Plans (44) ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE 1. WHERE ALL TERMINALS OF THE DISCONNECTING ` AC ALTERNATING CURRENT MEANS MAY BE ENERGIZED IN THE OPEN POSITION, BLDG BUILDING A SIGN WILL BE PROVIDED WARNING OF THE CONC CONCRETE HAZARDS PER ART. 690.17. RECEIVED DC DIRECT CURRENT 2. EACH UNGROUNDED CONDUCTOR OF THE jj�� EGC EQUIPMENT GROUNDING CONDUCTOR MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY (E) EXISTING PHASE AND SYSTEM PER ART. 210.5. EMT ELECTRICAL METALLIC TUBING 3. A NATIONALLY-RECOGNIZED TESTING MAY 2 82014 GALV GALVANIZED LABORATORY SHALL LIST ALL EQUIPMENT IN GEC GROUNDING ELECTRODE CONDUCTOR COMPLIANCE WITH ART. 110.3. CITY OF TIGARII CITY OFTIGARD GND GROUND 4. CIRCUITS OVER 250V TO GROUND SHALL REyI�'y�J�;D FOR CODE COMPLIANCE DIVISION HDG HOT DIPPED GALVANIZED COMPLY WITH ART. 250.97, 250.92(B) I CURRENT 5. DC CONDUCTORS EITHER DO NOT ENTER Approved: I LJ Imp CURRENT AT MAX POWER BUILDING OR ARE RUN IN METALLIC RACEWAYS OR OTC: Isc SHORT CIRCUIT CURRENT ENCLOSURES TO THE FIRST ACCESSIBLE DC kVA KILOVOLT AMPERE DISCONNECTING MEANS PER ART. 690.31(E). Permit#: 'rir *fii -e'Me + kW KILOWATT 6. ALL WIRES SHALL BE PROVIDED WITH STRAIN Address: -' LBW LOAD BEARING WALL RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY ��� � �- �' MIN MINIMUM UL LISTING. Suite #: (N) NEW 7. MODULE FRAMES SHALL BE GROUNDED AT THE ( NEUT NEUTRAL UL-LISTED LOCATION PROVIDED BY THE By: Gt Data ,. t ' NTS NOT TO SCALE MANUFACTURER USING UL LISTED GROUNDING OC ON CENTER HARDWARE. PL PROPERTY LINE 8. MODULE FRAMES, RAIL, AND POSTS SHALL BE P01 POINT OF INTERCONNECTION BONDED WITH EQUIPMENT GROUND CONDUCTORS AND OFFICE COPY PV PHOTOVOLTAIC GROUNDED AT THE MAIN ELECTRIC PANEL. SCH SCHEDULE 9. THE DC GROUNDING ELECTRODE CONDUCTOR SS STAINLESS STEEL SHALL BE SIZED ACCORDING TO ART. 250.166(B) & STC STANDARD TESTING CONDITIONS 690.47. TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V VOLT Vmp VOLTAGE AT MAX POWER W Voc VOLTAGE O T GE AT OPEN CIRCUIT VICINITY MAP INDEX 3R NEMA 3R, RAINTIGHT -, 1-L;::,-: _ > ,g.-- , w PV1 COVER SHEET PV2 SITE PLAN PV3 STRUCTURAL VIEWS ` '1 `- PV4 UPLIFTCALCULATIONS LICENSE GENERAL NOTES , i . ':, ' PV5 THREE LINE DIAGRAM • PV6 ELECTRICAL CALCULATIONS OR # 180498 1. THIS SYSTEM IS GRID—INTERTIED VIA A m. - 94,. .. Cutsheets Attached 44 RGC, CGC1 UL-LISTED POWER-CONDITIONING INVERTER. M ,.itst a $ 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. - 3. SOLAR MOUNTING FRAMES ARE TO BE - GROUNDED. 4. ALL WORK TO BE DONE TO THE 2010 OBC 4 ':. e 14 " 'r MODULE GROUNDING METHOD: ZEP SOLAR BASED ON THE 2009 IBC. ' !� -# s NI t 1 5. ALL ELECTRICAL WORK SHALL COMPLY WITH '' ' ' REV BY DATE COMMENTS AHJ: Tigard THE CURRENT NATIONAL ELECTRIC CODE AS r • AMENDED BY THE OREGON ELECTRICAL SPECIALTY ° �` ��DATE COMMENTS CODE. - ,0 � _ � ��<�� � ©®© UTILITY: Portland General Electric .« ®©© * N teran : e o c,,®®© „ e no, _ T g n, State of Orege U.S. Geological Sure®©© CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER: JB-9721981 O O PREMISE OWNER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED THE LIVENGOOD, TERRY W. LIVENGOOD RESIDENCE Aaron Banks -me.�SolarCU BENEFIT OF ANYONE EXCEPT SD FORTT INC., MOUNTING SYSTEM: beer NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Com Mount Type C 12255 SW BELL CT 9.18 KW PV ARRAY ►lA y PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH , THE SALE AND USE OF THE RESPECTIVE (36) TRINA SOLAR # TSM-255PA05.18 3055 Clearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN Z PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER: 9 71 2 3 546 6 6 T:(650)638-1028 F:(650)638-1029 FRONIUS i IG PLUS A 7.5 COVER SHEET PV 1 5/14/2014 (888)—SOL—CITY(765-2489)www.solarcity.com PITCH: 38 ARRAY PITCH:38 MP1 AZIMUTH: 190 ARRAY AZIMUTH: 190 • MATERIAL: Comp Shingle STORY: 2 Stories r AC T ,�� LEGEND IDLL_-I L___ J O (E) UTILITY METER & WARNING LABEL \ ® INVERTER W/ INTEGRATED DC DISCO 12"Fire Setback 12"Fire Setback & WARNING LABELS . X o o _ - 1 , 0 1 0—]-1 I HHHH DC DISCONNECT & WARNING LABELS ° y ! ° I AC I ( M) A AC DISCONNECT & WARNING LABELS o o d_ MP1 • -=W ® OB DC JUNCTION/COMBINER BOX & LABELS -e--e0 0 0 "e _ �; OEM DISTRIBUTION PANEL & LABELS e O Un Locked Gated Lc LOAD CENTER & WARNING LABELS °Un tocked Gated y J MEI a e o o ° _ O DEDICATED PV SYSTEM