Loading...
Report (23) (/i Zl)(G (.) 2 LL-le--(7 5( „; WALL SIGN DESIGN Scope of work is for the design of the connection of the wall sign to the existing structure only. See following pages for structural notes. Input Data: ASCE 7-10-Components and Cladding Wind Speed,V= 120.00 mph Risk Category= II Exposure Category= B Ridge Height,hr= 30.00 ft Eave Height,he= 30.00 ft Building Width= 240.00 ft(Normal to Building Ridge) Building Length= 240.00 ft(Parallel to Building Ridge) Topo.Factor,Kzt= 1.00 Direct.Factor,Kd= 0.85 Corner Zone: No 16'-0" Resulting Parameters and Coefficients: Roof Angle,0=_ 0.00 deg. Mean Roof Ht.,h= 30.00 ft Wall External Pressure Coefficients,GCp: GCp Zone 4 Pos.= 0.90 GCp Zone 5 og.=NCellular® GCp Zone 4 Neg.= 0.90.9 9 Consumer GCp Zone 5 Neg.= -1.26 a= 7.00 zg= 1200 Kh= 0.70 (Kh=Kz evaluated at z=h) qh= 13.17 psf =0.00256*Kh*Kzt*Kd*VA2*0.6 (allowable) 3/8" HILTI KBTZ ANCHOR TYP. (10) LOCATIONS. Wall Pressure for Anchor Design EMBED 2-1/2". Design Net External Wind Pressures: F= -13.04 psf =-0.99*13.17 Sign Dead Load= 4.00 psf(max) �t�ED PROc�- Fastener Capacities: GIN Tc= 645 lb � • Fac Vc= 736 lb z 41 725 ,. p offset= 0.00 in o.d.of spacer= 0.00 in Max trib.area= 38.98 ft2 =1/(((13.04)/6451b+4/7361b) 11, ' c eN oo O~ Sign Geometry: qO� y 8 ,1 �- Height= 3.50 ft(max) l68 Width ✓ 0 � = 16.00 ft(max) SEPH\*\ %solid= 100% Area= 56.0 ftz =3.5*16*100% EXPIRES:12-31-2016 Space anchors around perimeter of sign #of fasteners= 2 required(min.) Fastener spacing= N/A Fasteners Used= 10 Provide 3/8"dia.Hilti KBTZ for every 38.98 sgft.of sign area(10 fasteners used) 9570 SW Barbur BlvdConsumer Cellular Wall Sign 161229 Project Name Project# Suite One Hundred Portland,OR 97219 Location 12447 SW 69th Avenue, Portland, Oregon 1111) Client Security Signs MILLER Phone 503.246.1250 CONSULTING Fax 503.246.1395 EWA9/30/16 1 of 3 www.miller-se.com By Ck'd Date Page ENGINEERS GENERAL THE CONTRACTOR IS RESPONSIBLE FOR VERIFICATION AND CORRELATION OF ALL ITEMS AND WORK NECESSARY FOR COMPLETION OF THE PROJECT AS INDICATED BY THE CONTRACT DOCUMENTS. SHOULD ANY QUESTION ARISE REGARDING THE CONTRACT DOCUMENTS OR SITE CONDITIONS, THE CONTRACTOR SHALL REQUEST INTERPRETATION AND CLARIFICATION FROM THE ENGINEER BEFORE BEGINNING THE PROJECT. THE ABSENCE OF SUCH REQUEST SHALL SIGNIFY THAT THE CONTRACTOR HAS REVIEWED AND FAMILIARIZED HIMSELF WITH ALL ASPECTS OF THE PROJECT AND HAS COMPLETE COMPREHENSION THEREOF. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CONFORMANCE TO ALL SAFETY REGULATIONS DURING CONSTRUCTION. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. UNLESS OTHERWISE SPECIFICALLY NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION OR CONSTRUCTION LOADS. ONLY THE CONTRACTOR SHALL PROVIDE ALL METHODS, DIRECTION AND RELATED EQUIPMENT NECESSARY TO PROTECT THE STRUCTURE, WORKMEN AND OTHER PERSONS AND PROPERTY DURING CONSTRUCTION. THE CONTRACTOR SHALL, AT HIS OWN EXPENSE, ENGAGE PROPERLY QUALIFIED PERSONS TO DETERMINE WHERE AND HOW TEMPORARY PRECAUTIONARY MEASURES SHALL BE USED AND INSPECT SAME IN THE FIELD.ANY MATERIAL NOT AS SPECIFIED OR IMPROPER MATERIAL INSTALLATION OR WORKMANSHIP SHALL BE REMOVED AND REPLACED WITH SPECIFIED MATERIAL IN A WORKMANLIKE MANNER AT THE CONTRACTOR'S EXPENSE. THESE PLANS, SPECIFICATIONS, ENGINEERING AND DESIGN WORK ARE INTENDED SOLELY FOR THE PROJECT SPECIFIED HEREIN. MILLER CONSULTING ENGINEERS DISCLAIMS ALL LIABILITY IF THESE PLANS