Report (3) fr Oc (e6 sw• � ,.. RECEIVED ? AFP Systems,Inc. Automatic Fire Protection MAR 3 0 2.016 19435 SW 129th Avenue TIGARD Tualatin,OR. 97062 CITY iy OF TIF,�AT�D SYSTEM'S f (503)692-9284 BUILDINGDIVISION �9F (503)692-1186 fax PRa Submittal Project Name: Greenburg Road Apartments 9550 SW Greenburg Rd. Tigard, OR For Evergreen Builders, Inc. 7420 SW Hunziker Rd. Suite D Tigard, OR 97223 OFFICE COPY it/ �-- AFP Systems,Inc. V)„. Y Automatic Fire Protection 7 o 19435 SW 129th Avenue • Tualatin,OR. 97062 SYSTEMS (503)692-9284 (503)692-1186 fax Table of Contents A. Sprinkler Heads 1. Tyco TY2234 White Recessed Pendent /4.9 K-Factor /'/2"NPT/ 155° 2. Tyco TY1334 White Recessed Horizontal Sidewall / 4.2 K-Factor /'/2"NPT/ 155° 3. Tyco TY2131 Brass Uprights /4.2 K-Factor /'/2"NPT/200° 4. Tyco TY3335 Chrome Dry Horizontal Sidewall/5.6 K-Factor /'/2"NPT/ 155° 5. Tyco TY3235 Chrome Dry Pendent/5.6 K-Factor/'/2"NPT/ 155° B. Pipe - CPVC Pipe and Fittings-Tyco BlazeMaster - Steel Pipe Mega-Flow- Wheatland Pipe C. Valves - Dry Pipe Valve-Tyco DPV-1 &Automatic Air Maintenance Device - Grooved Butterfly Valve—Tyco BFV-N - Grooved Check Valve—Tyco CV-1F D. Electrical Devices - Waterflow Switch—Potter Electric - PS40 Pressure Switch—Potter Electric - PS 10 Pressure Switch—Potter Electric - Electric Bell—Potter Electric y � E. Hangers - CPVC Hangers: B-Line Figures-28M&23 - Ring Hangers: B-Line Fig.200 - Wood Sammy's GST-20&SWG 25-380 F. Sway Bracing - Fig. 1001 Tolco Fast Clamp - Fig.4L Tolco Pipe Clamp for Sway Bracing - Fig.980 Tolco No Thread Swivel Sway Brace Attachment r r ficoWorldwide ontacts www•tyco-fire.com Fire Protection C Products RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Pendent Wet Pipe and Dry Pipe Systems General Escutcheon reduces the accuracy to which the pipe drops to the sprinklers Description must be cut. The Series LFII Residential Sprinklers The TYCO RAPID RESPONSE have been designed with heat sensi- j`{ Series LFII Residential Pendent tivity and water distribution charac- and Recessed Pendent Sprinklers teristics proven tohelp in the control4 Li (TY2234) are decorative, fast of residential fires and to improve the response, frangible bulb sprinklers chance for occupants to escape or be designed for use in residential occu- evacuated. , pancies such as homes, apart- ments, dormitories,and hotels. When Dry Pipe System Application aesthetics and optimized flow charac- The Series LFII Residential Pendent teristics are the major consideration, and Recessed Pendent Sprinklers the Series LFII Residential Sprinklers offers a laboratory approved option (TY2234)should be the first choice. for designing dry pipe residential Sprinkler The Series LFII Residential Sprinklers sprinkler systems, whereas, most are intended for use in theresidential sprinklers are laboratory Identification following approved for wet systems only. scenarios: Number (SIN) • wet and dry pipe residential sprin Through extensive testing,it has been determined that the number of design TY2234 kler systems for one-and two-family sprinklers(hydraulic design area)for dwellings and mobile homes per the SeriesLFII Residential Pendent NFPA 13D and Recessed Pendent Sprinklers Technical • wet and dry pipe residential sprin (TY2234) need not be increased kler systems for residential occu- over the number of design sprinklers Data pancies up to and including four (hydraulic design area) as specified stories in height per NFPA 13R for wet pipe sprinkler systems, as is Approvals accustomed for area s• wet and dry pipe sprinkler systems systems d s gn d peer NFPA 13rinkler dry Listed pe systems with wet pipe and for the residential portions of any Consequently, the Series LFII CUL Listed for use only with wet pipe occupancy per NFPA 13 Residential Sprinklers offer the systems The recessed version of the Series features of non-water filled pipe in LFII Residential Sprinklers is intended addition to not having to increase the NSF Certified to NSF/ANSI 61 for use in areas with finished ceilings. number of design sprinklers(hydraulic For details on these approvals, refer It employs a two-piece Style 20 design area)for systems designed to to the Design Criteria section. Recessed Escutcheon.The Recessed NFPA 13, 13D, or 13R. Escutcheon provides 1/4 inch(6,4 mm) Maximum Working Pressure of recessed adjustment or up to 1/2 NOTICE 175 psi(12,1 bar) inch (12,7 mm) of total adjustment from the flush ceiling position. The The Series LFII Residential Pendent and Discharge Coefficient adjustment provided by the Recessed Recessed Pendent Sprinklers(TY2234) K=4.9 GPM/psis/2(70,6 LPM/bar1/2) described herein must be installed and Temperature Rating maintained in compliance with this 155°F(68°C)or 175°F(79°C) document and the applicable stan- IMPORTANT dards of the National Fire Protection Finishes Always refer to Technical Data Association, in addition to the stan- Natural Brass Sheet TFP700 for the "INSTALLER dards of any authorities having jurisdic- Pure or Signal White WARNING" that provides cautions tion. Failure to do so may impair the Chrome Plated with respect to handling and instal- performance of these devices. Physical Characteristics lation of sprinkler systems and The owner is responsible for main- Frame Brass components.Improper handling and Button Copper installation can permanently damage taming their fire protection system and SealingAssembl devices in proper operating condi- Y Beryllium a sprinkler system or its components tion. Contact the installingcontractor Bulb(3 mm) Nickel w/TEFLON and cause the sprinkler to fail to Glass operate in a fire situation or cause it or sprinkler manufacturer with Compression Screw Bronze any questions. Deflector Bronze to operate prematurely. Ejection Spring Stainless Steel • Page 1 of 6 FEBRUARY 2014 TFP400 1 r TFP400 Page 2 of 6 7/16"(11,1 mm) 1/2„ ESCUTCHEON NOMINAL PLATE SEATING 2-7/8"DIA. Components: MAKE-IN NPT SURFACE (73,0 mm) 1 - Frame — 2 - Button 3 - Sealing Assembly 1 y 4 - Bulb a 5 Compression 2 2-1/4„ 1___�� Screw ��1 1 � j�_�r (57,2 mm) ���- 6 Deflector* 3 r IL t - i 1, 4 1 I 1-5/8" STYLE 20 (41,3 mm) WRENCH ` RECESSED FLATS 5 ;�, l ESCUTCHEON *Temperature `.` rating is 6* 0 indicated on Deflector. CROSS SECTION PENDENT RECESSED PENDENT FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) 2-7/8"DIA. _ G- r— (73,0 mm) 7/16±1/8" 1/2"(12,7 mm) (11,1±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) WRECESS r (57,2 mm) (END"A" USED FACE OF FOR TY2234) SPRINKLER MOUNTING // RENCH FITTING PLATE FIGURE 3 W-TYPE 6 i-- whit r SPRINKLER WRENCH -m i ' INWRENCH MOUNTING 1/8„ RECESS SURFACE 11 (3,2 mm) 1-3/8"(34,9 mm) iir CLOSURE TY2234 1-1/8"(28,6 mm) FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE L RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER (TY2234) PUSH WRENCH IN TO ENSURE Residential Sprinkler Design Guide ENGAGEMENT Operation When conditions exist that are WITH SPRINKLER outside the scope of the provided WRENCHING AREA eThe glass bulb contains a at.d that criteria, refer to the Residential FIGURE 4 rated when exposed is reached,o heat.When Sprinkler Design Guide TFP490 for W-TYPE 7 RECESSED theflexpands temperatureuf icier yto shatter the the manufacturer's recommendations SPRINKLER WRENCH glass sufficiently rinkle the that may be acceptable to the local bulb, allowing the sprinkler to activate and flow water. authority having jurisdiction. Ceiling Types Smooth flat horizontal, or beamed, or System Types sloped, in accordance with the 2013 Design Per the UL Listing, wet pipe and dry Edition of NFPA 13D, 13R, or 13 as pipe systems may be utilized. Per the applicable. Criteria C-UL Listing, only wet pipe systems may be utilized. Hydraulic Design The TYCO RAPID RESPONSE Refer to Technical Data Sheet TFP485 (NFPA 13D and 13R) Series LFII Residential Pendent for the use of residential sprinklers in For systems designed to NFPA and Recessed Pendent Sprinklers residential dry pipe systems. 13D or NFPA 13R, the minimum (TY2234)are UL and C-UL Listed for required sprinkler flow rates are installation in accordance with this section. 4 � TFP4OO Page 3 of 6 given in Tables A and B as a func- Installation Step C. Tighten the sprinkler into the tion of temperature rating and the sprinkler fitting using only the W-Type 7 maximum allowable coverage areas. The TYCO RAPID RESPONSE Recessed Sprinkler Wrench(Figure 4). The sprinkler flow rate is the minimum Series LFII Residential Pendent With reference to Figure 1, apply the required discharge from each of the Pp Y and Recessed Pendent Sprinklers total number of"design sprinklers"as W-Type 7 Recessed Sprinkler Wrench specified in NFPA 13D or NFPA 13R. (TY2234) must be installed in accor- to the sprinkler wrench flats. The number of "design sprinklers" dance with this section: Step D. After the ceiling has been specified in NFPA 13D and 13R for wet installed or the finish coat has been pipe systems is to be applied when General Instructions applied, slide on the Style 20 Closure designing dry pipe systems. Do not install any bulb type sprin- over the Series LFII Residential kler if the bulb is cracked or there is a Sprinkler and push the Closure over the Hydraulic Design loss of liquid from the bulb.With the Mounting Plate until its flange comes in (NFPA 13) sprinkler held horizontally, a small air contact with the ceiling. For systems designed to NFPA 13, bubble should be present.The diam- the number of design sprinklers is eter of the air bubble is approximately to be the four most hydraulically 1/16 inch(1,6 mm). demanding sprinklers.The minimum A leak-tight 1/2 inch NPT sprinkler required discharge from each of the four sprinklers is to be the greater of joint should be obtained by applying the following: a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher • The flow rates given in Tables A levels of torque can distort the sprin- or B as a function of temperature kler Inlet with consequent leakage or rating and the maximum allowable impairment of the sprinkler. coverage area. Do not attempt to compensate • A minimum discharge of 0.1 gpm/ft2 for insufficient adjustment in an over the "design area" comprised Escutcheon Plate by under- or over- of the four most hydraulically tightening the sprinkler. Re-adjust the demanding sprinklers for actual position of the sprinkler fitting to suit. coverage areas protected by the four sprinklers. Series LFII Residential Pendent The number of "design sprinklers" Sprinklers specified in NFPA 13 for wet pipe The Series LFII Residential Pendent pe Sprinklers must be installed in accor- systems is to be applied when dance with the following instructions. designing dry pipe systems. Step 1. Install pendent sprinklers in Dry Pipe System Water Delivery the pendent position with the deflector When using the Series LFII Residential parallel to the ceiling. Sprinklers(TY2234)in dry pipe sprin- Step 2. With pipe thread sealant kler systems, the time for water applied to the pipe threads, hand- delivery must not exceed 15 seconds tighten the sprinkler into the sprinkler for the most remote operating fitting. sprinkler. Step 3. Tighten the sprinkler into Obstruction to Water Distribution the sprinkler fitting using only the Sprinklers are to be located in accor- W-Type 6 Sprinkler Wrench (Figure dance with the obstruction rules 3). With reference to Figure 1, apply of NFPA 13D, 13R, and 13 as appli- the W-Type 6 Sprinkler Wrench to the cable for residential sprinklers as wrench flats. well as with the obstruction criteria Series LFII Residential Recessed described within the Technical Data Pendent Sprinklers Sheet TFP490. The Series LFII Residential Recessed Operational Sensitivity Pendent Sprinklers must be installed Sprinklers are to be installed with a in accordance with the following deflector-to-ceiling distance of 1-1/4 to instructions. 4 inches. Step A. Install recessed pendent sprinklers in the pendent position with Sprinkler Spacing the deflector parallel to the ceiling. The minimum spacing between sprin Step B. After installin the Stylklers is 8 feet(2,4 m). The maximum 9 y e 20 spacing between sprinklers cannot Mounting Plate over the sprinkler exceed the length of the coverage threads and with pipe thread sealant area(Table A or B)being hydraulically applied to the pipe threads, hand- calculated(e.g.,maximum 12 feet for a tighten the sprinkler into the sprinkler 12 ft.x 12 ft.coverage area, or 20 feet fitting. for a 20 ft.x 20 ft. coverage area). , TFP400 Page 4 of 6 WET PIPE SYSTEM Minimum Flow and Residual Pressure(b,c) Max. Ordinary Temp.Rating Intermediate Temp.Rating Coverage 155°F(68°C) 175°F(79°C) Minimum Area(a) Deflector to Installation Spacing Ft.x Ft. Flow Pressure Flow Pressure Ceiling Type Ft. (m x m) GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings lig 1-1/4o 14 x 14 13 7.0 13 7.0 4 inches Recessed (4,3 x 4,3) (49,2) (0,48) (49,2) (0,48) using Style 20 Beamed Escutcheon or 8 16 x 16 13 7.0 13 7.0 Ceilings per (4,9 x 4,9) (49,2) (0,48) (49,2) (0,48) NFPA 13D non recessed (2,4) 18 x 18 17 12.0 17 12.0 or 13R per NFPA or 13 D (5,5 x 5,5) (64,3) (0,83) (64,3) (04 ,83) nchesobelow 20 x 20 20 16.7 20 16.7 bottom of (6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam. (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flow and Residual Pressure(b,c) Coverage Ordinary Temp.Rating Intermediate Temp.Rating Minimum Area(a) 155°F(68°C) 175°F(79°C) Deflector to Installation Spacing Ft.x Ft. Flow Pressure Flow Pressure Ceiling Type Ft. (m x m) GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 13 7.0 13 7.0 Smooth (3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings 1-1/4 to 14 x 14 14 8.2 14 8.2 4 inches Recessed (4,3 x 4,3) (53,0) (0,57) (53,0) (0,57) using Style 20 16 x 16 15 9.4 15 9,4 Beamed Escutcheon or 8 (4,9 x 4,9) (56,8) (0,65) (56,8) (0,65) Ceilings per NFPA 13D non-recessed (2,4) per NFPA 13D, 18 x 18 18 13.5 18 13.5 or 13R,or13 (5,5 x 5,5) (68,1) (0,93) (68,1) (0,93) nchesobelo/w 20 x 20 21 18.4 21 18.4 bottom beam of (6,1 x 6,1) (79,5) (1,27) (79,5) (1,27) (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP400 Page 5 of 6 Care and Automatic sprinkler systems are recommended to be inspected, Maintenance tested, and maintained by a qualified Inspection Service in accordance with The TYCO RAPID RESPONSE Series local requirements and/or national LFII Residential Pendent and Recessed codes. Pendent Sprinklers(TY2234) must be maintained and serviced in accordance Limited with this section: Before closing a fire protection system Warranty main control valve for maintenance work on the fire protection system that For warranty terms and conditions, it controls, permission to shut down visit www.tyco-fire.com. the affected fire protection system must be obtained from the proper Ordering authorities and notify all personnel who may be affected by this action. Procedure Absence of the outer piece of an escutcheon, which is used to cover Contact your local distributor for a clearance hole, can delay sprinkler availability. When placing an order, operation in a fire situation. indicate the full product name and Part The owner must assure that the Number(P/N). sprinklers are not used for hanging Sprinkler Assembly any objects and that the sprinklers Specify: Series LFII(TY2234), K=4.9, are only cleaned by means of gently Residential Pendent Sprinkler, dusting with a feather duster; other- (specify)temperature rating, (specify) wise, non-operation in the event of finish, P/N (specify): a fire or inadvertent operation may 155°F(68°C) result. Natural Brass P/N 51-201-1-155 Sprinklers which are found to be Pure White(RAL 9010)* P/N 51-201-3-155 leaking or exhibiting visible signs of Sig corrosion must be replaced. chromenalWhite Plated(RAL 9003) P/N 51-201-4-155 P/N 51-201-9-155 175°F(79°C) Automatic sprinklers must never be Natural Brass P/N 51-201-1-175 painted, plated, coated, or other- Pure White(RAL 9010)* P/N 51-201-3-175 wise altered after leaving the factory. Signal White(RAL 9003) P/N 51-201-4-175 Modified sprinklers must be replaced. Chrome Plated P/N 51-201-9-175 Sprinklers that have been exposed to *Eastern Hemisphere sales only corrosive products of combustion, but Recessed Escutcheon have not operated,should be replaced Specify: Style 20 Recessed if they cannot be completely cleaned Escutcheon with (specify*)finish, P/N by wiping the sprinkler with a cloth or (specify*) by brushing it with a soft bristle brush. Care must be exercised to avoid *Refer to Technical Data Sheet TFP770 damage to the sprinklers - before, Sprinkler Wrench during, and after installation. Specify:W-Type 6 Sprinkler Wrench, Sprinklers damaged by dropping, P/N 56-000-6-387 striking,wrench twist/slippage,or the Specify:W-Type 7 Sprinkler Wrench, like, must be replaced.Also, replace P/N 56-850-4-001 any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and mainte- nance of their fire protection system and devices in compliance with this document, as well as with the appli- cable standards of the National Fire Protection Association (e.g., NFPA 25),in addition to the standards of any authorities having jurisdiction.Contact the installing contractor or sprinkler manufacturer regarding any questions. TFP400 Page 6 of 6 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. Fire Protection Products k a tqC/3 WorldwideContacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Escutcheon reduces the accuracy to which the pipe nipples to the sprinklers Description must be cut. Sil 41, The TYCO RAPID RESPONSE Series The Series LFII Residential Sprinklers ` *-' - have been designed with heat sensitivit <, LFII Residential Horizontal Sidewall g s Sprinklers (TY1334) are decorative, and water distribution characteristics fast response,frangible bulb sprinklers proven to help in the control of residen- ,i..,, designed for use in residential occupan- , ) tial fires and to improve the chance for cies such as homes,apartments,dormi- occupants to escape or be evacuated. tories,and hotels.When aesthetics and Dry Pipe System Application optimized flow characteristics are the The Series LFII Residential Horizontal , major consideration, the Series LFII and Recessed Horizontal Sidewall w '` Residential Sidewall Sprinklers(TY1334) Sprinklers offers a laboratory approved should be the first choice. option for designing dry g g pipe residen- The Series LFII Residential Sprinklers tial sprinkler systems, whereas, most are intended for use in the following residential sprinklers are laboratory Sprinkler scenarios: approved for wet systems only. p • wet and dry pipe residential sprinkler Through extensive testing, it has been Identification systems for one- and two-family determined that the number of design dwellings and mobile homes per NFPA sprinklers (hydraulic design area) for Number (SIN) 13D the Series LFII Residential Horizontal • wet and dry pipe residential sprinkler Sidewall Sprinklers (TY1334) need not TY1334 systems for eidential occupancies be increased over the number of design stories is sprinklers (hydraulic design area) as up to and including four oc height per NFPA 13R specified for wet pipe sprinkler systems, as is accustomed for density/ area • wet and dry pipe sprinkler systems sprinkler systems designed per NFPA for the residential portions of any 13. occupancy per NFPA 13 Consequently,the Series LFII Residential The recessed version of the Series Sprinklers offer the features of non-water LFII Residential Sprinklers is intended filled pipe in addition to not having to for use in areas with finished walls. increase the number of design sprin- It employs a two-piece Style 20 klers(hydraulic design area)for systems Recessed Escutcheon.The Recessed designed to NFPA 13, 13D, or 13R. Escutcheon provides 1/4 inch(6,4 mm) Non-water filled pipe will permit options of recessed adjustment or up to 1/2 inch for areas sensitive to freezing. (12,7 mm)of total adjustment from the flush mounting surface position. The NOTICE adjustment provided by the Recessed The Series LFII Residential Horizontal Sidewall Sprinklers described herein must be installed and maintained in IMPORTANT compliance with this document and the Always refer to Technical Data applicable standards of the National Fire SheetiwaTFP700 for the "INSTALLER Protection Association,in addition to the WARNING' that providesticautions standards of any authorities having juris- with respect to handling and instal- pderformance nce of toh s so may impair the lation of sprinkler systems and Performance these devices. components. Improper handling and The owner is responsible for maintaining installation can permanently damage a their fire protection system and devices sprinkler system or its components and in proper operating condition. The cause the sprinkler to fail to operate in installing contractor or sprinkler manu- a fire situation or cause it to operate facturer should be contacted with any prematurely. questions. Page 1 of 6 APRIL 2013 REV A TFP410 r r TFP410 Page 2 of 6 Components: 5 3 2 1 1 - Frame WRENCH 2 - Button Assembly 76.n►��� FLATS I 3 - Sealing Assembly o nA :� Iii■ r. 4 - Bulb ° o���� 1?01, 5 Compression Screw - 6* 7/16"(11,1 mm) , �����IIIIIIIIIIII 6 - Deflector* TOP-OF- 4 2 7/8" DIA. DEFLECTOR NOMINAL I IMO- (73,0 mm) *Temperature rating \ MAKE-IN 1 101111 is indicated on top 9 of Deflector. - �� 111 CENTERLINEOFWATERWAY7/16" �,� STYLE 20 (11,1 mm) 1/2"NPT RECESSED 1-5/8" ESCUTCHEON END-OF- (41,3 mm) \I ESCUTCHEON DEFLECTOR _ 2-1/4" J PLATE SEATING BOSS (57,2 mm) SURFACE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334) 7/16±1/8" Gl y (11,1±3,2 mm) MOUNTING FACE OF WRENCH RECESS SURFACE SPRINKLER (END"A"USED FITTING FOR TY1334) TOP-OF- CLOSURE � DEFLECTOR 0 1 FIGURE 3 TY1334 W-TYPE 6 \ 2-7/8" DIA. SPRINKLER WRENCH ----��SE (73,0 mm) n 2-1/4"DIA. WRECESSRCH ,, Ii rIll (57,2 mm) 7/(11,11mm) �•1 kjift_ iorMOUNTING I�� PLATE END-OF- DEFLECTOR 1/8" lift BOSS (3,2 mm) PUSH WRENCH 1-3/8"(34,9 mm) 1/2"(12,7 mm) IN TO ENSURE 1-1/8"(28,6 mm) 1/4"(6,4 mm) ENGAGEMENT WITH SPRINKLER FIGURE 2 WRENCHING AREA STYLE 20 RECESSED ESCUTCHEON FIGURE 4 FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL W-TYPE ER RECESSED WRENCH HORIZONTAL SIDEWALL SPRINKLER(TY1334) . TFP410 Page 3 of 6 Technical System Types Operational Sensitivity Per the UL Listing, wet pipe and dry The sprinklers are to be installed with an Data pipe systems may be utilized. Per the end-of-deflector-boss to wall distance C-UL Listing, only wet pipe systems of 1-1/4 to 6 inches. may be utilized. Approvals In addition the top-of-deflector-to- UL Listed for use with wet pipe and dry Refer to Technical Data Sheet TFP485 ceiling distance is to bewithin the range pipe systems about the use of Residential Sprinklers (Tables A and B) being hydraulically in residential dry pipe systems. calculated. NSF Certified to NSF/ANSI 61 C-UL Listed for use only with wet pipe Ceiling Types Sprinkler Spacing systems Smooth flat horizontal, or beamed, or The minimum spacing between sprin sloped, in accordance with the 2013 klers is 8 feet (2,4 m). The maximum NYC Approved under MEA 44-03-E Edition of NFPA 13D, 13R, or 13 as spacing between sprinklers cannot For details on these approvals,refer to applicable. exceed the width of the coverage area the Design Criteria section. (Tables A and B) being hydraulically Hydraulic Design calculated(e.g.,maximum 12 feet for a Maximum Working Pressure (NFPA 13D and 13R) 12 ft.x 12 ft.coverage area, or 16 feet 175 psi(12,1 bar) For systems designed to NFPA 13D for a 16 ft.x 20 ft.coverage area.). or NFPA 13R, the minimum required sprinkler flow rates are given in Tables DDischarge GgCoefficient2(6e,5 LPM/bar��2) A and B as a function of temperature rating and the maximum allowable Rating coverage areas.The sprinkler flow rate T55°F Temperatureatorating(79°C) is the minimum required discharge ( ) from each of the total number of "design sprinklers" as specified in Finishes NFPA 13D or NFPA 13R.The number of Signal or Pure White "design sprinklers"specified in NFPA Chrome Plated 13D and 13R for wet pipe systems is Natural Brass to be applied when designing dry pipe Physical Characteristics systems. Frame Button Brass Hydraulic Design Copper (NFPA 13) Sealing Assembly Beryllium For systems designed to NFPA 13, Bulb(3 mm) Nickel w/TEFLON the number of design sprinklers is Glass to be the four most hydraulically Compression Screw Bronze demanding sprinklers. The minimum Deflector Copper required discharge from each of the four sprinklers is to be the greater of Operation the following: The glass bulb contains a fluid that • The flow rates given in Tables A and expands when exposed to heat.When B as a function of temperature rat- the rated temperature is reached,the ing and the maximum allowable fluid expands sufficiently to shatter the coverage area glass bulb, allowing the sprinkler to • A minimum discharge of 0.1 gpm/ft2 activate and flow water. over the"design area"comprised of the four most hydraulically demand- Design ing sprinklers for actual coverage ar- eas protected by the four sprinklers Criteria The number of "design sprinklers" The TYCO RAPID RESPONSE specified in NFPA 13 for wet pipe systems is to be applied when Series LFII Residential Horizontal designing dry pipe systems. and Recessed Horizontal Sidewall Sprinklers(TY1334)are UL and C-UL Dry Pipe System Water Delivery Listed for installation in accordance When using the Series LFII Residential with the following criteria. Horizontal