Plans (42) ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE 1. WHERE ALL TERMINALS OF THE DISCONNECTING - AC ALTERNATING CURRENT MEANS MAY BE ENERGIZED IN THE OPEN POSITION, BLDG BUILDING A SIGN WILL BE PROVIDED WARNING OF THE CONC CONCRETE HAZARDS PER ART. 690.17. - DC DIRECT CURRENT 2. EACH UNGROUNDED CONDUCTOR OF THE EGC EQUIPMENT GROUNDING CONDUCTOR MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY (E) EXISTING PHASE AND SYSTEM PER ART. 210.5. s,. EMT ELECTRICAL METALLIC TUBING 3. A NATIONALLY—RECOGNIZED TESTING GALV GALVANIZED LABORATORY SHALL LIST ALL EQUIPMENT IN )i. GEC GROUNDING ELECTRODE CONDUCTOR COMPLIANCE WITH ART. 110.3. CITY OF TIGARD . GND GROUND 4. CIRCUITS OVER 250V TO GROUND SHALL REVIEWID FOR CODE COMPLIANCE HDG HOT DIPPED GALVANIZED COMPLY WITH ART. 250.97, 250.92(B) Approved:I CURRENT 5. DC CONDUCTORS EITHER DO NOT ENTER PP [ a� Imp CURRENT AT MAX POWER BUILDING OR ARE RUN IN METALLIC RACEWAYS OR OTC: [ I Isc SHORT CIRCUIT CURRENT ENCLOSURES TO THE FIRST ACCESSIBLE DC Pcrtnit#�: IA/672.6(A-- kVA KILOVOLT AMPERE DISCONNECTING MEANS PER ART. 690.31(E). Address: �( kW KILOWATT 6. ALL WIRES SHALL BE PROVIDED WITH STRAIN � � U LBW LOAD BEARING WALL RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY Suite MIN MINIMUM UL LISTING. (N) NEW 7. MODULE FRAMES SHALL BE GROUNDED AT THE By: .molb-,...M.�� Date: 7 (k-- (N) NEUTRAL UL—LISTED LOCATION PROVIDED BY THE NTS NOT TO SCALE MANUFACTURER USING UL LISTED GROUNDING OC ON CENTER HARDWARE. � PL PROPERTY LINE 8. MODULE FRAMES, RAIL, AND POSTS SHALL BE OFFICE COPY P0! POINT OF INTERCONNECTION BONDED WITH EQUIPMENT GROUND CONDUCTORS AND PV PHOTOVOLTAIC GROUNDED AT THE MAIN ELECTRIC PANEL. SCH SCHEDULE 9. THE DC GROUNDING ELECTRODE CONDUCTOR SS STAINLESS STEEL SHALL BE SIZED ACCORDING TO ART. 250.166(B) & STC STANDARD TESTING CONDITIONS 690.47. TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V VOLT Vmp VOLTAGE AT MAX POWER VoW c WATTAGE AT OPEN CIRCUIT VICINITY MAP INDEX 3R NEMA 3R, RAINTIGHT •. "i _-- i ty PV1 COVER SHEET PV2 SITE PLAN PV3 STRUCTURAL VIEWS 4 "°•` PV4 UPLIFT CALCULATIONS LICENSE GENERAL NOTES '# `` . -� PV5 THREE LINE DIAGRAM i w 3 � ' °�/ZO PV6 ELECTRICAL CALCULATIONS SW McDonald St - 1"" •®'' -ax creek Cutsheets Attached OR # 180498 1. THIS SYSTEM IS GRID—INTERTIED VIA A RGC, CGC1 UL—LISTED POWER—CONDITIONING INVERTER. 1 1 _ 8' I 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. ' � ` 3. SOLAR MOUNTING FRAMES ARE TO BE _ le ,. GROUNDED. — 4. ALL WORK TO BE DONE TO THE 2010 OBC `.. - MODULE GROUNDING METHOD: ZEP SOLAR BASED ON THE 2009 IBC. " ` 5. ALL ELECTRICAL WORK SHALL COMPLY WITH f trr, *` REV BY DATE COMMENTS AHJ: Tigard THE CURRENT NATIONAL ELECTRIC CODE AS • 1'""' r AMENDED BY THE OREGON ELECTRICAL SPECIALTY '' ' ,,,,,��DATE COMMENTS CODE. C ' , �. _ rt .. ®®® UTILITY: Portland General Electric ,,, ,T._ � L ,„,1=111.© Ilii 1 I -i- � _ ®®® a, and Oregon, 'State-471 Oregon, U.S. Geological Survey®®® CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: J B-9721935 0 O PREMISE OWNER: DESCRIPTION: DESIGN:CONTAINED SHALL NOT BE USED FOR THE KUESTER, ROBERT KUESTER RESIDENCE Aaron Banks \ ,S SolarCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 8450 SW COLONY CREEK CT �'�"� NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Com Mount Type C 5.75 KW PV Array /1‘ PART TO OTHERS OUTSIDE THE RECIPIENTS p ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: TIGARD, OR 97224 THE SALE AND USE OF THE RESPECTIVE (23) CANADIAN SOLAR # CS6P-250PX 3055 Clearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER: 5036202648 T:(650)638-1028 F:(650) 638-1029 POWER—ONE ; AURORA PVI-5000—OUTD—US—Z—A COVER SHEET PV 1 4 21 2014 / / (888)-SOL-CITY(765-2489)www.solarcity.com PITCH: 18 ARRAY PITCH:18 MP1 AZIMUTH: 180 ARRAY AZIMUTH: 180 8450 SW Colony Creek Ct MATERIAL: Comp Shingle STORY: 1 Story (E) DRIVEWAY ATTACHMENTS SHALL BE SPACED NO GREATER THAN 24 INCHES ON CENTER Front Of House IN ANY DIRECTION WHERE ARRAY is LOCATED WITHIN 3 FEET OF A ROOF tDGE,HIP, EAVE OR RIDGE, 3SISC 305.1.3 iBi 0 0 AC LEGEND -- -- �� O (E) UTILITY METER & WARNING LABEL I 0,-.-\ D i INVERTER W/ INTEGRATED DC DISCO I ..-' l 0 & WARNING LABELS I-1 DC DISCONNECT & WARNING LABELS I-I AC DISCONNECT & WARNING LABELS 0 DC JUNCTION/COMBINER BOX & LABELS • DISTRIBUTION PANEL & LABELS 12"Fire Setback u`" L v--M-P1 J Lc LOAD CENTER & WARNING LABELS ODEDICATED PV SYSTEM METER - L__. 