Report Sw Fire Protection Services, Inc. 5573 SW Arctic Dr 1 J Beaverton Or,97005 D O Phone: (503) 590-3732 J I 1 N Fax: (503) 628-6214 Sumner College � I 15350 SW Sequoia Parkway Portland, Oregon DEC 2 2914 FIRE ALARM DESCRIPTION C1TYUF IGARD BUILDING DPVISION DESCRIPTION An automatic fire protection system will be installed utilizing an addressable control panel. This will provide for monitoring of smoke detectors. Gentex ceiling and wall mount horn/strobes and strobes will be utilized in this installation. All audible devices will sound in the ANSI temporal pattern. Primary power to the panel shall be 110 VAC utility power with a 12VDC 7aH battery back-up. All fire alarm circuits will be wired with 16 gauge Fire Alarm Cable with the exception of NAC circuits, which will be wired with (minimum) 14 gauge Fire Alarm Cable. Monitoring will be provided through Alarm Central Station, A UL Listed Monitoring Company in Beaverton, OR. (503.641.6761) All installation will be done according to NFPA 70 & 72 standards. Work will be performed in a neat and professional manner. All work will be performed according to the timeline set. All equipment will be UL listed and approved for the application. SYSTEM COMPONENTS Silent Knight 5820XL Addressable Fire Alarm Control &Communicator Silent Knight SD 500 Series Smoke Detectors and Heat Detectors Silent Knight 5496 Distributed Power Supplies Silent Knight Addressable Relay Modules Gentex Horn/Strobes Global Project Values: SILENT Project Name: Sumner College Standby Hours: 24 KNIGHT Project ID: Alarm Mins: 5 Prepared By: Jeff C Derating Factor: 1.2 5496 Power Expander Calculations Date: 12/2/2014 Voltage Drop Warning Version 02.24.09 Threshold%: 10 Panel ID: 5496-A Model: 5496 Power Expander Max NAC Current: 3.0 Amps Location: Volts: 24 VDC Max Panel Current: 6.0 Amps Part.# Description Qty Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Standby Alarm &Type 1000 Ft. One-Way Ohms EOL 5496 5496 Pwr Module 1 0.040 0.160 NAC#1 Notification Appl Circuit 0.000 1.036 #14 Solid 3.14 270 1.70 18.64 8.61% NAC#2 Notification Appl Circuit 0.000 0.942 #14 Solid 3.14 260 1.63 18.86 7.54% NAC#3 Notification Appl Circuit 0.000 0.626 #14 Solid 3.14 240 1.51 19.46 4.63% NAC#4 Notification Appl Circuit 0.000 0.902 #14 Solid 3.14 250 1.57 18.98 6.94% Total Standby Current(Amps) 0.040 3.666 Total Alarm Current(Amps) Alarm Time In Minutes/60 (5 Mins) Time In Hours 24 0.083 a Total Standby AH Required 0.960 0.306 Total Alarm AH Required Total Combined AH Required 1.27 Command Shortcuts Multiply By The Derating Factor 1.20 Minimum Battery AmpHours Required 1.52 Configure Circuits Print Page v DSiIJCA I kNI( III Circuit Configuration - Project Name: Sumner College Project ID: 0 Prepared By: Jeff C Date: 12/2/2014 Ckt. Number: NAC#1 Panel ID: 5496-A Ckt. Name: Notification Appl Circuit Use: Notification Appl Circuit • Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 2 Gentex GCC24 Horn/Strobe (75cd) 0.000 0.222 0.000 0.444 2 Gentex GES324 Strobe (75cd) 0.000 0.116 0.000 0.232 2 Gentex GCS24 Strobe (30cd) 0.000 0.120 0.000 0.240 1 Gentex GCS24 Strobe (15cd) 0.000 0.120 0.000 0.120 0.000 0.000 Totals 0.000 1.036 Ckt. Number: NAC#2 Panel ID: 5496-A Ckt. Name: Notification Appl Circuit Use: Notification Appl Circuit • Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 1 Gentex GCC24 Horn/Strobe (75cd) 0.000 0.222 0.000 0.222 1 Gentex GCS24 Strobe (15cd) 0.000 0.120 0.000 0.120 3 Gentex GCS24 Strobe (30cd) 0.000 0.120 0.000 0.360 2 Gentex GCS24 Strobe (15cd) 0.000 0.120 0.000 0.240 0.000 0.000 Totals 0.000 0.942 Ckt. Number: NAC#3 Panel ID: 5496-A Ckt. Name: Notification Appl Circuit Use: Notification Appl Circuit • Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 1 Gentex GCC24 Horn/Strobe (75cd) 0.000 0.222 0.000 0.222 1 Gentex GCS24 Strobe (75cd) 0.000 0.200 0.000 0.200 2 Gentex GES324 Strobe (15cd) 0.000 0.042 0.000 0.084 1 Gentex GCS24 Strobe (15cd) 0.000 0.120 0.000 0.120 0.000 0.000 Totals 0.000 0.626 •FNlGIF1 Circuit Configuration Project Name: Sumner College Project ID: 0 Prepared By: Jeff C Date: 12/2/2014 Ckt. Number: NAC#4 Panel ID: 5496-A Ckt. Name: Notification Appl Circuit Use: Notification Appl Circuit Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 1 Gentex GCC24 Horn/Strobe (75cd) 0.000 0.222 0.000 0.222 1 Gentex GCS24 Strobe (75cd) 0.000 0.200 0.000 0.200 2 Gentex GCS24 Strobe (30cd) 0.000 0.120 0.000 0.240 2 Gentex GCS24 Strobe (15cd) 0.000 0.120 0.000 0.240 0.000 0.000 Totals 0.000 0.902 INTELLIKNIGHT FIRE ALARM CONTROL PANEL IntelliKnight® Model 5820XL 1 Addressable Fire Alarm Control System t Ilk The IntelliKnight System is the easy „ way to make the most of fire alarm ite technology. IntelliKnight is the first fire alarm system to provide you with the revolutionary value and performance of addressable sensing technology combined with exclusive, built-in digital communication, distributed intelligent power, a modular design and an expanded, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-446-6444, or in Minnesota, call 612-493-6435. Description programming via PC. The IntelliKnight 5820XL performs • Built-in digital communicator. drift compensation and calibration • Built-in Form C trouble relay checks on each of the sensors in rated at 2.5 amps at 24 VDC. the system. • Two built-in Form C ro rammable relays rated at 2.5 ,-- The basic IntelliKnight 5820XL P 9 Y system can be expanded by adding amps at 24 VDC. modules such as the Model 5860 • Uses standard wire—no shielded El Remote Annunciator, Model or twisted pair required. 5815XL Signalling Line Circuit • Supports Sounder Bases. Expander, the Model 5824 Specifications • Serial/Parallel Interface (for printing Primary AC: 120 VRMS at 50 /60 system reports), and the 5895XL hz, 2.5A Intelligent Power Module. The Model 5820XL also features a Total Accessory Load: 5A at 24 powerful built-in dual line fire VDC communicator that allows for 5 amps at 24 VDC of power-limited reporting of all system activity to a notification power Weight: 28 lbs. (12.8 kg) remote monitoring location. Standby Current: 140 mA Color: Red Features Alarm Current: 260 mA Telephone Requirements: • Up to 381 addressable points. TM Flexput Circuits FCC Part 15 and Part 68 approved • Supports Class B (Style 4) and Six programmable circuits which Type of Jack: RJ31X (two required) Class A(Style 6) configuration can be programmed individually as: for SLC, SBUS, and Flexput Approvals: circuits. Notification circuits: 3 amps of UL Listing • Distributed, intelligent power. power limited power per circuit at NFPA 72 -Central Station • Drift compensation. 24 VDC. -Remote Signalling • FlexputTM I/O circuits. Auxiliary power circuits: 3 amps -Local Protective • Eight pre-programmed output of power-limited power per circuit at Signalling System cadences, (including ANSI-3.41), 24 VDC. -Auxiliary Protected and 4 programmable outputs. Initiation Circuits: 100 mA of Premises Unit • Built-in annunciator with 80- power limited power per circuits at CFSM: 7165-0559: 130 character LCD display. 