Plans (37)
ABBREVIATIONS ELECTRICAL NOTES INDEX LEGEND LICENSE A AMPERE 1. WHERE ALL TERMINALS OF THE DISCONNECTING PV1 COVER SHEET E M AC ALTERNATING CURRENT MEANS MAY BE ENERGIZED IN THE OPEN PV2 SITE PLAN 0 ( ) UTILITY METER & WARNING LABEL (6)* OR # 180498 POSITION, A SIGN WILL BE PROVIDEDPV3 STRUCTURAL VIEWS BLDG BUILDING WARNING - INVERTER W/ INTEGRATED DC DISCO CONC CONCRETE OF THE HAZARDS PER ART. 690.17. PV4 STRUCTURAL VIEWS ® RECEIVED C COMBINER BOX 2. EACH UNGROUNDED CONDUCTOR OF THE PV5 UPLIFT CALCULATIONS & WARNING LABELS (3),(4),(5),(6) D DISTRIBUTION PANEL MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED PV6 THREE LINE DIAGRAM Dc NOV 27 202 ' DCBY PHASE AND SYSTEM PER ART. 210.5. PV7 ELECTRICAL CALCULATIONS ® DC DISCONNECT & WARNING LABELS (4),(5) EG DIRECTEQUIPMENT CURRENT 3. A NATIONALLY—RECOGNIZED TESTING CITYOFTIGARD (E) STIGROUNDING CONDUCTOR LABORATORY SHALL LIST ALL EQUIPMENT IN AC AC DISCONNECT & WARNING LABELS BUILDINGDNISION (E) EXISTING COMPLIANCE WITH ART. 110.3. I✓� (3),(4),(5),(6) EMT ELECTRICALOARA METALLICMTUBING 4. CIRCUITS OVER 250V TO GROUND SHALL G SOLAR GUARD METER GALV GALVANIZED COMPLY WITH ART. 250.97, 250.92(8) 0 JUNCTION BOX GEC GROUNDING ELECTRODE CONDUCTOR 5. DC CONDUCTORS EITHER DO NOT ENTER DC COMBINER BOX & WARNING GND GROUND BUILDING OR ARE RUN IN METALLIC RACEWAYS (-,7 e.E OR ENCLOSURES TO THE FIRST ACCESSIBLE DC GENERAL NOTESLABELS (7),(9) 'T}C` t�* = `j a 9AL b SPACED �,O HDG HOT DIPPED GALVANIZED OHEATER'THAN A `*d,.4.H€ ON CENTER I CURRENT DISCONNECTING MEANS PER ART. 690.31(E). D DISTRIBUTION PANEL & WARNING ?}1 Atir k.�tFS =C e rON V'1H'I ARRAY It, Imp CURRENT AT MAX POWER 6. ALL WIRES SHALL BE PROVIDED WITH STRAIN 1. THIS SYSTEM IS GRID—INTERTIED VIA A LABELS (1),(2) LOCATED VJiTHlN S FM OF A FtOOP INVS INVERTERS RELIEF AT ALL ENTRY INTO BOXES AS UL—LISTED POWER—CONDITIONING INVERTER. LOAD CENTER & WARNING LABELS CKC EA'eE OR RIDGE. Isc SHORT CIRCUIT CURRENT REQUIRED BY UL LISTING. 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. Lc , ) kVA KILOVOLT AMPERE 7. MODULE FRAMES SHALL BE GROUNDED AT THE 3. ALL INVERTERS AND ARRAYS ARE NEGATIVELY (3),(4),(5),(6) DSC SOF,�.3 r4't kW KILOWATT UL—LISTED LOCATION PROVIDED BY THE GROUNDED. DEDICATED PV SYSTEM METER M LBW LOAD BEARING WALL MANUFACTURER USING UL LISTED GROUNDING 4. SOLAR MOUNTING FRAMES ARE TO BE GROUNDED, O MIN MINIMUM HARDWARE. 5. ALL WORK TO BE DONE TO THE 2010 OBC CONDUIT RUN ON EXTERIOR MIR MIRROR 8. ALL EXPOSED METAL PARTS (MODULE FRAMES, BASED ON THE 2009 IBC. ���& CONDUIT RUN ON INTERIOR A CITY OF TIGARD (N) NEW RAIL, BOXES, ETC.) SHALL BE GROUNDED USING 6. ALL ELECTRICAL WORK SHALL COMPLY WITH THE — GATE r NEC NATIONAL ELECTRIC CODE UL LISTED LAY—IN LUGS LISTED FOR THE CURRENT NATIONAL ELECTRIC CODE AS AMENDED ——— INTERIOR EQUIPMENT pp oved�.� �� [BY THE OREGON ELECTRICALi•a� SPECIALTYConditionallyApproved CODE. NIC NOT IN CONTRACT PURPOSE. POSTS SHALL BE MADE � ] NTS NOT TO SCALE ELECTRICALLY CONTINUOUS WITH ATTACHED *( ) NUMBERS REFER TO LABELS See Letter to:Follow [ I OC ON CENTER RAIL. ON CUTSHEET PAGE Attached [ I P PANEL BOARD 9. MODULE FRAMES, RAIL, AND POSTS SHALL BE Permit Ntpliber:� k C I( PL PROPERTY LINES BONDED WITH EQUIPMENT GROUND CONDUCTORS Addr • 4 155 9 'U A PV PHOTOVOLTAIC AND GROUNDED AT THE MAIN ELECTRIC PANEL. By: Dale: 1 ?� SPVC SUBPANEL POLYVINYL CHLORIDE 10. THE SHALLDCBE SIZED GROUNDING ACCORDING ELECTRODTO ART.E CONDUCTOR VICINITY MAP SCH SCHEDULE 250.166(B) & 690.47. Y"„°`r" Approved plans SS STAINLESS STEEL K cam« "�` g Fu SSD SEE STRUCTURAL DRAWINGS T'9" '`` °° � a c..:07:::::, e rp, . STC STANDARD TESTING CONDITIONS Southwest shall be on Ob site SWH SOLAR WATER HEATER M � � Mangy f " , �°""�*, TYP TYPICAL vet? �"°,^�, —? OFFICE COPY 1rme�lt&ry Rrlival y3' ' UON UNLESS OTHERWISE NOTED .G" swW^k•,", rpd q Oak Crdsk f a 1 \ UPS UNINTERRUPTIBLE POWER SUPPLY 74 ��a � V VOLT4 : sw Fo R¢° er: s te PatlxM Vmp VOLTAGE AT MAX POWER �efew la.Medi of d &Fpm., Voc VOLTAGE AT OPEN CIRCUIT t e z "'' 0.-/r1)-' td doe WeedtlMe # Leak Palk �"u ' wawa. W WATT `k P 1 Perk m 3R NEMA 3R, RAIN11GHT 1 I ,. swQawaat SWacaontddSr i r wee k REV BY DATE COMMENTS Sonia Pere if REV$ * s/./s *8W SOM.Rd , kotedont&Rd te SW Ea*Rbu ttert Rd sw Pworadh 3 amiayca�s r (Wow Pe Lake Pee*** a 'y1 ' .yv♦ } , SW Sat*SI _ t Y f4 P J B-9721168 0 0 PREMISE Dw► R AHJ. Tigard DESCRIPTION: DEIGN: vi,,� CONFIDENTIAL A THE INFORMATION USTION HEREINTHE NUMBER: LOCK, RICHARD D LOCK RESIDENCE LROBLES CONTAINED SHALL NOT BE USED FOR THE BEHEST OF ANYONE EXCEPT SOLARCDE THE iE INC., MARKET: MODULES .:,°Sola1' ity NOR SHALL IT BE DISCLOSED IN WHOLE OR IN REST (33) TRINA SOLAR # TSM-240PA05 14155 SW 103RD AVE 7NTS .92 KW PV Arra ��� ORGANIZATION, EX- PART TO OTHERS CEPTIIIN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TI GARD, OR 97224 m THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Oearview Way San Mateo,CA PERMISSIONITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV: DATE: 94402 OF SOLARgPY INC. PAYMENT PIPE: INVERTER: 5038496935 T:(650)638-1028 F:(650)638-1029 PPA (1) SMA # SUNNY BOY 7000—US COVER SHEET PV 1O/22/2O1 , (888)-SOL-CITY(765-2489)www.solardty.com - Roof Mounted SEEPV3 DETAILS MP1 PITCH: 18 ARRAY PITCH:18 T AZIMUTH: 179 ARRAY AZIMUTH: 179 MATERIAL:Comp Shingle Roof STORY: One Story 30'to PL — Roof Mounted SEEPV4 DETAILS MP2 PITCH: 16 ARRAY PITCH:16 AZIMUTH:179 ARRAY AZIMUTH: 179 v MATERIAL: Comp Shingle Roof STORY: One Story 20'to PL TOTAL ARRAY AREA: 620 SQ. FT. TOTAL ROOF AREA: 2280 SQ. FT. 