victaulic Company, P.O. Box 31, Easton, PA 18044-0031 USA, Telephone: 001-610-559-3300. InstallationNote Reference should always be made to the appropriate Installation,Maintenance,and This product shall be manufactured by Victaulic or to Victaulic specifications.All products Testing Manual included with each shipment of Victaulic products.These manuals are also be installed in the r anht eo with current proVictaulic instaionsodesignsbind stnainstructions.y available in PDF format on our website at victaulic.com equipment without notice and without incurring obligations. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks and FireLock®are registered trademarks of Victaulic Company. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. �CtaUliC victaulic.com 13 IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS • FireLock® Devices Air Maintenance Trim Assembly SERIES 757 PROPER AIR SUPPLIES FOR SERIES 1. When a riser or base mounted air compressor is being used to supply air to a dry valve or preac- 756/SERIES 758/SERIES 768/SERIES769 tion system it is not necessary to use the air maintenance trim assembly with the air regulator. In this ACTUATED VALVES: circumstance the air line of the compressor is connected to the valve trim at the fitting into which the Air Maintenance Trim is normally installed. When the valve is used with this setup it is the engineer/system designer's responsibility to size the compressor so that the compressor brings the entire system to the required pressure in 30 minutes. The compressor must not be oversized to provide more air flow as this will slow down or possibly prevent the operation of the valve. It must further be emphasized that the base mounted compressor does not provide any backup air to the system and that continuous service(24 hours per day, 7 days per week)must be maintained in order to prevent the potential of false tripping of the valve due to loss of air pressure. Additionally,due to the large on/off differential available on pressure switches that control base mounted compressors,the compressor pressure switch must be adjusted so that the"ON" contact of the pressure switch is set a minimum of 5psi higher than the set point of the regulator. 2.When shop air or a tank mounted air compressor is being used,the Air Maintenance Trim Assembly(AMTA)must be used.The AMTA is designed to provide the proper air regulation to the sprinkler system which will assure the proper operation of the Fire Safety Valve. In the event of a compressor becoming inoperative the tank mounted air compressor provides the greatest protection.With a properly sized tank,air can be continuously supplied to the sprinkler sys- tem for an extended period of time even with a loss of compressor. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 13IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII WCAS-7MYM68 For complete contact information,visit www.victaulic.com 30.35 2515 REV D UPDATED 1/2009 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. jctaUI1a 30.35 I'm also available In a BASEPLATE Ly UNIT C AIRE . _ 1IIIIIJllhl'! ° 1!1 COMPRESSORS .. ( !''p,l� , .. 4, --. „,, ..,.._S300 . . .PRODUCT NUMBERING SYSTEM S300, H - SD1 -,i 1 5 „ , 1.5 HP 1 it 1 l I Ll SYSTEM CAPACITY MOUNTING OPTIONS SERIES PHASE VOLTAGE ADDITIONAL OPTION 8 CFM M 115 a,.ailaokmssoo P.Prewired Power Cord ® i HD BH Baseplate HD:Heavy Duty 1:Single Phase ane:mailed 175 300 H:Horizontal Tank SD:Standard Duty 3:Three Phase 230(zoan3a) S:Prewired Magnetic Starter 265 2000 V:Vertical Tank 460 U:30-40psi Pressure Switch 325 {err on SSW and larger) (Also available in PU and SU) 500 300 GAL. MAX CAP. 750 1 900700 1300 *Greyed out options do not apply to this unit *S300H-SD1-115 is a stocked item 27" x 12" x 22" ■ SPECIAL ORDER OPTIONS: SINGLE PHASE ("� (�(� 1 Phase:115v/200v/230v VOLTS AMPSS.F.En . 70 100 PSI -3 Phase:200v/230v/460v 208 H 1.0 -Power Cord 230 IIII 1.0 v^,� -3 Phase Starter THREE PHASE 85 LBS• 30-40 PSI Pressure Switch VOLTS AMPS S.F. -Horizontal or Baseplate Mount 208M® 230 M® 1/2" MPT ■ DON'T FORGET YOUR INSTALLATION KIT! 460 ®® 'C ' The Advantage 26549 Fallbrook Avenue,Wyoming,MN 55092//800.762.2247//651.462.3440//www.c-aireinc.com Spare Sprinkler Head Storage Cabinet Description Fire Protection Products, Inc. Spare Sprinkler Head Cabinets are designed to allow for spare sprinkler head storage as required by NFPA guidelines. The Spare Sprinkler Head Cabinets are available Specifications in six configurations. Three head, six head, six head ESFR, twelve head, twenty-four head and thirty-six head. All six styles are Material: manufactured with "knockouts" to accommodate the most common Painted plain steel size sprinklers. The shelf is located to allow for the storage of a typical sprinkler head wrench. Each cabinet is finished with a red Finish: enamel fi nish. Each spare head cabinet comes with a hinged Rid enamel door which remains closed to protect the spare sprinklers from the Styles: elements and features two holes on the back panel to allow for 3 Spare sprinklers, attachment to most surfaces utilizing the appropriate fasteners. 