24 VDC. • RS-485 bus provides communi- Mechanical Speafications: SILENT cation to system accessories. Dimensions: 16"W x 26.4"H x ` KNIGHT • Built-in RS-232 interface for 4.65"D (40.6 x 67 x 11.8 cm) a INTELLIKNIGHT FIRE ALARM CONTROL PANEL ~! `1 IntelliKnight Model 5820XL Addressable Fire Alarm , .; ,, , Control Panelii. ''t,A Indicator Lights: amp hours. An additional cabinet capability, download phone number GENERAL ALARM (Red) On for enclosure is required for batteries capability and touchtone or rotary in excess of 17 amp hours. dialing. The communicator is alarm TM compatible with SIA and Ademco SUPERVISORY (Yellow) - On Flexput circuits on the Model 5820XL control can be individually Contact ID. The format is when a supervisory condition selectable by account number. exists. programmed to function as notifi- SYSTEM TROUBLE (Yellow) On cation circuits, auxiliary power User Interface when a trouble condition exists. outputs, or initiation circuits that The IntelliKnight's built-in support both 2- and 4-wire smoke annunciator with 80 character LCD SYSTEM SILENCED (Yellow) - On detectors. display and large easy-to-use when an alarm, trouble or supervisory condition has been The IntelliKnight system operates tactile touchpad can be used for silenced but not yet cleared. on non-twisted, unshielded cable system operation, programming when wired in compliance with and maintenance. It has five LEDs SYSTEM POWER (Green) On standard wiring practices as called for alarm, supervisory, system when power systems are out in the National Electric Code trouble, system silenced and normal;flashes for AC or DC 760 specifications for power-limited system power. System operations failure. fire protective signalling cables. No include silencing alarms and System Application special wiring is required. troubles, resetting alarms and the The IntelliKnight Model 5820XL The Model 5820XL provides seven display of alarm troubles and control panel has one built-in preset notification cadence patterns memory. The system's non-volatile Signalling Line Circuit (SLC)which including ANSI 3.41 and four user event history buffer stores 1000 supports 127 devices. Two programmable selections for fire , additional loops can be added alarm notification. using the 5815XL SLC expanders Two programmable general owes to increase overall capacity to 381 purpose Form C relay outputs are '' '"""'• i devices. provided on the Model 5820XL . - ••w The Model 5820XL's SLC loops FACP. - _ - A support multiple device types: Additionally, the IntelliKnight ` . . . 4 • ► ai • Addressable photoelectric smoke system features a built-in walk test ' al El • an i r detector and auto-programming. Its .-0` • Addressable ionization smoke innovative, dead-front cabinet 4 _ 4Nk» detector design allows for flush or surface • Addressable heat sensor mounting. System maintenance is events for viewing from the built-in • Addressable duct smoke easy to perform. or remote annunciator. System detector Built-In Digital Communicator operation can be initiated with a • Contact module The IntelliKnight Model 5820XL mechanical firefighter's key or a • Relay output module features a built-in UL listed digital valid 4 to 7-digit operator's code. • Addressable notification module communicator for remote reporting Programming The following advanced sensor of system activity and system The IntelliKnight system offers capabilities are available using the programming. The communicator several options to simplify and IntelliKnight Model 5820XL: has the ability to seize two speed up programming. The • Automatic drift compensation telephone lines to report alarms JumpStartTM feature minimizes • Maintenance alert and troubles to a monitoring facility. programming required to start a The communicator supervises two new system. The built-in keypad • Built-in sensor test to comply phone lines and will activate a and the 5860 Remote Annunciator with NFPA 72 calibration testing trouble signal if a line failure is give on-site access to all requirements sustained for more than 45 The IntelliKnight 5820XL features a programming. You can also 9 seconds. Other communication program remotely using the 5 amp power supply and maximum features include: retry if communi- TM battery charging capacity of 33 cation fails, two phone number Windows Download Software. INTELLIKNIGHT FIRE ALARM CONTROL PANEL WelkKnight Model 5820XL Addressable Fire Alarm Control Panel IntelliKnight 5820XL Addressable Fire Alarm System 4,4,1 ... v .., 1.1441," v ...... ', .4410 , , -aaaa i IL i a i IMO 4 1111** lh 1114.1 164:41 . - - 4 citl,. 4.. ,... 6 6 Flexput r Flex: - V 44 4 . E ••••' '.41"ti'1 •#1 ,71;41,'1 to V V ... -.... APS SI>5134,411.5.35E54512 5E1005 0.115 7.1:154f-51:N ow. 1 l I ,.r. W f.4”IAN iNINIONII $O181141111 1111111111411ill r-in 6 kqes,Um kw* k *ow kkokk ilti. .tr2141a7:2 I 4 I —1.— w-1-- I i 1 ' I 41M' .,.., 1 Ma SCLOO*Pa 0010641.014 1113406111111$ GINIMMIN Mario It, I .11tai Wt. ...Witt. al to...a twit Riii.111, kmin*kw as I Ilk ke,I, i il I II I '-. — 1 I ", 5-4 er IMPS ....... I 1.100,h.MID la carirri opal 4 I 54213 14.44.,trier14,54 lAktkabg. I — L J INTELLIKNIGHT FIRE ALARM CONTROL PANEL IntelliKnight System Accessories mount on a 4 inch square electrical 5860 Remote Fire box. Provides indicator LED to show Annunciator output status and comes with a coverplate. The 5860 features the `-t same 80 character ) Model SD500-AHM •n' ` � backlit LCD display Addressable Notification Module keypad and firefighter's providing a single Class A or Class B keyswitch as the 5820. The system can notification circuit on the SLC. be fully programmed and operated Model SD505-ADH from any remote annunciator. 1,1 Duct Housing. Detects smoke in HVAC 5815XL Signal Line Circuit Expander '_. ducts. The SLC expander is used to add more Model SD505-ADHR addressable devices to the IntelliKnight --..r.— Duct detector base with relay. Provides system. The 5820XL can support two form C alarm contact. For use with 5815XLs. Each 5815XL can support Compatible Devices SD505-APS and AIS sensors. 127 devices. IntelliKnight's devices feature a low Compatible with SD505-DTS remote 58993.Intelligent Power Module profile design and EEprom addressing. test switch. Adds 5 amps of power, 6 FlexputTM I/O EEprom addressing prevents water Model SD505-DTS circuits and 2 Form C relay circuits to intrusion problems via the back of the Remote test switch. Used with SD505- an IntelliKnight system. sensor and eliminates mechanical ADHR. Provides remote key operated 5880 LED/10 Module failures related to decade switches. test function and annunciation of Features 40 LED outputs, 8 normally Model SD505-APS detector alarm. open dry contact inputs and one piezo Addressable photoelectric smoke Model SD505-6SB output. detector. Six-inch sounder base. Operates in 5865-3 and 5865-4 Model SD505-AIS single and multi-station modes and/or Remote LED Annunciator Addressable ionization smoke detector. as a system sounder. Used with Features 30 Programmable LEDs (15 Model SD505-AHS existing sensor and base. Requires 2 red and 15 yellow) outputs and piezo additional wires for power. sounder. The 5865 4 adds a silence Addressable heat sensor. Model SD505-6AB Model SD505-61B and reset switch to the package. Six-inch isolator base. Used with 5883 Relay Board Six inch base designed for use with existing base and the SD505-APS, detector head models SD505-APS, AIS, and AHS sensors. Provides Features 10 General purpose Form C SD505-AIS and