'un-Licked Gated Fence Un'Lock@d Gated Fence TOTAL ARRAY AREA IS ^-27% LEGEND OF TOTAL ROOF AREA. 3' MIN. FIR5,SETBACK UCTURE C � STR40'to PL O (E) UTILITY METER & WARNING LABEL (6)* T _ CHANGE PV3 Ash INVERTER W/ INTEGRATED DC DISCO & WARNING LABELS (3),(4),(5),(6) 1' MIN. LI LI — — ❑ FIRE SETBACK NH DC DISCONNECT & WARNING LABELS (4),(5) B AC PV3 I , �� �AAcc AC DISCONNECT & WARNING LABELS ip r___N--------- f (3),(4),(5),(6) 0 X I i 1 0 JUNCTION BOX ,I � I MP1A I �' ``� G DC COMBINER BOX 8c WARNING r 00 l Inv , LABELS (7),(9) �.-- MP1 ' L`_'_ - L-_ . DISTRIBUTION PANEL & WARNING ,, O LABELS (1),(2) _ ___ 'hi— PV3 1 \ L-/ .3% , A LC LOAD CENTER & WARNING LABELS T:- . .-.1. _NN '';--j\ -1.L. PV3 ..MP2 LG (3),(4),(5),(6) 1 \ 1�\ i` , -,�~ / D O DEDICATED PV SYSTEM METER �� Front Of House 20'toPL i CONDUIT RUN ON EXTERIOR ' \ ,- l PV4 i OA NOPE i ___ CONDUIT RUN ON INTERIOR /`; i'-,---\:- -k \ 'r/ I " �� ��► — GATE ' �L /`\ ....\ \/-•---V- -1\\''' // ; 14155 SW 103rd Ave ; 44, c":0$ ' --- INTERIOR EQUIPMENT I I• * NUMBERS REFER TO LABELS j. �' \- 1 ‘004,4,'�r • �N4► ON CUTSHEET PAGE -.._ ., y _. - 7His '� k\ -- i { urf.a.4.4.13 i �/` Digitally signed by Yoo Jin Kim SITE PLAN N Date:2012.10.26 12:19:27-07'00' A ______ _ _.._-r--- --__i__--- Scale: 1/8" = 1' w ", E —- i---- 0 1' 8' 16' �+ ■ I S ■ JR-9721168 0 0 PREMISE OWNER: AHJ Tigard DESCRIPTION: DESIGN: CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER: +0114 CONTAINED SHALL NOT BE USED FOR THE LOCK, RICHARD D LOCK RESIDENCE LROBLES BENEFIT OF IT ANYONE EXCEPT SOIN WHOLE INC., MARKET: MODULES �4i��SolarCityNOR SHALL IT BE DISCLOSED IN WHOLE aR INREST (33) TRINA SOLAR # TSM-240PA05- PART TO OTHERS OUTSIDE THE RECIPIENTS 14155 SW 103RD AVE 7.92 KW PV Arra ��ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TIGARD, OR 97224 , THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE INVERTER: PAGE NAME: SHEET: REV: DATE: 94402 PERMISSION OF SOLARCITY INC. (1) SMA SUNNY BOY 7000-US 5038496935 -OL-CfrY( 65-2650)638-1028 896www www.solarcity.com# SITE PLAN PV 2 10/22/201 (888)-SOL-CITY(765-2489)wwwsolarccity.com 4' BETWEEN FOOTINGS (N) SIMPSON A34 CLIP W/ (STAGGERED) (8) 8d (0.131x1.5") NAILS (ID (E)(E) 22x6x8 RAFTER @ 24" O.C. A II II i 11 11 ,. (N) 2x6 DF #2 SISTER DE 12'-7" (+ -) dim RIDGE BOARD Jr' SEE TOP VIEW 2' TYP � TOP OF MP2 (E) 2x4 COLLAR TIE WHEN MODULES ARE WITHIN 36" OF A ROOF EDGE, (E) 2x6 RAFTERS 1r3° STANDOFFS WILL BE PLACED NO MORE THAN 24" O.0 @ 24" SPACING • -• '-11 K E 2 ) x8 CEILING FRONT VIEW OF MOUNTING PLANES (JOIST@24" O.C. B Scale: 1/2" = 1'-0" t (E) LBW PRoPF RAFTER: 2x6 .tae t N UPGRADE NOTES: SUPPORT: 2x6, 2x8, 2x4 ti OA I MAX SPAN: 11'-11" Of 448 1. CUT AND ADD (N) SISTER AS SHOWN IN THIS SIDE VIEW AND REFERENCED TOP VIEW. 2. FASTEN (N) SISTER TO (E) MEMBER W/ SIMPSON SDW 22300 (IF 2-PLY) OR 22458 pq (IF 3-PLY) SDW SCREWS STAGGERED AT 16" O.C. ALONG SPAN AS SPECIFIED, IF C I SIDE VIEW OF MP1A "�k �s•x°44 WOOD SPLITTING IS SEEN OR HEARD, PRE-DRILL WITH A " DRILL BIT. ALT. OPTION FOR FULL LENGTH MEMBERS ONLY- FASTEN (N) SIDE MEMBER TO (E) RAFTER W/ 10d (IF 2-PLY) OR 16d FROM EACH SIDE (IF 3-PLY) COMMON NAILS AT 6" O.C. ALONG SPAN. V • SISTER ALL RAFTERS ON THIS MP SECTION INTO WHICH THE ARRAY IS LAGGED Digitally signed by Yoo Jin Kim (N) SIMPSON A34 CLIP W/ 1 STANDOFF Date:2012.10.26 12:19:38-07'00' (8) 8d (0.131x1.5") NAILS CD (E) 2x6 RAFTER Y Scale: 1 1/2" = 1' © 24" O.C. INSTALLATION ORDER (N) 2x6 DF #2 SISTER O 12'-9" (+ -) 104x ) 2x8 SOLAR PANEL NOTE: RAIL TO BE PLACED IN THE UPHILL DIRECTION SEE TOP VIEW ATTACHED WITH MODULE LOCATE RAFTER, MARK HOLE 1h RIDGE BOARD CLAMPS, 1"-16 BOLTS, (1) LOCATION, AND DRILL PILOT AND ' NUT HOLE. � ` (E) 2x4 COLLAR TIE SOLARCITY SOLAR RAIL (4) (2) SEAL PILOT HOLE WITH . & BOLT '" POLYURETHANE SEALANT. .� I,� (3) (E) 2x8 CEILING YETI (E) COMP. SHINGLE > (1) (3) INSERT ECOFASTEN FLASHING. / _ ,` — — 11' JOIST @ 16" O.C. -,I- (E) LBW !10!..41.-ippre (4) PLACE THE LEVELING FOOT. RAFTER: 2x6 ECOFASTEN FLASHING SUPPORT: 2x6, 2x8, 2x4 (5) INSTALL LAG WITH SEALING (E) LBW MAX SPAN: 12'-0" (E) ROOF DECKING WASHER. 