Loading...
Plans (39) ABBREVIATIONS ELECTRICAL NOTES INDEX LEGEND LICENSE A AMPERE 1. WHERE ALL TERMINALS OF THE DISCONNECTING PV1 COVER SHEET AC ALTERNATING CURRENT MEANS MAY BE ENERGIZED IN THE OPEN PV2 SITE PLAN 0 (E) UTILITY METER & WARNING LABEL OR # 180498 BLDG BUILDING POSITION, A SIGN WILL BE PROVIDED WARNING PV3 STRUCTURAL VIEWS 4 CONC CONCRETE OF THE HAZARDS PER ART. 690.17. PV4 UPLIFT CALCULATIONS ® INVERTER W/ INTEGRATED DC DISCO C COMBINER BOX 2. EACH UNGROUNDED CONDUCTOR OF THE PV5 THREE LINE DIAGRAM & WARNING LABELS D DISTRIBUTION PANEL MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED PV6 ELECTRICAL CALCULATIONS DC DC DIRECT CURRENT BY PHASE AND SYSTEM PER ART. 210.5. CUTSHEETS ATTACHED ..H DC DISCONNECT & WARNING LABELS EGC EQUIPMENT GROUNDING CONDUCTOR 3. A NATIONALLY-RECOGNIZED TESTING (E) EXISTING LABORATORY SHALL LIST ALL EQUIPMENT IN A AC COMPLIANCE WITH ART. 110.3. AC DISCONNECT & WARNING LABELS EMT ELECTRICALARGUAARD METER METALLIC TUBING O G LVR 4. CIRCUITS OVER 250V TO GROUND SHALL GALV GALVANIZED COMPLY WITH ART. 250.97, 250.92(B) CUTSHEETS ATTACHED 0 JUNCTION BOX RECEIVED GEC GROUNDING ELECTRODE CONDUCTOR 5. DC CONDUCTORS EITHER DO NOT ENTER HOG GROUND ORBUILDING OR ENCLOSURESETOUN IN METALLIC THE FIRST ACCESSIBLE AYS DC GENERAL NOTES 0 DC COMBINER BOX & WARNING DEC 3212 HDG HOT DIPPED GALVANIZED I CURRENT DISCONNECTING MEANS PER ART. 690.31(E). CITY OFTIGARD Imp CURRENT AT MAX POWER 6. ALL WIRES SHALL BE PROVIDED WITH STRAIN 1. THIS SYSTEM IS GRID-INTERTIED VIA A 0 DISTRIBUTION PANEL & WARNING BUILDING DIVISION INVS INVERTERS RELIEF AT ALL ENTRY INTO BOXES AS UL-LISTED POWER-CONDITIONING INVERTER. Isc SHORT CIRCUIT CURRENT REQUIRED BY UL LISTING. 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. O LC LOAD CENTER & WARNING LABELS kVA KILOVOLT AMPERE 7. MODULE FRAMES SHALL BE GROUNDED AT THE 3. PHOTOVOLTAIC SOURCE AND INPUT CIRCUITS AND kW KILOWATT UL-LISTED LOCATION PROVIDED BY THE INVERTER INPUT CIRCUIT ARE UNGROUNDED. LBW LOAD BEARING WALL MANUFACTURER USING UL LISTED GROUNDING 4. SOLAR MOUNTING FRAMES ARE TO BE GROUNDED O DEDICATED PV SYSTEM METER CITY OF TIGARD MIN MINIMUM HARDWARE. 5. ALL WORK TO BE DONE TO THE 2010 OBC CONDUIT RUN ON EXTERIOR Approved S t bj [ 14------ MIR MIRROR 8. ALL EXPOSED METAL PARTS (MODULE FRAMES, BASED ON THE 2009 IBC. CONDUIT RUN ON INTERIOR Conditionally Approved [ i NEC(NNEW RAIL,L BOXES, ETC.) SHALLGBE GROUNDEDHUSING 6. ALL CURRENTRICAL NATIONALELECTRIC CODE ASSHALL COMPLY WITH THE AMENDED --- INTERIORCE EQUIPMENTSee Letter to:Follow [ NENATIONAL ELECTRIC CODE UL LISTED LAY-IN LUGS LISTED FOR THEAttached NIC NOT IN CONTRACT PURPOSE. POSTS SHALL BE MADE BY THE OREGON ELECTRICAL SPECIALTY