Report (23) /I/c 5T,L0IL —O0 .3-3 . i 3 A 314 ... /-v t VI/Pliktr71)4, 11111"'' 4:1 V ti41 JUN 052012 C!Iv OF `it;i:11-, B ssa S 4 t. AquaSAFETM FIRE SAFETY SYSTEM � �(4:0 '1� e . . Uponor 5925 148th Street West Apple Valley, MN 55124 800-321-4739 Job Name : HIGHLAND HILLS LOT 3-Two Head Calculation (H.16& H.20) Drawing : RESIDENTIAL Location : 13234 SW WILMINGTON LANE TIGARD OR 97224 Remote Area : 1 Contract : 120515-42L Data File : 120515-42L Highland Hills Lot 3.wx2 L Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Uponor Page 1 HIGHLAND HILLS LOT 3-Two Head Calculation (H.16&H.20) Date 5/29/2012 HYDRAULIC DESIGN INFORMATION SHEET Name - HIGHLAND HILLS LOT 3 Date - 5/29/12 Location - TIGARD OR 97224 Building - RESIDENTIAL System No. - 1 Contractor - MISSION HOMES NW Contract No. - 120515-42L Calculated By - BRENT KOTULA SET IV Drawing No. - 1 Construction: (X) Combustible ( ) Non-Combustible Ceiling Height VARIES OCCUPANCY - RESIDENTIAL S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D Y Number of Sprinklers Flowing: ( )1 (X)2 ( ) 4 ( ) S ( )Other T ( )Specific Ruling Made by Date E M Listed Flow at Start Point - 13 Gpm System Type Listed Pres. at Start Point - 9.14 Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle S Additional Flow Added - Gpm Make RELIABLE Model RFC43 I Elevation at Highest Outlet - 119 Feet Size 3/8 K-Factor 4.3 G Note: Temperature Rating 165 N Calculation Gpm Required 26.0199 Psi Required 54.1 At Ref Pt STR Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - x Rated Cap. Cap. T Time of Test - x @ Psi Elev. E Static (Psi) - 60 Elev. R Residual (Psi) - 55 Other Well Flow (Gpm) - 300 Proof Flow Gpm S Elevation - 98 P Location: x P L Source of Information: STREET Y J Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Uponor HIGHLAND HILLS LOT 3-Two Head Calculation (H.16&H.20) Page 2 Date 5/29/2012 City Water Supply: Cl -Static Pressure : 60 Demand: C2-Residual Pressure: 55 D1 - Elevation 9.095 C2-Residual Flow : 300 D2-System Flow : 26.0199 D2-System Pressure : 54.104 Hose(Adj City) Hose (Demand) : D3-System Demand : 26.0199 Safety Margin : 5.842 150 140 130 • p 120 R 110 E 100 S 90 S 80 U70 Cl R60 ° U C2 E 50 e 40 30 20 10 ° D1 50 100 150 200 250 . . . .300 . .350 .400 FLOW(N^ 1.85) 450 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Flow Summary - NFPA 2007 Uponor HIGHLAND HILLS LOT 3-Two Head Calculation (H.16&H.20) Page 4 Date 5/29/2012 SUPPLY ANALYSIS Node at Static Residual Available Source Pressure Pressure Flow Pressure Total Demand Required Pressure • STR 60.0 55 300.0 59.946 26.02 54.104 NODE ANALYSIS Pressure Node Tag Elevation Node Type at Node att Node e Notes H.16 119.0 4.3 9.14 13.0 H.12 119.0 9.55 H.13 119.0 10.28 H.6 119.0 11.43 T.41 119.0 11.84 T.38 109.0 17.35 T.39 109.0 17.6 T.40 109.0 18.68 H.3 109.0 18.98 H.10 109.0 19.83 H.11 109.0 20.45 H.17 109.0 21.07 T.50 109.0 21.99 S.1 104.0 31.41 MTR 98.0 46.97 STR 98.0 54.1 H.20 119.0 4.3 9.17 13.02 T.51 119.0 11.25 T.52 109.0 16.92 H.23 109.0 17.01 H.32 109.0 17.32 T.55 109.0 17.5 T.56 109.0 17.76 H.33 109.0 19.69 H.24 109.0 21.35 H.27 119.0 11.39 H.29 119.0 11.77 H.35 119.0 12.17 H.34 119.0 12.45 T.57 119.0 12.62 H.5 119.0 11.87 H.4 119.0 12.05 H.7 119.0 12.22 T.42 119.0 12.36 H.14 119.0 12.38 T.45 119.0 12.52 T.44 109.0 16.98 T.43 109.0 17.05 H.9 109.0 17.2 H.2 109.0 17.42 H.18 119.0 12.54 T.47 119.0 12.54 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Flow Summary - NFPA 2007 Page 5 i : ag Uponor PPage 5/29/2012 HIGHLAND HILLS LOT 3-Two Head Calculation(H.16&H.20) NODE ANALYSIS(cont.) Pressure Discharge Node Tag Elevation Node Type at Node at Node Notes H.22 119.0 12.56 H.26 119.0 12.57 H.28 119.0 12.58 H.30 119.0 12.6 H.36 119.0 12.61 T.48 109.0 16.95 H.19 109.0 16.99 H.15 109.0 17.03 H.1 109.0 17.36 H.8 109.0 17.39 H.21 109.0 17.43 T.53 109.0 17.45 T.54 109.0 17.45 H.31 109.0 17.47 H.25 109.0 17.45 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 • Final Calculations - Hazen-Williams Uponor Page 6 HIGHLAND HILLS LOT 3-Two Head Calculation (H.16& H.20) Date 5/29/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn H.16 11.59 0.862 1 Utr 2.0 3.000 9.140 K Factor=4.30 • to 150.0 0.0 2.000 0.0 H.12 11.59 0.0816 0.0 5.000 0.408 Vel= 6.37 H.12 0.0 0.862 1 Utr 2.0 7.000 9.548 to 150.0 0.0 2.000 0.0 H.13 11.59 0.0818 0.0 9.000 0.736 Vel= 6.37 H.13 0.0 0.862 1 Utr 2.0 12.000 10.284 to 150.0 0.0 2.000 0.0 H.6 11.59 0.0816 0.0 14.000 1.143 Vel= 6.37 H.6 0.0 0.862 1 Utr 2.0 3.000 11.427 to 150.0 0.0 2.000 0.0 T.41 11.59 0.0818 0.0 5.000 0.409 Vel= 6.37 T.41 -4.14 0.862 2Utb 12.0 20.676 11.836 to 150.0 0.0 12.000 4.331 T.38 7.45 0.0361 0.0 32.676 1.179 Vel= 4.10 T.38 -1.64 0.862 1 Utr 2.0 9.000 17.346 to 150.0 0.0 2.000 0.0 T.39 5.81 0.0227 0.0 11.000 0.250 Vel= 3.19 T.39 5.43 0.862 0.0 14.000 17.596 to 150.0 0.0 0.0 0.0 T.40 11.24 0.0771 0.0 14.000 1.080 Vel= 6.18 T.40 0.0 0.862 1 Utr 2.0 2.000 18.676 to 150.0 0.0 2.000 0.0 H.3 11.24 0.0770 0.0 4.000 0.308 Vel= 6.18 °` H.3 0.0 0.862 1 Utr 2.0 9.000 18.984 to 150.0 0.0 2.000 0.0 H.10 11.24 0.0771 0.0 11.000 0.848 Vel= 6.18 H.10 0.0 0.862 1 Utr 2.0 6.000 19.832 to 150.0 0.0 2.000 0.0 H.11 11.24 0.0771 0.0 8.000 0.617 Vel= 6.18 H.11 0.0 0.862 1 Utr 2.0 6.000 20.449 to 150.0 0.0 2.000 0.0 H.17 11.24 0.0771 0.0 8.000 0.617 Vel= 6.18 H.17 0.0 0.862 1 Utr 2.0 10.000 21.066 to 150.0 0.0 2.000 0.0 T.50 11.24 0.0772 0.0 12.000 0.926 Vel = 6.18 T.50 14.78 0.862 1T 7.528 11.000 21.992 to 150.0 1 Utb 6.0 8.904 2.166 S.1 26.02 0.3645 0.0 19.904 7.255 Vel = 14.30 S.1 0.0 0.862 2E 7.528 25.000 31.413 to 150.0 0.0 2.323 5.599 *Fixed loss= 3 MTR 26.02 0.3646 0.0 27.323 9.961 Vel= 14.30 MTR 0.0 0.995 1E 2.336 30.000 46.973 to 150.0 1T 5.841 9.345 0.0 STR 26.02 0.1812 1G 1.168 39.345 7.131 Vel= 10.74 0.0 26.02 54.104 K Factor= 3.54 H.16 1.41 0.862 1 Utr 2.0 15.000 9.140 to 150.0 0.0 2.000 0.0 H.20 1.41 0.0016 0.0 17.000 0.028 Vel= 0.78 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Uponor Page 7 HIGHLAND HILLS LOT 3-Two Head Calculation(H.16&H.20) Date 5/29/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn H.20 13.02 0.862 1 Utr 2.0 15.000 9.168 K Factor=4.30 to 150.0 0.0 2.000 0.0 T.51 14.43 0.1225 0.0 17.000 2.082 Vel = 7.93 T.51 -5.92 0.862 2Utb 12.0 17.000 11.250 to 150.0 0.0 12.000 4.331 T.52 8.51 0.0461 0.0 29.000 1.336 Vel= 4.68 T.52 -2.59 0.862 1 Utr 2.0 2.000 16.917 to 150.0 0.0 2.000 0.0 H.23 5.92 0.0235 0.0 4.000 0.094 Vel= 3.25 H.23 0.0 0.862 1 Utr 2.0 11.000 17.011 to 150.0 0.0 2.000 0.0 H.32 5.92 0.0235 0.0 13.000 0.306 Vel= 3.25 H.32 0.0 0.862 1 Utb 6.0 2.000 17.317 to 150.0 0.0 6.000 0.0 T.55 5.92 0.0235 0.0 8.000 0.188 Vel= 3.25 T.55 1.64 0.862 0.0 7.000 17.505 to 150.0 0.0 0.0 0.0 T.56 7.56 0.0371 0.0 7.000 0.260 Vel= 4.16 T.56 7.22 0.862 lUtr 2.0 13.000 17.765 to 150.0 0.0 2.000 0.0 H.33 14.78 0.1281 0.0 15.000 1.921 Vel= 8.13 H.33 0.0 0.862 lUtr 2.0 11.000 19.686 to 150.0 0.0 2.000 0.0 H.24 14.78 0.1281 0.0 13.000 1.665 Vel= 8.13 H.24 0.0 0.862 1 Utr 2.0 3.000 21.351 to 150.0 0.0 2.000 0.0 T.50 14.78 0.1282 0.0 5.000 0.641 Vel= 8.13 0.0 14.78 21.992 K Factor= 3.15 T.51 5.92 0.862 1 Utr 2.0 4.000 11.250 to 150.0 0.0 2.000 0.0 H.27 5.92 0.0235 0.0 6.000 0.141 Vel= 3.25 H.27 0.0 0.862 1 Utr 2.0 14.000 11.391 to 150.0 0.0 2.000 0.0 H.29 5.92 0.0236 0.0 16.000 0.377 Vel= 3.25 H.29 0.0 0.862 1 Utr 2.0 15.000 11.768 to 150.0 0.0 2.000 0.0 H.35 5.92 0.0236 0.0 17.000 0.401 Vel= 3.25 H.35 0.0 0.862 1 Utr 2.0 10.000 12.169 to 150.0 0.0 2.000 0.0 H.34 5.92 0.0236 0.0 12.000 0.283 Vel= 3.25 H.34 0.0 0.862 1 Utr 2.0 5.000 12.452 to 150.0 0.0 2.000 0.0 T.57 5.92 0.0236 0.0 7.000 0.165 Vel = 3.25 T.57 1.30 0.862 2Utb 12.0 12.000 12.617 to 150.0 0.0 12.000 4.331 T.56 7.22 0.0340 0.0 24.000 0.817 Vel= 3.97 - 0.0 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Uponor HIGHLAND HILLS LOT 3-Two Head Calculation (H.16& H.20) Dat 8 te 5/29/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 7.22 17.765 K Factor= 1.71 T.41 4.14 0.862 1Utr 2.0 1.000 11.836 to 150.0 0.0 2.000 0.0 H.5 4.14 0.0120 0.0 3.000 0.036 Vel= 2.28 H.5 0.0 0.862 1Utr 2.0 13.000 11.872 to 150.0 0.0 2.000 0.0 ... .: H.4 4.14 0.0121 0.0 15.000 0.182 Vel= 2.28 H.4 0.0 0.862 1Utr 2.0 12.000 12.054 to 150.0 0.0 2.000 0.0 H.7 4.14 0.0122 0.0 14.000 0.171 Vel= 2.28 H.7 0.0 0.862 1Utr 2.0 9.000 12.225 to 150.0 0.0 2.000 0.0 T.42 4.14 0.0121 0.0 11.000 0.133 Vel= 2.28 T.42 0.0 0.862 0.0 2.000 12.358 to 150.0 0.0 0.0 0.0 H.14 4.14 0.0125 0.0 2.000 0.025 Vel= 2.28 H.14 0.0 0.862 1Utr 2.0 9.000 12.383 to 150.0 0.0 2.000 0.0 T.45 4.14 0.0121 0.0 11.000 0.133 Vel= 2.28 T.45 -1.30 0.862 1 Utb 6.0 16.132 12.516 to 150.0 0.0 6.000 4.331 T.44 2.84 0.0061 0.0 22.132 0.134 Vel= 1.56 T.44 0.0 0.862 1 Utb 6.0 4.000 16.981 to 150.0 1Utr 2.0 8.000 0.0 T.43 2.84 0.0061 0.0 12.000 0.073 Vel= 1.56 T.43 2.59 0.862 1Utr 2.0 5.000 17.054 to 150.0 0.0 2.000 0.0 H.9 5.43 0.0201 0.0 7.000 0.141 Vel= 2.99 H.9 0.0 0.862 1Utr 2.0 9.000 17.195 to 150.0 0.0 2.000 0.0 H.2 5.43 0.0200 0.0 11.000 0.220 Vel= 2.99 H.2 0.0 0.862 lUtr 2.0 1.000 17.415 to 150.0 1 Utb 6.0 8.000 0.0 T.39 5.43 0.0201 0.0 9.000 0.181 Vel= 2.99 0.0 5.43 17.596 K Factor= 1.29 T.45 1.30 0.862 lUtr 2.0 13.000 12.516 to 150.0 0.0 2.000 0.0 H.18 1.3 0.0015 0.0 15.000 0.022 Vel= 0.71 H.18 0.0 0.862 1Utr 2.0 2.000 12.538 to 150.0 0.0 2.000 0.0 T.47 1.3 0.0012 0.0 4.000 0.005 Vel= 0.71 T.47 0.0 0.862 1Utr 2.0 7.000 12.543 to 150.0 0.0 2.000 0.0 H.22 1.3 0.0014 0.0 9.000 0.013 Vel= 0.71 H.22 0.0 0.862 1Utr 2.0 9.000 12.556 to 150.0 0.0 2.000 0.0 H.26 1.3 0.0015 0.0 11.000 0.016 Vel= 0.71 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Uponor Page 9 HIGHLAND HILLS LOT 3-Two Head Calculation (H.16&H.20) Date 5/29/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt ** *** Notes ""*"'* Ref. "C" or Ftng's Pe Pv Point Qt Pf/Ft Eqv. Ln. Total Pf Pn H.26 0.0 0.862 1 Utr 2.0 6.000 12.572 to 150.0 0.0 2.000 0.0 H.28 1.3 0.0014 0.0 8.000 0.011 Vel= 0.71 H.28 0.0 0.862 1 Utr 2.0 6.000 12.583 to 150.0 0.0 2.000 0.0 H.30 1.3 0.0015 0.0 8.000 0.012 Vel= 0.71 H.30 0.0 0.862 1 Utr 2.0 11.000 12.595 to 150.0 0.0 2.000 0.0 H.36 1.3 0.0014 0.0 13.000 0.018 Vel= 0.71 H.36 0.0 0.862 0.0 3.000 12.613 to 150.0 0.0 0.0 0.0 T.57 1.3 0.0013 0.0 3.000 0.004 Vel= 0.71 0.0 1.30 12.617 K Factor= 0.37 1 T.52 2.59 0.862 1 Utr 2.0 4.000 16.917 to 150.0 0.0 2.000 0.0 T.48 2.59 0.0050 0.0 6.000 0.030 Vel= 1.42 T.48 0.0 0.862 1 Utr 2.0 7.000 16.947 to 150.0 0.0 2.000 0.0 H.19 2.59 0.0051 0.0 9.000 0.046 Vel= 1.42 H.19 0.0 0.862 1 Utr 2.0 6.000 16.993 to 150.0 0.0 2.000 0.0 H.15 2.59 0.0051 0.0 8.000 0.041 Vel= 1.42 H.15 0.0 0.862 1 Utr 2.0 2.000 17.034 to 150.0 0.0 2.000 0.0 T.43 2.59 0.0050 0.0 4.000 0.020 Vel= 1.42 0.0 2.59 17.054 K Factor= 0.63 T.38 1.64 0.862 1 Utr 2.0 6.000 17.346 to 150.0 0.0 2.000 0.0 H.1 1.64 0.0021 0.0 8.000 0.017 Vel= 0.90 H.1 0.0 0.862 1 Utr 2.0 9.000 17.363 to 150.0 0.0 2.000 0.0 H.8 1.64 0.0023 0.0 11.000 0.025 Vel= 0.90 H.8 0.0 0.862 1 Utr 2.0 16.000 17.388 to 150.0 0.0 2.000 0.0 Vel= 0.90 H.21 1.64 