1 a" DIA LAG BOLT (2-3" EMBED, MIN) (5) SIDE VIEW OF MP1 (E) RAFTER A ; CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER: J B-9 7 2116 8 0 0 PREMISE OMER: AHJ Tigard DESCRIPTION: DESIGN: `Wei CONTAINED SHALL NOT BE USED FOR NE LOCK, RICHARD D LOCK RESIDENCE LROBLES ; BENEFIT OF ITANYONE EXCET SOIN WHOLE INC., MARKET: MODULE) SoIaiCity NOR SHALL IT BE DISCLOSED IN WHOLE OR IN REST (33) TRINA SOLAR # TSM-240PA05 14155 SW 103RD AVE 7.92 KW PV Arra ►� - PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER MOUNTING SYSTEM: TIGARD, OR 97224 NE SALE AND USE OF NE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT NE WRITTEN PAYMENT TYPE INVERTER PAGE NAME: SHEET: �: DATE: 94402 PERMISSION OF SOLARCITY INC. PPA (1) SMA # SUNNY BOY 7000-US 5038496935 STRUCTURAL VIEWS PV 3 10/22/201. (888)-SOL-CITY(765-248)6www.solacity.com • (E) 2x6 RAFTER 24" O.C. 0000111011:11111 BOTTOM OF MP1A (N) SISTER MEMBER TO BEAR ON SUPPORT BELOW SIMPSON SDW 22458 SIMPSON SDW 0 STRUCTURE MEETS THE WOOD SCREWS m 22300 WOOD (E) 4x8 BEAM PRESCRIPTIVE REQUIREMENTS 11 (E) RAFTER v 1 II SCREWS OF THE OSISC SECTION 305.4 riff 1/„//////,,,N///// ,eA////// ///// „/,// /„/A 2' 2” 4`-0"' :i (E) LBW 1 ( r////A/A/1/1/////////////l //////,' //7%/2/////47///////////7 RAFTER: 2x611 )? 4'-0" MIN. / (E) 4x4 COLUMN SUPPORT: 2x6, None MAX SPAN: 4'-6" (E) WALL OR m (N) SIMPS(0.131 N1 A34 CLIP SUPPORT BELOW O W/ (8) 8d (0.131x1.5") NAILS SIDE VIEW OF MP2 (E) RIDGE BOARD OR SUPPORT BELOW D TOP VIEW OF FULL LENGTH LAPPED SISTER NOTE: LAP SPLICE DOES NOT NEED TO BE CENTERED ON THE MEMBER Scale: 3/4"=1'-0" (.9$Cp PROPe qt �' 82286PE�� VP 13,A6" END 4. DISTANCE SIMPSON SDW Jew ' ,r 6" ,� 16" O.C., TYP WOOD SCREWS IElfeek mil 30_-o L'1 j 1 4" e o Digitally signed by Yoo Jin Kimy_ _ Date:2012.10.26 12:19:47 07'00' (N) 2x6 SIDE MEMBER (E) 2x4 MIN. RAFTER Go 2x6 END FASTENER GROUPING Scale: 1"=1'-0" J B-9 721 16 8 0 0 PREMISE OWNER: AHJ Tigard DESCRIPTION: DESIGN: ,,,��.." CONFIDENTIAL – THE INFORMATION HEREIN JOB NUMBER: 1,11A4 CONTAINED SHALL NOT BE USED FOR THE LOCK, RICHARD D LOCK RESIDENCE LROBLES NORBENEFIT OF SHALL IT YONE BEDISCLOEXCEPT SOLARCITY OR RCIN MARKET: MODULES 14155 SW 103RD AVE i'►�'�Solat'Ci PART TO OTHERS OUTSIDE THE RECIPIENTS RESI (33) TRINA SOLAR # TSM-240PA05 7.92 KW PV Array ty ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER MOUNTING SYSTEM: TIGARD, OR 97224 THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearyiew Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE INVERTER: PAGE NAME: SHEET: REV: DATE: 94402 PERMISSION OF SOLARCITY INC. PPA (1) SMA # SUNNY BOY 7000—US 5038496935 STRUCTURAL VIEWS PV 4 10/22/201 (888)-SOL-CI TY 5-2489;www5o�°ty.com UPLIFT CALCULATIONS ASCE7-2005 C&C Partially/Fully Enclosed Structure Wind Design Input Variables Calculations and Values Required Variables Design Wind Pressures based upon: mean roof height, ft 13 ASCE 7-05 Chapter 6 Wind Loading Exposure Category (6.5.6.3) B Basic Wind Speed(Figure 6-1 or local data) 95 Equation 6.5.12.4.1: h<60 ft Comp. and Cladding Elements Importance Factor(1 for residential) 1 Wind Pressure P =qh*(G*Cp) Roof Shape Gable/Hip 6.5.10: Velocity Pressure Panel Tilt (degrees) 18.0 deg qh= 0.00256*Kz*Kzt*Kd*V^2*I Roof Zone 3 contiguous sq. feet of array 67 From Table 6-3: least width of the building 34 Kz = 0.70 From Figure 6-4: Kzt= 1.00 Local Topographical Features From Table 6-4: (choose"standard"or refer to pictures right,and before Kd= 0.85 type of hill none From figure 6-1: Hill Height(h)(ft) V= 95 slope of hill (degrees) From table 6-1: horizontal distance from hilltop to house(x) I= 1 height from bottom of hill to mean roof height(z) From Velocity Pressure Equation: qh= 13.75 Design Wind Pressures From Figure 6-19A P(lbs. per sq. ft.)=qh*Cn*G Cn (down)= 0.34 Pd (downforce pressure)= 4.73 Cn (uplift)= -1.31 Pu (uplift pressure)= -18.02 From 6.5.8.1 G= 0.85 PROPS Max Tributary Area Max Uplift Force on a Single Standoff "� N '�`>!',, Individual Rows in Portrait Pmax (lbs.)=Amax*Pu+ 0.6*PL*COS0 .140► V Trina TSM-240PC Pmax= -177 Amax (sq.ft)= 0.5*L*X Factor of Safety= FI*D*NI/Pmax L(length of panel in ft. perpendicular to rail 5.41 Fastner Type: Hex Lag Screw (Per Plans) wIA, i •Ot� X(distance between standoffs in ft.) 4.00 Fastener Diameter: 5116" -2.5"Min Embed Y(distance between standoffs in ft.) 2.67 250 = Fl (pullout capacity of fastener(lbs/inch)) a 13.2 Amax = 10.83 2.5 = D(minimum fastener thread depth) 4!l 1 = NI (number of fasteners per standoff) P 3.53 = Factor of Safety !EXPIRE&Rita J6.•/} j Dead Load Calculations DL(lbs/sq. ft)=(Mm+Mh)/(L*W) Point Load Calculations Digitally signed by Yoo Jin Kim L(length of Trina TSM-240PC modules) 5.41 PL(lbs)=Amax*DL Date:2012.10.26 12:19:57 W(width of Trina TSM-240PC modules) 3.09 PL= 33 -07'00' Mm(weight of Trina TSM-240PC modules) 43.00 Mh (weight of hardware per module)= 7.62 DL= 3.03 ( B Version 1_8 CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: JB-97211 68 00 PREMISE OWNER: AHJ Tigard DESCRIPTION: DESIGN: '�tt 1Is CONTAINED SHALL NOT BE USED FOR THE LOCK, RICHARD D LOCK RESIDENCE LROBLES .._ - NOR FIT OF ITANYONE EXCEPT INLWROLE INC., MARKET: MODULES •'•,`t`SoIa ity NOR SHALL IT BE DISCLOSED WHOLE OR IN REST (33) TRINA SOLAR TSM-240PA05 14155 SW 103RD AVE 7.92 KW PV Array °A PART TO OTHERS OUTSIDE THE RECIPIENTS PROJECT MANAGER, MOUNTING SrsIkM: TIGARD, OR 