Loading...
Report (10) AUG-31-2016 WED 02:54 PM AUTOMATIC FIRE PROTECT FAX NO. 5036921186 P. 04 g5A.o./(e —O7( Lir .. �O SLS tez�car Lel/ tqRECIEN/—ricaWorldwide Protection AUG 3 12016 Contacts www.tyoa-fire.com Products Ci Y OF 110;44) If—�, . t\ O tZ.' Series TY-B, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General woricE - 1-,.4‘4, , The Series TY-13 Sprinklers described Description herein must be installed and maintained in compliance with this document,as The TYCO Series TY-B, 5.6 K-factor, well as with the applicable standards a "" r et Upright(TY315)and Pendent(TY325) of the National Fire Protection Asaocia- ' Sprinklers described in this data sheet tion,in addition to the standards of any " b'.it '' are standard response,standard cover- othr authorities havingJurisdiction. '� ` age,decorative 5 mm glass bulb type Failure to da so may impair the perfor- 'f "''`' ' , , spray sprinklers designed for use In mance of these devices. '' ,,; ! '`11,4 light, ordinary, or extra hazard, corn- illq mercial occupancies such as banks, The owner Is responsible for maintain hotels, shopping malls, factories. ing their fire protection system and refineries,and chemical plants, devices in proper operating condition. The installing contractor or sprinkler The recessed version of the Series manufacturer should be contacted with ail TY-B Pendent Sprinkler, where appil- any questions. ,«"ii,, ea i"` , !' cable,is intended for use In areas with a }1fi:�,!!��:i�i, ` ,t :!'i finished ceiling.This recessed pendent - it ; sprinkler uses one of the following: Sprinkler �lii • A two-piece Style 15 Recessed „ t;J 1 �, ,u ,y ,.; y � ,.i � qlf� o� � f .���f 1}rb:,li, Identificationust- i,,, , > ', t, , ,,]I,, menttup to 5/8 inch(15,9 mm)fromNumbers �i;),r4r`�, ��+,, ”'• : f414'�,,1` the flush pendens position. �u �e (SI s) 'i�,P .r , -.4,. , ,.f1 �{i • A two-piece Style 20 Recessed TY315 Upright 5.6K, 1/2"NPT �, Escutcheon with recessed adjust TY325 Pendent 5.6K, 1/2"NPT ; '',,,,- ,,%,,,, ment up to 1/2 inch (12,7 mm)from the flush pendent position. Technical MV The adjustment provided by theTemperature Ratings Recessed Escutcheon reduces the Data 135°F(57°C) accuracy to which the fixed pipe drops 155°F(68°C) to the sprinklers must be cut. Approvals 175°F(79°C) Intermediate level versions of Series UL and C-UL Listed 200°F 93°C) FM, LPCB,and VdS Approved 296°F(141°C) TY-B Sprinklers are described in CE Certified 360°F(182°C)1 Technical Data Sheet TFP352.Sprinkler guards and shields are descnbed in Sprinklers with Polyester Finish are t UL,C-UL,and VdS Approved only Technical Data Sheet TFP7B0. UL and C-UL Listed as Corrosion- Finishes Resistant Sprinklers. Sprinkler Refer to Table A Maximum Working Pressure Recessed Escutcheon:White Coated, 175 psi(12.1 bar) Chrome Plated,or Brass Plated 250 psi(17-2 bar)* 'The maximum working pressure of 250 psi Physical Characteristics `-' (17.2 bar)only applies to the listing by Un- Frame Bronze IMPORTANT derwriters Laboratories,Inc.(NL). Button Brass/Copper Always refer to Technical Data Sealing Assembly Stainless Sheet TFP700 for the "INSTALLER Discharge Coefficient Steel w/TEFLON WARNING" that provides cau- K=5.6 GPM/psis (80,6 LPM/barter) Bulb Glass tions with respect to handling and Compression Screw Bronze installation of sprinkler systems and Deflector Bronze components.Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fall to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP162 AUG-31-2016 WED 02:54 PM AUTOMATIC FIRE PROTECT FAX NO. 5036921186 P. 05 TFP152 Page 2of4 Components: *Temperature rating Is **Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request, 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT"''' NOMINAL MAKE-IN ESCUTCHEON >T rTr 1-�1�\\ i 5 e©t 7/16" — (11,1 mm) eller, 4 NOMINAL 2" ----T I 1 MAKE-IN ' (50,8 mm) \ T , �ta�� 2 is j) �Y 2" 1-3/8"" r1 (50,8 mm) (34,9 mm) r � ��� 3 ,1 = ! WRENCH Ii ������_ FLATS f 1 "' 1/2"NPT""" DEFLECTOR* �---- 2-7/8'"(73,0 mm)PIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-B UPRIGHT(TY315)AND PENDENT(TY325)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT,STANDARD RESPONSE Operation Installation The glass bulb contains a fluid which The TYCO Series TY-B, 5.6 K-factor, ,.. io/i-- • • WRENCH RECESS expands when exposed to heat.When Upright(TY315)and Pendent(TY325) (USE ONLY the rated temperature is reached,the Sprinklers must be installed In accor- END"A') fluid expands sufficiently to shatter the dance with this section. " glass bulb, allowing the sprinkler to activate and water to flow. General Instructions FIGURE 2 Do not install any bulb type sprinkler if W-TYPE 6 the bulb is cracked or there Is a loss of SPRINKLER WRENCH Design liquid from the bulb.With the sprinkler ., held horizontally, a small air bubble WRENCH Criteria should be present.The diameter of the RECESS The TYCO Series TY-B, 5,6 K factor" air bubbler approximately inch U right( 32 TY315)and Pendent(TY325) (1,6 mm)for the 135°F (57°C)to 23°C) p inch (2,A mm) for the 360 F {182 Cj �� r Sprinklers are intended for fire protec- temperature ratings. ri tion systems designed in accordance with the standard installation rules A leak tight 1/2 inch NPT sprinkler recognized by the applicable Listing joint should be obtained by applying a or Approval agency (e.g., UL Listing minimum-to-maximum torque of 7 to 14 is based on the requirements of NEPA ft.-lbs- (9,5 to 19,0 Nm). Higher levels ►, • 13, and FM Approval is based on the of torque may distort the sprinkler inlet requirements of the FM Loss Proven- and cause leakage or impairment of the PUSH WRENCH tion Data Sheets). Only the Style 15 sprinkler. IN TO ENSURE or Style 20 Recessed Escutcheon,as ENGAGEMENT Do not attempt to compensate for WITH SPRINKLER applicable,is to be used for recessed insufficient adjustment In the escutch- WRENCHING AREA pendent installations. eon plate by under-or over-tightening FIGURE 3 the sprinkler. Readjust the position of WTYPE 7 RECESSED the sprinkler fitting to suit. SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-B Upright and Pendent Sprinklers must be installed in accor- dance with the following instructions- Step 1. Install pendent sprinklers In the pendent position; install upright sprinklers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. AUG-31-2016 WED 02:54 PM AUTOMATIC FIRE PROTECT FAX NO. 5036921186 P. 06 TFPIS2 Page 3 of 4 Step 3.Tighten the sprinkler into the 2-7/8"DIA sprinkler fitting using only the W-Type (73,0 mm) 6 Sprinkler Wrench (Figure 2). With reference to Figure 1,apply the W Type 2-1/4"DIA. 6 Sprinkler Wrench to the wrench flats. FACE OF r (57,2 mm) — Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers es FLUSH The Series TY-B Recessed Pendent 3/9±5/16" J'1 Sprinklers must be installed In actor- (9,5±7,9 mm) 7 Ai dance with the following Instructions. f / j \IV Step A..After Installing the Style 15 or MOUNTING 1/e" Style 20 Mounting Plate,as applicable, SURFACE (3,2 mm) over the sprinkler threads and with _.----._ pipe-thread sealant applied to the pipe CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) threads,hand-tighten the sprinkler into TY-8 PLATE 3/4"(19,1 mm) the sprinkler fitting. Step B.Tighten the sprinkler into the FIGURE 4 Step B. fitting using onin the W-Type SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325) 7spriRecessed Sprinkler Wrench (Figure WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque 2-7/e"DIA. sprinklers 7 to 14 ft-lbs. (9,5 to 19,0 ---__ (73,0 mm) Nm). FACE OF Step C.After the ceiling is installed or SPRINKLER 2-1/4"DIA. - the finish coat is applied, slide on the FITTING (57,2 mm) Style 15 or Style 20 Closure over the 5/16:1/4" Series TY-B Sprinkler and push the (7,9±6,4 mm) 1/2'(12,7 mm) Closure