CODE. NTS NOT TO SCALE ELECTRICALLY CONTINUOUS WITH ATTACHED OC ON CENTERPermit Number:IttA' T- 1 - RAIL. Addre d Li,ir P PANEL BOARD 9. MODULE FRAMES, RAIL, AND POSTS SHALL BE By:, Date: � PL PROPERTY LINES BONDED WITH EQUIPMENT GROUND CONDUCTORS lr PV PHOTOVOLTAIC AND GROUNDED AT THE MAIN ELECTRIC PANEL. PVC POLYVINYL CHLORIDE 10. THE DC GROUNDING ELECTRODE CONDUCTOR Approved pians S SUBPANEL SHALL BE(B)SIZED I E690.47ORDING TO ART. ram �a VICINITY MAP shalt be on job site SCH SCHEDULE SS STAINLESS STEEL a ,GwP« ,YYh,,:arA � B SSD SEE STRUCTURAL DRAWINGS • V,r17.i 2 1,0:w""'"° 's""`a'` Southwest e=' STC STANDARD TESTING CONDITIONSo„k '' � �tsorhoods OFFICE COVY SWH SOLAR WATER HEATER Makn.m py TYP TYPICAL SWBrocMmMSt Greenway � ,yknsFerc,Rd crastwoodef P 2 ? �1 � UON UNLESS OTHERWISE NOTED * ....sac'e` '`° �`"'h'W °a”"` °" South Si ';i Y9 WnWan Path UPS UNINTERRUPTIBLE POWER SUPPLY Beavertail r Re "' � '�° �, , V VOLT a ;. 4�+ "tee" t0 * Portant!Park swroved s� Vmp VOLTAGE AT MAX POWER s ,. Pr f . di-AL � • 8a ,� Voc VOLTAGE AT OPEN CIRCUIT4,01-Y41,;'. le: W WATT Sanme ike* f $ saAhweat ACreak m:: ands � AaHi3R NEMA 3R, RAINTIGHT `�"°� a' ,'tom "sg6'la aS, a $ (Yak Crcok • pMtt Rack Bads Fool a '. e�eemo St /44? AddhonaREV BY DATE COMMENTS 4 � counbl'Glut y` t : CountyClLelaGo sw cs..a.m s+coonaw st RNp q. - . ,oMhSho °SWOP R"Foa MOLIStath 'e.'"-"V". Ever9�aaelz' gyy t k!u„rMMn as cc� SW Borate Ret B.441 R4 F.,a. �fi .� fdett9�'v Lake FMIaJ. ¢° as go,erne:« � �a _ ,., esu. . CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER J B—9 721 2 6 3 00 PREMISE ONNER: AHJ: Tigard DESCRIPnON: DESIGN: >1��4 CONTAINED SHALL NOT BE USED FOR THE MUSANTE, ROBERT R RASOR -fr Z BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MARKET: MODULES MUSANTE RESIDENCE NOR SHALL IT BE DISCLOSED IN WHOLE OR IN 9635 SOUTHWEST PIHAS STREET I'll'`SoIar'CituTRECIPNTS REST (28) TRINA SOLAR # TSM-245PC05/PA05.18 6.86kW ROOF MOUNTED PV ARRAY A ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TIGARD, OR 97223 THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI SOLARGTY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE INVERTER: PAGE NAME3055 Clearview Way San Mateo,CA PERMISSION OF SOLARGTY INC. PPA (2) XANTREX # GT2.8-NA-240/208 9712352743 SHEET: REV: DATE: 94402(650)638-1029 COVER SHEET PV 1 12/7/2012 (888)S(OL-CITY(7652489)www.solaraty.com PITCH: 34 ARRAY PITCH:34 MP1 AZIMUTH:179 ARRAY AZIMUTH: 179 IMATERIAL: Comp Shingle STORY: 2 PITCH: 34 ARRAY PITCH:34 25'to PL MP2 AZIMUTH:269 ARRAY AZIMUTH:269 I MATERIAL: Comp Shingle STORY: 2 • 3'Fre Setback AT'TACHP+.rl4_'-ii :e i:),--IAL: LE SPACED NO OREATER 1-1.1/:11`°4#;4CH%S ON CENTER IM ANY GREG r iON WHERE E A€ Y 13 