Loading...
Specifications (30) 6U/42016e (X)()S-1 CtS76' 5A) "s� S2-4 Dan Nelson From: Scott Homan <Scott.Homan@callisonrtkl.com> Sent: Thursday, March 03, 2016 3:18 PM To: Dan Nelson Cc: Mike Reading; Craig Klinkam; Grant Seaman; Scott Johnson; Michael Cook; Erik Mueller- Ali; Karen Stoner; Grant Seaman Subject: Ben Bridge-Washington Square: revised structural drawings Attachments: 16066 Permit Revision Narrative_revision2.pdf; 16066 Ben Bridge - Washington Square_REVISED_SU BMITTAL.pdf Importance: High Hello Dan, Please find attached the revised structural drawings and narrative per our structural engineer's conversation with you earlier this week. Please confirm receipt. Our GC, Mike Reading, will be in touch to review over-the-counter with you and we hope this satisfies all of your comments to date so the building permit can be issued. • Please let us know if you require any additional information. Thank you, Scott Homan AIA, LEED AP Senior Associate 11 312 542 5974 Direct +1 206 786 4429 Cell CALLISQR TKL A DESIGN CONSULTANCY OF ARCADIS CallisonRI KI Inc. 200 South Michie an!`avenue,Suitc 1200 Chicago, IL 60604 CallisonRTKL.com This e-mail and any files transmitted with it are the property of Arcadis and its affiliates. All rights, including without limitation copyright, are reserved. This e-mail contains information which may be confidential and/or privileged. It is for the exclusive use of the intended recipient(s). If you are not the intended recipient(s),please note that any form of distribution, copying or use of this communication or the information in it is strictly prohibited and may be unlawful. If you have received this communication in error, please return it to the sender, delete it and destroy any copies of it. While reasonable precautions have been taken to ensure no viruses are present, we cannot guarantee that this e- mail or any attachment is virus-free or has not been intercepted or changed. Any opinions or other information in this e-mail that do not relate to the official business of Arcadis or CallisonRTKL are neither given nor endorsed by it. 1 13228 NE 20th Street, Suite 100, Bellevue, WA 98005-2049 Phone (425) 614-0949 Fax (425) 614-0950 AUE Bellevue, WA I New York, NY March 3,2016 Dan Nelson Senior Plans Examiner City of Tigard Tigard,Oregon RE: Ben Bridges Washington Square AUE No: 16066 Building Permit#BUP2016-00051 Dear Mr.Nelson, The following is a response to the structural items discussed over the phone. • There was some confusion regarding the definition of"O.W.J.":the teen is short for'`Open Web Joist". • The spacing and required layout of the unistrut was incorrect. It has now been revised to the correct spacing requirements and the note has been revised to indicate that new unistrut is only required where new wires do not align with (E) framing and where soffit or compression stud members are installed. • The compression stud and soffit bracing details have been revised to show maximum heights and lengths. In addition, the soffit bracing detail has been altered to allow for splicing. • Regarding the standard notes regarding field adjustments,those are variations on industry standard notes that are typically covered in the structural general notes. AUE's policy is to include them on every plan sheet on TI and remodel projects. In addition, the ceiling framing has been revised per the contractors request to have the upper ceiling framing continue over the lower ceiling. The compression stud is considered braced in both directions at the upper ceiling. Minor edits were made to properly indicate detail specifications. No revised calculations have been provided. With the transition from a single 43 mil brace to a double 33 mil brace,the soffit bracing is OK by