Report (2) • , Response: See revised plans. 7) Show all hold down locations on plans. Response: All Hold-downs are now shown on all plans, including the foundations. Reference modified plans. 8) Provide engineer calcs showing depth, length, and width of foundation at hold down locations. Response: All buildings were carefully reviewed and footing sizes were checked for all HD's for uplift. Buildings 1, 5 and 6 have been modified to include larger footings as needed. See included additional footing calculations and revised building foundation plans. 9) All ground floor units are required to be B type accessible units. Response: Reference modified plans. 10) Provide 60 inch clearance between appliances and counters on floor plans in u-shaped kitchen. Response: Reference modified plans. 11) Show option A or B for B type units. Response: Reference modified plans. 12) Show details of A type showers including controls, required grab bars. Response: Reference modified plans. 13) All general notes are to be upgraded to current code requirements. Response: Reference modified plans. 14) Provide calcs for 17ft 2x10s @ 16" oc joist on third floor framing. Response: See included calculations per designer. 15) Show connections for back span beam to cantilever beam at both ends. Response: Reference modified plans. 16) Detail #2 from calcs to be on main plans and type of hold down required. Response: Reference modified plans. 17) Detail#4 from calcs to be on main plans. Response: Reference modified plans. Ep PROFe g. 154) 65469PE OREGON Sincerely, _ 1 P / P0 Julie Havelka, PE Summit Engineering, LLC ‘... 5. 40/1 971-251-0194 Julie@summitengineeringllc.com C °,�itf SUMMIT ENGINEERING L.L.C. July 11, 2016 Project: New Apartments 9550 SW Greenburg Road Tigard, OR 97202 Subject: Application no. SIT2015-00013 To DAN NELSON, For the above referenced project, the latest set of Structural drawings dated July 7, 2016 are correct and current. tDPROPe stsio 65469PE t OREGON Sincerely, \ktei' Julie Havelka, PE �0,2 Summit Engineering, LLC 6 45° '( 971-251-0194 Julie@summitengineeringllc.com FOR OFFICE USE ONLY—SITE ADDRESS: This form is recognized by most building departments in the Tri-County area for transmitting information. Please complete this form when submitting information for plan review responses and revisions. This form and the information it provides helps the review process and response to your project. mi City of Tigard • COMMUNITY DEVELOPMENT DEPARTMENT . - Transmittal Letter 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.718.2439 •www.tigard-or.gov TO: DATE RECEIVED: DEPT: BUILDING DIVISION RECEIVED JUL 1 i. 2016 FROM: l 1E"j2L.>, CITY OFTIGARD BUILDING DIVISION COMPANY: ,a 'x�tzS PHONE: C�3 j�,�,�• ��a By YL.�, RE: Address) ( - L f b�� czoe ttAddress ( ernut er flocs roject name or subdivision name and lot number) ATTACHED ARE THE FOLLOWING ITEMS: X Additional set(s)of plans. X Revisions: Cross section(s)and details. Wall bracing and/or lateral analysis. V( Floor/roof framing. Basement and retaining walls. x Beam calculations. X Engineer's calculations. Other(explain): REMARKS: C. iT.L G S# T = NS� - LSCO AiS Routed to Permit Technician: Dater M 111111111111=� ! "�j�;: Fees Due: • Yes j'o Fee Descri.tion: Amour i ue: Special Instructions: Re i rint Permit ser PE : ❑ Yes El No ❑ Done A• •licant Notified: Date: Initials: I:\Building\Forms\TransmittalLetter-Revisions.doc 05/25/2012 FOR OFFICE USE ONLY—SITE ADDRESS: This form is recognized by most building departments in the Tri-County area for transmitting information. Please complete this form when submitting information for plan review responses and revisions. This form and the information it provides helps the review process and response to your project. City of Tigard • COMMUNITY DEVELOPMENT DEPARTMENT Transmittal Letter 1111 T l G A R D 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.718.2439 • www.tigard-or.gov TO: A N ;-.\,0is 4 1 0u5 . DATE RECEIVED: DEPT: BUILDING DIVISION RECEIVED FROM: NOV 1 215 CITY Or U-:-40 COMPANY: Lf s)24.17 -t.1 t,--0,QS BUIL14N(. tU:',;. A PHONE: 93 6243a. c .o 4s- RE: SIL.). 7.RE: sisCO S cw No_-E .-x urz.� _ • �� (Site Address) ( it Num er GQ -.--.- V fL- A i2_t.+-�� x.,, s- 6 l<� S `3 (Project name or subdivision name anlot number) ATTACHED ARE THE FOLLOWING ITEMS: ;:Copies ,ya DescrlAtion: \ ' Copies: [''Description ;' , . .', XAdditional set(s) of plans. Revisions: Cross section(s) and details. Wall bracing and/or lateral analysis. Floor/roof framing. Basement and retaining walls. Beam calculations. Engineer's calculations. Other(explain): C REMARKS: . 4.--, , ,„,.,,,,,_ c� 1 (.1.2 .12-kc ..t. 'NIS 4 it,,,rte ILS t=-T _. ,„. FOR OF CE17 E ONLY Routed to Permit Technician: ate: '2'5 (c-, Initials 1 Fees Due: ❑ Yes o Fee Description: Amount sue: $ $ $ Special Instructions: Reprint Permit(per PE): 0 Yes ❑No ❑ Done Applicant Notified: Date: Initials: I:\Building\Forms\TransmittalLetter-Revisions.doc 05/25/2012