97224 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE• INVERTER: PAGE NAME SHEET: REV: DATE 94402 PERMISSION OF SOLARCITY INC. PPA (1) SMA # SUNNY BOY 7000-US UPLIFT CALCULATIONS PV 5 10/22/201. (888)-SOL-CITY(60 )638765-248)6550)ww638 5038496935 arraty.com GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #6 GEC TO TWO (N) GROUND (E)E 200A MAIN SERVICE PANEL Inv 1: DC Negatively Grounded INV 1 -(1)SMA/SUNNY BOY 7000 US LABEL A -(33)TRINA SOLAR/TSM-240PA05 OR # 180498 RODS AT PANEL WITH IRREVERSIBLE CRIMP 200/2P MAIN CIRCUIT BREAKER everter, 7000W,zaov,96x PV Module(-2011); 240W,218.2W PTC,40MM,Silver Frame Voc: 37.2 Panel Number:BXH34/K INV 2 Vpmax:30.4 Meter Number:24563638 *MODULE CURRENT RATINGS ARE SHOWN AS Isc AND Imp IN Underground Service Entrance INV 3 THE DC STRINGS IDENTIFIER OF THE SINGLE LINE DIAGRAM. MAIN SERVICE PANEL (E) WIRING Inverter 1 CUTLER—HAMMER COOPER 200A/2P Disconnect Meter Socket (3) SMA • (E) LOADS SUNNY BOY 7000—US p R. n B p L1 I FCI `-t``'� DC+ zGFP/G All • \. L2 r / N - V DC- 3 String(s)Of 11 On MP 1 III 40A/2P A r Yy ---- GND f— -- GNDr 7 EGC/GEC - r - DC+ •{ I DC+ m m �i l V El L---°CI • • B --� DC- All I GND )___ EGC_ _ EGC 1 T N 1- _ J EGC/GEC j Z- 1 _ T DECr 1 TO 120/240V I SINGLE PHASE I I UTILITY SERVICE ICE I l I l I l I I I I __i__i_ POI-(1)(1)SQUARE D/9011240 PV BACKFEED BREAKER -(1)CUTLER-HAMMER 1 DG222UR8 AC INV-(3)FERRAZ SHAWMUTT ATM1 S DC Breaker; 40A/2P,2 Spokes B Disconnect; 60A,240Vac,Nm-Fusible,NEMA 3R v -(2)Ground Rod; 5/8"x 8',Capper -(1)CURER-HAMMER j DGIOONB Fuse; 15A, 600VD , Midget Ground/Neutral Kit 60-100A,General Duty(DO) C (1)COOPER j B-Line Meter Socket 011 Meta Socket; 125A,4-14AWG,Ring Type -(1)AW CAP; B-Line Meter Socket Accessory O (1)AWG#8,TH*1-2,Black (6)AWG 110,USE-2/MHW-2,Black VOC =409.2 VDC Isc =8.37 ADC �-(1)AWG 16,THWM-2,Red 1 w • (1)AWG 110,THWN-2,White NEUTRAL Vmp =240 VAC Imp=29.17 AAC O -(1)ANG/6,Stranded Bare Capper EGC Vmp =334.4 VDC Imp=7.89 ADC -(1)AWG j6,THNM-2,Green ECC/GEC -(1)Conduit Kit 3/4'EMT CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER J 8-9721 1 6 8 00 PRE)SE OWNER: AHJ Tigard DESCRIPTION: DESIGN: _��14 04,0 CONTAINED SHALL NOT BE USED FOR THE LOCK, RICHARD D LOCK RESIDENCE LROBLES BENEFITROF ITANYONE EXCEPT INLAROLE INC., MARKET: MULES: '/�"`SOIaIC'ty NOR SHALL IT BE DISCLOSED WHOLE OR IN REST (33) TRINA SOLAR # TSM-240PA05 14155 SW 103RD AVE 7.92 KW PV Arra �'� PART TO OTHERS OUTSIDE THE RECIPIENT'S Y ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TIGARD, OR 97224 THE SALE AND USE OF NE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN 50)638-1028 F:(650)638-1029 PAYMENT TYPE: INVERTER: PAGE NAME: SHEET: REV: DATE: T:( 94402 PERMISSION OF SOLARCITY INC. PPA (1) SMA # SUNNY BOY 7000-US 5038496935 THREE LINE DIAGRAM PV 6 10/22/201 (888)SO6L-CITY(765-2489)www,solarrcity.com 1. Conductor Sizing per Art 690.8(6)(1) ELECTRICAL CALCULATIONS a. Conductor must have 30 deg. C ampacity >= 125% of continuous current per Art 215.2(A)(1). Module: 33 Trina TSM-240PA05 SiIrer 218.2 Inv Pwr W PTC StrLen Voltage Drop Calculations Version 5_8.37 Inverter 1: 1 SMA SB-7000US(240V) 96.0% 7,000 6,913 11 Vdrop= (Imp) * (2*Length)*(Resistance) / (Vmp) b. Conductor must have (after corrections for conditions of use) >= Module: Imp(A) Max. Length(ft) Wire continuous current per Table 310.15(6)(16). Inverter 2: String: 7.89 30 C AWG 10 at Max Are Hi: 80 deg F Module: Vdrop= (7.89 A * 60 ft *0.00124 Ohms) / 306 V= 0.19% Inverter 3: Branch: 7.89 30 C AWG 10 at Max Are Hi: 80 deg F c. Evaluate conductor temperature at terminations per 110.14(C). Module: Vdrop= (7.89 A * 60 ft *0.00124 Ohms) / 306 V= 0.19% Ampacity of wire derated for conditions of termination must be >= Inverter 4: Total voltage drop in DC conductors= 0.38% continuous current*1.25. All string terminations are rated at 90' C. Inverter: 29.00 10 D AWG 08 at 240v Total: 33 modules Total Inv Pwr 7,000 6,913 PTC Vdrop= (29.00 A * 20 ft *0.00078 Ohms) / 240 V 0.19% 2. OCP Sizing per Art 690.8(6)(1) Photovoltaic Module Electrical Specifications: Total STC 7,920 Combined! 29.00 0 D AWG 08 at 240V a. Round up to next size per Art 240.4(8) Voc= 37.2 V deg F deg C Vdrop= (29.00 A * 0 ft *0.00078 Ohms) I 240 V 0.00% Vmp= 30.4 V Record Low Temp: 8 -13.3333333 Total voltage drop in AC conductors= 0.19% 3. Conductor Sizing per Art 690.8(B)(1) Isc= 8.37 A Max Average Hi Temp: 80 26.66666667 Total voltage drop in AC and DC conductors= 0.57% a. Conductor must have 30 deg. C ampacity >= 125% of continuous Imp= 7.89 A Record Hi Temp: 106 41 Two= -0.1302 V/deg C current per Art 215.2(A)(1). Tisc= 4.185 mA/deg C String Type A and 2 Combined Strings Type A Voc Correction Method: Manuf-Roc data Branch Circuit Type A 1-way wire length: 30 ft b. Conductor must have (after corrections for conditions of use) >= SMA SB-7000US(240V) 1 strings per branch 1 continuous current per Table 310.15(6)(16). 