1/2 or 3/4 Not intended for exposed or harsh environments. 6 Spare sprinklers, 1/2 or 3/4 Installation 6 Spare, ESFR, Select the correct Spare Once the correct Spare Sprinkler 1/2;3/4 or 1" Sprinkler Head Cabinet in Head Cabinet has been select- 12 Spare sprinklers accordance with the Automatic ed, installation is accomplished 1/2 or 3/4 Sprinkler Systems Handbook. by inserting the correct fastener 24 Spare sprinklers As per the 1989 Edition the in each of the two holes inside 36 Spare sprinklers correct number of spare the cabinet, securing the cabinet sprinkler is as follows: securely to the wall. The insert the correct number and type of "0-300 sprinklers, not less than 6 sprinklers in accordance with the 300-1000, not less than 12 "handbook". 1000 or more, not less than 24. *Final determination is subject to approval Stock of spare sprinklers shall include all types and ratings by the AHJ. installed."* Fire Protection Products, Inc F P P '® 6241 Yarrow Dr.,Suite A,Carlsbad,CA 92011-1541 102000-2007 Fire Protection Products,Inc(FPPI) For questions: 1 800 344-1822• 1 800 344-3775 fax•www.fppi.com P POTTER BELLS The Symbol of Protection PBA-AC & MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm General Signaling „_" w_ Burglar Alarm Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires DC Bells-Terminal strip 41> (Q) Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA-6-12 1750070 .12A 85 76 8(200) 12VDC MBA-8-12 1750080 .12A 90 77 10(250) 12VDC MBA-10-12 1750060 .12A 92 78 6(150) 24VDC MBA-6-24 1750100 .06A 87 77 8(200) 24VDC MBA-8-24 1750110 .06A 91 79 10(250) 24VDC MBA-10-24 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing. In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company, LLC • St. Louis, MO, • Phone: 866-572-3005/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 1 OF 2 01/13 ES-A-InBuildingRiser For Fire Protection Applications Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. Approval Representative LEAD FREE* Series IBR In-Building Risers Customizable Sizes: 4" - 10" (100-250mm) it .- Building Floor Building perimeter wall ST C " u �_ �� In oapap a itt, . i 6'x6'standard length o a (custom lengths from 3'—20'available) Flow Features Series IBR In-Building Risers are used to connect the main fire supply to the building overhead fire system.The fitting passes under the foundation without joints and ex- •Cost savings tends up through the floor. Provided with installation tabs,the unit has a CIPS(Cast •Corrosion resistant stainless steel Iron Pipe Size)coupler for easy connection to the underground supply(AWWA C900 construction, type 304 PVC and Ductile Iron Pipe)and industry standard grooved-end connection(AWWA •Ease of installation and light weight allows C606)on the building side for easy connection to the overhead fire sprinkler system. one person to position and handle the riser The IBR features Lead Free`construction to comply with Lead Free*installation •Minimal site preparation;joint restraint one requirements. piece construction reduces time and labor; Ames In-Building Risers are precision engineered and manufactured to provide no missing parts, no leaks; easily identifiable exceptional reliability and reduce installation time&labor costs associated with field for approvals assembly. In accordance with NFPA 24,the UL/FM approved In-Building Risers •Includes Test Cap and Coupler replace numerous fittings, elbows&spools and reduces the possibility of leaks or failure in comparison to traditional installation methods and materials. Factory tested •UL/FM approved integrity ensures the highest quality installation.The use of stainless steel significantly •Sizes: available in 4"— 10" (100-250mm) increases the reliability and life of the riser. with various lengths to meet local require- ments *The wetted surface of this product contacted by consumable water contains less •Designed to meet NFPA 24 than 0.25%of lead by weight. •AWWA C900 Inlet/DIP •AWWA C606 Outlet Ames Fire&Waterworks product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measure- ments,please contact Ames Fire&Waterworks Technical Service.Ames Fire&Waterworks reserves the right to change or modify product design,construction, specifications,or materials without prior notice and without incumng any obligation to make such changes and modifications on Ames Fire&Waterworks products previously or subsequently sold. A M E .S FIRE&WATERWORKS Specifications Standards In-Building Riser shall be installed as indicated on the plans. NFPA— Designed