1j1j - .ffi U STANDOFF LOCATIONS - - - CONDUIT RUN ON EXTERIOR l --- CONDUIT RUN ON INTERIOR - _ o - - L GATE/FENCE . O HEAT PRODUCING VENTS ARE RED 1-;,---1 11 ;1 INTERIOR EQUIPMENT IS DASHED L.J a SITE PLAN N • PV3 TOTAL ARRAY AREA (SF): 406 Scale: 1/8" = 1' �, TOTAL ROOF AREA (SF): 2692 w `r E TOTAL ARRAY AREA IS 15.1 0 1' 8' 16' PERCENT OF TOTAL ROOF AREA mel, . s CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: J 3-9721 935 0 0 PREMISE OWNER: DESCRIPTION: DESIGN: KUESTER,E S TE R, ROBERT \��t,. ■ CONTAINED SHALL NOT BE USED FOR HE KUESTER RESIDENCE Aaron Banks SoIarCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 8450 SW COLONY CREEK CTA.,„ NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C KW PV Array rl‘ • PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: TIGARD, OR 97224 THE SALE AND USE OF THE RESPECTIVE (23) CANADIAN SOLAR # CS6P-250PX 3055 Clearvew Way THE LTY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER: 5036202648 T:(650)638-1028 F:(650)638-1029 POWER-ONE # AURORA PVI-5000-OUTD-US-Z-A SITE PLAN PV 2 4/21/2014 (888)-SOL-CITY(765-2489)www.sdarcity.com Si °°°°III.III."°°llillIllijll'il (E) 2x4 9 \I - ___,---1-- PRE—MANUFACTURED TRUSS /1'-6'74 7' / 6'-1" / STRUCTURE MEETS THE • (E) LBW PRESCRIPTIVE REQUIREMENTS OF THE OSISC SECTION 305.4 SIDE VIEW OF MP1 NTS A MPl X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES LANDSCAPE 72" 24" STAGGERED PORTRAIT 48" 19" RAFTER: 2x4 @ 24" OC ROOF AZI 180 PITCH 18 STORIES: 1 ARRAY AZI 180 PITCH 18 C.J.: 2x4 @24" OC Comp Shingle PV MODULE 5/16" BOLT WITH LOCK INSTALLATION ORDER & FENDER WASHERS LOCATE RAFTER, MARK HOLE ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT ZEP ARRAY SKIRT (6) HOLE. (4) --- SEAL PILOT HOLE WITH POLYURETHANE SEALANT. ZEP COMP MOUNT C , ' It____ / ZEP FLASHING C illit �NIL�FM �� (3) INSERT FLASHING. (E) COMP. SHINGLE imiiiiii1 iw (4) PLACE MOUNT. (E) ROOF DECKING NM 1111111111 (5) INSTALL LAG BOLT WITH 5/16" DIA LAG BOLT (5) SEALING WASHER. WITH SEALING WASHER LOWEST MODULE SUBSEQUENT MODULES — INSTALL LEVELING FOOT WITH (2-1/2" EMBED, MIN) (6) BOLT & WASHERS. (E) RAFTER . 4101 STANDOFF Scale: 1 1/2" = 1' J 3—9721935 0 0 PREMISE OVER: DESCRIPTION: DESIGN: CONFIDENTIAL— THE INFBEORMATION HEREIN JOB NUMBER: KUESTER, ROBERT KUESTER RESIDENCE Aaron Banks = .� CONTAINEDEEFIT OFSHALL NOT EXCEPT USED FOR THE SolarCityBENEFIT ANYONE SOLARCITY INC., MOUNTING SYSTEM: 8450 SW COLONY CREEK CT • NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C KW PV Array PART OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD OR 97224 ORGANIZATION, EXCEPT IN CONNECTION WITH ' THE SALE AND USE OF THE RESPECTIVE (23) CANADIAN SOLAR # CS6P-250PX 3055 Cleorview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER: 5036202648 T:(650)638-1028 F:(650)638-1029 POWER–ONE # AURORA PVI-5000–OUTD–US–Z–A STRUCTURAL VIEWS PV 3 4/21/2014 (888)—SOL—CITY(765-2489) www.solarcity.com UPLIFT CALCULATIONS 04.21.2014 SolarCity SleekMountTM PV System Version#34.3 Structural Design Software Project Information&Table Of Contents - Risk Category: II PV System Type SolarCity SleekMount"" Comp Roof Comp Roof Layers of Comp Roofing 1 . Roof Slope 18° Rafter Spacing 24"O.C. PV System Module Orientation Landscape and Portrait PV Module Area 398 sf PV Module Width 39" PV Module Length 64" Standoff(Attachment Hardware) Comp Mount Type C Reduced Ground/Roof Live/Snow Loads Ground Snow Load pg 25.0 psf "ASCE Table 7-1 Surrounding Roof Snow 100% 25.0 psf 'ASCE Eq:7.4-1 Roof Snow Over PV Modules 100% 25.0 psf 'ASCE Eq: 7.4-1 Wind Design Criteria Wind Design Code ASCE 7-05 • Wind Design Method Partially/Fully Enclosed Method Basic Wind Speed V 95 mph Fig.6-1 Exposure Category C ' Section 6.5.6.3 Roof Style Gable Roof 'Fig.6-11B/C.rD-14A/B Mean Roof Height h 15 ft Section 6.2 Effective Wind Area(1 Module) A 17.3 sf IBC 1509.7.1 Wind Pressure Calculation Coefficients Wind Pressure Exposure Kz 0.85 Table 6-3 Topographic Factor Kzt 1.00 Section 6.5.7 Wind Directionality Factor Kd 0.85 Table 6-4 Importance Factor I 1.0 Table 6-1 Velocity Pressure qh qh =0.00256(Kz)(Kzt)(Kd)(V^2)(I) Equation 6-15 16.7 psf Ext.Pressure Coefficient(Up) GCp(Up) -0.88 Fig.6-1113:C/D-14A1B Ext.Pressure Coefficient(Down) GCp(Down) 0.45 Fig.6-11B/C/D-14A/B Design Wind