11 Trina TSM-240PA05 Silver Inverter Min Vdc Input: 250 Vdc 11 modules per series string Voc= 409.2 V Min Vmp at Max Temp: 306 Vdc Voc= 409.2 V c. Evaluate conductor temperature at terminations per Art 110.14(C). Vmp= 334.4 V Max Voc at Min Temp: 464 Vdc Vmp= 334.4 V Ampacity of wire derated for conditions of termination must be >= Isc= 8.37 A Inverter Max Vdc Input: 600 Vdc Isc= 8.37 A continuous current*1.25. All branch terminations are rated at 75' C Imp- 7.89 A Max String Size: 14 Imp= 7.89 A Icont= 10.46 A Art 690.8(A)(1) 1-way wire length: 30 ft Icont= 10.46 A Art 690.8(A)(1) min. 1.a Conductor. C AWG 10 USE-2/RHW-2 at 90 deg C:Table 310.15(6)(16) 2.a Conductor 1:C AWG 10 THWN-2/USE-2 at 90 deg C:Table 310.15(B)(16) 4. OCP Sizing Conductor 1: a. Round up to next size per Art 240.4(8) Icont*1.25=(Amps) 13.08 Icont*1.25=(Amps) 13.08 30 deg C ampacity= 40 30 deg C ampacity= 40 5. Conductor Sizing Der Art 690.8(B)(1) 1.b lcont=(Amps) 10.46 2.b Icont=(Amps) 10.46 a. Conductor must have 30 deg. C ampacity >= 125% of continuous Start ampacity 40 Start ampacity 40 current per Art 215.2(A)(1). Temperature derate(%=F) 0.71 Temp.derate(%=F) 0.71 Conduit fill derate(%=#) 0.8 Cndt.fill derate(%=#) 0.8 b. Conductor must have (after corrections for conditions of use) >= Derated ampacity 22.72 Derated ampacity 22.72 continuous current per Table 310.15(8)(16). Term 1 Term 2 1.c Icont*1.25=(Amps) 13.08 Temp table 75degC 75degC Ampacity 40 2.c Icont*1.25=(Amps) 13.08 13.08 c. Evaluate conductor temperature at terminations per Art 110.14(C). Ampacity 35 35 Ampacity of wire derated for conditions of termination must be >= 1.d Icont*1.25=(Amps) 13.08 2.d EGC C AWG 10 C AWG 10 Art.250.122 continuous current*1.25. All inverter output terminations are rated at OCP size= 15 OCP size= 15 75' C. Inverter Type A Output Combined Inverter Output 6. OCP Sizing SMA SB-7000US (240V) 1-way wire length: 10 ft Service Voltage= 240 Volts a. Round up to next size per Art 240.4(B) Icont= 29.00 A Art 690.8(A)(1) Total lnrerter Power= 7,000 Nameplate Watts 1-way wire length: 0 ft 3.a Icont*1.25=(Amps) 36.25 A Art 690.8(6)(1) Icont=#of inverters*max inverter current Art 690.8(A)(1) OCP size= 40 A Art. 240.6(A) Icont=(Amps) 29.00 7. Conductor Sizing per Art 690.8(B)(1) 3.b Conductor D AWG 08 THWN-2 at 90 deg C:Table 310.15(6)(16) '4.a Icont*1.25= (Amps) 36.25 A Art 690.8(B)(1) a. Conductor must have 30 deg. C ampacity >= 125% of continuous (cont*1.25=(Amps) 36.25 OCP size= 40 A Art.240.6(A) current per Art 215.2(A)(1). 30 deg C ampacity= 55 4.b Conductor D AWG 08 THWN-2 at 90 deg C:Table 310.15(6)(16) 3.c Icont=(Amps) 29.00 Icont*1.25=(Amps) 36.25 b. Conductor must have (after corrections for conditions of use) >= Start ampacity 55 30 deg C ampacity= 55 continuous current per Table 310.15(6)(16). Temperature derate(%=F) 0.91 4.c Icont=(Amps) 29.00 Conduit fill derate(%=#) 1 Start ampacity 55 c. Evaluate conductor temperature at terminations per Art 110.14(C). Derated ampacity 50.05 Temp.derate(%=F) 0.91 Ampacity of wire derated for conditions of termination must be >= 3.d Icont*1.25=(Amps) 36.25 Cndt. fill derate(%=#) 1 * Ampacity 50 Derated ampacity 50.05 continuous current 1.25. All inverter output terminations are rated at 3.e EGC = C AWG 10 Art. 250.122 4.d Icont*1.25=(Amps) 36.25 75' C min. GEC = D AWG 08 Art.690.47,250.166(B) Ampacity 50 I CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: J B-9 721 1 6 8 00 PREMISE OWIIER: Al-11 Tigard DESCRIPTION: DESIGN: .i 841i CONTAINED SHALL NOT BE USED FOR THE LOCK, RICHARD D LOCK RESIDENCE LROBLES ... NOR FIT OF ITANYONE EXCET SOINLW INC., MARKET: MO33) •-,���:So'ai;t NOR SHALL IT BE DISCLOSED IN WHOLE OR IN REST (33) TRINA SOLAR TSM-240PA05 14155 SW 103RD AVE 7.92 KW PV Array14� PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TICARD, OR 97224 THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE: INVERTER: PAGE NAME: 94402 PERMISSION OF SOLARCITY K. PPA (1) SMA # SUNNY BOY 7000-US 5038496935 SHEET: REV DATE: T:(650)638-1028 F:(650)638-1029 ELECTRICAL CALCULATIONS PV 7 10/22/201 (888)-SOL-CITY(765-2489)www.solarcity.com PHOTOVOLTAIC DC DISCONNECT Label Location: Label Location: (DC), (INV) (DC), (INV), (AC), (LC) WARNING! ELECTRIC SHOCK HAZARD! Per Code: Solar Disconnect Per Code: Voc V CEC 690.53, NEC 690.53 CEC 690.17, NEC 690.14 (4) Vmp v WARNING-Electric Shock Hazard In A DO NOT TOUCH TERMINALS _�,,,� Imp A Terminals on both line and Load sides "` (888)SOL-CITY may be energized in the Open Position �� SolarCity. SOLARCITY.COM Label Location: Label Location: WARNING - Dual Power Sources (INV), (AC), (LC), (M) DC DISCONNECT (DC), (INV), (AC), (LC) Second source is photovoltaic system WARNING-Electric&lock Hazard DO NOT TOUCH TERMINALS Terminals on bofh Fine and Load sides Label Location: may be energized in the Open Position WARNING - Electric Shock Hazard (CB) DC VOLTAGE IS ALWAYS PRESENT WHEN No user serviceable parts inside lif SOLARMODULES ARE EXPOSED TO SUNLIGHT Contact authorized servicer for assistance WARNING! Label Location: PHOTOVOLTAIC POINT OF INTERCONNECTION Label Location: INVERTER OUTPUT CONNECTION.DO NOT (P01) WARNING! ELECTRIC SHOCK HAZARD! (P01) RELOCATE THIS OVERCURRENT DEVICE. DO NOT TOUCH TERMINALS.TERMINALS ON BOTH THE LINE AND LOAD SIDE MAY BE ENERGIZED PV POWER SOURCE MAXIMUM AC CIRCUIT OUTPUT A PHOTOVOLTAIC AC DISCONNECT Label Location: OPERATING CURRENT (AC), (D), (LC) OPERATING AC VOLTAGE v WARNING! ELECTRIC SHOCK HAZARD! Per Code: ,•!,+,f, �.