inspection. Please feel free to contact me if you have any questions regarding this narrative. Sincerely, AUE Karen M.Stoner,P.E. Senior Engineer (425)502 5075 CALLJSON TKL A O€SIO I Oo sULTAI cY OF ARCADIS - PERMIT RESUBMITTAL NARRATIVE riPc r:Cfiv r 26 February 2016 Ben Bridge Store:Washington Square ry' 201 6 Callison Project Number: 006-090940.00 1 ti1(' , _ See below for a narrative of responses to the permit review comments: 1GI �� rN PERMIT REVIEW COMMENTS: 1. Comment:Construction requirements for suspended ceiling systems are found in the Oregon Building Codes Division website under Statewide Code Interpretations dated 4/20/2007. (see interpretations(structural)at www.bcd.oregon.gov) Response: Refer to structural for compression strut details for the 30'-0"deck above on sheet S-004. Architectural details C1 & E1/A-802 reference CISCA 3-4(figures 2, 3,4, and 5) and ASCE 7-10 section 13.5.6. 2. Provide calculations and construction details including seismic bracing details for non full height partitions,suspended ceilings and any ceiling soffits as well as ceiling clouds. Note:The roof structure may be approximately 30'above the finished floor. Please note roof structure height at wall details on plans. OSSC 106.1 Response: Refer to structural sheet S-004. 3. Please provide calculations and construction details for the storefront construction. Every structure, and portion thereof, including non structural components that are permanently attached to structures and their supports and attachments,shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7 as modified by Section 1613.7. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1 Response:Veneer tile ST-1 and ST-2 at the storefront are 3/8"thick veneer tile,which will replace the existing veneer tile (no change in load).They are installed with thinset over tile backer board (refer to detail A8/A-301). Refer to spec section 093000 for tile installation specifications. Refer to structural for new framing details/connections and tile backer board fastener specification. Refer to sheet 5-003. CALLISON ARCHITECTS, P.C. 1420 FIFTH AVENUE #2400 SEATTLE, WASHINGTON 98101-2343 - T 206 623 4646 F 206 623 4625 www.callison.com 13228 NE 20th St, Suite 100, Bellevue, WA 98005 Phone (425) 614-0949 Fax(425) 614-0950 { AUE STRUCTURAL CALCULATIONS FOR: FEB 29 ?_016 lig IN nIVISION Ben Bridge Washington Square 9585 SW Washington Square Road, Portland, OR 97223 Client: ��c �o PN OFFSs/� CALLISON �0'EGON A#� AMdA 0.• OOYrAMY •, a) gY132� rCAI_LISON ARCHITECTS, P .C. 9� 1 UNSO www_cal�aeon �Q EXPIRES: 06/30/16 1420 Fifth Avenue #2400 Seattle, WA By Karen M. Stoner, P.E. Brian Unsderfer, S.E., SECS AUE No. 16066 Date 2/26/2016 IBC Seismic I I Non-Structural Systems I IBC 2012 Risk Category: H Standard-Occupancy Building Fa= 1.11 Sms= 1.084 Ss= 0.978 hn= 15 ft Fv= 1.58 Sml= 0.669 Sl= 0.4251 Ct= 0.02 Ie= 1.00 SDC: D Sds= 0.723 Sdl= 0.446 Site Class= D Zipcode: I 97223 I Use User Input I Seismic Variables from USGS Seismic Variables from User Input Max Loc Max Ss= 0.9954 45.47,-122.75 Ss= 0.9780 S1= 0.4291 45.47,-122.77 S1= 0.4250 PGA= 0.4342 45.47,-122.75 Min Loc Ss= 0.9546 45.42,-122.84 51= 0.4208 45.42,-122.8 PGA= 0.4196 45.42,-122.84 ISee ASCE 13.3 Non Structural Systems I -Ceilings -Interior Walls A3.Cantilever Elements(Unbraced or Braced to Structural Frame Below its Center of A14.Ceilings-All Mass)-Parapets and Cantilever Interior Non-Sdnctural Wa s Ap= 1.0 z= 15.00 ft IP= 1.0 Ap= 2.5 z= 15.00 ft Ip= 1.0 Rp= 2.5 h= 15.00 ft Rp= 2.5 h= 15.00 ft S2o= 2.5 S2o= 2.5 Fp= 0.35 *WpI Fp= 0.347 *Wp I Fp= 0.87 *Wp I Fp= 0.868 *Wp Fp max= 1.16 *Wp Fp max= 1.16 *Wp Fp min= 0.22 *Wp With Overstrength factor: Fp min= 0.22 *WpI Fid Overstrength factor: I Fp= 0.868 *Wp A2.Interior Nonstructural Walls and Partitions-All other walls and partitions Ap= 1.0 z= 15.00 ft Ip= 1.0 Ap=- z= 15.00 ft Ip= 1.0 Rp= 2.5 h= 15.00 ft gp=- h= 15.00 ft S2o=.. S2o= Fp.