Loading...
Plans ' 3 AMERICAN HEATING \"('I f^ INC 5035 SE 24th Avenue, Portland,Oregon 97202 ri t V, i`�i`�.• P 1 503.239.4600 Fl 503.239.7038 BUILT ON TRUST OREGON CCB:33135 I WASHINGTON AMERII*212JC/AMERIHI123R0 TO: City of Tigard Building Division ATTN: Walter Chip Barnett FROM: Brian Shea and Mac Nelson DATE: October 19, 2016 PROJECT: Burnham and Ash Apartments SUBJECT: Refrigerant Piping Compliance—OSMC 2014 1107.2.2 Project Information Building Permit: MEC2016-00068 Construction Type: 5A Tenant Name: Burnham and Ash Apartments Occupancy Type: M Address: 12850 SW Ash Occupant Load: NA Area: NA Stories: 4 Per OMSC 2014 1107.2.2: "Refrigerant piping shall not penetrate floors, ceilings, or roofs." Exception 4 Exempts"Penetrations by piping in a direct system where the refrigerant quantity does not exceed Table 1103.1 for the smallest occupied space through which the piping passes." The Smallest Occupied space(s)through which the piping passes is the 3 restrooms in the X25 stack(225, 324,425).This restroom has been calculated,accounting for sheetrock,to have a volume of 492.4 cubic feet(calculation sketch attached for reference). The 4 ton split system in question will be charged to 12.31 lbs of refrigerant(R410a) maximum. Per OMSC 2014 Table 1103.1,the maximum amount of refrigerant per occupied space for R410a is 25 lbs/1000 cubic feet. 12.31 Lbs/492.4 cubic ft* 1000 cubic ft/lb allowed=25. Maintaining a maximum charge of 12.31 lbs of refrigerant in FC/HP 1-1-3 is sufficient to comply with Exception 4 of OMSC 2014 1107.2.2 Respectfully, Brian Shea and Mac Nelson American Heating, Inc. (503) 239-4600 brian@americanheating.net mac@americanheating.net AMERICA N ,, I E 1 11 � I 1.* 5035 SE 24th Avenue,Portland,Oregon 97202 4600 Fl503.239.7038 . . ._......___ _.._.... OREGON CCB:33135 WASHINGTON AMERII*212JC/AMERIHI123RO P 503.239. BUILT 9N TRUST on * 1 ,ft / 2 7 ' . l` '