LOCATED WITHIN 8 FEET Of A ROOF; — CGL HfP,EA'iE OR RIDGE. Pltdi + iiaC*�(3 a.3 rr. 3 N TOTAL ARRAY AREA: 530 SQ. FT. TOTAL ROOF AREA: 1890 SQ. FT. 30'to PL TOTAL ARRAY AREA IS N28% m 1 Fire Setback LEGEND OF TOTAL ROOF AREA. • 11 ti M FT\ o Li — — — C 5'to PL ir O (E) UTILITY METER & WARNING LABEL • .c---12-:-. � • I \ INVERTER W/ INTEGRATED DC DISCO S • \ B ® & WARNING LABELS °Non-..e. - � r ' i-r. -. 1-....1 DC DISCONNECT & WARNING LABELS i r 4.- ` � W. 1.21±>_1.1:,::::_.,%)._ ���� D i A0 AC DISCONNECT & WARNING LABELS f I l _, N� \'\' C t M �D 0 JUNCTION BOX _.. PV3 ��Inv ,1 0 DC COMBINER BOX & WARNING '�""J 0 DISTRIBUTION PANEL & WARNING I I B A PV3 I PV3 LC LOAD CENTER & WARNING LABELS 9635 Southwest Pihas Street I I O DEDICATED PV SYSTEM METER _®_ CONDUIT RUN ON EXTERIOR CONDUIT RUN ON INTERIOR 25'to PL � i GATE/FENCE --- INTERIOR EQUIPMENT 1 SITE PLAN N Front Of House Scale: 1/8" = 1' w _i E O 1' 8' 16' •�_�.. S CONFIDENTIAL— THE INFORMATION HERON JOB NUMBER: J B-9721263 0 0 PREMISE OYMER: AH,k Tigard DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE MUSANTE RESIDENCE ��►+�' MUSANTE, ROBERT R RASOR ,._ 4 BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MARKET: MODULES: -� � NOR SHALL IT BE DISCLOSED IN WHOLE OR IN 9635 SOUTHWEST PIHAS STREET ' ....link OfarCity PART TO OTHERS OUTSIDE THE RECIPIENTS REST (28) TRINA SOLAR # TSM-245PC05/PA05.18 6.86kW ROOF MOUNTED PV ARRAY �►' ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TIGARD, OR 97223 THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE: INVERTER: PAGE NAME: 94402 PERMISSION OF SOLARCITY INC. 9712352743 SHEET: REV DATE PPA 2) XANTREX # GT2.8-NA-240/208 T:(650)638-1028 F:(650)638-1029 SITE PLAN PV 2 12/7/2012 (888)-SOL-CITY(765-2489)www.solarcity.com I (L) 2x4 IOP CHORD @ 24" 'O.C. ,k 4 BLPhi:LN ir FOOTING, -y • " �x {'� k;;GEI7 ED) �i / 1 T i ' 1 - -- i_ : , _._ Ji. 7/ ,I, --2' ,YIP 1 WHEN MODULES ARE WITHIN 36" OF A ROOF EDGE, -- (E) 2x4 RAF IERS ISOI BE PLACED NO MORE THAN 24" ,nC 24" SPICING B FRONT VIEW OF MOUNTING PLANES Scale: 1/2" = 1'-0" 34' .l- '_- I ___-5'-6"- ----- / €'-- _ (E) 2x4 BOTTOM _ PRE-MANUFACTURED TRUSS CHORD 24" O.C. STRUCTURE MEETS THE PRESCRIPTIVE REQUIREMENTS OF .. _THE OSISC SECTION 305.9 _ J (E) 2x4 TOP CHORD TOP CHORD: 2x4 (0 24" 0.0. r INSTALLATION ORDER 1 SUPPORT: 2x4, WEB SOLAR , ANEL NOTE: RAIL TO BE PLACED IN THE UPHILL MEC HON ATIAI HED WITII MODULE __.