METER A (E) DRIVEWAY 0 STANDOFF LOCATIONS PV3 — CONDUIT RUN ON EXTERIOR Front Of House CONDUIT RUN ON INTERIOR GATE/FENCE Q HEAT PRODUCING VENTS ARE RED 12255 SW Bell Ct I/`I INTERIOR EQUIPMENT IS DASHED L--I SITE PLAN N TOTAL ARRAY AREA (SF): 647 TOTAL ROOF AREA (SF): 2230 Scale: 1/8" = 1' W `�r E - TOTAL ARRAY AREA IS R3 29.03 0 1' 8' 16' PERCENT OF TOTAL ROOF AREA mii �iiioiioaiiiioiioi� s J 3-9721 9 81 00 PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL— THE INFORMATION USED FORHN JOB NUMBER: tt:SolarCity CONTAINED SHALL NOT FO USED THE LIVEN000D, TERRY W. LIVEN000D RESIDENCE Aaron Banks BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 12255 SW BELL CT 9.18 KW PV ARRAY NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD, OR 97223 ORGANIZATION, EXCEPT IN CONNECTION %ATH3055 Clearview Way THE SALE AND USE OF THE RESPECTIVE (36) TRINA SOLAR # TSM-255PA05.18 PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: T:(65O)638-1028 F:(65O)638-1029 PERMISSION OF SOLARCITY INC. FRONIUS # IG PLUS A 7.5 9712354666 SITE PLAN PV 2 5/14/2014 (888)—SOL—CITY(765-2489)www.solarcity.com • PV MODULE (E) 2x4 5/16" BOLT WITH LOCK INSTALLATION ORDER 1°1'1.°z & FENDER WASHERS LOCATE RAFTER, MARK HOLE \ ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT ZEP ARRAY SKIRT (6) HOLE. SEAL PILOT HOLE WITH (4) (2)) POLYURETHANE SEALANT. ZEP COMP MOUNT C �.�g �� L I I I •� /Ali ZEP FLASHING C �Lj�T� �� (3) INSERT FLASHING. STRUCTURE MEETS THE (E) COMP. SHINGLE �� (4) PLACE MOUNT. PRESCRIPTIVE REQUIREMENTSNOEMIMI OF THE OSISC SECTION 305.4 (E) ROOF DECKING (5) INSTALL LAG BOLT WITH 5/16" DIA LAG BOLT (5) SEALING WASHER. WITH SEALING WASHER LOWEST MODULE SUBSEQUENT MODULES INSTALL LEVELING FOOT WITH (2-1/2" EMBED, MIN) (6) BOLT & WASHERS. (E) RAFTER 4`' » Iii! 8'_1" ��, 8'_0., STANDOFF ,/� E (11) (E) LBW (E) LBW Scale: 1 1/2" = 1' A SIDE VIEW OF MP1 NTS MP1 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES LANDSCAPE 64" 24" STAGGERED PORTRAIT 32" 16" ROOF AZI 190 PITCH 38 RAFTER: 2x4 @ 16" OC STORIES: 2 ARRAY AZI 190 PITCH 38 C.).: 2x10 @16" OC Comp Shingle CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER: JB-9721981 0 O PREMISE OWNER: DESCRIPTION: DESIGN: ����CONTAINED SHALL NOT BE USED FOR THELIVENGOOD, TERRY W. LIVENGOOD RESIDENCE Aaron BanksSoIarCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 12255 SW BELL CT 9.18 KW PV ARRAY NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Com Mount T e C PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD, OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (36) TRINA SOLAR # TSM-255PA05.183055 Clearview Way PAGE NAME: SHEET: REV DATE: San Mateo,CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: T:(65O)638-1028 F:(65O)638-1029 PERMISSION OF SOLARCITY INC. FRONIUS # IG PLUS A 7.5 9712354666 STRUCTURAL VIEWS PV 3 5/14/2014 (688)—SOL—CITY(765-2489)www.solaraltyaom UPLIFT CALCULATIONS 05.14.2014 SolarCity SleekMountTM PV System Version#34.3 Structural Deslan Software Project Information&Table Of Contents Risk Category: II PV System Type SolarCity SleekMount.' Comp Roof Comp Roof Layers of Comp Roofing 1 Roof Slope 380 Rafter Spacing 16°O.C. PV System Module Orientation Landscape and Portrait PV Module Area 634 sf PV Module Width 39" PV Module Length 65" Standoff(Attachment Hardware) Comp Mount Type C Reduced Ground/Roof Live/Snow Loads Ground Snow Load pg 25.0 psf 'ASCE Table 7-1 Surrounding Roof Snow 100% 25.0 psf 'ASCE Eq:7.4-1 Roof Snow Over PV Modules 100% 25.0 psf 'ASCE Eq:7.4-1 Wind Design Criteria Wind Design Code ASCE 7-05 • Wind Design Method Partially/Fully Endosed Method Basic Wind Speed V 95 mph Fig.6-1 Exposure Category C ' Section 6.5.6.3 Roof Style Gable Roof 'Fig.6-11B;C/D-14A15 Mean Roof Height h 25 ft Section 6.2 • Effective Wind Area(1 Module) A 17.6 sf IBC 1509.7.1 Wind Pressure Calculation Coefficients Wind Pressure Exposure Kz 0.95 Table 6-3 Topographic Factor Kzt 1.00 Section 6.5.7 Wind Directionality Factor Kd 0.85 Table 6-4 Importance Factor I 1.0 Table 6-1 Velocity Pressure qh qh=0.00256(Kz)(Kzt)(Kd)N^2)(I) Equation 6-15 18.6 psf Ext.Pressure Coefficient(Up) GCp(Up) -0.95 Fig.6-11B:C•D-14r;B Ext.Pressure Coefficient(Down) GCp(Down) 0.88 Fig.8-11BICgD-14A/B Design Wind Pressure p p=qh(GCp) Equation 6-22 Wind Pressure Up p(up) -17.7 psf Wind Pressure Down p(down) 16.3 