Loading...
Plans JULRECEiVEr 1 3 2016 „ •t‘ • 4441 • W FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 BLUE NILE WASH SQ 9364 WASHINGTON SQUARE RD #R01 TIGARD, OR 97223 CITY OF TIGARD REVIEWED FOR CODE COMPLIANCE Approved: [ OTC: Permit#: Kam Address: 419— Atir,„,e a Ath Suite : 9(1. By: itk Date: OFFICE COPY FIRE PROTECTION EQUIPMENT SUBMITTAL tito Worldwide Contacts www,tyco-fire.com Series RFII — 5.6 K-factor "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General stallation or finish. The tip of the Pro- tective Cap can be used to mark the Description center of the ceiling hole into plaster p board or ceiling tiles by gently push- The TYCO Series RFII 5.6 K-factor, ing the ceiling product against the Pro "Royal Flush II" Concealed Pendent tective Cap. When ceiling installation is complete,om the Protective Ca 1'- Sprinklers Quick Response (3-mmpis re bulb) and Standard Response (5 mm moved and the Cover Plate/Retainer -- bulb), are decorative sprinklers featur .,;,-.., Assembly is installed. ing a flat cover plate designed to con- As an option,the Series RFII Standard X' ceal the sprinkler.These sprinklers are Response(5-mm bulb)"Royal Flush II" optimal for architecturally sensitive ar- Concealed Pendent Sprinklers can be eas such as hotel lobbies,office build- fitted with a silicone Air and Dust Seal. ings,churches,and restaurants. (Refer to Figure 5.) The Air and Dust • TY3531 (3-mm Bulb) is UL Listed, Each sprinkler includes a Cover Plate/ Seal is intended for sensitive areas C-UL Listed, 90 Approved (Certif Retainer Assembly and a Sprinkler/ where it is desirable to prevent air and icate No. G4090007), and NYC Quick Support Cup Assembly. The separa dust from the area above the ceiling to proved (MEA 353-01-E) as Quick ble, two-piece assembly design pro pass through the cover plate. Response. vides the following benefits: • TY3531 (3 mm Bulb) is FM and • NOTICE LPCB Approved (Ref. No. 094a/10) Allows installation of the sprinklers The Series RFII Concealed Pendent Approved as Standard Response. and pressure testing of the fire pro Factor Mutual and LPCB do not tection system prior to installation Sprinklers described herein must be y of a suspended ceiling or applica installed and maintained in compli approve any concealed sprinklers tion of the finish coating to a fixed ance with this document and with the for quick response. ceiling. applicable standards of the National • TY3551 (5 mm Bulb) is UL Listed, Fire Protection Association, in addi- C-UL Listed, FM Approved, LPCB • Permits the removal of suspended tion to the standards of any authori- Approved (Ref. No. 094a/9), and ceiling panels for access to building ties having jurisdiction.Failure to do so NYC Approved (MEA 353-01-E) as service equipment without having may impair the performance of these Standard Response. to first shut down the fire protection devices. system and remove sprinklers. Approvals for Air and Dust Seal The owner is responsible for maintain- • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de- UL and C-UL Listed for use with the vertical adjustment to allow a mea- vices in proper operating condition. RFII Standard Response Concealed sure of flexibility in determining the The installing contractor or sprinkler Sprinkler(TY3551). length of fixed piping to cut for the manufacturer should be contacted Maximum Working Pressure sprinkler drops. with any questions. The Series RFII Sprinklers are shipped Maximum 250 psi (17,3 bar) by UL, with a Disposable Protective Cap.The Sprinkler C-UL,and NYC Maximum 175 psi (12,1 bar) by FM, Protective Cap is temporarily removed during installation and replaced to help Identification VdS,and LPCB protect the sprinkler during ceiling in Temperature Rating Number (SIN) 155°F(68°C)Sprinkler with IMPORTANT TY3531 — 3 mm bulb 139°F(59°C)Plate Always refer to Technical Data Sheet TFP700 for the `INSTALLER TY3551 — 5 mm bulb 200°F(93°C)Sprinkler with WARNING" that provides cautions 165°F(74°C)Plate with respect to handling and instal- Technical Discharge Coefficient lation of sprinkler systems and com- ponents. Improper handling and in- Data K.5.6 GPM/psiv2(80,6 LPM/barli2) stallation can permanently damage Adjustment a sprinkler system or its components Sprinkler Approvals 