SD505-AHS. isolation for style 7 circuits. relays. Used with 5880 module. Model SD505-4AB Model SD505-6RB 5824 Serial/Parallel Gateway Four inch base designed for use with Six-inch relay base. Used with existing Module detector head models SD505-APS, sensor and base. Provides one Form C Has one parallel and one RS-232 serial SD505-AIS and SD505-AHS. contact. port for connecting any standard IBM- Model SD500-AIM Model SD500-SDM compatible printer to the IntelliKnight Dry Contact Input Module. Designed to Two-wire detector input module.Allows system. Interfaces with building control used with normallyopen drycontacts. system. P for the connection of conventional 2- Mounts in a 4 inch square electrical wire detectors on the SLC loop. SKSS Silent Knight Software Suite box. It features an indicator LED to Requires two additional wires for 5660 Up Down Load Software show alarm status and a coverplate. Model SD500-MIM power. User-friendly, WindowsTM software for Model SD500-LIM remote programming of the IntelliKnight Mini Dry Contact Input Module.A Loop Isolator Module. Provides panel using a PC. miniature version of the addressable isolation for style 7 circuits. 5670 Facility Management Software input module which is designed to be used with pull stations and other Model SD500-PS Powerful end-user software allows normally open dry contact inputs where Addressable Pull Station viewing of detector status and event a smaller size is desired. S-BUS Accessories history via modem or direct connection. Model SD500-ARM The following items listed are devices Addressable Relay Module. Features 2 that connected to the IntelliKnight's RS- Form C output relays, designed to 485 Bus ItSILENT ili KNIGHT MADE IN AMERICA FORM#350210, Rev.09/00 7550 Meridian Circle, Maple Grove, MN 55369-4927 800-446-6444 or in Minnesota 612-493-6435 Copyright©2000 Silent Knight FAX: 612-493-6475 IntelliKnight is a Registered Trademark of Silent Knight World Wide Web: http://www.silentknight.com Flexput is a Trademark of Silent Knight f 1' )f FIRE SYSTEM ACCESSORY . Firepower 5496 I s Distributed Power Module lib ir� ��' * A dynamic combination of power and intelligence .. . . r ., ntelli ence . �-;' for your notification expansion needs. uCil The Model 5496 Intelligent Power Module by Silent Knight is the most- ''` P. •powerful and cost-effective power supply available today. It delivers 6 amps of . ,F 1 j 0 notification appliance circuit power and built-in synchronization for appliances from Gentex®, Faraday,AMSECO and Wheelock®—what you need to drive power-hungry components like ADA notification appliances. The 5496's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. For the most sophisticated and cost-effective notification power supply available, you need Firepower 5496. Call Silent Knight today for more information at 1-800-446-6444. Model 5496 • 3 amps per output circuit tor Intelligent Power Module • Groundfaultto 9 Communicates the to the FACP via 4- The model 5496 is a 6 amp notification wire SBUS (wire runs up to 6000 ft) power expander that provides its own • AC loss delay option shuts off power AC power connection, battery charging to non-essential high-current _$ circuit, and backup battery for use with accessories like magnetic door fire and security controls such as the holders IntelliKnight Model 5808 Fire Control Lightweight design adds to ease of . /Communicator. The 5496 is the cost installation and reduces shipping ,E effective solution for powering pp g notification appliances required by the costs z -_ Americans with Disabilities Act (ADA). • UL 864 & 1481 listed The 5496 has built-in ANSI cadence • CSFM approved pattern, which can upgrade older • ANSI Cadence pattern output control panels that lack cadence capability built-in capability. The Output circuits can be Specifications programmed as Notification Appliance Ili K',`.(111 Circuits, or as Auxiliary Power AC Input 120 VAC at 2.7 A (configurable for, constant, resettable, Output: 24 VDC at 6 amps Model 5496 Intelligent or door holder power). Current: Power Module Features Standby 40 mA Battery charging • UL Listed for 6 amps of notification Alarm 160 mA capacity: 33.0 AH power Notification/Aux. Ambient Temp.: 32°to 120° F • Power supply's advanced switch Power circuits: 4 0°to 49°C mode design reduces damaging Output Dimensions: 12.25"W x 16"H x heat and manages power up to 50% configuration: 2 Class A(Style Z) 3" D(30.88 cm W more efficiently than other systems 4 Class B(Style Y) x 40.64 cm H x • Built-in synchronization for (1 Class A& 7.62 D cm) appliances from AMSECO, Gentex®, 2 Class B) Faraday, and Wheelock® Amps per Approvals: UL • 24 VDC filtered output voltage output circuit: 3.0(6.0 amps total) NFPA 72 • Four power-limited notification Notification outputs; 2 Class A or 4 Class B, or 1 circuit output: 20.4 to 27.3 VDC Class A and 2 Class B @ 3.0 amps each, • NACs are programmable as 4.s kS2 EOL resistor required SILENT Notification Appliance Circuits, or as on each Class B auxiliary power to be used as circuit ` KNIGHT constant, resettable, or door holder power FIRE SYSTEM ACCESSORY Firepower 5496 Distributed Power Module Engineering Specifications The contractor shall supply a power module compatible with the Silent Knight FACP. The power module must have 6.0 amps of output power. The power module shall connect to the main FACP via an RS 485 system bus (SBUS). The Outputs shall be programmable as Notification Appliance Circuits, or as Auxiliary Power (configurable for, constant, resettable, or door holder power). The power module shall have four separate outputs. The power module RS 485 bus shall be optically isolated providing ground loop isolation and transient protection. 4 outputs programmable as Notification Appliance Circuits, or as Auxiliary Power Output 1 .4SBUS Communication to a compatible Output 2 All Silent Knight FACP .411111111M111111111111111111111111111111111111111111111111111111111111111111111011011. Output 3 ", Output 4 44 Auxiliary power can be programmed to be, constant, resettable, or door holder power Compatible FACPs IntelliKnight 5808 IntelliKnight 5820XL itSILENT o KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763-493-6435 FORM#350387, Rev.04/02 FAX: 763-493-6475 World Wide Web: http://www.silentknight.com Copyright©2002 Silent Knight q.E INTELLIKNIGHT ACCESSORY 4fi Addressable Photoelectric Type Smoke Detector tf Detect smoldering fires quickly and get help fast - -. with IntelliKnight® photoelectric smoke detectors. , x t; IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505-APS photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds are wasted in determining location of an alarm. The SD505-APS compensates automatically for contamination in the environment.And detector testing is simple—even from a remote site. Like other IntelliKnight detector models, the SD505-APS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505-6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight smoke detectors—easy installation, stable operation, RF/transient protection, and vandal-resistant locking—and it adds up to a flexible solution for all your fire protection needs. Model SD505-APS The light received is converted into Analog/Addressable an electronic signal. Under normal conditions, the status LED blinks Photoelectric Type approximately every 15 seconds, 1 f) \ Smoke Detector indicating that the head is ® ,,► 1 communicating with the loop. The The SD505-APS is particularly LED lights continuously during the suited to detecting dense smoke alarm period. typical of fires involving materials such as soft furnishings, plastic, Features foam or other similar materials • Low profile, 2 inches, including SD505-APS Smoke Detector which tend to smolder and produce base Specifications large visible particles. • Simple and reliable addressing Operating Voltage: 17-41 VDC The detector features automatic without mechanical switches Current Consumption: compensation for contamination • Automatic compensation for and a simple detector calibration sensor contamination Alalarrmm .55 mA A : .55 mA test procedure that can be run from • Built-in fire test feature the panel or remotely (using the Ambient Temperature. 