psf Allowable Standoff Spacings X-Direction Y-Direction Max Allowable Standoff Spacing Landscape 64" 39" Max Allowable Cantilever Landscape 24" NA Standoff Configuration Landscape Staggered Max Standoff Tributary Area Trib 17 sf PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -282 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capacity DCR 56.4% Max Allowable Standoff Spacing Portrait 32" 65" Max Allowable Cantilever Portrait 16" NA Standoff Configuration Portrait Staggered Max Standoff Tributary Area Trib 14 sf PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -234 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capacity DCR 46.9% CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER: J 3-9 7 21 9 81 0 0 PREMISE OWNER: DESCRIPTION: DESIGN: \`` - CONTAINED SHALL NOT BE USED FOR THE LIVENGOOD TERRY W. LIVENGOOD RESIDENCE Aaron Banks ����` BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: ' SoIarCity NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C 12255 SW BELL CT 9.18 KW PV ARRAY Pr PART TO OTHERS OUTSIDE THE RECIPIENT'S MODULES: OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH TIGARD, THE SALE AND USE OF THE RESPECTIVE (36) TRINA SOLAR # TSM-255PA05.18 3055 Rearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN ateo, CA 94402 INVERTER: PAGE NAME: SHEET: REV: DATE: SanT:(650)638'1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. FRONIUS # IG PLUS A 7.5 9712354666 UPLIFT CALCULATIONS PV 4 5/14/2014 (888)—SOL—CITY(765-2489)www.solarcityaom GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #8 GEC TO TWO (N) GROUND Panel Number:LC240PS Inv 1: DC Negatively Grounded INV 1 —(1)FRONIUS # IG PLUS A 7.5 LABEL: A —(36)TRINA SOLAR # TSM-255PA05.18 OR # 180498 RODS AT PANEL WITH IRREVERSIBLE CRIMP Meter Number:23 789 947 lie—In: Supply Side Connection AFCI Inverter; 7500W, 240V, 95.5% PV Module; 255W, 232.2W PTC, 40MM, Black Frame, MC4, ZEP Enabled RGC, CGC1 Underground Service Entrance INV 2 Voc: 37.7 Vpmax: 30.5 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER (E) 200A MAIN SERVICE PANEL E 200A/2P MAIN CIRCUIT BREAKER Inverter 1 CUTLER—HAMMER Disconnect CUTLER—HAMMER COOPER STRINGS TO BE COMBINED Cti INVERTER. 0 Disconnect Meter Socket CC' FRONIUS FUSING REQUIRED INSIDE INVERTER. i riico i •P� A 40A B C IG PLUS A 7.5 . . A r, . n I. L, I zanv l ►s I ��' 11 13 Fri n � ,,� DC+ 200A/2P + N HL-—__ DC- 3 String(s)Of 12 On MP 1 ill (E) LOADS GND _ Lid) _ 10—— --1 GND I- --— EGC/ it I •_ DC+ J DC. DC- III I J ®i —_ E — EGC - • • r---- -- -GC--------m--- -- N I 0 —z cp T GEC r-♦ TO 120/240V I I SINGLE PHASE I I UTILITY SERVICE I I I I I I I I I I I • - — Voc* = MAX VOC AT MIN TEMP POI—(2)Ground Rod; 5/B" x 8', Copper A —(1)CUTLER—HAMMER #DG222NRB i^ D -(2)ILSCO IPC 4/O-#6 Disconnect; 60A, 240Vac, Fusible, NEMA 3R Insulation Piercing Connector; Main 4/0-4, Tap 6-14 -(1)CUTLER-HAMMERd DG100NB C (1)COOPER /B-Line Meter Socket 011 Ground/Neutral Kit; 60-100A, General Duty(DG) Meter Socket; 125A, 4-14AWG, Rin T e -(1)CUTLER HAMMER #DS16FK 9 YP Class R Fuse Kit -(1)AW CAP; B-Line Meter Socket Accessory -(2)FERRAZ SHAWMUTTTR4OR PV BACKFEED OCP ! -(1)MILBANK CL200 Fuse; 40A, 250V, Class RK5 Meter; FORM 2S SSC-SUPPLY SIDE CONNECTION. DISCONNECTING MEANS SHALL BE SUITABLE B (1)CUTLER—HAMMER #DG222URBDisconnect; 60A, 240Vac, Non-Fusible, NEMA 3R AS SERVICE EQUIPMENT AND SHALL BE RATED PER NEC. —(1)CUTLER—HAMMER)DGIOONNB Ground/Neutral it; 60-100A, General Duty(DO) 1 AWG 16, THWN-2, Black 1.-1-- I I (1)AWG#8, THWN-2, Black (6)AWG #10, USE-2/RHW-2, Black Voc* =507.41 VDC Isc =8.92 ADC O�+(1)AWG #6, THWN-2, Red O 6 �(1)AWG#8, THWN-2, Red 1 O0 , THWN-2, White NEUTRAL Vmp =240 VAC Imp 31.2 MC LLL I O .F(1)AWG #6, Stranded Bare Copper EGC Vmp =366 VDC Imp=8.36 ADC (1)AWG #6 p= (1)AWG#10, THWN-2, White NEUTRAL Vmp =240 VAC Imp=31.2 mc • (1)Conduit Kit; 1" EMT -(1)AWG 16,,Solid Bare,Copper, GEC. , , .-(1)Conduit Kit; 3/4" EMT. . . . . . . . . . . . . . . . .