Pressure p p= qh(GCp) Equation 6-22 Wind Pressure Up p(up) -14.6 psf Wind Pressure Down p(down) 10.0 psf Allowable Standoff Spacings X-Direction Y-Direction Max Allowable Standoff Spacing Landscape 72" 39" Max Allowable Cantilever Landscape 24" NA Standoff Configuration Landscape Staggered Max Standoff Tributary Area Trib 19 sf PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -249 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capaaty DCR 49.8% Max Allowable Standoff Spacing Portrait 48" 64" Max Allowable Cantilever Portrait 19" NA Standoff Configuration Portrait Staggered Max Standoff Tributary Area Trib 21 sf PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -277 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capacity DCR 55.4% 1 PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL THE INFBEORMATION HEREIN JOB NUMBER: JB-972 I g35 0o KUESTER, ROBERT KUESTER RESIDENCE Aaron Banks �\\ BENEFIT OF SHALL NOT EXCEPT USED FOR THE SolarCity BENEFIT ANYONE SOLARCITYT INC., MOUNTING SYSTEM: I.•„•. NOR RTSHALL OTHERS DISCLOUTSIOSED E IN RECIPIENTS IN Comp Mount Type cPA8450 SW COLONY CREEK CT 5.75 KW PV Array Pr ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: TIGARD, OR 97224 THE SALE AND USE OF THE RESPECTIVE (23) CANADIAN SOLAR # CS6P-250PX 3055 Clearvew Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER: 503620264Q T:(650)638-1028 F:(650)638-1029 POWER—ONE # AURORA PVI-5000—OUTD—US—Z—A L 8 UPLIFT CALCULATIONS PV 4 4/21/2014 (888)—SOL—CITY(765-2489)www.solarcHycom GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #8 GEC TO (E) GROUND ROD Panel Number:Square D Inv 1: DC Ungrounded INV 1 —(1)POWER—ONE AURORA P41-5000—OUTD—US—Z—A LABEL: A —(23)CANADIAN SOLAR__# CS6P-25OPX OR # 180498 Z AT PANEL WITH IRREVERSIBLE CRIMP Meter Number:24 542 547 FCI Inverter; igbee 5000W, 240V, 96.5% PV Module; 250W 229.6W PTC, 40mm, Black Frame, MC4, ZEP Enabled RGC, CGC1 Underground Service Entrance INV 2 Voc: 37.2 Vpmax: 30.1 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER (E) 200A MAIN SERVICE PANEL Multiple Main Breakers (6 or fewer) Inverter 1 IND (E) WIRING COOPER CUTLER—HAMMER I Meter Socket Disconnect ® POWER—ONE 1 DC+ DO NOT ADJUST MIN.ACTIVATION V LTAGE AURORA PVI-5000—OUTD US—Z—A DC- 1 Stnng(s)Of 12 On MP 1 (E) LOADS A g r EGC J n �. . — n Li I 2407, --— ■ • , . �r L2 DC, . N I, 30A/2P , r......_— DC-I -- GND 1T GND — EGG ___— DC+ I X DC, DO NOT ADJUST MIN.ACTIVATION V LTAGE /I� I 1 1 String(s)Of 11 On MP 1 I� IA ��� I -- A Z�f— GEC -1 DC- DC- —. /( p B I EGC (1)Conduit Kit; 1" EMT N — J EGCIGEC —j Z—z CD GEC -, TO 120/240V I SINGLE PHASE UTILITY SERVICE Voc* = MAX VOC AT MIN TEMP POI_(1)SQUARE D 3'##Q 230 30A /2P BREAKER A —(1)COOPER #B—Line Meter Socket 011 /k H D Breaker, 30A/2P, 2 Spaces, Plug—On Meter Socket; 125A, 4-14AWG, Ring Type _(1)AW CAP; B—Line Meter Socket Accessory —(2)SQUARE D f Q012020 30A /2P BREAKER —(1)MMBer; #OR L20S Breaker, 20A/1P-20A/1P, 1 Space, Plug—On, Tandem B (1)CUTLER-HAMMER #DG221URB B Disconnect; 30A, 24OVac, Non—Fusible, NEMA 3R —(1)CUTLER—HAMMER 1!DGO3ONB Ground/Neutral Kit; 30A, General Duty(DG) (1)AWG#10, THWN-2, Black (2)AWG#10, PV 1MRE, Black Voc* =504.38VDC Isc =8.87 ADC ' O 6..l—(1)AWG#10, THWN-2, Red O L$—(1)AWG #6, Stranded Bare Copper EGC Vmp =361.2 VDC Imp=8.3 ADC 1111 (1)AWG#10, THWN-2, White NEUTRAL Vmp =240 VAC Imp=23 MC 6 (1)Conduit Kit; 3/4" EMT . , , _-(1)AWG#t3,.THWN-2,_Greeq . EGC/GEC.-(1)Conduit,Kit;,3/4".EMT. . . . . . . . . O 2 (2)AWG #10, PV WIRE, Black Voc* =462.35VDC Isc =8.87 ADC oo 1)AWG)AWG #6, Stranded Bare Copper EGC Vmp =331.1 VDC Imp=8.3 ADC ( )Conduit Kit; 3/4" EMT . I CONFIDENTIALTHE INFORMATION HEREIN JOB NUMBER: J3-9721935 00 PREMISE OWNER: DESCRIPTION: DESIGN:KUESTER, ROBERT KUESTER RESIDENCE Aaron Banks �\\`• CONTAINEDEEFIT SHALL NOT BE USED THE SolarCity BENEFIT OF ANYONE EXCEPT DSOLARCITYFOR INC., MOUNTING SYSTEM: �.