(� CEC 690.8.A.3&CEC 690.54, NEC 690.14 (c)(2) SoIal City OPERATING AC VOLTAGE V l'if (888)SOL-CITY SOLARCITY.COM MAXIMUM OPERATING CURRENT A Label Location: if :SolarCity (888)SOL-CITY. PV COMBINER BOX (CB) SOLARCITY.COM WARNING: ELECTRIC SHOCK HAZARD (AC): AC Disconnect Label Location: (C): Conduit CAUTION: SOLAR CIRCUIT (C) (CB): Combiner Box (D): Distribution Panel (DC): DC Disconnect (IC): Interior Run Conduit (INV): Inverter With Integrated DC Disconnect (LC): Load Center (M): Utility Meter (P01): Point of Interconnection CONFIDENTIAL— THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR `014 3055 Cleaview Way THE BENEFIT OF ANYONE EXCEPT SCARCITY INC., NOR SHALL IT BE DISCLOSED _ IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENT'S ORGANIZATION, San Mateo,CA 94402 638-108 F: EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE Labels � Iai( �ty (888)-SO6L-CITY50) (765-22489)(650) ?52248)6 www.solar0city.com SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. o SMA Technical data Sunny Boy 5000-US Sunny Boy 6000-US Sunny Boy 7000-US Sunny Boy 8000-US • p 208VAC 240VAC 277YAC 208VAC 240VAC 277VAC 238VAC 240VAC 277VAC 240VAC 277VAC Max.recommended PV power(@ module STC) 6250 W 7500 W 8750 W 10000 W Max.DC power)@ cos 9-1) 5300 W 6350 W 7400 W 8600 W Max.DC voltage 600 V 600 V 600 V 600 V DC nominal voltage 310 Y 310 V 310 Y 345 V MPP voltage range 250 V-480 V 250 V-480 V 250 V-480 V 300 V-480 V Min.DC voltage/start voltage 250V/300V 250V/300V 250V/300 V 300 V/365 V Max.input current/per string(at DCdisconnect) 21A/20A 25A/20A 30A/20A 30A/20A 36 A @combined terminal 36 A @combined terminal 36 A @combined terminal 36 A @combined terminal + # � ". t .. Number of MPP trackers/ m r Asa 1/4(DC disconnect) u a fused strings per MPP tracker T Output(AC) r�x = AC nominal power 5000 W 6000 W 7000 W 7680 W 8000 W 't%- _m-..... - f - Max.AC apparent power 5000 VA 6000 VA 7000 VA 8000 VA h '. `fr s, Nominal AC voltage/adjustable 2049/• 2409/• 277V/• 2089/• 240V/• 277V/• 2089/• 2409/• 2779/• 2409/• 2779/• _ r 'rira AC yolta eronge t83-229v 211-2649 244-3059 t83-229Y 211-2649 244-3059 1e3-229V 211-2649 244-3059 2t1-2649 244-3059 9 F >n. �`"" - s AC grid frequency;range 60 Hz;59.3-60.5 Hz 60 Hz;59.3-60.5 Hz 60 Hz;59.3-60.5 Hz 60 Hz;59.3-60.5 Hz Max.output current 24A 21A 18A 29A 25A 22A 34A 29A 25A 32Ar. Power factor(cos c) 1 1 1 1 . Phase conductors/connection phases 1/2 1/2 1/1 1/2 1/2 1/1 1/2 1/2 1/1 1/2 1/1 Harmonics <4% <4% <4% <4% S 1 .�} Efficiency Max.efficiency 96.7°/ 96.8% 96.8% 96.9% 96.8% 97.0% 97.1% 96.9% 97.0% 96.3% 96.5% _ CEC efficiency 95.5% 95.5% 95.5% 955% 95.5% 96.0% 95.5% 96.0% 96.0% 96.0% 96 0% u Protection devices DC reverse-polarity protection • • • • AC short circuit protection • • • • f t Galvanically isolated/all-pole sensitive monitoring unit 5/- •/- •/- 5/- 2 Ay z Protection class/overvoltage category I/III I/Ill I/111 I/Ill 0 • Genera)data s, Dimensions(W/H/D)inmm(in) 470/615/240 (18.5/24/9) -: ` NDi lin) } DC Disconnect dimensions)W/H/D in mm in 187/297/190 (7/12 7.5) ,*., - Packing dimensions(W/H/D)in mm(in) 390/580/800 (16/23/31.5) F. DC Disconnect packing dimensions(W/H/D)in mm(in) 370/240/280 (15/9/11) Weight/DC Disconnect weight 64 kg (141 1b)/3.5 kg (8 lb) 66 kg(145 lb)/3.5 kg(8 Ib) Packing weight/DC Disconnect packing weight 67 kg (14716)/4 kg (9 Ib) 69 kg(152 lb)/4 kg(91b( Operating temperature range(Full power) -25°C...+45°C (-13°F...+113°f( Noise emission(typical) 44 48(A) 45 48(A) 46 48(A) 49 48(A) Internal consumption at night 0.1 W 0.1 W 0.1 W 0.1 W -" - Topology IF transformer IF transformer LF transformer IF transformer _ Cooling concept OptiCool OptiCool OptiCool OptiCool Electronics protection rating/connection area NEMA 3R/NEMA 3R NEMA 3R/NEMA 3R NEMA 3R/NEMA 3R NEMA 3R/NEMA 3R Features Display:text line/graphic •/- •/- •/- •/- t Interfaces:RS485/Bluetooth 0/0 0/0 0/0 0/0 • c: ., Warrany:10/is/20 years •/o/o 41/0/0/o/o et/0/0 •/o/o 's„)E but r...:� 'm.$`a=.0. ` T( '"tO "i x".'tatr; Certificates and permits(more available on request) UL1741,UL1998,IEEE 1547,FCC Part 15(Class A&BE CSA C22.2 No.107.1-2001 n NOTE:US inverters ship with gray lids. r � Data at nominal conditions -";, m •Standard features 0 Optional features -Not available a Type designation SB 5000US SB 6000US SB 7000US SB 8000US Efficiency curve SUNNY BOY 7000US; Accessories ,w, .g-y, 9 m )(:)(1-1,i p,r'»t / i y 98 RS485 interface [Olio�BlaebNMe ngBy Back 0.I , q, � ROY &i gyp O'" J s"T 3(#r« (1• 7V S 8 Y y A t 96 �,-. '�+.- ,� -S ( � X '��'"�,��...„� .�� �^�,� � S BSUSPeSMGNR INVNR a 7 / 4 BTPS .