-(1)AWG 0.,THWN-2•.Green EGC/GEC-(1)Conduit Kit; 3/4W EMT. _ . . . . . . . . CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: J 3-9721981 00 PREMISE OWNER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE LIVENGOOD, TERRY W. LIVENGOOD RESIDENCE Aaron Banks -\‘`• SolarCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: -•,� NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C 12255 SW BELL CT 9.18 KW PV ARRAY ►i% - PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH TIGARD, THE SALE AND USE OF THE RESPECTIVE (36) TRINA SOLAR # TSM-255PA05.18 3055 Clear-view Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. INVERTER: 971 2354666 PV 5 5/14/2014 T:(650)638-1028 F:(650)638-1029 • FRONIUS # IG PLUS A 7.5 THREE LINE DIAGRAM (888)-SOL-CITY(765-2489)www.solarcity.com Label Location: Label Location: Label Location: ' CAUTION: SOLAR CIRCUIT (C)(IC)(CB) MAXIMUM AC _ A (AC) (P01) CAUTION (P01) Per Code: OPERATING CURRENT Per Code: DUAL POWER SOURCE Per Code: IFC 605.11.1.4 MAXIMUM AC _ v NEC 690.54 SECOND SOURCE IS NEC 690.64.6.4 OPERATING VOLTAGE PHOTOVOLTAIC SYSTEM Label Location: PHOTOVOLTAIC DC (DC) (INV) DISCONNECT Per Code: NEC 690.14.C.2 Label Location: Label Location: PV SYSTEM (AC) WARNING (DC) (INV) DISCONNECT FOR Per Code: UTILITY OPERATION ELECTRIC SHOCK HAZARD NEC 690.35(F) Label Location: THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN MAXIMUM POWER _ (DC) (INV) A UNGROUNDED AND INVERTER IS POINT CURRENT(Imp) Per Code: MAY BE ENERGIZED UNGROUNDED MAXIMUM POWER v NEC 690.53 POINT VOLTAGE(Vmp) Label Location: MAXIMUM SYSTEM V VOLTAGE(Voc) WARNING (AC) (P01) SHORT-CIRCUIT_ Per Code: CURRENT(Isc) A ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS NEC 690.17(4) TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION Label Location: . WARNING (DC) (CB) Per Code: ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS NEC 690.17(4) Label Location: TERMINALS ON BOTH LINE AND WARNING (P01) • LOAD SIDES MAY BE ENERGIZED Per Code: IN THE OPEN POSITION INVERTER OUTPUT NEC 690.64.6.7 DC VOLTAGE IS CONNECTION ALWAYS PRESENT WHEN DO NOT RELOCATE SOLAR MODULES ARE THIS OVERCURRENT EXPOSED TO SUNLIGHT DEVICE Label Location: Label Location: WARNING (DC) (INV) PHOTOVOLTAIC POINT OF (P01) INTERCONNECTION Per Code: Per Code: ELECTRIC SHOCK HAZARD NEC 690.5(C) WARNING: ELECTRIC SHOCK NEC 690.17.4; NEC 690.54 IF A GROUND FAULT IS INDICATED HAZARD. DO NOT TOUCH NORMALLY GROUNDED TERMINALS.TERMINALS ON CONDUCTORS MAY BE BOTH THE LINE AND LOAD SIDE UNGROUNDED AND ENERGIZED MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER. PV POWER SOURCE Label Location: MAXIMUM AC _ A AC) OPERATING CURRENT (AC): AC Disconnect PHOTOVOLTAIC AC (AC) (P01) MAXIMUM AC _ (C): Conduit DISCONNECT Per Code: OPERATING VOLTAGE V (CB):CB : Combiner Box NEC 690.14.C.2 (D): Distribution Panel (DC): DC Disconnect (IC): Interior Run Conduit Label Location: (INV): Inverter With Integrated DC Disconnect CAUTION (D) (P01) (LC): Load Center PHOTOVOLTAIC SYSTEM Per Code: (M): Utility Meter CIRCUIT IS BACKFED NEC 690.64.6.4 (P01): Point of Interconnection CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR %i114 3055 Cleaview Way THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED •- San Mateo,CA 94402 IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, SC - OR Label Set 1���� T:(650)638-1028 F:(650)638-1029 EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE I, Sola rC qty (888)SOL-CITY(765-2489)www.solarcity.com SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. ZS Comp Edge Zone Calculations 1 of 4el ZS Comp Edge Zone Calculations 2 of 4 Zep So to r 5/28/13 Zep So to r 5/28/13 This set of calculations is intended to show that ZS Comp has sufficient strength to allow for attachment Down Force Spacing spacings of at least 48"in Edge Zones whether the modules are orientated in landscape or portrait.The Allowable Down Force Load calculations will vary the design variables to account for the worst case for each failure mode that is being down force spacing= module width x design load checked. Wind Down Calculations All variable the same as above except for roof pitch General Design Information: Roof Pitch Module Size: 39"x 65" Basic Wind Speed= 95 mph 14 30 45 System Weight= 3 psf Ground Snow Load= 30 psf GCN landscape= 0.5 0.9 0.9 GCN portrait= 0.4 0.9 0.9 Comp Mount Allowable Loads design load = 9.62 17.32 17.32 psf Uplift= 656 lbs ii landscape Lateral= 436 lbs design load portrait= 7.70 17.32 17.32 psf Down Force= 1147 lbs - -Ro•.t6,I1 note:use 10 psf minimum tic- isoolgr Snow Calculations Attachment Spacing Calculationsfir 85818 VA To account for unbalanced snow loads,ground snow loads will be used for roof