to allow the contractor to conform to NFPA Riser shall be composed of a single extended 90 degree fitting 24 of fabricated 304 stainless steel tubing, maximum working Where a riser is close to building foundations, underground pressure 200psi (14 bar).The fitting shall have a grooved-end fittings of proper design and type shall be used to avoid pipe joints connection on the outlet(building)side and a CIPS coupler on being located under the foundations. the inlet(underground)side.The grooved end shall include a coupler and cap to facilitate testing of the underground pip- End Connections ing.The In-Building Riser shall be an Ames Fire&Waterworks Series IBR. Horizontal End:Mates with Ductile Iron Pipe and AWWA 0900 Pipe(PVC Pipe with Ductile Iron Pipe Equivalent OD's) Utilizes Gasket conforming to UL 157 with"Lock in" gasket configuration Approvals Fittings FM class 1920 SIZE(DN) MATING PIPE OD UL HKQA(4"-10") in. mm in. mm ® ® 4 100 4.8 122 6 150 6.9 175 8 200 9.1 230 10 250 11.1 282 Dimensions-Weights ---.44-- A Vertical End: Meets AWWA C-606 dimensions for roll grooved pipe V Grooved End Meets AWWA C-207 class D for flanges (Flange Optional) Ratings Meets AWWA C-900 pressure class 200, DR 14 Pipe B Testing Welds are 100%leak tested at the factory CIPS Coupling Tie-Rod Bracket SIZE DESIGN PROOF PRESSURE M in. mm psi bar 4 100 1000 70 Iiir C ►i 6 150 1000 70 8 200 800 56 10 250 800 56 SIZE(DN) WEIGHT A(OD) B C NOTICE in. mm in. mm ft. cm ft. cm lbs. kg 4 100 41/2 114 6 183 6 183 71 32 Inquire with governing authorities for local installation 6 150 6% 168 6 183 6 183 98 44 requirements 8 200 85/8 219 6 183 6 183 129 59 10 250 10% 273 6 183 6 183 202 92 *'Each B(vertical)and C(horizontal)leg is customizable from 3'to 20'with UUFM NOTICE approvals.Consult with your factory representative for details. The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer.You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product. A AMES FIRE&WATERWORKS A Watts Water Technologies Company USA:Backflow Tel:(978)689-6066•Fax:(978)975-8350•AmesFireWater.com USA:Control Valves Tel:(713)943-0688•Fax:(713)944-9445•AmesFireWater.com Canada: Tel:(905)332-4090•Fax:(905)332-7068•AmesFireWater.ca Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091 •AmesFireWater.com ES-A-InBuildingRiser 1540 ©2015 Ames Fire&Waterworks ,. P POTTER BELLS ® The Symbol of Protection PBA-AC & MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C.BELLS 10"[ 1,, WHITE(IN) WHITE(OUT) (250) r PROM C ONTROL(200) 6" PANEL OR '(150) PRECEDING �� P BLACK(IN) BLACK(OUT) _1_ CAUTION: WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN_...] . 2 11/16" (68) DWG#776-1 NOTES: I.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2 END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. DWG,/'176-1 Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded 1/2"conduit entrance roi . , .. 5 3/4" 0 _ 3 3/8" 5" Limiimm To Next (146) (86) (127) Device or End-of-Line Resistor Li- Iv 3 3/8" 5/8" (86) (41) f- 41/4" (108) Installation DWG#776-2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and not less than 6"below the ceiling. 2. Remove the gong. 'e'l)#* 3. Connect wiring(see Fig.3). 04. Mount bell mechanism to backbox(bell mechanism must be /e mounted with the striker pointing down). 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). 0 0 ��� 6. Test all bells for proper operation and observe that they can BBX-1 ti Y be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). Failure to install striker down will prevent bell from operating. PRINTED IN USA MFG.#5400776-REV V-1 PAGE 2 OF 2 01/13 Product Information IIN11=71'11 - • FS-ONE High Performance Intumescent 0. Firestop Sealant , j , Product description r ■ Intumescent(expands when exposed to fire)firestop sealant that T helps protect combustible and non-combustible penetrations for f," ° °�, up to 4 hours fire rating •' ''' µ" '*f Product features • Smoke,gas and water resistant after material has cured „ 1. • Contains no halogen,solvents or asbestos k , ■ High fire rating properties • Water based,easy to clean °° k¢. q_. t ■ Protects most typical firestop penetration applications ■ Paintable TScht 1© •,..z , ., ',Iii, *401,1,g4;.. ::,. ■ Single component systems available Chemical basis Water-based intumescent acrylic IIIMeets LEEDTM requirements for indoor environmental quality credit dispersion 4.1 Low Emitting Materials,Sealants and Adhesives and 4.2 Paints Color Red and Coatings Application temperature 40°F to 104°F(5°C to 40°C) Skin forming time Approx.20-30 min. Areas of application Curing time Approx.2 mm/3 days • Steel,copper and EMT pipes Movement capability Approx.5% ■ Insulated steel and copper pipes Expansion rate(unrestricted) Up to 3-5 times original volume • Cable bundles Temperature resistance(cured) -40°F to 212°F(-40°C