« a ,.. acs .�:,•,• Com6S..;th ('nmbiner box .,Urtf. ,Y • ,',I)I,S C7 - , ,. .i (-•7 '',u7.. ..). ..,1.--1.-,,:.0(P..-P,'.,:./',. exct,1 "; 90 - Simplify voting for added fl r .? / e DC d ttomrecr end P/ Sim combiner nr 88 r • 5ovoc. aas - COMBO-WITC6H SBCB63RorrSBC&N e 22 48 86 )- j aSe ( ., I � ec v„ o v Dc' ; v. Ivl .., - ( $ 1000 2000 3000 4000 5000 6000 7000 5' Toll Free+1 888 4 SMA USA US Patent US735254981 www.SMA-America.com SMA America, LLC Yeti with Eco-Fasten GreenFasten Flashing Yeti with Eco-Fasten GreenFasten Flashing r The SolarCity Yeti with Eco-Fasten GreenFasten flashing optimizes strength,performance and aesthetics while structurally attaching solar panels to composition shingle roofs. This engineered connection uses �.378T1iRUALL Eco-Fasten's patented, IAPMO certified "green fasten"technology to achieve a watertight seal. 6000 PRIOR TO COUNTERSINK mil IIIIIIOI series aluminum offers superb structural and fatigue strength,which in conjunction with anodization offers excellent corrosion resistance even in coastal environments. 'I 11•11. 1.92 NM • IAPMO-ES-certified for waterproofing—Tested to ICC ac286 j'I 44 I • Tested in accordance with UL 441—Waterproofing for rooftop penetrations • Anodized for long term corrosion resistance and best aesthetics • No shingle cutting required 2.53 • Fast and error-proof installation reduces overall impact on roof • Compatible with SolarCity Canopy Rail 3.75 • Rail is attached using Stainless Steel Fasteners .3801.010 Components Installation Instructions + r_ A. 5/16"Lag Screw 1. Drill pilot hole in rafter B. Stainless Steel+EPDM Sealing Washer 2. Seal pilot hole with roofing sealant 1.94 .11 f j C. Yeti(L-foot) 3. InsertEco Fasten flashing under upper layer of • D. Eco-Fasten GreenFasten Flashing shingle 3.00 4. 5. InstallPlace lag withSolarCity sealYetiing washer A i 4 ' — 440.°{ C z \ *4 \* ' ''''''' " t }p SolarCity. 73° SolarCity TSM-PC05 / TSM-PA05 THE UNIVERSAL SOLUTION Mono Multi Solutions • DIMENSIONS OF PV MODULE TSM-PC/PA 05 ELECTRICAL DATA SIC ISM-225 TSM-230 ISM-2.35 TSM-240 TSM-24S 947mm Pi:/PAt.S Pi:/PASS Fpm/PAitS PC/PMTS Pil/PAfs -Tsm Peak Power Watts Pem.(Wp) 225 230 235 240. 245 .En pc()5 . . Power Output Tolerance-P...x(%) i 0/+3 "0/+3 0/+3. 0/+3 0/+3 Maximum Power Voltage-Vor(V) '29.4 ,29.8 30.1 30.4 30.7 Maximum Power Current-!mw(A) `7.66 7.72 7.81 7.89. g 7.98 11.5 M ... pA05 n= - Open Circuit Voltage-Voc(V) 36.9 37.0 37.1 .37.2 37.3 /''� ; Short Circuit Current-Ise(A) 8.20 ,8.26 ;8.31 ::.8.37 8.47 THE UNIVERSAL SOLUTION Module Efficiencygm(%) 13.7 14.1 14.4 14.7 15.0 0 o Values a}Standard Test Conditions STC IAIr Mass AM7.5,Irradiance I OOOW/m',Cell Temperature 25°C) 3 ELECTRICAL DATA s NOCT TSM-225 ISM-230 I TSM-235 TSM-240 TSM-245 PC/PA05 l PC/PA05 PC/PA05 PC/PA05 j PC/PADS • .- Maximum Power(W) 164 ' 168 172 175 178 1 5 Maximum Power Voltage{V) ,26.9 27.1 27.4 27.7 27.8 MAX EFFICIENCY t�" _�, f 812mm 1180 Maximum Power Current(A) 6.12 6.20 6.27 :6.32 6.41 Open Circuit Voltage(V) i 33.8 33.9 34.0 34.1 :34.2 Short Circuit Current(A) 6.62 !6.68 6.70 6.75 6.83 ' ' '' '''''' '' 0 Module can bear snow loads up to 5400Pa and Back View NOCT:Irradiance a1800W/m',Ambient Temperature 20°C,Wind Speed IM/s. 245W w., wind loads up to 2400Pa MAX POWER OUTPUT -- -------- _---__._-_ MECHANICAL DATA E jEll , u Guaranteedo Solar cells Multicrystalline 156 x 156mm(6 inches) .y*o 0-+3% powerOUt("JUt Celiorientation )6O cells(6x 10) 1'0 YEAR •� - 40rnm_ A-A Module dimension 1650 x 992 x 40mm(64.95 x 39.05 x 1.57 inches) _--.. Weight ) 19.5kg(43.0 Ib) PRODUCT WARRANTY Glass High transparancy solar glass 3.2mm(0.13 inches) M '' ' 0 ^ High rformacno under low lir conditions ht diti g p � Frame Anodized aluminium allay, 25 �t Cloudy days. mornings and evenings 1-VC.l1RVES OF PV MODULE TSM-230 PC/PA 05 D Rax IP 65 rated YEARD _ _______ Cables/Connector `Photovoltaic Technology cable 4.0mm.(0.006 inches'), i ` ,1 i 1000mm(39.4 inches),MC4/H4 LINEAR POWER WARRANTY Independently certified by international B °°''w'm? ' 600wrro2 certification bodies IEC61215, IEC61730, UL1703, TUV Safety Class II, CE 3:. s= 60,,,,„2 TEMPeRAruRE RATINGS MAXIMUM RATINGS, Nominal Operating Cell :46°C(±2°C) Operational Temperature -40-+85°C _. ____._. _ 4x ---__-- .__._. _______ --_.i Temperature(NOCT) Founded in 1997,Trina Solar a tically 3 3. j-ww/m2 -""� Maximum System 1000V DC(IEC)/ nt Iraf d Pi anufu-ttr r,ineol� d 1 2 Temperature Coefficient of Poux -0.43%/°C Voltage 600V DC(UL) the Trod do ofIn of r»fers ani oIIs Manufactured accordingto International Quality 200W/m2 \} 9 - 1 m `�\ Temperature Coefficient of Voc -0.32%/°C Max Series Fuse Rating ISA tCea .1'lbly,of high 7s.ilily m modules, ISO / agement System Standards o= -. pe using both mono and n-uliicrytolllre and kin\Ironment Man's _- . �. Temperature Coefficient of Ise 0.047%/°C technol 'I s.Asaf July on the 1$09001, IS014001 or' toy 20� �� 401° _ampa ny has already ochieved an volragelvl annualized nameplate module oxpaclty of approximately 1.90PW.Trina Solar's Average efficiency reduction of 4.5%at 200W/m' WARRANTY wide range of products are used in according to EN 60904-1. 