— HO' MAX SPAN: 8'-8" LOCATE RAFTER MARK HOLE • CLAMPS, '-16 BOLTS, 1(?) I.00ATI IN, AND DRII PII or I 2x'=. AND NU.T i- AN E. SIDE VIEW OF MP1 _ _ (4) SEAQ � IL 0 (A) 2x.3 SOLARCi TY LAR RAIL �,`, _ - j T i+ (� 'r'v'I I H SCALE: 1/4" = 1' & BOLT i" Ir 'I PO: YURET"+.A.NE SEALANT. ,/\/ Y 1 t j �� V 1 INS'R. �((OI-;.SIEN HASHING. (E) COMPiiiii4k . sHINUI-E �� (1) 1 ���' I0)1 PLACE IHE LEVELING r0 1. LOOFASI.N I-LASIIIING 1- LL LA0 r � '41MINMIffrilMilliff-1 _ ---„ H SF AN. WASHER.i- >, 6” HF) 2x4 0(Il (E) ROODECKING . RE MANUFACTURED TRUSS CHORD CO 24" O.C. f " DIA LAG BOLT �� (E) LBW RUCTUREHET THE PRESCRIPTIVE - /- (5) REQUIREMENTS OF THE OSISC SECTION 3054 _ (24 EMBED, MIN) (F) RAE CFR TOP CHORD: 2x4 SUPPORT: 2x4, , 2x3 WEB 1 STANDOFF MAX SPAN: 5'-6" y Scale: 1 1/2" = 1' SIDE VIEW OF MP2 * SCALE: 1/4" = 1' CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER: UB-9721263 0 0 PREMISE OWNER: AH,k Tigard DESCRIPTION: DESIGN: `10441 CONTAINED SHALL NOT BE USED FOR THE MUSANTE ROBERT R MUSANTE RESIDENCE RASOR �_ BENEFIT OF ANYONE EXCEPT SCARCITY INC., MARKET: MODULES: a " NOR SHALL IT BE DISCLOSED IN WHOLE OR IN REST (28) TRINA SOLAR # TSM-245PC05/PA05.18 9635 SOUTHWEST PIHAS STREET 6.86kW ROOF MOUNTED PV ARRAY 0n SoiarCi PART TO OTHERS OUTSIDE THE CONNECTION IT PROJECT MANAGER: ty ORGANIZATION, EXCEPT IN CONNECTION WITH MOUNTING SYSTEM: TIGARD, OR 97223 THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE INVERTER: PAGE NAME 94402 PERMISSION OF SOLARCITY INC. 9712352743 : REV: DATE: (2) XANTREX GT2.8-NA-240/208 T:(6L-C 638-1028 F:(650)638-1029 PPA # / STRUCTURAL VIEWS PV 3 i2/�/20�2 (888)-SOL-CITY(765-2489)www.solarcity.com UPLIFT CALCULATIONS INPUT VARIABLES CALCULATIONS AND VALUES Required Variables Design wind pressures based upon: Mean Roof Height: 25 ASCE 7-05 Chapter 6 Wind Loading Exposure Category: C Equation 6.5.13.3: Component and Cladding Elements Basic wind speed(or city in the future): 95 Wind pressure P=qh*Cn*G Importance factor(1 for residential): 1 6.5.10:Velocity pressure qh=0.00256*Kz*Kzt*Kd*V^2*I Roof shape: pitched From Table 6-3: Roof Angle(degrees): 22 Kz=0.94 Roof zone: 3 From Figure 6-4: Contiguous sq. feet of array: 176 Kzt= 1.00 Least width of the building: 50 Obstructed wind flow? TRUE From Table 6-4: Kd=0.85 Local Topographical Features (choose "standard"or refer to pictures right,and below) From figure 6-1: V=95 Type of hill: none Hill height(h)(ft): From table 6-1: 1= 1 Slope of hill(degrees): Horizontal distance from hilltop to house(x): From Velocity Pressure Equation Height from bottom of hill to mean roof height(z): qh= 18.46 Design Wind Pressure From Figure 6-19B P(lbs.per sq.ft.)=qh*Cn*G Cn(uplift)=-1.41 Pd(downforce pressure)= 7.85 Cn(down)=0.50 Pu(uplift pressure)= 22.18 From 6.5.8.1 G=0.85 Max Tributary Area Feet Inches Individual Rows in Portrait X(E-W distance between standoffs)= 4 0 Trina TSM-2XXPA05 Y(N-S distance between standoffs)= 2 8 Amax(sq.ft.)