to 100°C) • Closed or vented plastic pipes Surface burning characteristics Flame Spread:0 • HVAC penetrations (ASTM E 84-96) Smoke Development:5 Sound transmission classification 56(Relates to specific construction) For use with (ASTM E 90-99) • Concrete,masonry,drywall and wood floor assemblies Approvals ■ Wall and floor assemblies rated up to 4 hours •California State Fire Marshal- No.4485-1200:108 •City of New York-MEA 326-96-M Vol.IV Examples Tested in accordance with • Sealing around combustible pipe penetrations in fire rated •UL 1479 •ASTM E 814 •ASTM E 84 construction 'At 73°F(23°C)and 50%relative humidity ■ Sealing around non-combustible penetrations in fire rated construction o`'PsOo FOR SE IINDTHROUG PENTETRA ON � r U FIRESTOP SYSTEMS ® Sritrer COMPAT►ss.t C USSEE UL FIRE RESISTANCE DIRECTORY 66Y7 APPROVED Installation instructions for FS-ONE Notice 4. Smoothing of firestop sealant:To complete the • On materials where oil,plasticizers or solvents may • Before handling,read Material Safety Data Sheet seal,tool immediately to give a smooth appearance. bleed i.e.impregnated wood,oil based seals,green and product label for safe usage and health Excess sealant,prior to curing,can be cleaned away or partially vulcanized rubber information. from adjacent surfaces and tools with water. • In any penetration other than those specifically • Instructions below are general guidelines—always 5. Leave completed seal undisturbed for 48 hours. described in this manual or the test reports refer to the applicable drawing in the UL Fire 6. For maintenance reasons,a penetration seal could Storage Resistance Directory or Hilti Firestop Systems Guide be permanently marked with an identification plate. . Store only in the original packaging in a location for complete installation information In such a case,mark the identification plate and protected from moisture at temperatures between Opening fasten it in a visible position next to the seal. 40°F(5°C)and 86°F(30°C) 1. Clean the opening.Surfaces to which FS-ONE will Not for use • Observe expiration date on the packag be applied should be cleaned of loose debris,dirt, • High movement expansion joints oil,moisture,frost and wax.Structures supporting • Underwater penetrating items must be installed in compliance with local building and electrical standards. W s Application of firestop sealant J yR 2. Install the prescribed backfilling material type and Q .....004 +^ 00. depth to obtain the desired rating(if required).LeaveHti1L'1 ++'. sufficient depth for applying FS-ONE. ' , 3. Application of firestop sealant:Apply FS-ONE to the 1.Clean opening. 2.Pack mineral wool. 3.Apply FS-ONE. 4.Smooth 5.Lowecompleted 6.Fasten identification (If required) FS-ONE. seal undisturbed for plate(if required). required depth in order to obtain the desired fire rating. 48 hours. Make sure FS-ONE contacts all surfaces to provide - maximum adhesion.For application of FS-ONE use a �+�w A standard caulking gun,foil pack gun,bulk loader and a / bulk gun.With FS-ONE buckets,Graco type sealant pumps may be used.(Contact pump manufacturer for 11 _ proper selection). 1.Clean opening. 2.Pack mineral wool. 3.Apply FS-ONE. 4.Smooth 5.Leave completed 6.Fasten identification (If required) FS-ONE. seal undisturbed for plate(f required). 48 hours. Hilti. Outperform. Outlast. Hilti,Inc.(U.S.)1-800-879-8000•www.us.hifi.com•en espanol 1-800-879-5000•Hilti Firestop Systems Guide M ito.I il Safoty 1)1;1 Shoet MSDS No.: 259 Revision No.: 010 Revision Date: 08/17/04 Page: 1 of 2 Product name: FS-ONE High Performance Intumescent Firestop Sealant Description: One-part acrylic-based sealant Supplier: Hilti, Inc. P.O.Box 21148,Tulsa,OK 74121 Emergency#(Chem-Trec.): 1 800 424 9300(USA, PR,Virgin Islands,Canada);001 703 527 3887(other countries) INGREDIENTS AND EXPOSURE LIMITS Ingredients: CAS Number: PEL: TLV: STEL: Polyacrylate dispersion Mixture NE NE NE Calcium carbonate 001317-65-3 5 mg/ms(T) 10 mg/m1(1) NE Zinc borate 138265-88-0 NE NE NE Ammonium polyphosphate 068333-79-9 NE NE NE Talc 014807-96.-6 20 mppcf 2 mg/hi' NE Expandable graphite 012777-87-6 5 mg/m3 M 2 mg/m3(F) NE Ethylene glycol 000107-21-1 NE C:100 mg/m"(A) NE Polybutene 009003-29-6 NE NE NE Iron oxide 001309-37-1 10 mg/rn, 5 mg/m3 NE Glass filament 065997-17-3 NE 5 mg/m3(T) NE Silicon dioxide 014808-60-7 0.05 mg/m'(1) 0.1 mgirre(1) NE Water 007732-18-5 NE NE NE Abbreviations: PEL=OSHA Permissible Exposure Limit. TLV=ACGIH Threshold Limit Value. C=Ceiling. STEL=Short Term Exposure Limit. NE=None Established. NA=Not Applicable. (T) indicates"as total dust". (R)indicates"as respirable fraction". (A)indicates"as an aerosol". mppcf=million particles per cubic foot. PHYSICAL DATA Appearance: Red paste. Odor: Odorless. Vapor Density: (air=1) Not determined. Vapor Pressure: 23mbar 0 20C/68F