�„ NNOR ORTSHO OTHERS DISCLOUTSIOSED IN E WHOLE IN Comp Mount Type C 8450 SW COLONY CREEK CT 5.75 KW PV Array ►,,� TS ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: TIGARD, OR 97224 THE SALE AND USE OF THE RESPECTIVE (23) CANADIAN SOLAR # CS6P-250PX 3055 Clearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER: 5036202648 T:(650)638-1028 F:(650)638-1029 POWER-ONE # AURORA PVI-5000-OUTD-US-Z-A THREE LINE DIAGRAM PV 5 4/21/2014 (888)—SOL—CITY(765-2489)www.solarcity.com Label Location: Label Location: Label Location: CAUTION: SOLAR CIRCUIT (C)(IC)(CB) MAXIMUM AC A (AC) (P01) CAUTION (P01) Per Code: OPERATING CURRENT Per Code: DUAL POWER SOURCE Per Code: IFC 605.11.1.4 MAXIMUM AC _ v NEC 690.54 SECOND SOURCE IS NEC 690.64.8.4 OPERATING VOLTAGE PHOTOVOLTAIC SYSTEM Label Location: PHOTOVOLTAIC DC (DC) (INV) DISCONNECT Per Code: NEC 690.14.C.2 Label Location: Label Location: PV SYSTEM (AC) WARNING (DC) (INV) DISCONNECT FOR Per Code: • UTILITY OPERATION ELECTRIC SHOCK HAZARD NEC 690.35(F) Label Location: THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN MAXIMUM POWER--A (DC) (INV) ) UNGROUNDED AND POINT CURRENT(Imp) Per Code: MAY BE ENERGIZED INVERTER IS MAXIMUM POWER-_V NEC 690.53 UNGROUNDED POINT VOLTAGE(Vmp) MAXIMUM SYSTEM-V Label Location: VOLTAGE(Voc) WARNING (AC) (P01) SHORT-CIRCUIT_A Per Code: CURRENT(Isc) ELECTRIC SHOCK HAZARD NEC 690.17(4) DO NOT TOUCH TERMINALS TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION Label Location: WARNING (DC) (CB) Per Code: ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS NEC 690.17(4) Label Location: TERMINALS ON BOTH LINE AND WARNING (P01) LOAD SIDES MAY BE ENERGIZED Per Code: IN THE OPEN POSITION INVERTER OUTPUT NEC 690.64.B.7 DC VOLTAGE IS CONNECTION ALWAYS PRESENT WHEN DO NOT RELOCATE • SOLAR MODULES ARE THIS OVERCURRENT EXPOSED TO SUNLIGHT DEVICE Label Location: Label Location: WARNING (DC) (INV) PHOTOVOLTAIC POINT OF (P01) Per Code: INTERCONNECTION Per Code: ELECTRIC SHOCK HAZARD NEC 690.5(C) WARNING: ELECTRIC SHOCK NEC 690.17.4; NEC 690.54 IF A GROUND FAULT IS INDICATED HAZARD. DO NOT TOUCH NORMALLY GROUNDED TERMINALS.TERMINALS ON CONDUCTORS MAY BE BOTH THE LINE AND LOAD SIDE UNGROUNDED AND ENERGIZED MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER. PV POWER SOURCE Label Location: MAXIMUM AC _ A AC (P01) OPERATING CURRENTAC PHOTOVOLTAIC AC (AC) MAXIMUM AC (AC):): Conduit Disconnect DISCONNECT Per Code: OPERATING VOLTAGE V (C): : Com NEC 690.14.C.2 (CB): Combiner Box (D): Distribution Panel (DC): DC Disconnect (IC): Interior Run Conduit Label Location: (INV): Inverter With Integrated DC Disconnect CAUTION (D) (P01) (LC): Load Center Per Code: PHOTOVOLTAIC SYSTEM NEC 690.64.B.4 (M): Utility Meter CIRCUIT IS BACKFED (P01): Point of Interconnection . CONFIDENTIAL— THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR 044 THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED mi..'��� 3055 Cleaview Way IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, SC - OR Label Set ; ■ San Mateo,CA 94402 EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE 'r, So1arC�ty -SOL-)638-1028 F:(650)638-1029 (888)-SOL-CITY(765-2489)wwwsolarcity.com SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. a ZS Comp Edge Zone Calculations 1 of 4 ZS Comp Edge Zone Calculations 2 of 4 5/28/13 5/28/13 ZepSoLar ZepSolar This set of calculations is intended to show that ZS Comp has sufficient strength to allow for attachment Down Force Spacing spacings of at least 48"in Edge Zones whether the modules are orientated in landscape or portrait.The Allowable Down Force Load down force spacing = calculations will vary the design variables to account for the worst case for each failure mode that is being module width x design load checked. • Wind Down Calculations All variable the same as above except for roof pitch General Design Information: Roof Pitch Module Size: 39"x 65" Basic Wind Speed= 95 mph 14 30 45 System Weight= 3 psf Ground Snow Load= 30 psf GCN landscape= 0.5 0.9 0.9 GCN portrait= 0.4 0.9 0.9 Comp Mount Allowable Loads Uplift= 656 lbs design load landscape= 9.62 17.32 17.32 psf Lateral= 436 lbs design load portrait= 7.70 17.32 17.32 psf Down Force= 1147 lbs • 'Ro Oil note:use 10 psf minimum Ae 17-,714:Fell l Snow Calculations Attachment Spacing Calculations 85818 VI To account for unbalanced snow loads,ground snow loads will be used for roof pitches 30 degrees and Uplift Spacing OREGON o lower.Per section 7.6.1 of ASCE 7-10 unbalanced snow loads do not need to be considered for slopes 4y1, zti h' above 30 degrees. Allowable Uplift Load FR m, ot. uplift spacing= fMr Ro module length or width x design load EXPIRES: 12/31/14 Ground Snow Load= 30 psf Wind Uplift Calculations FOR PAGES 1-4 Roof Pitch ASCE 7-05 Method 2 14 30 Design Snow Load 29.11 25.98 psf p=ghGCN