Sidewall Sprinklers(TY1334) in dry pipe sprinkler systems,the time Residential Sprinkler Design Guide for water delivery must not exceed 15 When conditions exist that are outside seconds for the most remote operating the scope of the provided criteria,refer sprinkler. to the Residential Sprinkler Design Guide TFP490 for the manufactur- Obstruction to Water Distribution er's recommendations that may be Sprinklers are to be located in accor- acceptable to the local authority having dance with the obstruction rules of jurisdiction. NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the TYCO Technical Data Sheet TFP490. • , TFP410 Page 4 of 6 WET PIPE SYSTEM Max. Minimum Flow and Residual Pressure(b"c) Max.Coverage Spacing Ordinary Temp.Rating Intermediate Temp.Rating Minimum Width x Length fa) Ft• 155°F(68°C) 175°F(79°C) Deflector to Installation Spacing Ft.x Ft. (m) Flow Pressure Flow Pressure Ceiling Type Ft. (m x m) GPM PSI GPM PSI (m) (L/min) (bar) (L/min) (bar) 12 x 12 12 12 8.2 12 8.2 (3,7 x 3,7) (3,7) (45,4) (0,57) (45,4) (0,57) 14 x 14 14 14 11.1 16 14.5 (4,3 x 4,3) (4,3) (53,0) (0,77) (60,6) (1,00) 19 x 1 1616 14.5 (60,6) (1 00) 6 inches(4,9 x 4,9) (4,,9) (60,6) ( ,00) 16 x 18 16 19 20.5 19 20.5 (4,9 x 5,5) (4,9) (71,9) (1,41) (71,9) (1,41) Recessed 16 x 20 16 23 30.0 23 30.0 using Style 20 (4,9 x 6,1) (4,9) (87,1) (2,07) (87,1) (2,07) Escutcheon or 8 12 x 12 12 13 9.6 13 9.6 non-recessed (2,4) (3,7 x 3,7) (3,7) (49,2) (0,66) (49,2) (0,66) per NFPA 13D, 13R,or 13 14 x 14 14 17 16.4 18 18.4 (4,3 x 4,3) (4,3) (64,3) (1,13) (68,1) (1,27) 16x16 16 18 18.4 18 18.4 6to (4,9 x 4,9) (4,9) (68,1) (1,27) (68,1) (1,27) 12 inches 16 x 18 16 21 25.0 21 25.0 (4,9 x 5,5) (4,9) (79,5) (1,72) (79,5) (1,72) 16 x 26, 1626 (2 64) 26 38.3. (4,9 x 6,1) (4,,9) (98,4) (2,64) (98,4) (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K- factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used. (d) The Width x Length dimension refers to the Width(backwall where the sprinkler is located)times the Length(horizontal throw of sprinkler). TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP410 Page 5 of 6 DRY PIPE SYSTEM Max.Coverage Max. Minimum Flow and Residual Pressurelb,c) Area(a) Spacing Ordinary Temp.Rating Intermediate Temp.Rating Width x Length(d) Ft. 155°F(68°C) 175°F(79°C) Minimum Ft.x Ft. (m) Flow Pressure Flow Pressure Deflector to Installation Spacing (m x m) GPM PSI GPM PSI Ceiling Type Ft. (L/min) (bar) (L/min) (bar) (m) 12 x 12 12 12 8.2 12 8.2 (3,7 x 3,7) (3,7) (45,4) (0,57) (45,4) (0,57) 14 x 14 14 16 14.5 16 14.5 (4,3 x 4,3) (4,3) (60,6) (1,00) (60,6) (1,00) 16 x 16 16 16 14.5 16 14.5 4 to (4,9 x 4,9) (4,9) (60,6) (1,00) (60,6) (1,00) 6 inches 16 x 18 16 19 20.5 (4,9 x 5,5) (4,9) (71,9) (1,41) N/A N/A 16 x 20 16 23 30.0 Recessed (4,9 x 6,1) (4,9) (87,1) (2,07) N/A N/A using Style 20 Escutcheon or 8 12 x 12 12 13 9.6 13 9.6 non-recessed (2,4) (3,7 x 3,7) (3,7) (49,2) (0,66) (49,2) (0,66) per NFPA 13D, 14 x 14 14 18 18.4 18 18.4 13R,or13 (4,3 x 4,3) (4,3) (68,1) (1,27) (68,1) (1,27) 16x 16 16 18 18.4 21 25.0 6to (4,9 x 4,9) (4,9) (68,1) (1,27) (79,5) (1,72) 12 inches 16 x 18 16 21 25.0 21 25.0 (4,9 x 5,5) (4,9) (79,5) (1,72) (79,5) (1,72) 16 x (4,9 x 601) (4 g) N/A N/A N/A N/A (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K- factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used. (d) The Width x Length dimension refers to the Width(backwall where the sprinkler is located)times the Length(horizontal throw of sprinkler). TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL HORIZONTAL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS(TY1334) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP410 Page 6 of 6 Installation Step B. After installing the Style 20 damaged by dropping,striking,wrench Mounting Plate over the sprinkler twist/slippage, or the like, must be The TYCO RAPID RESPONSE threads and with pipe-thread sealant replaced. Also, replace any sprinkler Series LFII Residential Horizontal applied to the pipe threads, hand- that has a cracked bulb or that has lost and Recessed Horizontal Sidewall tighten the sprinkler into the sprinkler liquid from its bulb. (Ref. Installation Sprinklers(TY1334) must be installed fitting. Section.) in accordance with this section. Step C. Tighten the sprinkler into the The owner is responsible for the sprinkler fitting using only the W-Type inspection,testing,and maintenance of General Instructions 7 Recessed Sprinkler Wrench (Figure their fire protection system and devices Do not install any bulb type sprinkler if 4).With reference to Figure 1,apply the in compliance with this document,as the bulb is cracked or there is a loss of W-Type 7 Recessed Sprinkler Wrench well as with the applicable standards of liquid from the bulb.With the sprinkler to the sprinkler wrench flats. the National Fire Protection Association held horizontally, a small air bubble StepD. After the ceiling has been (e.g., NFPA 25), in addition to the should be present.The diameter of the standards of any authorities having air bubble is approximately 1/16 inch installed or the finish coat has been jurisdiction. Contact the installing (1,6 mm). applied, slide on the Style 20 Closure contractor or sprinkler manufacturer over the Series LFII Residential regarding any questions. A leak-tight 1/2 inch NPT sprinkler Sprinkler and push the Closure over the joint should be obtained by applying a Mounting Plate until its flange comes in Automatic sprinkler systems are recom- minimum to maximum torque of 7 to 14 contact with the wall. mended to be inspected, tested, and ft. lbs. (9,5 to 19,0 Nm). Higher levels maintained by a qualified Inspection of torque can distort the sprinkler Inlet Service in accordance with local with consequent leakage or impairment Care and requirements and/or national codes. of the sprinkler. Do not attempt to compensate Maintenance Ordering for insufficient adjustment in an The TYCO RAPID RESPONSE Escutcheon Plate by under- or over- Series LFII Residential Horizontal Procedure tightening the Sprinkler. Re-adjust the and Recessed Horizontal Sidewall position of the sprinkler fitting to suit. Sprinklers(TY1334)must be maintained Contact your local distributor for and serviced in accordance with this availability. When placing an order, Series LFII Residential Horizontal section. indicate the full product name and Part Sidewall SprinklersNumber(P/N). The Series LFII Residential Horizontal Before closing a fire protection system Sidewall Sprinklers must be installed main control valve for maintenance Sprinkler Assembly in accordance with the following work on the fire protection system Specify: Series LFII (TY1334), K=4.2, instructions. that it controls, obtain permission to Residential Horizontal Sidewall shut down the affected fire protection Sprinkler, (specify)temperature rating, Step 1.Install horizontal sidewall sprin- systems from the proper authorities (specify)finish, P/N (specify). klers in the horizontal position with their and notify all personnel who may be 155°F(613°C) centerline of waterway perpendicular to affected by this action. Natural Brass P/N 51-211-1-155 the backwall and parallel to the ceiling. Pure White(RAL9010)* P/N 51-211-3-155 The word"TOP"on the Deflector is to Absence of the outer piece of an Signal White(RAL9003) P/N 51-211-4-155 face towards the ceiling with the front escutcheon, which is used to cover Chrome Plated P/N 51-211-9-155 edge of the Deflector parallel to the a clearance hole, can delay sprinkler 175°F(79°C) ceiling. operation in a fire situation. Natural Brass P/N 51-211-1-175 Step pipe-thread The owner must assure that the sprin- Pure White(RAL9010)` P/N 51-211-3-175 appliedN 51-211-4-175 e 2. With i pethread sealant klers are not used for hanging any Chrome Platednal White P/N P/N 51-211-9 175 to the pipe threads, hand objects and that the sprinklers are only tighten the sprinkler into the sprinkler ) fitting. cleaned by means of gently dusting `Eastern Hemisphere sales only. with a feather duster;otherwise, non- Step 3. Tighten the sprinkler into the operation in the event of a fire or inad- Recessed Escutcheon sprinkler fitting using only the W-Type vertent operation may result. Specify: Style 20 Recessed 6 Sprinkler Wrench (Figure 3). With Escutcheon with(specify*)finish, P/N reference to Figure 1,apply the W-Type Sprinklers which are found to be (specify*). 6 Sprinkler Wrench to the wrench flats. leaking or exhibiting visible signs of corrosion must be replaced. *Refer to Technical Data Sheet TFP770. Series LFII Residential Recessed Automatic sprinklers must never be Sprinkler Wrench Horizontal Sidewall Sprinklers painted, plated, coated, or otherwise Specify W-Type 6 Sprinkler Wrench, The Series LFII Residential Recessed altered after leaving the factory. P/N 56-000-6-387. Horizontal Sidewall Sprinklers must Modified sprinklers must be replaced. Specify W-Type 7 Sprinkler Wrench, be installed in accordance with the Sprinklers that have been exposed to P/N 56-850-4-001. following instructions. corrosive products of combustion, but Step A. Install recessed hori- have not operated,should be replaced zontal sidewall sprinklers in the hori- if they cannot be completely cleaned zontal position with their centerline by wiping the sprinkler with a cloth or of waterway perpendicular to the by brushing it with a soft bristle brush. backwall and parallel to the ceiling.The Care must be exercised to avoid word"TOP"on the Deflector is to face damage to the sprinklers - before, towards the ceiling. during,and after installation.Sprinklers GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation. . . tl,CD Worldwide Fire Protection Contacts www.tyco-fire.com Products Series TY-FRB — 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General when exposed to corrosive atmo- spheres. Although corrosion-resistant Description coated sprinklers have passed the standard corrosion tests of the appli- The TYCO Series TY FRB, 2.8, 4.2, cable approval agencies,the testing is t c 5.6,and 8.0 K-factor,Upright,Pendent, not representative of all possible cor and Recessed Pendent Sprinklers rosive atmospheres. Consequently, described in this data sheet are quick it is recommended that the end user response, standard coverage, deco be consulted with respect to the suit- "fit_ rative 3 mm glass bulb type spray ability of these coatings for any given a sprinklers designed for use in light or corrosive environment. The effects of ordinary hazard,commercial occupan ambient temperature,concentration of 04 chemicals, andgas/chemical velocity, cies such as banks, hotels, and shop- Y = -r r , ping malls. should be considered, as a minimum, �^ along with the corrosive nature of the The recessed version of the Series chemical to which the sprinklers will be TY-FRB Pendent Sprinkler, where exposed. applicable,is intended for use in areas An intermediate level of the Series with a finished ceiling. This recessed TY-FRB Pendent Sprinklers is detailed pendent sprinkler uses one of the following: in Technical Data Sheet TFP356, and Sprinkler Guards are detailed in Tech- • A two-piece Style 10 (1/2 inch NPT) nical Data Sheet TFP780. or Style 40(3/4 inch NPT)Recessed Escutcheon with 1/2 inch (12,7 mm) NOTICE of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment The Series TY-FRB, 2.8, 4.2, 5.6, from the flush pendent position,or a and 8.0 K-factor, Upright, Pendent, t and Recessed Pendent Sprinklers • A two-piece Style 20(1/2 inch NPT) described herein must be installed or Style 30(3/4 inch NPT)Recessed and maintained in compliance with Escutcheon with 1/4 inch (6,4 mm) this document and with the applica- t c of recessed adjustment or up to 1/2 ble standards of the National Fire Pro- ,gin;' " inch (12,7 mm) of total adjustment tection Association, in addition to the from the flush pendent position. standards of any authorities having e adjustment provided by the jurisdiction.Failure to do so may impair Rece :• Escutcheon reduces the the performance of these devices. Sprinkler accuracy to w i •-fixed pipe drops The owner is responsible for maintain Identification to the sprinklers must be • . ing their fire protection system and Corrosion-resistant coatings, where •evices in proper operating condition. Number (SIN) applicable,are utilized to extend the life The • contractor or sprinkler of copper alloy sprinklers beyond that manufacturers •. - .e contacted with TY1131 -Upright 2.8K,1/2"NPT which would otherwise be obtained any questions. TY1231 -Pendent 2.8K,1/2"NPT TY2131 -Upright 4.2K,1/2"NPT TY2231 -Pendent 4.2K,1/2"NPT IMPORTANT TY3131 Upright 5.6K,1/2"NPT Always refer to Technical Data TY3231 -Pendent 5.6K,1/2""NPT Sheet TFP700 for the "INSTALLER TY4131 -Upright 8.0K,3/4"NPT WARNING"that provides cautions TY4231 -Pendent 8.0K,3/4"NPT with respect to handling and instal- TY4831 -Upright 8.0K,1/2"NPT lation of sprinkler systems and corn- TY4931 -Pendent 8.0K, 1/2"NPT ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 NOVEMBER 2015 TFP171 TFP171 Page 2 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 7 - Bushing 7 11111 IN I k '. 7/16"1 (11,1 mm) p� 3 NOMINAL 2-1/4' m� I A r 2 INVMAKE IN ��� 1(57,2 mm) r�r 2 3/16" 4 (55,6 mm) I 1-9/16" (39,7 mm) II ��_ 5 1/2" NPT** f WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY/131)AND PENDENT(TY1231)SPRINKLERS 2.8 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE 9 P , iwriFirm ------------- MIE 67/16" � 3 11,1 mm Y/ _i 2 4 0 glit NOMINAL 2-3/16" �t`IR�� r - MAKE-IN i (55,6 mm) 4 1�� 2 3/16" ii 1-1/2" 1 l (55,6 mm) 38 1 mm) 5 1 ( . ` —. ----�--- ,�a 6* 1/2"NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY2131)AND PENDENT(TY2231)SPRINKLERS 4.2 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector* PLATE SEATING SURFACE 0 liiii 7/16" 1 / ME im1:'- (11,1 mm) Lk NOMINAL -1 2-3/16" ar�,- iAiAit.4 2 MAKE IN I (55,6 mm) _ �l� 4 (55,6 m) 1 1 1/2" (38,1 mm) ` �5 1 — 6* 1/2"NPT** WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector* SURFACE r-, 1/2"04 p ft 1 (12 7 mm) � ��� 3 NOMINAL � �� Oi =� MAKE-IN } 2-5/16" L,— 2 (58,7 mm OA!" = 21/4" 1 9/16" I 4 (57,2 mm) (39,7 mm) 5 3/4"NPT t WRENCH STYLE 30 or 40 6* FLATS RECESSED - 2-7/8"(73,0 mm)DIA. UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw 1 1 3 - Sealing 6 - Deflector i�-�--Y--��► T F Assembly 1p. 3 4 - Bulb (11,17/16"mm) �— 2-1/4" 104 �f, NOMINAL (57,2 mm) P A 2 ` , MAKE-IN ai 1 it * Temperature rating is l 2-3/16" Ilp 1-9/16" 1 4 indicated on Deflector. (55,6 mm) (39,7 mm) ,5 ** Pipe thread connections _.__• r,Ii s\` per ISO 7-1 can be 6 * provided on special 1/2"NPT** WRENCH request. UPRIGHT FLATS PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT G- WRENCH RECESS WRENCH RECESS "i"... (END"A"USED FOR ` !f ^ 1/2" NPT MODELS) WRENCH RECESS 4r$11,2 t (END"B"USED FOR *kr 3/4"NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 6 FIGURE 7 W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED WRENCH SPRINKLER WRENCH TFP171 Page 4 of 10 TechnicalDesi n g Do not attempt to compensate for insufficient adjustment in the Escutch- eon Plate by under- or over-tightening Data Criteria the sprinkler. Re-adjust the position of Approvals The TYCO Series TY-FRB, 2.8, 4.2, the sprinkler fitting to suit. UL and C-UL Listed 5.6,and 8.0 K-factor,Upright,Pendent, Series TY-FRB Upright and Pendent FM,LPCB,and NYC Approved and Recessed Pendent Sprinklers are Sprinklers Refer to Table A and B for complete intended for fire protection systems The Series TY-FRB Pendent and approval information including corrosion- designed in accordance with the stan- Upright Sprinklers must be installed resistant status. dard installation rules recognized by in accordance with the following Maximum Working Pressure the applicable Listing or Approval instructions. Refer to Table C. agency (such as, UL Listing is based Step 1.Install Pendent sprinklers in the on the requirements of NFPA 13, and tep 1. position. upright sn the Discharge Coefficient FM Approval is based on the require- pendentpin the upright Install position. in- K=2.8 gpm/psis(40,3 Ipm/bar'h) ments of FM's Loss Prevention Data K=4.2 gpm/psis(60,5 Ipm/bar's) Sheets). Only the Style 10, 20, 30, or Step 2. With pipe-thread sealant K=5.6 gpm/psi' (80,6 Ipm/bar'h) 40 Recessed Escutcheon, as applica- applied to the pipe threads, hand- K=8.0 gpm/psis(115,2 Ipm/bar'h) ble,is to be used for recessed pendent tighten the sprinkler into the sprinkler installations. fitting. Temperature Rating Refer to Table A and B. Step 3.Tighten the sprinkler into the Installation sprinkler fitting using only the W-Type Finishes Sprinkler:Refer to Table D. The TYCO Series TY-FRB,2.8,4.2,5.6, 6 Sprinkler Wrench(Figure 6).With ref- erence to Figures 1 through 5, apply Recessed Escutcheon:Signal or Pure and 8.0 K-factor,Upright,Pendent,and the W-Type 6 Sprinkler Wrench to the White,Jet Black,Chrome Plated,or Recessed Pendent Sprinklers must p s rinkler wrench flats. Natural Brass be installed in accordance with this section. Series TY-FRB Recessed Pendent Physical Characteristics Frame Bronze General Instructions Sprinklers The Series TY FRB Recessed Pendent Button Brass/Copper Do not install any bulb type sprinkler Sprinklers must be installed in accor- Sealing Assembly..Beryllium Nickel w/TEFLON if the bulb is cracked or there is a loss dance with the following instructions. Bulb Glass of liquid from the bulb.With the sprin- Compression Screw Bronze kler held horizontally,a small air bubble Step A.After installing the Style 10,20, Deflector Copper/Bronze Bushing(K=2.8) Bronze should be present.The diameter of the 30, or 40 Mounting Plate, as applica air bubble is approximately 1/16 inch ble,over the sprinkler threads and with Operation (1,6 mm)for the 135°F(57°C)and 3/32 pipe-thread sealant applied to the pipe inch(2,4 mm)for the 286°F(141°C)tern- threads,hand-tighten the sprinkler into The glass bulb contains a fluid that perature ratings. the sprinkler fitting. expands when exposed to heat.When A leak-tight 1/2 inch NPT sprinkler Step B. Tighten the sprinkler into the the rated temperature is reached, the joint should be obtained by applying a sprinkler fitting using only the W-Type fluid expands sufficiently to shatter the minimum to maximum torque of 7 to 7 Recessed Sprinkler Wrench (Figure glass bulb, allowing the sprinkler to 14 ft.-lbs. (9,5 to 19,0 Nm).A leak tight 7). With reference to Figures 1 to 4, activate and water to flow. 3/4 inch NPT sprinkler joint should be apply the W-Type 7 Recessed Sprinkler obtained with a torque of 10 to 20 ft.- Wrench to the sprinkler wrench flats. lbs. (13,4 to 26,8 Nm). Higher levels of Step C. After ceiling installation and torque can distort the sprinkler Inlet finishing, slide on the Style 10, 20, 30, with consequent leakage or impairment or 40 Closure over the Series TY-FRB of the sprinkler. Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. • • TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME FACTOR COLOR BRASS PLATED POLYESTER*** 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) and 175°F(79°C) Yellow 1,2,3,4 UPRIGHT (TY1131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red (TY1231)* 175°F(79°C) Yellow Figure 8 200°F(93°C) Green 135°F(57°C) Orange 1,2,4 RECESSED PENDENT 155°F(68°C) Red (TY1231)** 175°F(79°C) Yellow Figure 9 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 4.2 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red 1,2 (TY2231)* 175°F(79°C) Yellow Figure 10 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231)** 175°F(79°C) Yellow Figure 11 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 Page 6 of 10 SPRINKLER FINISH(See Note 8) KBULB LIQUID NATURAL CHROME POLYESTER*** LEAD FACTOR TYPE TEMPERATURE COLOR BRASS PLATED COATED 135°F(57°C) Orange PENDENT (TY3231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5 UPRIGHT 200°F(93°C) Green (TY3131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 N/A 1/2"NPT (TY3231)* Figure 12 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red (TY3231)**PENDET 1 Figure 13 175°F(79°C) Yellow 1,2,3,4,5 N/A 200°F(93°C) Green Blue 286°F(141°C) 135°F(57°C) Orange PENDENT (TY4231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A 3/4"NPT (TY4231)* Figure 14 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT 175°F(79°C) Yellow 1,2,3,5 N/A (TY42 )** Figure 15 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT (TY4931) 155°F(68°C) Red 8.0 1,2,5 1/2"NPT NOTES: and 175°F(79°C) Yellow 1,2,4,5,6 UPRIGHT 200°F(93°C) Green (TY4831) 286°F(141°C) Blue 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. 'Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. -Frame and Deflector only. N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 7 of 10 SPRINKLER FINISH K TYPE NATURAL CHROME LEAD FACTOR BRASS PLATED POLYESTER COATED PENDENT(TY1231) and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY1231) PENDENT(TY2231) and 4.2 UPRIGHT(TY2131) 1/2"NPT 175 PSI(12,1 BAR) N/A RECESSED PENDENT(TY2231) PENDENT(TY3231) and 5.6 UPRIGHT(TY3131) 250 PSI(17,2 BAR) 1/2"NPT OR 175 PSI(12,1 BAR) RECESSED (SEE NOTE 1) PENDENT(TY3231) PENDENT(TY4231) 175 PSI and 8.0 UPRIGHT(TY4131) (12,1 BAR) 3/4"NPT 175 PSI(12,1 BAR) — RECESSED N/A PENDENT(TY4231) PENDENT(TY4931) 175 PSI 1/2"NT and 175 PSI(12,1 BAR) UPRIGHT(TY4831) (12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Under- writers Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE Care and have not operated,should be replaced Care must be exercised to avoid if they cannot be completely cleaned damage to the sprinklers -before, Maintenance by wiping the sprinkler with a cloth or during, and after installation. Sprin- klers brushing it with a soft bristle brush. klers damaged by dropping, striking, The TYCO Series TY-FRB must be Care must be exercised to avoid wrench twist/slippage,or the like,must maintained and serviced in accordance damage to the sprinklers before, be replaced. Also, replace any sprin- with this section. during, and after installation. Sprin- kler that has a cracked bulb or that has Before closing a fire protection system klers damaged by dropping, striking, lost liquid from its bulb. (Ref. Installa- main control valve for maintenance wrench twist/slippage,or the like,must tion Section). work on the fire protection system be replaced. Also, replace any sprin- Initial and frequent visual inspections of that it controls, obtain permission to kler that has a cracked bulb or that has random samples are recommended for shut down the affected fire protection lost liquid from its bulb. (Ref. Installa- corrosion-resistant sprinklers to verify systems from the proper authorities tion Section.) the integrity of the corrosion resistant and notify all personnel who may be The owner is responsible for the material of construction. Thereafter, affected by this action. inspection,testing,and maintenance of annual inspections per NFPA 25 should Absence of the outer piece of an their fire protection system and devices suffice. escutcheon, which is used to cover in compliance with this document, as Inspections of corrosion resistant a clearance hole, can delay sprinkler well as with the applicable standards sprinklers are recommended at close operation in a fire situation. of the National Fire Protection Asso- range, instead of from the floor level ciation (e.g., NFPA 25), in addition to per NFPA. Inspection at close range Sprinklers which are found to be the standards of any other authorities can better determine the exact sprin- leaking or exhibiting visible signs of having jurisdiction.Contact the install- kler condition and the long-term integ- corrosion must be replaced. ing contractor or sprinkler manufac- rity of the corrosion-resistant material, Automatic sprinklers must never be turer regarding any questions. which can be affected by the corrosive painted, plated, coated, or other- Automatic sprinkler systems are rec- conditions present. wise altered after leaving the factory. ommended to be inspected, tested, Modified sprinklers must be replaced. and maintained by a qualified Inspec- Sprinklers that have been exposed to tion Service in accordance with local corrosive products of combustion, but requirements and/or national codes. TFP171 Page 8 of 10 2-7/8" DIA. 2-7/8"DIA. (73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2"(12,7 mm) 5/8±1/4" 1/2±1/8" (15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) 2-1/4"DIA. / FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" / 1/8" (3,2 mm) �j, int (3,2 mm) 1 li' _./z _ 1 I $11 �Jt\ , } SURFACEO MOUNTING SURFACE "er• /%•�� . SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 8 FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT 2-7/8" DIA. _ 2-7/8"DIA. _ (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) 5/8±1/4" (15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm) 2-1/4"DIA. / FACE OF (57,2 mm) / FACE OF f- (57,2 mm) MOUNTING MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8.. 1/8" / (3,2 mm) / (3,2 mm) =�- li %0_ ill II 1777 7/ i "111 -J\ , MOUNTING ,Ir MOUNTING �. . SURFACE I SURFACE ._ _. •. •. SERIES 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm) CLOSURE CLOSURE TY-FRB 1"(25,4 mm) TY-FRB 3/4"(19,1 mm) FIGURE 10 FIGURE 11 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 9 of 10 2-7/8"DIA. 2-7/8"DIA. (73,0 mm) 3/4"(19,1 mm) (73,0 mm)5/8±1/4" 1/2±1/8" 1/2"(12,7 mm)mm) 1/4"(64 mm) (127±3,2 mm)2-1/4"DIA. , , 2-1/4"DIA. 1/4"(6,4 mm)/ FACE OF (57,2 mm) y MOUNTING / FACE OF (57,2 mm) _y SPRINKLER PLATE SPRINKLER MOUNTING FITTING FITTING PLATE / 1/8" (3,2 mm) / 2 ( 3 2m m) 1._j 7 771 1 / ;I r , ../74._[_ pi , MOUNTING IIt MOUNTING SURFACE SURFACE .A_ ._ CLOSURE SERIES 1-1/4"(31,8 mm) SERIES 1-1/4"(31,8 mm) TY-FRB 3/4"(19,1 mm) CLOSURE TY-FRB 1"(25,4 mm) FIGURE 12 FIGURE 13 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. 