Boiling Point: Not applicable. VOC Content: 75.0 g/L. Evaporation Rate: Not applicable. Solubility in Water: Soluble. Specific Gravity: 1.5 pH: Not determined. FIRE AND EXPLOSION HAZARD DATA Flash Point: Non-flammable. Flammable Limits: Not applicable. Extinguishing Media: Not applicable. Use extinguishing media as appropriate for surrounding fire. Special Fire Fighting Procedures: None known.Use a self-contained breathing apparatus when fighting fires involving chemicals. Unusual Fire and Explosion Hazards: None known. Thermal decomposition products can be formed such as oxides of carbon, sulfur and phosphorous. REACTIVITY DATA Stability: Stable. Hazardous Polymerization: Will not occur. Incompatibility: Strong acids,peroxides,and oxidizing agents. Decomposition Products: Thermal decomposition can yield CO and CO2. Conditions to Avoid: None known. HEALTH HAZARD DATA Known Hazards: None known. Signs and Symptoms of Exposure: Possibly irritating upon contact with the eyes or upon repeated contact with the skin. Medical Conditions Eye and skin conditions. Aggravated by Exposure: Routes of Exposure: Dermal. p HIItIv. Livesng Firestop Saa through innovation L and education HiIt'. Outperform. Outlast. Hatt,Inc (U.S.)1-800-879-80000 www.tss.hilleoin•en espanoI 1-800-879-5000•Htti(Canada)Corp. 1-800-363-4458 www.IVIti.ca • ; M£3tt�rial S.if,ty Cl at<. Shti.E,t ' s MSDS No.: 259 Revision No.: 010 Revision Date: 08/17/04 Page: 2 of 2 Carcinogenicity: IARC classifies crystalline silica(quartz sand)as Group I based upon evidence among workers in industries where there has been long-term and chronic exposure(via inhalation)to silica dust e.g.mining,quant',stone crushing,refractory brick and pottery workers. This product does not pose a dust hazard;therefore,this classification is not relevant. Based upon the nature and intended use of this product,it does not pose an increased cancer risk to workers. EMERGENCY AND FIRST AID PROCEDURES Eyes: Immediately flush with plenty of water. Call a physician if symptoms occur. Skin: Immediately wipe off material and wash with soap and water. Material can adhere to the skin. If material has adhered to the skin,use an abrasive containing hand cleaner. If material does not come off,buff with a pumice stone. Inhalation: Move victim to fresh air if discomfort develops. Call a physician if symptoms persist. ingestion: Seek medical attention. Do not induce vomiting unless directed by a physician.If a large quantity was ingested,give 1 to 2 glasses of water to dilute. Never give anything by mouth to an unconscious person. Other.. Referral to a physician is recommended if there is any question about the seriousness o f the injury/exposure. CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT Ventilation: General(natural or mechanically induced fresh air movements). Eye Protection: Not required,however,safety glasses should be worn in most industrial settings. Skin Protection: Avoid skin contact.Cloth gloves are suitable for hand protection. Respiratory Protection: None normally required. Where ventilation Is inadequate to control vapors,use a NIOSH- approved respirator with organic vapor cartridges. Never enter a confined space without an appropriate air-supplied respirator. PRECAUTIONS FOR SAFE HANDLING AND USE Handling and Storing Precautions: Store in a cool,dry area preferably between 40o and 77o F. Keep from freezing. Do not store in direct sunlight. Avoid contact with the eyes or skin. Practice good hygiene;i.e. always wash thoroughly after handling and before eating or smoking. For industrial use only. Keep out of reach of children. Follow labeVuse instructions Spill Procedures: Immediately wipe away spilled material before it hardens. Place in a container for proper disposal in accordance with all applicable local,state,or federal requirements. REGULATORY INFORMATION Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication Standard 29 CFR 1910.1200. - - HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B DOT Shipping Name: Not regulated. IATA/ICAO Shipping Name: Not regulated. TSCA Inventory Status: Chemical components listed on TSCA inventory.SARA Title Ill,Section 313:This product contains<3%ethylene glycol(CAS 107-21-1)and<15%zinc borate(re:zinc compounds)which are subject to reporting under Section 313 of SARA Title III(40 CFR Part 372). EPA Waste Code(s): Not regulated by EPA as a hazardous waste. Waste Disposal Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that comply with local,state,and federal safety,health and environmental regulations. CONTACTS Customer Service: 1 800 879 8000 Technical Service:1 800 879 8000 Health/Safety: 1 800 879 6000 Jerry Metcalf(x6704) Emergency# (Chem-Tree): 1 800 424 9300(USA,PR,\nrgin Islands,Canada); 001 703 527 3887(other countries) The information and recommendations contained herein are based upon data believed to be correct;however,no guarantee or warranty of any kind expressed or implied is made with respect to the information provided. Hilti Firestop Saving Lives through innovation and education Hilt i. Outperform. Outlast. Hitt(,Inc.