0.0022 0.0 18.000 0.039 H.21 0.0 0.862 1 Utr 2.0 7.000 17.427 to 150.0 0.0 2.000 0.0 Vel= 0.90 T.53 1.64 0.0022 0.0 9.000 0.020 T.53 -0.19 0.862 1 Utr 2.0 1.000 17.447 to 150.0 0.0 2.000 0.0 T.54 1.45 0.0017 0.0 3.000 0.005 Vel= 0.80 T.54 0.19 0.862 1 Utr 2.0 4.000 17.452 to 150.0 0.0 2.000 0.0 H.31 1.64 0.0023 0.0 6.000 0.014 Vel= 0.90 H.31 0.0 0.862 1 Utr 2.0 16.000 17.466 to 150.0 0.0 2.000 0.0 T.55 1.64 0.0022 0.0 18.000 0.039 Vel= 0.90 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Uponor HIGHLAND HILLS LOT 3-Two Head Calculation (H.16&H.20) Date Page50 5/29/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 1.64 17.505 K Factor= 0.39 1.53 0.20 0.671 1 Utr 2.0 10.000 17.447 to 150.0 lUtb 6.0 8.000 0.0 H.25 0.2 0.0002 0.0 18.000 0.003 Vel= 0.18 H.25 0.0 0.671 lUtb 6.0 11.000 17.450 to 150.0 0.0 6.000 0.0 T.54 0.2 0.0001 0.0 17.000 0.002 Vel= 0.18 0.0 0.20 17.452 K Factor= 0.05 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 BLICAAccEIvED JUN 0522012 LE'Y/Plf I AquaSAFETM FIRE SAFETY SYSTEMNit' 1 12, kb32 Uponor 5925 148th Street West Apple Valley, MN 55124 800-321-4739 Job Name : HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Drawing : RESIDENTIAL Location : 13234 SW WILMINGTON LANE TIGARD OR 97224 Remote Area : 1 Contract : 120515-42L Data File : 120515-42L Highland Hills Lot 3.wx1 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 4 Uponor Page 1 HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Date 5/29/2012 HYDRAULIC DESIGN INFORMATION SHEET Name - HIGHLAND HILLS LOT 3 Date - 5/29/12 Location - TIGARD OR 97224 Building - RESIDENTIAL System No. - 1 Contractor - MISSION HOMES NW Contract No. - 120515-42L Calculated By - BRENT KOTULA SET IV Drawing No. - 1 Construction: (X) Combustible ( ) Non-Combustible Ceiling Height VARIES OCCUPANCY - RESIDENTIAL S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D Y Number of Sprinklers Flowing: (X) 1 ( )2 ( ) 4 ( ) S ( (Other T ( (Specific Ruling Made by Date E M Listed Flow at Start Point - 18 Gpm System Type Listed Pres. at Start Point - 17.52Psi (X) Wet ( ) Dry D MAXIMUM LISTED SPACING 18 x 18 ( ) Deluge ( ) PreAction E Domestic Flow Added - 0 Gpm Sprinkler or Nozzle S Additional Flow Added - Gpm Make RELIABLE Model RFC43 I Elevation at Highest Outlet - 119 Feet Size 3/8 K-Factor 4.3 G Note: Temperature Rating 165 N Calculation Gpm Required 18 Psi Required 46.58 At Ref Pt STR Summary C-Factor Used: Overhead 150 Underground 150 W Water Flow Test: Pump Data: Tank or Reservoir: A Date of Test - x Rated Cap. Cap. T Time of Test - x @ Psi Elev. E Static (Psi) - 60 Elev. R Residual (Psi) - 55 Other Well Flow (Gpm) - 300 Proof Flow Gpm S Elevation - 98 P Location: x P L Source of Information: STREET Y Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) Uponor HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Page 2 Date 5/29/2012 City Water Supply: Cl -Static Pressure : 60 Demand: C2-Residual Pressure: 55 D1 -Elevation 9.095 C2-Residual Plow : 300 D2-System Flow : 17.9985 D2-System Pressure 46.580 Hose(Adj City) Hose(Demand) : D3-System Demand : 17.9985 Safety Margin : 13.393 150 140 : 130 p 120 R 110 E 100 S 90 S 80 U 70 - Cl R 60 ° et E 50 ; D2 6 40 30 20 10 ° D1 50 100 150 200 250 . . . .300 . 350 .400. FLOW(N^ 1.85) 450 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Flow Summary - NFPA 2007 Uponor HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Page 4 Date 5/29/2012 S Node at Static Residual Source Pressure Pressure Avai/able F/ow Pressure STR 60.0 55 300.0SUPPLYANALY 59.9/S 73 18.0Total Demand 46.58Required Pressure NODE ANALYSIS Node Tag Elevat/on Node Type at Node Dat Node e Notes H.28 119.0 4.3 17.52 H.30 119.0 18.0 18.94 H.36 119.0 19. T.57 119.0 19.155 T.56 109.0 3 24 H.33 109.0 25.3 25.3 H.24 109.0 26.17 T.50 109.0 S.1 104.0 26.5 MTR 98.04 32.34 STR 42.97 98.0 46.58 H.26 119.0 17.81 H.22 119.0 18.22 T.47 119.0 18.55 H.18 119.0 18.69 T.45 119.0 19.24 T.44 109.0 23.89 T.43 109.0 24.06 H.9 109.0 24.14 H.2 109.0 24.26 T.39 109.0 24.36 T.40 109.0 24.89 H.3 109.0 25.04 H.10 109.0 25.45 H.11 109.0 25.75 H.17 109.0 26.05 H.34 119.0 19.2 H.35 119.0 19.29 H.29 119.0 19.42 H.27 119.0 19.55 T.51 119.0 19.59 T.52 109.0 24.07 H.23 109.0 24.1 H.32 109.0 24.2 T.55 109.0 24.26 H.14 119.0 19.32 T.42 119.0 19.33 H.7 119.0 19.4 H.4 119.0 19.5 H.5 119.0 19.6 T.41 119.0 19.61 T.38 109.0 24.26 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Flow Summary - NFPA 2007 Page 5 Uponor Date 5/29/2012 HIGHLAND HILLS LOT 3-One Head Calculation (H.28) NODE ANALYSIS(cont.) Pressure Discharge Notes Node Tag Elevation Node Type at Node at Node H.20 119.0 19.6 H.16 119.0 19.6 H.12 119.0 19.6 H.13 119.0 19.61 H.6 119.0 19.61 H.15 109.0 24.06 H.19 109.0 24.06 T.48 109.0 24.07 H.31 109.0 24.26 T.54 109.0 24.26 H.25 109.0 24.26 T.53 109.0 24.26 H.21 109.0 24.26 H.8 109.0 24.26 H.1 109.0 24.26 Computer Programs by Hydratec Inc. Route 111 Windham N.H.USA 03087 Final Calculations - Hazen-Williams Uponor HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Page 6 Date 5/29/2012 ReHyd. Qa Dia. Fitting Pipe Pt Pt Ftng' Point Qt Pf/Ft Eqv.r Ln. Totals Pf PvPe ******* Notes ****** ' H.28 10.48 0.862 1 Utr 2.0 6.000 10.520 K Factor=4.30 to 150.0 H.30 10.48 0.0679 0.0 2.000 0.0 0.0 8.000 0.543 H.30 0.0 0.862 1 Utr 2.0 Vel= 5.76 to 150.0 11.000 18.063 0.0 2.000 0.0 H.36 10.48 0.0678 0.0 13.000 0.881 H.36 0.0 0.862 0.0 Vel= 5.76 to 150.0 3.000 18.944 T.57 10.48 0.0680 0.0 0'0 0.0 0.0 3.000 0.204 T.57 -3.21 0.862 2Utb 12.0 12.000 Vel= 5.76 to 150.0 0 19.148 T.56 .0 12.000 4.331 7.27 0.0344 0.0 24.000 T.56 3.11 0.862 0.826 Vel= 4.00 to 1 Utr 2.0 13.000 24.305 150.0 0.0 2.000 H.33 10.38 0.0666 0.0 0.0 15.000 0.998 H.33 0.0 0.862 1 Utr 2.0 Vel= 5.71 to 150.0 11.000 25.304 0.0 2.000 0.0 H.24 10.38 0.0666 0.0 13.000 0.866 H.24 0.0 0.862 1 Utr 2.0 Vel= 5.71 to 150.0 3.000 26.170 T.50 10.38 0.0666 0.0 2.000 0.0 0.0 5.000 0.333 T.50 7.62 0.862 1T 7.528 11.000 26.503 Vel= 5.71 to 150.0 1 Utb 6.0 S.1 18.0 0.1843 8.904 2.166 0.0 19.904 3.669 S.1 0.0 0.862 2E 7.528 25.000 Vel= 9.90 to 150.0 32.338 MTR 18.0 0.10 0.0 2.323 5.599 0.0 27.323 *Fixed loss=3 5.974 to Vel= 9.90 MTR 0.0 0.995 1 E 2.336 30.000 42.974 150.0 1T 5.841 9.345 STR 18.0 0.0917 1G 1.168 39.345 0.0 0.0 3.606 Vel= 7.43 18.00 H.28 7.51 0.862 46.580 K Factor= 2.64 to 1 Utr 2.0 6.000 17.520 150.0 0.0 2.000 H.26 7.51 0.0366 0.0 0.0 8.000 0.293 H.26 0.0 0.862 1 Utr 2.0 Vel= 4.13 to 150.0 9.000 17.813 0.0 2.000 0.0 H.22 7.51 0.0366 0.0 11.000 0.403 H•22 0.0 0.862 1 Utr 2.0 Vel= 4.13 to 150.0 7.000 18.216 T.47 7.51 0.0367 0.0 2.000 0.0 0.0 9.000 0.330 T.47 0.0 0.862 1 Utr 2.0 2.000 Vel= 4.13 to 150.0 0 18.546 H.18 .0 2.000 0.0 7.51 0.0365 0.0 4.000 H.18 0.0 0 862 0.146 Vel= 4.13 to 1 Utr 2.0 13.000 18.692 150.0 0.0 2.000 T.45 7.51 0.0367 0.0 0.0 15.000 0.550 T.45 -2.99 0.862 1 Utb 6.0 16.132 Vel= 4.13 to 150.0 19.242 0.0 6.000 4.331 T.44 4.52 0.0143 0.0 22.132 0.317 Vel= 2.48 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Page 7 Uponor Page 7/29/2012 HIGHLAND HILLS LOT 3-One Head Calculation(H.28) Pipe Pt Pt fHydNotes ""*"" Re . „ Qa Dia. FittingPe Pv ******* C„ or Ftng's PoEqv. Ln. Total Pf Pn Point Qt Pf/Ft T.44 0.0 0.862 1 Utb 6.0 4.000 23.890 to 150.0 1 Utr 2.0 8.000 0.0 Vel= 2.48 T.43 4.52 0.0142 0.0 12.000 0.171 T.43 -0.57 0.862 1 Utr 2.0 5.000 24.061 150.0 0.0 2.000 0.0 Vel= 2.17 to 0.0 7.000 0.078 H.9 3.95 0.0111 H.9 0.0 0.862 1 Utr 2.0 9.000 24.139 150.0 0.0 2.000 0.0 Vel= 2.17 to 0.0 11.000 0.123 H.2 3.95 0.0112 H.2 0.0 0.862 1 Utr 2.0 1.000 24.262 to 150.0 1 Utb 6.0 8.000 0.0 Vel= 2.17 T.39 3.95 0.0111 0.0 9.000 0.100 T.39 3.67 0.862 0.0 14.000 24.362 150.0 0.0 0.0 0.0 to TAO 7.62 0.0376 0.0 14.000 0.526 Vel= 4.19 T.40 0.0 0.862 1 Utr 2.0 2.000 24.888 150.0 0.0 2.000 0.0 Vel= 4.19 to 0.0 4.000 0.150 H.3 7.62 0.0375 H.3 0.0 0.862 1 Utr 2.0 9.000 25.038 to 150.0 0.0 2.000 0.0 Vel= 4.19 H.10 7.62 0.0376 0.0 11.000 0.414 H.10 0.0 0.862 1 Utr 2.0 6.000 25.452 to 150.0 0.0 2.000 0.0 Vel= 4.19 H.11 7.62 0.0375 0.0 8.000 0.300 H.11 0.0 0.862 1 Utr 2.0 6.000 25.752 to 150.0 0.0 2.000 0.0 Vel= 4.19 H.17 7.62 0.0375 0.0 8.000 0.300 H.17 0.0 0.862 1 Utr 2.0 10.000 26.052 to 150.0 0.0 2.000 0.0 Vel= 4.19 T.50 7.62 0.0376 0.0 12.000 0.451 0.0 26.503 K Factor= 1.48 7.62 T.57 3.22 0.862 1 Utr 2.0 5.000 19.148 to 150.0 0.0 2.000 0.0 Vel= 1.77 H.34 3.22 0.0076 0.0 7.000 0.053 H.34 0.0 0.862 1 Utr 2.0 10.000 19.201 to 150.0 0.0 2.000 0.0 Vel= 1.77 H.35 3.22 0.0077 0.0 12.000 0.092 H.35 0.0 0.862 1 Utr 2.0 15.000 19.293 to 150.0 0.0 2.000 Vel= 1.77 H.29 3.22 0.0076 0.0 17.000 0.130 H.29 0.0 0.862 1 Utr 2.0 14.000 19.423 150.0 0.0 2.000 0.0 to Vel= 1.77 H 27 3.22 0.0076 0.0 16.000 0.122 H.27 0.0 0.862 1 Utr 2.0 4.000 10.045 to 150.0 0.0 2.000 Vel= 1.77 T.51 3.22 0.0075 0.0 6.000 0.045 T.51 -0.63 0.862 2Utb 12.0 17.000 19.590 150.0 0.0 12.000 4.331 Vel= 1.42 to 0.0 29.000 0.149 T.52 2.59 0.0051 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Uponor HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Page 8 Date 5/29/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. C„ or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn T.52 0.58 0.862 1 Utr 2.0 2.000 24.070 to 150.0 0.0 2.000 0.0 H.23 3.17 0.0072 0.0 4.000 0.029 H.23 0.0 0.862 1 Utr 2.0 11.000 24.099 Vel= 1.74 to 150.0 0.0 2.000 0.0 H.32 3.17 0.0075 0.0 13.000 0.097 H.32 0.0 0.862 1 Utb 6.0 2.000 24.196 Vel= 1.74 to 150.0 0.0 6.000 0.0 T.55 3.17 0.0074 0.0 8.000 0.059 T.55 -0.05 0.862 Vel= 1.74 0.0 7.000 24.255 to 150.0 0.0 0.0 T.56 3.12 0.0071 0.0 0.0 7.000 0.050 Vel= 1.72 0.0 3.12 24.305 T.45 2.99 0.862 1 Utr 2.0 9.000 19.242 K Factor= 0.63 to 150.0 0.0 2.000 0.0 H.14 2.99 0.0066 0.0 11.000 0.073 Vel= 1.64 H.14 0.0 0.862 to0.0 2.000 19.315 150.0 0.0 0.0 0.0 T.42 2.99 0.0065 0.0 2.000 0.013 T.42 0.0 0.862 lUtr 2.0 9.000 19.328 Vel= 1.64 to 150.0 0.0 2.000 0.0 H.7 2.99 0.0067 0.0 11.000 0.074 H.7 0.0 0.862 1 Utr 2.0 12.000 19.402 Vel= 1.64 to 150.0 0.0 2.000 0.0 H.4 2.99 0.0066 0.0 14.000 0.093 H.4 0.0 0.862 1 Utr 2.0 13.000 19.495 Vel= 1.64 to 150.0 0.0 2.000 0.0 H.5 2.99 0.0067 0.0 15.000 0.100 H.5 0.0 0.862 1 Utr 2.0 1.000 19.595 Vel= 1.64 to 150.0 0.0 2.000 0.0 T.41 2.99 0.0067 0.0 3.000 0.020 1.41 0.63 0.862 2Utb 12.0 20.676 19.615 Vel= 1.64 to 150.0 0.0 12.000 4.331 T.38 3.62 0.0095 0.0 32.676 0.309 T.38 0.05 0.862 1 Utr 2.0 9.000 24.255 Vel= 1.99 to 150.0 0.0 2.000 0.0 T.39 3.67 0.0097 0.0 11.000 0.107 Vel= 2.02 0.0 3.67 24.362 T.51 0.62 0.862 1 Utr 2.0 15.000 19.590 K Factor= 0.74 to 150.0 0.0 2.000 0.0 H.20 0.62 0.0004 0.0 17.000 0.007 H.20 Vel= 0.34 0.0 0.862 1 Utr 2.0 15.000 19.597 to 150.0 0.0 2.000 0.0 H.16 0.62 0.0004 0.0 17.000 0.006 H.16 0.0 0.862 1 Utr 2.0 3.000 19.603 Vel= 0.34 to 150.0 0.0 2.000 0.0 H.12 0.62 0.0004 0.0 5.000 0.002 Vel= 0.34 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Page 9 ag Uponor PPage 9/29/2012 HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Hyd. Qa Dia. Fitting Pipe Pt Pt ** **** Notes '" Ref. "C" or Ftng's Pe Pv Point Qt Pf/Ft Eqv. Ln. Total