2-7/8"DIA. 5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) / FACE OF (57,2 mm) MOUNTING ~ (57,2 / FACE OF mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING / 1/8" / (3,2 mm) �WigT r r (3,22 _ai mm) \ II��� J• MOUNTING MOUNTING . SURFACE SURFACE ----- w ■ CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm) FIGURE 14 FIGURE 15 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT 8.0 K-FACTOR,3/4 INCH NPT TFP171 Page 10 of 10 P/N 57 - XXX - X - XXX SIN SPRINKLER TEMPERATURE FINISH RATINGS 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 155°F(68°C) (RAL9010)1 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C) POLYESTER(RAL9003) 341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK2 200 200°F(93°C) POLYESTER(RAL9005)2 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT(3/4"NPT) TY4131 NOTES: 1. Eastern Hemisphere sales only. 391 8.0K PENDENT(3/4"NPT) TY4231 2. Available °C) and 200°F(93IC );requires lead time to manufacture. 360 8.0K UPRIGHT(1/2"NPT) TY4831° 361 8.0K PENDENT(1/2"NPT) TY4931* TABLE D SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for www.tyco-fire.com. availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright)Sprinkler(specify)temperature rating, (specify) finish or coating, P/N (specify from Table D) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify*) finish, P/N(specify") Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 Refer to Technical Data Sheet TFP770 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. t CD TEFLON is trademark of The DuPont Corporation. Fire Protection Products . . tqcci Worldwide Fire Protection Contacts www.tyco-fire.com Products Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General The owner is responsible for maintain- ing their fire protection system and Description devices in proper operating condi- ---- tion, Contact the installing contrac- ill' TYCO Series DS-1 Dry-Type Sprinklers, tor or product manufacturer with any 5.6K Pendent, Upright,and Horizontal questions. Sidewall,Quick Response(3 mm bulb) The Series DS-1 Dry-Type Sprinklers and Standard Coverage are decora- must only be installed in fittings that tive glass bulb automatic sprinklers meet the requirements of the Design 11;1 designed for commercial use.Dry-type Criteria section. sprinklers are typically used where: ? �.r • pendent sprinklers are required on dry Sprinkler pipe systems that are exposed to freez- ing temperatures(e.g.,sprinkler drops Identification from unheated portions of buildings) •sprinklers and/or a portion of the con- Numbers (SINs) , necting piping are exposed to freezing .-, temperatures;for example, sprinkler 3/4 Inch NPT: < • •• •• wet systems into freezers, TY3935-Pendent sprinkler sprigs • - , -t s stems into TY3735-Horizontal Sidewall a i-ated attics,or horizon . .' •• 1 Inch NPT: extensions •._• - A all to protect an TY3235-Pendent unheated areas such as loa•i • _ TY3135-Upright overhangs,and building exteriors TY3335-Horizontal Sidewall •sprinklers are used on systems that Technical are seasonally drained to avoid freez- ing(e.g.,vacation areas) Data _- NOTICE Approvals The Series DS-1 Dry-Type S Sprinklers P UL and C-UL Listed described herein must be installed FM Approved and maintained in compliance with thisNYC Approved under MEA 352-01-E document,as well as with the applica- ble standards of the National Fire Previous New York City Approval Protection Association(NFPA), in ad- and MEA certification numbers ap- Maximum Working Pressure dition to the standards of any authori- ply to product as shown in this data 175 psi(12,1 bar) ties having jurisdiction.Failure to do so sheet. In accordance with Section may impair the performance of these BC 3502 of the Construction Code, Inlet Thread Connections devices. current NYC Approvals for use in the 3/4 Inch NPT City of New York apply to all products 1 Inch NPT or ISO 7-R 1 that contain UL or FM Approvals and Listings; therefore, not all products Discharge Coefficient currently Approved for use in the City K=5.6 gpm/psi1/2 IMPORTANT of New York will carry an actual MEA (80,6 Ipm/bar1/2) Always refer to Technical Data Certification number. Sheet TFP700 for the "INSTALLER Refer to Tables A and B. Temperature Ratings WARNING"that provides cautions Refer to Tables A and B. with respect to handling and in- Finishes stallation of sprinkler systems and Sprinkler: Natural Brass, Chrome components.Improper handling and Plated,or Signal White installation can permanently dam- age a sprinkler system or its compo Escutcheon: Signal White, Chrome nents and cause the sprinkler to fail Plated,or Brass Plated to operate in a fire situation or cause it to operate prematurely. Page 1 of 10 SEPTEMBER 2014 TFP51O TFP510 Page 2 of 10 ��` 11111 � Physical Characteristics PLUG WITH � INLET Inlet Copper SEALING Plug CoPPer ASSEMBLY YOKE Yoke Stainless Steel Casing Galvanized Carbon Steel �IIIII� Insert Bronze PLUG E _.__t+ INLET Bulb Seat Stainless Steel SPRING 1'=_ BAND Bulb Glass 1 ,mm, 1 Compression Screw Bronze WATER 1 1 SPRING Deflector Bronze r Frame Bronze TUBE 1 CASING Guide Tube Stainless Steel 1Water Tube Stainless Steel 1GUIDE INSERT Spring Stainless Steel TUBE �1 Plug Spring` Stainless Steel BULB Sealing Assembly . . Beryllium Nickel w/TEFLON SEAT Escutcheon Carbon Steel FRAME q/� For 3/4 inch NPT only 111( ` � 3 mm BULB VENT HOLE 11110111 , I01�� Operation �_VA.' COMPRESSION When the TYCO Series DS-1 Dry-Type DEFLECTOR SCREW Sprinklers,5.6K Pendent, Upright,and -'–_–- Horizontal Sidewall,Quick Response(3 FIGURE 1 mm bulb)and Standard Coverage are SERIES DS-1,3/4 INCH NPT,DRY-TYPE SPRINKLER in service,water is prevented from en- ASSEMBLY tering the assembly by the Plug with Sealing Assembly in the Inlet of the Sprinkler.See Figures 1 and 2. PLUG WITH ""I q INLET The glass bulb contains a fluid that ex SEALING '� pands when exposed to heat.When the ASSEMBLYrated temperature is reached,the fluid 1YOKE expands sufficiently to shatter the glass Bulb,and the Bulb Seat is released. SPRING ;�:��(� INLET The compressed Spring is then able 1'���_ BAND to expand and push the Water Tube as 1 ,�i 1 well as the Guide Tube outward.This WATER , 1 action simultaneously pulls inward on TUBE ;I, 1 CASING the Yoke, withdrawing the Plug with 1 Sealing Assembly from the Inlet and III 1 allowing the sprinkler to activate and GUIDE 1 I� 1 INSERT flow water. TUBE 1 y- .1 \' 1 BULB FRAME 7111, IM1 SEAT lggrf VENT HOLE �I `I�li 3 mm BULB /�• COMPRESSION DEFLECTOR SCREW FIGURE 2 SERIES DS-1, 1 INCH NPT AND ISO 7-R 1 DRY-TYPE SPRINKLER ASSEMBLY TFP510 Page 3 of 10 3/4 Inch NPT TY3935 Pendent TY3935 Pendent TY3735 Horizontal Sidewall with Top of Deflector-to-Ceiling with Standard with Standard Escutcheon Distance of 4 to 12 inches Recessed Escutcheon (Figure 3) (100 to 300 mm) (Figure 4) with Deep Escutcheon with Standard Escutcheon (Figure 5) (Figure 8) without Escutcheon with Deep Escutcheon (Figure 6) (Figure 9) without Escutcheon (Figure 10) Finish Temperature Bulb Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester 135°F(57°C) Orange 155°F(68°C) Red 175°F(79°C) Yellow 1,2 1,2 1* 2* 200°F(93°C) Green 286°F(141°C) Blue Notes: * Light and Ordinary Hazard occupancies only 1. Listed by Underwriters Laboratories,Inc.(maximum order length of 48 inches) 2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches) TABLE A 3/4 INCH NPT SERIES DS-1 QUICK RESPONSE,STANDARD COVERAGE DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS 1 Inch NPT(and ISO 7-R 1) TY3235 Pendent TY3235 Pendent TY3335 Horizontal Sidewall with Top of Deflector-to-Ceiling with Standard with Standard Escutcheon Distance of 4 to 12 inches Recessed Escutcheon (Figure 3) (100 to 300 mm) (Figure 4) with Deep Escutcheon with Standard Escutcheon (Figure 5) (Figure 8) without Escutcheon (Figure 6) with Deep Escutcheon (Figure 9) TY3135 Upright withoutEscutcheon5 without Escutcheon (Figure 7) (Figure 10) Finish Temperature Bulb Rating Color Code Natural Chrome White Natural Chrome White Natural Chrome White Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester 135°F(57°C) Orange 155°F(68°C) Red 1,2,3,4 1,2,4 175°F(79°C) Yellow 1,2,3,4 1,2,4 1*,2*,3**,4 1*,2*,4 200°F(93°C) Green 286°F(141°C) Blue 1,2,4 Notes: * Light and Ordinary Hazard occupancies only **Light Hazard occupancies only 1. Listed by Underwriters Laboratories,Inc.(maximum order length of 48 inches) 2. Listed by Underwriters Laboratories for use in Canada(maximum order length of 48 inches) 3. Approved by Factory Mutual Research Corporation(maximum order length of 48 inches) 4. Approved by the City of New York under MEA 352-01-E 5. The Upright Sprinkler without an Escutcheon(TY3135)is available in 1 inch NPT only N/A-Not Available TABLE B 1 INCH NPT(AND ISO 7-R 1)SERIES DS-1 QUICK RESPONSE,STANDARD COVERAGE DRY-TYPE SPRINKLERS LABORATORY LISTINGS AND APPROVALS TFP51O Page 4 of 10 SPRINKLER FITTING SPRINKLER FITTING SPRINKLER FITTING (REFER TO DESIGN (REFER TO DESIGN (REFER TO DESIGN CRITERIA SECTION) CRITERIA SECTION) CRITERIA SECTION) FACE OF FACE OF FACE OF SPRINKLER SPRINKLER SPRINKLER FITTINGFITTING FITTING - � \ L_ _J \ L_ _J \ L_ _J ORDER LENGTHS: ORDER LENGTHS: ORDER LENGTHS: 3-1/2"DIA. 2-3/4"to 48" 1-3/4"DIA. 3-3/4"to 48" 1/2"to 46" (88,9 mm) 2,7 to 1168,4 mm) (69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm) (1IN 1/4"(6,4 mm) 2-11/2"DIA. IN 1/4"(6,4 mm) IN 1/4"(6,4 mm) 2-1/4" DIA. x(63,5"11)_i INCREMENTS INCREMENTS (57,2 mm) INCREMENTS ' =' FACE OF 1 - CEILING I FACE OF' Mr FACE OF I �j�ll■ICEILING CEILING I I_u k1:, V 4-1/4"±1/8" I (108,0±3,2 mm) 2-3/16"±1/8" 3"DIA. 2 7/8"DIA. (76,2 mm) 1-3/8"±1/8" (73,0 mm) �11'� (55,6±3,2 mm) (34,9±3,2 mm) _ ■_ FIGURE 4 FIGURE 3 PENDENT TY3235 AND TY3935 FIGURE 5 PENDENT TY3235 AND TY3935 WITH STANDARD RECESSED PENDENT TY3235 AND TY3935 WITH STANDARD ESCUTCHEON ESCUTCHEON WITH DEEP ESCUTCHEON SPRINKLER FITTING I (REFER TO DESIGN TOP OF CRITERIA SECTION) DEFLECTOR FACE OF SPRINKLER FITTING \ L_ _J ORDER LENGTHS: I5"to 48" (127,0 to 1219,2 mm) ORDER LENGTHS: IN 1/4"(6,4 mm) 5"to 48" INCREMENTS (127,0 to 1219,2 mm) IN 1/4"(6,4 mm) INCREMENTS FACE OF SPRINKLER FITTING MINIMUM \ 1-3/4"(44,5 mm) DEFLECTORIF TO CEILING SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) FIGURE 7 FIGURE 6 UPRIGHT TY3135 PENDENT TY3235 AND TY3935 WITHOUT ESCUTCHEON WITHOUT ESCUTCHEON 1 INCH NPT ONLY TFP510 Page 5 of 10 ORDER LENGTHS: Design 2-3/4"to 48"(69,9 to 1219,2 mm) IN 1/4"(6,4 mm)INCREMENTS Criteria i __ 2-3/8"±1/8" (60,3±3,2 mm) The TYCO Series DS-1 Dry-Type FACE OF FACE OF Sprinklers,5.6K Pendent, Upright,ad — SPRINKLER MOUNTING — FITTING SURFACE Horizontal Sidewall,Quick Response(3 mm bulb)and Standard Coverage are Iintended for use in fire sprinkler sys- tems111 a� 3"DIA. designed in accordance with the Ilii-H... J } (76,2 mm) standard installation rules recognized by the applicable Listing or Approval 'T 3.5° agency; for example, UL Listing is SPRINKLER FITTING 1-3/4"DIA. based on NFPA 13 requirements. (REFER TO DESIGN (44,5 mm) CENTERLINE 5/16" Sprinkler Fittings CRITERIA SECTION) OF WATERWAY (7,9 mm) Install the 3/4 or 1 inch NPT Series FIGURE 8 DS-1 Dry-Type Sprinklers in the 3/4 or TY3335 AND TY3735 HORIZONAL SIDEWALL 1 inch NPT outlet or run of the follow- WITH STANDARD ESCUTCHEON ing fittings: • malleable or ductile iron threaded tee ORDER LENGTHS: fittings that meet the dimensional re- 1/2"to 45-3/4"(12,7 to 1162,1 mm) quirements of ANSI B16.3(Class 150) IN 1/4"(6,4 mm)INCREMENTS • cast iron threaded tee fittings that 4-1/4"±1/8" meet the dimensional requirements 2-1/2"DIA. FACE OF (108,0±3,2 mm) of ANSI B16.4(Class 125) FACE OF (63,5 mm) MOUNTING Do not install the DS-1 Sprinklers into S FRTTING INKLER SURFACE an elbow fittings.The Inlet of the sprin- kler can contact the interior of the el- .�.- t bow, potentially damaging the Inlet iiillmmil!' 3-1/2"DIA. seal. (88,9 mm) The unused outlet of the threaded tee is `_' •p— 3.5° plugged as shown in Figure 13. SPRINKLER FITTING You can also install the Series DS-1 (REFER TO DESIGN CENTERLINE 5/16" Dry-Type Sprinklers in the 3/4 or 1 inch CRITERIA SECTION) OF WATERWAY (7,9 mm) NPT outlet of a GRINNELL Figure 730 FIGURE 9 Mechanical Tee. However, the use of TY3335 AND TY3735 HORIZONAL SIDEWALL isthe Figure 730 Tee for tht arrangement limited to wet pipe systems. WITH DEEP ESCUTCHEON The configuration shown in Figure 12 is only applicable for wet pipe systems ORDER LENGTHS: where the sprinkler fitting and water- - 5-1/2"to 48"(139,7 to 1219,2 mm) — filled pipe above the sprinkler fitting are IN 1/4"(6,4 mm)INCREMENTS MINIMUM not subject to freezing and where the 2-1/4"(57,2 mm) length of the Dry-Type Sprinkler has the FACE OF — DEFLECTOR TO minimum exposure length depicted in SPRINKLER MOUNTING Figure 11.Refer to the Exposure Length FITTING SURFACE section. For wet pipe system installations of e-, the 1 inch NPT Series DS-1 Dry-Type Sprinklers connected to CPVC piping, use only the following TYCO CPVC -� 3.5° 5/16" fittings: SPRINKLER FITTING (7,9 mm) • 1"x 1"NPT Female Adapter(P/N 80145) (REFER TO DESIGN CENTERLINE • 1"x 1"x 1"NPT Sprinkler Head Adapter CRITERIA SECTION) OF WATERWAY Tee(P/N 80249) FIGURE 10 For wet pipe system installations of the TY3335 AND TY3735 HORIZONAL SIDEWALL the 3/4 inch NPT Series DS-1 Sprinklers WITHOUT ESCUTCHEON connected to CPVC piping, use in the 3/4" x 3/4" NPT Female Adapter(P/N 80142). TFP510 Page 6 of 10 RUN OUTLET FACE OF TO WET SIDE H rE PLUGGED SPRINKLER SYSTEM OUTLET FITTING PLUGGED --7 FITTING , y f-SPRINKLER HEATED TO DRY (SEE DESIGN HEATED EXPOSURE AREA SYSTEM AREA LENGTH CRITERIA (SEE DESIGN SECTION) DSB-2 CRITERIA DSB-2 SPRINKLER AREA INTENDED SECTION) INTENDED FITTING(SEE DESIGN SUBJECT O INTENDED FOR FREEZER FOR FREEZER CRITERIA FREEZING FOR FREEZER STRUCTURES STRUCTURES SECTION) A STRUCTURES .1110 )L 11 lir FIGURE 12 FIGURE 13 FIGURE 11 SPRINKLER FITTING SPRINKLER FITTING EXPOSURE LENGTH HEATED AREA UNHEATED AREA STRAP TIES 1-3/4" DIA. (ENDS ON (44,5 mm) OPPOSING CLEARANCE INSULATED WRENCH e- SIDES OF HOLE FREEZER RN BOOT) ADHESIVE STRUCTURE RECESSt ,, DSB-2 BOOT 11 tib DSB-2 rill" ADHESIVE BOOT �I� S lh 1-3/4" DIA. it WRENCH A T �� (44,5 mm) _ IIS 9 i CLEARANCE 1� �% \./ 1 PUSH WRENCH INSULATED ������ FREEZER INTO ENSURE Jill�, STRUCTURE STRAP TIES ENGAGEMENT DS-1 (ENDS ON DS-1 WITH SPRINKLER ,FP,: SHOWN WITH OPPOSING SHOWN WITH WRENCHING AREA SIDES OF STANDARD FIGURE 16 STANDARD BOOT) ESCUTCHEON W-TYPE 7 ESCUTCHEON SPRINKLER WRENCH FIGURE 14 FIGURE 15 MODEL DSB-2 SPRINKLER MODEL DSB-2 SPRINKLER BOOT WITH PENDENT SERIES BOOT WITH SIDEWALL SERIES DS-1 DRY SPRINKLER DS-1 DRY SPRINKLER TFP510 Page 7 of 10 Clearance Space Temperatures for Heated Areat In accordance with Section 8.4.9.2 of 40°F 50°F 60°F the 2010 edition of NFPA 13,when con- Ambient Temperature necting an area subject to freezing and Exposed to (4°C) (10°C) (16°C) an area containing a wet pipe sprinkler Discharge End of Sprinkler MinimumExposed Barrel Length2, system,the clearance space around the Inches sprinkler barrel of Dry-Type Sprinklers (mm) must be sealed.Due to temperature dif- 40°F ferences between two areas,the poten- 40°F 0 0 0 tial for the formation of condensation in the sprinkler and subsequent ice build- 30°F uP is increased. If this condensation is (1°C) 0 0 0 not controlled, ice build-up can occur sprin- 20°F that i ht damage the dry type sprin- 4 0 0 kler and/or prevent proper operation in (-7°C) (100) a fire situation. 10°F 8 1 Use of the Model DSB 2 Dry Sprinkler (-12°C) (200) (25) 0 Boot, described in Technical Data Sheet TFP591 and shown in Figures 14 0°F 12 3 and 15,can provide the recommended (-18°C) (305) (75) 0 seal. 10°F 14 4 1 (-23°C) (355) (100) (25) Installation -20°F 14 6 3 The TYCO Series DS-1 Dry Type (-29°C) (355) (150) (75) Sprinklers,5.6K Pendent, Upright,and Horizontal Sidewall, Quick Response -30°F 16 8 4 (3 mm bulb) and Standard Coverage (-34°C) (405) (200) (100) must be installed in accordance with this section. -40°F 18 8 4 (-40°C) (455) (200) (100) General Instruct ions The Series DS-1 Dry Type Sprinklers -50°F 20 10 6 must only be installed in fittings that (-46°C) (510) (255) (150) meet the requirements of the Design Criteria section. Refer t the Design -60°F 20 10 6 Criteria section for other important re- (51°C) (510) (255) (150) quirements regarding piping design and sealing of the clearance space around Notes: the Sprinkler Casing. 1. For protected area temperatures that occur between values listed above,use the next cooler temperature. Do not install any bulb-type sprinkler 2. These lengths are inclusive of wind velocities up to 30 mph(18,6 kph). TABLE C if the bulb is cracked or there is a loss EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS of liquid from the bulb.With the sprin MINIMUM RECOMMENDED LENGTHS kler held horizontally,a small air bubble lpresent. diamet shoud be Thediameter of the For drypipe system installations, use Drainage air bubble is approximately 1/16 inch p p y (1,6 mm)for the 135°F(57°C) rating to only the side outlet of maximum 2-1/2- In accordance with the minimum1/8 inch(3,2 mm)for the 286°F(141°C) inch reducing tee when locating the requirements of the National Fire rating. Series DS-1 Sprinklers directly below Protection Association for dry pipe the branch line.Otherwise,use the con- sprinkler systems, branch,cross, and •A leak-tight 3/4 inch NPT sprinkler figuration shown in Figure 13 to assure feed-main piping connected to Dry joint should be obtained by applying complete water drainage from above Sprinklers and subject to freezing tern- a minimum-to-maximum torque of 10 the Series DS-1 Dry Type Sprinklers peratures must be pitched for proper to 20 ft. lbs.(13,4 to 26,8 Nm). and the branch line. Failure to do so drainage. •A leak-tight 1 inch NPT sprinkler joint may result in pipe freezing and water should be obtained by applying a damage. Exposure Length minimum-to-maximum torque of 20 When using Dry Sprinklers in wet pipe to 30 ft.-lbs.(26,8 to 40,2 Nm). NOTICE sprinkler systems to protect areas sub- Higher levels of torque can distort the Do not install the Series DS 1 Dry-Type ject to freezing temperatures,use Table C to determine a sprinkler's appropriate sprinkler Inlet with consequent leakage Sprinkler into any other type fittingor impairment of the sprinkler. without first consulting the Technical exposed barrel length to prevent water Services Department.Failure to use from freezing in the connecting pipes Do not attempt to compensate for Services De fittingamay result in oneethef due to conduction.The exposed bar- insufficient adjustment in an the following: rel length measurement must be taken Escutcheon Plate by under or over- from the face of the sprinkler fitting to tightening the sprinkler. Re-adjust the •failure of the sprinkler to operate prop- the surface of the structure or insula- position of the sprinkler fitting to suit. erly due to formation of ice over the tion that is exposed to the heated area. inlet Plug or binding of the Inlet Plug Refer to Figure 11 for an example. •insufficient engagement of the Inlet pipe threads with consequent leakage TFP51O Page 8 of 10 Step 1. Install pendent sprinklers only Absence of the outer piece of an es- Ordering in the pendent position,and install up- cutcheon, which is used to cover a right sprinklers only in the upright posi- clearance hole,can delay the time to Procedure tion.The deflector of a pendent or up- sprinkler operation in a fire situation. right sprinkler must be parallel to the A Vent Hole is provided in the Bulb Contact your local distributor for avail- ceiling. Seat(Ref. Figures 1 and 2)to indicate ability.When placing an order,indicate Install horizontal sidewall sprinklers in if the Dry-Type Sprinkler is remaining the full product name and Part Number the horizontal position with their cen- dry. Evidence of leakage from the Vent (P/N). terline of waterway perpendicular to Hole indicates potential leakage past DS-1 Dry-Type Sprinklers the back wall and parallel to the cell- the Inlet seal and the need to remove When ordering TYCO Series DS-1 ing. Ensure the word"TOP"on the De- the sprinkler to determine the cause of Dry Type Sprinklers, 5.6K Pendent, flector faces the ceiling. leakage(e.g.,an improper installation Upright,and Horizontal Sidewall,Quick or an ice plug). Close the fire protec- Response(3 mm bulb)and Standard Step 2. With a non-hardening pipe- tion system control valve and drain the Coverage, specify the following thread sealant such as TEFLON tape s stem before removing the sprinkler. information: applied to the Inlet threads,hand-tight y en the sprinkler into the sprinkler fitting. Sprinklers which are found to be leak- • SIN: ing or exhibiting visible signs of corro Pendent—TY3935 or TY3235 Step 3.Wrench-tighten the sprinkler sion must be replaced. Sidewall—TY3735 or TY3335 using either: • a pipe wrench on the Inlet Band or the Automatic sprinklers must never be Upright—TY3135 Casing(Ref. Figures 1 and 2) painted, plated, coated, or other- • 5.6 K-factor wise altered • after leaving the factory. • Deflector Style: •the W-Type 7 Sprinkler Wrench on the Modified sprinklers must be replaced. y Wrench Flat(Ref. Figure 16) Sprinklers that have been exposed to Upright,Pendent,or Horizontal Sidewall corrosive products of combustion,but Apply the Wrench Recess of the •Quick Response,Standard Coverage, W-Type 7 Sprinkler Wrench to the have not operated,should be replaced Dry-Type Sprinkler Wrench Flat. if they cannot be completely cleaned Order Length: by wiping the sprinkler with a cloth or •OO Note: If sprinkler removal becomes by brushing it with a soft bristle brush. Dry-TypeSprinklers are furnished based necessary, remove the sprinkler us- upon Order Length as measured per ing the same wrenching method not- Care must be exercised to avoid dam Figures 3 through 10.After taking the age to the sprinklers before,during,and measurement,round it to the nearest ed above. Sprinkler removal is easier after installation.Sprinklers damaged 1/4 inch increment. when a non hardening sealant was by dropping, striking, wrench twist/ used and torque guidelines were fol- slippage,or the like,must be replaced. • Inlet Connections: lowed.After removal,inspect the sprin- Also, replace any sprinkler that has a 3/4 Inch NPT,1 Inch NPT,or ISO 7-R 1 kler for damage. cracked bulb or that has lost liquid from •Temperature Rating Step 4. After installing the ceiling or its bulb.(Ref. Installation Section.) . Sprinkler Finish wall and applying a ceiling finish,slide The owner is responsible for • the in- on the outer piece of the escutcheon • Escutcheon Style and Finish, as spection,testing,and maintenance of applicable until it comes in contact with the ceil- their fire protection system and devices ing or wall. Do not lift the ceiling panel in compliance with this document, as • Part Number(P/N)from Table D out of its normal position. well as with the applicable standards of The Upright Sprinkler without an When using the Deep Escutcheon, the National Fire Protection Association Escutcheon (TY3135) is available in hold the outer piece in contact with (e.g., NFPA 25),in addition to the stan 1 Inch NPT only. the mounting surface(ceiling or wall). dards of any other authorities having Then rotate the inner piece approxi- jurisdiction.Contact the installing con- Part Numbers are for 3/4 inch and mately 1/4 turn with respect to the out- tractor or product manufacturer with 1 inch NPT standard order sprin- er piece,to hold the Deep Escutcheon any questions. klers. Orders for all other sprinkler firmly together. assemblies must be accompanied Automatic sprinkler systems are recom- by a complete description. Refer to mended to be inspected,tested, and the Price List for a complete listing of Care and maintained by a qualified Inspection Part Numbers. A. Service in accordance with local re- maintenance quirements and/or national codes. Sprinkler Wrench Specify:W-Type 7 Sprinkler Wrench, The TYCO Series DS-1 Dry Type P/N 56-850-4-001 Sprinklers,5.6K Pendent,Upright,and Limited Sprinkler Boot Horizontal Sidewall,Quick Response(3 warrant Model DSB-2 Dry Sprinkler mm bulb)and Standard Coverage must Y Boot,Specify: Model 63-000-0-002 be maintained and serviced in accor- For warrantyterms and conditions, dance with this section. This Part Number includes one (1) visit www.tyco-fire.com. Boot,two(2)Strap Ties,and 1/3 oz.of Before closing a fire protection system Adhesive(a sufficient quantity for in- main control valve for maintenance stalling one boot). work on the fire protection system that it controls,obtain permission to shut down the affected fire protection sys- tems from the proper authorities and notify all personnel who may be affect- ed by this action. TFP510 Page 9 of 10 P/N* 60 - XXX - X - XXX SIN SPRINKLER ESCUTCHEON FINISH FINISH1 01 Pendent with Standard TY3935 Escutcheon(3/4"NPT) (Figure 3) 0 CHROME PLATED SIGNAL WHITE (RAL9003) 02 Pendent with Deep TY3935 SIGNAL WHITE Escutcheon(3/4"NPT) (Figure 5) 1 NATURAL BRASS (RAL9003) 03 Pendent with Standard Recessed TY3935 2 NATURAL BRASS BRASS PLATED Escutcheon(3/4"NPT) (Figure 4) SIGNAL WHITE SIGNAL WHITE 04 Pendent without TY3935 4 (RAL9003) (RAL9003) Escutcheon(3/4"NPT) (Figure 6) 9 CHROME PLATED CHROME PLATED 05 Sidewall with Standard TY3735 Escutcheon(3/4"NPT) (Figure 8) 06 Sidewall with Deep TY3735 TEMPERATURE Escutcheon(3/4"NPT) (Figure 9) SAMPLE RATINGS ORDER LENGTHS2 07 Sidewall without TY3735 0 135°F(57°C) Escutcheon(3/4"NPT) (Figure 10) 055 5.50" 1 155°F(68°C) 082 8.25" 36 Pendent with Standard TY3235 2 175°F(79°C) Escutcheon(1"NPT) (Figure 3) 180 18.00" 3 200°F(93°C) Pendent with Deep TY3235 187 18.75" 33 Escutcheon "1NPT)) (Figure 5) 4 286°F(141°C) 372 37.25" 37 Pendent with Standard Recessed TY3235 Escutcheon(1"NPT) (Figure 4) 480 48.00" 32 Pendent without TY3235 Escutcheon(1"NPT) (Figure 6) Notes: * Use Prefix"I"for ISO 7-R 1 Connection(e.g.,1-60-010-4-055). Sidewall with Standard TY3335 1. Escutcheon Finish applies to sprinklers provided with escutcheons. 