over the Mounting Plate until FLUSH Its flange contacts the ceiling, )7 41------ 1 /,� LI- Care � Care andf / `~ } Maintenance SURFACE �, (3,21/mm) The TYCO Series TY-B, 5.6 K-factor, – Upright(TY315)and Pendent(TY325) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-13 PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 6 Before closing a fire protection system SERIFS TY-B RECESSED PENDENT SPRINKLER ASSEMBLY(TY325) main control valve for maintenance WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that It controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. The owner is responsible for the system from the proper authorities Sprinklers that have been exposed to inspection,testing,and maintenance of and notify all personnel who may be corrosive products of combustion,but their fire protection system and devices affected by this action. have not operated,should be replaced in compliance with this document, as Absence of the outer piece of an if they cannot be completely cleaned by well as with the applicable standards escutcheon, which is used to cover wiping the sprinkler with a cloth or by of the National Fire Protection Associa- a clearance hole, can delay sprinkler brushing it with a soft bristle brush. tion (e.g., NFPA 25), in addition to the operation in a fire situation. Care must be exercised to avoid dam- standards of any other authorities hay- ing jurisdiction. Contact the installing The owner must assure that the agep contractor or sprinkler manufacturer sprinklers are not used for hanging and after installation. Sprinklers dam- regarding any questions. any objects and that the sprinklers are aged by dropping, striking, wrench only cleaned by means of gently dust- twist/slippage, or the like, must be Automatic sprinklers are recommended ing with a feather duster; otherwise, replaced. Also, replace any sprinkler to be inspected,tested,and maintained non-operation in the event of a fire or that has a cracked bulb or that has lost by a qualified Inspection Service in inadvertent operation may result. liquid from its bulb. (Ref. Installation accordance with local requirements Section.) and/or national codes. Sprinklers which are found to be leak- ing Inspectionsper or exhibiting visible signs of corro- p sion must be replaced. NFPA 25 are required;however,instead of Inspecting from the floor level, a Automatic sprinklers must never be random sampling of close-up visual painted, plated, coated, or otherwise inspections should be made. altered after leaving the factory. AUG-31-2016 WED 02:54 PM AUTOMATIC FIRE PROTECT FAX Na 5036921186 P. 07 TFP1S4 Page 4 of 4 P/N* 77 - XXX - X _ XXX - SIN SPRINKLER TEMPERATURE FINISH RATINGS 57(7 5.6K UPRIGHT(1/2"NPT) TY315 1 NATURAL BRASS 135 135°F(57°C) 571 5.BK PENDENT(112"NPT) TY325 3 PURE WHITE(RAL6010)""— 155 155°F(68°C) POLYESTER Uan aulllx T for ISO 7-1 connectIon; SIGNAL WHITE(RAL8003) Tor exarnple,77-570.4.176-I 4 POLYESTER 175 1Y5°F(79°C) S CHROME PLATED 200 200°F(03°C) ""Faatern Hemisphere sales only 286 286°F(141"C) 360 360°F(182°C) 000 OPEN`"` '"'OPEN Indlcato :prinkler gnnnmbly without Giese Bulb, Dutton,and Sealing Assembly TABLE A SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- ' www,tyco-fire.com. ability.When placing an order,indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY B Upright or Pen- dent(specify)Sprinkler, SIN (specify), K=5.6, Standard Response, (specify) temperature rating,(specify)finish,P/N (specify,refer to Table A) Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify')finish, P/N(specify') Specify:Style 20 Recessed Escutcheon with(specify")finish, P/N(specify°) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1400 Pennbrook Parkway,Lansdale,PA 19446'Telephone+1-215-362-0700 Copyright©20141yco Fire Products,LP. All rights reserved. TEFLON In trademark of Tho DuPont Corporation. File Prgtoctian Products