Pf Pn H.12 0.0 0.862 1 Utr 2.0 7.000 19.605 to 150.0 0.0 2.000 0.0 H.13 0.62 0.0003 0.0 9.000 0.003 Vel= 0.34 H.13 0.0 0.862 1 Utr 2.0 12.000 19.608 to 150.0 0.0 2.000 0.0 H.6 0.62 0.0004 0.0 14.000 0.005 Vel= 0.34 H.6 0.0 0.862 1 Utr 2.0 3.000 19.613 to 150.0 0.0 2.000 0.0 T.41 0.62 0.0004 0.0 5.000 0.002 Vel= 0.34 0.0 0.62 19.615 K Factor= 0.14 T.43 0.57 0.862 1 Utr 2.0 2.000 24.061 to 150.0 0.0 2.000 0.0 H.15 0.57 0.0005 0.0 4.000 0.002 Vel= 0.31 H.15 0.0 0.862 1 Utr 2.0 6.000 24.063 to 150.0 0.0 2.000 0.0 H.19 0.57 0.0002 0.0 8.000 0.002 Vel= 0.31 H.19 0.0 0.862 1 Utr 2.0 7.000 24.065 to 150.0 0.0 2.000 0.0 T.48 0.57 0.0003 0.0 9.000 0.003 Vel= 0.31 T.48 0.0 0.862 1 Utr 2.0 4.000 24.068 to 150.0 0.0 2.000 0.0 T.52 0.57 0.0003 0.0 6.000 0.002 Vel= 0.31 0.0 0.57 24.070 K Factor= 0.12 T.55 0.05 0.862 1 Utr 2.0 16.000 24.255 to 150.0 0.0 2.000 0.0 H.31 0.05 0.0 0.0 18.000 0.0 Vel= 0.03 H.31 0.0 0.862 1 Utr 2.0 4.000 24.255 to 150.0 0.0 2.000 0.0 T.54 0.05 0.0 0.0 6.000 0.0 Vel= 0.03 T.54 -0.04 0.671 1 Utb 6.0 11.000 24.255 to 150.0 0.0 6.000 0.0 H.25 0.01 0.0 0.0 17.000 0.0 Vel= 0.01 H.25 0.0 0.671 1 Utr 2.0 10.000 24.255 to 150.0 1 Utb 6.0 8.000 0.0 Vel= 0.01 T.53 0.01 0.0 0.0 18.000 0.0 T.53 0.04 0.862 1 Utr 2.0 7.000 24.255 to 150.0 0.0 2.000 0.0 H.21 0.05 0.0 0.0 9.000 0.0 Vel= 0.03 H.21 0.0 0.862 1 Utr 2.0 16.000 24.255 to 150.0 0.0 2.000 0.0 H.8 0.05 0.0 0.0 18.000 0.0 Vel= 0.03 H.8 0.0 0.862 1 Utr 2.0 9.000 24.255 to 150.0 0.0 2.000 0.0 H.1 0.05 0.0 0.0 11.000 0.0 Vel= 0.03 H.1 0.0 0.862 1 Utr 2.0 6.000 24.255 to 150.0 0.0 2.000 0.0 T.38 0.05 0.0 0.0 8.000 0.0 Vel= 0.03 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations - Hazen-Williams Uponor HIGHLAND HILLS LOT 3-One Head Calculation (H.28) Page 10 Date 5/29/2012 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. ..C.. or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 0.05 24.255 T.53 -0.05 0.862 1 Utr 2.0 1.000 24.255 K Factor= 0.01 to 150.0 0.0 2.000 0.0 T.54 -0.05 0.0 0.0 3.000 0.0 0.0 Vel= 0.03 -0.05 24.255 K Factor= -0.01 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 J � ' t feet on center. See NFPA 13 Appendix for detailed ex- Residential sprinklers must be installed with the man- closets,itis permitted to install pendent sprinklers sothat Definitions lanations of this type of construction. ufacturer's specified sprinkler wrench. Channel locks, the deflector is within 12 inches(305 mm)of the ceiling. r The following NFPA definitions are applicable is the P crescent wrenches or anything other than the proper Residential sidewall sprinklers that have not been listed terms used in this installation guide. Where terms are sprinkler wrench shall not be used. with specific positioning criteria must be positioned so not included, refer to NFPA 13,NFPA 13D and NFPA Flat Ceiling-a continuous ceiling in a single plane. Installing sprinklers in CPVC and copper piping sys- that the deflectors are within 4 in.to 6 in.(102 mm to 152 f 13R for official definitions: terns require special considerations. Never install the mm)from the ceiling. Install sidewall sprinklers having Smooth Ceilinn-A continuous ceiling free from signifi- sprinkler into the reducing fitting prior to attaching the listed positioning criteria in accordance with their listing. Residential Sprinkler-le type of fast-response sprin- cant irregularities,lumps or indentations. educing fitting to the system piping. When installing Under both horizontal and sloped ceilings,always align kler that has a thermal element with ed RTI of 50(m-s) esidential sprinklers or commercial sprinklers in a CPVC sprinkler deflectors so that the deflector is parallel with piping system,sprinklers must be installed only after the the plane of the ceiling surface. e h less,has been specifically tested for its ability to Horizontal piilin sl A ceiling that does not exceed a reducing tieing has been installed and the CPVC man- enhance survivability in the room in fire origin and listed slope of 2/12 pitch(slope of 16.7%or 9.4°). � - for use in the protection of dwelling units. Residential ufacturer's setting time for the primer and/or cement has passed. This is to ensure that the cement does not ac- Several maximum coverage areas are used for resi- sprinklers posses a fast response thermal element and Sloped Ceiling-A ceiling exceeding a maximum slope cumulate within the sprinkler.In copper piping systems, dential sprinklers in accordance with minimum listed produce ll spray pattern that discharges water higher of 2/12(9.4°)pitch. on the wall than a standard spray sprinkler. sprinklers must be installed only after the inside of the flows and pressures.The area of coverage must e Installation ConSideratlOnS sprinkler drop and associated fittings have been wire- equal to or greater than both the length and width of the Ili Any building that contains not more than Residential sprinklers utilizing a glass bulb thermal els- brushed to remove any residual flux..Residual flux can hazard area.Residential sprinklers must be located not one or two dwelling units intended to be used,rented, ment have orange protective caps and straps to provide cause corrosion. Both of these conditions can impair moreftha wallst e listeent pp nk e sor less t ocated1022 leased,let or hired out to be occupied or that are occu- temporary protection to the frangible glass bulb during and prevent proper sprinkler operation. farther apart than the listed spacing;the minimum dis- pied for habitation purposes. shipping and installation. lance to prevent cold soldering,unless otherwise speci- a. Do not install any bulb type sprinkler if the bulb is System Design Criteria fied,is 8 feet(2.44 m). Dwelling Unit-One or more rooms,arranged for the cracked or there is liquid missing from the bulb. permitted Sprinklers for Residential Sprinkler Systems use of one or more individuals living together,as in a While holding the sprinkler in the horizontal po- For NFPA 13D and 13R sprinkler systems,only Ilsted When selecting an area of coverage,the suggested single housekeeping unit,that normally have cooking, salon,n,a small air bubble having an approximate residential sprinklers shall be used,with the following practice elects lectoneea of ove ode,th sly suppled living,sanitary, and sleeping facilities. Dwelling units diameter of 1/16"should be visible. exceptions: by the available water supply,allowing for the installa- include hotel rooms,dormitory rooms,condominiums, b. The sprinkler is designed for installation with the protective strap in place using the appropriate 1. Listed standard dry-pendent or dry sidewall sprinklers tion of as few sprinklers as possible while observing all apartments,and similar living units. sprinkler wrench. uidelines pertaining to obstructions and spacing. Af- c. Sprinklers that are dropped during the installs- = nstalls- shall be permitted to be extended Into unheated areas 9 not intended for living purposes. ter selection of an area of coverage,sprinklers must be compartment-A compartment is a space completely tion process or that are installed on piping other spaced according to the criteria set forth in the NFPA enclosed by walls and a ceiling. The compartment en- than that in accordance with item"a"shall be re- 2. Quick-response sprinklers shall be permitted to be used p closure is permitted to have openings(in walls)to an placed,including sprinklers with protective caps in mechanical closets. standards and this document. 3. For NFPA 13R listed quick-response sprinklers adjoining space,provided that soffits or lintels along the or straps. shallrFFbe permitted systems,installedtein unitspmeet- Sprinkler Spacing Under Stoned Ceilings ceiling over the compartment opening has a minimum d. Protectiveticaps and straps shall be removed only ing the definitionermittof a e sarldwellingelli no more than For installation under Ssloped ceilings, several maxi- depth of 8 in.(203mm)from the ceiling. In other words, using means in accordance with the are n not tootbe four(4)sprinklers are located within the dwelling unit. mum coverage areas are also provided,but at different areas such as hallways,stairwells,and rooms must be Br's installation instructions. They be minimum flows and pressures than those for horizontal s depth tedto ecobeams, considered or soffits t more inches in leftplaced the sprinklerrvceafter the sprinkler system is Non-residential sprinklers are to be installed in accor- ceilings. The spacing of sprinklers is measured along depth to be considered single compartments. v capspica. dance with the criteria specified by NFPA 13. the slope when determining the distance off of walls and e. Protective and straps shall be removed only between sprinklers. Residential sprinklers may be spr Osed Construction - Panel ,constructionthrand when water poly is made cto the lo- other construction where beams,trusses,or other mem- kler for the purposes of fire protection and placed Residential Sprinkler Positioning ann- d SpaC- X102 mm)froo re m the peak of the sloped Y2 the listed geilorgless than 4" Res Ben- n service. ing Requirements bers impede heat flow or water distribution in a manner f A leak-tight%z"NPT sprinkler joint should be ob- When locating residential sprinklers, consideration tial sprinklers located at the highest elevation must not or s suppress materially affects the NFPA 13y of sprinklersefto control tamed with a maximum torque of 14 ft-lbs to 21 be located more than 3 feet(0.9 m)measured vertically or suppress a fire.See Appendix for detailed ft-lbs.(approximately 2 turns past hand tight.Do must be given to sensitivity,sprinkler spacing,obstruc- down from the peak. Refer to Reliable Bulletin 035 for type of construction. tions to discharge,temperature rating,and proximity to listed coverage areas,flow and pressure requirements, explanations of this not over tighten).Higher levels of torque may din- heat sources. and positioning criteria for residential sprinklers installed tort the sprinkler inlet or bend the frame,causing ander sloped ceilings. Unobstructed Construction - Construction where leakage or impairment of the sprinkler. .rinkl•r -n ivi - -c•r�• i•ni beams,trusses,or other members not impede heat Residential pendent sprinklers not listed with specific Obstruction to Water Distribution flow or water distribution in a manner that materially af- Where applicable, escutcheon plates must be in- positioning criteria positionediers so ed wthe defied- Refer to Figures 1 through 13 for the location of sprin- fire.shis abilityeof construction s ri ction to hetfol or suppress a stalled. Absence of an escutcheon plate,where there is tors are within 1 in.to 4 must be(25.4 mm fp 102 mm)from the klers relative to obstructions. The discharge from resi- (l1) This l t uc ural has the followingrent features: an annular space between the ceiling and the sprinkler, ceiling. On flat,horizontal ceilings,Reliable Model F1 dential sprinklers is directed radially outward and down- the horizontal structural members that are not solid;(2) Res 49 pendent and recessed pendent sprinklers maySprinklers openings of the structural members are at least 70%of may delay sprinkler operation in the event of a fire. ward from tke s is direc lymust be located Never introduce any leak stopping additives to any fire also be positioned with the deflector 4"to 8"(102 mm to such that will not be any spaces shielded from the cross sectional area;(3)depth of the structural mem- sprinkler system. 