34 2. Dry-Type Sprinklers are furnished based upon"Order Length"as measured Escutcheon(1"NPT) (Figure 8) per Figures 3 through 10,as applicable,and for each individual sprinkler where it is to be installed.After the measurement is taken,round it to the Sidewall with Deep TY3335 nearest 1/4 inch increment. 43 Escutcheon(1"NPT) (Figure 9 9) 44 Sidewall without TY3335 Escutcheon(1"NPT) (Figure 10) 38 Upright without TY3135 Escutcheon(1"NPT) (Figure 7) TABLE D SERIES DS-1 DRY-TYPE SPRINKLERS PART NUMBER SELECTION TFP510 Page 10 of 10 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. truce TEFLON is trademark of the DuPont Corporation. Fire Protection Products tqco /Ffre & Building fir Products rapid response HOME FIRE SPRINKLER SYSTEM Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 BlazeMaster CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General Description Technical Tyco® CPVC Pipe and Fittings pro- Data duced by Tyco Fire & Building Prod- ucts (TFBP) are designed exclusively Sizes for use in wet pipe automatic fire sprin- 3/4"to 3" kler systems. The Tyco CPVC Pipe Maximum Working PressureArt 7, and Fittings are produced from Blaze- 175 psi Master® CPVC compound that is a 14. specially developed thermoplastic Approvals y compound composed of post chlorin- UL, FM, C-UL, NSF, LPCB, MEA, and ated polyvinyl chloride (CPVC) resin the City of Los Angeles. (Refer to (n- and state of the art additives. Tyco stallation Handbook IH-1900 dated CPVC Pipe and Fittings are easier to June 2008 for exact listing/approval ,n - t install than traditional steel pipe sys- information.) tems, and at the same time, provide Manufacture Source superior heat resistance and strength U.S.A. as compared to traditional CPVC and PVC piping materials used in the Material plumbing trade. Various adapters are • Pipe:ASTM F442, SDR 13.5 available to connect CPVC pipe to me- tallic piping. All female pipe thread • Fittings: ASTM F438 (Sch. 40) and adapters have brass inserts for dura- ASTM F439(Sch.80),ASTM F1970 bility. Grooved adapters connect di- Color rectly to grooved end valves and me- Orange tallic pipe, with flexible grooved end couplings. NOTICE Tyco® CPVC Pipe and Fittings pro- duced with BlazeMaster®CPVC com- pound described herein must be in- stalled and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may im- pair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMaster®is a registered trademark of The Lubrizol Corporation Page 1 of 2 JUNE, 2008 TFP1915 Page 2 of 2 TFP1915 InstallationL/�i�mited Tyco® CPVC Pipe and Fittings pro Warranty duced by Tyco Fire & Building Prod- ucts (TFBP) are to be installed in Products manufactured by Tyco Fire& accordance with Installation Hand- Building Products (TFBP) are war- book IH-1900 dated June 2008. ranted solely to the original Buyer for ten(10)years against defects in mate- Care and rial and workmanship when paid for and properly installed and intained ma Maintenance under normal use and ( 0)s1This warranty will expire ten (10) years from date of shipment by TFBP. No The owner is responsible for the in- warranty isgiven for products or com- spection, testing, and maintenance of ponents manufactured by companies their fire protection system and de- not affiliated by ownership with TFBP vices in compliance with this docu- or for products and components which ment, as well as with the applicable have been subject to misuse,improper standards of the National Fire Protec- installation, corrosion, or which have tion Association (e.g., NFPA 25), in not been installed, maintained, modi- addition to the standards of any fled or repaired in accordance with ap- authority having jurisdiction. The in- plicable Standards of the National Fire stalling contractor or product manufac- Protection Association, and/or the turer should be contacted relative to standards of any other Authorities any questions. Having Jurisdiction. Materials found Automatic sprinkler systems should be by TFBP to be defective shall be either inspected,tested,and maintained by a repaired or replaced, at TFBP's sole qualified Inspection Service in accord- option. TFBP neither assumes, nor ance with local requirements and/or authorizes any person to assume for it, national codes. any other obligation in connection with the sale of products or parts of prod- ucts.TFBP shall not be responsible for NOTICE sprinkler system design errors or inac- curate or incomplete information sup- Before closing a fire protection system plied by Buyer or Buyer's repre- control valve for inspection or mainte- sentatives. nance work on the fire protection sys- tem that it controls,permission to shut In no event shall TFBP be liable, in down the affected fire protection sys- contract, tort, strict liability or under tern must first be obtained from the any other legal theory, for incidental, proper authorities and all personnel indirect,special or consequential dam- who may be affected by this action ages, including but not limited to labor must be notified. charges, regardless of whether TFBP was informed about the possibility of After placing a fire protection system such damages, and in no event shall in service,notify the proper authorities TFBP's liability exceed an amount and advise those responsible formoni- equal to the sales price. toring proprietary and/or central sta- The foregoing warranty is made in lieu tion alarms. of any and all other warranties. ex- press or implied. including warranties of merchantability and fitness for a par- ticular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products,materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law.The invalidity,in whole or part, of any portion of this warranty will not affect the remainder. ©2008 TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 ,„,I,,,.. 000 Fire Sprinkler Pipe Mega-Flow and Mega-Thread Submittal Data Sheet #.n# FM Approved and Fully Listed Sprinkler Pipe MEGA-FLOW SPECIFICATIONS Wheatland's Mega-Flow steel fire sprinkler pipe is FM Approved for roll-grooved,plain-end and NPS NOM OD NOM ID UL CRR' MEGA-FLOW welded joints for wet systems;and UL,C-UL sc5edule lied'"e Schedule No ina# and FM Listed for use with roll grooved,plain eg+ ioyt= ==10 ,"fc 40 Mega-Flow 40 *. Pcs/L1ft �... /t1. ,.=x._.�...: end couplings and welded joints for wet,dry 1'%s 1.660 1.530 1.442 1.380 1.80 1.00 1108 61 preaction and deluge systems.Mega-Thread is FM Approved for use in wet systems and is UL, 1'� _' 1.900 1.740 1.682 1.610 2 4 1.00 1.556 61 C-UL and FM Listed for wet,dry and preaction 2 2.375 2.215 2157 2.067 214 1.00 1.961 37 sprinkler systems. 2%;" 2.875 2.707 2.635 2.469 1.43 1.00 2.504 30 Approvals and Specifications Both products meet or exceed these standards: 3 3.500 3.316 3.260 3.068 34 00 3.349 9 • ASTM A795,Type E,Grade A 4 ,i,i 4.500 4.316 4.260 4.026 1.00 1.00 4.331 19 • NFPA 13 and NFPA 14 6 6.625 6.395 6.357 6.065 .75 1.00 8.000 10 .................... ................ • Mega-Thread is approved for Calculated using Standard UL CRR formula,UL Fire Protection Directory,Category VIZY. •The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. standard hanger spacing Threaded Schedule 40 steel pipe is used as the benchmark(value of 1.0). Manufacturing Protocols Mega-Flow and Mega-Thread are subjected to MEGA-THREAD SPECIFICATIONS the toughest possible testing protocols to ensure the highest quality and long-lasting performance. NPS NOM OD NOM ID UL CRR* MEGA-THREAD stiwoule Schedule Nominal " '_" Finishes and Coatings Mega Tl+tead 40 Mega-Thread 40 L.W.T.Piper wt tk Pm/Lift Mega-Flow black steel fire sprinkler pipe 1 1.315 1.087 1.049 1.00 1.00 .61 1.462 70 receives a proprietary mill coating to ensure a clean,corrosion-resistant surface that outlasts 1% 1.660, 1.416 1.380 1.00 1.00 .39 1.989 Sk_ standard lacquer coatings.This coating allows 1% 1.900 1.650 1.610 1.00 1.00 .31 2.370 44 the pipe to be easily painted without special preparation.Mega-Thread is hot-dip galvanized 2 2.375 2.117 2.067 1,00 1.00 .25 3.094 30 to meet FM requirements for dry systems and •Calculated using Standard UL CRR formula,UL Fire Protection Directory,Category VIZY. is safer to weld than many zinc-coated,light-wall •The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. threadable products. Threaded Schedule 40 steel pipe is used as the benchmark(value of 1.0). Producthroing ® C 0 4:: Eachachlength gtth of Wheatland fire sprinkler pipe is continuously stenciled to show the APPROVED manufacturer,type of pipe,grade,size and length.Barcoding is acceptable as a supplementary identification method. SUBMITTAL INFORMATION PROJECT: CONTRACTOR: DATE: ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE: LOCATIONS: COMMENTS: ❑ MEGA-FLOW-BLACK ❑ MEGA-THREAD-HOT-DIP GALVANIZED Wheatland Tube 700 South Dock Street Sharon, PA 16146 Wheatland Tube P 800.257.8182 I F 724.346.7260 I info(awheatland.com I wheatland.com lMC STEEL GROUP . , ti,ca Worldwide Contacts www,tyco-fire.com Model DPV-1 Dry Pipe Valve, External Resetting 2-1/2 thru 6 Inch (DN65 thru DN150) 250 psi (17,2 bar) General Description The TYCO Model DPV-1 Dry Pipe Valves are differential valves used to automatically control the flow of water , into dry pipe fire protection sprinkler systems upon operation of one or more automatic sprinklers. The DPV-1 also - -- . provides for actuation of fire alarms upon system operation. The Model - DPV-1 features are as follows: • External reset. ! • 250 psi(17,2 bar)pressure rating. • Unique offset single clapper design _ enabling a simple compact valve to minimize installation labor. • Ductile iron construction to ensure a lightweight valve to minimize shipping cost. • A variety of inlet and outlet connections. Available End Connections and Sizes • Compact, Pre-Trimmed, and Semi- Nominal Valve Size Assembled, easy to operate valve End Connection 2-1/2 Inch 3 Inch 4 Inch 6 Inch trim. (DN65) (DN80) (DN100) (DN150) • Simple reset procedure through the Flange x Flange N/A N/A elimination of priming water. Dry pipe sprinkler systems are used Flange x Groove N/A N/A • 0 in unheated warehouses, parking Groove x Groove garages, store windows, attic • • • • spaces, loading docks, and other areas exposed to freezing tempera- S Available tures, where water filled pipe cannot N/A Not Available be utilized. When set for service, the dry pipe sprinkler system is pressur- NOTICE The owner is responsible for main- ized with air (or nitrogen). The loss tainin their fire rotection s stem and of pressure through an operated The Model DPV-1 Dry Pipe Valves g P Y automatic sprinkler in response to described herein must be installed devices in proper operating condition. heat from a fire permits the DPV-1 Dry and maintained in compliance with this The installing contractor or manufac- Pipe Valve to open and allow a flow of document, as well as with the appli- turer should be contacted with any water into the sprinkler system piping. cable standards of the National Fire questions Table B establishes the minimum Protection Association, in addition to required system air pressure that the standards of any other authorities includes a safety factor to help prevent having jurisdiction. Failure to do so false operations that might occur due to may impair the performance of these water supply fluctuations. devices. Page 1 of 20 MARCH 2013 TFP1O2O TFP1020 Page 2 of 20 NO. DESCRIPTION QTY. REF. 1 Valve Body 1 NR 2 Air and Water Seat 1 NR 410 3 Handhole Cover...1 NR 4 Handhole Cover 11 Gasket 1 See(b) 5 1/2-13 UNC x 1" Hex fr , — 12 Head Cap Screw: 2-1/2&3 Inch 4I4 , 6 Valves 5 CH 13 4 Inch Valve 6 CH ` o, 7 .-- 6 Clapper 1 See(a) 1 --..\ CLAPPER RESET 7 Clapper Facing....1 See(a)or(b) .. �� ASSEMBLY CD------14 PLUNGER PARTS 8 Clapper Facing I `-J\ 8 Retaining Plate....1 See(a) `� / -ii 15,18 9 2-1/2 and 3 Inch Valves: 0 1/4"x 3/8"Long 9 #10-32 Shoulder 16 Screw 5 See(a) 4 Inch Valve: 17 1/4-20 UNC x 1/2" Socket Head Cap Screw 7 See(a) 10 Clapper Hinge Pin 1 See(a) 11 Reset Knob 1 See(c) C • 12 Reset Spring 1 See(c) • 13 Reset Bushing ....1 See(c) 14 Reset Bushing 0-Ring 1 See(b)or(c) t 15 Reset Plunger 0-Ring 1 See(b)or(c) — 16 Reset Plunger 1 See(c) 17 Reset Latch Subassembly 1 See(c) 18 Dow Corning FS3452 \ 1 FlourosGrease,licone / 4 Grease, 1.5 g 1 See(b)or(c) ` c ( 2 ` / 3 NR:Not Replaceable C'�: CH:Common Hardware ®��� �(0/ REPLACEMENT PARTS --6,2 0 NO. DESCRIPTION P/N 'r �� (a) Clapper Assembly �� �1 �� foo Includes Items 6-10: / 2-1/2&3 Inch Valves.. 92-309-2-203 �j, 0 4R Inch Valve 92-309 2-403 10 • � (/IUII (b) Repair Parts Kit 1 5 Includes Items 4,7,14,15,&18: 2-1/2&3 Inch Valves.. 92-309-1-204 4 Inch Valve 92-309-1-404 (c) Reset Plunger Parts Kit Includes Items 11-18.. 92-310-1-405 FIGURE 1 -PART 1 OF 2 MODEL DPV-1 DRY PIPE VALVE 2-1/2,3,AND 4 INCH(DN65,DN80,DN100)ASSEMBLIES TFP1020 Page 3 of 20 NO. DESCRIPTION QTY. REP.PART NO.DESCRIPTION QTY. REP.PART NO. DESCRIPTION QTY. REP.PART 1 Valve Body 1 NR 5 Socket Head Cap 8 Hex Head Cap Screw 2 Air and Water Screw 5/8-11 UNC x 1"...6 CH Seat 1 NR 3/8-16 UNC x 1"...8 NR 9 Clapper 1 See(a) 3 Water Seal 6 Handhole Cover...1 NR 10 Clapper Facing....1 See(a)or(b) 0-Ring 1 NR 7 Handhole Cover 11 Clapper Facing 4 Air Seal 0-Ring....1 NR Gasket 1 See(b) Retaining Plate....1 See(a) 12 Socket Head Cap �, Screw • 1/4-20 UNC x 1/2°.9 See(a) 14 13 Clapper Hinge Pin..1 See(a) 14 Reset Knob 1 See(c) 7�I15 15 Reset Spring 1 See(c) g 16 Reset Bushing ....1 See(c) I 17 Reset Bushing �,.•'' Coj 16 0-Ring 1 See(b)or(c) 10 �! 18 Reset Plunger CLAPPER � RESET 0-Ring 1 See(b)or(c) ��- `11 ASSEMBLY 0117 PLUNGERARTS19 Reset Plunger 1 See(c) """ i 20 Reset Latcsemh �// �• 18,21 Subassembly 1 See(c) e 12 r _ 21 Dow Corning FS3452 I Flourosilicone 19 Grease, 1.5 g 1 See(b)or(c) O O NR:Not Replaceable > 20 CH:Common Hardware REPLACEMENT PARTS NO. DESCRIPTION P/N r; (a) Clapper Assembly ei Includes Items 9-13... 92-309-2-603 / (b) Repair Parts Kit fi Includes Items 7- i' J 7, 10,17,18,21 92-309-1-604 2 O (c) Reset Plunger Parts Kit 1 Includes Items 14-21 .. 92-310-1-405 (c ----;__11--_, ,, , . .. 4 1 i 411 _ .= o 0 �` .', 4 1 ,..,,a .„,.,, _ i, / /6 4 € 3 5 ® \ A41AJ 'N� / /' A. 7;$91'0 13 �4 0 0 i 4 01 0 CD_ t0 FIGURE 1 -PART 2 OF 2 MODEL DPV-1 DRY PIPE VALVE 6 INCH(DN150)ASSEMBLY TFP1020 Page 4 of 20 Technical Data Handhole Cover are ductile iron. The • PS10-2 waterflow alarm switch Handhole Cover Gasket is neoprene, • and the Clapper Facing is EPDM. PS40 2 low air pressure alarm switch Approvals The Air/Water Seat Ring is brass,the Note: When the system pressure is ULand Listed. FM Approved. Clapper is bronze or aluminum bronze, greater than 175 psi(12,1 bar),provision NYC undeerr MEA 172-02-E (4 and 6 and both the Clapper Retaining Plate is to be made to replace the standard inch). and Latch are bronze.The Hinge Pin is order 300 psi(20,7 bar)Water Pressure Dry Pipe Valve aluminum bronze,and the fasteners for gauge with a separately ordered 600 The TYCO Model DPV-1 Dry Pipe the Handhole Cover are carbon steel. psi(41,4 bar)Water Pressure Gauge. Valves are for vertical installations(flow Valve Trim Air Supply going up), and they are rated for use Installation dimensions are given Table B shows the system air pressure at a maximum service pressure of 250 in Figure 7, and the Valve Trim and requirements as a function of the psi(17,2 bar).The Valve dimensions are Pre-Trimmed Valve Assemblies are water supply pressure. The air (or shown in Figure 7. illustrated in Figures 4, 5, and 6. The nitrogen) pressure in the sprinkler Flanged connections are available and Valve Trim and Pre Trimmed Valve system is recommended to be auto- drilled per ANSI,ISO,AS,and JIS spec- forms a part of the laboratory listings matically maintained by using one of ifications (Ref. Table A). The grooved and approval of the DPV-1 Valve and is the following pressure maintenance outlet connections, as applicable, necessary for the proper operation of devices,as appropriate: are cut in accordance with standard the DPV-1 Valve. Each package of trim • Model AMD-1 Air Maintenance groove specifications for steel pipe. and pre-trimmed includes the following Device(pressure reducing type). They are suitable for use with grooved items: end pipe couplings that are listed or . Water Supply Pressure Gauge • Model AMD-2 Air Maintenance approved for fire protection system pp y Device(compressor control type). service.Available combinations of inlet • System Air Pressure Gauge • Model AMD-3 Nitrogen Maintenance and outlet connections are detailed in • Air Supply Connections Device(high pressure reducing type). the Ordering Procedure section.They are also noted in the "Available End • Main Drain Valve The Pressure Relief Valve provided with Connection and Sizes" table located the valve trim is factory set to relieve • Low Body Drain Valve pressure of approximately 45 psi on Page 1. ata pP y Threaded port connections of valves • Alarm Test Valve (3,1 bar). If the normal system air having flanges drilled to ANSI, AS, or • Automatic Drain Valve pressure is less than or exceeds 40 psi JIS specifications are NPT threaded per (2,8 bar),then the pressure Relief Valve • Drip Funnel must be reset to relieve at a pressure ANSI Standard B1.20.1.Threaded port connections of valves having flanges • Connections For Optional Quick that is in accordance with the authority drilled to ISO are available either Opening Device(Accelerator) having jurisdiction. threaded per ISO 7-1 or NPT threadedAlso included in the Pre Trimmed Valve Quick Opening Device per ANSI Standard B1.20.1.Valves withAssembly,which can be ordered sepa As an option,the Model DPV-1 Dry Pipe NPT threaded ports will readily accept rately for the Valve Trim, includes the Valve may be equipped with the VIZOR the trim arrangements detailed in Parts following items: Electronic Dry Pipe Valve Accelerator 2 and 3 of Figures 4,5,and 6. (4 and 6 inch sizes) as detailed in • Model BFV-N butterfly vlave Technical Data Sheet TFP1105 or the Components of the DPV-1 Valves Model ACC-1 Mechanical Dry Pipe are shown in Figure 1.The Body and • Figure 577 grooved coupling Flange Drilling Specification Nominal Dimensions in Inches and(mm) Nominal ANSI B16.1 1 ISO 7005-2 JIS B 2210 AS 2129 Valve Size (Class 125) (PN16)2 (10K) (Table E) Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. Dim. Dim. Qty. A B N A B N A B N A B N 4 Inch 7.50 0.75 8 7.09 0.75 8 6.89 0.59 8 7.00 0.71 8 (DN100) (190,5) (19,0) (180,0) (19,0) (175,0) (15,0) (178,0) (18,0) 6 Inch 9.50 0.88 8 9.45 0.91 8 9.45 0.75 8 9.25 0.87 8 (DN150) (241,3) (22,2) (240,0) (23,0) (240,0) (19,0) (235,0) (22,0) 1 Same drilling as for ANSI B16.5(Class 150)and ANSI B16.42(Class 150). Dim.A Qty.N 2 Same drilling as for BS 4504 Section 3.2(PN16)and DIN 2532(PN16). Bolt Circle Number of Diameter '-----72---o Bolt Holes f0 0 Dim.B f C� Bolt Hole�o\o_o TABLE A Diameter DIMENSIONAL SPECIFICATIONS FOR SELECTION OF FLANGE DRILLING TFP1020 Page 5 of 20 Valve Accelerator (2-1/2, 3, 4, and 6 When one or more automatic sprin- inch sizes)as detailed in Technical Data klers operate in response to a fire, Sheet TFP1112. air pressure within the system piping Maximum System Air The VIZOR or the ACC-1 is used to is relieved through the open sprin- Water Supply Pressure Range, klers. When the airpressure is suffi- Pressure, psi reduce the time to valve actuation psi following the operation of one or more ciently reduced, the water pressure automatic sprinklers. In some cases overcomes the differential holding 20 10 the Clapper Assembly closed and the 60 15 23 the use of a quick opening device such Clapper Assembly swings clear of the as the VIZOR or the ACC-1 may be required to meet the requirements of water seat, as shown in Figure 3C, 80 20-28 the National Fire Protection Association This action permits water flow into the 100 25-33 to meet water delivery times. system piping and subsequently to be discharged from any open sprinklers. 120 30 38 Also,with the Clapper Assembly open, 145 35-43 Operation the intermediate chamber is pres- 165 40-48 surized and water flows through the The TYCO Model DPV-1 Dry Pipe Valve alarm port(Ref. Figure 3B)at the rear 185 45-53 is a differential type valve that utilizes of the DPV-1 Valve to actuate system a substantially lower system (air or water flow alarms. The flow from the 205 50-58 nitrogen) pressure than the supply alarm port is also sufficient to close the 225 55-63 (water) pressure, to maintain the set otherwise normally open Automatic 250 60-68 position shown in Figure 3A.The differ- Drain Valve in the valve trim. ential nature of the DPV-1 is based on the area difference between the air seat After a valve actuation and upon sub- TABLE B and the water seat in combination with sequent closing of a system main SYSTEM AIR PRESSURE the ratio of the radial difference from control valve to stop water flow, the REQUIREMENTS the Hinge Pin to the center of the Water Clapper Assembly will latch open as Seat and the Hinge Pin to the center of shown in Figure 3D. Latching open of the Air Seat.The difference is such that Continued on page 16 1 psi(0,07 bar)of system air pressure FLOW RATE IN LITRES PER MINUTE(LPM) can hold approximately 5.5 psi (0,38 (1 GPM=3.785 LPM) bar)of water supply pressure. 500 700 1000 2000 3000 5000 10000 Table B establishes the minimum —9.0 I H I I I I l required system air 0,60 q y pressure that o- 7 0 , Or NI 0 0,50 includes a safety factor to help prevent Jill I, II 0,40 false operations that occur due to water 0supply fluctuations. z 5.oIThe Intermediate Chamber of the DPV-1 m4'0 00,�,��iII" Ille�''� 0,30 is formed by the area between the < 3.0 .. ... •? !'i11111111��1111ID,11M111I m o 0 .. `O �uu. ...■ 020 < Air Seat and Water Seat as shown in m ■■••U . !dIIII11111�11iillllllllii111 m ■■000n■■oo V �, rnm ■n� Figure 3B.The Intermediate Chamber m ■■■mm�■■io �n r z p w 2.0 - ..... ...... /Huno 'IIIIll",'/"III'"f1 o_ normally remains at atmospheric o •••••••• �' 1111 1/11111111111 o< pressure through the Alarm Port co .111 •',••• �o covun 1 i UIU..u.0 0,10 m m connection and the valve trim to the z 2,,,,,, o ....MO 0 a, normallyopen Automatic Drain Valve = • _ rm. o "'■" ,, G■■■■""'■■■■■ 0,08 w 0 P o 1.0 ■nonm■ O UP . run . ,nnoun■■o! or co (Fig.4,5,or 6).Having the Intermediate Z O� . 20 O 00:==::E 0,06 con 0 :. .9:: .-. .::..■. -. 0.7 \ ... VZ.::: :u..... 0,05 w u Chamber, Figure 3B, open to atmo- .. ■■ a sphere is critical to the DPV-1 Valve o _ "' _!Holum ■■'■' m MEI !! ^�L_ -�nnm �nn.om■•!!!!i 0,04 a_LIJ remaining set, otherwise the full __ , ,....;� "!!E!!! J a 0 0.5 E _ R% 1111111/i 1H11l. resulting pressure of the system air w iIJilJp,,I r�■■■"'"""""lr•uuul��m■■■===er:��= = 0,03 z`" pressure on top of the Clapper 0.4 11 Assembly cannot be realized. w 03II 0 02 Z For example, and assuming a watero supply pressure of 100 psi(6,9 bar), if _, 0.2 ØJ"iII011I � 1111111111 the system air pressure is 25 psi (1,7z ''Ii I1 11111111111 IIIII 0,01 bar) and there was 15 psi (1,0 bar) ( I WWWIIII " pressure trapped in the Intermediate o Chamber, the resulting pressure Z 0.1 across the top of the Clapper would 100 200 300 500 700 1000 2000 3000 only be 10 psi (0,7 bar).This pressure FLOW RATE IN GALLONS PER MINUTE(GPM) would be insufficient to hold the The approximate friction losses,based on the Hazen and Williams formula and ex- Clapper Assembly closed against pressed in equivalent length of Schedule 40 pipe with C=100 are as follows: a water supply pressure of 100 psi 2.2 feet for the 2-1/2 inch valve at a typical flow rate of 250 GPM (6,9 bar). It is for this reason that the 4.9 feet for the 3 inch valve at a typical flow rate of 350 GPM plunger of the Automatic Drain Valve 8.9 feet for the 4 inch valve at a typical flow rate of 600 GPM must be depressed during several of 22 feet for the 6 inch valve at a typical flow rate of 1500 GPM the resetting steps, as well as during FIGURE 2 inspections, making certain that the MODEL DPV-1 DRY PIPE VALVES Automatic Drain Valve is open. NOMINAL PRESSURE LOSS VS.FLOW TFPI020 Page 6 of 20 AIR PRESSURE WATERFLOW TO SYSTEM TO SYSTEM CLAPPER CLAPPER 1"NPT .� ASSEMBLY ASSEMBLY AIR SUPPLY IN SET FULLY OPEN PORT POSITION `- 01 d .01 I"! • CLAPPER LATCH \ PIVOTS TO ALLOW 1/2"NPT .n�Q' 2 CLAPPER ASSEMBLY •� WATER ' f, TO FULLY OPEN SUPPLY %/ PRESSURE 3/4"NPT ALARMiiiiiiii/ ��II. % i`r PORT OPEN TO ��I .