32°F to 100°F TM • Simple detector calibration (0°C to 50°C) WindowsTM based downloading testing through the control panel software). or remotely through a Mounting: 4"Square,4"OCT, Single gang mud operation WindowsTM based computer ring Software. Relative Humidity. 85% The SD505-APS units made up of an LED light source and a silicon • Vandal-resistance locking noncondensing photo diode receiving element. In a features Air Velocity: 0-300 FPM normal standbycondition, the • Field cleanable Compatible Bases: SD505-6AB receiving element receives no light UL listed, meets NFPA 72 Ch 7 (Sold Separately) (6"Base) from the pulsing light source. In the requirements SD505-4AB event or fire, smoke enters the • CSFM approved (4"Base) detector and light is reflected from • MEA approved the smoke particles to the receiving • FM Approved SILENT element. 44 KNIGHT INTELLIKNIGHT ACCESSORY Model SD505-APS Addressable Photoelectric Type Smoke nistly Detector Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector Silent Knight SD505-APS. The combination detector head, and twist-lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with Silent Knight SD505-AIS Ionization Smoke Detector, or SD505- AHS Heat Detector. Base shall be the appropriate twist-lock base SD505-6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SD505-APS shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. Diameter=5-15/16" Diameter=3-15/16" ,I O ale ea c-) \ 0 Height=2 inches, \ including base / f SILENT O KNIGHT Model SD505-6AB Detector Base Model SD505-APS Detector Head (front view) (front view) itSILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763-493-6435 FORM#350225, Rev. 12/01 FAX: 763-493-6475 World Wide Web: http://www.silentknight.com Copyright©2001 Silent Knight INTELLIKNIGHT ACCESSORY Model SD500-AIM Addressable Input Module And Yp Model SD500-MIM Miniature Input ModuleUP" IntelliKnight's addressable contact monitor modules combine fast response with pin-point location ID. A combination that saves lives and property. The SD500-AIM and SD500-MIM are addressable input modules for use with Silent Knight's IntelliKnight fire control panel. The SD500-AIM and SD500-MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. The SD500-AIM addressable input module mounts to a 4"-square box. The SD500-MIM mini input module fits inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister, they monitor for alarm contact closures and for open circuit wiring fault conditions. The SD500-AIM and SD500-MIM offer a compact design for adaptability and pleasing aesthetics as well as easy installation and stable operation—a flexible solution for all your fire protection needs. Model SD500-AIM and SD500-MIM Input Modules The addressable input modules expand the flexibility of the IntelliKnight system by allowing the use of contact type inputs. Typical - applications include manual pull ®i stations and water flow switches. ��_ Features • Operates on Class A(Style 6 & Style 7)or Class B (Style 4)SLC Loop. • Single contact monitor. SD500-AIM SD500-MIM • Up to 127 modules per SLC loop. .�r,.�; • SD500-MIM mounts in a single gang Ope'at■on Specifications box. Each addressable input module is Operating Voltage: 24 VDC • SD500-AIM mounts in a programmed with a unique SLC Standby Current: 0.55 mA 4"-square or double gang electrical loop address. The module box, and has an attractive ivory supervises the wiring to the contact Alarm Current: 0.55 mA cover plate. with an End Of Line (EOL) resistor. Ambient Temperature: 32°F to 120°F • SD500-AIM/MIM are DIP switch If a fault occurs in the wiring, the (0°C to 49°C) programmable. module alerts the FACP. Mounting SD500-AIM • Accepts up to 14 gauge wire. double gang box or • Both modules UL 864 listed; comply 4"-square electrical with NFPA 72 box • 2500 ft max. wiring distance from SD500-MIM input module to contact. single gang box • CSFM listed. • MEA 429-92-E, Vol. 9 SILENT • FM approved tvp KNIGHT INTELLIKNIGHT ACCESSORY Model SD500-AIM and SD500-MIM Addressable Input and Mini Input Modules I Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight SD500-AIM or SD500-MIM. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight FACPs. The SD500-MIM shall fit inside a single gang electrical box. The SD500-AIM shall be supplied with a plastic cover and shall be suitable for mounting to a 4"-square or double gang electrical box. The SD500-AIM addressable input module must provide a monitor LED that is visible from outside the cover plate. Model S0500-AIM FRONT VIEW BACK VIEW SIDE VIEW C®OO ICI I,eG am ♦ 4719" 1!4' M---i� Model SD500-MIM 2-112" 1ill + � • � 11/16MEM " 4 1 SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763-493-6435 FORM#350231, Rev. 11/01 FAX: 763-493-6475 World Wide Web: http://www.silentknight.com Copyright©2001 Silent Knight ,0 , GENTEX CORPORATION Commander4 Series Selectable GCS/GCC Candela Evacuation Signals 24VDC Applications SERIES The GCS/GCC Series is a ceiling mount strobe or horn/strobe combination that offers dependable audible and visual alarms and the lowest current consumption. The GCS/GCC offers tamperproof field selectable candela options of 15, 30, 75, 95, 115 and 150 candela. The GCC horn offers a continuous or synchable temporal three in 2400Hz and mechanical tone. All tones are easy for the professional to change in the field • , by using switches. The models are shipped from the factory in the temporal "C‘_ three alarm mode. a -- w The GC Series has a very minimal operating current and has a minimum flashk; „ / rate of 1 Hz regardless of input voltage. ' 11' The Commander4 Series comes standard with the 4” mounting plate which incorporates the popular Super-Slide®feature that allows the installer to easily test for supervision. The product also features a locking mechanism which secures the product to the bracket without any screws showing. The Commander4 also features the patented Checkmate®- Instant Voltage Product Listings Verification feature which allows the installer to check the voltage drop draw SIGNALING (ISM:_ without removing the signal. The GC Series appliances are ANSI/UL 464 and ANSI/UL 1971 listed for use APPROVED with fire protective systems and are warranted for three years from the date of LISTED 1 purchase. •ANSI/UL 464 and ANSI/UL 1971 Listed •FM Approved •CSFM: 7135-0569:122(GCC) Standard