203 mm)from the ceiling,in accordance with the listed distribution thereby walls,dividing partitions,or other dwell- flows do not exceed the least dimension of the openings; or(4)the spacing of structural members exceeds 7.5 flows and pressures shown in Bulletin 135. If located in 4. 3. • Fxamnle No,2 Care and Maintenance If a room is 10 ft wide x 20 ft long(3.0 m x 6.1 m), It is recommended that automatic sprinkler systems the coverage area being considered would be 200 b e e inspected criteria tset forrtmaintained th in NFPA 25,Inspen ction, oance Testing x x ith (1(18.6 ilia toUsing le tFlO Res58 pendentsprinklera and Maintenance of Water-Based Fire Protection // (1"-4"ceiling-to-deflector distance),the flow for a Systems bya qualified inspection service. gpm ft x 20 14.4(6.1 m x 6.1 m)coverage area is 22 Do not clean the sprinklers with soap and water,de- on a psi(83.3 L min©0.99 bar). Based Y on a discharge density of 0.1 gpm/ftz,the flow rate tergents,ammonia,or any other cleaning fluid. Re- I everrequired flowd only2 be 20 gpm 75.b L/min). How-the move dust by using a soft brush or feather duster, ever,the flow of 22 gpm must still be used as the or by gentle vacuuming with a soft bristle brush. minimum flow for each design sprinkler,since this Any sprinklers that have operated,been damaged ise re- the minimum ft flow for this sprinkler p�ab ed with a new sprpainted inkler.thee of factory newrspr sprinkler shall ELEVATION at the 20 ft x 20 ft coverage area. have the same performance characteristics as the Fxamnle No 3 original sprinkler;that is the same temperature rat- x ing,nominal K-factor,coverage area,and the same For a situationfwhere the coverage4 m),ora1282 ftz (11 9 or lower flow rate requirements. x keel ist16 ft x 8 ft4 H m x 2.4 a ee ft e rat- �� m),the Ft RES 44 HSW,having a temperature rat- Wet-pipe sprinkler systems must be maintained at ing of 155°F(68°C)and positioned 4"to 6"(101 a minimum temperature of 40°F(4°C). Exposure to mm to 152 mm)below the ceiling,requires a mini- freezing temperatures can damage system piping mum flow of 16 gpm 4.13.3 psi(60.6 L/min©.92 and Do not ihantiag anphnklers. n anything sprinklers or sprinkler / bar)for a 16 ft x 16 ft(4.9 m x 4.9 m)coverage area. Do not put curtains,drapes or valences T Based one minimum discharge of 0.1 gpm/ft,the piping. flow rate needed would only be 12.8 gpm 41 10.2 around sprinklers.s thDoing oi gnseso will obstruct the dis- psi(48.4 L/min©0.7 bar). However,the flow rate MAxiNUM AS OW,+aLE=LAWS s£^," of 16 gpm(60.6 L/min)must still be used for each 015TANCF fate5RRINKLERS LQ design sprinkler. SEE QE OBSTRUCTION 1x) daQOE AOTTDN SE OBsrRUCION al LESS THAN 1'-0"(LS0" Sloped CeilingsListed 1'-0"[304.x'- TO LESS THAN 1'-6"(457.2mm] 5"[25.4mm] Specific s for sloped Liefiling pressuresroiand coverage 1'-6"(457.2mm]re LESS THAN 1'-0"(609.6mm) I"[25.4mm] areas ceilings are provided in Reliable 2'-6"(762.0mm]TO LESS THAN 2'-e"(914.0mm] i"(25.4mm) 2'-0"[609.6mm]TO LESS THAN 2'-"(762.0mm] 3"(25.4mm] Bulletin equi Refer to this bulletin o for hydraulic 3'-0"(914.0mm]TO LESS THAN 3'-6"(1016.0mm] 3"(76.2mm) design requirements.The number of design sprin- 3'-6"(1219.omm]TO LESS THAN 4'-6"(I371.6mm) 5"[127.0mm] 4'-6"(1016.0mm)TO LESS THAN 4'-0"(1219.2mm) 7"[7.2 mm] klers is the same xasc that specified for horizontal 4'-6"(1371.6mm]TO LESS THAN 5'-0"[1524.0mm) 7"[7778mm] ceilings,with the exception of the Model F1 Res 44 5'-6"[1676.4mm]TO LESS THAN 6'-6"(1828.8mm] 7"(177.8mm] 5'-0"[1524.0mm]TO LESS THAN 6'-6"[1676.4mm] 9"(l77.8mm) 140FG01A deli This compartmentar enrws a minimum 3 sprinkler across 6'-0"(1828.8mm]TO LESS THAN 6'-8"(1981.2mm) (2 8.6 un design in a when discharging across 7'-0"(2933.6mm]AND81.2rnm]TO LESS GREATEAN 7.-0"(2r33.6mm] 14"(355.6mm) the slope,as specified in Bulletin 035. For systems designed to NFPA 13, 13D or 13R, where specific cULus Listed flows for sloped ceil- ings are not required,consult with the AHJ regard- ing the number of "design sprinklers"for sloped Figure l ceilings having a pitch greater than 2 in 12(9.4°). Position of sprinklers to avoid obstructions to discharge radially from pendent sprinklers. cULus Listed flows and pressures do not exist for sloped ceilings having a pitch greater than 8/12 (33.7°). Again,consult with the AHJ regarding the number of "design sprinklers"for these types applications. Listed areas of coverage must cor- respond to ceiling slope,and spacing of sprinklers under sloped ceilings is measured along the slope when determining distance off of walls and be- tween sprinklers. 8. 7. • 1 g I N \ , .. to m''A m �xs�y D .8m67mm ci F 2 V <gm,, o -4$° O Q u,� \ a. T�Nb� \ m 3 a 0vr p 4 X X / /07 / / DISTANCE FROM SIDEWA_L L MAXIMUM ALLOWARI F DISTANCF SPRINKLER IQ SIDE QE DEFLECTOR ABOVE BOTTOM QE OBSTRUCTION LX) QE OBSTRUCTION £y] ry LESS THAN 1'-6" [508.0mm] NOT ALLOWED 1'-6" (508.0mm] TO LESS THAN 3'-0" (914.0mm] 1"(25.4mm] 3'-0"[914.0mm] TO LESS THAN 3'-6" (1016.0mm] 1"[25.4mm 3'-6" (1016.0mm] TO LESS THAN 4'-0" [1219.2mm] 3"(76.2mm 4'-0" [1219.0mm] TO LESS THAN 4'-6" [1371.6mm] 4"[101.6mm 4'-6" (1371.6mm] TO LESS THAN 5'-0" (1524.0mm) 5"l 127.0mm 5'-0" (1524.0mm] TO LESS THAN 5'-6" (1676.4mm] 6"(152.4mm 5'-6" [1676.4mm] TO LESS THAN 6'-0" [1828.8mm] 7"(177.8mm 6'-0" (1828.8mm] TO LESS THAN 6'-6"(1981.2mm] 9"(228.6mm] 6'-6" [1981.2mm] TO LESS THAN 7'-0" (2133.6mm] 1 1"(279.4mm] 7'-0" [2133.6mm] TO 8'-0" (2438.0mm] 14"(355.6mm] 140FGOSA Figure 5 Positioning of sidewall sprinklers to avoid obstructions along the wall. • g on m X # ytli N 4 1 R t Q <-1 Ilk O 6. g4 O • m tiAizA k..;w x..;w 44.:114.u.;,. 4..:. 44.;; m ( \\� 1 /3.14111I 11-111 4111 i1 \ T Q. "-eoo -oo oo TP 7 C -..o _i o00 00o itoao 00o N:=wq I'i N :y o 14 "www 4L41; bb:w> .. ... '.®' co ni• A If ill! ll!" Dili 11111 Hill 1�-. . LOPi -\.,,,,m LQ 4 X Zxi n Es - s iii j C j PENDENT SPRINKLER SIDEWALL SPRINKLER ELEVATION ELEVATION A-ACCEPTABLE CEILING ANGLE I0' - 60' rn B-ONE-HALF THE MAXIMUM LISTED SPRINKLER SPACING(SEE TECHNICAL BULLETINS REFERENCED IN TABLE A)FOR THE COVERAGE AREA. MEASURED ALONG THE SLOPE. C-MINIMUM DISTANCE TO INTERSECTING SLOPED CEILING. 9NNNNY r-6'(14311.40 H OMIONTAL INSTANCE 6CTWCDI 1rNNMlMt y MILL(H(I$I70NTM CEILING&CALE(A) TMCTANCF(,C) 10' 1'-0"(704Amm) 15' 1'-0'(. 4.6mm) 16.4' 1'-0'(304.8mm) 20' 1'-0'(204.600) 25" 1'-0'(304.600) 30' l'-6'(457.2mm) 35' 1'-6'(457.2mm) 40' 1'-6'(508mm) 45' 2'-0'(609.6mm) 50' 2'-0'(609.6mm) 60' 2'-0"(609.6mm) 140FG09A Figure 9 Obstruction to discharge by intersecting sloped ceiling. B B • _ D A -ACCEPTABLE CEILING ANGLE 10' - 33.7" B - ONE-HALF THE MAXIMUM LISTED SPRINKLER SPACING(SEE TECHNICAL BULLETINS REFERENCED IN TABLE A)FOR THE COVERAGE AREA, MEASURED ALONG THE SLOPE. C -MINIMUM DISTANCE TO INTERSECTING CEIUNG,AS PERMITTED BY FIGURE 9. D - MINIMUM 8'-0'(2438.4mm) 140FGIOA Figure 10 Minimum distance between sprinklers on intersecting ceilings. E !h • 3 m qA�AyA:4 AgAAz.CA_Y4 AAAA4 yp;;:;>{ppRZ:;itgg;s:YyS Kyi;r4 14 i R^EC }I f^! R^ R C i 1 11'If!'I 1!'i !!'ifH'I 1!till @ I I' z R y G 0 c G9 al.m' I 11 {{{{4 4L.4 ;•. •44444{{{44{4444 44444 IH fits fffilf111111111111111co y O 1rr= ,. _ / • ' , ,/ :1 / / / • /" , A:/ D Sri .. /i•Si ' / . z . ', '4, I/X PENDENT SPRINKLER SIDEWALL SPRINKLER A-ACCEPTABLE CEILING ANGLES TO -.3.3.r. B-ONE-NILE THE IIAMIL/44 LISTED SPRINKLER SPACING(SEE TECHNICAL BULLETINS REFERENCED IN TABLE A)FOR THE COVERAGE AREA, MEASURED ALONG THE SLOPE. C-MINIMUM(UNOBSTRUCTED)DISTANCE TO OPPOSED SLOPE AS PERMITTED BY FIGURE II. D-.3'-0 (914.400M)MXIMUM 140,4114 Figure 12 Single sprinkler coverage criteria for cathedral ceilings. , I 1-isEi ID ''''', iiii 1 .111 CI l—i-§11 V3 I-• 8 i e A ID® 111 ,i BEAM g 1___ .co.4- a. * .i-,..,LB81 e8gS. .' A „A '-':° '''"1<7''' V MINIM Immo 0 togurs; c .„"g.g.. F. 0,, 3-,77:i Ae4r——/.. 1--.2r. FIRES 49 q 1-- 3. VS' W. 11111) Fl RES49/F2 - gc`' '- I . . A - 0.-7" (177.8mm) MAXIMUM B - 7"-6" (2286mm) MINIMUM. 2 i,9 'I di. c - 0.-8 (203.2mm) MAXIMUM. gid.g2i 0,5' NOTE: CORE DRILLING OF STRUCTURAL OR LOAD BEARING BEAMS TO E ALLOW THE INSTALLATION OF SPRINKLER DROPS REQUIRES 5 APPROVAL OF A STRUCTURAL ENGINEER. i° 2L 1 40FG13A I' - , ,93_ °.7' gi• 8 - t III ,,, ® ,-1 ',,,,. ,, . Figure 13 s' - n -7,, Pendent sprinkler positioning for beamed ceiling. 0: a -E ,c, g - F.' •Z •=<' 1r RBulletin 006 Rev. F Model RFC30 (SIN RA0611) oi ® Model RFC43 (SIN RA0612) e 1...ai Model RFC49 (SIN RA0616) o Residential Flat Concealed o Sprinklers -n A Residential Flat Concealed Sprinkler engineered fora minimum design density of 0.05 gpm/ft2 with o T low GPM requirements. ` Features 1. Very low water flow requirements. 2. 1" (13mm) Total adjustment. . i. 3. Thread-On/Thread-Off or Push-On/Thread 4 Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval .... 