qh=0.00256 lc K„Kd V2 I (snow load spread over the length of the rafter) Basic Wind Speed= 95 mph Down Force Load Roof Pitch Exposure= C Roof Zone= Edge Zone Combinations: 14 30 Importance Factor= 1.0 KZ= 0.98 from Table 6-3 D+S= 31.16 25.10 psf Gable/Hip Roof KZt= 1.0 per 6.5.7.2 D+W= 12.91 19.92 psf /orst Case Roof Pitch= 14 degrees Kd= 0.85 from Table 6-4 D+0.75W+0.755 31.59 32.46 psf Roof Height= 30 GCN landscape= -1.6 iscape effective area= 13.0 ft2 GCN portrait= -1.5 landscape down force spacing = 39"x 32.46psf x 144 in = 130" ortrait effective area= 21.7 ft2 Plandscape= -30.79 psf qh= 19.25 psf Pportrait= -28.87 psf 11471bs in portrait down force spacing = 65"x 32.46psf x 144 ft2 = 78" Uplift Load Combination:0.6D+W(ASCE Section 2.4.1 equation 7) design load landscape= -29.05 psf design load portrait= -27.12 psf 656 lbs in landscape uplift spacing = 39"x 29.05 psf x 144 ft2 =83" 656 lbs in portrait uplift spacing = 65"x 27.12 psf x 144 ft2 = 54" ZS Comp Edge Zone Calculations 3 of 4 ZS Comp Edge Zone Calculations 4 of 4 5/28/13 5/28/13 ZepSolor ZepSolar Lateral Spacing Module Deflection Spacing The lateral force on the system increases as the pitch of the roof increases,but the amount of snow on landscape module spacing = -1.4545 x Maximum Uplift or Down Force Pressure+120.7273 the roof decreases for slopes greater than 30 degrees.With this in mind,the lateral force will be checked • at 30 degrees with ground snow load and 45 degrees with sloped roof snow. portrait module spacing =-1.7917 x Maximum Uplift or Down Force Pressure+118.58 Allowable Lateral Load lateral spacing= module width x design load Maximum Uplift of Down Force Pressure= 32.46 psf Snow Calculations Ground Snow Load= 30 psf landscape module spacing = -1.4545 x 32.46 psf+120.7273 =73" P5=C5 Pf Roof Pitch= 31 45 degrees pf=0.7 Ce Ct I pg Ce= 0.9 C5= 0.71 0.45 portrait module spacing=-1.7917 x 32.46 psf+118.58 = 60" Ct= 1.2 pf= 22.68 22.7 psf I= 1.0 p5= 16.1 10.2 psf Calculation Summary Calculated Edge Zone Spacing Roof Pitch Spacing Check Landscape Portrait 27 30 31 45 Uplift 83" 54" Design Snow Load 26.73 25.98 13.80 7.22 psf Down Force 130" 78" (snow load spread over the length of the rafter) 30° 27° 30° Lateral 74" 48" 45" Lateral Force Component Module Deflection 73" 60" Down Force Load Roof Pitch Combinations: 27 30 31 45 As can be seen in the table above,for Design Wind Speeds up to 95 mph and Ground Snow Loads up to 30 D+S= 13.50 14.49 8.65 7.22 psf psf with modules orientated in landscape,the system is strong enough to be installed at 72"on center in D+0.75W+0.75S 10.46 11.24 6.88 5.95 psf the Edge Zone.When modules are installed in portrait,the spacing for edge zone installations can be 48" on center for most roof pitches.For roof pitches that are greater than 27°but less than 31°,the maximum 30 degree roof pitch attachment spacing is 45". a lateral spacing 294.49 psf in landscape p g 39"x 14.49 x 144 Ft2 = 74" portrait lateral spacing = 65"x 14149 psf x 144 ft2 =45" Portrait spacing is less than 48".Try roof pitch of 27 degrees / 2921bs in portrait lateral spacing = 65"x 13.50 psf x 144 ft2 =48" SolarCity SleekMountTM - Comp SolarCity SleekMountTM - Comp The SolarCity SleekMount hardware solution •Utilizes Zep Solar hardware and UL 1703 listed `t Installation Instructions is optimized to achieve superior strength and Zep CompatibleTM modules ' aesthetics while minimizing roof disruption and • Drill Pilot Hole of Proper Diameter for labor.The elimination of visible rail ends and •Interlock and grounding devices in system UL t listed to UL 2703 Fastener Size Per NDS Section 1.1.3.2 mounting clamps, combined with the addition . of array trim and a lower profile all contribute •Interlock and Ground Zep ETL listed to UL 1703 . Seal pilot hole with roofing sealant to a more visually appealing system.SleekMount as"Grounding and Bonding System" ` Insert CompMount flashingunder upper ,l utilizes Zep CompatibleTM modules with •Ground Zep UL and ETL listed to UL 467 as layer of shingle strengthened frames that attach directly to grounding device • Zep Solar standoffs,effectively eliminating the Place Comp Mount centered need for rail and reducing the number of •Painted galvanized waterproof flashing upon flashing Standoffs required. In addition, composition •Anodized components for corrosion resistance • Install