(U.S.)1-800-879-8000•www.us.hUli.cOm•en espas of 1-800-879-5000•Hihti(Canada)Corp.1-800-363-4458 www.hiltice Certificate of Cori s fiance Certificate Number 20100512-RI3240 Report Reference 2010 May 12 Page 1 of 1 1 Issue Date 2010 May 12 Underwriters Laboratories Inc. Issued to: Hilti, Inc. 54 S 122ND East AVe Tulsa, OK 74146 USA This is to certify that Fill, Void or Cavity Materials representative samples of FS-ONE Have been investigated by Underwriters Laboratories Inc.®(UL)or any authorized licensee of UL in accordance with the Standard(s)indicated on this Certificate. Standard(s)for Safety: ANSI/UL 1479,ANSI/UL 2079,CAN/ULC-S115-05 Third Edition,revised March 1,2010 Additional Information: FS-ONE Sealant for use in Joint Systems and FS-ONE for use in Through-Penetration Firestop Systems as currently described in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow-Up Service. The UL Classification Mark includes: UL in a circle symbol: ® with the word"CLASSIFIED"(as shown);a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of lin of the product;and, the product category name(product identity)as indicated in the appropriate UL Directory, Look for the UL Classification Mark on the product • .401W t ' •`" �.. 4 • „t °Ir 0o tr� tam RI t Ak ei � X Certificate of Com i liance Certificate Number 20060214-R13240E Page 1 of 1 Report Reference 2006 February 14 Issue Date 2006 February 14 Underwriters L Laboratories Inc., Issued to: Hilti, Inc. 5400 S 122ND East Ave Tulsa,OK 74146 USA This is to certify=that Fill, Void or Cavity Materials representative samples of FS-ONE Have einvesigby rwoos Inc.®in accordance ben withtthe StandaratedUnde ds) indicatedritersLabon thisratCertirieficate. Standard(s)for Safety: ANSI/UL 1479, ANSI/UL 2079,CAN/ULC-S115-05 Additional Information: FS-ONE Sealant for use in Joint Systems and FS-ONE for use in Through- Penetration Firestop Systems as currently described in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow-Up Service. $► The UL Classification Mark includes: UL in a circle symbol: �^r+ with the word "CLASSIFIED" (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product;and, the product category name(product identity)as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product Issued by: Reviewed by: `. IrtiaCouloute Christopher7�on Underwriters Laboratories Inc. Underwriters •.oratories Inc. Hilti North America 5400 South 122nd East Avenue Tulsa,OK 74146 P.O.Box 21148 I Tulsa,OK 74121-1148 T 1-800-879-8000 I F 918-252-6742 www.hilti.com June 27, 2008 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post- consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at(918) 252-6704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 252 6704 ierrv.metcalf(a�hilti.com NOTES/DEFINITIONS: 1. Post-Consumer Recycled Content: Portion of material or product derived from discarded consumer waste that has been recovered for use as a raw material[e.g.,plastic bottles, newspaper] 2. Post-Industrial Recycled Content: Portion of material or product derived from recovered industrial and mfg.materials that are diverted from municipal solid waste for use in a different mfg.process,prior to use by a consumer[e.g.,fly-ash in concrete or synthetic gypsum board,both of which are by-products of coal-burning power plants].Spills and scraps from the original manufacturing process that are combined with other constituents after a minimal amount of reprocessing for use in further production of the same product do not qualify. 3. Manufactured: Final assembly of components into building product that is furnished and installed by trades[e.g.,if the hardware comes from Dallas,TX,the lumber from Keene, NH,and the joist is assembled in Kent,WA;then the location of final assembly is Kent,WA]. www.gpsvisualizer.com/calculators can be used to calculate straight-line distance between project site/New York,NY and location of manufacture and raw material source. Note:location noted on material data sheets is often corporate location;need manufacturer to verify actual manufacture location. 4. Raw Materials: Virgin or recovered resources from which the product's components are made[i.e.,before processing or manufacturing]. 5. Rapidly Renewable: Materials and products made from raw materials that are harvested within a 10-year cycle[e.g.,bamboo,cork,linoleum,fast-growing poplar,wheatboard,wool carpet]. 6. FSC Certified: Wood-based products that are certified by the Forest Stewardship Council and carry a Chain-of-Custody certificate number from the vendor or manufacturer. 