Report (22) Capitol / 02_6,0 sw
Electric Co., Inc. JUN 3 0 201
6
BUILDING DNISION
June 30, 2016
Plans Examiner
City of Tigard
Building Services
13125 SW Hall Blvd.
Tigard, OR 97223
Re: Tenant Fire Alarm System Modifications
Reinisch Wilson, Suite 1250 @ Lincoln Tower
10260 SW Greenburg Road
Tigard, OR 97223
Please find attached building and electrical permit applications, three sets of plans,
calculations, and product submittals for the fire alarm tenant improvements at the address
shown above.
Occupancy Group: B
The fire alarm system design includes the following:
1. Install (1)new ceiling strobe in tenant space per fire alarm plans.
2. We will pre-test the fire alarm devices prior to requesting a final fire alarm
inspection.
3. Fire alarm design by Simplex-Grinnell, installation by Capitol Electric Co.
Please contact me if you have questions or comments.
Respectfully,
Dan Wilson, SET
Project Manager/Estimator
Fire/Life Safety Division
Capitol Electric Company, Inc.
(503) 262-0411 Direct
Dan@cepdx.com
NICET Level IV, Fire Alarm Systems #104512
11401 NE Marx Portland, Oregon 97220-1041 • 503-255-9488 • Fax 503-257-7121
CCB# 48748 • www.capitolelectricco.corn
hEW YGR% y /'
MEA ADA ry: �
,15TFM.,
Helping People Take Actions'
r; . SERIES RSS & RSSP SINGLE
IU Nsi 3 0 2016 & MULTI-CANDELA STROBES
$ F'�
& STROBE PLATES
p(f �
v, e t i k i,,,,°C S
FIRE
DESCRIPTION <<
Wheelock's patented Series RSS Strobe Appliances and "' akli#
Series RSSP Strobe Plates have lower current draw while FIRE
maintaining outstanding performance,reliability and cost
effectiveness. These versatile appliances will satisfy
virtually all requirements for indoor,wall or ceiling mount Series RSS Series RSSP RSS Round
applications.
Strobe options for wall mount models include 1575 or
Wheelock's Patented MCW multi-candela strobe with field
selectable candela settings of 15/30/75/110cd or the high
intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models include the patented MCC multi- Multi-Candela Indicator
candela ceiling strobe with field selectable intensities of of Strobe Lens)
15/30/75/95cd or the high intensity MCCH strobe with (bottom
field selectable 115/177cd. Features
• Approvals include: UL Standard 1971,New York City
All models may be synchronized using the Wheelock (MEA),California State Fire Marshal(CSFM),Factory
SM,DSM Sync Modules or the PS-12/24-8CP and Mutual(FM),and Chicago(BFP) See approvals by
PS-12/24-8MP Power Supplies with Wheelock's Patented model in Specifications and Ordering Information
Sync Protocol. Synchronized strobes can eliminate ADA/NFPA/UFC/ANSI compliant. Meets OSHA 29
possible restrictions on the number of strobes in the field •
Part 1910.165
of view.Wheelock's synchronized strobes offer an easy Wall mount Multi-Gandela models are available
way to comply with ADA recommendations concerning
photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/
75/110cd or 1351185cd. Single Candela models
requirements of NFPA72. are available in 1575cd
Wheelock's Series RSS Strobes employ a Patented • Ceiling mount Multi-Candela models are
available with field selectable candela settings of
Integral Strobe Mounting Plate that can be mounted to a 15/30/75/95cd or 115/177cd. (Round or Square)
single gang,double gang,4"square, 100mm European Strobes produce 1 flash per second over the
backboxes or the SHBB surface backbox. If the flush •
regulated voltage range
backbox has side or top space between it and the finished reand 24 VDC models with wide UL"Regulated
wall,the NATP(Notification Appliance Trimplate)may be using filtered(DC)or unfiltered VRMS input
used.It provides an additional.65"of trim for the Appliance. voltage
Voltage"An attractive cover plate is provided for a clean,finished • Synchronize using Wheelock's sync modules or power
appearance on all models. supplies with built-in sync protocol
The Series RSSP Multi-Candela Strobe Plates are a cost • Fast installation with IN/OUT screw terminals using
effective way to retrofit required wall strobe appliances to #12 to#18 AWG wire
bells, horns,chimes, multitones or speakers and easily
mounts to standard 4" backboxes or for surface mount
use with Wheelock's SBL2 surface backbox.
For Weatherproof Series RSS See Datatsheet S9004
Copyright 2004 Wheelock, Inc. All rights reserved.