1/2 inch12,7 mm and cause the sprinkler to fail to Approvals apply only to the service inch( ) operate in a fire situation or cause it conditions indicated in the Design Cri- Finishes to operate prematurely. teria section. See the Ordering Procedure section. Page 1 of 4 MARCH 2013 TFP181 TFP181 Page 2 of 4 Physical Characteristics 1/2" NPT Frame Bronze , P SEALING SuSupport ' ASSEMBLY PP Cup Chrome Plated Steel Guide Pins Stainless Steel FRAME i' \ / t Deflector Bronze CAP Compression Screw Brass Bulb Glass / \ -.6►,i , Cap Bronze or Copper SUPPORT Sealing Assembly Beryllium Nickel w/TEFLON CUP WITH jjJ BULB Cover Plate Brass ROLL FORMED - Retainer Brass THREADS Ejection Spring Stainless Steel O Design I CO SCREW MPRESSION GUIDE Criteria PINS(2) ' A AI The TYCO Series RFII 5.6 K-factor, `T-�� DEFLECTOR "Royal Flush II" Concealed Pendent ROPPED Sprinklers are intended for fire protec- DEFLECTOR i i i i POSITION) �-z� r 1_r--1_,.....„-------- with � I tion systems designed in accordance � - _ - �� with the standard installation rules rec- ognized by the applicable Listing or I SPRINKLER/SUPPORT CUP Approval agency;for example, UL List- ASSEMBLY ing is based on NFPA 13 and VdS Ap- proval I j is based on the CEA 4001. THREAD INTO RETAINER SUPPORT J I WITH THREAD For more information on LPCB and CUP UNTIL O VdS Approvals, contact Tyco Fire Pro- MOUNTING 0 ) DIMPLES tection Products at the following office: SURFACE IS EJECTION Enschede,Netherlands FLUSH WITH SPRING Telephone:31-53-428-4444 CEILING Fax:31-53-428-3377 The Series RFII Concealed Pendent Sprinklers are only listed and approved mo �� with the Series RFII Concealed Cover / Plates having a factory applied finish. SOLDER -- COVER TABS(3) COVER PLATE/RETAINER PLATE NOTICE ASSEMBLY Do not use the Series RFII in applica- FIGURE 1 tions where the air pressure above MODEL RFII CONCEALED SPRINKLER the ceiling is greater than that be- ASSEMBLY low. Down drafts through the Sprin- kler/Support Cup Assembly can delay Installation Do not attempt to compensate for in- sprinkler operation in a fire situation. sufficient adjustment in the Sprinkler The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin- Oneration "Royal Flush II" Concealed Pendent kler/Support Cup Assembly. Re-adjust I" Sprinklers must be installed in accor- the position of the sprinkler fitting to When exposed to heat from a fire, the dance with this section. suit. Cover Plate, normally soldered to the General Instructions Step 1. Install the sprinkler only in the Retainer at three points, falls away to pendent position with the center-line expose the Sprinkler/Support Cup Do not install any bulb type sprinkler if of the sprinkler perpendicular to the Assembly. the bulb is cracked or there is a loss mounting surface. of liquid from the bulb. With the sprin- Step 2. Remove the Protective Cap. The Deflector - supported by the kler held horizontally, a small air bub- Guide Pins - then drops down to its ble should be present. The diameter Step 3. With pipe thread sealant ap- operational position. of the air bubble is approximately 1/16 plied to the pipe threads, hand-tighten inch (1,6 mm)for the 155°F(68°C) and the sprinkler into the sprinkler fitting. The glass bulb contains a fluid that ex 3/32 inch(2,4 mm)for the 200°F(93°C) Step 4. Wrench-tighten the sprinkler pathe when exposed to heat. When temperature ratings. using only the RFII Sprinkler Wrench. the rated temperature is reached, the (Refer to Figure 3.) Apply the RFII fluid expands sufficiently to shatter the A leak-tight 1/2 inch NPT sprinkler joint Sprinkler Wrench to the Sprinkler as glass bulb, activating the sprinkler and should be obtained by applying a min- shown in Figure 3. allowing water to flow. imum to maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels Step 5. Replace the Protective Cap of torque can distort the sprinkler In by pushing it upwards until it bottoms out against the Support Cup. (Refer let with consequent leakage or impair- ment of the sprinkler. to Figure 4.)The Protective Cap helps prevent damage to the Deflector and TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER - DIAMETER HOLE —' I FITTING ` DIMENSION C SPRINKLER J ►�C- SUPPORT CUP ASSEMBLY i P'S 1/2"(12,7 mm)THREADED 0 DADJUSTMENT l - FACE `� __In___. OF CEILING, \ /__. RETAINING RING ,,, ,_/ r MOUNTING � SURFACE j � U FIGURE 4 ia.