=0.5*L*X Staggered Penetrations= Yes L(length of panel in ft. perpendicular to rail) 5.41 Module Rail Max. Span/Cantilever(in)= 72 35 X= 4.00 Y= 2.67 Max Uplift Force on a Single Standoff L= N/A Pmax(lbs.)=Amax*Pu Amax= 10.83 240 Dead Load Calculations Factor of safety=FI*D*NI/Pmax DL(lbs/sq.ft.)=(Mm+Mh)/(L*W) 5/16 x 4 in. = Lag size and length 984 =Capacity(lbs)of 1 lag(NDS) L(length of modules) 5.41 1 = NI(number of lags per standoff) W(width of modules)3.25 4.10 =Factor of safety Mm(weight of modules)43.00 Point Load Calculations Mh(weight of hardware per module)= 8.10 PL(lbs)=Amax*DL DL= 2.90 31 CONFIDENTIAL— THE INFORMATION HEREIN JCB NUMBER: J B-9721263 0 0 PREMISE OWNER: AH,k Tigard DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE MUSANTE, ROBERT R RASOR .:�"=! BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MARKET; MODULES MUSANTE RESIDENCE �„' O�� i NOR SHALL IT BE DISCLOSED IN WHOLE OR IN RESI (28) TRINA SOLAR # TSM-245PC05/PA05.18 9635 SOUTHWEST PIHAS STREET 6.86kW ROOF MOUNTED PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TIGARD, OR 97223 THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TWE: INVERTER: PAGE NAME SHEET: 94402 638-1029 PERMISSION OF SOLARCITY INC. DALE: PPA (2) XANTREX # GT2.8-NA-240/208 9712352743 UPLIFT CALCULATIONS PV 4 12/7/2012 (888)-SOL-CITy(7652489)50wwwsolarcty.com GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #6 DEC TO (E) DEER AT PANEL FT TOUA MAIN S-RVI(L PANEL Inv 1: DC Negatively Grounded )XA ITREX 612.8-NA-210/208 + ,F. 28) ZIJA SOLAR '}} TSM 2" 'CT PA+ a )/ p TA T .JJ ]J 1. 05 S 18/493 '4/IIH IRiZ wT.� IBLE CRIMP 0 A INV 1 hve ter; 2800W, 240V,50r0V1)C, 94Z Err. IN MO:Ve; 4.` 5 200/2 MAIN CIRCUIT BREAKER Inv '2; DC decyJtively Groundedaw, >z_.yWPIC, 411 , Oa.k r.,ma P,,r I I.;f^, f A INV 2 `1 X 8-NA-24d/208 (n . z �VO : Ji, me ter; 2iv, N, 4 ✓pmaX.3 (.Motor Numbor:94 541 4i{ *,MODULE CURRENT RATINGS ARE SHOWN AS Idc AND Imp IN Underground Ser/ice 1 ntrunce INV 3 THE DC STRINGS IDENTIFIER OF THE SINGLE LINE DIAGRAM. r MAIN SERVICE PANEL (E) WIRING BRYAN I Inverter 1 CU BRYAN [LER � ,� tdfar drv1R-XDisconnect ,20nA/2P c, JI IR (") LOADS A BJ 20A/!r' U(2.g �'A 21O/203 • 11 1 1 i A • • ik1 L1 t 1auyl m m I I • 41- I U 'tib ••__ I N GFP/GFCI �M J (> 1 / A -- GND 1T--,-y.--1 r_ f EGG/ _ I ,� DC+ pC+ 30A/2P 111 •LI Ti •-- I v GEC L DC- DC_ [,., 1 String(s)Of 14 On MP 1 • I I w I I GND I _EGC EGC /y I I Z I i ild — I —.l I �n_,v�f J N Inverter 2 J_ — o EGC/GEC I > XAN'REX izi- , Z-z I 0T2.8-NA-240/208 — 20A/2P T GEC I �y�• 2wv r —IP Ll I —I TO 120/240V I I I •-- L2 GFP/GFCI SINGLE PHASE _ r E N (2)UTILITY SERVICE I I J-L �/ - I •�Dc+ Dc+ I I I GND I-___EGC EEGC 1 String(s)Of 140n MP 2 M I I J_ � I I I I U 4 P01 _(i) l R- AMMER # 32230 ;-,7 A K.r- 00 Ak-a — t 1) 0PIT i !r. M to ick C1 _ AC DC Breaker; 30Af7P,2 1pocey - /'1 iter So ket; 17oA 4 144Wt Rinc e (2)0r_,:,d 2_d; o,8" 8, Copper o ) Y 1 (1)AN CAP; B Line Meter Socket Accessory B (1)BRYAN T #BR816.125RP Load Center; 125A, 120/2401, NEMA 3R -(2)CUTLER-RAMMER $BR220 1 Breryksr, 20A/2P, Z Spaces -(1)AWG T HWN 7, Black -____.