Features 7125-0569:123(GCS) • Nominal voltage 24VDC •MEA: 285-91-E • Tamperproof field selectable candela options of 15, 30, 75, 95,115 & 150 Patents • Super-Slide®Bracket- Ease of Supervision Testing •7,375,617 May 20,2008 • Checkmate®- Instant Voltage Verification • Unit Dimensions:6"(15.24 cm) x 2.6"(6.604 cm) Product Compliance • Synchronize strobe and/or horn with Gentex AVSM Control Module • 72 •Ammerieri cans with Disabilities Act(ADA) • Prewire entire system, install mounting bracket, then install signals •IBC/IFC/IRC • Documented lower installation and operating costs •City&State ordinances/Laws/Regulations • Input Terminals 12 to 18 AWG •Quality Management System is certified to: ISO 9001:2008 • Switch Selection for High or Low dBA • Switch Selection for 2400Hz or Mechanical Tone • Switch Selection for Continuous or Temporal 3 MEMBER • Tamperproof re-entrant grill ASSEMBLED IN • Surface mount with the GCSB (Gentex Ceiling Surface Mount Box) THE USA • Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions) • Faceplate available in red or off-white GCS Series 24 Volt Ceiling Mount Selectable Strobe Model Part Nominal Candela Number Number Voltage GCS24CR 904-1213-002 24VDC 15, 30,75,95, 115, 150 GCS24CW 904-1215-002 24VDC 15, 30,75, 95, 115, 150 GCS24PCR 904-1214-002 24VDC 15, 30, 75, 95, 115, 150 GCS24PCW 904-1216-002 24VDC 15, 30,75,95, 115, 150 GCC Series 24 Volt Ceiling Mount Selectable Horn/Strobe Model Part Nominal Candela Reverberant dBA® In Anechoic Room Number Number Voltage 10ft.per ANSI/UL 464 dBA @ 10ft. GCC24CR 904-1209-002 24VDC 15,30, 75, 95, 115, 150 81-86 90 GCC24PCR 904-1210-002 24VDC 15, 30, 75,95, 115, 150 81-86 90 GCC24CW 904-1211-002 24VDC 15, 30,75, 95, 115, 150 81-86 90 GCC24PCW 904-1212-002 24VDC 15,30, 75, 95, 115, 150 81-86 90 Model Designations: C=Ceiling Mount R=Red Faceplate W=White Faceplate All units are available in plain (no lettering). Plain units are non-returnable. GC24 Product Strobe Current Ratings (mA) Candela 15cd 30cd 75cd 95cd 115cd 150cd 24VDC 72mA 101 mA 167mA 200mA 214mA 286mA 24VDC(16-33 Volts) UL Max1 120mA 120mA 200mA 220mA 290mA 321 mA GCC24 Product Horn Decibel and Current Ratings (mA) Minimum dBA @ 10ft. Minimum dBA @ 10ft. Regulated 24VDC Horn Mode per ANSI/UL 464 per ANSI/UL 464 Max.Operating (HIGH) (LOW) CO High Setting(mA) Temp 3 2400Hz 83 75 23 Temp 3 Mechanical 81 73* 22 Continuous 2400Hz 86 78 23 Continuous Mechanical 84 76 22 NOTES: • Operating temperature:32°to 120°F(0°to 49°C). The GC Series is not listed for outdoor use. • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. • For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see installation manual. • Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe products(see Technical Bulletin Number 014). • Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units). For strobes the UL max current is usually at the minimum listed voltage(16VDC for 24VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings,see installation manual. Mounting Super-Slide® 3.SNAP COVER OVER ASSEMBLY A �r 2.INSERT LOCKING SCREW 1' et ISIIIIII-- - ---- 11111 ��a�oa�sc_>/ l'7 4711111111111111111117 i • �I 1111' ���; SII► / \ 1 ........,,r,....,, ,,„,fek-W ,;_ • . titql 11 �� �f �;�r;=-� =a„4, 1.SLIDE ONTO BRACKET Checkmate® Instant Voltage Verification Switch Locations 7;a /-�) DO NOT Nr ^1 k 12345, 1 ^_ , � f O U DIE- YNui ea Si O Si ii > O Fl s- Ic on — O g ® b¢ IIF' 0 � � c w7EY ,06 I" ®EWITI 5 -. . _ The access holes are provided in the back of the terminal block 0 to allow the voltage to be measured directly without removing the Switch positions 1 and 2 in the down position to select device.Typically this would be done at the end of the line to isolated horn and strobe power inputs. Switch 3 selects confirm design criteria.Most measurements will be taken using between temporal or non-temporal tone. Up is temporal. the S+and S-locations although access is provided to other Switch 4 selects between mechanical or high frequency locations. NOTICE:CARE SHOULD BE TAKEN TO NOT tone. Up is mechanical. Switch 5 selects between high SHORT THE TEST PROBES. or low dBA. Up is high dBA. • GCS/GCC 24VDC SERIES Conventional GC Series Wiring Diagrams UL Listed UL Listed Control ControlSignal Signal Panel Signal Signal 5+ 5+ S- H+ H- S+ S+ S- H+ H- Panel S+ S+ S- H+ H- S+ S+ S- H+ H- Supervised O Oy S e Mira Supervised S q S e S . . a e S Signal Circuit M1111111111111 Signal Circuit " \ o I"' I"' ERESISTORE O / END OF LINE 0 " RESISTOR o \ O END OF LINE 7 \ � RESISTOR O NOTES: • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. See Technical Bulletin 014 for additional information. • FOR SYNCHRONIZATION WIRING INFORMATION,REFERENCE AVSM CONTROL MODULE DATA SHEET(551-0031) AND/OR AVSM CONTROL MODULE MANUAL(550-0284)FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.gentex.com OR CALL GENTEX CORPORATION AT 1-800-436-8391. Architect & Engineering Specifications The visible and audible/visible signal shall be Gentex model GCS or GCC or approved equal and shall be listed by Underwriters Laboratories Inc.per ANSI/UL 1971 for the GCS and ANSI/UL 464 for the GCC.The notification appliance shall also be listed with the California State Fire Marshal (CSFM)and the Bureau of Standards and Appeals (NYC). The notification appliance (combination audible/visible units and audible units only)shall produce a peak sound output of 90dBA or greater as measured at 24VDC in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The appliance shall have an operating current of 72mA or less at 24VDC for the 15 candela strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. 24 units per carton 29 pounds per carton Important Notice: 551-0051-06 GENTEX These materials have been prepared by Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties,express or implied,that these materials are complete and CORPORATION accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regulations and rules. The materials do not address all legal considerations as there is inevitable uncertainty regarding Fire Protection Products Grou •www. entex.com interprelationoflaws,regulalionsandrulesandtheapplicationofsuchlaws,regulationsandrulesto p g particular fact patlerns.Each person's activities can differently affect the obligations that exist under 10985 Chicago Drive •Zeeland, Michigan 49464 apppoebsle ans,hroegonse ounaThsebsote hfeeseagnap hodnabelegeldodvliycefmwlna t be 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax responsible for any action or failure to act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. • GENTEX CORPORATION Commander3 Series Selectable GEC3/GES3 Candela Evacuation Signals 12 & 24 VDC Applications The Commander3 Series is a low profile strobe and horn/strobe combination SERIES that offers dependable audible and visual alarms and the absolute lowest current available. The GE3 Series 24VDC offers tamperproof field selectable candela options of ,, 15, 30, 60, 75, and 110 candela. The 12VDC offers tamperproof field selectable candela options of 15, 30, 60, and 75 candela. The Commander3 Series horn offers a continuous or synchable temporal three in 2400Hz and mechanical tone, a chime and whoop tone. All tones are easy �� for the professional to change in the field by the use of switches. The GE3 Series has a minimal operating current and has a minimum flash rate of 1 Hz regardless of input voltage. Product Listings The Commander3 Series is shipped with a standard 4" metal mounting plate SIGNALING which incorporates the popular Super-Slide®feature that allows the installer to easily test for supervision.The product also features a locking mechanism 42, which secures the product to the bracket without any screws showing. =- LISTED 1'R" 1 The Commander3 also features the patented Checkmate®- Instant Voltage Verification feature which allows the installer to check the voltage drop draw • ANSI/UL 464&ANSI/UL 1971 Listed and match it to the blueprint. • CSFM: 7135-0569:122(GEC3-24& The GE3 Series appliances are ANSI/UL 464 and ANSI/UL 1971, listed for use GEH-24) with fire protective systems and are warranted for three years from date of 7125-0569:123(GES3-24) purchase. 