---- _, DISPOSABLE PROTECTIVE CAP 1 N\ Arms during ceiling installation and/or 77----, zr I finish. You can also use the Protective T i Cap to locate the center of the clear- 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ance hole by gently pushing the ceiling (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER material up against the center point of REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY the Protective Cap. COVER PLATE COVER PLATE NOTICE -PROFILE DEPTH DIAMETER DIMENSION B DIMENSION A As long as the Protective Cap remains in place, the system is considered A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) "Out of Service': B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) Step 6.After the ceiling has been com- pleted with the 2-1/2 inch(63,5 mm)FIGURE 2 di- ameter clearance hole and in prepa- ration for installing the Cover Plate/ SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer Assembly, remove and dis- card the Protective Cap.Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the 'j=� FRAME lj�e Deflector does not move up and down freely, replace the entire Sprinkler. ARM \ (% MI= n1 Do not attempt to modify or repair a poil , SUPPORT ?1 1' damaged sprinkler. CUP ( � �; Step 7. When installing an Air and i Dust Seal, refer to Figure 5; otherwise, Il Iproceed to Step 8. To attach the Air Elba ' 4,1111111_40 and Dust Seal, verify the angle of the I _---- outside edge of the seal is oriented ac- .I ` 9 Figure ac- cording to Fi 5. Start the edge of the Retainer in the grooved slot of the 0 7/8"(23 mm) Air and Dust Seal and continue around SQUARE the retainer until the entire Air and Dust Seal is engaged. ALIGN �� � Step 8. Screw on the Cover Plate/ ARROWS WITH / Retainer Assembly until the Retainer FRAME ARMS /I / 1 1 \� (shown in Figure 2)or the Air and Dust i al Seal (shown in Figure 5) contacts the `� r ceiling. Do not continue to screw on ACCEPTS �� ,� the Cover Plate/Retainer Assembly 0 1/2"SOCKET �\�_�� so that it lifts a ceiling panel out of its DRIVE ` normal position. If you cannot engage the Cover Plate/Retainer Assembly FIGURE 3 with the Support Cup or you cannot RFI/SPRINKLER WRENCH engage the Cover Plate/Retainer As sembly sufficiently to contact the ceil- ing, you must reposition the Sprinkler Fitting. TFP181 Page 4 of 4 Care and SUPPORT SPRINKLER FACE OF ORIENT L Maintenance CUP CEILING / BEVEL lniW-- ) SHOWN The TYCO Series RFII 5.6 K-fac -, COVER j� tor, "Royal Flush II" Concealed Pen- PLATE dent Sprinklers must be maintained III.+ ; RETAINER — , ASSEMBLY ' 'and serviced in accordance with this section. I % Before closing a fire protection system i�p�� tAS main control valve for maintenance !; �i ti ►,.' r,. AIR - work on the fire protection system that / ����� / AND DUST 1iI- `:1 SEAL it controls, obtain permission to shut•—_ -----• -, 11... LIP OF COVER down the affected fire protection sys- RETAINER PLATE tem from the proper authorities and FIGURE 5 notify all personnel who may be affect- OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) ed by this action. Absence of the Cover Plate/Retainer If you must remove a sprinkler, do not Ordering Assembly can delay sprinkler opera- reinstall it or a replacement without re- tion 7 in a fire situation. installing the Cover Plate/Retainer As- Procedure When properly installed, there is a sembly. If a Cover Plate/Retainer As nominal 3/32 inch(2,4 mm)air gap be- sembly becomes dislodged during Contact your local distributor for service, replace it immediately. tween the lip of the Cover Plate and the availability. When placing an order, ceiling,as shown in Figure 2. The owner is responsible for the in- indicate the full product name. specThis air gap is necessary for proper their ire testing, and maintenance of Sprinkler/Support Cup Assembly operation of the sprinkler. If the ceil- their fire protection system and devic- ing repainting after sprinkler es in compliance with this document, Specify: Series RFII (specify SIN), ing requiresation, ensure the new paint as well as with the applicable stan- K=5.6, "Royal Flush II" Pendent Sarin- installation, not seal offu any thatothe air