�-. .__..-_ -__. 11 I -(1)AWG #1) HAN -) Reck 5 I 1 AWG #8, BRA-2, lea ( �_ 1 1 1 (2))AWG 110, U>F 2/RHW I Back Von =522.2 VDC Is: =8.47 ARC t_ 3 (I)AWG #10, `IWN 2 Red {1)AWG R HAA-2, 'Nnite NEUTRAL Vmp =240 VAC Imp=30.8 AAC J ") _' White1 -(1)AWG ¢iv, Sul Bare Copp_ EGO Vmo -429.8 VDC Imp-7.98 AOC 1)AWG #10, THWN-2, NEUTRAL /mp =240 VAC Imp=15.4 NAC - _,1 . . _ _ .-(1)AWG.#6,IHWA-2, Green EGC/GtC.7.(.1)Conduit KR; 3/4' EMT. . . . . . . , . . . . -'1)AWG THWN 2, Green EGC GFC 1)Conduit Kit; i 4" EMT #10, U Conduit 3/4" EMT t. .. . . .i��. .. . .� „ /. . ( v ./. . ( )ANG 7_ SE-2%RHW 1 Rock Von -522.2 VDC Isc -8.47 ADC /�\ (1)AWG #10, THWTJ 2, Block (2) (1)AWG #10, Solid Bare Copper EGC Vmp =429.8 VDC Imp=7.98 AX I �} 11D (1)AWG #10, ,Hi`NN 2, Red \.. \J -(1)AWG X10, 01WN-2, White NEU IRAL Vmp =240 VAC Imp=15,4 MC (1)Conduit Kit; 3/4" EMT -(1)ARC #6, TH'W'N-2, Green EGC/GEC-(1)Conduit Kit; 3/4" EMT I t CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER J B-9721263 00 PREMISE OWNER: NU Tigard DES RIP11ON: ki.4 CONTAINED SHALL NOT BE USED FOR THE MUSANTE, ROBERT R MUSANTE RESIDENCE RASOR NORBENFITSH OFLL ANYONE EXCEPT SOIN WHOLE INC., MART; MODULES: 9635 SOUTHWEST PIHAS STREET '�,�'�'O'a i NOR SHALL IT BE DISCLOSED IN N1iOLE OR IN ►S PART TO OTHERS ouT51DE THE RECIPIENTS REST (28) TRINA SOLAR TSM-245PC05/PA05.18 6.86kW ROOF MOUNTED PV ARRAY ORGANIZATION, EXCEPT IN CONNECTION WITH PROJECT MANAGER: MOUNTING SYSTEM: TIGARD, OR 97223 ° THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI 3055 Clearview Way San Mateo,CA SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE INVERTER: PAGE NAME: SHEET: REY: DATE 94402 PERMISSION OF SOLARgTY INC. PPA ) XANTREX # GT2.8—NA-240/208 9712352743 T:(650)638-1028 F:(650)638-1029 THREE LINE DIAGRAM PV 5 12/7/2012 (888)-SOL-CITY(765-2489)www.solarcity.com 1. Conductor Sizing per Art 690.8(6)(1) a. Conductor must have 30 deg. C ampacity >= 125% of continuous ELECTRICAL CALCULATIONS current per Art 215.2(A)(1). b. Conductor must have (after corrections for conditions of use) >= Module: 14 t ; - InvPwr W PTC StrLen Voltage Drop Calculations continuous current per Table 310.15(8)(16). Version 5_9.2 Inserter 1: 1 ; + £ ,i gVdrop= (Imp) * (2*Length)*(Resistance) / (Vmp) � �. or 14 Im Module: 14 Imp(A) Max. Length(ft) Wire c. Evaluate conductor temperature at terminations per 110.14(C). Inserter 