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) 2. NYC MEA 258-93-E UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- the most dependable fire protection available,an automat- tial Sprinklers are fast response residential fusible solder is sprinkler system. link automatic sprinklers. Residential sprinklers differ from The RFC30,RFC43 and RFC49 are UL Listed Residential standard sprinklers primarilyin their responseSprinklers to be installed in the residentialportions of any time and water distribution patterns. occupancy in accordance with NFPA 13, 13R, & 13D. Model RFC30, RFC43 and RFC49 sprinklers discharge The RFC30, RFC43 and RFC49 can reduce the need for water in a hemispherical pattern below the sprinkler de- precise cutting of drop nipples. The threaded cover plate flector. Residential distribution patterns are higher and assembly can be adjusted without tools to fit accurately generally contain a finer droplet size than standard sprin- against the ceiling. The fire protection system need not be kler patterns. shut down to adjust or remove the cover plate assembly. The combination of speed of operation and high dis- Application and Installation charge pattern required for residential sprinklers has dem- The RFC30, RFC43 and RFC49, for residential installa- onstrated, in fire testing, an ability for controlling residen- tions,use a 165°F(74°C)fusible solder link in a tuning fork tial fires,and thereby providing significant evacuation time style sprinkler frame with a drop-down deflector. This as- for occupants. sembly is recessed into the ceiling and concealed by a flat The RFC30, RFC43 and RFC49 Sprinklers provide the cover plate. The cover plate is attached to the skirt, using best form of fire protection by combining an attractive ap- 135°F (57°C) ordinary temperature classification solder. pearance and 1/2" (13mm)of cover adjustment for ease of When the ceiling temperature rises, the solder holding installation. The small diameter cover plate is easily and the cover plate releases the cover allowing the deflector positively attached and blends into the ceiling,concealing to drop into position and exposing the sprinkler inside to The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 "Ir ceiling temperature. The subsequent operation of the sol- OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, der link opens the waterway and causes the deflector to RFC43 AND RFC49 CONCEALED SPRINKLERS MUST drop into position to distribute the discharging water in a BE INSTALLED ONLY WITH 135°F RATED COVERS. hemispherical pattern below the sprinkler deflector. Any Note:A leak tight 1" NPT(R1/2)sprinkler joint can be ob- adjustment of thread engagement between the cover tained with a torque of 8-18 ft-lbs(10,8-24,4 N-m). Do not plate and cup will assure that the drop-down deflector is tighten sprinklers over maximum recommended torque. It - properly located below the ceiling. The residential distri- may cause leakage or impairment of the sprinklers. bution pattern contains a finer droplet size than a standard Cover assemblies provide up to 1/2" (13mm) of adjust- sprinkler, and the pattern produces significantly higher ment. Turn the cover clockwise until the flange is in con- wall wetting. tact with the ceiling. For the push-on/thread-off option,the After a 25/8 inch diameter hole is cut in the ceiling, the cover assembly is pushed onto the cup and final adjust- sprinkler is to be installed with the Model FC Wrench. ment is made by turning the cover clockwise until the skirt When installing a sprinkler, the wrench is first positioned flange makes full contact with the ceiling. Cover removal into the sprinkler/cup assembly and around the hexagonal requires turning in the counter-clockwise direction. body of the sprinkler frame. The Wrench must bottom out In ceilings that have a plenum space above the sprinkler, against the cup in order to ensure proper, safe installation. the plenum space may have neutral or negative pressur- The sprinkler is then tightened into the pipe fitting. When ization but must not be positively pressurized. Inspect all inserting or removing the wrench from the sprinkler/cup sprinklers after installation to ensure that the gap between assembly, care should be taken to prevent damage to the cover plate and ceiling and the 4 slots in the cup are the sprinkler. DO NOT WRENCH ON ANY OTHER PART all open and free from any air flow impediment. Temperature Rating Sprinkler Cover Plate Max.Ambient Temp. 165°F/74°C 135°F/57°C 100°F/38°C Installation Data: RFC30 (SIN RA0611) Maximum Minimum Minimum Required Thread SprinklerDistance to Distance between Sprinkler Discharge Size K Factor Spacing Wall sprinklers inch(mm) ft.(m) P Flow Press. ft.(m) ft.(m) gpm(Lpm) psi(bar) 1/2"(15mm) 3.0 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 9(34.1) 9.0(0.62) 1/2"(15mm) 3.0 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 10(37.8) 11 (0.76) Note: 1 bar=100 Kpa Installation Data: RFC43 (SIN RA0612) Maximum Minimum Minimum Required Thread Sprinkler Distance to Distance between Sprinkler Discharge Size K Factor Spacing Wall sprinklers inch(mm) ft.(m) p Flow Press. ft.(m) ft.(m) gpm(Lpm) psi(bar) 1/2"(15mm) 4.3 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 12(45) 7.8(0.54) 1/2"(15mm) 4.3 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63) 1/2"(15mm) 4.3 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 9.1 (0.63) 1/2"(15mm) 4.3 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 18(68) 17.5(1.21) 1/2"(15mm) 4.3 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 21 (79) 23.8(1.64) Note: 1 bar=100 Kpa Installation Data: RFC49 (RA0616) Thread S rinkler Maximum Minimum Minimum Required p Distance to Distance between Sprinkler Discharge Size K Factor Spacing Wall sprinklers inch(mm) ft.(m) p Flow Press. ft.(m) ft.(m) gpm(Lpm) psi(bar) 1/2"(15mm) 4.9 12 x 12(3.6x3.6) 6(1.83) 8(2.43) 13(49) 7.0(0.48) 1/2"(15mm) 4.9 14 x 14(4.3x4.3) 7(2.13) 8(2.43) 13(49) 7.0(0.48) 1/2"(15mm) 4.9 16 x 16(4.9x4.9) 8(2.43) 8(2.43) 13(49) 7.0(0.48) 1/2"(15mm) 4.9 18 x 18(5.5x5.5) 9(2.74) 8(2.43) 17(64.3) 12.0(0.83) 1/2"(15mm) 4.9 20 x 20(6.0x6.0) 10(3.05) 8(2.43) 20(75.7) 16.7(1.14) Note: 1 bar= 100 Kpa FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035. 2. l Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprinklers consist of a brass cover plate and copper alloy retainer should be inspected quarterly and the sprinkler system flange allowing a'/z" cover plate adjustment. Any secure maintained in accordance with NFPA 25. Do not clean engagement between the cover plate and the cup will sprinklers with soap and water, ammonia or any other assure that the drop-down deflector is properly located cleaning fluids. Remove dust by using a soft brush or gen- below the ceiling. A plastic protective cap shall be tle vacuuming. Remove any sprinkler cover plate assem- provided and factory installed inside the sprinkler cup bly which has been painted(other than factory applied)or to protect the drop-down sprinkler deflector from dam- damaged in any way. A stock of spare sprinklers should age,which could occur during construction before the be maintained to allow quick replacement of damaged or cover plate is installed. Standard cover finish: [Chrome] operated sprinklers. Prior to installation, sprinklers should [White] [Specialty—specify]. Residential concealed be maintained in the original cartons and packaging until sprinklers shall be Reliable Model RFC30, SIN RA0611 used to minimize the potential for damage to sprinklers (Bulletin 006), Model RFC43, SIN RA0612(Bulletin 006) that would cause improper operation or non-operation. or Model RFC49, SIN RA0616(Bulletin 006). Model RFC30, RFC43 and RFC49 Residential Ordering Information Cover Plate Finishes(1) Concealed Sprinkler Specification pecify: Standard Finishes 1. Sprinkler Model Sprinklers shall be cULus Listed low flow residential con- 2. Cover Plate Finish chrome cealed sprinklers with drop-down deflector and adjust- 3. Thread-On or White able flat cover plate engineered for a minimum design Push-On Feature Special Application density of 0.05 gpm/ft2. Sprinkler frame and deflector Finishes shall be of bronze frame construction having a'/2" NPT Bright Brass thread. Thermal element shall consist of an approved Black Plating black-painted beryllium-nickel fusible solder link with Black Paint symmetric lever mechanism, maintaining a Teflon-coated OW Satin CChrhrome Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler (1)Other colors and finishes avail- able.Consult factory for details. K-factor shall be nominal 3.0(44),4.3(62.4), and 4.91 Note:Paint or any other coatings (70)having a 5/16",3/8" and 7/16"orifice. Temperature rating applied over the factory finish will shall be Ordinary 165°F(74°C); cover plate temperature void all approvals and warran rating to be 135°F(57°C). Cover plate assembly shall ties. /-x 1/2"REDUCING TEE OR ELBOW I — _ _ �II -- is-, T- -- IL -fi----'ii __T r 58.42mm]D/A _--__ HOLE IN CEILING 2/-1"[CUP -- =', ■M■ 11111 !Fill 2"[50.8mm]MAX. – L t�: FACE OF FITTING _ TO FACE OF CEILING 11 DIMENSION CEILING ������� ��,-- sem-• `. /1� ::. "[12.70mm]MAX. 7 I J COVER ADJUSTMENT fi"[4.96mm] 0 CCP COVER PLATE ASSEMBLY "(84.21mmJ DIA. '�' a SPRINKLER oocrcou yy COVER PLATE: 1/2" [12.7mm] ADJUSTMENT 3. T 1 Reliable. . . For Complete ProtectiOn Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. • Automatic sprinklers • Deluge valves • Flush automatic sprinklers • Detector check valves • Recessed automatic sprinklers • Check valves • Concealed automatic sprinklers • Electrical system • Adjustable automatic sprinklers • Sprinkler emergency cabinets • Dry automatic sprinklers • Sprinkler wrenches • Intermediate level sprinklers • Sprinkler escutcheons and guards • Open sprinklers • Inspectors test connections • Spray nozzles • Sight drains • Alarm valves • Ball drips and drum drips • Retarding chambers • Control valve seals • Dry pipe valves • Air maintenance devices • Accelerators for dry pipe valves • Air compressors • Mechanical sprinkler alarms • Pressure gaugesldentification signs • Electrical sprinkler alarm switches • Fire department connection • Water flow detectors The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co., Inc. �� Recycled - Paper (800)431 1588 Sales Offices Reliable (800)848-6051 Sales Fax Revision lines indicate updated or new data. (914)829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A 02/11 P/N 9999970261 Uponor AquaPEX°White J� X07 Submittal Information CITY Revision D: July 6, 2010OFN`IG,>�,' D Project Information ��i� J O Job Name: Location: Engineer: Date Submitted: Contractor: Part No. Ordered: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: Crosslinked polyethylene PEX-a Engel Method; PEX 5006 Standard Grade Hydrostatic 200°F(93°C)at 80 psi Ratings(PPI): 180°F(82°C)at 100 psi 73.4°F(23°C)at 160 psi 1/2", 3/4",and 1"AquaPEX®White only: 120°F(49°C)at 130 psi Linear Expansion Rate: 1.1"/10°F(12°C)/100' "t i Product`information and Application Use Uponor AquaPEX White is tubing used for hot and cold domestic potable water distribution, residential 11 fire safety and radiant heating systems containing no ferrous corrodible components or where ferrous components are isolated from the tubing. h Description Part Number LD. A C ) O.D. (B) Weight 1/4"Uponor AquaPEX White, 100-ft. coil F1040250 0.241" 0.375" 3/8" Uponor AquaPEX White,400-ft. coil 4.0 lbs. F1090375 0.350" 0.500" 20.0 lbs. 3/a" Uponor AquaPEX White, 1,000-ft. coil F1120375 0.350" 0.500" Y/2"Uponor AquaPEX White, 100-ft. coil* 44.0 lbs. F1040500 0.475" 0.625" 6.0 lbs. '/2"Uponor AquaPEX White, 300-ft. coil* F1060500 0.475" 0.625" 18.0 lbs. 1/2"Uponor AquaPEX White, 1,000-ft. coil* F1120500 0.475" 0.625" 54.0 lbs. 5/8" Uponor AquaPEX White, 300-ft. coil F1060625 0.574" 0.750" 28.0 lbs. 5/s" Uponor AquaPEX White, 1000-ft. coil F1120625 0.574" 0.750" 86.0 lbs. 3/4" Uponor AquaPEX White, 100-ft. coil* F1040750 0.671" 0.875" _ 3/4"Uponor AquaPEX White, 300-ft. coil* 10.0 lbs. _.i 3/4"Uponor AquaPEX White, 500-ft. coil* F106075010 0.671" 0.875" 34.0 lbs. 11-1_,1 , F1100750 0.671" 0.875" 54.0 lbs. 1"Uponor AquaPEX White, 100-ft.coil* F1041000 0.862" 1.125" 20.0 lbs. 1" Uponor AquaPEX White, 300-ft. coil* F1061000 0.862" 1.125" 56.0 lbs. I 1" Uponor AquaPEX White, 500-ft. coil* F1101000 0.862" 1.125" 93.0 lbs. 1�/a" Uponor AquaPEX White, 100-ft. coil F1061250 1.054" 1.375" 34.0 lbs. _ 11" Uponor AquaPEX White, 300-ft. coil F1021250 1.054" 1.375" 106.0 lbs. 11/2" Uponor AquaPEX White, 