= 0.35 *Wp I Fp= 0.347 *Wp I Fp= #VALUE! *Wp I Fp= #VALUE! *Wp I P= Fp max= 1.16 *Wp Fp max= 1.16 *Wp Fp min= 0.22 *Wp With Overstrength factor: Fp min= 0.22 *Wp With Overstrength factor: I Fp= 0.868 *Wp I I Fp- #VALUE! *Wp I 13228 NE 20th St,Suite 100,Bellevue,WA 98005 Project: Ben Bridge Washington Square Pg.No: C&C Seis 1 Address: 9585 SW Washington Square Road,Portland,OR Date: 2/26/16 AUE Client: Callison Job No.: 16066 Braced Soffit Drop V 90# y A V Lateral load= 2.2555 psf I 173# 90# A Gravity Load= 6.5 psf < > 90# V Stud spacing= 16 in Brace Spacing= 48 in -4 1 j: -4 1 • Vertical Studs: 20.00 ft j1 Moment= 1.8044 k-in 1 — Try: 362S137-33 (33ksi) Mallow= 4.59 k-in OK -4 f ,,.. (from SSMA catalog) V c. Ix= 0.48 in4 < > deflection= 0.78 in .0# =Point load to align with brace • =L/ 309 > 240 OK Bottom Track to span between braces N/A-horiz, strongback provided, OK by inspection Connection at brace: Axial load in brace= 128 # Allowable Shear of #8 in 33mi1= 164.00 lb screws req'd= 0.78 Connection of brace to deck Seismic load factor= 1.4 Factored shear= 178.6265 # factored tension= 0 # Try: (3)#10 screws to angle(angle OK by inspection) Shear Cap= 789 # Tension Cap= 327 # Check Unity= 0.226396 < 1.0 OK Check bending of clip N/A-attaches to plate gusset 13228 NE 20th St,Suite 100,Bellevue,WA 98005 Project: Ben Bridge Washington Square Pg.No: Soffit-1 Address: 9585 SW Washington Square Road,Portland,OR Date: 2/26/16 AVE Client: Callison Job No.: 16066 Connection at vert: Tension load in stud= 264 # Allowable Shear of #8 in 33mil= 164.00 lb screws req'd= 1.61 Connection of VERT @ brace to deck Seismic load factor= 1.4 Factored shear= 42.10267 # factored tension= 369 # Try: 1/2"bolt to(E) strut Shear Cap= 500 # Tension Cap= 500 # Assumed minimum values Check Unity= 0.822155 < 1.0 OK Check bending of clip N/A-square washer provided Check bending of track for dead load only P= 86.67 ea side span = 2.50 Moment = 54 #-in Use min 43 mil clip b= 12.00 in t= 0.05 in Fy= 33000 psi S, btA2/6= 0.00 in^3 Moment capacity 0.75*Fy*S= 100.7 #-in > 54.17 OK Connection of VERT to deck shear= 0.00 # tension= 173.33 # Try: (2)#8 to ea. stud Allowable Shear of #8 in 43mi1= 244.00 lb Fasteners req'd= 0.710383 13228 NE 20th St,Suite 100,Bellevue,WA 98005 Project: Ben Bridge Washington Square Pg.No: Soffit-2 AUE Address: 9585 SW Washington Square Road,Portland,OR Date: 2/26/16 Client: Callison Job No.: 16066 11101 Single Soffit Drop Lateral load= 6.94 psf(cant.) Lateral load= 17.36 psf(cant.) Gravity Load= 20 psf 47# A M' Stud spacing= 16 in ��'; DL/Brace Spacing= 16 in Front vertical stud: 3.00 ft Moment= 0.31248 k-in 1I Try: 250S137-33 (33ksi) 1 Mallow= 3.1 k-in OK —3 (from SSMA catalog) lx= 0.2 in4 ,{ ;. deflection= 0.01 in 47# =L/4950 > 240 OK V ' " ' Bottom stud 1.25 ft Moment= 0.05425 k-in , 97# TRY 250S137-33 (33ksi) Mallow= 3.1 k-in OK lx= 0.2 in4 deflection= 0.00 inch =L/ 72986 > 240 OK Connection at brace: Axial load in brace= 47 # Allowable Shear of #8 in 33mil= 164.00 lb screws req'd= 0.28 Rear vertical stud Total height= 14.00 ft Moment= 2.76 k-in Try: 362S162-43 (33ksi) Mallow= 7.34 k-in OK (from SSMA catalog) lx= 0.71 in4 deflection= 0.37 in =U 459 > 360 OK Note: Deflection shown is based on LL conditions only. Per conversation with Arch., (E)finish material is being replaced w/like and has not had issues to date despite LL deflection exceeding manufacturer recommendations. Finish damage is anticipated during code level seismic event. Seismic deflection = U331. 