lag pursuant to NDS Section 11.1.3 shingles are not required to be cut for this system,allowing for minimal roof disturbance. •Applicable for vent spanning functions with sealing washer. \ • Secure Leveling Foot to the Comp Mount using machine Screw • Place module c' t • Components .mii11" _ • 5/16"Machine Screw . Leveling Foot _, • Lag Screw ® • Comp Mount • Comp Mount Flashing • *' O 0^ 1' / o 0 Fall ..e*,',,, 0,4,TSA `Ii i14I p, SolarCity ` F ETA ® :` SolarCity o January 2013 LISTED 14; tomo m January 2013 e N �`c.d�epes�g° 1 0 CS6P-235/240/2451250/255PX $e�„�o.6b*ca� �r CanadianSolar Electrical Data Black-framed 03 STC CS6P-235PXCS6P-240PXCS6P-245PXCS6P-250PXCS6P-255PX Temperature Characteristics „v Nominal Maximum Power(Pmax) 235W 240W 245W 250W 255W ,// Nw w C d g e Optimum Operating Voltage(Vmp) 29.8V 29.9V 30.0V 30.1V 30.2V Pmax -0.43%/°C 'v G C Optimum Operating Current(Imp) 7.90A 8.03A 8.17A 8.30A 8.43A Temperature Coefficient Voc -0.34%/°C Open Circuit Voltage(Voc) 36.9V 37.W 37.1V 37.2V 37.4V Isc 0.065%/°C Ba c k-framed C S 6 P Short Circuit Current(lsc) 8.46A 8.59A 8.74A 8.87A 9.00A Normal Operating Cell Temperature 45±2°C 1 - Module Efficiency 14.61% 14.92% 15.23% 15.54% 15.85% _ Operating Temperature -40°C-+85°C Performance at Low Irradiance 235/240/245/250/255PX Maximum System Voltage ,000vuec)/600vaL) Industry leading performance at low irradiation Maximum Series Fuse Rating 15A environment,+95.5%module efficiency from an Application Classification ClassA irradiance of 1000w/m'to 200w/m' it-1 Power Tolerance 0-+5W (AM 1.5,25'C) Next Generation Solar Module Under Standard Test Conditioeb(STC)of irradiance of 1000W/m',spectrum AM 1.5 and cell temperature of 25'C NewEdge,the next generation module designed for multiple -- Engineering Drawings NOCT CS6P-235PXCS6P-240PXCS6P-245PX CS6P-250PX CS6P-255PX types of mounting systems,offers customers the added Nominal Maximum Power(Pmax) 170W 174W 178W 181W 185W value of minimal system costs,aesthetic seamless Optimum Operating Voltage(Vmp) 27.2V 27.3V 27.4V 27.5V 27.5V I - appearance,auto groundingand theft resistance. Optimum operating current(Imp) 6.27A 6.38A 6.49A 6.60A 6.71A Open Circuit Voltage(Voc) 33.9V 34.OV 34.1V 34.2V 34.4V The black-framed CS6P-PX is a robust 60 cell solar module Short Circuit Current(Isc) 6.86A 6.96A 7.08A 7.19A 7.29A incorporating the groundbreaking Zep compatible frame. Under Normal Operating Cell Temperature,Irradiance of eoo W/m',spectrum AM 1.5,ambient temperature z0'C, The specially designed frame allows for rail-free fast wind speed 1 m/s installation with the industry's most reliable grounding Mechanical Data system.The module uses high efficiency poly-crystalline Cell Type Poly-crystalline 156 x 156mm,2 or 3 Busbars Key Features silicon cells laminated with a white back sheet and framed Cell Arrangement 60(6 x 10) with black anodized aluminum.The black-framed CS6P-PX Dimensions 1638 x 982 x 40mm(64.5 x 38.7 x 1.57in) - • Quick and easy to install - dramatically is the perfect choice for customers who are looking for a high Weight 20.5kg(45.2 Ibs) reduces installation time quality aesthetic module with lowest system cost. Front Cover 3.2mm Tempered glass Frame Material Anodized aluminium alloy • Lower system costs - can cut rooftop Best Quality J-BOX IP65,3diodes • installation costs in half 42 Cable 4me(IEC)/12AWG(UL),1000mm • 235 quality control points in module production Connectors • Aesthetic seamless appearance - low profile • EL screening to eliminate product defects MC4orMC4Comparabte with auto leveling and alignment • Current binning to improve system performance Standard Packaging(Modules per Pallet) 24pcs Module Pieces per • Accredited Salt st resistant • Built-in hyper-bonded grounding system - if it's Best Warrant I Insurance I-V Curves (CS6Pr255PXntainery s72pcs(ao'Ho) I. mounted,it's groundedy (CS6P-255PX) • Theft resistant hardware • 25 years worldwide coverage _ I 1 • 100%warranty term coverage SectionA-A I i - • Ultra-low parts count - 3 parts for the mounting • Providing third party bankruptcy rights j - and grounding system • 35.0 Non-cancellable• • Industry first comprehensive warranty insurance by Immediate coverage - \` /„ AM Best rated leading insurance companies in the • Insured by 3 world top insurance companies t world - Comprehensive Certificates - _` _ i • Industry leading plus only power tolerance:0-+SW % • IEC 61215,IEC 61730, IEC61701 ED2,UL1703, 1 15 a ■��� • Backward compatibility with all standard rooftop and CEC Listed,CE and MCS ' ground mounting systems • IS09001:2008:Quality Management System • ISO/TS16949:2009:The automotive quality 'Specifications included in this datasheet are subject to change without prior notice. • Backed By Our New 10/25 Linear Power Warranty management system Plus our added 25 year insurance coverage • lS014001:2004:Standards for Environmental About Canadian Solar management system Canadian Solar Inc. is one of the world's largest solar Canadian Solar was founded in Canada in 2001 and was 100%- • QC080000 HSPM:The Certification for com anies. As a leadin vertically-integrated EaIIommrit manufacturer of in ots,wafers,cells,solar modues and November112006. CanadiinS SollarEhasa odulemmanuactuuringHazardous Substances Regulations 9 9 • solar systems, Canadian Solar delivers solar power capacity of 2.05GW and cell manufacturing capacity of 1.3GW. OHSAS 18001:2007 International standards for products of uncompromising quality to worldwide - occupational health and safety customers. Canadian Solar's world class team of 0% • professionals works closely with our customers to s 10 15 20 25 • REACH Compliance provide them with solutions for all their solar needs. Headquarters 1545 Speedvale Avenue West _ Guelph I Ontario N 1 K 1E6 I Canada •10 year product warranty on materials and workmanship 0g,'1°.,', g•((t",,, G SG o a_r Tel:+1 519 837 1881 •25 year linear power output warranty Fax:+1 519 837 2550 inquire.ca@canadiansolar.com www.canadiansolar.com www.canadiansolar.com EN-Rev 10.17 Copyright o 2012 Canadian Soler Inc. PONOf One Renewable Energy Solutions D TECHNICAL DATA VALUES PVI-5000-OUTD-US PVI-6000-OUTD-US cc _ Nominal Output Power W 5000 6000 0i Maximum Output Power W _..... 5000 6000Cd Rated Grid AC Voltage V 208 240 277 208 240 277 Q input side(DC) r; ,: ';:.- z: :: , ...... .:.;i PVI-5000-TL Number of Independent MPPT Channels 2 :14- 2 t:. Maximum Usable Power for Each Channel W 4000 4000 PVI-6000-TL Absolute Maximum Voltage lvmaxl V 600 600 ��»» ..,.a.. Start-Up Voltage lVstartl V 200 (adj.120-350) 200 (adj.120-350) Full Power MPPT Voltage Range V 200-530 200-530 Operating MPPT Voltage Range V 0.7xVstart-580 0.7xVstart-580 Maximum Current Udcmaxl for both MPPT in Parallel A 36 36 Maximum Usable Current per Channel A 18 18 Maximum Short Circuit Current Limit per Channel A 22 22 GENERAL SPECIFICATIONS </ilg Number of Wire Landing Terminals Per Channel 2 Pairs 2 Pairs CArray Wiring Termination Terminal block,Pressure Clamp,AWG8-AWG4 ia6Output Side IAC) ' 0 Grid Connection Type 10/2W Split-0/3W 10/2W 10/2W Split-0/3W 10/2W irk AdjustableVoltage Range lVmin-Vmaxl V 183-228 211-264 244-304 183-228 211-264 244-304 Grid Frequency Hz 60 60 • D Adjustable Grid Frequency Range Hz 57-60.5 57-60.5 Maximum Current(lacmax) Am,, 27 23 20 30 28 24 Power Factor >0.995 >0.995 Total Harmonic Distortion At Rated Power % <2 <2 Contributory Fault Current*' ApdAms 36.25/25.63 36.5/25.81 31.75/22.45 36.25/25.63 36.5/25.81 31.75/22.45 Designed for residential and small commercial PV installations,this Grid Wiring Termination Type Terminal block,Pressure Clamp,AWG8-AWG4 Protection Devices inverter fills a specific niche in the Aurora product line to cater for Input those installations producing between 5kW and 20kW. Reverse Polarity Protection Yes Yes ,,,t/..--:,/'j''%':-.7":,°.. .<<";<, Over-Voltage Protection Type Varistor,2 for each channel Varistor,2 for each channel PV Array Ground Fault Detection Pre start-up too and dynamic GFDI Pre start-up Rico and dynamic GFDI This inverter has all the usual Aurora benefits,including dual input (Requires Floating Arrays) (Requires Floating Arrays) section to process two strings with independent MPPT,high speed Output ' Anti-Islandin Protection �- r 9 Meets UL 1741/IEE1547 requirements Meets UL 1741/IEE7547 requirements and precise MPPT algorithm for real-time power tracking and ) I Over-Voltage Protection Type Varistor,2(L, L,/L-G) Varisto 2(1.,-L,/L,-G) energy harvesting, as well as transformerless operation for high Maximum AC OCPD Rating A 35 30 25 40 35 30 Efficiency performance efficiencies of up to 97.1%. 