gap. dards of the National Fire Protection klers (specify) temperature rating and Association(e.g.,NFPA 25), in addition (specify)finish, P/N(specify). Do not pull the Cover Plate relative to to the standards of any other authori- the Enclosure.Separation may result. ties having jurisdiction.Contact the in- 155°F(68°C) 200°F(93°C) S rinklers which are found to be leak- stalling contractor or sprinkler manu- TY3531 51-792-1-155 51-792-1-200 pfacturer regarding any questions. TY3551 51-790-1-155 51-790-1-200 ing or exhibiting visible signs of corro- • sion must be replaced. Automatic sprinkler systems should be Separately Ordered Cover Plate/ inspected,tested,and maintained by a Retainer Assembly: Automatic sprinklers must never be qualified Inspection Service in accor- painted, plated, coated, or other- dance with local requirements and/or Specify: (temperature rating from be- wise altered after leaving the factory. national code. low) Series RFII Concealed Cover Modified sprinklers must be replaced. Plate with(finish),P/N(specify). Sprinklers that have been exposed to 139°F(59°C)(a) 165°F(74°C)(b) corrosive products of combustion, but Grey White have not operated,should be replaced (RAL9002) 56-792-0-135 56-792-0-165 if they cannot be completely cleaned Brass 56-792-1-135 56-792-1-165 by wiping the sprinkler with a cloth or Pure White(c) by brushing it with a soft bristle brush. (RAL9010) 56-792-3-135 56-792-3-165 Care must be exercised to avoid dam- Signal white (RAL9003) 56-792-4-135 56-792-4-165 age to the sprinklers - before, during, Jet Black and after installation. Sprinklers dam- (RAL9005) 56-792-6-135 59-792-6-165 aged by dropping, striking, wrench Brushed twist/slippage, or the like, must be re- Chrome 56-792-8-135 56-792-8-165 placed.Also,replace any sprinkler that Chrome 56-792-9-135 56-792-9-165 has a cracked bulb or that has lost Custom 56-792-X-135 56-792-X-165 liquid from its bulb. (Ref. Installation (a) For use with 155°F(68°C)sprinklers. Section.) (b) For use with 200°F(93°C)sprinklers. Exercise care to avoid damage to (c) Eastern Hemisphere sales only. _ sprinklers before, during, and after in- Sprinkler Wrench stallation.Replace sprinklers damaged Specify: RFII Sprinkler Wrench, by dropping, striking, wrench twisting, P/N 56-000-1-075. wrench slipping, or the like. Also, re- place any sprinkler that has a cracked Air and Dust Seal bulb or that has lost liquid from its Specify:Air and Dust Seal, bulb.(Refer to the Installation section.) P/N 56-908-1-001. - GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. .,FICO TEFLON is trademark of The DuPont Corporation. i Eddyth read 40 A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS NOMINAL PIPE SIZE n) WEIGI.D. (in) BUNDLE IZ 1 1.461 1.083 70 11/4 2.070 1.418 51 1 1/2 2.547 1.654 > 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINAL PIPE'SIZE ''SCHEDULE40 EDDYTHREAD 40 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 ' 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems 1819 Clarkson Road For additional information, Chesterfield,MO 63017 contact your salesperson today at e �L us II BULL MOOSE TUBE COMPD►NY (800)325-4467 (800)325-4467 or(636)537-2600 UST En FAX:(636)537-2645 in the USA,or from Canada www.bullmoosetube.com call(800)882-4666 4:› A C�RF1ROcompany e-mail:sales@bullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 i ::;)= Ductile Iron Fittings- Class 300 UL/FM cCOus 4::)III APPROVED Fig. 35E 3-90°Elbow LISTED A , e ,Size Part tuber , :A Packing£' ` . Weight in x ., in 1M Innen .: Master: lb ___�� 1/2 35E 3004 1.13 100 200 0.2 111 i „la;4 .. E 3006 , "1:89'' "� 70 1/ ' ! 3 A 1 35E 3010 1.50 40 80 0.5 nn{ !' 1-1/4 ,, 380Al2 ;-:°:'..: Tit'''''-161 75 „f 25 4714i 50N.? . 0:$ ri 1-1/2 35E 3014 1.94 18 36 1.1 €,,, l . s35E 3020 '2.25 1 y,"; 20 1.8 ,. 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3-90°Reducing Elbow ill ( ) jSize Part Numbe rA ''''...;41"` B Packing ,, Weight in a 4,;.i.. S,,,r in z . in ,CI,,Inner; Master lb-•".. 3/4 x 1/2 35RE3006004 1.20 1 22 80 160 0.3 %:A ' 1 x112 1 35RE3 1000 26 h 1 36 70 ,,,,ii 0 4 1x3/4 35RE3010006 1 38 1.45 50 100 0.4 1-f.*x 1/2 35F 3012004 1. 0 .> 70 =.x. 0.s 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 : 11j4x 1 ilt.05R4041f0. ` 158 1 30 . 