�1% t TEST PORT ATMOSPHERE ,r4iLl -1 ^^' 02 ft V I 03 ALARM PORT WATERFLOW Iw CLAPPER TO ALARM ASSEMBLY FROM FROM WATER SUPPLY AIR WATER SUPPLY SEAT FIGURE 3A %/ FIGURE 3C SET POSITION WATERN OPERATED POSITION SEAT I �� 03 ALARM PORT DRAIN FROM DRAIN FROM SYSTEM SYSTEM VALVEINTERMEDIATE COMPLETE A. WATERWAY CHAMBER PUSH HERE FIGURE 3B TO RESET VALVE SET POSITION INTERMEDIATE RESET ke,t CHAMBER4. KNOB CLAPPER ASSEMBLY LATCHED = RESET �II�I OPEN • i • M� •Z ASSEMBLY CLAPPER / LATCH 6� ---v n•P. PIVOTS TO ' /4000101.111 a CLAPPER UNLATCH //////// //.a.. y LATCH CLAPPER T-T- ASSEMBLY Huh. •_i MAIN DRAIN PORT: ph I 1-1/4"NPT`(2-1/2 INCH CLAPPER OS & 3/4"NPT ^^' 3 INCH VALVES) u h� ASSEMBLY LOW BODY 2" NPT(4 INCH VALVE) 1 RESEATED DRAIN Is3. PORT ro WATER SUPPLY *DN40 FOR VALVES WITH WATER SUPPLY SHUT OFF ISO THREADED PORTS SHUT OFF FIGURE 3D FIGURE 3E DRAIN POSITION RESET POSITION FIGURE 3-PART 1 OF 2 MODEL DPV-1 DRY PIPE VALVES 2-1/2,3,AND 4 INCH(DN65,DN80,AND DN100) SET AND OPEN POSITIONS TFP1020 Page 7 of 20 AIR PRESSURE WATERFLOW TO SYSTEM TO SYSTEM At CLAPPER ASSEMBLY At t FULLY OPEN to :: ate. 1"NPT k CLAPPER LATCH AIR SUPPLY k. PIVOTS TO ALLOW O�- PORT \ aft CLAPPER ASSEMBLY `% '` 01 adTO FULLY OPEN % 3/4" NPT ALARM ' c� CLAPPER � 03 PORT OPEN TO ASSEMBLY ATMOSPHERE g IN SET ��_�������������� A. ,� ,,, POSITION _. ������� 1/2"NPT �, �• WATER SUPPLY ��'' ��' 1. s.�hulL 02 _TEST PORT IWJIIIlli � ALARM PORT WATERFL RW ASSEMBLY AIR CLAPPER a _ :_ TO ALARM FROM SEAT FROM WATER SUPPLY WATER SUPPLY FIGURE 3A . ' FIGURE 3C SET POSITION WATER VAAliv 4,0-.4% �� �� = PORTn OPERATED POSITION SEAT % z,r---L-�. / 1111 1 03 DRAIN FROM DRAIN FROMMilSYSTEM SYSTEM COMPLETE INTERMEDIATE VALVE I CHAMBER FIGURE 3B WATERWAY `i PUSH HERE r SET POSITION TO RESET ,,"''` INTERMEDIATE VALVE CLAPPER '' ASSEMBLY CHAMBER 4 iiti \ _ LATCHED a RESET OPEN KNOB RESET ASSEMBLY _ 3/4"NPT " IMP LOW BODY �0DRAIN �������OD���``� cn t"' � CLAPPERLATCH y70 e, V'= PORT ��� / s PIVOTS TO 04 II //// ; UNLATCH 0 tp`� CLAPPER ������������������ %/.0,1 �_ ASSEMBLY ((�/��;;'"" 2"NPT % . -/% .,�. �% %.^. // 01, CLAPPERMAIN DRAIN 11111kV' 1uiuiV 05 ASSEMBLY I :; ` RESEATED �p: WATER SUPPLY WATER SUPPLY SHUT OFF SHUT OFF FIGURE 3D FIGURE 3E DRAIN POSITION RESET POSITION FIGURE 3-PART 2 OF 2 MODEL DPV-1 DRY PIPE VALVES 6 INCH(DN150) SET AND OPEN POSITIONS TFP1020 Page 8 of 20 NOTES: 1. SEE FIGURE 4 PART 3 FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS LOW AIR AND COMPONENT PART NUMBERS. PRESSURE 2. TRIM SHOWN FULLY ASSEMBLED;COMPONENTS SUCH AS GAUGES AND ALARM SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT INSTALLATION. SWITCH SYSTEM • CONTROL VALVE 1 INCH NPT SYSTEM (NORMALLY CONNECTION AIR SUPPLY 41. _. _ OPEN) FOR LOCAL �_ "� PRESSURE �f � SPRINKLER ^� GAUGE 2 1/2 INCH(DN65) /''�rtrair \ WATERFLOW �/ or 3 INCH(DN80) 1, : PRESSURE 1/2 INCH NPT - •�� ';>''' ►t � MODEL DPV-1 rq ri ALARM CONNECTION �` � - Are.-011 tit ��I�f ' SWITCH 1,-0,,, ? DRY PIPE VALVE .1 � ; FOR SYSTEM �,. , q �, ti. (GxG ONLY) r,� �, /' �C./Ig r /4 a AIR SUPPLY r\ �L- �'it 1 /•I` �i GROOVED `fi��O r� MAIN \�``�Jr•E4 _ COUPLING ALARM --------- .j 41: f Orli'? I Ljv�." �1� fir:/,I , DRAIN VALVE ��r TEST VALVE I �`d lit*- (NORMALLY G i 1 1/2 INCH NPT (NORMALLY • ( T CLOSED) CONNECTION CLOSED) SYSTEM 3/4 INCH NPT SYSTEM , FOR OPTIONAL WATER ........ _-_—_,.../ CONNECTION SHUT-OFF 1-1/4 INCH NPT ACCELERATOR SUPPLY TO DRAIN VALVE CONNECTION PRESSURE (NORMALLY TO DRAIN AUTOMATIC GAUGE LOW BODY OPEN) DRAIN VALVE DRAIN VALVE 1-1/4 INCH NPT (NORMALLYCONNECTION DRIP CLOSED) TO DRAIN FUNNEL FIGURE 4-PART 1 OF 3 2-1/2 AND 3 INCH(DN65 AND DN80)MODEL DPV-1 DRY PIPE VALVE PRE-TRIMMED ASSEMBLY AIR SUPPLY 1/2 INCH NPT 1/2 INCH NPT NOTES: CONTROL VALVE CONNECTION CONNECTION 1. INSTALL TRIM ASSEMBLIES IN (NORMALLY OPEN) FOR OPTIONAL FOR OPTIONAL ALPHABETICAL ORDER. ACCELERATOR AIR PRESSURE AUTOMATIC SWITCH 2. SEE FIGURE 3 FOR VALVE PORT 1/2 INCH NPT DRAIN VALVE IDENTIFICATION. CONNECTION / _ 3. ROUTE 1/4"TUBING TO DRIP FOR SYSTEM 1Y0 a FUNNEL. AIR SUPPLY H 44* (rre o rr SYSTEM (40,i �`. AIR SUPPLY MAIN1��i� ��� �i - PRESSURE DRAIN VALVE 1/2 INCH NPT ,l D GAUGE (NORMALLY CONNECTION G /,3"' A CLOSED) FOR WATERFLOW \ ,111' E _ PRESSURE ALARM ��101 ,�y..� "' �U �_ SWITCH 61,/ `C �7i ((,� `-� l0( ..$149ii 03 - 05 �� DRIP 1-1/4 INCH NPT i -j kVFUNNEL l CONNECTION 0� (� s 1-1/4 INCH NPT TO DRAIN U 'l')! 111 �1 'ILA L �\ CONNECTION �' ! av 2-1/2 INCH(DN65) TO DRAIN 1 INCH NPT O2 or 3 INCH(DN80) CONNECTION i C' MODEL DPV-1 FOR LOCAL C ri 0 DRY PIPE VALVE SPRINKLER a Op, (GxG ONLY) r/cd1 �F /'t-,.. - (-4, LOW BODY ALARM ! �r<>/ B k"� DRAIN VALVE TEST VALVE SYSTEM `` (NORMALLY (NORMALLY WATER SUPPLY 3/4 INCH NPT CLOSED) CLOSED) PRESSURE CONNECTION GAUGE TO DRAIN FIGURE 4-PART 2OF3 2-1/2 AND 3 INCH(DN65 AND DN80)MODEL DPV-1 DRY PIPE VALVE EXPLODED ARRANGEMENT OF SEMI-ASSEMBLED TRIM TFP1020 Page 9 of 20 NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N 1 250 psi/1750 kPa 13 3/32"Vent 281"x 1"x 1/2" Air Pressure Fitting 1 92-032-1-002 Reducing Tee 1 CH Gauge 1 92-343-1-012 14 1/4"Tube, 29 Not Used 2 300 psi/2000 kPa 18"Long 1 CH PIPE NIPPLES: Water Pressure 15 1/4"Plug 2 CH 30 1/4"x 3" 2 CH Gauge 1 92-343-1-005 16 1/2"Plug 2 CH 31 1/2"x Close 4 CH 3 1/4"Gauge Test 17 1"Plug 1 CH 32 1/2"x 1-1/2" 8 CH Valve 2 46-005-1-002 18 1/2"Union 1 CH 33 1/2"x 2" 1 CH 4 Model AD-1 19 1/2"x 1/4"Reducing 34 1/2"x 4-1/2" 1 CH Automatic Bushing 1 CH 35 1/2"x 6" 1 CH Drain Valve 1 52-793-2-004 20 1/2"90°Elbow....3 CH 36 3/4"x Close 1 CH 5 1/4"Pressure 21 3/4"90°Elbow....1 CH 37 3/4"x 1-1/2" 1 CH Relief Valve 1 92-343-1-020 22 1-1/4"90°Elbow... 1 CH 38 3/4"x 2-1/2" 1 CH 6 1/2"Ball Valve ....2 46-050-1-004 23 1/2"Cross 2 CH 39 1"x Close 1 CH 7 3/4"Angle Valve... 1 46-048-1-005 24 1/2"x 1/2"x 1/4" 40 1-1/4"x Close . ...1 CH 8 1-1/4"Angle Valve .1 46-048-1-007 Reducing Tee 1 CH 41 1-1/4"x 4" 1 CH 9 1/2"Swing 25 1/2"Tee 1 CH COMPONENTS INCLUDED ONLY IN Check Valve 2 46-049-1-004 26 1/2"x 1/4"x 1/2" PRE-TRIMMED VALVE ASSEMBLIES: 10 Drip Funnel Reducing Tee 2 CH Connector 1 92-211-1-005 27 1/2"x 1/2"x 3/4" 42 Model BFV-N 11 Drip Funnel Reducing Tee 1 CH Butterfly Valve, Bracket 1 92-211-1-003 2-1/2"(DN65) 1 59300F025N 12 Drip Funnel 1 92-343-1-007 3"(DN80) 1 59300F030N 45 43 Figure 577 Coupling, 2-1/2"(DN65) 1 57725ACP 16 3"(DN80) 1 57730ACP �� _ 44 Waterflow Pressure 20 . 1 Alarm Switch, WX _ \>\\ /j�/c 19 Model PS10-2 1 25710 �� 32 --c)-- - 45 Low Air Pressure 6 vvI 32 � � 30 (0 Alarm Switch, 5 32 . ., •0 23 /�'" � Model PS40-2 1 25730 le. y` 32 itil \* i 24 ll, '� 17 32 p� Ol�l Y 15 20 a, Il 341 " 39 3 VA 1 28 44 ��J, '\\ 33 r 2-1/2 INCH(DN65) ` ' or 3 INCH(DN80) 9 O 16 4 MODEL DPV-1 25 O 31 27 E DRY PIPE VALVE' �� v_ ,\\1�i 1 (GxG ONLY) 31 LOCATION '�' \\ t 23 36 FOR OPTIONAL 1: V ELECTRICALLY \\' 10 ( �� 41 (t\�U) 8 '.,!� SUPERVISED 32 �� • ` �_ 31 N.O.ALARM 20 0f 22 �• CONTROL 11 �� 05 40 %i ♦�, c. 26 O VALVE �/� 1 �� �n1� ♦, 13 ry 12 37 NOTES: (GREEN ' �a ��� TINT) 14 21 ��/(� 011h� 0-1.1*—) �, 43 1. SEE FIGURE 3 FOR VALVE I f A PORT IDENTIFICATION. //, 38 ���Y: p2 ��I�1� 31 �•i„ 7 f \\ 42 2. ROUTE 1/4"TUBING,ITEM 14, ft 6 ,� ;, rr 0111.11°0 TO DRIP FUNNEL,ITEM 12. % \\ • / 1(� 3. ALL FITTINGS AND NIPPLES 32 14 35 x. 141 �// V ARE GALVANIZED. 26 /'`, 2 `'� Iy i`b 4. CH:COMMON HARDWARE 30 Y ', `1 5. ITEMS 42-45 INCLUDED 3 •;4- ' % 15 ( ONLY IN PRE-TRIMMED VALVE ASSEMBLIES AS APPLICABLE;OTHERWISE SEPARATELY ORDERED. FIGURE 4-PART 3 OF 3 2-1/2 AND 3 INCH(DN65 AND DN80)MODEL DPV-1 DRY PIPE VALVE EXPLODED ARRANGEMENT OF VALVE TRIM TFP1020 Page 10 of 20 1. SEE FIGURE 5 PART 3 FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS LOW AIR AND COMPONENT PART NUMBERS. PRESSURE 2. TRIM SHOWN FULLY ASSEMBLED;COMPONENTS SUCH AS GAUGES AND ALARM SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT INSTALLATION. SWITCH SYSTEM AIR SUPPLY , /�/ CONTROL VALVE 1/2 INCH NPT SYSTEM 4 INCH(DN100) (NORMALLY CONNECTION AIR SUPPLY MODEL DPV-1 OPEN) FOR SYSTEM PRESSURE DRY PIPE VALVE < ,--- AIR SUPPLY �� GAUGE (FxG SHOWN) I. '1 , 3/4 INCH NPT r, - `,` ��� CONNECTION 1 INCH NPT��.4l r �i . FLANGE ADAPTER FOR WATER CONNECTION 1)� � 41--, 4"' OR GROOVED ! If MOTOR ALARM FOR LOCAL _�,�``�' 4 ? COUPLING ;( )„" )�`, SPRINKLER 0 - 1 / fiI/I," r \ WATERFLOW •,r. �)rill.,I1W4 ; ( MAIN 'SOA' �•-tei 1`'�\\ PRESSURE ��' ,` �'� DRAIN VALVE _ :.� ALARM 3/4 INCH NPT ��� jCONNECTION ��� � (� (NORMALLY �►���� �0 SWITCH TO DRAIN `,-, ! ,I 7- CLOSED) �frh,:)/ ``1 1/2 INCH NPT / „ lyMr �0t1,1/ CONNECTION ( FOR OPTIONAL TSAV VE RM ��\ 2 INCH NPT ....'"•—• ACCELERATOR (NORMALLY SYSTEM CONNECTION LOW BODY SYSTEM SHUT-OFF TO DRAIN AUTOMATIC CLOSED) DRAIN VALVE WATER VALVE DRAIN VALVE (NORMALLY SUPPLY (NORMALLY CLOSED) PRESSURE OPEN) 1-1/4 INCH NPT CONNECTION DRIP GAUGE TO DRAIN FUNNEL FIGURE 5-PART 1 OF 3 4 INCH(DN100)MODEL DPV-1 DRY PIPE VALVE PRE-TRIMMED ASSEMBLY 1 : 1/2 INCH NPT AIR SUPPLY �� CONNECTION CONTROL VALVE FOR OPTIONAL (NORMALLY MAIN i +t�t-( tilt,, ACCELERATOR OPEN) 1/2 INCH NPT SYSTEM DRAIN VALVE Ffli, ��;s CONNECTION �a AUTOMATIC AIR SUPPLY (NORMALLY o 6_4,7 1/2 INCH NPT FOR OPTIONAL CONNECTION DRAIN VALVE AIR PRESSURE PRESSURE CLOSED) FOR WATERFLOW SWITCH GAUGE PRESSURE ALARM \ � SLOPE DOWN SWITCH / D I�) -, \ �i �I� 3/4 INCH NPT �,� CONNECTION ,,„ �111�� _ , �, FOR WATER 10�� �� > A = � /�/ MOTOR ALARM �% , ce,`�� \ 1�, 03 05 u1�� Z�f((p `%��`•, �< i 2 INCH NPT 1/2 INCH NPT "NJ /� I lv> j^'U p1 f ro �, CONNECTIONO DRAIN CONNECTION �!t(' FOR SYSTEM * I �'Ai-- ow,,-„,,,,,, <„ I AIR SUPPLY ----4 �� . �" „- r (� ��� 1 � ' ���; ol, 4 INCH(DN100) ♦'�� �i MODEL DPV-1 ALARM ���� O� �o - 01� DRY PIPE VALVE TEST VALVE '4P4 ! TFP1020 Page 11 of 20 _ 47 NOTES: 16 48 1. SEE FIGURE 3 FOR VALVE 4 ,�' ,iy 28 �� PORT IDENTIFICATION. "i� C/13 .' 18 =o h\ k, •�' 4 5 ,. ;,, 2. ROUTE 1/4"TUBING,ITEM 16, S L k�� 34 !` ; v1 15 27TO DRIP FUNNEL,ITEM 14. (GREEN g = ��C TINT) _ 00 3. SLOPE 3/4"ANGLE VALVE, SLOPE DOWN 29 �1 �`\1\ /'•//P ��~ 34 18 111 12 14 ITEM 9,DOWN TOWARD .i BACK OF VALVE TO ®1 34 8 l //Iij� O 26 O, '`" n FACILITATE SUFFICIENT 19 'l\,�� 34 IC Q� 34 LOW BODY DRAINAGE. i `7 /� 27 4. ALL FITTINGS AND NIPPLES LOCATION �` tali, 30 36 � 1 0 '�/ ARE GALVANIZED. FOR OPTIONAL j� ; 5. CH:COMMON HARDWARE WO�i 21 t, ;7, ELECTRICALLY e1111� ��C ��((e 32 "'• 17 13 6. ITEMS 45-48 INCLUDED SUPERVISED N.O.ALARM 41 r � � 30 ,- 3 ONLY IN PRE-TRIMMED �� !��; VALVE ASSEMBLIES AS CONTROL O p)ll�� 39 40 �l�%' L------"S �, VALVE r,1•.►1 10 ((�` O APPLICABLE;OTHERWISE 11``�� / SEPARATELY ORDERED. ��11�� 39 04 23 3 Al 30 �ll�ll 40 ��� 4 INCH(DN100) 24 34 (-410 34 V 43 �- MODEL DPV-1 � c�a�-4} 01 ) I (-0 4 DRY PIPE VALVE 33 •(� `av, 42 31 IV �� 0}:: I (t (FxG SHOWN) Oyu �i 25 ///e '�+r 7 9 20 �`�1 l �\z�o� i' 11�1 33 cf''- 38 0Z -lam ,gp 46 �1AD ✓���� 05 �1 11 NO. DESCRIPTION QTY. P/N 40 22 (1-0 2 " 44 1 250 psi/1750 kPa 28 '' = 3 —_ 45 Air Pressure Gauge 1 92-343-1-012 35 a�"f,-, I�- 2 300 psi/2000 kPa 32 .`% 17 Water Pressure ` %, '� Gauge 1 92-343-1-005 �� 441.4 ;�A3 1/4"Gauge Test Valve 2 46 005-1-002NO. DESCRIPTION QTY. P/N 4 1/4"Pressure 21 1/2"x 1/4" Reducing Relief Valve 1 92-343-1-020 Bushing 1 CH 5 1/2"Angle Valve...1 46-048-1-004 22 1/2"Union 1 CH NO. DESCRIPTION QTY. P/N 6 Model AD-1 23 3/4"Union 1 CH 41 3/4"x 2" 1 CH Automatic24 1/2"90°Elbow....1 CH 42 3/4"x 3" 1 CH Drain Valve 1 52-793-2-004 25 1/2"45°Elbow....1 CH 7 1/2"Ball Valve ....1 46-050-1-004 26 1/2"Cross 1 CH 43 1"x 4" 1 CH 8 1/2"Swing 27 1/2"Tee 2 CH 44 2"x 4 1/2" 1 CH Check Valve 1 46-049-1-004 28 1/2"x 1/4"x 1/2" COMPONENTS INCLUDED ONLY IN 9 3/4"Angle Valve... 1 46-048-1-005 Reducing Tee 2 CH PRE-TRIMMED VALVE ASSEMBLIES: 10 3/4"Swing 29 1/2"x 1/2"x 1/4" 45 Model BFV-N Butterfly Check Valve 1 46-049-1-005 Reducing Tee 1 CH Valve,4"(DN100)..1 59300F040N 11 2"Angle Valve ....1 46-048-1-009 30 3/4"x 1/2"x 3/4" 46 Butterfy Valve 12 Drip Funnel Reducing Tee 3 CH AssemblyComponent: Connector 1 92-211-1-005 31 1"x 1"x 1/2" GxG DPV-1 Valves, 13 Drip Funnel Reducing Tee 1 CH Figure577 Coupling, Bracket 1 92-211-1-003 PIPE NIPPLES: 4"(DN100) 1 57740ACP 14 Drip Funnel 1 92-343-1-007 32 1/4"x 3" 2 CH FxF,FxG DPV-1 Valves, 15 3/32"Vent 33 1/2"x Close 2 CH Figure 71 Flange Adapter, Fitting 1 92-032-1-002 34 1/2"x 1-1/2" 7 CH 4"(DN100) 1 7140S 16 1/4"Tube, 35 1/2"x 2" 1 CH 47 Waterflow Pressure 24"Long 1 CH 36 1/2"x 2-1/2" 1 CH Alarm Switch, 17 1/4"Plug 2 CH 37 1/2"x 3" 1 CH Model PS10-2 1 25710 18 1/2"Plug 2 CH 38 1/2"x 3-1/2" 1 CH 48 Low Air Pressure 19 3/4"Plug 1 CH 39 3/4"x Close 2 CH Alarm Switch, 20 1"Plug 1 CH 40 3/4"x 1-1/2" 2 CH Model PS40-2 1 25730 FIGURE 5-PART 3 OF 3 4 INCH(DN100)MODEL DPV-1 DRY PIPE VALVE EXPLODED ARRANGEMENT OF VALVE TRIM TFP1020 Page 12 of 20 NOTES: 1. SEE FIGURE 6 PART 3 FOR TRIM ARRANGEMENT WITH BILL OF MATERIALS LOW AIR AND COMPONENT PART NUMBERS. PRESSURE 2. TRIM SHOWN FULLY ASSEMBLED;COMPONENTS SUCH AS GAUGES AND ALARM / SWITCHES MAY REQUIRE ASSEMBLY IN TRIM AT INSTALLATION. SWITCH SYSTEM !— AIR SUPPLY `� / CONTROL VALVE SYSTEM (NORMALLY AIR SUPPLY ,_ OPEN) PRESSURE � ,•, 1/2 INCH NPT GAUGE 4111. 1f.: j LOW BODY CONNECTION c SYSTEM `, FOR SYSTEM �'' WATER APP R W� .:' DRAIN VALVE �.,� (NORMALLY AIR SUPPLY \igiVI,\j� /^/ PRESSURE r V CLOSED) 1 INCH NPT j t 4- , J��i��( GAUGE ( ipiAl • O� ;:,t , AUTOMATIC CONNECTION ��'�' / �`I�ai,_ ( � GROOVED v� r� DRAIN VALVE FOR LOCAL ,, �J I � SPRINKLER ,�� A . � s COUPLING / �1�' �'��17,� OR FLANGE �I �11! " �1a-i P`` 1/2 INCH NPT �� "t~r.„ .�:, ,�'� ",�� CONNECTION DRIP FUNNEL `-" �� -- ADAPTER ,440.444+7�� �� i``‘7).• \ 4,� I, ,'art; t FOR OPTIONAL \' I - ` ACCELERATOR MAIN /t� ( l�� DRAIN VALVE1 t11 TEST AVALVE• ` 1-1/4 INCH NPT RM (NORMALLY 2 INCH NPT \ SYSTEM (NORMALLY WATERFLOW CONNECTION CLOSED) CONNECTION 6 INCH(DN150) SHUT-OFF CLOSED) 3/4 INCH NPT PRESSURE TO DRAIN TO DRAIN MODEL DPV-1VALVE CONNECTION ALARM DRY PIPE VALVE (NORMALLY FOR WATER SWITCH (GxG SHOWN) OPEN) MOTOR ALARM FIGURE 6-PART 1 OF 3 6 INCH(DN150)MODEL DPV-1 DRY PIPE VALVE PRE-TRIMMED ASSEMBLY 1/2 INCH NPT 1/2 INCH NPT NOTES: B 1' CONNECTION CONNECTION 4. SLOPE 3/4"ANGLE VALVE AND r G1 FOR OPTIONAL FOR SYSTEM 3/4"x 4-1/2"NIPPLE(OF ASSEMBLY B) ,lYli'IE tel. SYSTEM AIR PRESSURE AIR SUPPLY INTO DRIP FUNNEL TO FACILITATE SWITCH SUFFICIENT LOW BODY DRAINAGE. Ili AIR SUPPLY AIR SUPPLY DRIP _ PRESSURE :711 \ `f'/ CONTROL VALVE LOW BODY 1/2 INCH NPT FUNNEL SLOPE GAUGE C (NORMALLY DRAIN VALVE CONNECTION ��it �c r, OPEN) (NORMALLY FOR OPTIONAL TO FIT 1 INCH NPT ' Y 1/2 INCH NPT u•1�, 1, CLOSED) ACCELERATOR CONNECTION >) �/ CONNECTION FOR LOCAL --_ � A / AUTOMATIC FOR WATERFLOW SPRINKLER �'' /` • 4r. ,l ,;, DRAIN VALVE PRESSURE ALARM .''4 �� o �� o I \ SWITCH I%Ifi Ol © • o ;e\l�\ B 3/4 INCH NPT 0 0 ,-, CONNECTION MAIN // i FOR WATER DRAIN VALVE \- 7-)(( �P(q \ ,'1 MOTOR ALARM NORMALLY 05 �� 1� � (CLOSED) �; �' ���� r� 2 INCH NPTwirer CONNECTION 6 INCH(DN150)I/ �, i TO DRAIN MODEL DPV-1 DRIP ��� C DRY PIPE VALVE �' �� FUNNEL (FxF SHOWN) ���1 Q�j"s �� �� NOTES: OZ _ ,1.�,i��0 G 1. INSTALL TRIM ASSEMBLIES IN ) • ALPHABETICAL ORDER. •,((C ;r \ ALARM 2. SEE FIGURE 3 FOR VALVE PORT 1-1/4 INCH NPT SYSTEM TEST VALVE IDENTIFICATION. CONNECTION WATER SUPPLY (NORMALLY 3. ROUTE 1/4"TUBING TO DRIP TO DRAIN PRESSURE CLOSED)GAUGE FUNNEL. FIGURE 6-PART 2OF3 6 INCH(DN150)MODEL DPV-1 DRY PIPE VALVE EXPLODED ARRANGEMENT OF SEMI-ASSEMBLED TRIM TFP1020 Page 13 of 20 9 ('ll OF q NOTES: 1. SEE FIGURE 3 FOR VALVE 4. ALL FITTINGS AND NIPPLES '- (441 t�[ii VALVE 29 PORT IDENTIFICATION. ARE GALVANIZED. 42 _-_� (`�, 35 2. ROUTE 1/4"TUBING,ITEM 16, 5. CH:COMMON HARDWARE 14 /� � / 5 TO DRIP FUNNEL,ITEM 14. 6. ITEMS 45-48 INCLUDED 18 ,;,` 3. SLOPE 3/4"ANGLE VALVE, ONLY IN PRE-TRIMMED SLOPE 111 48 V1 a ' IA7 ITEM 9,AND 3/4"x 4-1/2" VALVE ASSEMBLIES AS TO FIT Rik 35 NIPPLE, ITEM 42,INTO APPLICABLE;OTHERWISE 26 p �' DRIP FUNNEL,ITEM 14,TO SEPARATELY ORDERED. 1 21 0 alp* ' 8 ;fir''•) FACILITATE SUFFICIENT 15 Q �4 ,� 40 LOW BODY DRAINAGE. (GREEN LOCATION �� i.' 3 _ 35 ((�e ;a„r 18 TINT) FOR OPTIONAL a. �� << 35 ° - ELECTRICALLY 17 '40 r(� _ 35 9 30 ��Ii/c ��” 33 �� `O 42 6 ��� 27 .'0, 023 SUPERVISED (♦ 43 16 f 47 N.O.ALARM ;il! 11 20 27 �4r!a `C CONTROL fll ► 32 4*. (`�D. ii 35 31 28 37��,ire VALVE *� �� 44 01 bll��� (' /d /' 40 31 �t , J \\ % o:, ,'� 10 � 0� ��� (r, 40 �/� 40 �llh elle U .., L., 05 , ll tO�',• 40 1 � r 41 19 6 INCH(DN150) ,� �ll� 23 ~L !(�� O MODEL DPV-1 DRY PIPE VALVE ��i�� 1 03 42 ilio-ii 12 � (G1 (GxG SHOWN) ,i _�� I 40 ?/e ��/J 13 31 NO. DESCRIPTION QTY. P/N �_� �, 39 35 '� 24 1 250 psi/1750 kPa ,� OZ f$ 22 14 7 38 11 rjl' 34 Air Pressure ee 36 35 01/ 25 Gauge 1 92-343-1-012 it 2 300 psi/2000 kPa �' 28 ���d 2 it °��$ Water Pressure ��� 1rB ;���� Gauge 1 92-343-1-00571 I 3 1/4"Gauge Test `V� ;: .. .J � Valve 2 46-005-1-002 �1� ,v 33 4 1/4"Pressure 46 11111111.4)1 3 Relief Valve 1 92-343-1-020 17 NO. DESCRIPTION QTY. P/N 5 1/2"Angle Valve...1 46-048-1-004 45 35 1/2"x 1-1/2" 8 CH 6 Model AD-1P) // 36 1/2"x 2" 1 CH Automatic ' - 37 1/2"x 2-1/2" 1 CH Drain Valve 1 52-793-2-004 ' 38 1/2"x 3" 1 CH 7 1/2"Ball Valve .... 1 46-050-1-004 � � 39 1/2"x 6" 1 CH 8 1/2"Swing �' i 40 3/4"x 1-1/2" 5 CH Check Valve 1 46-049-1-004 1 41 3/4"x 2" 1 CH 9 3/4"Angle Valve... 1 46-048-1-005 r '` . 42 3/4"x 4-1/2" 2 CH 10 3/4"Swing ,) 43 1"x 4" 1 CH Check Valve 1 46-049-1-005 44 2"x 4-1/2" 1 CH 11 2"Angle Valve ....1 46-048-1-009 12 Drip Funnel COMPONENTS INCLUDED ONLY IN Connector 1 92-211-1-005 PRE-TRIMMED VALVE ASSEMBLIES: 13 Drip Funnel NO. DESCRIPTION QTY. P/N 45 Model BFV-N Butterfly Bracket 1 92-211-1-003 25 1/2"45°Elbow....1 CH Valve,6"(DN150)..1 59300F060N 14 Drip Funnel 1 92-343-1-007 26 1/2"Cross 1 CH 46 Butterfy Valve 15 3/32"Vent 27 1/2"Tee 2 CH Assembly Component: Fitting 1 92-032-1-002 28 1/2"x 1/4"x 1/2" GxG DPV-1 Valves, 16 1/4"Tube, Reducing Tee 2 CH Figure 577 Coupling, 24"Long 1 CH 29 1/2"x 1/2"x 1/4" 6"(DN150) 1 57760ACP 17 1/4"Plug 2 CH Reducing Tee 1 CH FxF,FxG DPV-1 Valves, 18 1/2" Plug 2 CH 30 3/4"90°Elbow....1 CH Figure 71 Flange Adapter, 19 3/4"Plug 1 CH 31 3/4"x 1/2"x 3/4" 6"(DN150) 1 7160S 20 1"Plug 1 CH Reducing Tee 3 CH 47 Waterflow Pressure 21 1/2"x 1/4"Reducing 32 1"x 1"x 1/2" Alarm Switch, Bushing 1 CH Reducing Tee 1 CH Model PS10-2 1 25710 22 1/2"Union 1 CH PIPE NIPPLES: 48 Low Air Pressure 23 3/4"Union 1 CH 33 1/4"x 3" 2 CH Alarm Switch, 24 1/2"90°Elbow....1 CH 34 1/2"x Close 1 CH Model PS40-2 1 25730 FIGURE 6-PART 3 OF 3 6 INCH(DN150)MODEL DPV-1 DRY PIPE VALVE EXPLODED ARRANGEMENT OF VALVE TRIM TFP1O2O Page 14 of 20 7-1/8" 9" 14-7/8" 9-1/4" f- (180 mm) (230 mm) (380 mm) (235 mm) RI'U a ■w■ : 2-1/2&3 INCH ii ' (DN65&DN80) / VALVE ■�■ r .�. 20-7/16" ���'� r (520 mm) - ■■I'■' II 16-1/8" 011ie alle , :, (409,6 mm) • •11 1•I���= 2-1/2or3INCH ,, •—• rd b, kuII-01!I■I-� Oii74 VALVES l 4'�1.i, MI DqP'wits - i'l IrE3111FINII liej 12" 6" 12" _ 14" (300 mm) I (150 mm) (300 mm) (355 mm) a� C �� ,, . 4 INCH i �111 01i , ILII y'i!-) m (DN100) • VALVE l (555 mm) _ IF L.* \.'r,, I �,■-.-'� D P L. 18-5/16" grie ,..lIIML./46 • lj A 465 mm) fez' _ =_cam� ��_� .I�■=ol:0mI �- ,i' ( (..710_::0•'_ .I.I, I -.�111 1 4 11-1/2" 7-1/4" 15" 14-3/4" (290 mm) (190 mm) (380 mm) (375 mm) ■ CO6 INCH �� (DN150) I �1.� ■ 1 .•, VALVE • * • �� ■•■ 1= 24-1/2" �I�� h .,I I. (620 mm) !� 1-'7,1i Wim 217/8„ iI..„.;��WI � (-01'i ���� db `. (555,6 mm) 11141111011=1"tii■riii.o.„. ::i. ��� wig =�,4/1.'D - - __ - \v__-// FIGURE 7-PART 1 OF 2 MODEL DPV-1 DRY PIPE VALVE INSTALLATION DIMENSIONS,PRE-TRIMMED VALVE TFP1O2O Page 15 of 20 6-3/4" 8" 14-7/8" 9-1/4" (170 mm) (200 mm) (380 mm) (235 mm) U A. ..L I 0 2-1/2&3 INCH a41.11' 1.m � C■ . 16-9/16" ori il1-_,, � (DN65&DN80) (420,7 mm) VALVE �� 12-1/4" - to (311,2 mm) ovr,...m.' ' °11 'I 2 1/2 or 3 INCH u■i_11 4'1.1`■"1i-1 VALVES ,1t _ il ■11-01■1imi � ._ I I -�d b j'\ 6„ III (150 mm) IA.. t 12" _ 6" (300 mm) (150 mm) 12 14" (300 mm) (355 mm) 1 ! © 4INCH ! - - iliii:l�I,mi ::1 I (440 mm) I1111 =:•,it-II (DN100) VALVE , :��_ 1 �� -1; FxF:13-5/8"(346,1 mm) 1��•ilt • • NM I* i II-i FxG:13-11/16"(347,7 mm) •nl db GxG: 13-3/4"(349,3 mm) ar .010=c111.1•1111.114511. I •11E'Ll=11111N 111111 apiwomoll 11W I 2-1/2"(65 mm) - f 11-1/2" 7-1/4" 15" 14-3/4" (290 mm) (190 mm) (380 mm) (375 mm) 6 INCH ! �� ! © �� (DN150) �;iIii � iillii ju. 18-3/4" 1111111::,!,•, VALVE • (475 mm) • _ * 16" 1' (406,4 mm) cr. ioi y FxF,FxG, ,T..--,, I or GxG an moo r1i • I 11160 Hell11.111 ._lelli. db IIII IV 4-1/2" � (115 mm) - f FIGURE 7-PART 2 OF 2 MODEL DPV-1 DRY PIPE VALVE INSTALLATION DIMENSIONS, VALVE AND SEMI-ASSEMBLED TRIM TFP1020 Page 16 of 20 the DPV-1 will permit complete draining • The main drain and drip funnel drain of the system (including any loose may be interconnected provided Valve Setting scale)through the main drain port. a check valve is located at least Procedure 12 inches (300 mm) below the drip During the valve resetting procedure funnel. The Low Body Drain Valve and after the system is completely (Figure 4,5,or 6)may be piped so as Steps 1 through 11 are to be performed drained,the external reset knob can be when initially setting the Model DPV-1 to discharge into the Drip Funnel or to Dry Pipe Valve;after an operational test easily depressed to externally unlatch a separate drain. the Clapper Assembly, as shown of the fire protection system; or, after in Figure 3E. As such, the Clapper • Suitable provision must be made system operation due to a fire. Assembly is returned to its normal set for disposal of drain water. Drainage NOTES:If the DPV-1 is equipped with position to facilitate setting of the dry water must be directed such that it a Dry Pipe Valve Accelerator,refer to its pipe sprinkler system,without having to will not cause accidental damage to resetting instructions before resetting remove the Handhole Cover. property or danger to persons. the DPV-1. Refer to TFP1105 for the • Unused pressure alarm switch and/or VIZOR or TFP1112 for the ACC-1. Installation water motor alarm connections must Based on the instructions provided, be plugged. reset the Accelerator at the appropriate General Instructions • The Pressure Relief Valve provided time during the resetting of the DPV-1. Proper operation of the Model DPV-1 with the Valve Trim is factory set to Unless otherwise noted,refer to Figure Dry Pipe Valve depends upon its trim relieve at a pressure of approximately 4, 5, or 6 to identify functional trim being installed in accordance with the 45 psi(3,1 bar),which can typically be components. instructions given in this Technical Data used for a maximum normal system Sheet.Failure to follow the appropriate air pressure of 40 psi (2,8 bar).The Step 1.Close the Main Control Valve, trim diagram may prevent the DPV-1 Pressure Relief Valve may be reset to and close the Air Supply Control Valve. Valve from functioning properly, as a lower or higher pressure; however, If the DPV-1 is equipped with a Dry well as void listings,approvals,and the it must be reset to relieve at a pres- Pipe Valve Accelerator,remove the Dry manufacturer's warranties. sure which is in accordance with the Pipe Valve Accelerator from service Failure to latch open the Clapper requirements of the authority having in accordance with its Technical Data Assembly prior to a system hydro- jurisdiction. Sheet(Refer to TFP1105 for the VIZOR static test may result in damage to the To reset the Pressure Relief Valve, or TFP1112 for the ACC-1). Clapper Assembly. first loosen the jam nut and then Step 2.Open the Main Drain Valve and The DPV-1 Valve must be installed in a adjust the cap accordingly — clock- all auxiliary drains in the system.Close readily visible and accessible location. wise for a higher pressure setting the auxiliary drain valves after water or counter-clockwise for a lower ceases to discharge. Leave the Main The DPV-1 Valve and associated trim pressure setting. After verifying the Drain Valve open. must be maintained at a minimum desired pressure setting,tighten the Step 3. Depress the plunger of the temperature of 40°F(4°C), jam nut. Automatic Drain Valve to verify that Heat tracing of the DPV-1 Valve or its • Installation of an Air Maintenance it is open and that the DPV-1 Valve is associated trim is not permitted. Heat Device,as described in the Technical completely drained. tracing can result in the formation of Data Section,is recommended. Step 4. Open the Optional Alarm hardened mineral deposits that are capable of preventing proper operation. • An Inspector's Test Connection Control Valve, as applicable, if it was as required By NFPA 13 must be closed to silence local alarms. The Model DPV-1 Dry Pipe Valve is provided on the system piping at the Step 5.As necessary,replace all sprin to be installed in accordance with the most remote location from the Model klers that have operated. Replacement following criteria: DPV-1 Valve. sprinklers must be of the same type • All nipples,fittings,and devices must • Conduit and electrical connections and temperature rating as those which be clean and free of scale and burrs are to be made in accordance with have operated. before installation. Use pipe thread the requirements of the authority sealant sparingly on male pipe having jurisdiction and/or the National NOTICE threads only. Electric Code. In order to prevent the possibility of • The DPV-1 Valve must be trimmed • Before a system hydrostatic test is a subsequent operation of an over- in accordance with Figures 4, 5, performed in accordance with NFPA heated solder type sprinkler,any solder or 6, as applicable. If the DPV-1 13 system acceptance test require- type sprinklers which were possibly is to be equipped with a Dry Pipe ments, the Clapper Assembly is exposed to a temperature greater than Valve Accelerator, refer to the to be manually latched open (Ref. their maximum rated ambient must be Technical Data Sheet TFP1105 for Figure 3D);the Automatic Drain Valve replaced. the VIZOR Electronic Dry Pipe Valve (Figure 4,5,or 6)is to be temporarily Step 6. Push down on the Reset Accelerator or TFP1112 for the Model replaced with a 1/2 inch NPT plug,the Knob(Figure 3E)to allow the Clapper ACC-1 Mechanical Dry Pipe Valve 3/32 inch Vent Fitting(Item 13,Figure Assembly to re seat. Accelerator. 