7125-0569:129(GES3-12) 7135-0569:130(GEC3-12& Standard Features GEH-12) • Nominal voltage 12VDC and 24VDC • MEA: 285-91-E(GEC3-24&GES3 24) • 24VDC units have field selectable candela options of 15, 30, 60, 75 & 110 580-06-E(GEC3-12&GES312) • 12VDC units have field selectable candela options of 15, 30, 60&75 Patents • GEH horn is available in 12VDC or 24VDC • 7,375,617 May 20,2008 • Unit Dimensions:5"(12.7 cm) high x 4.5"(11.43 cm) wide x 2.5"(6.35 cm) deep Product Compliance • Super-Slide®Bracket- Ease of Supervision Testing • NFPA 72 • Checkmate®- Instant Voltage Verification • Americans with Disabilities Act(ADA) • Synchronize strobe and/or horn with Gentex AVSM Control Module • IBC/IFC/IRC • Prewire entire system, install mounting bracket, then install signals • Quality Management System is certified • Documented lower installation and operating costs to:ISO 9001:2008 • Input terminals accept 12 to 18 AWG • Switch selection for high or low dBA • Switch for chime, whoop, mechanical and 2400Hz tone NEM MEMBER • Tamperproof re-entrant style grill • Switch for continuous or temporal 3 tone (not available on whoop tone) ASSEMBLED IN • Surface mount with the GSB (Gentex Surface Mount Box) THE USA • Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions) • Faceplate available in red or off-white GEH 12VDC or 24VDC Low Profile Evacuation Horn Model Number Part Number Nominal Voltage Reverberant dBA at In Anechoic Room 10ft.,per ANSI/UL 464 dBA at 10ft. GEH12-R 904-1239-002 12VDC 62-82 100 GEH12-W 904-1241-002 12VDC 62-82 100 GEH24-R 904-1205-002 24VDC 62-82 100 GEH24-W 904-1207-002 24VDC 62-82 100 GES3 12VDC or 24VDC Selectable Candela, Low Profile Evacuation Strobe Model Number Part Number Nominal Voltage Candela (ANSI/UL 1971) GES3-12WR 904-1235-002 12 VDC 15, 30, 60, 75 GES3-12WW 904-1237-002 12 VDC 15, 30, 60,75 GES3-24WR 904-1321-002 24 VDC 15,30, 60, 75, 110 GES3-24WW 904-1319-002 24 VDC 15, 30,60,75, 110 GEC3 12VDC or 24VDC Selectable Candela, Low Profile Evacuation Horn/Strobe Model Number Part Number Nominal Voltage Candela Reverberant dBA at In Anechoic Room (ANSI/UL 1971) 10ft.,per ANSI/UL 464 dBA at 10ft. GEC3-12WR 904-1231-002 12 VDC 15,30, 60,75 62-82 100 GEC3-12WW 904-1233-002 12 VDC 15,30, 60, 75 62-82 100 GEC3-24WR 904-1317-002 24 VDC 15, 30,60, 75, 110 62-82 100 GEC3-24WW 904-1315-002 24 VDC 15,30, 60,75, 110 62-82 100 GE3 Product Strobe Current Ratings (mA) Model Designations: 12 VDC(8-17.5 Volts) 24 VDC(16-33 Volts) W =Wall mount Candela 12VDC UL Max1 24VDC UL Max' R = Red Faceplate W =White Faceplate 15cd 106mA 92mA 30mA 42mA • All units are available in plain (no lettering). 30cd 131 mA 141 mA 35mA 58mA Plain units are non-returnable. 60cd 186mA 260mA 66mA 97mA 75cd 237mA 312mA 80mA 116mA ALERT bezel available for order AGENT bezel available for order 110cd 103mA 161 mA GE3-12 Product Horn Current Ratings GE3-24 Product Horn Current Ratings Horn Decibel Levels Horn Current Ratings Horn Decibel Levels Horn Current Ratings Minimum SPL Minimum SPL Regulated 12VDC Minimum SPL Minimum SPL Regulated 24VDC Horn Mode at 10ft,per at 10ft.,per Max.Operating @ Horn Mode at 10R.,per at 10ft.,per Max.Operating ANSWL 464 ANSWL 464 High Setting(mA) ANSWL 464 ANSI/UL 464 High Setting(mA) (HIGH) (LOW) (HIGH) (LOW) Temp 3 2400Hz 76 dBA 69*dBA 29mA Temp 3 2400Hz 78 dBA 71*dBA 28mA Temp 3 Mechanical 75 dBA 68*dBA 26mA Temp 3 Mechanical 76 dBA 70*dBA 25mA Temp 3 Chime 62"dBA 60*dBA 13mA Temp 3 Chime 70*dBA 66*dBA 15mA Continuous 2400Hz 79 dBA 74*dBA 29mA Continuous 2400Hz 81 dBA 74*dBA 28mA Continuous Mechanical 78 dBA 72*dBA 26mA Continuous Mechanical 80 dBA 72*dBA 25mA Continuous Chime 63*dBA 61*dBA 13mA Continuous Chime 70*dBA 66*dBA 15mA Whoop 78 dBA 71*dBA 55mA Whoop 82 dBA 69*dBA 56mA NOTES: • Operating temperature:32°to 120°F(0°to 49°C). The GEC3 and GES3 Series is not listed for outdoor use. • For nominal and peak current across ANSI/UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see installation manual. 12VDC models are DC only. • Gentex does not recommend using a coded or pulsing signaling circuit with any of our strobe products(see Technical Bulletin Number 014). • The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. • Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). 1 RMS current ratings are per ANSI/UL average RMS method. ANSI/UL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units)(8-17VDC for 12VDC units). For strobes the UL max current is usually at the minimum listed voltage(16VDC for 24VDC units)(8VDC for 12VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings,see installation manual. 1 Tone Switch Locations TONE SWITCH POSITION 3 4 5 r. Mechanical Temporal 3 ON ON ON [_■ ..0]=1 Mechanical-Continuous OFF ON ON 1=EN■ ■. —= 2400Hz-Temporal 3 ON OFF ON — 2400Hz-Continuous OFF OFF ON 1=E03. •E ---= Chime Temporal 3 ON ON OFF 1=I-1'• — 1�► Chime-Continuous OFF ON OFF �� —� Whoop ON OFF OFF [01■ ■■ s+ ODP Whoop OFF OFF OFF 1=EcD. M. SI- 11 NOTE: ® j S. 1gif • Switch Positions 1 and 2 in the OFF position to II+ lie rl select isolated horn and strobe power inputs IW -___ • Switch Position 6 ON =HIGH dBA �Il�� • Switch Position 6 OFF=LOW dBA Gentex Super-Slide® ir1 Checkmate® Instant Mounting Bracket , Voltage Verification Allows the installer to pre-wire It is often necessary to confirm the the system, test for system voltage drop along a line of devices.The supervision, remove the signal J� access holes are provided in the back of head until occupancy, switch ft the terminal block to allow the voltage to out Gentex signals without be measured directly without removing the changing mounting bracketsdevice.Typically this would be done at the ii, and has locking edge connector (�I11111 4,- end of the line to confirm design criteria. for snap-in-place installation. Most measurements will be taken using , the S+ and S- locations although access `.