60 ' 70.7 1-1/2 x 1/2 35RE3014004 1.52 1.75 30 60 0.6 1- �,.3/4140• - `,1.,-1:t i_. >•' r`Aa '25-, 7i ,, 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 11-1/2_4-#4 ,-1,135R, ,1,14 , r'1.82 d.1.8. _`18. 4 .r 0 , 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 .7 90.0201%:'. -.4...„ 1. t' $° lies 18#.4, „„ ! t 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 ;x 1-'1/2', 3 3i ®p 0 " 2 10 .Y i 13 -. 1' 2 x 1-1/2 35RE3020014 2.02 2.16 ' 10 120 1.5 1 x1, E3040144x' 6 ' ,51 n ,� =id`s 2,2 2-1/2 x�2 35RE3024020 2.39 2.60 6 12 2.5 Fig. 35F 3-45°Elbow Ye Pa' m tr 1 A "Packing,,,-,,. .'ht' A .yin ,; -4,, in` ,lo eras- Maste ` ,, u= ,. 1/2 35F 3004 0.88 150 300 0.2 1111 3 , ,1u;,. ..3:Q 4'; 1740.161 ., 8 .R -160 .' ir .P..32:,tg a 1 35F 3010 1.13 40 80 0.5 T. '1-� ;. � i2.° .-1.29 - '25 �`` 0<", , 0.7, �� IA 1-1/2 35F3014 1.44 20 40 1.0 IMS 2 ' i,s35 _ 0 . ..9 10 t .; 20 ....1 1.6 2-1/2 35F'3024 1.95 4 8 2.7 ' Fig. 35T 3- Tee Si g r b , ,, A° � ; (o,Packin�. eig in v 'x : in ..a, Inner . 0.Master « .,• lb a. 1/2 35T3004 1.13 80 160 0.3 --7. I - IA 3/4 t: 351,,a,':°6,'''' '' . 1 a•,v 30 „ixb X60,. ,x'0.5 =;- ---_�-- - 1 35T3010 1.50 25 50 0.7 1 , �. I % .I 1.7 I '',.1 - 2® '1: A A 1-1/2 35T 3014 1.94 10 20 1.5 3020 6 2-1/2 35T3024 2.70 4 8 4.3 111 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com !_ Ductile Iron Fittings - Class 300 UL/FM Malin c (DI us 4141> APPROVED A LISTED Fig. 35CP3 -Straight Coupling with Ribs ze Part umbet A Y, Packing , `i Weight • in Inner'', Master �,,.lb ____ __ 1/2 35CP3004 1.38 200 400 0.1 ,,0 , 4 .` if 35G '6 43''1.63 .444 Q0 r a e ' * 02, . 1 35CP3010 1.75 60 120 0.4 1-1/4 ' ,.`3CP3012: 1417. tib0 35-,,,'',,, 70" , +;.5w" 1-1/2 35CP3014 2.19 25 50 0.7 4355 p3, 1. _ 2 62,x, , 15 a 11.7 `, 30 e-R- 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling t� Y . ,4 ze ParNum `in -ic ' InnerPaekin aster � ,W,eg ht ® 1 x 1/2 35RC3010004 1.69 80 _ 160 0.3 A1x3/4 =35l3Q100Q6 , 159 60- -. 120 y 0 1-1/4 x 3/4 „ 35RC3012006 2.06 40 80 0.a ( 6 2 x 1(t1 ,ex) 5RC 2001 _ 2.e to" Y". 1.0' Fig. 35HB3 -Hex Bushing B ' .Size„ ' er f A ''; Packln =, "Weight 4-,'' . Part'' -in ; Inner> zIgNMaster `lb . 1 x 1/2 35H83010004 1.06 180 360 0.2 i T 4 X1I x 3f r. B3s a s 06 ti . `l o-' k :36 0.11 11 I 1 4 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 . .1 3 + ! x. s 1 1T. 1-1/2 x 1-1/4 35HB3014012 1.25 75 150 0.3 x 1 . "30 ;a�`•: "8 r. ry40" 80 r 0' 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 2z"1-1/ " -f 30200.14' . 448r4 g0 i 0.6 r`,.• Fig. 35SP3 -Square Head Plug SizeA ; .r.. P,' in Wel htI in • .;tea ' b in.* , r I-tier 111-Master s 1/2 35SP3004 0.94 600 1200 0.07 i I A ,'3T4 ,. 35S"`"r® '< s wx ..'' *x' '''4607' 0 :�, . 3.0.1 ' 1 35SP3010 1.25 200 400 0.1 N ' $1=1/? {P . 1131 v .W 1 4 .00, • ::.:4'6.3 41 1-1/2 35SP3014 1.44 80 160 0.4 2 =4B' ;!.# ;50.. _Si45 `90 11-.:.;-:',,..;''..1.6 ,wt i.6 Fig. 35U 3-Union with Brass Seat A Size Part er" acking4 eight. - ,, ; in . " n Innen`° aster .. iib ': ar " 1 35U 3010 2.19 20 40 1.0 ,..,,,,r-w 3012 „4. . } , i°,t a1 2 ' 1-1/2 35U 3014 2.62 10 20 1.7 ._I% - 2' 510 "4 -3.120. 1,6 -a 1 2.4 113 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com IP ARB N STEEL PIPE H LEUT PRQDUGT • FireLock'' a `° c 4l ua Fut LPCBI VdS @ U67Eo 491a/27 SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS t----_— ---_ -___-_— --__-- --------------- STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating',3/4,and 1715,20 and 25 mm outlets for directly connecting sprinklers,drop nipples,sprigs,gauges,drains and other outlet products.Available for 1%through 76.1 mm/32 to 76.1 mm piping systems,Style 922 outlets are UL/ULC Listed,LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe.When tightened,the assembly compresses the gasket onto the OD of the pipe.The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard,lightwall,Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Gasket: • Grade"E"EPDM -Type A (Violet color code).FireLock products have been Listed by Underwriters Laboratories Inc.and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services up to the rated working pressure using the Grade"E"Type A Gasket System. Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: • Orange enamel(North America,Latin America,Asia Pacific) • Red enamel(Europe) • JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved Date www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICitalllIIic` REV G 10.52_1 IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS 10.52 r u ' - STYLE 922 DIMENSIONS Nominal Size Hole Approx. inches/mm Diameter Dimensions-inches/millimeters Weight Each Run X Branch +0.06t+13 ,"`� T '.. Z lbsikg 11/4 X h 3/16 1.30 1.83 1.10 3.87 2 56 1.0 ��� 32 15 30.2 33.0 46.5 27.9 983 65.0 0.45 1 ' � T 3/a 13/16 1.28 1.83 1.10 3.87 2.56 1.1 • . 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 I■r 'r W 1 i 1 13/16 1.52 2.18 1.10 3.87 2.56 1.2 �� 1151 25 30.2 38.6 55.4 27,9 98.3 65.0 0.54 11/2 , 13/16 1.42 1.95 1.22 4.08 2.56 1.2 40 X 15 30.2 36.1 49.5 31.0 103.6 65.0 0.54 34 13/16 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 0.54 1 13/16 1.64 2.30 1.22 4.08 2.56 1.3 25 30.2 41.7 58.4 31.0 103.6 65.0 0.59 21 13/16 1.66 2.19 1.46 4.60 2.56 1.3 50 X 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 34 13/16 1.64 2.19 1.46 4.60 2.56 1.4 20 30.2 41.7 55.6 I 37.1 116.8 65.0 0.64 1 13/16 1.88 2.54 1.46 4.60 2.56 1.5 25 30.2 47.8 64.5 37.1 116.8 65.0 ! 0.68 2'/z1/2 13/16 1.91 2.44 1.71 5.40 2.56 1.6 65 X 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73 14 13/16 1.89 2.44 1.71 5.40 2.56 1.6 20 30.2 48.0 62.0 I 43.4 137.2 65.0 0.73 1 13/16 2.13 2.79 1.71 5.40 2.56 1.6 ---- 25 30.2 1 54.1 70.9 43.4 137.2 65.0 0.73 76.1 mm X %z 13/16 1.91 2.44 1.71 5.50 2.56 1.6 15 30.2 48.5 62.0 43.4 139.7 ! 65.0 0.73 14 13/16 1.89 2.44 1.71 5.50 . 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0.73 1 13/16 ---- 2.13 2.79 1.71 5.50 2.56 1.7 -- 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT(optional) male pipe threads only.Use of male threaded products with special features,such as probes,dry pen- dent sprinklers,etc.,should be verified as suitable for use with this Victaulic product.Failure to verify suitability in advance may result in assembly problems or leakage. *Center of run to engaged pipe end for NPT threads(dimensions are approximate). • www.victaulic.com ' VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ✓ritalillc. 10.52 2 REVG IPS CARBON STEEL PIPE -HOLE CUT PRODUCTS 10.52 FireLockOutlet-1. STYLE 922 PERFORMANCE Equivalent Length of 1 inch Schedule 40 Steel Pipe(per UL Run Size x Outlet Size 213,Section 16)(C=120)',FT . . - 19CheSIMIT, Feethlrieters 11/4 x 1 8.5 32 25 2.6 11/2 X 215 8.5 40 2.6 2 1 8.5 50 25 2.6 21/2 1 8.5 65 25 2.6 1 8.5 76.1 mm X 25 2.6 *Hazen-Williams coefficient of friction is 120 • www.victaulic.com jctaulid • VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV G 10.52 3 IP ARB N TEFL PIPE H LE, UT PRQD $_.. Z , ,aa. -,,,. •'k %,� �; ,-m ..,x. "e;.:'.��. .x _ L.= e•,;��� >� Y�. Pa=.� nt��E• i r Loc 3 Outlet-T STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 ictauliC+, VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10.52 Pipe Hangers Fig. 200- "Trimline"Adjustable Band Hanger (B-Line Fig. B317ONF) 45TOLCO Fig. 200F- "Trimline"Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) VL OS • Fig. 200C - "Trimline"Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) tau Fig. 200S - "Trimline"Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" 1200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications Function: For fire sprinkler and other general piping purposes. Knurled - V swivel nut design permits hanger adjustment after installation. Features: • (1/2" (15mm)thru 2" (5omm)) Flared edges ease installation for all pipe . types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily , \ B / installed around pipe. A For hanger with non-captured nut order Fig. 200S. p • (21/2" 165mm)thru 8" (2oomm))Spring tension on nut holds it securely in \ ,__ hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed(1/2" 115mm)thru 8" (200mm)) Fig.200-1/2.200-3/4 in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved(FM)(3/4" (20mm)thru 8" (200mm))• Fig.200-1 to 200-2 Fig.200-21/2 to 200-8 Conforms to Federal Specifications WW-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, Type 10. . Maximum Temperature: 650°F 1343°C) '''' 1."' ;1.