4;Item 15,Figure 5;or Item 15,Figure • Care must be taken to make sure that 6)is to be temporarily replaced with a Step 7.Pressurize the system with air check valves,strainers,globe valves, 1/4 inch NPT plug,and the Handhole (or nitrogen) to 10 psi (0,7 bar), and etc.are installed with the flow arrows Cover Bolts are to be tightened using then individually open all auxiliary drain in the proper direction. a cross-draw sequence. valves in the system piping to drain any remaining water in trapped sections. • Drain tubing to the drip funnel must Close each drain valve as soon as be installed with smooth bends that water ceases to discharge. will not restrict flow. TFP102O Page 17 of 20 Also partially open the Low Body work on the fire protection system that sub-section Steps 2 through 5 for Drain Valve to assure that the riser is it controls,permission to shut down the instructions with regard to the inspec- completely drained. Close the Low affected fire protection system must be tion of the Clapper Facing. Body Drain Valve as soon as water obtained from the proper authorities ceases to discharge. and notify all personnel who may be Quarterly Waterflow Step 8. Refer to Table B and then affected by action. Alarm Test Procedure restore the system to the normal The owner is responsible for the sThouldg bef the system quarwateteow alarms system air pressure as necessaryto inspection, testing, and mainte- should er performed quarterly.th To testm p 9. the waterflow alarm, open the Alarm hold the DPV-1 Valve closed. nance of their fire protection system Test Valve, which will allow a flow of and devices in compliance with this water to the Waterflow Pressure Alarm Step 9. Depress the plunger on the Automatic Drain Valve to make sure document, as well as with the appli- Switch and/or Water Motor Alarm. it is open and that there is no air cable standards of the National Fire Upon satisfactory completion of the discharging. Protection Association (e.g., NFPA test,close the Alarm Test Valve. 25), in addition to the standards of any The absence of air discharging from authority having jurisdiction. Contact Water Pressure Inspection the Automatic Drain Valve is an indica- the installing contractor or sprinkler The Water Pressure Gauge is to be tion of a properly set air seat within the manufacturer regarding any questions. inspected monthly (per NFPA 25) DPV-1 Valve.If air is discharging, refer to ensure that normal system water to the Care and Maintenance section Automatic sprinkler systems are recom- pressure is being maintained. under Automatic Drain Valve Inspection mended to be inspected, tested, and to determine/correct the cause of the maintained by a qualified Inspection Air Pressure Inspection leakage problem. Service in accordance with local The Air Pressure Gauge is to be requirements and/or national codes. inspected monthly (per NFPA 25) to Step 10.Partially open the Main Control The operational test procedure ensurethatnormal system air pressure is being Valve.Slowly close the Main Drain Valve maintained. as soon as water discharges from the and waterflow pressure alarm test drain connection. procedure will result in operation of Automatic Drain Valve Inspection the associated alarms.Consequently, The Automatic Drain Valve should be Depress the plunger on the Automatic notification must first be given to the inspected monthly (per NFPA 25) by Drain Valve to make sure that it is open owner and the fire department,central depressing the plunger and checking to and that there is no water discharging. station,or other signal station to which ensure that the Automatic Drain Valve The absence of water discharging from the alarms are connected. is not discharging water and/or air. A the Automatic Drain Valve is an indica- discharge of water and/or air is an indi- tion of a properly set water seat within Annual Operation Test Procedure cation that the air and/or water seats the DPV-1 Valve.If water is discharging, Note:Unless otherwise noted, refer to are leaking,which could subsequently refer to the Care and Maintenance Figure 4, 5, or 6 to identify functional cause a false operation should the section under the Automatic Drain trim components. intermediate chamber become inad- Valve Inspection to determine/correct Proper operation of the DPV-1 Valve vertently pressurized. the cause of the leakage problem. (i.e.,opening of the DPV-1 Valve during If leakage is present, take the DPV-1 If there are no leaks,the DPV-1 Valve is afire condition) should be verified at Valve out of service(i.e.,close the main ready to be placed in service and the least once a year as follows: control valve, open the main drain Main Control Valve must then be fully Step 1.If water must be prevented from valve,close the air supply control valve, opened. flowing beyond the riser, perform the remove the Dry Pipe Valve Accelerator Note: After setting a fire protection following steps. from service, as applicable, in accor- system, notify the proper authorities • Close the Main Control Valve. dance with its Technical Data Sheet and advise those responsible for moni (Refer to TFP1105 for the VIZOR or toring proprietary and/or central station • Open the Main Drain Valve. TFP1112 for the ACC-1),and open the alarms. • Open the Main Control Valve one turn Inspector's Test Connection to relieve beyond the position at which water Step 11.Once a week after a valve is indicated on the S the system air pressure to 0 as stem Air Pressure reset following an operational test or just begins to flow from the Main Gauge), and then after removing the system operation,the Low Body Drain Drain Valve. Handhole Cover, perform the following Valve(and any low point drain valves) • Close the Main Drain Valve. steps: should be partially opened (and then Step 2.Open the system's Inspector's Step 1. Make sure that the Seat Rin subsequently closed)to relieve drain- Test Connection. is clean and free of any nicks or signifi- back water. Continue this procedure cant scratches. until drain-back water is no longer Step 3. Verify that the DPV-1 Valve present. has operated, as indicated by the flow Step 2.Remove the Clapper Assembly of water into the system and that all from the valve by first pulling out the Care and waterflow alarms operate properly. Hinge Pin. Step 4. Close the system's Main Step 3. Disassemble the Clapper Maintenance Control Valve. Facing Retainer from the Clapper Step 5.Reset the DPV-1 Valve in actor- so that the Clapper Facing can be The following procedures and inspec- removed and inspected. Make sure tions should be performed as indicated, dance with the Valve Setting Procedure. that the Clapper Facing does not show in addition to any specific requirements Note: It is recommended that the signs of compression set,damage,etc. of the NFPA,and any impairment must requirement of NFPA 25 to annually Replace the Clapper Facing if there is be immediately corrected. inspect the inside of the valve be any signs of wear. Before closing a fire protection system performed at this time and prior to main control valve for maintenance resetting the DPV-1 Valve. Refer to the Automatic Drain Valve Inspection TFP1020 Page 18 of 20 Step 4. Clean the Clapper Facing, Pre-Trimmed DPV-1 Assemblies Accessories Clapper,and Clapper Facing Retainer, with Butterfly Valve Order the Technical Data Sheets for the and then reassemble the Clapper Specify:2-1/2 Inch DPV-1 Pre-Trimmed following,as applicable,for details and Assembly. Valve Assembly, P/N 52-310-3-925 additional accessories: Step 5.Reinstall the Clapper Assembly Specify: 3 Inch DPV-1 Pre-Trimmed Model PS10-2 with its Hinge Pin and then reinstall the Valve Assembly, P/N 52-310-3-930 Potter Electric Waterflow Handhole Cover. Specify: 4 Inch DPV-1 Pre Trimmed Pressure Alarm Switch Valve Assembly,P/N(specify) P/N 25710 Model PS40-2 Ordering FxF P/N 52-310-3-040 Potter Electric Low Air Pressure Alarm Procedure FxG GxG P/N 52-310-3-440 P/N 52-310-3-940 Switch Model WMA1 P/N 25730 Refer to Table A for Flange Drilling Specify: 6 Inch DPV-1 Pre Trimmed Water Motor Alarm Specifications. Valve Assembly, P/N(specify) P/N 52-630-1-001 P/N 52-310-3-060 Model AMD-1 Standard DPV-1 Dry Pipe Valve FxFAir Maintenance Device (American Standard Flange Drill- FxG P/N 52-310-3-460 P/N 52-324-2-002 ing,Threaded Ports,and Groove GxG P/N 52-310-3-960 Model AMD-2 Outside Diameter,as applicable) Pre-Trimmed DPV-1 Assemblies Air Maintenance Device Specify:(specify size)Model DPV-1 Dry without Butterfly Valve P/N 52-326-2-001 Pipe Valve with(specify Inlet x Outlet) Specify: 4 Inch DVP-1 Pre Trimmed Model AMD-3 end connections, P/N(specify). Valve Assembly without Butterfly, P/N Nitrogen Maintenance Device 2-1/2 Inch(DN65) (specify) P/N 52-328-2-001 GxG, FxF P/N 52-310-4-040 Replacement Valve 2.88 inch(73,1 mm)O.D. FxG P/N 52-310-4-440 Specify:lac (description)Parts for use with Groove x 2.88 inch(73,1 mm) Specify: 6 Inch DVP-1 Pre Trimmed (specify size) Model DPV-1 Dry Pipe O.D.Groove P/N 52-310-1-925 Valve Assembly without Butterfly, P/N Valve, P/N (see Figure 1 Parts 1 and 2 3 Inch(DN80) (specify) as applicable). GxG, FxF P/N 52-310-4-060 Replacement Trim Parts 3.50 inch(88,9 mm)O.D. FxG P/N 52-310-4-460 Specify: (description) for use with Q.D.Groove x 3. inch(88,9N mm) s ecif size) Model DPV-1 Dry Pipe O.D. P/N 52-310-1-930 Standard Galvanized (specify 4 Inch(DN100) Semi-Assembled DPV-1 Trim Valve, P/N (Figures 4,5, or 6, Part 3 as Specify:2-1/2 and 3 Inch DPV-1 Semi- applicable). GxG, Assembled Galvanized Trim, P/N 4.50 inch(114,3 mm)0.D. 52-309-2-005. Weights Groove x 4.50 inch(114,3 mm) The following are the nominal weights O.D.Groove P/N 52-310-1-940 Specify:4 Inch DPV-1 Semi-Assembled for the valves and trim: FxG, Galvanized Trim, P/N 52-309-2-001 ANSI Drilled FlangePre-Trimmed DPV-1 Valve Specify:6 Inch DPV-1 Semi-Assembled Assemblies: x 4.50 inch(114,3 mm) Galvanized Trim, P/N 52-309-2-002 sseInch(DN65) O.D.Groove P/N 52-310-1-440 FxF, Optional Accelerator GxG Dry Pipe Valve. .... 87lbs.(40kg) ANSI Drilled Flange x ANSI VIZOR Electronic Dry Pipe 3 Inch(DN80) Drilled FlangedP/N 52-310-1-040 Accelerator(with Trim) GxG Dry Pipe Valve 901bs.(42kg) 6 Inch DN150 (Details provided in TFP1105) 4 Inch(DN100) GxG, ( ) Specify:VIZOR Electronic Dry Pipe GxG Dry Pipe Valve.... 1211bs.(56kg) 6.62Accelerator for use with the 4 or 6 4 Inch(DN100) Groove inch 6.626inch3 (168,3O.D. FxG DryPipe Valve 1351bs.(64kg) x mm) inch TYCO Model DPV-1 Dry Pipe 4 Inch DN100 O.D.Groove P/N 52-310-1-960 Valve trim, P/N 52-312-3-001 ( ) FxF Dry Pipe Valve 1451bs.(69kg) FxG, Model ACC-1 Mechanical 6 Inch(DN150) ANSI Drilled Flange Accelerator GxG Dry Pipe Valve 1751bs.(81kg) x 6.62 inch(168,3 mm) (Details provided in TFP1112) 6 Inch(DN150) O.D.Groove P/N 52-310-1-460 Specify: Model ACC-1 Dry Pipe FxG Dry Pipe Valve 1951bs.(90kg) FxF, Accelerator,P/N 52-311-1-001,and 6 Inch(DN150) ANSI Drilled Flange x ANSI FxF Dry Pipe Valve.. .. 2081bs.(96kg) Drilled Flanged.... P/N 52-310-1-060 Galvanized Accelerator Trim for Model DPV-1 Dry Pipe Valve, Standard Galvanised P/N 52-311-2-010 Semi-Assembled DPV-1 Trim: 2-1/2 Inch(DN65) Optional 600 PSI Water Pressure Valve Trim 23lbs.(11kg) Gauge 3 Inch(DN80) Specify: 600 PSI Water Pressure Valve Trim 231bs.(11kg) Gauge,P/N 92-343-1-004 4 Inch(DN100) Valve Trim 301bs.(14kg) 6 Inch(DN150) Valve Trim 3OIbs.(14kg) TFP1020 Page 19 of 20 DPV-1 Valve: Part Numbers For Other 4 Inch FxG, 2172- 1/2 Inch(DN65) (DN100)Dry Pipe Valves JIS Flange x 6.62"(168,3 mm) GxG Dry Pipe Valve 37lbs.(17kg) Valves with NPT Ports Outside Dia.Groove 3 Inch(DN80) FxG, GxG Dry Pipe Valve 381bs.(18kg) ISO Flange x 4.50"(114,3 mm) FxG, P/N 52-309 1-815 4 Inch(DN100) Outside Dia.Groove JIS Flange x 6.50"(165,1 mm) GxG Dry Pipe Valve 571bs.(26kg) P/N 52-309-1-253 Outside Dia.Groove 4 Inch(DN100) FxG, FxG Dry Pipe Valve 67lbs.(31kg) AS Flange x 4.50"(114,3 mm) FxF, P/N 52-309-1-835 4 Inch(DN100) Outside Dia.Groove ISO Flange x ISO Flange FxF Dry Pipe Valve 771bs.(36kg) P/N 52-309-1-613 6 Inch(DN150) FxG, P/N 52-309 1-135 GxG Dry Pipe Valve 951bs. 44k g mm) FxF, 6 Inch(DN150) ( g) JIS Flange x 4.50"(114,3 AS Flange x AS Flange FxG Dry Pipe Valve.... 108 lbs.(50kg) Outside Dia.Groove P/N 52-309-1-515 6 Inch(DN150) P/N 52-309-1-813 FxF, FxF, JIS Flange x JIS Flange FxF Dry Pipe Valve 1211bs.(56kg) ISO Flange x ISO Flange Other DPV-1 Dry Pipe Valves P/N 52-309-1-715 P/N 52-309-1-133 Valves with ISO Ports Notes: Other DPV-1 Dry Pipe Valves FxF, GxG, are valves ordered with a any combi- AS Flange x AS Flange nation of flange, threaded ports, or Groove 8,3 2 (18,3 Outside Dia. groove outside diameter not offered FxF, P/N 52-309 1-513 Groove x 6.62"(168,3 mm) under"Standard DPV-1 Dry Pipe Valve" JIS Flange x JIS Flange Outside Dia.Groove offerings. P/N 52-309-1-713 P/N 52-309-1-925 Valves with NPT threaded ports are Valves with ISO Ports Gx 6. intended for use with the "Standard GxG, Groove 5,1 mm)65,1 Outside Dia. Galvanized Semi-Assembled DPV-1 Groove x Dia.6. Groove mm) 4.50"(114,3 mm)Outside Dia. Outside Groove Valve Trim"offered and detailed in this Groove x 4.50"(114,3 mm) document. Valves with ISO threaded P/N 52-309-1-945 ports are intended for use with special Outside Dia.Groove FxG, order trim that is provided by local P/N 52-309-1-923 ISO Flange x 6.62"(168,3 mm) distributors to meet the specific needs ISFxG, Outside Dia.Groove of certain localities.Please contact your Outside ide Dia.ge x 4.Groove(114,3 mm) P/N 52-309 1-215 local distributor regarding valves and Outside FxG, valve trim for specific localities. P/N 52-309-1-213 ISO Flange x 6.50"(165,1 mm) FxF, Outside Dia.Groove Specify:(specify size)Model DPV-1 Dry ISO Flange x ISO Flange P/N 52-309-1-315 Pipe Valve with (specify inlet x outlet) P/N 52-309-1-113 FxF, connections with(specify NPT or ISO) ISO Flange x ISO Flange threaded ports, P/N(specify). Part Numbers For Other 6 Inch (DN150)Dry Pipe Valves P/N 52-309-1-115 Part Numbers For Other 2-1/2 Inch Valves with NPT Ports (DN65)Dry Pipe Valves GxG, Valves with NPT Ports 6.50"(165,1 mm)Outside Dia. GxG, Groove x 6.50"(165,1 mm) 3.00"(76,1 mm)Outside Dia. Outside Dia.Groove Groove x 3.00"(76,1 mm) P/N 52-309-1-935 Outside Dia.Groove FxG, P/N 52-309-1-930 ANSI Flange x 6.50"(165,1 mm) Valves with ISO Ports Outside Dia.Groove GxG, P/N 52-309-1-435 2.88"(73,0 mm)Outside Dia. FxG, Groove x 2.88"(73,0 mm) ISO Flange x 6.62"(168,3 mm) Outside Dia.Groove Outside Dia.Groove P/N 52-309-1-920 P/N 52-309-1-255 GxG, FxG, 3.00"(76,1 mm)Outside Dia. ISO Flange x 6.50"(165,1 mm) Groove x 3.00"(76,1 mm) Outside Dia.Groove Outside Dia.Groove P/N 52-309-1-335 P/N 52-309-1-940 FxG, Part Numbers For Other 3 Inch AS Flange x 6.62"(168,3 mm) (DN80)Dry Pipe Valves Outside Dia.Groove Valves with ISO Ports P/N 52-309-1-615 GxG, FxG, 3.50"(88,9 mm)Outside Dia. AS Flange x 6.50"(165,1 mm) Groove x 3.50"(88,9 mm) Outside Dia.Groove Outside Dia.Groove P/N 52-309-1-635 P/N 52-309-1-922 TFP7020 Page 20 of 20 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2013 Tyco Fire Products,LP. AU rights reserved. Vico tqca Fire Suppression & Building Products Technical Services 800-381-93121+1-401-781-8220 www.tyco-fire.com Model AMD-1 Automatic Air Maintenance Device Pressure Reducing Type with Field-Adjustable Pressure Regulator General Technical Description Data r. The TYCO Model AMD-1 Automatic Air Approvals �' Maintenance Device is an automatic, UL and C-UL Listed -111111111.11. , field-adjustable, pressure reducing FM Approved device. It is used to control the pres- NYC Approved under MEA 206-02-E sure in a dry pipe sprinkler system,pre- action system, or dry pilot line system Maximum Inlet Air(or Nitrogen) of a dry pilot actuated deluge or preac- Supply Pressure tion valve. 200 psi(13,8 bar) The Model AMD-1 Device is utilized Field-Adjustable Outlet Pressure Installation in applications where there is a corn- 5Range pressed air (or nitrogen) source con- to 70 psi(0,4 to 4,8 bar) The TYCO Model AMD-1 Automatic Air trolled at a higher pressure than the Assembly Maintenance Device must be installed desired system pressure. Pressure Major components illustrated in Figure in accordance with the following sources include plant air supplies with 1 are factory assembled with galva- instructions. their own automatic compressor con- nized steel nipples and malleable iron trols or nitrogen supplies with sin- pipe fittings. NOTICE gle-stage, cylinder-mounted pressure regulators. Moisture build-up can adversely affect The Model AMD-1 Automatic Air Main Operation performance. Suitable consideration must be given to the removal of exces tenance Device is a re-designation for The By-Pass Valve in the Model AMD-1 sive moisture from the compressed air the Central Model D-2, Gem Model Automatic Air Maintenance Device is supply. F324,and Star Model S460. opened to quickly fill the system during initial pressurization.Once the required 1. Make connections(DN15) pipe a minimum of NOTICE system pressure has been reached, the1/e inch irsupply and between The Model AMD-1 Automatic Air Main- the By-Pass Valve is closed and the Air inlet air and the Model tenance Devices described herein Supply Control Valve is left open to AMD-1 Device, as well as between must be installed and maintained in place the Model AMD-1 Device in auto- the Model AMD-1 Device and the compliance with this document and matic operation. system to pressurize. with the applicable standards of the When there is a small leak in the sys- 2. Place a 1/2 inch(DN15),non-spring National Fire Protection Association, tem, the Pressure Regulator automati- loaded, rubber faced, swing type in addition to the standards of any cally maintains system pressure at the check valve between the Model authorities having jurisdiction. Failure preset level.The 3/32 inch(2,4 mm)ori- AMD-1 Device, and the systemeofthis to to do so may impair the performance fice in the Restrictor Check Valve limits type isprovidedsrcheck valve of of these devices. the flow of air from the Pressure Regu- type TYCO ini theeair supply Owners are responsible for maintain- pre- lator into the system to a value signifi- trim of dry pipe valves, cantlyless than that exhausted by the action valves, and dry pilot trim. ing their fire protection system and devices in proper operating condition. operation of a 5.6 K-factor sprinkler. The installing contractor or sprinkler manufacturer should be contacted with any questions. Page 1 of 4 JULY 2010 TFP1221 TFP1221 Page 2 of 4 2„ 16-1/8"" (50,8 mm) (409,6 mm) 1 BY-PASS VALVE 1/4"NPT (NORMALLY -" t GAUGE CLOSED) 31/4" T 1/2"NPT TEST PORT T P/N 46-047-1-004 OUTLET . us gla (82,6 mm) CONNECTION ro (TO SYSTEM) iii91I*111I�I_'�ierild!i 8-1/2" 1/2"NPT (215,9 mm) r INLET CONNECTION a LABEL eff _=._ • • ; (FROM COMPRESSED iIii-�--!i. , ., AIR SUPPLY) omen num ISI .ss*� i�i RESTRICTOR if • I I, CHECK VALVE P/N 92-326-1-003 PRESSURE AIR SUPPLY REGULATOR STRAINER CONTROL VALVE (ADJUSTABLE) P/N 52-353-1-002 R(NORMALLY OPEN)) P/N 92-324-1-012 002 FIGURE 1 MODEL AMD-1 AUTOMATIC AIR MAINTENANCE DEVICE 7. While observing the relocated pres- 10.Open the control valve in the Setting sure gauge,adjust the output pres- air supply trim to the system to sure of the Pressure Regulator. Pull pressurize. Procedure the knob out and away from the 11.Open the Air Supply Control Valve The TYCO Model AMD-1 Automatic Pressure Regulator body and then in the Model AMD-1 Device. slowly turn the knob clockwise, as Air Maintenance Device must be set viewed from the knob end of the 12.Open the By-Pass Valve in the in accordance with the following Pressure Regulator, to increase Model AMD-1 Device. instructions. pressure,and counter-clockwise to 13.Close the By-Pass Valve after the 1. Determine the pressure that meets decrease pressure. system is pressurized to approxi- the minimum requirements of the When decreasing pressure, the air mately 5 psi (0,4 bar) less than the system to pressurize. pressure must be relieved down- minimum required system pressure 2. Close the Model AMD-1 By-Pass stream of the Pressure Regulator determined in Step 1. Valve, and close the Model AMD-1 by temporarily opening the control 14.After the system pressure stabi- Air Supply Control Valve. valve in the air supply trim of the lizes, note the value and compare 3. Open the control valve in the air system to pressurize,assuming that with the requirement.Re-adjust the supply trim of the system to pres- the system to pressurize is at 0 psi. Pressure Regulator,as required. surize and then reduce the system After the Pressure Regulator is set, air pressure to 0 psi. push the knob in and towards the NOTICE Pressure Regulator body to "snap" If the system was over-pressur- 4. Close the control valve in the y it in a locked position. ized duringmanual fill, open a air supply trim of the system to pressurize. 8. Close the Air Supply Control Valve suitable connection to the system 5. Remove the system pressure gauge in the Model AMD-1 Device. and manually reduce the pressure from its connection and tem oraril to the desired value. The Model p Y 9. Return the system air pressure AMD-1 Automatic Air Maintenance install it in the 1/4 inch NPT Model gauge to its normal location. Re- Device then automatically maintains AMD-1 Gauge Test Port. install the 1/4 inch pipe plug in the the preset system pressure. The Model AMD-1 Gauge Test Port. Restrictor Check Valve prevents CAUTION Apply pipe-thread sealant sparingly the Pressure Regulator from bleed- to the plug threads only. in down the system pressure. Before removing the plug, make g y certain that the piping to which the In order to minimize the for Model AMD-1 Gau e Test Port is CAUTION g system trip in the event of a time fo connected is at 0 psi. Failure to do Before removing the pressure kler operation,set the system pres- so may result in personal injury or gauge,make certain that the piping sure at the minimum required value. property damage. to which the Model AMD-1 Gauge 6. Open the Air Supply Control Valve in Test Port is connected is at 0 psi. the Model AMD-1 Device. Failure to do so may result in per- sonal injury or property damage. TFP1221 Page 3 of 4 Care and 4. Verify that the system pressure is The foregoing warranty is made in lieu essentially the same as the previ- of any and all other warranties,express Maintenance ously established requirement. If or implied,including warranties of mer- not, adjust the system pressure as chantability and fitness for a particular The TYCO Model AMD-1 Automatic follows: purpose. Air Maintenance Device must be main- a.Close the system's main con- This limited warranty sets forth the tained and serviced in accordance with trol valve and open the main exclusive remedy for claims based on the following instructions,in addition to drain valve. If the system is so failure of or defect in products, materi- any specific requirements of the NFPA. equipped, close the Accelerator als or components,whether the claim is Any impairment must be immediately Control Valve. made in contract, tort, strict liability or corrected. any other legal theory. b.Follow Steps 1 through 14 in the NOTICE Setting Procedure section. This warranty will apply to the full extent permitted by law.The invalidity, c.Slowly open the Accelerator Con- in whole or part, of any portion of this Before closing a fire protection system main control valve for maintenance trol Valve,as applicable. warranty will not affect the remainder. work on the fire protection system d.Slowly open the main control that it controls, obtain permission to valve.After water begins to flow, Ordering shut down the affected fire protec- slowly close the main drain valve, tion system from the proper authori- then completely open the main Procedure ties and notify al/personnel who may control valve. The Model AMD-1 be affected by this action. Automatic Air Maintenance Contact your local distributor for avail- It is recommended that accumulated Device is now ready for service. ability. When placing an order, indi- cate the full product name, including moisture be removed from air supply moisture filtration equipment at least Limited description and Part Number(P/N). quarterly. More frequent inspections Model AMD-1 Device may be necessary in particularly humid Warranty Specify: Model AMD-1 Automatic Air environments. Products manufactured by Tyco Fire Maintenance Device, After placing a fire protection system Suppression & Building Products P/N 52-324-2-002. in service, notify the proper authorities (TFSBP) are warranted solely to the and advise those responsible for mon- original Buyer for ten(10)years against Replacement Parts itoring proprietary and/or central sta- defects in material and workmanship Specify: (description) for use with the tion alarms. when paid for and properly installed Model AMD-1 Automatic Air Mainte- and maintained under normal use and nance Device, P/N(from Figure 1). Responsibility lies with owners for the service. This warranty will expire ten inspection,testing,and maintenance of (10) years from date