` , is provided to other locations. "-_'AI I NOTE:Care should be taken to not short ig' the test probes. / , Candela selection slider _ �- switch. Depress center //;- =.. =- __^=v ;{ and slide switch to desire - ".. - it `f �I_-,, - _= ,0titi 1, r brightness level. --__i_ c,,,,,-r=�`""t 1 f SII Is �1 I ii 4 1 � l 411 .1Ir } y tt� 41 c I ill :V _: { l 111 i n i Break off pin and insert �,�l �N lye v II into hole at the bottom of ri 30 `' I -' ' f "� `so i I E 11 ll the selector to lock ��5 1 111 j' ji 110 MODEL 1 s I. ° ,1 -i candela setting. Signal SELF°TION I 1 i i ' �� } i; 4'•. it I� MAf1KEN i --�} l F must be removed from �'-' I i Ill 1 II ; ,. `I tf f r_ I. ',,gio i i 1 I it III -L1 f11 O ft 111 bracket and pin pushed - - 1 L., 1 I ) /' 1_ r_ forward from backside out _ f of hole to change ip1 candela. ^: :;. �' To remove bezel, grip both sides of bezel and pull in a downward and outward motion. GEC3/GES3 12 & 24VDC SERIES Conventional Wiring Diagrams for Emergency Notification Evacuation Series UL Listed UL Listed Control Signal Signal Control Panel Signal Signal s+ s+ S- H+ H- s+ s+ S- H+ H- Panel S+ S+ S- H+ H- S+ S+ S- H+ H- Supervised 0 y r��i :. ,►�. .►�r Supervised S S S S ® ► 0 S Signal Circuit „I„' Signal Circuit o 1111 11111 ENDORLINE ORESISTOR \ + 11 11 END OF LINE mai \ o RESISTOR O END OF LINE RESISTOR O NOTES: • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. See Technical Bulletin 014 for additional information. • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET(551-0031) AND/OR AVSM CONTROL MODULE MANUAL(550-0284) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.gentex.com OR CALL GENTEX CORPORATION AT 1-800-436-8391. • When synchronizing the GE3 12VDC Series,the Gentex AVSM control module or Gentex synchronization protocol MUST be used. Architect & Engineering Specifications The audible and/or visible signal shall be Gentex GEH, GES3, GEC3 Series or approved equal and shall be listed by Underwriters Laboratories, Inc.per ANSI/UL 1971 and/or ANSI/UL 464.The notification appliance shall also be listed with Factory Mutual Listing Service(FM)and the California State Fire Marshal (CSFM). The notification appliance(combination audible/visible)shall produce a peak sound output of 100dBA or greater at 12VDC or 24VDC as measured in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. Unit shall be capable of being installed so that any unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The strobe appliance shall have an operating current of 42mA or less at 24VDC for the 15Cd strobe circuit and 92mA or less at 12VDC for the 15Cd strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals and barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current or full wave rectified power for 24VDC models or a voltage range of 8-17.5 volts for 12VDC models. The appliance shall be capable of testing supervision without disconnecting wires,verify voltage without removing unit and be capable of mounting to a surface back box. 24 units per carton 28 pounds per carton Important Notice. 551-0050-06 GENTEX These materials have been prepared by Gentex Corporation("Gentex")for informational purposes only,are necessarily summary,and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties,express or implied,that these materials are complete and CORPORATION accurate,up-to-date,or in compliance with at relevant local,state and federal laws,regulations and rules. The materials do not address at legal considerations as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and the application of such laws,regulations and rules to Fire Protection Products Group•www.gentex.com particular fact patterns.Each person's activities can differently affect the obligations that exist under applicable laws,regulations or rules.Therefore,these materials should be used only for informational 10985 Chicago Drive •Zeeland, Michigan 49464 purposes and should not be used as a substitute for seeking professional legal advice.Gentex will not be responsible for any action or failure to act in ref anee upon the information contained in this material. 616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax Gentex Corporation reserves the right to make changes to the product data sheet at their discretion. _ . GENTEX CORPORATION Commander2 Series Low GEC/GES/GEH Frequency Evacuation Signals 24 VDC Applications SERIES The Commander2 Series is a low profile strobe, horn or horn/strobe combination that offers dependable audible and audible/visual alarms and the absolute lowest current available. The GE Series is available in fixed candela options of 15/75 and 177. . ii t`ANL W i The Commander2 Series horn offers a continuous or synchable temporal three in 2400Hz and mechanical tone, a chime and whoop R 111111111 tone. All tones are easy for the professional to change in the field by using switches. The GE Series has a minimal operation current and has a minimum flash rate of 1 Hz regardless of input voltage. Product Listings The Commander2 Series is shipped with the standard 4" mounting SIGNALING - =- plate which incorporates the popular Super-Slide®feature that T.,- allows ,-allows the installer to easily test for supervision.The product alsoCO) °` features a locking mechanism which secures the product to the "F ,` bracket without any screws showing. LISTED 1 F 1 The Commander2 Series also features the patented Checkmate°- • ANSI/UL 464,ANSI/UL 1971 and/or ANSI/UL 1638 Listed Instant Voltage Verification feature which allows the installer to • CSFM: 7135-0569:122 (GEH-24&GEC-24) check the voltage drop draw and match it to the blueprint. 7125-0569:123 (GES 24) 7135-0569:130 (GEH-12) The GE Series appliances are ANSI/UL 464,ANSI/UL 1971 and/or • MEA: 285-91-E-XV ANSI/UL 1638 listed for use with fire protective systems and are patents warranted for three years from date of purchase. . 7375,617 May 20,2008 Standard Features Product Compliance • Nominal voltage 24VDC • NFPA 72 • Fixed candela options of 15/75 and 177 • Americans with Disabilities Act(ADA) • GEH horn is available in 12VDC or 24VDC • IBC/IFC/IRC • Super-Slide®Bracket-ease of supervision testing • City&State Ordinances/Laws/Regulations • Checkmate°- instant voltage verification • Quality Management System is certified • Unit Dimensions: 5"(12.7 cm) high x 4.5"(11.43 cm)wide x to:ISO 9001:2008 2.5"(6.35 cm) deep • Synchronize strobe and/or horn with Gentex AVSM Control Module NEM • Prewire entire system, install mounting bracket, then install signals MEMBER • Documented lower installation and operating costs ASSEMBLED IN • Input terminals 12 to 18 AWG THE USA • Switch selection for high or low dBA • Switch for chime,whoop, mechanical and 2400Hz tone • Switch for continuous or temporal 3 (not available on whoop tone) • Tamperproof re-entrant grill • Surface mount with the GSB (Gentex Surface Mount Box) • Silence horn while strobes remain flashing • Faceplate available in red or off-white GEH 12VDC and 24VDC Low Profile Evacuation Horn Model Part Nominal Reverberant dBA 0 In Anechoic Room Number Number Voltage 10ft.,per ANSI/UL 464 dBA 0 10ft. • GEH12-R 904-1239-002 12 VDC 70-82 100 GEH12-W 904-1241-002 12 VDC 70-82 100 GEH24-R 904-1205-002 24 VDC 70-82 100 • GEH24-W 904-1207-002 24 VDC 70-82 100 GES 24 VDC Low Profile Evacuation Strobe Model Part Nominal Strobe Model Designations: Number Number Voltage Candela W=Wall mount GES24-177WR 904-1183-002 24 VDC 177 R= Red Faceplate W=White Faceplate GES24-177WW 904-1203-002 24 VDC 177 All units are available in plain (no lettering). GES24-15/75WR 904-1167-002 24 VDC 15(ANSI/UL 1971)/ Plain units are non-returnable. 