-.. ''''''P''' 1 Finish: Pre-Galvanized. Stainless Steel ., materials will be supplied with (2) hex nuts :'''1 1. in place of a knurl nut. t Order By: Figure number and pipe size f Designed to meet or exceed requirements of FM DS 2-0. .. Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) X00 1/z 1/2" (15), 3/8'-16 r 31/8" (19.4) 25/8" (66.7) 11 (5.0) x, 4..,. „ A 200-3/4 3/4" (20) 3/8"-16 31/8' (79.4) 21/2" (63.5) 11 (5.0) 200-1 1" (25) 3/8-16 33/8" (85.7) 25/8" (66.7) 12 (5.5) 200-11/4 11/4" (32) 3/8'-16 33/4" (94.0) 27/8" (73.0) 13 (5.9) . 200-11/2 11/2" (40) 3/8"-16 37/8" (98.4) 27/8" (73.0) 14 (6.4) 00.7.1';;; ,:; 200-2 2" (50) 3/8"-16 41/2" 1114.31 3" (76.3) 15 (6.9) 200-21/2 21/2" (65) 3/8"-16 55/8" (142.9) '41/8" (104.71 27 (12.3) 200-3 3" (751 3/8'-16 57/8" (149.1) 4" {101.6) 29 (13.3) Fig.2005 200-31/z 31/2" (90) 3/8"-16 73/8" (187.3) 51/4" (133.3) 34 (15.6) 200-4 4" (100) 3/8"-16 73/8" 1187.31 5" (127.0) 35 (16.0) 200-5 5" (125) 1/2"-13 91/8" (231.8) 61/4" (158.7)' 66 (30.2) 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4` (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line Protection Solutions B-Line 21 by IFA•Itt Threaded Accessories B3205 - Threaded Rod (right-hand threads- both ends) (ToLCo Fig.103) - B3205L -Threaded Rod (right&left hand threads) SpecrfyLeng,,,, --- -TL TL 11111) Size Range: /8 -16 thru 3"-4 rod ., »> 1 Material: Steel Function: Recommended for use as a hanger support in hanger assemblies. TL Rod is th ends with right available with leftft andon oright hand threadsh specify Fig. B3205L when orderin and threads of the length Iso t)'') ll��i A g Thread Size Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. • Order By: Part number,rod size,length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) 83205-3x' ";`s; 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) B3205-10'L', ' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) B3205-5/81'L'l' 5/e"-11 21/2 (63.5) 2160 (9.61) 1692 (7.52) 63205-3/4 x'L' ,: 3/4"-10 3" (76.2) 3230 Mall 2530 (11.25) *'‘B321.:7/8°''L' 7/8"-9 31/2 (88.9) 4480 (19.93) 3508 (15.60 B3205-1x ) 1.' 1"8 4" " (101.6} 5900 (26.24) 4620 (20.55} B3205-1'/8 'L'1 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) B3205- 1/4 L' rc, 1 V4"-7 5'A (127.0) 9500 (42.25) 7440 (33.09) 8320 1/2 L'; 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) 11:.':°'1..-- 063X/4'';:r12'. /4" 'L' 13/a"5 (177.8) 18600 82.7 14566 ® :�` ( � �> (64.79) .; r 1.-- x 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) '1.3'171.. 214 x ' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) 1+-2./2tit' ^, ' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) B3205-"2 4, '.A 23/a"4 11 (279.4) 49400 (219.73) 38687 (172.08) 83205 101.' ' 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR -All Threaded Rod 120" (3.05m) Lengths (TOLCO Fig.100) Fig. 99-All Threaded Rod Cut To Length i) 4 "''o,'„111111>>>j111 Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length �����1\ll»��11 Material: Steel 1„ur 5" �)11111111 N am Maximum Temperature: 750°F(399°C) `o Finish: Plain.Contact B-Line for alternative finishes and materials. i Order By: Part number,rod diameter and finish F a Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) 0/441 x 120S 4" n! 20 240 (1.07) 12 (5.44) R x ., ' .11:4 1 16 730 (3.24) 29 'Mill AIR' /2" 2 i= ,,' t x '° , 13 1350 (6.00) 53 (24.04)A /8" 120" "i ngt 11 2160 (9.60) 89' (40.37) TR 4" 2 A..k 10 3230 (14.37) 123 (55.79) ATB /8" 120 . 99-„18 x = 9 4480 (19.93) 170 Millii ' 1 (,1 i"� "x nng 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Hangers&Supports 236 Revised 4/28/2014 B-Line by EAslil SAMMY X-PRESS® SAMMYS Sammy X Press° e:r, r ,`. . Product Features ,� '. 3I XP •The Sammy X-Press expands to provide •Installs in seconds,saving time& Patent No.( ) direct vertical attachment in: installation costs. 6,935,821 -Metal Deck(22-16 gauge) ,ti,,,� -Z-Purlin(18-16 gauge) •Use in applications where access .,•` ' to the back of the installed fastener is • -r •The Sammy X-Press Swivel allows you prohibited.ie.metal roof deck,tubular to hang plumb in extreme roof pitches: steel,or vapor barrier fabric. (SWXP) -89°in Z-Purlin 1/ -45°in metal deck for 12/12 pitch •Less jobsite material needed. Patent Pending for •The Sammy X-Press Sidewinder expands •No retaining nut required. t (SXP) extreme to provide horizontal attachment in: -16 ga-3/16"steel-purlin,tubular •Provides design flexibility or . steel. Patent Pending variant roof Pitches Appra4afa Rod Part > • • Ultimata �UL Test . , F7M Test'.'