of shipment by their fire protection system and devices TFSBP. No warranty is given for prod- in compliance with this document, as ucts or components manufactured by well as with the applicable standards of companies not affiliated by ownership the National Fire Protection Association with TFSBP or for products and corn- (for example, NFPA 25), in addition to ponents which have been subject to the standards of any other authorities misuse, improper installation, corro- having jurisdiction. Contact the install- sion, or which have not been installed, ing contractor or sprinkler manufac- maintained, modified or repaired in turer regarding any questions. accordance with applicable Standards Automatic sprinkler systems are rec- of the National Fire Protection Associa- tion, and/or the standards of any other ommend to be inspected, tested, and Authorities Having Jurisdiction. Mate- maintained by a qualified Inspec- tion Service in accordance with local rials found by TFSBP to be defective requirements and/or national code. shall P'be either repaired F replaced,itat TFSBP's sole option. TFSBP neither The Model AMD-1 Device must be assumes, nor authorizes any person inspected quarterly in accordance with to assume for it, any other obligation the following instructions. in connection with the sale of prod- 1. Verify that the By Pass Valve is ucts or parts of products.TFSBP shall closed. not be responsible for sprinkler system design errors or inaccurate or incom- 2. Close the Model AMD-1 Air Supply plete information supplied by Buyer or Control Valve and clean out the 1/4 Buyer's representatives. inch Strainer located at the inlet to In no event shall TFSBP be liable, in the Restrictor Check Valve. Be sure contract, tort, strict liability or under to reinstall the strainer screen and any other legal theory, for incidental, tighten the cap securely. indirect,special or consequential dam- 3. Open the Model AMD-1 Air Sup- ages, including but not limited to labor charges,regardless of whether TFSBP ply Valve and verify that the con- trol valve in the air supply trim to the was informed about the possibility of such damages, and in no event shall system to pressurize is open. TFSBP's liability exceed an amount equal to the sales price. TFP1221 Page 4 of 4 Copyright©2007-2010 Tyco Fire Suppression&Building Products.All rights reserved. VicoWorldwide Fire Protection Contacts www.tyco-fire.com Products Model BFV-N Butterfly Valve Grooved End General Technical Description Data The Model BFV-N Grooved End But- Approvals 4 $` terfly Valves (Ref. Figure 1) are indi- UL and C-UL Listed cating type valves designed for use in FM Approved fire protection systems where a visual Listed by California State Fire Marshall indication is required as to whether the under Listing No.7770-1670:100 valve is open or closed.They are used, for example,as system,sectional,and All laboratory listings and approvals are for pump water control valves.They have indoor and outdoor use. cut groove inlet and outlet connections Sizeshi that are suitable for use with grooved 2-1/2 thru 10 Inch(DN65 thru DN250) end pipe couplings that are listed and approved for fire protection systems. Maximum Working Pressure 2-1/2 to 8 Inch(DN65 to DN200) For applications requiring supervision 300 psi(20,7)bar of the open position of the valve, the Gear Operators for the Model BFV-N 10 Inch(DN250) Butterfly Valves are provided with 175 psi(12,0 bar) two sets of factory installed inter- Materials of Construction nal switches each having SPDT con- Body tacts (Ref. Figure 3). The supervisory switches transfer their electrical con Ductile iron conforming to ASTM A395 tacts when there is movement from the Body Coating valve's normal open position during the Polyamide first two revolutions of the handwheel. Disc NOTICE Ductile iron conforming to ASTM A395 DThe Model BFV-N Grooved End But- Grade Seal terfly Valves described herein must be conformingnEPDM"ASTM D2000 rubber installed and maintained in compliance to D2000 with this document,as well as with the Upper&Lower Stem applicable standards of the National Type 416 Stainless Steel conforming to Fire Protection Association,in addition ASTM 582 to the standards of any other authori- Lower Plug ties having jurisdiction.Failure to do so PVC may impair the performance of these devices. Operator Gear operator with iron housing The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Page 1 of 4 JULY 2015 TFP151O TFP1510 Page 2 of 4 Nominal Nominal Installation Dimensions Weight Valve OD Inches(mm) Lbs. Sizes Inches Inches (mm) A B C D E F G H (kg) (DN) 2-1/2 2.88 3.85 11.94 3.25 (144,0)5.67 5.90 5.82 2.13 22 (149 9) (147 8) (54,1) 0 (10,0) (65) (73,0) (98,0) (303,3) (83,0) 76,1mm 3.00 3.85 11.94 3.25 5.67 5.90 5.82 2.130 22 (65) (76,1) (98,0) (303,3) (83,0) (144,0) (149,9) (147,8) (54,1) (10,0) (80) (88 9) (98,0) (317,0) (90,0) (150,9) (149,9) (147,8) (54,1) 0 (10,4) 4 4.50 4.56 14.18 4.35 6.31 5.90 7.64 2.13 0 128 (100) (114,3) (116,0) (360,2) (110,0) (160,3) (149,9) (194,1) (54,1) (12,7) 5 5.56 5.86 15.17 4.84 7.32 5.90 7.64 2.13 31 0 (125) (141,3) (149,0) (385,3) (123,0) (185,9) (149,9) (194,1) (54,1) (14,1) 165,1mm 5.86 17.54 5.93 8.62 5.90 7.64 2.13 0.67 41 (150) (165,1) (149,0) (445,5) (151,0) (218,9) (149,9) (194,1) (54,1) (17,0) (18,6) 6 6.63 5.86 17.54 5.93 8.62 5.90 7.64 2.13 0.67 41 (150) (168,3) (149,0) (445,5) (151,0) (218,9) (149,9) (194,1) (54,1) (17,0) (18,6) 8 8.63 5.26 19.42 6.87 9.80 9.80 7.91 2.13 5.86 53 (200) (219,1) (134,0) (493,3) (174,0) (248,9) (248,9) (200,9) (54,1) (148,8) (24,1) 10 10.75 6.29 24.03 9.17 11.61 18.00 9.49 3.03 7.41 88 (250) (273,1) (160,0) (610,4) (233,0) (294,9) (457,2) (241,0) (77,0) (188,2) (40,0) INDICATOR G ---- F 1 HANDWHEEL FLAG / 1/2"NPT CONDUIT GEAR — _, CONNECTION - 1 d �' �/ OPERATOR E �Oi 16111 w BODY bD B �� D H r t :EIsC FIGURE 1 MODEL BFV-N GROOVED END BUTTERFLY VALVE NOMINAL DIMENSIONS r 7 r , I—SUPERVISORY • I— AUXILIARY CONTACT RATING: SWITCH GND SWITCH • 1/2A @ 125 VDC SWITCH SHOWN 1/4A @ 250 VDC SWITCH SHOWN 15.1A/12HP @ 125,250 VAC WITH VALVE _______ WITH VALVE 5A @ 125 VAC"L" `- --- -- --- -J FULL OPEN L --' FULL OPEN 3 3 wry w (5 w Li o w O O Z Z w -J w J ¢ O_ ¢CC >- > o o C7 > m 1 • +_.--r\--• BELL END OF LINE PANEL POWER • + RESISTOR FIGURE 2 MODEL BFV-N BUTTERFLY VALVE INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION TFP1510 Page 3 of 4 FLOW RATE IN LITRES PER MINUTE(LPM) (1 GPM=3,785 LPM) 300 400 600 1000 2000 4000 6000 10000 20000 40000 5.0 .� _ _IMIII=IMM _ -..-.. :�:.:..:m= r7� ��.___•:111.•:-�C =C: 0,30 4.0 ..M ■.�MIC,MM �.,� o•UoI... IIIIW1IIIMIVAI._-.__��.u.wawn...W��i.. ..M.II...MII.IIIIMrMI.MsMIMtWIMMI.MINIAMMINNIII.II.IIIMMMMI/ 0,20 ..-nI■■■--.—/,-I.-■ --,—■---■11■11' 11 111■■IMAIMMi1MMIA1NIINIil•■NIIMNIIMEI■11■1MINIMIf ■■•111■■■ IMAM 11M11IMEIMMIIMIMM■IIIIIIMIIIM■11117111111MIIV - 2.0 111111■■■IMMI•■��11MI��ML�■I_��■11�1I OE d UNIIIIN/ 11110 Ci) MMIMMIIMINMENIIMMENIMMUNIIIEGMIN=MIIIIMIN11/ 11/,==IM MIN==IINME11111 /IIIE =MENE I..L�rI�r1.MME/�r� I.�IM MMr.II.II�I� MIIMMIIIMMIMMAMMIIIM/IMIIIMMINFIIIMMINEMIWAIIIIIIIII=E1W/// 03 O 2 ■IIMImviINIMINIaIMIIIIMuMMINIMMFiIMMMMWMIMIMIwrn:■n CC 0 0 Z 11111/,■■�M1��IM�I—�� moi■■�A�I■11111 cc cc1.0 �� h ��M1= ■�f1 ����� I■11 w -0,08 O Q W w I■1 D Q r.■_�,■. ' -- — 0 NIM � i� , s O Al. ..,� 0O rmI O rtem m NE w 0.8 mar: . i �$iii �_ ��c�■ �O=� �O�n��. 0 O6 Li jCC e° m Z ,■o• nu Z M�■ Z. i Z ,n1 --0,05 o CC w 0.6 2 Al 0 I■�E?0:�1=U, =V.,L�1 2 a =U m1 0,04 w llo z� 0.5 ti^ ■_ a ha vU= ,'o _ _ ¢u) 2 z 0.4 :.. ...M1. .• ..�.��� z .... < :. 0,03 a O D aiUMIIMIIMINNIMIONIIMMFAIMIN=Ell'AMIMilmlirallEN/ MliMMIll iIMMIIiiIII __ _ _ INZ 0 AMMiIIii���.� �MIM��M CL 0.3 ME..rI.II..MMWAI�III._����i.IMMW�.II.II Z �.nMm...��I�.I.I.M —� ��...MIA..nI 0,02 0 — �iTAiriiiiiM�i��iiMI���i- ■�W�iriiri MIIM/II111■■■IM1IIIIMII11MIIIAIM�_WAIII■MII191IIMIMI■11■11 - 0.2 I1II111■■■IOMIIIIIII1■MII—I IM■NIS■11■11 -I..M�II..IIMIII �I.WI=Mminm•Mlmeme.WIMII=MIIM.II.II —/M..MIII■.■EMENIIMIONNO1■IM—NVI.�■IAMMOIMMEII.II MIIMMEIM.II=nI.IIIMENIMIIIIIMIMI1.IIIIWAIIIIMME-1111 OMEN 0,01 �r•u IIurAu•iMlIii i�t�FA�=�1.11�11 0.1 ��II II iii��I iii��t�•���MIlUII 60 100 200 400 600 1000 2000 4000 6000 10000 15000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH A DN65 THROUGH DN250 MODEL BFV-N BUTTERFLY VALVE NOMINAL PRESSURE DROP VERSUS FLOW Installation NOTE: For outdoor applications with internal supervisory switches, it is rec- The , Model BFV-N Grooved End Butter- ommended that wiring connections fly Valves may be installed with flow in be made at a temperature above 15°F ' either direction and can be positioned (-9°C),in order to insure sufficient flex- #4 lex ��C�� either horizontally or vertically. ibility of the wire lead insulation. �'I The grooved end pipe couplings used A _ 4� with the Model BFV-N must be listed or Stop l•/ approved for fire protection service and Adjustment OPEN B installed in accordance with the manu- facturers instructions. Procedure A The Model BFV-N Butterfly Valve may SHUT be installed with any schedule of pres- The gear operator's OPEN and SHUT FIGURE 3 sure class of pipe or tubing that is listed position have been factory set. The MODEL BFV-N GROOVED END or approved for fire protection. following procedure should be used if BUTTERFLY VALVE As applicable, refer to Figure 2 for the slight adjustments are needed.Refer to OPERATOR ADJUSTMENT internal switch wiring diagram. Figure 3. Step 1. Turn the Handwheel until the Step 6. Close the valve by turning the Conduit and electrical connections valve is fully closed. Handwheel until the valve is fully in are to be made in accordance with the closed position. Ensure the disc the authority having jurisdiction and/ Step 2. Remove two lockscrews (A) has returned to the fully closed posi- or the National Electrical Code. With from the gear operator body. tion and the disc is centered in the seat reference to Figure 2, the supervisory Step 3.Turn the Shut Stop Screw (B) area. Readjust the Shut Stop Screw if switch is intended for connection to clockwise until snug. necessary. the supervisory circuit of a fire alarm control panel in accordance with NFPA Step 4. Turn the Handwheel until the Step 7. Replace two lockscr oc (A) 72.The auxiliary switch is intended for valve is fully open. into the gear Operator body locking the unsupervised connection to aux the stops into position. iliary equipment in accordance with Step 5.Turnthe Open Stop Screw(C) NFPA 70, National Electric Code. clockwise until snug. TFP1510 Page 4 of 4 Care and Limited Ordering Maintenance Warranty Procedure Before closing a fire protection system For warranty terms and conditions,visit Grooved End Butterfly Valves control valve for maintenance or www.tyco-fire.com. SSpV ify: (specify Endch size) iz fly Model ireinspectionroawork on either the valve o- with internal supervisory switches, fire protection system which it con- P/N(specify): trols, permission to shut down the affected fire protection systems must 2-1/2 inch(DN65) 59-300-F-025N be obtained from the proper authorities 76,1 mm(DN65)* 59-300-F-076N and all personnel who may be affected 3 inch(DN80) 59-300-F-030N by this decision must be notified. 4 inch(DN100) 59-300-F-040N 5 inch(DN125) 59-300-F-050N The owner is responsible for the 165,1mm(DN150)* 59-300-F-165N inspection,testing,and maintenance of 6 inch(DN150) 59-300-F-060N 8 inch(DN200) 59-300-F-080N their fire protection system and devices 10 inch(DN250) 59-300-F-100N in accordance with the applicable stan Available for EMEA and APAC markets only dards of the National Fire Protection Association(e.g.,NFPA 25),in addition to the standards of any authority having jurisdiction.Contact the installing con- tractor or product manufacturer with any questions. Any impairment must be immediately corrected. It is recommended that automatic sprinkler systems be inspected,tested, and maintained by a qualified inspec- tion service. GLOBAL HEADQUARTERS I 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. fico Fire Protection Products tVICOWorldwide Fire Protection Contacts www.tyco-fire.com Products Model CV-1F Grooved End Swing Check Valves General The owner is responsible for main- taining their fire protection system II Description and devices in proper operating con- dition. Contact the installing contrac- The TYCO Model CV-1F Grooved End tor or product manufacturer with any Swing Check Valves are compact questions. and rugged swing-type units that allow water flow in one direction and Technical prevent flow in the opposite direction. A resilient elastomer seal facing on the Data spring-loaded clapper ensures a leak- tight seal and non-sticking operation. Approvals The Model CV-1F Check Valves are Compliance with CE Pressure designed to minimize water hammer Equipment Directive(PED)and caused by flow reversal. Standards of Engineering Practice The Model CV-1F Grooved End Swing • 2 to 12 Inch(DN50 to DN300): U1 c PL Check Valves are furnished with UL and C-UL Listed, FM Approved, L grooved ends and can be installed Bureau Veritas APPROVED using GRINNELL Grooved Couplings • 2-1/2 to 10 Inch(DN65 to DN250): «a°Ve or GRINNELL Figure 71 Flange Adapt- VdS Approved VdS �9> ers. The Model CV-1F Check Valves Certificate No.G4060018 Im have been designed with a removable 82s cover for ease of field maintenance. Sizes For fire protection pressure rating, These valves can be installed horizon- 2 to 12 Inch(DN50 to DN300) listing and approval information,contact tally(with cover in the upward position) your TYCO representative. Maximum Working Pressure or vertically with the flow in the upward direction(Ref. Figure 4). UL/FM 300 psi(20,7 bar) Installation VdS- 16 bar A check valve maintenance kit is avail Valve Assembly Finish The Model CV-1F Grooved End Swing able to allow backflushing through a Red, non-lead paint Check Valves are to be installed i fire department connection without removing the Model CV-1F Grooved accordance with this section: End Swing Check Valve from the riser. Step 1. The arrow cast on the body Refer to technical data sheet TFP1555. must point in the direction of the flow. Model CV-1F is a re-designation for Step 2. Valves installed vertically Central Figure 590F and GRINNELL must be positioned with the flow in the Figure 590F Grooved End Swing Check upward direction. Valves. Step 3. Valves installed horizontally NOTICE must be positioned with the cover facing up(Ref. Figure 4). The TYCO Model CV-1F Grooved End Step 4. Grooved end pipe cou lins Swing Check Valves described herein used with the Model CV-1F Grooved must be installed and maintained in compliance with this document and End Swing Check Valves must be with the applicable standards of the installed in accordance with manufac- National Fire Protection Association turer's instructions. (NFPA), in addition to the standards Note:Valves should be installed a rea- of any authorities having jurisdiction. sonable distance downstream from Failure to do so may impair the perfor- pumps, elbows, expanders, reducers, mance of these devices. or other similar devices to extend the valve life.Standard piping practices call Never remove any piping component nor correct or modify any piping defi for a minimum of five(5)times the pipe ciencies without first de-pressurizing diameter for general use. and draining the system. Failure to do so may result in serious personal injury, property damage, and/or impaired device performance. Page 1 of 4 AUGUST 2015 TFP1550 A TFP155O Page 2 of 4 Nominal Dimensions Nominal Pipe Size Inch Cover Approx. (mm) Bolt Weight Torque Lbs. Valve Size Pipe O.D. Lbs.-ft. (kg) Inch Inch A B C D E F J (Nm) (DN) (mm) 2 2.37 6.75 1.96 1.96 2.57 3.25 4.75 1.62 18 9.0 (50) (60,3) (171,5) (49,8) (49,8) (65,3) (82,3) (120,7) (41,5) (25) (4,5) 2-1/2 2.88 8.00(65) (73,0) (03 2) (136,87) (66,7) (78,5) (98,3) (149,1) (41,7) (54) (4,5) 76,1 mm 3.00 8.00 5.38 2.63 3.09 3.87 5.87 1.63 39 10.0 (65) (76,1) (203,2) (136,7) (66,7) (78,5) (98,3) (149,1) (41,7) (54) (4,5) 3 3.50 8.37 5.72 2.81 3.31 3.87 5.87 1.63 39 11.0 (80) (88,9) (212,6) (145,3) (71,4) (84,1) (98,3) (149,1) (41,7) (54) (5,0) 4 4.50 9.63 6.68 3.80 3.63 4.53 7.13 1.84 50 25.0 (100) (114,3) (244,6) (169,7) (96,5) (92,2) (115,4) (181,1) (46,7) (69) (11,3) 139,7 mm 5.50 10.50 7.40 4.46 4.13 4.90 7.50 1.75 39 29.0 (125) (139,7) (266,7) (188,0) (113,3) (104,9) (124,5) (190,5) (44,5) (54) (13,2) 5 5.56 10.50 7.40 4.46 4.13 4.90 7.50 1.75 39 29.0 (125) (141,3) (266,7) (188,0) (113,3) (104,9) (124,5) (190,5) (44,5) (54) (13,2) 165,1 mm 6.50 11.50 8.00 4.62 4.50 5.00 7.60 1.85 60 47.0 (150) (165,1) (292,1) (203,2) (117,3) (114,3) (127,0) (193,0) (47,0) (82) (21,3) 6 6.63 11.50 8.00 4.62 4.50 5.00 7.60 1.85 60 47.0 (150) (168,3) (292,1) (203,2) (117,3) (114,3) (127,0) (193,0) (47,0) (82) (21,3) 8 8.63 14.00 10.14 6.67 5.52 5.46 8.46 2.13 120 66.0 (200) (219,1) (355,6) (257,8) (169,4) (140,2) (138,7) (214,9) (54,1) (164) (29,9) 10 10.75 18.00 12.38 8.62 6.41 7.50 10.50 3.00 130 109.7 (250) (273,1) (457,2) (314,5) (218,9) (162,8) (190,5) (266,7) (76,2) (178) (49,4) 12 12.75 21.00 14.28 9.93 7.27 7.62 10.62 2.75 130 151.0 (300) (323,9) (533,4) (362,7) (252,2) (184,7) (193,5) (269,7) (69,9) (178) (68,0) B - A �M•1 tI 4- � O ♦ il ll ..t O.D. r, Ili D lik IlAb 1/2" NPT 1/2" J NPT IF E — F - FIGURE 1 MODEL CV-1F GROOVED END SWING CHECK VALVES NOMINAL DIMENSIONS Care and system from the proper authorities of the National Fire Protection Associa- and notify all personnel who may be tion (e.g., NFPA 25), in addition to the affected by this decision. standards of any authority having Maintenance After placing a fire protection system juris- diction.Contact the installing contrac- or product manufacturer The TYCO Model CV-1F Grooved End in service,notify the proper authorities torquorions. Any impairmentsmanufacturer witht anyy Swing Check Valves must be main- and advise those responsible for moni- immediately corrected. tained and serviced in accordance with toring proprietary and/or central station this section. alarms. Automatic sprinkler systems are rec- Before ommended to be inspected, tested, Before closing a fire protection system The owner is responsible for the and maintained by a qualified Inspec- main control valve for maintenance inspection,testing,and maintenance of tion Service in accordance with local work on the fire protection system their fire protection system and devices requirements and/or national codes. that it controls, obtain permission to in compliance with this document, as shut down the affected fire protection well as with the applicable standards TFP1550 Page 3 of 4 No. Part Material Qty. No. Part Material Qty. No. Part Material Qty. 1 Body Ductile Iron 1 6 Clapper FacingEPDM 1 14 Locknut Stainless 1 Grade"E" Steel 2 Cover Ductile Iron 1 7 Spring Stainless 1 15 Plug Cast Iron 2 Steel 1/2" NPT 3 Cover Gasket Nitrile 1 8 Hinge Shaft Stainless Thread Rubberg Steel 1 16 Adhesive Sealer AR 4 Hex Cap Screw Steel, AR 9 RetainingRingStainless Zinc Plated Steel AR 17 Nameplate Aluminum 1 Clapper,2"-8" Stainless 11 Retention Bolt Stainless 1 18 Rivet Steel 2 5 (DN50-200) Steel Steel 1 Clapper, -1 Ductile Iron 13 Retaining Disc Stainless 1 19 Spacer Stainless 1 Steel I Steel . 4,16 2 18 17 9 1III�I!llhIiiiiitl�,l'I 5 8 11'11 IIIIIIIIIIIIIIII�II 111111 ■ ■■ SEE ,-�� ��. VIEW A �vi 1.-. 2 7 9 2 7 5 3 �`� R i 2"-8" 10"-12" ewe ,`` /' ,AIF (DN50-DN200) (DN250-DN300) �\ \��� �`+� VIEW A tiil .._WVqk, 13 / I D SEE 5 / % i� 1 13 /moi 11,16 _' DETAIL B 11 ■li�� 14,16 �YY■ ) WI 1 �1�\\V��� 15 2"-8" 10"-12" (DN50-DN200) (DN250-DN300) DETAIL B FIGURE 2 MODEL CV-1F GROOVED END SWING CHECK VALVES ASSEMBLY FLOW RATE IN LITERS PER MINUTE(LPM) (1 GPM=3,785 LPM) 500 700 10)00 2000 3000 5000 7000 10000 20000 30000 50000 5.0 I I I I I i I fl I I I I 1 1 i i s ■�■:...■■ A h Ii .A ui�iiiii�■:'�...../AM ■■�,"' unii■■.■■■.•VA . 0,30 4.0 X5...1■■ 11111111111■1/i11Ill■ri■■■■iiiiiii ■■■i/,.III..lai .■/ ..■■■■■ O `O . o ■.■ono I■■■■■■.■.ri■■■■■ri■■..■■■■■■....oUmu■■■■ri■.■.r.■■■ ...■... 9 ,■■..n■.o III■■IllIIp4IiiiimIulli►nomeon Q_" ■■■■■1 U ■ \z A•UUuI.N ,. ,■■■■■ ►A■■■■I1IUIIMIIII ■rj■■..Ipl,IIIMIII ■■■■rA■■■■ 0,20 m C0C o •••• 2 � ,'a o i mu"'`O=in•••O ,.`Ly11, I1111„'11'5'���'�I��II����I�'�1I„"1 Z 0 Z ■■■■ �'' "I =/11■111 7111■■■ 2 A■ ho r 11 r ili I 11 111111 ►I /1 ■■■■ a< cc I 2.0 ...11111: `;.A�`;4111111 =x,11111■■ Q IIA .mei • - 4■o���i11i111111 41 1'11•■■■■ Q •••••' �•••■•■■• c-,••U €2,1111111161 oo X1111111111 1111■U151:G■■h■1 0 co 0)< ..■■.4■.L...I NIIII ■ b' OI■■■ = L.. .Z. l■■■.■... n/I■■■■...... P7■■■L.....■■■ CWC 0 ��%�U UhI�I���U�IlIt.iIMN IIIIIAll ■``�,�UI o������.uu IIMMINII Oau�iuii.ui., All NIEMEN NI y4111 I Gr (0Lu C3) m 2 �'A AI o•/�NIIIIM�111 o CL CC ■�I■PAIIIII■,■■■■ ENAIIIIIMI■■MIN o ■■■■■BBI 0ff,■■■U■UIII p=,111=Mo /■■■I11■■■■ 0,10 c,-) o "' ■I■P4■■■IIII■■■■■■II11111111111■I■■■11 I■■■■■■■ 2/■■■■■111 ,11 O I""",,," 0,09 W u z co a° ■■EN■■■IIII■■■■■11/11111111111■I■■■111■■■■■■■■ o ,■■■■■■■1 ` Cr — g Z 1.0 • iii■■'6.iiiii,r%11111111111•a ....rA. ii■■■■■'iiniiii, o=iiil=oi■■■11111■■■■1 AIIIIIIMIIMMI 0'08 Q r 0 D U. ...■oo■o..■■v r,I.■■■■ri.....■■■ .■■■o .. !L .■■■■■■o...■■ Z Z d 0.8 • �r.■.... ��■■■■■..1lIIUI ■Jr�•....■■■■■■ru..■■■■■.■.... m■ ■..■■■ 0,060.6JJPPJJJJJJP I Pr "Fari1rriIl . 0,05 0 ' Z I I II 0,04 0.5 100 200 300 400 600 1000 2000 3000 4000 6000 10000 15000 FLOW RATE IN GALLONS PER MINUTE(GPM) FIGURE 3 MODEL CV-1F GROOVED END SWING CHECK VALVES NOMINAL PRESSURE LOSS VS. FLOW TFP1550 Page 4 of 4 Valve Size Pipe O.D. Cover Gasket Clapper Facing Clapper Assembly Inch Inch (DN) (mm) Part Number Americas Only Part Number Americas Only Part Number Americas Only 2 2.37 97670501 595907020 59020EPDM 59020EPDM 97670201 97670201A (50) (60,3) 2-1/2 2.88 97561801 595907030 59025EPDM 59025EPDME 97562065 97562801A (65) (73,0) 76,1 mm 3.00 97561801 595907030 59025EPDM 59025EPDME 97562801 — (65) (76,1) 3 3.50 97561801 595907030 59030EPDM 59030EPDME 97562201 97562201A (80) (88,9) 4 114 3) . 97512001 595907040 59040EPDM 59040EPDME 97549001 97549001A (100) ( 139,7 mm 5.50 97512001 595907040 59050EPDM 59050EPDME 97565501 — (125) (139,7) (155) (5.56 3) 97512001 595907040 59050EPDM 59050EPDME 97562125 97565501A 4165,1 mm 6.50 97521801 595907060 59060EPDM 59060EPDME 97524101 — (150) (165,1) 6 6.63 97521801 595907060 59060EPDM 59060EPDME 97562150 97524101A (150) (168,3) 8 8.63 97547901 595907080 59080EPDM 59080EPDME 97592201 97592201A (200) (219,1) (210 0) (10.75 97600001 595907100 59100EPDM 59100EPDM 97598001 97598001A 12 12.75 97600002 595907120 59120EPDM 59120EPDM 97647701 97647701A (300) (323,9) TABLE A MODEL CV-1F GROOVED END SWING CHECK VALVES REPLACEMENT VALVE PARTS PART NUMBER SELECTION Limited Replacement Valve Parts OUTLET Refer to Figure 2 to identify Parts. Warranty Cover Gasket � 0 `. Specify: Model CV-1F Grooved End For warranty terms and conditions,visit Swing Check Valve,Cover Gasket,size COVER 'I o www.tyco-fire.com. (specify), P/N(specify per Table A) `� o(, Clapper Facing Ordering Specify: Model CV 1F Grooved End Swing Check Valve, Clapper Seal INLET Procedure Facing,EPDM Grade"E",size(specify), VERTICAL ORIENTATIONP/N(specify per Table A) Contact your local distributor for avail- P/N(specify per Table A) ability.When placing an order,indicate Clapper Assembly COVER FLOW the full product name and Part Number Includes items 2,3,5-14,and 17-19. (P/N).imi Specify: Model CV-1F Grooved End � �I.� Model CV-1 F Check Valve Swing Check Valve,Clapper Assembly, I Specify: Model CV-1 F Grooved End size(specify),P/N(specify per Table A) INLET II I OUTLET Swing Check Valve, size (specify), P/N(specify): . _r,' 2 Inch(DN50) 59-590-0-020 HORIZONTAL ORIENTATION 2-1/2 Inch(DN65) 59-590-0-025 76,1 mm(DN65) 59-590-0-076 FIGURE 4 3 Inch(DN80) 59-590-0-030 MODEL CV-1F GROOVED END 4 Inch(DN100) 59-590-0-040 SWING CHECK VALVES 5 Inch(DN125) 59-590-0-050 PROPER ORIENTATION 139,7 mm(DN125) 59-590-0-139 6 Inch(DN150) 59-590-0-060 165,1 mm(DN150) 59-590-0-165 8 Inch(DN200) 59-590-0-080 10 Inch(DN250) 59-590-0-100 12 Inch(DN300) 59-590-0-120 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. fico Fire Protection Products . . P POuu VSR VANE TYPE WATERFLOW e The Symbol of Protection ALARM SWITCH WITH RETARD UL,CUL and CSFM Listed,FM Approved,LPCBApproved,For CE Marked(EN12259-5)/VdS Approved model use VSR-EU - Service Pressure: 450 PSI(31 BAR)-UL Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)-UL Maximum Surge: 18 FPS(5.5 m/s) Contact Ratings: Two sets of SPDT(Form C) 10.0Amps at 125/250VAC l 2.0 Amps at 30VDC Resistive 10 mAmps min.at 24VDC "'lk. , Conduit Entrances: Two knockouts provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: i ,._ • NEMA 4/IP54 Rated Enclosure suitable for indoor or 1 , outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 40°F-120°F,(4.5°C-49°C)-UL • Non-corrosive sleeve factory installed in saddle. Service Use: Specifications subject to change without notice. Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Ordering Information Residential occupancy up to four stories NFPA-13R Nominal Pipe Size Model Part Number National Fire Alarm Code NFPA-72 2" DN50 VSR-2 1144402 21/2" DN65 VSR-21/2 1144425 3" DN80 VSR-3 1144403 • Installation must be performed by qualified personnel and in 3 1/2" - VSR-3 1/2 1144435 accordance with all national and local codes and ordinances. 4" DN100 VSR-4 1144404 • Shock hazard.Disconnect power source before servicing.Serious injury or death could result. 