10 year workmanship warranty residential_orr,,rnerc!al,industrial and public�tlLty applic Dtirns throuah,ut tl-�a 25 year linear performance warranty world. (Please refer to product warranty for details) Only by matching an efficient cost- structure-,Nithrroven performancev'ill LINEAR PERFORMANCE WARRANTY a nve as an industry achieve grid parity. CERTIFICATION PACKAGING CONFIGURATION And at Irina solar,we ave bath. 40' o Modules per o0soYear Prduct Warranty•25 Year LintreraSritnPoeawer Warranty :25 cs 6 ` Q� ( .. M _ $ Modules per 2naner:650 pcs I-1- Irina lar Limited Addfyr r.cm otrgt value from Trirq sof , ISO j 4:!...?. E cCjles vvcrLe warranty - Ct 80% Trinasclarfears 5 IT 15 20 25 Trinasalar CAUTION:READ SAFETY AND INSTALLATION INSTRUCTIONS BEFORE USING THE PRODUCT. The power heh'md the pmtel Ird�,is:ry standard ■ Trina Solar The p,ww behind the papal ®2011 Tr!no Solar Limited.All rights reserved.Specifications included in this dotosheet are subject to change r without notice. • Intertek AUTHORIZATION TO MARK Intertek AUTHORIZATION TO MARK • This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set forth in the Certification Agreement and Listing a TSM-200PA05,TSM-205PA05,TSM-210PA05,TSM-215PA05,TSM-220PA05,TSM-25PA05,TSM Report. This authorization also applies to multiple listee model(s) identified on the correlation page of the Listing 230PA05,TSM 235PA05 TSM-240PA05 TSM-245PA05 and TSM-250PA05. Report. This document is the property of Intertek Testing Services and is not transferable. The certification mark(s) may be TSM-200PA05.05,TSM-205PA05.05,TSM-210PA05.05,TSM-215PA05.05,TSM-220PA05.05,TSM- 225PA05.05,TSM-230PA05.05,TSM-235PA05.05,TSM-240PA05.05,TSM-245PA05.05 and TSM- applied only at the location of the Party Authorized To Apply Mark. 250PA05.05. Applicant: Trina Solar Ltd Manufacturer: Changzhou Trina Solar Energy Co., Ltd. TSM-200PA05.10,TSM-205PA05.10,TSM-210PA05.10,TSM-215PA05.10,TSM-220PA05.10,TSM- 225PA05.10,TSM-230PA05.10,TSM-235PA05.10,TSM-240PA05.10,TSM-245PA05.10 and TSM- No.2 Tian He Road,Electronic Park, No.2 Tian He Road,Electronic Park, 250PA05.10. Address: New District,Changzhou,Jiangsu Address: New District,Changzhou,Jiangsu TSM-200PA05.15,TSM-205PA05.15,TSM-210PA05.15,TSM-215PA05.15, Country: China Country: China Models: TSM-220PA05.15,TSM-225PA05.15,TSM-230PA05.15,TSM-235PA05.15, Contact: Ms. Lihua Yin Contact: Ms.Lihua Yin TSM-240PA05.15,TSM-245PA05.15 and TSM-250PA05.15. Phone: +8651968879039 Phone: +8651968879039 FAX: +8651968879006 FAX: +8651968879006 TSM-200PA05.18,TSM-205PA05.18,TSM-210PA05.18,TSM-215PA05.18, Email: lihua.yin@trinasolar.com Email: lihua.yin@trinasolar.com TSM-220PA05.18,TSM-225PA05.18,TSM-230PA05.18,TSM-235PA05.18, Party Authorized To Apply Mark: Same as Manufacturer TSM-240PA05.18,TSM-245PA05.18 and TSM-250PA05.18. Report Issuing Office: Menlo Park,CA, USA G TSM-155DA01,TSM-160DA01,TSM-165DA01,TSM-170DA01,TSM-175DA01, Control Number: 4003042 Authorized by: C/Gi TSM-180DA01,and TSM-185DA01. illiam T.St rr,Certification Manager TSM-155DA01.05,TSM-160DA01.05,TSM-165DA01.05,TSM-170DA01.05, TSM-175DA01.05,TSM-180DA01.05,and TSM-185DA01.05. C US ranoIntertek This document supersedes all previous Authorizations to Mark for the noted Report Number. This Authorization to Mark is for the exclusive use of Intertek's Client and is provided pursuant to the Certification agreement between Intertek and its Client.Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned by the use of this Authorization to Mark.Only the Client is authorized to permit copying or distribution of this Authorization to Mark and then only in its entirety.Use of Intertek's Certification mark is restricted to the conditions laid out in the agreement and in this Authorization to Mark.Any further use of the Intertek name for the sale or advertisement of the tested material,product or service must first be approved in writing by Intertek.Initial Factory Assessments and Follow up Services are for the purpose of assuring appropriate usage of the Certification mark in accordance with the agreement,they are not for the purposes of production quality control and do not relieve the Client of their obligations in this respect. Intertek Testing Services NA Inc. 165 Main Street,Cortland,NY 13045 Telephone 800-345-3851 or 607-753-6711 Fax 607-756-6699 Standard for Flat-Plate Photovoltaic Modules and Panels UL 1703-Third Edition,March 15,2002,with revisions through May 23,2011 Standard(s): Requirements for Flat-Plate Photovoltaic Modules and Panels, ULC/ORD-C1703-01-First Edition, ammended October 2001 Product: Flat Plate Photovoltaic Modules Brand Name: Trina Solar ATM for Report SH11031298-001 Page 1 of 2 ATM Issued: 19-Jul-2011 ATM for Report SH11031298-001 Page 2 of 2 ATM Issued: 19-Jul-2011 ED 8.9.4(8-Jan-10)Mandatory ED 8.9.4(8-Jan-10)Mandatory