-°.,Mink'-, Maxl'36:-.';;Case : n' Ic j:• Size Number SAC tlescilptmn Pullout(lbs) Load(81s) Lead a Thick 'Thick ":04(:'VERTICAL .:,•...:,•.. VERTICAL MOUNT `" : 1/4" 8181922 XP 200 X-Press 200 114622 a 185(Luminaire) 027" ( 9) 250(Luminaire) .056° 125' 25 125 Metal Deck . • ylx 650(2'�"P - c.�+t.=. .','"f, .-. 185 uminna •. (2'Pipe);' .02T :k. 'i. •.fir . ,,.318"`150922 z 20 X Press 201146(22 ga) •.. 250 urilaire) • i,....: ° 75(4704,18,027"021' .12b ?5 125 Deck +''. <. . 4x.056° 1500(4'Pipe) .060° O 3/8" 8153922 XP 35 X-Press 35 1783 16ga) 85(Luminaire) 940 (2'Pipe) 105° ( 250(Luminaire) 1475(4"Pipe) .027° 125" 25 125 Purlin 416(Conduit&Cable) .056° Wk. u • 1.i". 75 '' t ) .'4r : . 88 � 170 (Luminaire ;• $IS' 82 20 Sw lPress20 ' O6f 22 aVerBa ) ( y a `j25 .aletalDec F' • 829(45 r,„„ Bcaq 80 ` inane..:.. 635 2' r ».125 25 r •:e .283' at(Cond Cable) ?' k} t. ^' • ;: r ,t„� •:,„• `:,u ..:233 ii'45'(Condutable) 4 a r, ,. 1500(4'Pipe) 1675(16 Vertical) 250 vertical(Luminaire) �4 "' 3/8" 8295922 SXP 35 Swivel X-Press 35 1558(89°ga Off Venial) 80 @ 90°(Luminaire) 635(2'Pipe) .060" .125° 25 125 Purlin 500 vertical(Conduit&Cable) 333 @ 89°(Conduit&Cable) .: I.! . : Y 1,.,„,,,,,, <:. . ;, 7. .: %§) n. Metal Deck f • * f i' • • .P r Sirucbrrei COnOrete@ 3000 •; •":°:' 13/8" 1.50922 XP 20 •SammyX-Presi 20 114¢2. `850(2%Pk* '¢. a• .< 5 1254 (Pre-Pour}. . • := -Pour R 1l , 135 PCF. Metal Deck `,, ;a- 44' €A �. Post-Pou "t• 1250(3'W Pipe) ' ' 3/8' 8293957 SWXP 35 SidewinderX-Press 35 1798(16ga) 80(Luminaire) .060' .125" 25 125 Purlin 416(Conduit&Cable) Pro-Pour Structural Concrete@ 3000 psi Post•Pour Range II LWCS 35 PCF(Ibis fP) ....r—Lf-k_ _fir_ ef--Wir-u-IN` /NM ef v- , ' • l Sammy X Press It® INSTALLATION TOOL ' . , •. 7 UXPIT "T ° f }'" Patent Pending • ' ' _ A„ . r+°+ r aH ._ �, y moi, ,::'';'a. „.• 4. Part Number Model Description Each Qty 819491Q�"' UXP( ' Unieat Xfress itTool• 1 v i ; 8195910 RXPIT Retro Socket for 8151910 1 8152910 ) n8'. 484 Dstngl, r ihttp:/Avww.sammysuperscrew.comrsammyxptess.htm watch a video demonstration of the SammyX-Press,visithtip:/Avwsammysuperscrew.comrsammyxpress.htm 'Tool Includes:Sleeve,Bit Receiver,Hex Wrench,and 25/64"Drill Bit.• For the most up to date informationvisit www sammysuperscreW com8 le Vr / S_ NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series RSS&RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%). • "Regulated Voltage Range"is the newest terminology used by UL to identify the voltage range. Prior to this change,UL used the terminology"Listed Voltage Range". Table 1: Average RMS Current* RSS/RSSP RSSIRSSP-Wall Mount RSS-Ceiling Mount 24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH Models 1575cd 15cd 30cd 75cd 110cd 135cdI85cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189E 0.249 0.300 0.420 RSS/RSSP RSS/RSSP * RMS current ratings are per UL average RMS method. UL max current 24VDC Wall Mount rating is the maximum RMS current within the listed voltage range(16-33v Models 121575W for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage(16v for 24v units). For audibles the max current is usually at the maximum listed voltage(33v for 24v units). For unfiltered FWR ratings, UL max* 0.255 see installation instructions. Table 2: Audibles/Speakers for RSSP Strobe Plate Product Series Multitone Appliances AMT, MT Horns AH,NH,HS Motor Bells MB-G6/G10 Speakers ET-1010/1080,E70, ET70 Chimes CH70 A WARNING:CONTACT WHEELOCK FOR THE CURRENT"INSTALLATION INSTRUCTIONS" AND"GENERAL INFORMATION"SHEET(P82380)ON THESE PRODUCTS.THESE DOCUMENTS UNDERGO PERIODIC CHANGES.IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS,INCLUDING: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. • ADDING,REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR"REGULATED VOLTAGE RANGE". • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH. • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION,APPLICATION,AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. • CONDUCTOR SIZE(AWG),LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS,PARTICULARLY IN RETROFIT INSTALLATIONS.