AND SPECIFICATIONS OR THE DESIGN, ADVICE AND INSTRUCTIONS ATTENDANT THERETO ARE USED ON ANY PROJECT OR AT ANY LOCATION OTHER THAN THE PROJECT AND LOCATION SPECIFIED HEREIN. OBSERVATION VISITS TO THE JOB SITE AND SPECIAL INSPECTIONS ARE NOT PART OF THE STRUCTURAL ENGINEER'S RESPONSIBILITY UNLESS THE CONTRACT DOCUMENTS SPECIFY OTHERWISE. NON STRUCTURAL PORTIONS OF PROJECT, INCLUDING BUT NOT LIMITED TO PLUMBING, FIRE PROTECTION, LAND USE, SITE PLANNING, EROSION CONTROL, ELECTRICAL, MECHANICAL, FLASHING AND WATER-PROOFING ARE BEYOND THE SCOPE OF THESE DRAWINGS AND ARE PROVIDED BY OTHERS. EXISTING STRUCTURAL ELEMENTS ARE DESIGNED BY OTHERS. SPECIAL INSPECTION OF WELDS AND POST INSTALLED ANCHORS ARE TO BE PROVIDED BY A SPECIAL INSPECTION AGENCY AS REQUIRED BY THE BUILDING OFFICIAL FOR ELEMENTS OF THE PROJECT THAT DO NOT MEET THE APPROVAL OF CONSTRUCTION OF A MINOR NATURE OR AS WARRANTED BY CONDITIONS IN THE JURISDICTION (SECTION 1704.2, EXCEPTION 1). CONTRACTOR TO VERIFY ALL CONDITIONS PRIOR TO FABRICATION OR INSTALLATION. ENGINEER OF RECORD FOR THE PROJECT IS TO BE NOTIFIED IF CONDITIONS DIFFER FROM WHAT IS SHOWN ON THE DRAWINGS. BUILDING CODE ALL PHASES OF THE WORK SHALL CONFORM TO THE 2014 OREGON STRUCTURAL SPECIALTY CODE, BASED ON THE 2012 INTERNATIONAL BUILDING CODE, INCLUDING ALL REFERENCE STANDARDS, UNLESS NOTED OTHERWISE. ccs:L.D'PROF42 725 .-E lP di / t•N o ~ � I.°_q..,': � Yoa Fs, Ma''4 0SEPH EXPIRES:12-31-2016 04 9570 SW Barbur Blvd Consumer Cellular Wall Sign 161229 Project Name Project# Suite One Hundred APortland,OR 97219 Location 12447 SW 69th Avenue, Portland, Oregon Client Security Signs MILLER Phone 503.246.1250 CONSULTING Fax 503.246.1395 EWA9/30/16 2 of 3 www.miller-se.com By Ck'd Date Page ENGINEERS DESIGN LOADS THE FOLLOWING ARE THE DESIGN REQUIREMENTS: STRUCTURAL DESIGN CRITERIA RISK CATEGORY II WIND DESIGN DATA BASIC WIND SPEED(3 SEC GUST) 120 MPH EXPOSURE B POST-INSTALLED ANCHORS ANCHORAGE ANCHORS SHALL BE AS SPECIFIED ON THE DRAWINGS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURERS INSTALLATION CRITERIA AND PER THE CURRENT ICC EVALUATION REPORT FOR THE ANCHOR.ANCHORS ARE NOT TO CUT THROUGH ANY EXISTING STEEL REINFORCING. ALUMINUM ALL STRUCTURAL ALUMINUM SHAPES AND PLATES TO BE 6061-T6. ALL WELDS TO USE [4043] ALUMINUM FILLER ALLOY. A PROTECTIVE BARRIER SHALL BE PROVIDED BETWEEN ALL STEEL AND ALUMINUM TO PREVENT CORROSION.ALL WELDING TO CONFORM TO AMERICAN WELDING SOCIETY(AWS)D1.2.WELD LENGTHS SHOWN ARE EFFECTIVE AS SPECIFIED PER THE ALUMINUM DESIGN MANUAL. WELDING SHALL BE BY AWS CERTIFIED WELDERS FOR WELD TYPES SPECIFIED. WHERE WELD LENGTHS ARE NOT SHOWN, THE WELD SHALL BE FULL LENGTH OF MEMBERS BEING JOINED. ALL BUTT WELDS SHALL BE FULL PENETRATION WELDS UNLESS NOTED OTHERWISE ON STRUCTURAL DRAWINGS. ALL WELDS TO RECEIVE THE SAME FINISH COAT AS THE MEMBER BEING WELDED. ALL FASTENERS IN CONTACT WITH ALUMINUM TO BE TYPE 304 STAINLESS STEEL WITH MATCHING NUTS OR HAVE A PROTECTIVE BARRIER TO PREVENT CORROSION. NUTS SHALL BE TIGHTENED TO A SNUG TIGHT CONDITION. �\5,���� t D PROF i 725 „ trft IIPl0N, , , 49l r 08 , Fs JOSEPH Maga EXPIRES:12-31-2016 9570 SW Barbur Blvd Project Name Consumer Cellular Wall Sign Project# 161229 Art Suite One Hundred Portland,OR 97219 Location 12447 SW 69th Avenue, Portland, Oregon Mil Client Security Signs MILLER Phone 503.246.1250 CONSULTING Fax 503.246.1395 EWA > / 9/30/16 3 of 3 www.miller-se.com By Ck'd Date Page ENGINEERS