75(ANSI/UL 1638) ALERT bezel available AGENT bezel available GES24-15/75WW 904-1187-002 24 VDC 15(ANSI/UL 1971)/ 75(ANSI/UL 1638) GEC 24VDC Fixed Candela, Low Profile Evacuation Horn/Strobe Model Part Nominal Strobe Reverberant dBA 0 In Anechoic Room Number Number Voltage Candela 10ft.,per ANSVUL 464 dBA 0 10ft. GEC24-177WR 904-1143-002 24 VDC 177 70-82 100 GEC24-177WW 904-1163-002 24 VDC 177 70-82 100 GEC24-15/75WR 904-1127-002 24 VDC 15(ANSI/UL 1971)/ 70-82 100 75 (ANSI/UL1638) GEC24-15/75WW 904-1147-002 24 VDC 15 (ANSI/UL 1971)/ 70-82 100 75 (ANSI/UL 1638) GE-24 Product Strobe Current Ratings (mA) 24VDC(16-33 Volts) Candela 24VDC UL Maxi 15/75cd 63mA 67mA 177cd 96mA 213mA GEH-12 Product Horn Decibel and Current Ratings GE-24 Product Horn Decibel and Current Ratings Minimum dBA Minimum dBA Regulated 12VDC Minimum dBA Minimum dBA Regulated 24VDC Horn Mode 10ft.Per 10ft.per Max.Operating 0 Horn Mode 10ft.per 10ft.per Max.Operating 0 ANSI/UL 464 ANSI/UL 464 ANSI/UL 464 ANSI/UL 464 (HIGH) (LOW) High Setting(mA) (HIGH) (LOW) High Setting(mA) Temp 3 2400Hz 76 69* 29 Temp 3 2400Hz 78 71" 28 Temp 3 Mechanical 75 68* 26 Temp 3 Mechanical 76 70* 25 Temp 3 Chime 62* 60* 13 Temp 3 Chime 70* 66* 15 Continuous 2400Hz 79 74* 29 Continuous 2400Hz 81 74* 28 Continuous Mechanical 78 72* 26 Continuous Mechanical 80 72* 25 Continuous Chime 63* 61* 13 Continuous Chime 70* 66* 15 Whoop 78 71* 55 Whoop 82 69* 56 NOTES: • Operating temperature:32°to 120°F(0°to 49°C). The GE Series is not listed for outdoor use. The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode. • For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered(FWR[Full Wave Rectified])power,see installation manual. 12VDC models are DC only. * Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone.The chime tone is always private mode). RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range(16-33VDC for 24VDC units)(8-17VDC for 12VDC units). For strobes the UL max current is usually at the minimum listed voltage(16VDC for 24VDC units)(8VDC for 12VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings,see installation manual. Tone Switch Locations TONE SWITCH POSITION 3 4 5 i=[_ .�• BuO Mechanical Temporal 3 ON ON ON z Mechanical-Continuous OFF ON ON [NM ME I 2400Hz-Temporal 3 ON OFF ON w■ ■. _ 2400Hz-Continuous OFF OFF ON Chime-Temporal 3 ON ON OFF -U •E lb Chime-Continuous OFF ON OFF CD'■ ■N Whoop ON OFF OFF Whoop OFF OFF OFF c6'U III lb NOTE: ® I • Switch Positions 1 and 2 in the OFF position to J, select isolated horn and strobe power inputs SIF • Switch Position 6 ON=HIGH dBA S+ • Switch Position 6 OFF=LOW dBA S+ Si H+ 31 B` 0IE.. /figs ' ' ''•' . el Gentex Super-Slide® Gentex Checkmate® Instant Mounting Bracket 'or Voltage Verification . Allows the installer to pre-wire rri It is often necessary to confirm the the system, test for system voltage drop along a line of devices.The supervision, remove the signal ,r. access holes are provided in the back of head until occupancy, switch 1fllffl 1111k 1 the terminal block to allow the voltage to be measured directlywithout removing out Gentex signals without 9 thedevice.Typicallythis would be done dece changing mounting brackets .,. 1 i e; - at the end of the line to confirm design and has locking edge connector for snap-in-place "`` •1 m AP criteria. Most measurements will be installation. �"j.' is taken using the S+ and S- locations / although access is provided to other locations. NOTE:Care should be taken to not __- ` short the test probes. 141 fr*i 0101.111 : VI 1/ To remove bezel, grip both sides of bezel and pull in a Il f f downward and outward motion. i I I ! �f elp II impli..:..;.%-•---; „_,..i. / . i„1G f „,r GEC/GES/GEHs 24 VDC _ SERIES r Conventional GES/GEC Series Wiring Diagrams UL Listed UL Listed Control ControlSignal Signal Panel Signal Signal Panel S+ S+ 5- H+ H- S+ S+ S- H+ H- S+ S+ S- H+ H- S+ S+ S- H+ H- Supervised a” Z ► O ► ► ► i Supervised S S S SI ► 0 a 0 S Signal CircuitEl yrr r y 1 Signal Circuit O ' "I", 9 O J „ \ 111111ERES STORE \ / END OF UNE 0 „ RESISTOR MI O / \ O ENO IS LIRE iiiRESISTOR O NOTES: • All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn. See Technical Bulletin 014 for additional information. • FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET(551-0031) AND/OR AVSM CONTROL MODULE MANUAL(550-0284)FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.gentex.com OR CALL GENTEX CORPORATION AT 1-800-436-8391. • When synchronizing the GEH 12VDC Series,the Gentex AVSM control module or Gentex synchronization protocol MUST be used. Architect & Engineering Specifications The audible and/or visible signal shall be Gentex GE Series or approved equal and shall be listed by Underwriters Laboratories Inc. per ANSI/UL 1971,ANSI/UL 1638 and/or ANSI/UL 464.The notification appliance shall also be listed with the California State Fire Marshal (CSFM) and the Bureau of Standards and Appeals (NYC). The notification appliance (combination audible/visible and audible units only) shall produce a peak sound output of 100dBA or greater at 12VDC or 24VDC as measured in an anechoic chamber.The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of power wires.Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The audible/visible and visible signaling appliance shall also maintain a minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage.The appliance shall also be capable of meeting the candela requirements of the ADA (75Cd)for the combination listed (UL 1971/UL 1638) listed models.The appliance shall have an operating current of 67mA or less at 24 VDC for the 15/75Cd for the strobe circuit. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit shall be provided with a mounting bracket with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate.The unit shall have an input voltage range of 16-33 volts with either direct current of full wave rectified power. The appliance shall be capable of test supervision without disconnecting wires, verify voltage without removing unit and be capable of mounting to a surface back box. 24 units per carton 27 pounds per carton .- . ,.:'_.. . .. "-- 5 H.�r . sS .,: -,— ,.',Rs,,..''''' Important Nohce 551-0049-02 GENTEX These materials have been prepared by Gentex Corporation('Gentex'')for informational purposes only, are necessarily summary,and are not purported to serve as legal advice and should not be used as such.Gentex makes no representations and warranties,express or implied,that these materials are CORPORATION complete and accurate,up-to-date,or in compliance with all relevant local,state and federal laws,regu- lations and rules.The materials do not address all legal considerations as there is inevitable uncertainty Fire Protection Products Group•www.gentex.com les and the application of such laws, + regulations and rules to particular fact patterns.Each person's activities can differently affect the 10985 Chicago Drive •Zeeland, Michigan 49464 obligations that exist under applicable laws,regulations or rules.Therefore,these materials should be used only for informational purposes and should not be used as a substitute for seeking professional 616.392.7195 • 1.800.436.8391 •616.392.4219 Fax legal advice.Gentex will not be responsible for any action or failure to actin reliance upon the information contained in this material. Gentex Corporation reserves the right to make changes to the product data sheet at their discretion.