pitches 30 degrees and Uplift Spacing OREGON o lower.Per section 7.6.1 of ASCE 7-10 unbalanced snow loads do not need to be considered for slopes 49 V 'el' tiP above 30 degrees. Allowable Uplift Load '<,.. '0, "� uplift spacing= module length or width x design load EXPIRES: 12/31/14 Ground Snow Load= 30 psf Wind Uplift Calculations FOR PAGES 1-4 Roof Pitch ASCE 7-05 Method 2 14 30 p=qh GCN Design Snow Load 29.11 25.98 psf qh=0.00256 K,Kit Kd Vz I (snow load spread over the length of the rafter) Basic Wind Speed= 95 mph Down Force Load Roof Pitch Exposure= C Roof Zone= Edge Zone Combinations: 14 30 Importance Factor= 1.0 K,= 0.98 from Table 6-3 D+S= 31.16 25.10 psf Gable/Hip Roof Kit= 1.0 per 6.5.7.2 D+W= 12.91 19.92 psf forst Case Roof Pitch= 14 degrees Kd= 0.85 from Table 6-4 D+0.75W+0.755 31.59 32.46 psf Roof Height= 30 GCN landscape= -1.6 iscape effective area= 13.0 ft2 GCN portrait= -1.5 11471bs in z landscape down force spacing = 39"x 32.46psf x 144 ftz = 130" ortrait effective area= 21.7 ft Plandscape= -30.79 psf qh= 19.25 psf Pportrait= -28.87 psf 1147lbs in portrait down force spacing = 65"x 32.46psf x 144 ftz = 78" Uplift Load Combination:0.6D+W(ASCE Section 2.4.1 equation 7) design load landscape= -29.05 psf design load portrait= -27.12 psf 656 lbs in landscape uplift spacing = 39"x 29.05 psf x 144 ftz =83" 656 lbs in portrait uplift spacing = 65"x 27.12 psf x 144 ftz = 54" tt ZS Comp Edge Zone Calculations 3 of 4 ZS Comp Edge Zone Calculations 4 of 4 Zep S o to r 5/28/13 Zep So l a r 5/28/13 Lateral Spacing Module Deflection Spacing The lateral force on the system increases as the pitch of the roof increases,but the amount of snow on landscape module spacing = -1.4545 x Maximum Uplift or Down Force Pressure+ 120.7273 the roof decreases for slopes greater than 30 degrees.With this in mind,the lateral force will be checked at 30 degrees with ground snow load and 45 degrees with sloped roof snow. portrait module spacing = -1.7917 x Maximum Uplift or Down Force Pressure+118.58 Allowable Lateral Load lateral spacing = module width x design load Maximum Uplift of Down Force Pressure= 32.46 psf Snow Calculations Ground Snow Load= 30 psf landscape module spacing= -1.4545 x 32.46 psf+120.7273 = 73" Ps=C5 pf Roof Pitch= 31 45 degrees pf=0.7 Ce Ct I pg Ce= 0.9 Cs= 0.71 0.45 portrait module spacing =-1.7917 x 32.46 psf+118.58= 60" Ct= 1.2 pf= 22.68 22.7 psf = 1.0 Ps= 16.1 10.2 psf Calculation Summary Calculated Edge Zone Spacing Roof Pitch Spacing Check Landscape Portrait 27 30 31 45 Uplift 83" 54" Design Snow Load 26.73 25.98 13.80 7.22 psf Down Force 130" 78" (snow load spread over the length of the rafter) Lateral 30° 27° 30" 74" 48" 45" Lateral Force Component Module Deflection 73" 60" Down Force Load Roof Pitch Combinations: 27 30 31 45 As can be seen in the table above,for Design Wind Speeds up to 95 mph and Ground Snow Loads up to 30 D+S= 13.50 14.49 8.65 7.22 psf psf with modules orientated in landscape,the system is strong enough to be installed at 72"on center in D+0.75W+0.755 10.46 11.24 6.88 5.95 psf the Edge Zone.When modules are installed in portrait,the spacing for edge zone installations can be 48" on center for most roof pitches.For roof pitches that are greater than 27°but less than 31°,the maximum 30 degree roof pitch attachment spacing is 45". 292lbs in landscape lateral spacing = x 144 39"x 14.49 psf ft2 = 74" 292lbs in portrait lateral spacing= =45" 65"x 14.49 psf x 144 ft2 Portrait spacing is less than 48".Try roof pitch of 27 degrees 292lbs in portrait lateral spacing = 65"x 13.50 psf x 144 ft2 =48" SolarCity SleekMountTM - Comp SolarCity SleekMountTM - Comp The SolarCity SleekMount hardware solution •Utilizes Zep Solar hardware and UL 1703 listed �, .: � _� Installation Instructions is optimized to achieve superior strength and Zep CompatibleTM modules ! ,, aesthetics while minimizing roof disruption and , Drill Pilot Hole of Proper Diameter for labor.The elimination of visible rail ends and •Interlock and grounding devices in system UL Fastener Size Per NDS Section 1.1.3.2 listed to UL 2703 mounting clamps, combined with the addition of array trim and a lower profile all contribute •Interlock and Ground Zep ETL listed to UL 1703 .