7. VOC Content: The quantity of volatile organic compounds contained in products such as adhesives,sealants and architectural coatings.VOC content is to be reported in grams/liter or lbs/gallon,less water and any exempt compounds/solvents. CONTRACTOR CERTIFICATION: I, a duly authorized representative of hereby certify that the information contained herein accurately represents the listed"green building"characteristics of the material]to be provided by our company as components of the building construction.Furthermore, I understand that any change in such"green building"material characteristics during the purchasing and/or installation period will require prior written approval from the Construction Manager and Owner. SIGNATURE OF AUTHORIZED REPRESENTATIVE: DATE: p. of p MSDS No.: 259 `i I■I11`TI Revision No.: 010 Revision Date: 08/17/04 ® Page: 1 of 2 MATERIAL;SAFETY DATA SHEET Product name: FS-ONE High Performance Intumescent Firestop Sealant Description: One-part acrylic-based sealant Supplier: Hilti, Inc. P.O. Box 21148,Tulsa,OK 74121 Emergency#(Chem-Trec.): 1 800 424 9300(USA,PR,Virgin Islands, Canada);001 703 527 3887(other countries) I € ;. INGREDIENTS AND EXPOSURE LIMITS Polyacrylate dispersion Mixture NE NE NE Calcium carbonate 001317-65-3 5 mg/m3(T) 10 mg/m3(T) NE Zinc borate 138265-88-0 NE NE NE Ammonium polyphosphate 068333-79-9 NE NE NE Talc 014807-96-6 20 mppcf 2 mg/m3 NE Expandable graphite 012777-87-6 5 mg/m3(T) 2 mg/m3(T) NE Ethylene glycol 000107-21-1 NE C:100 mg/m3(A) NE Polybutene 009003-29-6 NE NE NE Iron oxide 001309-37-1 10 mg/m3 5 mg/m3 NE Glass filament 065997-17-3 NE 5 mg/m3(T) NE Silicon dioxide 014808-60-7 0.05 mg/m3(T) 0.1 mg/m3(T) NE Water 007732-18-5 NE NE NE Abbreviations: PEL= OSHA Permissible Exposure Limit. TLV=ACGIH Threshold Limit Value. C= Ceiling. STEL= Short Term Exposure Limit. NE=None Established. NA=Not Applicable. (T)indicates"as total dust". (R)indicates"as respirable fraction". (A) indicates"as an aerosol". mppcf=million particles per cubic foot. n . 3. PHYSICAL DATA Appearance Red paste. Odor Odorless. Vapor Density: (air=1) Not determined. Vapor Pressure: 23mbar @ 20C/68F Soiling Point: Not applicable. VOC Content: ' 75.0 g/L. Evaporation Rate Not applicable. o)pbilityarlater Soluble. Specifin:Gravity: £. 1.5pH: u.".w% Not determined. FIRE"AND EXPLOSION:HAZARD DATA -rrx A Flash Point: Non-flammable. clammableLimits n x "; Not applicable. Extinguishing Media: x Not applicable. Use extinguishing media as appropriate for surrounding fire. Special Fire Fighting „i F None known.Use a self-contained breathing apparatus when fighting fires involving chemicals. v.Procedures N, :: UnuoaI Fire and Explosion None known. Thermal decomposition products can be formed such as oxides of carbon, sulfur Hazard :..;. and phosphorous. REACTIVITY DATA Stability Stable. Hazardous Polymerization:" Will not occur. incompatibility Strong acids,peroxides,and oxidizing agents. Decomposition Products: Thermal decomposition can yield CO and CO2. Conditions to Avoid: :. None known. r, HEALTH:HAZARD DATA Known Hazards: None known. Signs and Symptoms of Possibly irritating upon contact with the eyes or upon repeated contact with the skin. txposure• :Medical Conditions * Eye and skin conditions. Aggravated by Exposure: a Routes of Exposure: Dermal. HILTI®is a registered trademark of Hilti Corp. s s•+ Crpino enicity IARC classifies crystalline silica(quartz sand)as Group I based upon evidence among workers in g industries where there has been long-term and chronic exposure (via inhalation) to silica dust; e.g. mining, quarry, stone crushing, refractory brick and pottery workers. This product does not pose a dust hazard; therefore, this classification is not relevant. Based upon the nature and f intended use of this roduct it does not ose an increased cancer risk to workers. r P v EMERGENCY AN D:1RST M.01ROCEDIURES Eyes: : Immediately flush with plenty of water. Call a physician if symptoms occur. Skin Immediately material has adhwipe offred mat toatetheriaskin, use an abrasive containing hand cleaner. If material does not come off,buff with a pumice stone. II i',alation'll ! = Move victim to fresh air if discomfort develops. Call a physician if symptoms persist. Ingest Seek medical attention. Do not induce vomiting unless directed by a physician. If a large quantity was ingested, give 1 to 2 glasses of water to dilute. Never give anything by mouth to an {.., unconscious person. Other rry Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure. v.. CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT Ventilation General(natural or mechanically induced fresh air movements). EyePr© ttionf Not required, however,safety glasses should be worn in most industrial settings. Sen Protection Avoid skin contact.Cloth gloves are suitable for hand protection. Respiratory Protection None normally required. Where ventilation is inadequate to control vapors, use a NIOSH- approved respirator with organic vapor cartridges. Never enter a confined space without an w: appropriate air supplied respirator. " PRECAUTIONS POR SA .: ANDLING AND USE x� . � .