iirl COMcheck Software Version 3.9.3
it
Interior Lighting Compliance
Certificate RECIIIVED
2010 Oregon Energy Efficiency Specialty Code
FEB 5 201`
Section 1: Project Information Cs::,
rOFIGIii)
Project Type:Alteration BUILDING DIVISION
Project Title: Noodles Company Store#819
Construction Site: Owner/Agent: Designer/Contractor:
10218 SW Washington Square Road Janina Kojs Davis Dickerson
Tigard,OR 97223 Chipman Designs Architects,Inc. Dickerson Engineering,Inc.
2700 S.River Road.,Suite 400. 8101 N.Milwaukee Ave.
Des Plaines,IL 60018 Niles, IL 60714
(847)298-6900 (847)966-0290
Section 2: Interior Lighting and Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B x C)
Common Space Types:Dining Area-Family Restaurant(Ceiling Height 13 ft.) 887 2.27(a) 2013
Common Space Types:Restrooms(Ceiling Height 8 ft.) 112 0.82 92
p.
Common Space Types:Food Preparation(Ceiling Height 10 ft.) 1151 1.07 1232
Common Space Types:Corridor/Transition(Ceiling Height 11 ft.) 120 0.41 49
ft Total Allowed Watts= 3386
(a) Allowed watts per sq.ft.adjusted for ceiling height.
Section 3: Interior Lighting Fixture Schedule
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Common Space Types:Dining Area;Family Restaurant(887 sq.ft.)
Compact Fluorescent:Al:Decorative Pendant:Other:Electronic: 4 1 112 112
Compact Fluorescent copy 1:A3:Decorative Pendant:Other:Electronic: 4 2 84 168
Compact Fluorescent:C:6"Recessed Downlight:Other:Electronic: 1 1 28 28
LED:GGA:Decorative Pendant:LED PAR 7W: 1 5 7 35
LED:K6/K6E:LED Track Head:LED MR 10W: 1 14 10 140
Common Space Types:Restrooms(112 sq.ft.)
Compact Fluorescent:C&CE:6"Recessed Downlight:Other:Electronic: 1 4 28 112
Compact Fluorescent:M:Decorative Overmirror Light:Quad 2-pin 13W:Electronic: 2 2 32 64
Common Space Types:Food Preparation(1151 sq.ft.)
Compact Fluorescent:D&DE:8"Recessed Downlight:Other:Electronic: 2 13 55 715
Linear Fluorescent:F&FE:2'X 4'Troffer:48"T8 32W:Electronic: 3 7 93 651
Linear Fluorescent:FC:Cooler Light:Other:Electronic: 2 2 62 Exempt
K Exemption:Lighting in Refrigerator/Freezer Cases
LED:JL:Decorative Pendant:Other: 1 7 6 42
LED:L:Decorative Pendant:LED MR 10W: 1 1 10 10
Track lighting copy 1:K1-(K2):TRACK:Wattage based on 10 feet of track 0 0 500 500
Common Space Types:Corridorlfransition(120 sq.ft.)
Track lighting:K3-(K4):TRACK:Wattage based on 10 feet of track 0 0 500 500
LED:K6/K6E:LED Track Head:LED MR 10W: 1 1 10 10
Compact Fluorescent copy 1:C:6"Recessed Downlight:Other:Electronic: 1 1 28 28
Total Proposed Watts= 3115
Project Title: Noodles Company Store#819 Report date: 02/04/15
Data filename: H:\14008.33\PORTLAND.CCK Page 1 of 3
Section 4: Requirements Checklist
In the following requirements,blank checkboxes identify requirements that the applicant has not acknowledged as being met.Checkmarks
identify requirements that the applicant acknowledges are met or excepted from compliance. 'Plans reference page/section'identifies where in
the plans/specs the requirement can be verified as being satisfied.
Lighting Wattage:
• 1. Total proposed watts must be less than or equal to total allowed watts.
Allowed Wattage:3386 Proposed Wattage:3115
Complies:YES
Mandatory Requirements:
✓ 2. Exit signs.Internally illuminated exit signs shall not exceed 5 watts per side.