- Seal pilot hole with roofing sealant as"Grounding and Bonding System" Insert CompMount flashingunder upper to a more visually appealing system.SleekMount � PP utilizes Zep CompatibleTM modules with •Ground Zep UL and ETL listed to UL 467 as layer of shingle strengthened frames that attach directly to grounding device 0 Place Comp Mount centered Zep Solar standoffs, effectively eliminating the need for rail and reducing the number of •Painted galvanized waterproof flashing upon flashing standoffs required. In addition, composition ► Install lag pursuant to NDS Section 11.1.3 •Anodized components for corrosion resistance shingles are not required to be cut for this with sealing washer. system,allowing for minimal roof disturbance. ••Applicable for vent spanning functions 1 Secure Leveling Foot to the Comp Mount ""� using machine Screw , • Place module • Components � :-\''''',4'4 , 4-1._.•0 . Itl �►_ • 5/16"Machine Screw • L�MI a L:: 00t • Lrew ! • Comp Mount • • Comp Mount Flashing 4 4 0 0 `. II—rielS'— ° 0 14vq OP • t w4£ti 0MPA. OP/ ' Solart ity© January 2013 0compo : m ,Ti1 ®LISTED ;-'i; SolarCity0 January 2013 TSM-PA05.18 TRINAMOUNT II WITH THE UNIVERSAL MODULE Mono Multi Solutions DIMENSIONS OF PV MODULE TSM-PA05.18 ELECTRICAL DATA @ STC TSM-240 TSM-245 TSM-250 TSM-255 TSM-260 PA05.18 PA05.18 PA05.18 PA05.18 PA05.18 941mm Peak Power Watts-Peru(Wp) 240 245 250 255 260 Power Output Tolerance-PMAx(%) 0/+3 0/+3 0/+3 0/+3 0/+3 -b ueaio5 o Maximum Power Voltage-VMe(V) 29.7 30.2 30.3 30.5 30.7 80X Maximum Power Current-Imre(A) 8.10 8.13 8.27 8.36 8.47 ISM - PA05.18 NAMEPLATEOpen Circuit Voltage-Voc(V) 37.3 37.5 37.6 37.7 37.9 d09xt] iesuw... `' Short Circuit Current-Ise(A) 8.62 8.68 8.85 8.92 9.00 i Module Efficiency qm(%) 14.7 15.0 15.3 15.6 15.9 THE TRINAMOUNT MODULE 3 a STC Irradiance 1000 W/m'Cell Temperature 25°C,Air Mass AMLS according to EN 60904-3. Average efficiency reduction of 4.5%at 200 W/maccording to EN 60904-1. m 0 ° 3 ELECTRICAL DATA @ NOCT TSM-240 TSM-245 TSM-250 TSM-255 TSM-260 PA05.18 PA05.18 PA05.18 PA05.18 PA05.18 60 CELL ELL Maximum Power-PMnx(Wp) 174 178 181 184 188 Maximum Power Voltage-Vme(V) 26.6 26.8 27.0 27.2 27.4 MULTICRYSTALLINE MODULE • 6-043rwx.s nM HOLE Maximum Power Current-lope(A) 6.55 6.64 6.70 6.77 6.86 A A i2-xw.rsor WITH TRINAMOUNT FRAME �- Open Circuit Voltage(V)-Vo (v) 34.1 34.2 34.3 34.4 34.6 '"^ _ Short Circuit Current(A)-Isc(A) 7.04 7.10 7.25 - 7.31 7.37 812mm I 180 I1 NOCT:Irradiance et 800 W/m',Ambient Temperature 20°C,Wind Speed I m/s. 240-260W Back View POWER OUTPUT RANGE Our most versitile product MECHANICAL DATA • Compatible with all major BOS components and system 11 Solar cells Multicrystalline 156.156 mm(6 inches) designs Cell orientation 60 cells(6 x 10) 15 1650.992.40 mm(64.95 x 39.05 x 1.57 inches) V^ v Weight 18.6 kg(41.0 lbs) MAXIMUM EFFICIENCY Glass High transparency solar glass 3.2 mm(0.13 inches) Backsheet White (/'` One of the industry's most trusted modules �• • Over 2 GW sold across all major global markets Frame Black Anodized Aluminium Alloy with Trinamount Groove ea 0~1 • Field proven performance I-V CURVES OF PV MODULE TSM-245 PA05.18 J-Box IP 65 or IP 67 rated 3 Cables Photovoltaic Technology cable 4.0 mm'(0.006 inches'), 10.00 1100 mm(43.3 inches) POWER OUTPUT GUARANTEE 900 1000W/m' 820 Connector Original MC4 _7m 800W/m' Highly reliable due to stringent quality control 5m 6410W/m2 _ ---1), As a leading global manufacturer • Over 30 in-house tests(UV,TC,HF,and many more) U'4.m 400W/m' TEMPERATURE RATINGS MAXIMUM RATINGS of next generation photovoltaic I SI • In-house testing goes well beyong certification requirements am 2.00 200W/m. m200W/m' Nominal Operating Cell ell as°c(±2°C) Operational Temperatureerasure -40-+85°C we believe close 1. Temperature(NOCT) cooperation with our partners Maximum System 1000V DC(IEC)/ IS critical to success. With local 0.40 Temperature Coefficient of PA,A% -0.43%/°C Voltage 600V DC(UL) 0.00 10.0° 20.m 30.40 40.00 presence around the globe,Trina is Temperature Coefficient of Voc -0.32%/°C Max Series Fuse Rating 15A Voltage(V) able to provide exceptional service Temperature Coefficient of Isc 0.047%/°C to each customer in each market Certified to withstand challenging environmental and supplement our innovative, en g g reliable products with the backing conditions of Trina as a strong,bankable • 130 km/hr wind load(2400 Pa) WARRANTY partner. We are committed • 900 kg snow load per module(5400 Pa) 10 year Product Workmanship Warranty to building strategic,mutually beneficial collaboration with 25 year Linear Power Warranty installers,developers,distributors (Please refer to product warranty for details) and other partners as the backbone of our shared success in CERTIFICATION o driving Smart Energy Together. LINEAR PERFORMANCE WARRANTY PACKAGING CONFIGURATION c il 10 Year Product Warranty•25 Year Linear Power Warranty ,� `" cw `I; �ertek r=spas Modules per box:24 pieces Trina Solar Limited R Modules per 40'container:672 pieces www.trinasolar.com 8100% Ad ISO ILO (( c UL us PV CYCLE - dlfjOgpl vulU WED V • 0 90% ` B�anl Tflf 4 SD/Qf S Isneaf mons) CAUTION:READ SAFETY AND INSTALLATION INSTRUCTIONS BEFORE USING THE PRODUCT. EOMP4l4 •Tnnasolar _ F4,12,,,,Nr-- Tr�nasolar ch• ange wit Solar notice. All rights reserved.Specifications included in this dotosheet are subject to ti O 80l Chan a without notice. •s' W Smart Energy Together Years 10 is 20 25 Smart Energy Together .0 �s0 aMPP ■Trina Solar /Battery Charging Systems/Welding Technology/Solar Electronics FrCfniU5 SHIFTING THE LIMITS FRONIUS IG PLUS ADVANCED INVERTER WITH INTEGRATED AFCI , /MIXT.Technology /Smart Transformer /WEAN ` /Quick Service /Smart Grid 'ca Switching Technology Ready ,f: `•_ /The Fronius IG Plus Advanced is the first complete inverter lineup of the NEC 2011 compliant AFCI protected inverters in the United States. Power classes ranging from 3 to 12 kW in both single and true 3 phase applications with integrated Fronius MIX Technology and wide voltage windows are the perfect match for your system design. TECHNICAL DATA:FRONIUS IG PLUS ADVANCED(3.0-1Uxl 3.8-1UNI 5.0-1„Nt6.0-1uNt7.5-1„NI) INPUT DATA 3.01axt 3.8-1„x, 5.0.1axi 6.0-1uxt 7.5-1xxt 8cenntn ten(led I'V-Power(AWP) _.5(1-7145 12 4:1(1 4-25 5.75 5-10-6.9A 6-t5-8.60 Nominal Input Current 8.3 A 10.5 A 13.8 A 16.5 A 20,7 A Max-Usable.I nput Cnttent 140 A 17.8 A 2:14 A 28-1 A :15.1 A MPPT-Voltage Range 230-500 V --. DC Startup 260 V Max.Input Voltage 600 V Admissiible Condo for 452e ID(I No.14to6 AWT,-For Iiirger wiie,050[minus(miiingdi,trihtno, Max.Correta per DC Input Terminal 20 Amps.For higher input current,use Fromm connecting distributor. .-- TECHNICAL DATA: FRONIUS 16 PLUS ADVANCED(3.0-1 3.8-1 5.0-1 6.0-1 7.5-1 ) UNI, UNI, UNI, UNI, UNI OUTPUT DATA 3.0-1„„, 3.8-1xxt 5.0-1„x, 6.0-1ax, 7.5 tux, Non inel o,Ip II Pnwet 1.000 W 3,801)W 5,000 W 6,000 W 7x00 W EFFICIENCY 3.0.1„x, 3.8-1„x, 5.0.1„x, 6.0-1„x1 7.5-1„x, Max-Continuous Output Power 3,000 W 3,800 W 5,0011 W 6,000 W 7,500 W op,rn 1),g A(.V Ingo Paugc 208 V 183-229 V(-12/I IMI'Z,) AC 00)pul Voltage 208/240/277 240 V 211.264 V(-12/+10%) Number of Phases 1 1 277 V 244 305 V(12/t 10,..,) Adnti,siblr•COINER(OI Slic(AC:) No.14-4 AWG Max.Continuous Output Current 208 V 14.4 A 183 A 24.OA 28.8 A 36.1 A Max.Continuous Utility Backfeed Current OA 240 V 12.5 A 15.8 A 2(1.8 A 25.0 A 31 I A Nominal Output F'quen(y 60 II, 277 V 10.8 A 13.7 A 18.1 A 21.7 A 27.1 A Operating Frequency Range 59.3-60.5 Hz Total Hat ntoulc Dilor tion Power Factor 0-85-1 ind-/cap. PROTECTIVE EQUIPMENT 3.0.1., 3.8-1ux, 5.0-1. 6.0-1., 7.5-1., GENERAL DATA 3.0-1 3.8-1 5.0-1 6.0.1 7.5-1 1, S 1 dt Ptt t(1100 Internal GI DI(Gonna I roll Deo(m'1 Icrroplt r) ,rdao„with 111.1741 2010„nd NE(AI 1690 xxt xxt xxt oxt axt DC Reverse Polarity Protection Internal Diode Max.1:111061ey 96.2 96-2 Ilau,lmg,'11,7,0,0 Imcrul-'in ritoulan(,'with UL 1741 2010,IEEE 1547-200'I and NEC Unit Dimensions(W x H x 0) 17.1 x 26.5 x 9.9 in. 171 x 26-5 x 9.9 in. 171 x 38-1 x 9.9 in. 171 x 38.1 x 9.9 in 171 x 38,1 x 9.9 in. Over Temperature Protection Output power derating/active cooling CEC Ellicieney 258 V 95.0'5, 95.5'1, 15.5>.� 95 5% 550'), Imo,u:d AF(1(Ai(F,dt Cr(uit Imcrrupter),in d- with 111 1699 Outhncon„e:rg.lt n Ibr Photovolwic(PV)DC 240 V 95.5 V. 95.5% 955% 96.0% 95.5% Arc-Fault Circmt Protection Arc Pauli Circuit Protection(Issur Number 2,January 14,2013) 277V 96-0 96.U% 960ki,, '16.5'% 96 0'5, Consumption in standby(Night) 0 1.5 W (onsuptutiou Du ring 0101,,106 8 W 8 W 14 W 14 W 14 W Cooling Controlled forced ventilation,variable speed fan Frit I,o,,re Type NEMA'I N Power Stack Weigle 31 lbs.(14 kg) 31 lbs.(14 kg) 57 lbs.(26 kg) 57 lbs.(26 kg) 57 lbs.