2: 1.' + , e , ,*a 14 String: 7.98 50 C AWG 10 at Max Ase Hi: 80 deg F Ampacity of wire derated for conditions of termination must be >= Module: Vdrop= (7.98 A * 100 ft *0.00124 Ohms) / 395 V= 0.25% continuous current 1.25. All string terminations are rated at 90' C. Branch: 7.98 50 I C AWG 10 at Max Me Hi: 80 deg F Module:r Vdrop= (7.98 A * 100 ft *0.00124 Ohms) / 395 V= 0.25% 2. OCP Sizing per Art 690.8(6)(1) Total wltage drop in GDC conductors= 0.50% Inverter: 11.70 I 10 I C AWG 10 at 240V a. Round up to next size per Art 240.4(B) Total:, modules Total Inv Pwr PTC Vdrop= (11.70 A * 20 ft *0.00120 Ohms) / 240 V 0.12% Photovoltaic Module Electrical Specifications: Total STC d A, Combined 23.40 5 D AWG 08 at 240V 3. Conductor Sizing per Art 690.8(6)(1) Voc= V deg F deg C Vdrop= (23.40 A * 10 ft *0.00078 Ohms) / 240 V 0.08% a. Conductor must have 30 deg. C ampacity >= 125% of continuous Vmp= V Record Low Temp: 8 Total voltage drop in AC conductors= 0.19% current per Art 215.2(A)(1). lsc= A Max Aserage Hi Temp: 80 Total voltage drop in AC and DC conductors= 0.69% Imp= A Record Hi Temp: 106 41 Twc= V/deg C b. Conductor must have (after corrections for conditions of use) >= Tisc= mA/deg C continuous current per Table 310.15(B)(16). String Type A and 2 Combined Strings Type A Voc Correction Method: Branch Circuit Type A t ,,< 1yr. 1-way wire length: 50 ft � 1=strings per branch 1 c. Evaluate conductor temperature at terminations per Art 110.14(C). 14 Inserter Min Vdc Input Vdc 14 modules per series string voc Ampacity of wire derated for conditions of termination must be >= V Min Vmp at Max Temp :;Vdc Voc= V * Vmp= V Max Voc at Min Temp h; `,Vdc Vmp= V continuous current 1.25. All branch terminations are rated at 75' C Isc= A "` Inserter Max Vdc Input: Vdc Isc= q - min. Imp= A Max String Size: Imp= A Icont= A Art 690.8(A)(1) 1-way wire length: 50 It Icont= A Art 690.8(A)(1) 4. OCP Sizing 1.a Conductor: USE-2/RHW-2 at 90 deg C:Table 310.15(6)(16) 2.a lctorTHWN-2/(J5E2 1: at 90 deg C:Table 310.15(6)(16) a. Round up to next size per Art 240.4(B) ( t*1.25= (Amps) Conductor 1: con 5. Conductor Sizing per Art 690.8(6)(1) ill Icont*1.25=(Amps) 30 deg C ampacity= 30 deg C ampacity= a. Conductor must have 30 deg. C ampacity >= 125% of continuous 1.b Icont=(Amps) 2.b Icont=(Amps) current per Art 215.2(A)(1). Start ampacity Start ampacity Temperature derate(%=F) Temp.derate(%=F) b. Conductor must have (after corrections for conditions of use) >= Conduit fill derate(%=#) Cndt.fill derate(%=#) continuous current per Table 310.15(8)(16). Derated ampacity Derated ampacity Term 1 Term 2 1.c Icont*1.25=(Amps) Temp table c. Evaluate conductor temperature at terminations per Art 110.14(C). Ampacity 2.c Icont*1.25=(Amps) Ampacity of wire derated for conditions of termination must be >= Ampacity continuous current*1.25. All inverter output terminations are rated at 1.d Icont*1.25=(Amps) 4 2.d EGC C AWG 10 C AWG 10 Art.250.122 75' C. OCP size= OCP size= 6. OCP Sizing Inverter Type A Output Combined Inverter Output ' ' "''`,', mak,. �. 