111111111111.1111111MMIIIIMM Maximum Efficiency % 971 97.1 CEC Efficiency % 96 965 96.5 96 96.5 965 ., Operating Performance The wide input voltage range makes the inverter suitable to lowa ; Stand-by Consumption WgMs <8 <8 Night time consumption Wams <0.6 <0.6 power installations with reduced string size.This outdoor inverter a Communication has been designed as a completely sealed unit to withstand the User-interface 16 characters x 2 lines LCD display harshest environmental conditions. ) ri,_ ._ .. . , �� �. Remote Monitoring 11 xR5485 incl.) AURORA UNIVERSAL(opt) _ Wired Local Monitoring 11xR5465 incl.) PVI-USB RS485 232(opt.),PVI-DESKTOP(opt) '- , Monitoring PVI-DESKTOP(opt.)with PVI-RADIOMODULE(opt.) , 1M ' - ° w Wireless Local Environmental -13 Ambient Air Operating Temperature Range °F(°C) 13 to+140(-25 to+60) with derating t ng ab veo122(50) a Ambient Air Storage Temperature Range °F(°C) -40 to 176(-40 to+80) -40 to 176(-40 to+80) e ;`,•:'.';',.. Relative Humidity %RH 0-100 condensing 0-100 condensing Fe ^^ s ay p Acoustic Noise Emission Level db(A)Ai m <50 <50 C,`.7 ;. Maximum Operating Altitude without Derating ft(m) 6560(2000) 6560(2000) _,,s...,.. Mechanical Specifications , Enclosure rating NEMA 4X NEMA 4X Cooling Natural Convection Natural Convection • Each inverter is set on specific grid codes which can be selected in the field Dimensions lHxWx D) in(mm) 41.4x 12.8 x 8.6(1052x 3250218) • Single phase output Weight lb(kg) <59.5(27.0) <59.5(27.0) Shipping Weight Ib(kg) <78(35.4) <78(35.4) • Dual input sections with independent MPPT,allows optimal energy harvesting from two sub-arrays oriented Mounting System Wall bracket Wail bracket Trade Size Kos:(2ea x 1/2") Trade Size Kos:(tea x 1/2') in different directions Conduit Connections and(2ea x 1-1/4;3 places side,front,rear) and(2ea x 1-1/4",3 places side,front,rear) •Wide input range DC Switch Rating-(Per Contact) AN 25/600 25/600 Safety • High speed and precise MPPT algorithm for real time power tracking and improved energy harvesting Isolation Level Transformerless(Floating Array) Transformerless(Floating Array) • Flat efficiency curves ensure high efficiency at all output levels ensuring consistent and stable performance Safety and EMC Standard U1.1741,CSA-C22.2 N.107.1-01,UL1998 UL1699B, 01.1741,CSA-C222N.107.1-01,UL1998 UL1699B, FCC Part 15 Class B FCC Part 15 Class B across the entire input voltage and output power range Safety Approval ,CSAR, ,CSA,, •Outdoor NEMA 4X rated enclosure for unrestricted use under any environmental conditions Warranty Standard Warranty years 10 10 • RS-485 communication interface(for connection to laptop or datalogger) Extended Warranty years 15&20 15&20 ' • Compatible with PVI-RADIOMODULE for wireless communication with Aurora PVI-DESKTOP Available Models • Integrated Arc Fault Detection and Interruption(-A Version) Standard-With DC Switch-Floating Array PVI-5000-OUTD-US PVI-6000-OUTD-US With DC Switch,Wiring box and Arc Fault Detector and Interrupter PVI-5000-OUTD-US-A PVI-6000-OUTD-US-A 'All data is subject to change without notice "Inverter can apply that much current Breaker will open AURORA UNO 1 AURORA UNO 3 CSA INTERNATIONAL 3 Certificate of Compliance Certificate: 1841082 Master Contract: 173688 Project: 2439384 Date Issued: July 19,2011 Issued to: Power-One,Inc 740 Calle Plano Camarillo,CA 93012 USA Attention:Robert White The products listed below are eligible to bear the CSA Mark shown with adjacent indicators 'C'and 'US'for Canada and US or with adjacent indicator 'US'for US only or without either indicator for Canada only. Ro-b-Hamp sto-ck, Issued by: Rob Hempstock,AScT. Ci US PRODUCTS CLASS 5311 09 -POWER SUPPLIES-Distributed Generation Power Systems Equipment CLASS 5311 89 -POWER SUPPLIES-Distributed Generation-Power Systems Equipment -Certified to U.S.Standards Utility Interactive Inverter,Models PVI-6000-OUTD-US,PVI-6000-OUTD-US-W and PVI-5000-OUTD-US, permanently connected. For details related to rating,size,configuration,etc.reference should be made to the CSA Certification Record, Annex A of the Certificate of Compliance,or the Descriptive Report. APPLICABLE REQUIREMENTS CSA-C22.2 No.107.1-01 - General Use Power Supplies UL Std No. 1741-Second Edition - Inverters,Converters,Controllers and Interconnection System Equipment For Use With Distributed Energy Sources(January 28,2010) DOD 507 Rev.2009-09-01 Page:1