Plans reference page/section: E1.0&E1.3
• 3. Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general area lighting
in the non-daylight zone.In all individual daylight zones larger than 350 sq.ft.,automatic daylight controls is provided.Automatic
daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic OFF control,
while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be controlled by a
single controlling device provided that they do not include zones facing more than two adjacent cardinal orientations(i.e.,north,east,
south,west).Daylight zones under skylights shall be controlled separately from daylight zones adjacent to vertical fenestration.
Exception applies:Display,exhibition and specialty lighting
Plans reference page/section: E1.0
✓ 4. Interior lighting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor area and
each area enclosed by walls or floor-to-ceiling partitions.The required controls are located within the area served by the controls or are
a remote switch that identifies the lights served and indicates their status.
Plans reference page/section: E1.0
✓ 5. Sleeping unit controls.Master switch at entry to hotel/motel guest room.
0 Plans reference page/section: NA
✓ 6. Egress lighting.Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut off during
periods that the building space served by the means of egress is unoccupied.
Plans reference page/section: E1.0
✓ 7. Additional controls.Each area that is required to have a manual control shall have additional controls that meet the requirements of
Sections 505.2.2.1 and 505.2.2.2.
Plans reference page/section: E1.0
✓ 8. Light reduction controls.Each space required to have a manual control also allows for reducing the connected lighting load by at least
50 percent by either
1)controlling(dimming or multi-level switching)all luminaires;or
2)dual switching of alternate rows of luminaires,alternate luminaires,or alternate lamps;or
3)switching the middle lamp luminaires independently of other lamps;or
4)switching each luminaire or each lamp.
Plans reference page/section: E1.0
✓ 9. Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This automatic
control device shall function on either:
1)a scheduled basis,using time-of-day,with an independent program schedule that controls the interior lighting in areas that do not
exceed 10,000 square feet and are not more than one floor;or
2)an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;or
3)a signal from another control or alarm system that indicates the area is unoccupied.
Plans reference page/section: E1.0
• 10.Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation.
Plans reference page/section: NA
✓ 11 An occupant sensor control device is installed that automatically turns lighting off within 30 minutes of all occupants leaving a space.
Plans reference page/section: E1.0
• 12Additional controls.An occupant sensor control device that automatically turns lighting off within 30 minutes of all occupants leaving a
space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated is installed in all storage and
supply rooms up to 1000 square feet.
Project Title: Noodles Company Store#819 Report date: 02/04/15
Data filename: H:\14008.33\PORTLAND.CCK Page 2 of 3
Plans reference page/section: NA
✓ 13.Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override switching device
that: 1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled by that switch,or
so that the area being lit is annunciated,3)is manually operated,4)allows the lighting to remain on for no more than 2 hours when an
override is initiated,and 5)controls an area not exceeding 2,000 square feet.
Plans reference page/section: E1.0
✓ 14.Holiday scheduling.Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday scheduling feature
that turns off all loads for at least 24 hours,then resumes the normally scheduled operation.
I Exception applies:Retail stores and associated malls,restaurants,grocery stores,places of religious worship,theaters and
exterior lighting zones.
Plans reference page/section: NA
✓ 15.Exterior lighting controls.Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a
photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by
an astronomical time switch or photosensor.
Plans reference page/section: E1.0
✓ 16.Tandem wiring.The following luminaires located within the same area shall be tandem wired:
1.Fluorescent luminaires equipped with one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet
center-to-center of each other.
2.Fluorescent luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted
within 1 foot edge-to-edge of each other.
Plans reference page/section: E1.0
✓ 17.Medical task lighting or art/history display lighting claimed to be exempt from compliance has a control device independent of the control
of the nonexempt lighting.
Plans reference page/section: NA
✓ 18.Each dwelling unit in a building is metered separately.
Plans reference page/section: E2.0
Interior Lighting PASSES
Section 5: Compliance Statement
Compliance Statement: The proposed lighting design repres- ed in this doc ent' consistent ' the .uilding plans,specifications and
other calculations submitted with this permit application.Th• proposed lighting s m has been desi.'e' o meet the 2010 Oregon Energy
Efficiency Specialty Code requirements in COMcheck Ver.ion 3.9. and to comp y Nrith the mandatory r:. irements in the Requirements
Checklist.
Davis L. Dickerson, PEj, 02/04/2015
Name-Title Sign. Date
Project Title: Noodles Company Store#819 Report date: 02/04/15
Data filename: H:\14008.33\PORTLAND.CCK Page 3 of 3