1 1-way wire length: 10,ft Service Voltage= 240 Volts a. Round up to next size per Art 240.4(6) ,`,7;.,. 9 - Icont= A Art 690.8(A)(1) Total Inserter Power= Nameplate Watts 1-way wire length: 5 ft 3.a Icont*1.25=(Amps) ; 4 , ' A Art 690.8(6)(1) (cont=#of inserters*max inserter current Art 690.8(A)(1) 7. Conductor Sizing per Art 690.8(6)(1) OCP size= A Art.240.6(A) Icont=(Amps) a. Conductor must have 30 deg. C ampacity >= 125% of continuous 3.b Conductor • r.THWN-2 at 90 deg C:Table 310.15(6)(16) 4.a Icont*1.25= (Amps) .y ,""„°.7-`,,,LT-,..7.A Art 690.8(6)(1) current per Art 215.2(A)(1). Icont*1.25=(Amps) OCP size= A Art.240.6(A) 30 deg C ampacity= 4.b Conductor THWN-2 at 90 deg C:Table 310.15(6)(16) 3.c Icont=(Amps) .,r b. Conductor must have (after corrections for conditions of use) >_ 30 Icont deg C25=(Amps) Start ampacity 30 C ampacity= continuous current per Table 310.15(6)(16). Temperature derate(%=F) 4.c Icont=(Amps) Conduit fill derate(%=#) �"°° ° Start ampacity Derated ampacity y I Temp.derate(%=F)c. Evaluate conductor temperature at terminations per Art 110.14(C). Ampacity of wire derated for conditions of termination must be >= 3.d Icont*1.25=(Amps) '°` f Cndt.fill derate(%=#) continuous current*1.25. All inverter output terminations are rated at Ampacity Derated ampacity 3.e EGC = C AWG 10 Art.250.122 4.d Icont*1.25=(Amps) 75' C min. .mom,: GEC = D AWG 08 Art.690.47,250.166(6) Ampacity P Y CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER JB-9721263 00 PREMISE OWNER: AHJ: Tigard DESCRIPTION: DESIGN:CONTAINED SHALL NOT BE USED FOR THE MUSANTE, ROBERT R RASOR ��►"v' BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MARKET: MODULES: MUSANTE RESIDENCE NOR SHALL IT BES DISCLDEED IN WHOLE OR IN REST (28) TRINA SOLAR # TSM-245Pco5/PAo5.1s 9635 SOUTHWEST PIHAS STREET 6.86kW ROOF MOUNTED PV ARRAY "`'if'SoIarCit.yORGA TO TION, EEPTOUTSIDEINTHE ECTION WITPROECT MANAGER: TIGARD, OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH MOUNTING SYSTEM: THE SALE AND USE OF THE RESPECTIVE SC ECOFASTEN YETI SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAYMENT TYPE INVERTER PAGE NAME: 3055 Clearview Way San Mateo,CA PERMISSION OF SOLARCITY INC. SHEET: REV PATE 94402 PPA (2) XANTREX # GT2.8-NA-240/208 9712352743 ELECTRICAL CALCULATIONS PV 6 12/7/2012 (888)-SOL-CITY(7652489)50wwwsolarc?ty.mm