100-ft.coil F1061500 1.244" 11"Uponor AquaPEX White, 300-ft. coil 1.625" 44.0 lbs. F1021500 1.244" 1.625" 133.0 lbs. 2" Uponor AquaPEX White, 100-ft. coil F1062000 1.629" 2.125" 68.2 lbs. 2" Uponor AquaPEX White, 200 ft. coil F1052000 1.629" 2.125" 136.4 lbs. 2" Uponor AquaPEX White,300-ft.coil F1022000 1.629" 2.125" 204.6 lbs. 3"Uponor AquaPEX White, 100-ft.coil 3"Uponor AquaPEX White, 350 ft. coil F106300012 2.400" 3.125" 128.0 lbs. F1023000 2.400" 3.125" 442.OIbs. Installation Approved fittings are ProPEX®fittings'for sizes 3/s"through 2"AquaPEX. Use WIPEXTM fittings for 3"AquaPEX. Refer to the Uponor Professional Plumbing Installation Guide, Radiant Floor Heating Installation Handbook or AquaSAFETM Residential Fire Sprinkler Installation Guide for more information. Standards Codes Listings CSA B137.5;ASTM F876;ASTM IPC; UPC; *y2' 3/4", 1"UL 1821; *ULC/ORD-C 199 P; IAPMO; CSA; HUD; WARNOCK HERSEY;NSF; F877; ASTM F1960; ASTM-E84; NSPC; NPC ITS; UL; ICC; ANSI/NSF 14-and 61-certified;AWWA C9042; CAN/ULC S102.2 (U.S.: 3/4" ASTM-E119/UL 263 of Canada diameter and smaller; Canada: 1"diameter and smaller) Related Applications Contact Information PEX-a Plumbing Systems Uponor,Inc. Uponor Ltd. Radiant Heating and Cooling Systems 5925 148th Street West 2000 Argentic Rd., Plaza 1, Ste. 200 AquaSAFE Fire Safety Systems Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Phone: (800)321-4739 Phone: (888)994-7726 Fax: (952)891-2008 Fax: (800) 638-9517 www.uponor-usa.com www.uponor.ca 'ProPEX®is a registered trademark of Uponor,Inc.ProPEX'"is a trademark of Uponor Ltd. 2This listing is for 3/4"AquaPEX tubing and larger. Print Stream on Tubing Explanation UPONOR AguaPEX Brand Name PE)(5006 ASTM F2023 Testing l/A/W ASTM F876 Tubing Size(Example:'!") SDR9 Standard Dimensional Ratio of 9 t$137.5 POTABLE Potable Water Listing by CSA 130PS1120°F(49°C)UL1821 Rating i/A/W UL 1821('h",3/i"`and 1"only) ULC-ORD C199P' Canadian Rating I/A/W t)Ll$21 and C199P ASTM F876/F877/172023 ASTU Tubing ndards Listed by NSF ASTM F1960/F2080/F1807 ASTM Fitting Standards Listed by NSF IAPMAO Res 3558,3960 ICC ESR-1099 ICC Evaluation Sitivices Report ESI1-'I099 ICC EsR1529 KC Evaluation 5eMces t ESR 1529 HUD MR1269dHUD Material Release Report 1269d Will-LISTED CAN/US FS25/SDSO Warnock Horse',fisdritli for 25/50 Plenum Rating Ifi(iI)S173.4°F(23°C)/100PSI Hydrostatic Ratings from PPI in Accordance with 1110°F(82'C)/moi 200°F(93°C) ASTM F876 UPONOR PEX-a TtjoifilG Type of C (P1 X-a) UN049501272 Manufacturing Code to Au*Material Source xxxxxx3 Footage Marker in increments of 3'(throe feet) For/,-nth tubing only 2 USA,Material Type,Extruder No.,Year,Month,Day 3 Footage marking in increments of three feet(3') Table 1-1:Prim Stream Identification ProPEX•Sprinkler Calculated Equivalent Adapters and Fittings Tubing Length Uponor offers sprinkler adapter Tubing Size fittings specifically designed for Fitting Type the AquaSAFE Fire Safety system. id* 7,1 These fittings feature ProPEX Tee-Run 2' 2' connections and a standard W NPT Tee-90° 6' 6' outlet for connecting fire sprinklers. 90• Elbow 5, 6' Table'1-2 shows the required Cpling 2' 2' tubing length needed to approximate the equivalent pressure Table 1-2:Pressure Resistance resistance of the different types of (Rttingsfr'leng) Uponor ProPEX fittings. 6 Uponor www.uponor-usa.com www.uponor.ca ProPEX Lead-free (LF) Brass Fire Sprinkler Adapter Tee Uponor Submittal Information Revision A: Nov. 20, 2009 Project Xnformation' Job Name: Location: Engineer: Part No. Ordered: Contractor: Date Submitted: Manufacturer's Representative: Submitted By: Approved By: Technical Data Material C69300 Brass A Product Information and Application Use A, Awl Designed for use with 3/4"or 1"Uponor AquaPEX®tubing,the ProPEX®Lead-free Brass Fire Sprinkler Adapter Tee connects fire sprinklers to the Uponor residential �' r c/S B AquaSAFE'" Looped multipurpose fire safety system,which combines fire sprinklers 7 W t ' yr�� with a home's potable cold-water plumbing system. Use Uponor ProPEX fittings for Ar- the connections. 1/2"-14 FNPT Description` Part Number B `.Weight ProPEX LF Brass Fire SprinklerAdapter Tee, 1"PEX x 1"PEX x 1/2" FNPT LF7701010 4.09" 2.325" 0.62 lbs. i ProPEX LF Brass Fire Sprinkler Adapter Tee, 3/4"PEX x 3/4" PEX x '/2"FNPT LF7707575 3.62" 2.325" 0.64 lbs. Installation Use the appropriate Uponor ProPEX Ring for the tubing. Install the tee using the Fire Sprinkler Adapter Mounting Bracket(A7750700) and Fire Sprinkler Adapter Push-on Nut(F7000005). For more information, refer to the Uponor AquaSAFE Looped System Installation Guide. Related Products A7750700: Fire Sprinkler Adapter Mounting Bracket, 3/4"and 1" F7000005: Fire Sprinkler Adapter Push-on Nut Standards ' CAN/CSA B137.5;ASTM F877;ASTM F1960; UL 1821; ULC/ORD-C199P CodeS'� ' IPC; UPC; NSPC; IRC; IMC; NPC of Canada Listings a ANSI/NSF 14-and 61-certified; ICC ESR 1099; HUD MR 1269; IAPMO Related Applications Contact Information PEX-a Plumbing Systems Uponor,Inc. AquaSAFE Fire Safety Systems 5925 148th Street West 200oU0or Ltd. 00 Argentic Rd., Plaza 1, Ste. 200 Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Phone: (800)321-4739 Phone: (888)994-7726 Fax: (952)891-2008 Fax: (800)638-9517 www.uponor-usa.com www.uponor.ca 1ProPEX®is a registered trademark of Uponor,Inc. ProPEX""is a trademark of Uponor Ltd. uponol Fire Sprinkler Adapter Mounting Bracket Submittal Information Revision A: Nov. 17, 2009 r " ' Project Information Job Name: Part No. Ordered: Location: Date Submitted: Engineer: Submitted By: Contractor: Approved By: Manufacturer's Representative: Technical Data A t U -U_n 1050 Annealed (spheroidized)spring steel s Material: B 1:1* Lalktr Product Information and Application Use I I • Uponor's Fire Sprinkler Adapter Mounting Bracket is designed to rigidly mount • ProPEX®Lead-free Brass Fire Sprinkler Adapter Tees(LF7701010 and LF7707575) in Uponor AquaSAFETM multi-purpose residential fire sprinkler V' systems.1111) 11/4 • Part Number ' A; B` C Di Weight .f Description � , Fire Sprinkler Adapter Mounting Bracket,3/4"and 1" A7750700 2.48" 1.84" 3.16" 1.42" 0.21 lbs. Installation or eAttachquivalent. the sprinkler-mounting to he sprinkler bracket or mounting detaer ils for correct placement ter to the structure th two of bracketOs and adapters,Fad, Full Thread Screws taking into account the ceiling001type and sprinkle nm Refer to tp sprinkler model.When installing adapter tee into bracket,use Fire Sprinkler Adapter Push-on Nut(F7000005). For more information, refer tot e Uponor AquaSAFE Looped System Installation Guide. Related,Products LF7701010: ProPEX Brass Fire Adapter Tee, 1" PEX x 1" PEX x1/2" FNPT LF7707575: ProPEX Brass Fire Adapter Tee,3/4"PEX x 3/4" PEX x'/2" FNPT Standards UL1821; ULC/ORD-C199P(for use with brass sprinkler adapter tees) Codes. a _ N/A Listing`s N/A Related Applications 'Contact Information PEX- Uponor,Inc. Uponor Ltd. AquaSAFE Fireeg Safety Systems 5925 148th Street West 2000 Argentia Rd., Plaza 1, Ste. 200 Safety Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Phone: (800)321-4739 Phone: (888)994-7726 Fax: (952)891-2008 Fax: (800)638-9517 www.uponor-usa.com www.uponor.ca 1ProPEX®is a registered trademark of Uponor,Inc.ProPEX'"'is a trademark of Uponor Ltd. ProPEX°Information Fire Sprinkler Adapter Uponor Submittal Revision B: March 17, 2009 Project;Information ` Job Name: Location: Part No.Ordered: En.ineer: Date Submitted: Contractor: Manufacturer's Representative: ApprovedSubmitted By: Technical Data Material: 300 Series Stainless Steel o M1 H 0 c Product Information and Application Use Use the ProPEX®Fire Sprinkler Adapter in conjunction with the appropriate sprinkler to provide a multi-purpose residential fire � sprinkler system'. For residential applications,the system is l `' installed with the cold-potable portion of the Uponor plumbing system. Make connections with Uponor ProPEX fittings.These fittings are designed for use only with 3/4"or 1"AquaPEX° ' White tubing in the Uponor AQUASAFE®Looped System. A ` - _ a .. - `Description Pam ,,' Number; A' B ` C , 'D E Weight` ProPEX Fire Sprinkler Adapter, 3/4" PEX x -/2" FNPT Q7517550 0.75" 1.88" 2.50" 1.82" 1.41" 0.268 lbs. ProPEX Fire Sprinkler Adapter, 1" PEX x 1/2" FNPT Q7511050 0.75" 1.88" 2.50" 2.06" 1.54" 0.408 lbs. Installation` Use a ppropriate ProPEX Ring for connecting the tubing. Refer to the AquaPEX Installation Handbook or the Uponor AQUASAFE® Installation Guide for additional information. Standards CAN/CSA B137.5; ASTM F877; ASTM F 1960 Codes -, IPC; UPC; NSPC; IRC; IMC; NPC of Canada L stings' �, ANSI/NSF 14-and 61-certified; U.P. Code; ICC ESR 1099; HUD MR 1269; UL 1821; ULC/ORD- C 199 P Related Applications Contact Information PEX-a Plumbing Systems Uponor, Inc. 2000 or AQUASAFE Fire Safety Systems 5925 148`"Street West Uponor Ltd. Argentia Apple Valley, MN 55124 USA Mississauga, ONdL5N11W1aza 1CANADA 0 Phone: (800)321-4739 Phone: (888)994-7726 Fax: (952) 891-2008 Fax: (800) 638-9517 www.uponor-usa.com www.uponor.ca 1ProPEX®is a registered trademark of Uponor,Inc.ProPEX'"is a trademark of Uponor Ltd. uponor ProPEX® Fire Sprinkler Adapter Elbow Submittal Information Revision B: March 17, 2009 Project Information Job Name: Part No. Ordered: Location: Date Submitted: Engineer: Submitted By: Contractor: Manufacturer's Representative: Approved By: c Technical Data Material: 300 Series Stainless Steel , Product Information and Application Use 1 Use the ProPEX®Fire Sprinkler Adapter Elbow in conjunction with the appropriate sprinkler to provide a multipurpose residential fire sprinkler system'.The system is installed with the cold-potable portion of the { f applications. Uponor plumbing system for residential app 1 Make connections using Uponor ProPEX fittings.The i a , fittings are designed for use only with 3/a"or 1" 1x ° AquaPEX®White tubing in the Uponor AQUASAFE® ( -� �, Looped System. , = a Part . B C D E F Weight Description, .Number ProPEX Fire Sprinkler Adapter Right Elbow,3/4" PEX x'/z' FNPT Q7537550 2.25" 1.95" 1.41" 2.25" 1.95" 1.41" 0.410 lbs. ProPEX Fire Sprinkler Adapter Right Elbow, 1" PEX x 1/2" FNP Q7531050 2.63" 2.43" 1.54" 2.63" 2.43" 1.54" 0.783 lbs. ProPEX Fire Sprinkler Adapter Left Elbow,3/4" PEX x1/2"FNPT Q7547550 2.25" 1.95" 1.41" 2.25" 1.95" 1.41" 0.410 lbs. 11 ProPEX Fire Sprinkler Adapter Left Elbow, 1" PEX x 1/2" FNPT Q7541050 2.63" 2.43" 1.54" 2.63" 2.43" 1.54" 0.783 lbs. Installation Use appropriate ProPEX Ring when connecting the tubing. Refer to the AquaPEX Installation Handbook or the Uponor AQUASAFE Installation Guide for additional information. Standards CAN/CSA B137.5; ASTM F877; ASTM F1960 Codes' IPC; UPC; NSPC;IRC;IMC; NPC of Canada Listings ANSI/NSF 14-and 61-certified; ICC ESR 1099; HUD MR 1269; IAPMO 3558; UL 1821; ULC/ORD-C 199 P ' ' Related Applications Contact Information"� Uponor Ltd. 5925 148th Street West PEX-a Plumbing Systems2000 Ltd. a Rd., Plaza 1, Ste. 