13228 NE 20th St,Suite 100,Bellevue,WA 98005 Project: Ben Bridge Washington Square Pg.No: Soffit-1 AVE Address: 9585 SW Washington Square Road,Portland,OR Date: 2/26/16 Client: Callison Job No.: 16066 T. Support of Ceiling Grid Wire Supports Support spacing= 4 ft x 4 ft Dead Load of Ceiling= 6 psf Axial Load on Each Wire= 96 lbs Check 12 GA Wire Diameter of 12 GA= 0.1046 inch Area of 12 GA Wire= 0.0086 sq inches Stress= 11 KSI Use 12GAWire (Allow Stress in Wire= 35 KSI > 11 KSI For typical Ceiling Supports Use HILT!CEILING CLIPS ESR-2892 Tension Load Req'd= 96.00 lbs Allow Tension= 100 OK Seismic Bracing of Ceiling 209.87 lb V= 209.87 1 L Ceiling Weight to calc lateral force= 6 PSF 209.87 1 V = 0.347 W Strength Vertical Load V= 0.243 W Working Stress 210 Trib area for lateral load= 144 sqft =12*12 Trib Dead Load,W= 864 # Lateral Load= 209.87 LBS Axial load in brace= 296.79 LBS #8 wood screws,2"penetration min 0.46 specific gravity Allow shear= 83 # Number of screws req'd= 3.58 #8 wood screws,2"penetration min 0.46 specific gravity Allow tension= 148.5 # Number of screws req'd= 2.00 Allowable Shear of #8 in 18mil= 66 lb number of#8reqd. = 4.50 Allowable Shear of #8 in 30mi1= 141 lb number of#8reqd. = 2.10 13228 NE 20th St,Suite 100,Bellevue,WA 98005 Project: Ben Bridge Washington Square Pg.No: Ceiling-1 Address: 9585 SW Washington Square Road,Portland,OR Date: 2/26/16 AVE Client: Callison Job No.: 16066 BRACE DESIGN Brace Span= 19.00 feet hole spacing= 24 KLy=KLt= 19 ft hole depth= 1.5 hole length= 4 Axial Load= 210 # A= 0.34 in2 J= 0.23 x1000 in4 TRY 3625162-4; Fy= 33 ksi Cw= 0.376 in6 xo= -1.297 in Calculate axial capacity m= 0.782 in a) Check flexural buckling ro= 2.036 in Fe,= 2.09 ksi p= 0.594 b) Check flexural-torsional buckling Lu= 3.54 ft Fe2= 2.9 ksi G= 11300 psi governing Fe= 2.1 ksi ax= 11.7 ksi Fn= 1.83 ksi at= 3.3 ksi Compute Effective Area S162 43.00 mil t= 0.0451 R= 0.0712 flange= 1.625 in w/t= 30.9 lip= 0.5 in D/w= 0.359 Check flange w= 1.3924 in S= 162.4 k= n/a Fcr= n/a ksi la= n/a Is= n/a effective,b= 1.3924 in R1= n/a n= 0.333 Check lip w= 0.384 w/t= 8.5 k= 0.43 Fcr= 158.4 ksi A= 0.107597 effective,b= 0.3837 in Check web hole w= 0.944 w/t= 20.9 depth= 3.62 in k= 0.43 Fcr= 26.2 ksi effective,b= 0.944 in Ae(inA2)= 0.272 Allowable Axial= 277 # OK 13228 NE 20th St,Suite 100,Bellevue,WA 98005 Project: Ben Bridge Washington Square Pg.No: Ceiling-2 AUE Address: 9585 SW Washington Square Road,Portland,OR Date: 2/26/16 Client: Callison Job No.: 16066 February 16, 2016 RE: TENANT IMPROVEMENT Project Information Building Permit: BUP2016-00051 Construction Type: 2-B Address: 9516 SW Washington Sq. Occupancy Type: M Area: 2620 Sq. Ft. Stories: 1 Name: Ben Bridge Sprinklers: Yes The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2014 edition; 2014 Oregon Fire Code. Please respond to conditions below. 1) Construction requirements for suspended ceiling systems are found in the Oregon Building Codes Division website under Statewide Code Interpretations dated 4/20/2007. (see interpretations{structural} at www.bcd.oregon.gov) 2) Provide calculations and construction details including seismic bracing details for non full height partitions, suspended ceilings and any ceiling soffits as well as ceiling clouds. Note: The roof structure may be approximately 30' above the finished floor. Please note roof structure height at wall details on plans. OSSC 106.1 3) Please provide calculations and construction details for the storefront construction. Every structure, and portion thereof, including non structural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7 as modified by Section 1613.7. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7. OSSC 1613.1 When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson Senior Plans Examiner (503) 718-2436 dann@tigard-or.gov