� tr. Handling and Storir '` Store in a cool, dry area preferably between 40°and 77°F. Keep from freezing. Do not store in P actions: * direct sunlight. Avoid contact with the eyes or skin. Practice good hygiene; i.e. always wash thoroughly after handling and before eating or smoking. For industrial use only. Keep out ofreach of children. Follow label/use instructions. Spill Procedures Immediately wipe away spilled material before it hardens. Place in a container for proper disposal l r .. y in accordance with all applicable local,state,or federal requirements. RE LATORY IN FORMATION *x Haaard Communication This MSDS has been prepared in accordance with the federal OSHA Hazard Communication l ,, .4 #.` Standard 29 CFR 1910.1200. lMIS�es Health 1, Flammability 0, Reactivity 0, PPE B 100' T Shipping f+ me Not regulated. IA`A/ICAAO Sh �ng Nance Not regulated. TSCAI yent()77Status; Chemical components listed on TSCA inventory. �w SARA Title III,fiction 315: This product contains < 3% ethylene glycol (CAS 107-21-1) and < 15% zinc borate (re: zinccompounds) which are subject to reporting under Section 313 of SARA Title III (40 CFR Part y ry; 372 ). EPA Waste Code(s)t: Not regulated by EPA as a hazardous waste. Waste,DisposalMethodsl Consult with regulatory agencies or your corporate personnel for disposal methods that comply #{ with local,state,and federal safety,health and environmental regulations. CONTACTS rty Customer Service:. 1 800 879 8000 echni l Service 1 800 879 8000 1 Health/S*fete`::` 1 800 879 6000 Jerry Metcalf (x6704) Emergency#(Chem-Tres) : 1 800 424 9300(USA, PR,Virgin Islands,Canada); 001 703 527 3887(other countries) The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or warranty of any kind expressed or implied is made with respect to the information provided. MSDS 259, Page 2 of 2 ..;:tCALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION C� AL t OFFICE OF THE STATE FIRE MARSHAL FIRE FIRE ENGINEERING — BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE `1.,+, LISTING No. 4485-1200:108 Page 1 of 1 CATEGORY: Opening Protection (Firestopping) LISTEE: Hilti, Inc., 5400 S. 122nd East Ave, Tulsa, OK 74146 Contact: *Clay Hensley (918)252-6216 Fax(918)254-1679 DESIGN: Model FS-ONE Firestop Sealant. Refer to listee's printed data sheet and UL Fire Resistance Directory for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes&ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, type identification and UL label. APPROVAL: Listed as firestop devices for use in through-penetration firestop system up to 3 hour rating. For indoor use only. Approved under Through-Penetration Fire Stop Systems: CAJ1155, CAJ2091, CAJ2118, CAJ3095, CAJ5044, CAJ8041, F-C-2025, WL1085, WL1056, WL3047, WL5029, WL8004. Refer to UL Fire Resistance Directory for detailed constructions. *Rev.06-20-2006 (Cps This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test result and/or other data but does not make an independent verification of any cbims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation �.. -I criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JUNE 10, 2008 Listing Expires June 30, 2009 Authorized By: BEN HO, Chief Fire Engineering Division Report of Materials and BUILDINGS Equipment Acceptance Division NYC Department of Buildings 280 Broadway, New York, NY 10007 Patricia Lancaster, FAIA, Commissioner (212)566-5000,T1Y: (212)566-4769 Pursuant to Administrative Code Section 27-131, the following equipment or material has been found acceptable for use subject to the terms and conditions contained herein. MEA 326-96-M Vol. 5 Manufacturer: Hilti, Inc., 5400 S. 122 East Avenue, Tulsa, OK 74146 Trade Name(s): Hilti, Inc. Product: Fill, void or cavity material for fire protection Pertinent Code Section(s): 27-345 Prescribed Test(s): RS 5-19 (ASTM E814), UL 2079 Laboratory: Underwriters Laboratories, Inc. Test Report(s): File R13240, dated July 16, 1993, July 21, 1993, July 13, 1993, July 22, 1993, April 1, 1993, March 25, 1994, March 3 and 6, 1995, September 4, 1996, September 27, 1997; File R13644, dated April 12, 1993 and May 3, 1993; File R12232, dated August 2, 1993; UL-design listings. Description: Fill, void or cavity material for through-penetrations in fire-rated wall and/or floor/ceiling construction. The Hilti FS-ONE Firestop Sealant shall be applied in' accordance with Underwriters Laboratories 'Inc.' system numbers, listed on following pages, in achieving the required fire-resistance ratings. MEA 326-96-M Vol. 5 Page 1 of 10