(26 kg) ) Wiring(ontpartt em W,•igltl 21,lis(II kg) Admissable Ambient Operating Temperature -13M1 4-11OF(-25"C.--a55"C) Advanced crid I(4itI,c. Al NV('.111,1 t,.t(m„'p„wet omro1,!ow voltage fah,through UL 1741-2010,IEEE 1547-2003,IEEE 1547.1,UL 16990-2013,ANS1/IEEE C62 41,FCC Part 15 A&B,NEC Article 690,C22.2;?= Compliance No.107-1-01(Sept.2011)California Solar Initiative Program Handbook.Appendix C'Inverter Integral 5%Meter Peeformariet Specification _._.._,._w&;::>_•::r:.=_-:x TECHNICAL DATA:FRONIUS IG PLUS ADVANCED(10.0-1., 11.4-1UN1,10.0-3uN.DELTA, 11.4-3UNIDELTA, 12.0-3 WYE277) TECHNICAL DATA:FRONIUS IG PLUS ADVANCED(10.0-1 UNI,11.4-1UNI,10.0-3UNI DELTA, 11.4-3UNI DELTA, 12.0-3 WYE277) EFFICIENCY 10.0-1,,,,, 11.4'1., 10.0-3.,DELTA11.4-3.,DELTA 12.0.3 WYE277 .... ohrraloyAC Vullagc Rang' 208V 181-22°9V1-12/+111';6) INPUT DATA 10.0-1 11.4-1 10.0-3 DELTA 11.4-3 DELTA 12.0-3 WYE277.i 40 V 211 264 V(12/+l0%) VMI uxl uxl xxl 277V 244-soyV(IZ/,I(I"e) I:ton n�dc�I 1'V I'owcl lkWp) -50-II-50 9.7(1 13.10 5.50 I1.5(1 9.7(1-11.18 10.20 I3.NO Max_Continuous Output Current t4 ,'; QBV 48.1A >4-8A 27.7A* 31.6 A* n-a Nominal Input Current 27,6 A 31.4 A 27.6 A 31.4 A 33.1 A 240 V 41 7 A 475 A 21.0 A. 274 A. n- d: M z-Usable Inl it Cnra•nI 4(.7 A 5:3-:1 A 4(i 7 A 51(A 56-I A = .':;277 V 36.1 A 41.2 A 11. n.a. 14.4 A. • MDPT-Voltage Range 230-500 V DC Slartnp 260 V M I p t v]c g 600 V PROTECTIVE EQUIPMENT10.0-1uxl 11.4-1xxl 10.0-3xxl DELTA 11.4-3uxl DELTA 12.0-3 WYE277 A<I1n--a111e e�Juelor ti�.e(l)Cl Nn.14 Io(,AWG.For I: i,c-w-re,u: I-. iiu con 'cling�Iil ri4luloi. >£ Max.Cuaent per UC lnpu(Terminal 2O Amps.For higher input cunei t use Pronms connecting distributor Gan I Fn Il l'rol,.,lion Inlet nal GPDl lGmund Feull ll�leclor/Inge n ptu l- ., n-d�n„relllr((I I II 1111 I NFC Art.690 DC Reverse Polarity Prot'non !( "t*t rf. Internal lliode I. OUTPUT DATA 10.0.1 11.4-1 10.0-3 DELTA 11.4-3 DELTA 12.0-3 WYE277 hland161'n,tctllnn tr11'r I �ar�nrI -lbu11 41 0u1,16FFI 47 11111 nI567 xxl UNI ux1 uxl Over Temperature Protection '" r Y r Nor ii ial Ontpnt 1'owrr `)995 W 11400 W 9,`195 W 11 4011W 12,1100 11 Internal AFCI(Arc Faolt Clrcml Internlpterl I wrUr UL IG99 Outirric of Invnslrgatiov for Photovolta is(PV)DC � Max Continuous Output Power 9,995 W 11,400 W 9,995 W 11.400 W 12,000 W AmFanlr Cimurr Protcenon Arc Paint Cor m1 I-m e,.no,(Issue Number 2 January 14,L013) 2 AC Oul pill Vullag, 200.110 277 200/240/277 2(18/24(1 208 i 218 180 1 1.77 W 1'r: 50 Number of Phaacs 1 1 3 3 3 h - Adniis�ilrlr.(:ondn�for Au'e(AC) No.11 4 AWG 0 Max.Gontrnuaus Utility Backfeed Current OA , o© Nnm al Oi Ilii I F yucncy 60 11/ Opernting Frequency Range 593-605 Hz ,; ea!x�^ec�,,, t Tolal Hannon-c 11-s lorlo,o �1'>0 Power Factor 0:85-1 ind/cap m U 8.1 GENERAL DATA 10.0-1. 11.4-1 Vxl 10.0-3UMI DELTA 11.4-3UNI DELTA 12.0•3 WYE277 e Mex.f4li,icnev (1)2 Unit Uimcnaion(W oHxD( 17.1 x497x 99 in. a CFC Fi firlcncy 2110 0 95.0'/ 95.0 2, 9,.5 i 95.(1'% 0 e A _ 240 V 95.5% 95.5% 95.5% 96.0% nal TA . _ 277 V 96(I'!, 96-0% n.7 n.a. 96 fl"i. Consumption in Standby(Night) <1.5 W Consnn�pllon Iluring Operation 20 w 1E _ Cooling Controticd forced vennlaaon,varfssble Speed fan ,,, /Battery Charging Systems/Welding Technology/Solar Electronics _ Encln�u rc l yllr NEMA 30 Power stack weight 84 lbs.(38 kg) WE HAVE THREE DIVISIONS AND ONE PASSION:SHIFTING TH LIMITS. - W b c nnpa 1 1 W,,gl 1 a ibs-112 kg) Ad ble Amb t Op rati ng T empe aurze d /Whether BatteryChargingSystems,WeldingTechnology or Solar Electronics-our goal is clearlydefined:to be the technology and qualityleader. 2 -13"F +131"F(-25"C..+55'C) nd�:rnrrd erid F'<nrn,s nerve and�eaer�e pnw'r control.Inw�nbag'��d� Ilnongb With more than 3,000 employees worldwide,we shift the limits of what's possible-our 737 active patents are testimony to this.While others progress o ; UL 1741-2010,IEEE 1547-2003,IEEE 15471,UL 1699B-2013,ANSI/IEEE C62 41,FCC Part 15 A&B,NEC Article 690,C22.2 step by step,we innovate in leaps and bounds.Further information about all Fronius products and our global sales partners and representatives can Compliance No.107.1-01(Sept.2011)California Solar Initiative-Program Handbook-Appendix C:Inverter Integral 5%Meter Performance be found at www.fronius.com "s Specification ::':Cl' Fronius USA LLC 6797 Fronius Drive Portage,IN 46368 w USA pv-usa@fronius.com www.fronius-usa.com �'