200 AQUASAFE Fire Safety Systems Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Phone: (800)321-4739 Phone: (888)994-7726 Fax: (952)891-2008 Fax: (800)638-9517 www.uponor-usa.com www.uponor.ca 1ProPEX®is a registered trademark of Uponor,Inc.ProPEX''"is a trademark of Uponor Ltd. , ProPEX® Ring uponor Submittal Information Revision B: April 13, 2011 Project Information Job Name: Location: Part No. Ordered: Engineer: ' Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: PEX-a (Engel Method) Density: 926 to 940 kg/m3 1 Degree of Crosslinking: 70%to 89% Product Information and Application Use Manufactured from PEX-a material,Uponor ProPEX®Rings are required to make a proper ProPEX connection.1 Red print on the rings indicates hot lines.The Y2", 3 ,�`• /a"and 1" ProPEX Ring with Stop includes a leadingedge e chamfer and stop edge. ✓ Description Part Number Length i.d. o.d. Weight ❑ ProPEX Ring,3/8" Q4690302 0.54" 0.49" 0.74" 0.005 lbs. ❑ ProPEX Ring with Stop, Yx"(red print) Q4690511 0.63" 0.63" 0.87" 0.006 lbs. ❑ ProPEX Ring with Stop, Yx" Q4690512 0.63" 0.63" 0.87" 0.006 lbs. Pr0PEX Ring,5/8" Q4680625 0.79 0.75" 1.00" 0.008 lbs. ❑ ProPEX Ring with Stop,3/4" Q4690756 0.87" 0.88" 1.13" 0.012 lbs. ❑ ProPEX Ring, 1" Q4681000 1.10" 1.13" 1.42" 0.020 lbs. ❑ ProPEX Ring with Stop, 1" Q4691000 1.10" 1.13" 1.42" ID ProPEX Ring, 1Y4" 0.020 lbs. Q4681250 1.35" 1.38" 1.66" 0.030 lbs. ❑ ProPEX Ring, 11/2" Q4681500 1.61" 1.63" 1.91" 0.040 lbs. ❑ ProPEX Ring, 2" Q4682000 1.97" 2.14" 2.61" 0.133 lbs. Installation �' Square cut the Uponor ProPEX tubing. Remove excess material.Slide the ProPEX Ring over the end of the tubing (maximum 1 When using the 1/2"ProPEX Ring with stop edge,slide the ring on (i.e.,chamfered edge first) until the end of the tubing contacts the stop over-hang) edge. Expand tubing and ring. Rotate tool a quarter turn after each expansion to prevent the formation of grooves. Remove the expansion tool and fully seat the tubing and ring against the shoulder of the fitting.You should make ProPEX connections at temperatures above 5°F/-15°C. For more information, refer to the AquaPEX®Professional Plumbing Installation Handbook,AquaSAFEr"' Fire Safety Installation Guide or the Uponor Radiant Installation Handbook. Standards ` ASTM F1960 Codes IPC; UPC; NSPC; NPC of Canada Listings UL 1821 (Yx",3/4"and 1"); ULC/ORD-C 199 P(Y2", 3/4"and 1"); HUD MR 1269; ICC ESR 1099;ANSI/NSF 14-and 61-certified Related Applications ,Contact Information PEX-a Plumbing Systems Radiant Heating and Cooling Systems Uponor,Inc. Uponor Ltd. Radiant Fire Safety Systemsling 5925 148 Street West 2000 Argentia Road, Plaza 1, Suite 200 Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Phone: (800) 321-4739 Phone: (888)994-7726 • Fax: (952)891-2008 Fax: (800) 638-9517 www.uponor-usa.corn www.uponor.ca 1ProPEX®is a registered trademark of Uponor,Inc. ProPEX`"is a trademark of Uponor Ltd. UOflO1 ProPEX° Lead-free (LF) Brass Sweat Adapter Submittal Information Revision A: Jan. 20, 2010 Project:Information'.' Job Name: Part No. Ordered: Location: _ Date Submitted: Engineer: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: C69300 Brass ?�� �rrt='' Product}Information and Application ProPEX°Lead-free Brass Sweat Adapters transition Uponor PEX tubing to copper pipe.l Adapters are approved for use in hot and cold potable water systems, hydronic radiant l , ;; heating systems and the AquaSAFETM Residential Fire Safety System. These adapters are safe for direct burial in soil. z part Ag C Weight Description Number LF4513850 1.32" 0.721" 0.50" CU 0.08 lbs. ProPEX LF Brass Sweat Adaoter.3/8" PEX x 1/2"Conner C { ProPEX LF Brass Sweat Adapter, '/z PEX x /z Copper LF4515050 1.44" 0.750" 0.50" CU 0.08 lbs. ProPEX LF Brass Sweat Adapter, '/z" PEX x 3/4"Copper LF4515075 1.63" 0.989" 0.75" CU 0.16 lbs. ProPEX LF Brass Sweat Adapter,3/4"PEX x'/z"Copper LF4517550 1.67" 1.070" 0.50" CU 0.16 lbs. ProPEX LF Brass Sweat Adapter, 3/4" PEX x 3/4"Copper* LF4517575 2.04" 1.070" 0.75" CU 0.30 lbs. r .; ProPEX LF Brass Sweat Adapter,3/4" PEX x 1"Copper LF4517510 2.17" 1.258" 1.00" CU 0.31 lbs. ProPEX LF Brass Sweat Adapter, 1" PEX x 1"Copper* LF4511010 2.40" 1.345" 1.00" CU 0.30 lbs. ProPEX LF Brass Sweat Adapter, 11/4" PEX x 11/4" Copper LF4511313 2.63" 1.640" 1.25"CU 0.50 lbs. 171 ProPEX LF Brass Sweat Adapter, 11/2" PEX x 11/2' Copper LF4511515 2.75" 1.875" 1.50"CU 0.50 lbs. I Pj ProPEX LF Brass Sweat Adapter, 2" PEX x 2" Copper LF4512020 3.53" 3.00" 2.00" CU 2.00 lbs. Installation . Use the appropriate Uponor g Installation Guidfor the ng (sold e, Radiant separately). Floor Heating Installation Handbook or AquaSAFETM Residential Fire iRefer to AquaPEX® ProfessionalPlumbing Sprinkler Installation Guide for additional information. Standards CAN/CSA B137.5; ASTM F877; ASTM F1960 Godes IPC; UPC; NSPC; NPC of Canada Listings t' ' '' HUD MR 1269; ICC ESR 1099; ANSI/NSF 14-and 61-certified; U.P. Code,Annex G; *UL 1821; *ULC/ORD C199P Related Applications . ' Contact Information PEX- Plumbing Systems Uponor,Inc. Uponor Ltd. Uponor Residential Fire Safety Systems 5925 148`h Street West 2000 Argentia Rd., Plaza 1, Ste. 200 Radiant Heating and Cooling Systems Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Snow and Ice Melting Systems Phone: (800) 321-4739 Phone: (888)994-7726 Permafrost Protection Systems Fax: (952)891-1409 Fax: (800)638-9517 Turf Conditioning Systems www.uponor-usa.com www.uponor.ca 'ProPEX®is a registered trademark of Uponor,Inc.ProPEX'"is a trademark of Uponor Ltd. ProPEX® Lead-free (LF) Brass Female Threaded Adapter UOflO1 Submittal Information Revision A: Jan. 20, 2010 Project Information' Job Name: Location: Part No. Ordered: Engineer: Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material C69300 Brass A Product Information and Application Use .rd„ ArAr'"/ 4 The ProPEX® Lead-free Brass Female Threaded Adapter connects Uponor PEX a tubing to female NPT threads.' Use these fittings in hot and cold domestic potable water systems or in any radiant heating system. One end of the adapter is manufactured with the Uponor ProPEX Fitting for connections to i���yr����' Wirsbo hePEXTM tubing or Uponor AquaPEX®tubing.The other end of the ���� A adapter connects to copper. These adapters are safe for direct burial in soil. c ✓ Description Part Numbeir A B C Weight ProPEX LF Brass Female Threaded Adapter, '/2" PEX x �/z" NPT LF4575050 1.57" 1" HEX 1/2" NPT 0.20 lbs. t E ""f ProPEX LF Brass Female Threaded Adapter, '/2" PEX x 3/4" NPT LF4575075 1.75" 13/16' HEX 3/4" NPT 0.40 lbs. r- 1 ProPEX LF Brass Female Threaded Adapter, 3/4" PEX x 3/4" NPT* LF4577575 1.87" 13/44" HEX 3/4" NPT 0.20 lbs. , ProPEX LF Brass Female Threaded Adapter, 3/4" PEX x 1" NPT LF4577510 2.21" 11/2" HEX 1" NPT 0.40 lbs. 1-.i ProPEX LF Brass Female Threaded Adapter, 1" PEX x 1" NPT LF4571010 2.44" 11/2" HEX 1" NPT 0.45 lbs. ProPEX LF Brass Female Threaded Adapter, 11/4" PEX x 11/4" NPT LF4571313 2.57" 2" HEX 11/4" NPT 1.00 lbs. { i ProPEX LF Brass Female Threaded Adapter, 1'/2" PEX x 11/2" NPT LF4571515 2.75" 21" HEX 11/2" NPT 2.20 lbs. ProPEX Brass Female Threaded Adapter, 2" PEX x 2" NPT LF4572020 3.53" 3" HEX 2" NPT 2.20 lbs. Installation ProPEX Tool and ProPEX Rings(sold separately) are required for connecting the PEX tubing. For more information, refer to the AquaPEX Professional Plumbing Installation Guide or the Radiant Floor Heating Installation Handbook. Standards CAN/CSA B137.5; ASTM F877; ASTM F1960 Codes IPC; UPC; NSPC; NPC of Canada Listings` ANSI/NSF 14- and 61-certified; ICC ESR 1099; HUD MR 1269; U.P. Code,Annex G; *UL 1821; *ULC/ORD C199P Related Applications Contact Information PEX-a Plumbing Systems Uponor,Inc. Uponor Ltd. Radiant Heating and Cooling Systems 5925 148th Street West Snow and Ice Melting Systems 2000 Argentic Rd., Plaza 1, Ste. 200 Permafrost Protection Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1W1 CANADA Turf tiPning Systems Phone: (800) 321-4739 Phone: (888)994-7726 Fax: (952)891-1409 Fax: (800) 638-9517 www.uponor-usa.com www.uponor.ca 'ProPEX®is a registered trademark of Uponor,Inc.ProPEX'"is a trademark of Uponor Ltd. uponor ProPEX® Lead-free (LF) Brass Male Threaded Adapter Submittal Information Revision A: Jan. 28, 2010 Project Information Job Name: Part No. Ordered: Location: Date Submitted: Engineer: Submitted By: Contractor: Manufacturer's Representative: Approved By: Technical Data `. Material: C69300 Brass yy,tr,® Product Information and Application Use ProPEX® Lead-free Male Threaded Adapters connect Uponor PEX tubing to male 0!""LifirwaVIU, Or t NPT threads.1 These adapters are safe for direct burial in soil. ?artA` B C Weight . V Description ' , ! ,° , Number r17:1 ProPEX LF Brass Male Threaded Adapter,3/8" PEX x 1/z" NPT LF4523850 1.62" 7/8" HEX '/z' NPT 0.11 lbs. ....,_ ProPEX LF Brass Male Threaded Adapter, 1/2" PEX x'/z" NPT LF4525050 1.73" 7/s" HEX 1/2" NPT 0.32 lbs. r- ProPEX LF Brass Male Threaded Adapter, 1/2" PEX x 3/4" NPT LF4525075 1.78" 11/8" HEX 3/4" NPT 0.18 lbs. ProPEX LF Brass Male Threaded Adapter, 3/4" PEX x 3/4" NPT* LF4527575 2.02" 11/8" HEX 3/4" NPT 0.20 lbs. ProPEX LF Brass Male Threaded Adapter,3/4" PEX x 1" NPT* LF4527510 2.22" 13/8" HEX 1" NPT 0.35 lbs. ProPEX LF Brass Male Threaded Adapter, 1" PEX x 3/4" NPT LF4521075 2.25" 11/4" HEX 3/4" NPT 0.30 lbs. ProPEX LF Brass Male Threaded Adapter, 1" PEX x 1" NPT* LF4521010 2.46" 13/e" HEX 1" NPT 0.44 lbs. ProPEX LF Brass Male Threaded Adapter, 11/4" PEX x 11/4" NPT LF4521313 2.72" 13/4" HEX 11/4" NPT 0.75 lbs. . ProPEX LF Brass Male Threaded Adapter, 11/2" PEX x 11/2" NPT LF4521515 3.00" 21/4" HEX 11/2" NPT 0.80 lbs. ProPEX Brass Male Threaded Adapter, 2" PEX x 2' NPT LF4522020 3.86" 21/2" HEX 2" NPT 1.90 lbs. installation , ProPEX Tool and ProPEX Rings(sold separately)are required for connecting the PEX tubing. Refer to the AquaPEX® Professional Plumbing Installation Guide or Radiant Floor Heating Installation Handbook for additional information. Standards Jr CAN/CSA B137.5; ASTM F877; ASTM F1960 Codes IPC; UPC; NSPC; NPC of Canada Listing$ f ANSI/NSF 14-and 61-certified; HUD MR 1269; ICC ESR 1099; IAPMO 3558; U.P. Code,Annex G; *UL 1821; *ULC/ORD C199P Related Applications Contact Information Uponor, Inc. Uponor Ltd. Radia PlumbingHeainSystems 2000 Argentia Rd., Plaza 1, Ste. 200 Radiant Heating and Cooling Systems 5925 148`h Street West 9 Snow and Ice Melting Systems Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Permafrost Protection Systems Phone: (800) 321-4739 Phone: (888)994-7726 Turf Conditioning Systems Fax: (952) 891-1409 Fax: (800) 638-9517 onor.ca www.uponor-usa.com www.0 P 1ProPEX®is a registered trademark of Uponor,Inc.ProPEX'm is a trademark of Uponor Ltd. • Pr0PEX® Lead-free (IF) Brass Coupling uponor Submittal Information Revision A: Jan. 28, 2010 Project Information Job Name: Location: Part No. Ordered: Engineer: Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data A Material C69300 Brass Product Information and Application Use eirAdrIrAirArdir.f ProPEX®Lead-free Brass Couplings are available for use in hot and systems.1 Also approvedB cold domestic potable water for use in any radiant heating system. The coupling features the Uponor ProPEX Fitting for connections to Wirsbo hePEXTM tubing or Uponor r�f�f�'llir �*drA/�j'd* AquaPEX®tubing. Couplings are safe for direct burial in soil. A'' Description Part Number A B CD Weight ProPEX LF Brass Coupling, 3/8" PEX x 1/2" PEX LF4543850 1.42" 0.740" 0.398" 0.280" 0.05 1 ProPEX LF Brass Coupling, Y2" PEX x V2" PEX* LF4545050 1.54" 0.740" 0.398" N/A 0.07 ProPEX LF Brass Coupling, 3/4" PEX x 3/4" PEX* LF4547575 2.02" 1.187" 0.595" N/A 0.13 ProPEX LF Brass Coupling, 3/4" PEX x 1" PEX* LF4547510 2.25" 1.345" 0.795" 0.595" 0.16 ProPEX LF Brass Coupling, 1" PEX x 1"PEX* LF4541010 2.49" 1.345" 0.818" N/A 0.20 Installation ProPEX Tool and ProPEX Rings(sold separately)are required for connecting the PEX tubing. Use the appropriately sized Uponor ProPEX Ring for tubing connections. For more information, refer to the AquaPEX Professional Plumbing Installation Guide,the AquaSAFETM Residential Fire Sprinkler Installation Guide or the Radiant Floor Heating Installation Handbook. Standards CAN/CSA 8137.5; ASTM F877; ASTM F1960 Codes IPC; UPC; NSPC; NPC of Canada Listings; IAMPO 3558; HUD MR 1269; ICC ESR 1099; NSF 14-and 61-certified; U.P. Code,Annex G; *UL 1821; *ULC/ORD C199P Related Applications Contact Information PEX-a Plumbing Systems Uponor, Inc. Uponor Ltd. Uponor Residential Fire Safety Systems 5925 148th Street West 2000 Argentia Rd., Plaza 1, Ste. 200 Radiant Heating and Cooling Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1W1 CANADA Snow and Ice Melting Systems Phone: (800) 321-4739 Phone: (888)994-7726 Permafrost Protection Systems Fax: (952) 891-2008 Fax: (800)638-9517 Turf Conditioning Systems www.uponor-usa.com www.uponor.ca 1ProPEX®is a registered trademark of Uponor,Inc. ProPEX-is a trademark of Uponor Ltd. l . . uponol ProPEX® Brass Elbow Submittal Information Revision B: March 17, 2009 Project Information Job Name: Location: Part No.Ordered: Engineer: Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: B16 Copper Alloy UNS C36000 r tor,noreesersawdro,ae Are At Product Information and Application Use ,, The brass ProPEX®Elbow is available for use in hot and cold ,' domestic potable water systems,and in the AQUASAFE® Residential -- 1 50 Fire Safety systems. Also approved for use in any hydronic heating t and AquaPEX® plumbing systems,each end of the elbow is 4 manufactured with the ProPEX fitting for connections to hePEXTM or any AquaPEX tubing. +/v Description Part Number A s ' B C Weight ProPEX Brass Elbow, 1/2" PEX x 1/2" PEX* Q4710500 1.45" 1.48" 0.500" 0.10 lbs. ProPEX Brass Elbow, 5/s" PEX x 5/8" PEX Q4710625 1.77" 1.57" 0.625" 0.15 lbs. 1. ProPEX Brass Elbow, 3/4" PEX x 3/4" PEX* Q4710750 2.04" 1.75" 0.750" 0.20 lbs. ProPEX Brass Elbow, 1" PEX x 1" PEX* Q4711000 2.61" 2.28" 1.000" 0.30 lbs. r ProPEX Brass Elbow, 2" PEX x 2" PEX Q4712000 4.66" 4.36" 2.000" 2.20 lbs. Installation Use appropriate ProPEX Ring for connecting the tubing. Refer to the AquaPEX Installation Handbook,the Radiant Floor Installation Handbook or the Uponor AQUASAFE®Installation Guide for additional information. Standards CAN/CSA B137.5; ASTM F877; ASTM F 1960 Codes IPC; UPC; NSPC; NPC of Canada Listings ANSI/NSF 14-and 61-certified; U.P. Code; ICC ESR 1099; HUD MR 1269; *UL 1821; *ULC/ORD C199P Related Applications Contact Information ' PEX-a Plumbing Systems Uponor,Inc. Uponor Ltd. AQUASAFE Fire Safety Systems 5925 148`h Street West 2000 Argentia Rd., Plaza 1, Ste. 200 Uponor Radiant Floor heating Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1W1 CANADA Phone: (800) 321-4739 Phone: (888)994-7726 Fax: (952) 891-2008 Fax: (800)638-9517 www.uponor-usa.com www.uponor.ca 1ProPEX®is a registered trademark of Uponor,Inc.ProPEX'"is a trademark of Uponor Ltd. ProPEX® Lead-free (LF) Brass Tee uponor Submittal Information Revision B: Jan. 28, 2010 Project Information • Job Name: Location: Part No. Ordered: Engineer: Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: C69300 Brass Product Information and Application Use r441 w Uponor's ProPEX® Lead-free Brass Tees are ideal for use in hot and cold domestic potable water systems.' This product is approved for use in the AquaSAFETM Residential Fire Safety System. Also approved for any hydronic heating system application. Each end of the ProPEX LF Brass Tee is manufactured with the Uponor ProPEX Fitting for connections to Wirsbo hePEXTM or Uponor AquaPEX®tubing.This product is safe for direct burial in soil. ✓ ' Description Part Number Length Width Weight ProPEX LF Brass Tee, 1/2" PEX x 1/2" PEX x 1/2" PEX LF4705050 2.52" 1.45" 0.20 lbs. ProPEX LF Brass Tee, 3/4" PEX x 3/4" PEX x 3/4" PEX LF4707575 3.27" 1.93" 0.40 lbs. ProPEX LF Brass Tee, 1" PEX x 1" PEX x 1" PEX LF4701010 4.09" 2.42" 0.40 lbs. Installation ProPEX Tool and ProPEX Rings (sold separately) are required for connecting the PEX tubing. Do not solder within 18 inches of the ProPEX connection. Refer to the AquaPEX Professional Plumbing Installation Guide,AquaSAFE Homeowner Handbook or Radiant Floor Heating Installation Handbook for additional information. Standards CSA B137.5; ASTM F877; ASTM F1960 CodesK , IPC; UPC; NSPC; NPC of Canada Listings IAPMO 3558; ANSI/NSF 14-and 61-certified; HUD MR 1269; ICC ESR 1099; UL 1821; ULC/ORD C 199P; U.P. Code,Annex G Related Applications Contact Information PEX-a Plumbing Systems Uponor, Inc. Uponor Ltd. Uponor Residential Fire Safety Systems 5925 148th Street West 2000 Argentia Rd., Plaza 1, Ste. 200 Radiant Heating and Cooling Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1W1 CANADA Phone: (800) 321-4739 Phone: (888) 994-7726 Fax: (952) 891-2008 Fax: (800) 638-9517 www.uponor-usa.com www.uponor.ca IProPEX®is a registered trademark of Uponor,Inc. ProPEX'"'is a trademark of Uponor Ltd. uponor ProPEX® Lead-free (LF) Brass Reducing Tee Submittal Information Revision B: Jan. 28, 2010 ProjectInformation Job Name: Location: Part No. Ordered: Engineer: Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: C69300 Brass A Product Information and Application Use NS Uponor's ProPEX®LF Brass Reducing Tee makes diverting connections 45.4-41021,-. for Uponor PEX tubing in supply and return mains.'This product is available for use in hot and cold domestic potable water systems, in any hydronic heating system and in the AquaSAFETM Residential Fire B '0"Mnitir I' A 'mega� Safety System. Uponor manufactures each end of the tee with the ProPEX Fitting for easy connections to Wirsbo hePEXTM or Uponor j AquaPEX®tubing.This product is safe for direct burial in soil. p i Note: Branch size is listed last in the part description. V Description part Number A `„ r B Weight ProPEX LF Brass Reducing Tee, 3/4" PEX x 3/4" PEX x '/2" PEX LF4707550 3.27" 1.69" 0.40 lbs. ProPEX LF Brass Reducing Tee, 3/4" PEX x 3/4" PEX x 1" PEX LF4707710 3.62" 2.42" 0.50 lbs. ProPEX LF Brass Reducing Tee, 1" PEX x 3/4" PEX x 3/4" PEX LF4701775 3.86" 2.18" 0.30 lbs. ProPEX LF Brass Reducing Tee, 1" PEX x /4" PEX x 1" PEX LF4701751 3.86" 2.42" 0.40 lbs. ProPEX LF Brass Reducing Tee, 1" PEX x 1" PEX x 1/2" PEX LF4701150 4.09" 1.95" 0.40 lbs. ProPEX LF Brass Reducing Tee, 1" PEX x 1" PEX x 3/4" PEX LF4701175 4.09" 2.18" 0.40 lbs. installation ProPEX Tool and ProPEX Rings(sold separately) are required for connecting PEX tubing. Refer to the AquaPEX Professional Plumbing Installation Guide,the AquaSAFE Residential Fire Sprinkler Installation Guide or the Radiant Floor Heating Installation Handbook for additional information. Standards CAN/CSA B137.5; ASTM F877; ASTM F1960 Codes IPC; UPC; NSPC; NPC of Canada Listings .„ IAPMO 3558; ANSI/NSF 14-and 61-certified; HUD MR 1269; ICC ESR 1099; UL 1821; ULC/ORD C 199P; U.P. Code,Annex G Related Applications ' Contact Information PEX-a Plumbing Systems Uponor, Inc. Uponor Ltd. Uponor Residential Fire Safety Systems 5925 148th Street West 2000 Argentia Rd., Plaza 1, Ste. 200 Radiant Heating and Cooling Systems Apple Valley, MN 55124 USA Mississauga,ON L5N 1W1 CANADA Snow and Ice Melting Systems Phone: (800) 321-4739 Phone: (888)994-7726 Permafrost Protection Systems Fax: (952) 891-2008 Fax: (800) 638-9517 Turf Conditioning Systems www.uponor-usa.com www.uponor.ca 'ProPEX®is a registered trademark of Uponor,Inc.ProPEX'"is a trademark of Uponor Ltd. uponor 1" Branch Manifold with 1/2" ProPEX® Lead-free (LF) Outlets Submittal Information Revision A: Jan. 28, 2010 Project Information • Job Name: Location: Part No. Ordered: Engineer: Date Submitted: Contractor: Submitted By: Manufacturer's Representative: Approved By: Technical Data Material: Type L Copper; C69300 Brass Maximum Temperature(no pressure): 320°F(160°C) A Maximum Working Temperature/Pressure: 210°F at 150 psi (99°C at 10 bar) Maximum Flow Rate at 5 fps: 12.8 gpm Maximum Flow Rate at 8 fps: 20.5 gpm Product Information and Application Use The Uponor 1" Copper Branch Manifold with 1/2" ProPEX®Lead-free outlets is used for hot and cold domestic potable water distribution systems.' The manifold has a 1"copper sweat fitting adapter supply connection.All outlets are configured with 1/2" ProPEX Lead-free brass connections. V. Description Part A B CD Weight C 1" Branch Manifold with 1/2" ProPEX LF outlets,4 outlets LF2801050 8.95" 2.40" 1.50" 1/2" 0.80 lbs. 1-7 1" Branch Manifold with 1/2" ProPEX LF outlets, 6 outlets LF2811050 11.95" 2.40" 1.50" 1/2" 1.10 lbs. 1" Branch Manifold with 1/2" ProPEX LF outlets, 8 outlets LF2821050 14.95" 2.40" 1.50" 1/2" 1.40 lbs. 1" Branch Manifold with 1/2" ProPEX LF outlets, 10 outlets LF2831050 17.95" 2.40" 1.50" 1/2" 1.70 lbs. 1 1" Branch Manifold with 1/2" ProPEX LF outlets, 12 outlets LF2841050 20.95" 2.40" 1.50" 1/2" 1.90 lbs. Installation Use any product designed to mount 1" copper pipe as a mounting bracket. Any bend within 6 inches of the ProPEX connection to the manifold requires the use of a Tube Talon (F7050750) or Bend Support(A5110500 and A5150500). Refer to the AquaPEX® Professional Plumbing Installation Guide or the AquaSAFETM Residential Fire Sprinkler Installation Guide for additional information. Standards CAN/CSA B137.5; ASTM F877; ASTM F1960 Codes IPC; UPC; NSPC;NPC of Canada Listings UL 1821; ULC/ORD - C 199P; ICC ESR 1099; ANSI/NSF 14-and 61-certified; IAPMO; U.P. Code,Annex G Related Applications Contact Information PEX-a Plumbing Systems Uponor, Inc. Uponor Ltd. Uponor Residential Fire Safety Systems 5925 1481'Street West 2000 Argentia Rd., Plaza 1, Ste. 200 Radiant Heating and Cooling Systems Apple Valley, MN 55124 USA Mississauga, ON L5N 1W1 CANADA Phone: (800) 321-4739 Phone: (888)994-7726 Fax: (952) 891-2008 Fax: (800) 638-9517 www.uponor-usa.com www.uponor.ca 'ProPEX®is a registered trademark of Uponor,Inc. ProPEX'm is a trademark of Uponor Ltd.