5" - VSR-5 1144405 • Risk of explosion.Not for use in hazardous locations.Serious 6" DNI50 VSR-6 1144406 injury or death could result. 8" DN200 VSR-8 1144408 Optional: Cover Tamper Switch Kit,stock no.0090148 ( .n Replaceable Components:Retard/Switch Assembly,stock no. 1029030 Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF,deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air,or short retard times. General Information Enclosure The Model VSR is a vane type waterflow switch for use on wet sprinkler The VSR switches and retard device are enclosed in a general purpose, systems. It is UL Listed and FM Approved for use on steel pipe; die-cast housing. The cover is held in place with two tamper resistant schedules 10 through 40,sizes 2"thru 8"(50 mm thru 200 mm).LPC screws which require a special key for removal. A field installable approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering cover tamper switch is available as an option which may be used Information chart. to indicate unauthorized removal of the cover. See bulletin number The VSR may also be used as a sectional waterflow detector on large 5401103 for installation instructions of this switch. systems.The VSR contains two single pole,double throw,snap action switches and an adjustable,instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM(38 LPM)or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5401146-REV L PAGE 1 OF 4 3/09 • .. P POTTER VSR VANE TYPE WATERFLOW ® The Symbol of Protection ALARM SWITCH WITH RETARD Installation (see Fig. 1) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6"(15 cm)of a fitting which changes the direction of the waterflow or within 24" (60 cm)of a valve or drain. NOTE:Do not leave cover off for an extended period of time. Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill(see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole.Roll the vane so that it may be inserted into the hole;do not bend or crease it.Insert the vane so that the arrow on the saddle points in the direction of the waterflow.Take care not to damage the non-corrosive bushing in the saddle.The bushing should fit inside the hole in the pipe.Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1).Thevane must not rub the inside of the pipe or bind in any way. . , z Do not trim the paddle.Failure to follow these instructions may prevent the device from operating and will void the warranty. Fig.1 DO NOT LEAVE COVER OFF FOR Retard Adjustment The dela can be adjusted by rotating the retard adjustment knob from ���� y AN EXTENDED PERIOD OF TIME y 1■ 0 to the max setting(60-90 seconds).The time delay should be set at � the minimum required to prevent false alarms '( 011014) TIGHTEN NUTS X. .r.,, .. .{ .:,11.04:) Al1ERNATELY N ".' n'j Hole must be drilled perpendicular to the pipe and vertically centered. Ti pi- gl _,._..... I / Refer to the Compatible Pipe/Installation Requirements chart for size. <444444444:2117' -- Correct Incorrect , , MOUNT ON PIPE SO / ARROW ON SADDLE _ d � POINTS IN DIRECTIONO rp. 11111 � OF WATERFLOW \\\as lin al Y ................., � ROLL PADDLE IN OPPOSITE DIRECTION ADAPTERirt,ADAPTER DIRECTION OF OF WATERFLOW I WATERFLOW \ \ I 20mm=2mm MAX. (Flowing water activates DN50 ONLY device in one direction only.) J USE(2)5180162 ADAPTERS AS SHOWN ABOVE i DWG.11 6-I1 DWG4 146.1? Compatible Pipe/Installation Requirements Pie Wall Thickness Hole Size U-Bolt Nuts Model Nominal Pipe Nominal Pipe p Torque Size 0.D. Schedule 10(UL) Schedule 40(UL) BS-1387(LPC) DN(VDS) inch mm inch mm inch mm inch nun inch mm inch mm inch mm ft-lb n-m VSR-2 2 DN50 2.375 60.3 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 VSR-2 1/2 2.5 - 2.875 73.0 0.120 3.05 0.203 5.16 - - - 1.25+.1251-.062 33.0±2.0 VSR-2 1/2 - DN65 3.000 76.1 - - - - 0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 VSR-3 1/2 3.5 - 4.000 101.6 0.120 3.05 0.226 5.74 - - - 20 27 VSR-4 4 DN100 4.500 114.3 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 2.00+.125 50.8=2.0 VSR-5 5 - 5.563 141.3 0.134 3.40 0.258 6.55 - - - - VSR-6 6 DN150 6.625 168.3 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 NOTE:For copper or plastic pipe use Model VSR-CF. MFG.#5401146-REV L PAGE 2 OF 4 PRINTED IN USA 3/09 ,_ , P POTTERVSR VANE TYPE WATERFLOW ® The Symbol of Protection ALARM SWITCH WITH RETARD Fig.2 Fig.3 Fig.4 Switch Terminal Connections Clamping To remove knockouts:Place screwdriver at Break out thin section of cover when Plate Terminal, inside edge of knockouts,not in the center. wiring both switches from one conduit p I entrance. I . rl oMidc O 0,0°'' oi 1'411' .- .S, '5'/ til©� DWG #1146-16 *kb-4 <- I 1 j1.z. An uninsulated section of a single conductor should not be looped �\ rel r�]✓ around the terminal and serve as two separate connections. The tf -;', � -4>I�/ wire must be severed,thereby providing supervision of the NOTICEconnection in the event that the wire become dislodged from under / the tenninal. Failure to sever the wire may render the device Do not drill into the base as this creates / .! swG 1146-13 inoperable risking severe property damage and loss of life. metal shavings which can create Do not strip wire beyond 3/8"of length or expose an uninsulated electrical hazards and damage the �� conductor beyond the edge of the terminal block.When using device.Drilling voids the warranty. stranded wire,capture all strands under the clamping plate. Fig.5 Typical Electrical Connections BELL To i+i eNotes: , { >.� Pi 1 souRCE 1. The Model VSR has two switches,one can be used to operate a central = i %+I R SUITABLE FOR BELL station,proprietary or remote signaling unit,while the other contact — :4'/ 1 I )iit is used to operate a local audible or visual annunciator. ' • ° ° ° 2. A condition of LPC Approval of this product is that the electrical i- `i= __v.-- o 0 0 entry must be sealed to exclude moisture. = +;1 i I E \ WATERFLOW ZONE 3. For supervised circuits,see"Switch Terminal Connections" Q JJ if EOLR ON FIRE PANEL drawing and warning note(Fig.4). Q ® 6 -• / DNO.114612 Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction(manufacturer recommends quarterly or more frequently). If provided,the inspector's test valve shall always be used for test purposes.If there are no provisions for testing the operation of the flow detection device on the system,application of the VSR is not recommended or advisable. A minimum flow of 10 GPM(38 LPM)is required to activate this device. NOTICE Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig.7 Mounting Dimensions 5.56 in Fig.8 3.50 in 2.00 in (141.2 mm) (89.0 mm) GREEN GROUND (50.8 mm) A SCREWS 4i� i O A 2 '4.6"1114 (59.4 tillill�1 Mill. , ali.n_ U-BOLT NUT PIPE DIA. - -_ +5.25 in ___ _ _ U-BOLT WASHER B MUM i ini (+ ) r� 133.4 mm ����t�` II7I�I�II I I IIII�I PIPE SADDLE I., .' wain. Q I ■ 71 1-4ra 6��E�T1��r7 1 PIPE %% 1 TI: 1nl-,-/i 4 PLASTIC PADDLEMMii.,410 DWG IN6-N , t vi U-BOLT NOMINAL PIPE DIA.+1.75 in(+44 5 MM)FOR DN 50-DN 65 2-2.5 in -��•O DWG IN6-u NOMINAL PIPE DIA.+2.125 in(+54.0 MM)FOR DN 80-DN 200 3-8 in PRINTED IN USA MFG.#5401146-REV L PAGE 3 OF 4 3/09 VSR VANE TYPE WATERFLOW P POTTER ® The Symbol of Protection ALARM SWITCH WITH RETARD Maintenance Inspect detectors monthly. If leaks are found,replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable.In the unlikely event that either component does not perform properly,please order replacement retard switch assembly stock#1029030(see Fig.6).There is no maintenance required,only periodic testing and inspection. Retard/Switch Assembly Replacement(See Fig.6) NOTICE The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe 1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell(if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the(2)mounting screws holding retard/switch assembly to the base.Do not remove the(2)retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly.Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re-install the(2)original mounting screws. 8. Reconnect all wires.Perform a flow test and place the system back in service. Fig. REMOVE(2)ORIGINAL MOUNTING g SCREWS HOLDING RETARD/SWITCH ASSEMBLY TO BASE BREAK OUTTHIN SECTION OF COVER WHEN WIRING BOTH SWITCHES FROM ONE CONDUIT ENTRANCE. (2)ORIGINAL MOUNTING CREWS I I RETARD/SWITCH ASSEMBLY ...,-,44- /III ., / ir , .. V I 0 r,...,1.77ig ,REE_____- Eoll h„. (*0. 'I1-.:.1_,,i111,1U -��11r \_��4r, (2)LOCATING PINS/� I I I (� (2)LOCATING PIN DO NOT REMOVE i I� :� BOSSES IN BASE r (2)RETARD HOUSING I n� SCREWS �� � "'cy _--_III i1�� 1 ��� hC*7 BAS To in G'�•-=�o NT:or DWG#1146-10 Removal of Waterflow Switch • To prevent accidental water damage,all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector,then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers,roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. PRINTED IN USA MFG.#5401146-REV L PAGE 4 OF 4 3/09 P POTTER PS40 SERIES The Symbol of Protection SUPERVISORY PRESSURE SWITCH UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA Accepted,CE Marked Dimensions:3.78"(9,6cm)W x 3.20"(8,1cm)D x 4.22"(10,7cm)H Conduit Entrance: Two knockouts provided for 1/2"conduit.Individual switch compartments and ground screw suitable for dissimilar voltages lr Enclosure: Cover-Die-cast with textured red powdercoat finish,single cover screw and rain lip. Base-Die-cast r., Pressure Connection:Nylon 1/2"NPT male Factory Adjustment: PS40-1 operates on decrease at 30 PSI(2,1 BAR) PS40-2 operates in increase at 50 PSI(3,5 BAR) and on decrease at 30 PSI(2,1 BAR) Pressure Range: 10-60 PSI(,7-4,1 BAR) Differential: Typical 1 lb.at 10 PSI(,07 at,7 BAR) 4 lbs at 60 PSI(,28 at 4,1 BAR) Maximum System Pressure:300 PSI(20,68 BAR) Switch Contacts: SPDT(Form C) 10.1 Amps at 125/250VAC,2.0 Amps at 30VDC One SPDT in PS40-1,Two SPDT in PS40-2 Environmental Specifications: NEMA 4/IP66 Rated Enclosure-indoor or outdoor when used with NEMA 4 conduit fittings. Temperature range:-40°F to 140°F(-40°C to 60°C) Tamper: Cover incorporates tamper resistant fastener that requires a Ordering Information special key for removal. One key is supplied with each device. Model Description Stock No. For optional cover tamper switch kit,order Stock No.0090200. See bulletin#5401200 PSCTSK. PS40-1 Pressure switch with one set SPDT contacts 1340403 Service Use: PS40-2 Pressure switch with two sets SPDT contacts 1340404 Automatic Sprinkler NFPA-13 Hex Key 5250062 One or two family dwelling NFPA-13D Cover Tamper Switch Kit 0090200 Residential Occupancy up to four stories NFPA-13R BVL Bleeder valve 1000018 National Fire Alarm Code NFPA-72 Installation The Potter PS40 Series Supervisory PressureActuated Switches are designed 4. Connect the wires to the appropriate terminal connections for the primarily to detect an increase and/or decrease from normal system pressure service intended. See Figures 2,4,5,6,and 8 in automatic fire sprinkler systems. Typical applications are: Dry pipe systems,pre-action air/nitrogen supervision,pressure tanks, air supplies, Adjustment And Testing and water supplies. The PS40 switch is factory set for 40 PSI(2,8 BAR) The operation of the pressure supervisory switch should be tested upon completion of installation and periodically thereafter in accordance with normal system pressure. The switch marked with the word LOW is set to operate at a pressure decrease of 10 PSI(,7 BAR)at 30 PSI(2,1 BAR). The the applicable NFPA codes and standards and/or the authority having switch marked with the word HIGH is set to operate at a pressure increase jurisdiction(manufacturer recommends quarterly or more frequently). of 10 PSI(,7 BAR)at 50 PSI(3,5 BAR). See section heading Adjustments Note: Testing the PS40 may activate other system connected devices. and Testing if other than factory set point is required. The use of a Potter BVL(see product bulletin 8900067 for details)is recommended to facilitate setting and testing of the PS40 pressure switch. 1. Connect the PS40 to the system side of any shutoff or check valve. 2. Apply Teflon tape to the threaded male connection on the device. When a BVL(bleeder valve)is used,the pressure to the switch can be (Do not use pipe dope) isolated and bled from the exhaust port on the BVL without effecting the supervisory pressure of the entire system. See Fig.3 3. Device should be mounted in the upright position. (Threaded connection down) The operation point of the PS40 Pressure Switch can be adjusted to any 4. Tighten the device using a wrench on the flats on the device. point between 10 and 60 PSI(0,7-4,11 BAR)by turning the adjustment knob(s)clockwise to raise the actuation point and counter clockwise to Wiring Instructions lower the actuation point. In the case of the PS40-2,both switches operate 1. Remove the tamper resistant screw with the special key provided. independent of each other. Each switch may be independently adjusted to 2. Carefully place a screwdriver on the edge of the knockout and sharply actuate at any point acrosss the switch adjustment range. Initial adjustment apply a force sufficient to dislodge the knockout plug. See Fig.9 can be made with a visual reference from the top of the adjustment knob 3. Run wires through an approved conduit connector and affix the across to the printed scale on the switch bracket. Final adjustments should connector to the device. A NEMA-4 rated conduit fitting is be verified with a pressure gauge. required for outdoor use. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400930-REV E PAGE 1 OF 3 09/12 . . P POTTER PS40 SERIES ® The Symbol of Protection SUPERVISORY PRESSURE SWITCH Dimensions Switch Clamping Plate Terminal Fig. 1 Fig.2 (r 100 n GROUND � CO� �" I ( ■ ■ 1 SCREWS IP N4 l:..�=`�. 2.87 ; , ADJUSTMENT 'I�'■r__-•�, [72,97] I PI® 4.22 o KNOB tl.—��� �a [107.191 al i•11.- �7 I I 1/2"NPT 1 Op G DWG#923-3 O\ .11s 2.48 1.60 [62.87] r' [40.64] 3.78 f 3.20 _.y. [95.89] [81.28] - - NOTE:To prevent leakage,apply Teflon tape sealant H male threads only. An uninsulated section of a single conductor DWG4930-1 should not be looped around the terminal and serve as two separate connections. The wire must be severed,thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. Typical Sprinkler Applications Fig.3 PS40 SUPERVISORY PRESSURE SWITCH <: ►' "' AIR LINE ♦ SHUT-OFF Pslo • Closing of any shutoff valves between the alarm VALVEA BLEEDER ALARM check valve and the PS 10 will render the PS 10 CHECK A TEST VALVE SWITCHREinoperative.To comply with IBC,IFC,and VALVE BVL Al 11. WATER NFPA-13,any such valve shall be electrically --> MOT GONGR supervised with a supervisory switch such as CHECK RBVS Potter Model RBVS. DRY PIPE VALVE VALVE OA WATER DWG.#924-1AOs&Y ♦ BY-PASS VALVE • VALVE Typical Connections Fig.4 WITH NORMAL SYSTEM PRES- PS40-1 PS40-2 SURE APPLIED LOW-TERMINAL 2 CLOSES ON PRESSURE DROP. TO FIRE ALARM PANEL cilL11111.;1111•111/11 HIGH 1331[M.114 AIR `/WM" 61. ������� LOW WITH NORMAL SYSTEM PRESSURE APPLIED HIGH TO FIRE EOLR AIR -TERMINAL I WILL CLOSE ALARM ON PRESSURE INCREASE. PANEL EOLR DWG#930-2 PRINTED IN USA MFG.#5400930-REV E PAGE 2 OF 3 09/12 . . P POTTER PS40 SERIES ® The Symbol of Protection SUPERVISORY PRESSURE SWITCH Low Pressure Signal Connection High Pressure Signal Connection One Conduit Wiring Fig.5 Fig.6 Fig.7 TO FIRE ALARM PANEL TO FIRE ALARM PANEL Break out thin section of divider to provide path for wires in when wiring both switches from one conduit entrance. ®v , .<<- i 1 ®®a--Z10 0 -- ,TMI— I= TRITATAT 1uri0 I ,�� T ® sI;IIIIOWOS . o ® �>,�..v_.-. imi- Mill DWG#928-4 Changing Pressure Removing Knockouts (With normal system pressure) Fig.9 Fig.8 Terminal LOW PRESSURE SWITCH C:Common 1: Closed when installed under normal system c pressure. 2: Open when installed tIli .' —hiliP under normals stem A pressure.Closes on c , m C�1". . pressure drop.Use for ►i�.��w low air signal. /% I Terminal HIGH PRESSURE SWITCH /,�,� A� 1: Open when installed under normal system c `.,,® �j pressure.Closes on � /�� > Use for inpressure.signal. o � � � Use for high air si 2: Closed under normal o system pressure. DWG#928-5 DWG#930-3 Engineer/Architect Specifications Pressure Type Waterflow Switch Pressure type supervisory switches;shall be a Model PS40 as manufactured by Potter Electric Signal Company,St.Louis,MO.,and shall be installed on the fire •Installation must be performed by qualified personnel and in accordance with all sprinkler system as shown and or specified herein. national and local codes and ordinances. Switches shall be provided with a 1/2"NPT male pressure connection to be •Shock hazard.Disconnect power source before servicing.Serious injuty or death connected into the air supply line on the system side of any shut-off valve. A could result. Model BVL bleeder valve as supplied by Potter Electric Signal Company of St. •Read all instructions carefully and understand them before starting installation. Save instructions for future use. Failure to read and understand instructions could Louis,MO.,or equivalent shall be connected in line with the PS40 to provide a result in improper operation of device resulting in serious injury or death. means of testing the operation of the supervisory switch.(See Fig.3) •Risk of ex•losion.Not for use is hazardous locations.Serious injm or death could result. The switch unit shall contain SPDT(Form C) switch(es). One switch shall be set to operate at a pressure decrease of 10 PSI(0,7 BAR)from normal. If two switches are provided,the second switch shall be set to operate at a pressure increase of 10 PSI(0,7 BAR)from normal. - • 'CAUTIONt Switch contacts shall be rated at 10.1 Amps at 125/250VAC and 2.0 Amps at •Do not tighten by grasping the switch enclosure. Use wrenching flats on the bushing 30VDC. The units shall have a maximum pressure rating of 300 PSI(20,68 BAR) only. Failure to install properly could damage the switch and cause improper operation and shall be adjustable from 10 to 60 PSI(0,7 to 4,1 BAR). resulting in damage to equipment and property. Pressure switches shall have two conduit entrances,one for each individual switch •To seal threads,apply Teflon tape to male threads only. Using joint compounds or compartment to facilitate the use of dissimilar voltages for each individual switch. cement can obstruct the pressure port inlet and result in improper device operation and The cover of the pressure switch shall be zinc die-cast with rain lip and shall attach damage to equipment. •Do not over tighten the device,standard piping practices apply. with one tamper resistant screw. The pressure switch shall be suitable for indoor or •Do not apply any lubricant to any component of the pressure switch. outdoor service with a NEMA-4/IP66 rating. The pressure switch shall be UL,ULC,and CSFM listed,FM and LPC approved and NYMEA accepted. PRINTED IN USA MFG.#5400930-REV E PAGE 3 OF 3 09/12 . , P POTTER PS10 SERIES ® The Symbol of Protection PRESSURE SWITCH .-� UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA Accepted,CE Marked Dimensions:3.78"(9,6cm)W x 3.20"(8,1cm)D x 4.22"(10,7cm)H QaPOTTER Conduit Entrance:Two knockouts provided for 1/2"conduit. Individual Tls syms.o/Pmmcrion s..s Miss°"r, switch compartments and ground screws suitable for Model Number PS10_z C f dissimilar voltages. w»� Enclosure: Cover-Die-cast with textured red powdercoat finish,single cover screw and rain lip. Base-Die-cast Pressure Connection:Nylon 1/2"NPT Male Factory Adjustment: 4-8 PSI(0,27-0,55 BAR) Differential: 2P SI(0,13 BAR)typical Maximum System Pressure: 300 PSI(20,68 BAR) Switch Contacts: SPDT(Form C) 10.1 Amps at 125/250VAC,2.0 Amps at 30VDC Ordering Information One SPDT in PS 10-1,Two SPDT in PS 10-2 Model Description Stock No. Environmental Specifications: PS 10-1 Pressure switch with one set 1340103 NEMA 4/IP66 Rated Enclosure-indoor or outdoor when used SPDT contacts with NEMA 4 conduit fittings. PS 10-2 Pressure switch with two sets 1340104 Temperature range:-40°F to 140°F(-40°C to 60°C) SPDT contacts Service Use: Hex Key 5250062 Automatic Sprinkler NFPA-13 Cover Tamper Switch Kit 0090200 One or two family dwelling NFPA-13D Tamper Residential Occupancy up to four stories NFPA-13R Cover incorporates tamper resistant fastener that requires a special key for National Fire Alarm Code NFPA-72 removal.One key is supplied with each device. For optional cover tamper switch kit,order Stock No.0090200. See bulletin#5401200 PSCTSK. Installation The Potter PS IO Series Pressure Actuated Switches are designed for the into alarm port piping on the input side of retard chamber and electrically detection of a waterflow condition in automatic fire sprinkler systems of connect PS 10 to control unit that provides a retard to compensate for surges. particular designs such as wet pipe systems with alarm check valves,dry Insure that no unsupervised shut-off valves are present between the alarm pipe,preaction,or deluge valves. The PS10 is also suitable to provide a check valve and PS I0. low pressure supervisory signal;adjustable between 4 and 15 psi(0,27 and Method 2: When using the PS10 for local bell application or with a control 1,03 BAR). that does not provide a retard feature-the PS 10 must be installed on the alarm 1.Apply Teflon tape to the threaded male connection on the device. outlet side of the retard chamber of the sprinkler system. (Do not use pipe dope) Testing: Accomplished by opening the inspector's end-of-line test valve. 2.Device should be mounted in the upright position(threaded connection down). Allow time to compensate for system or control retard. 3.Tighten the device using a wrench on the flats on the device. Note: Method 2 is not applicable for remote station service use,if there is an Wiring Instructions unsupervised shut-off valve between the alarm check valve and the PS 10. 1.Remove the tamper resistant screw with the special key provided. Wet System With Excess Pressure 2.Carefully place a screwdriver on the edge of the knockout and Connect PS10 into alarm port piping extending from alarm check valve. sharply apply a force sufficient to dislodge the knockout plug.See Fig 9 Retard provisions are not required. Insure that no unsupervised shut-off 3.Run wires through an approved conduit connector and affix the connector valves are present between the alarm check valve and the PS 10. to the device. Testing: Accomplished by opening the water by-pass test valve or the 4.Connect the wires to the appropriate terminal connections for the inspector's end-of-line test valve. When using end-of-line test, allow time service intended.See Figures 2,4,5,and 6.See Fig 7 for two switch,one for excess pressure to bleed off conduit wiring. Dry System Testing Connect PS10 into alarm port piping that extends from the intermediate The operation of the pressure alarm switch should be tested upon completion chamber of the alarm check valve. Install on the outlet side of the in-line of installation and periodically thereafter in accordance with the applicable check valve of the alarm port piping. Insure that no unsupervised shut-off NFPA codes and standards and/or the authority having jurisdiction valves are present between the alarm check valve and the PS 10. (manufacturer recommends quarterly or more frequently). Testing:Accomplished by opening the water by-pass test valve. Wet System Note: The above tests may also activate any other circuit closer or water Method 1: When using PS 10 and control unit with retard-connect PS 10 motor gongs that are present on the system. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400928-REV D-1 PAGE 1 OF 3 12/10 , ., P POTTER PS10 SERIES e The Symbol of Protection PRESSURE SWITCH Dimensions Switch Clamping Plate Terminal Fig. 1 Fig.2 �ivy! 00 I IIs. 1 SCREWS `� dcCo" ' � i 2.87 I I . ADJUSTMENT IiI.r-- ,, [72.97] �>\Y/ I.' ■1 ® 4.22 [ _ 1.- 4/ KNOB ��_� i [107.19] Ii n d MEM r 7 GOO DWG#923-3 1/2"NPT oU 2.48 F I 1.60 ---."1 [62.87] [40.64] 3.78 - . 3.20 An uninsulated section of a single conductor [95.89] [81.28] should not be looped around the terminal and serve as two separate connections. The wire NOTE:To prevent leakage,apply Teflon tape sealant to male threads only. must be severed,thereby providing supervision of the connection in the event that the wire DWG#930-1 becomes dislodged from under the terminal. Typical Sprinkler Applications Fig.3 WET SYSTEM WITHOUT DRY SYSTEM WET SYSTEM WITH EXCESS PRESSURE PRESSURE PSIO PSIO PSI0 WATER WATER WATER MOTOR MOTOR MOTOR Alin GONG GONG GONG CHECK RBVS RBVS RBVS DRY VALVE WET SYSTEWET SYSTEM ALARM ALARM M SYSTEM . CHECK CHECK CHECK RETARD VALUE VALVE *1 VALVE p,4 WATER WATER WATER OS&Y V BY-PASS VA&.E V BY-PASSOS&Y ♦ BY-PASS VALVE A VALVE VALVE VALVE VALVE A VALVE, DWG.#923-2AA e s Ate., .. ., Closing of any shutoff valves between the alarm check valve and the PS I0 will render the PSIO inoperative.To comply with NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model RBVS. Low Pressure Signal Connection Waterflow Signal Connection Local Bell For Waterflow Connection Fig.4 Fig.5 Fig.6 NEGATIVE DC TO FIRE ALARM PANEL TO FIRE ALARM PANEL OR NEUTRAL AC MI LINE LOAD POSITIVE DC OR AC �_. _— ------� o o ��----1 ® 0 r,►_,Infra."'1 O 0 (r'awn. _ 17,0,1"1 iri .O O IL p lio O 10101 o 0 -��1ui. DWG -----.1r11 p 92&5 WGp 920.-2 DWGa 92ft-I MFG.#5400928-REV D-1 PAGE 2 OF 3 PRINTED IN USA 12/10 . , P POTTER PS10 SERIES ® The Symbol of Protection PRESSURE SWITCH One Conduit Wiring Switch Operation Removing Knockouts Fig.7 Fig.8 Fig.9 Break out thin section of divider to provide path for wires Terminal w/PRESSURE APPLIED when wiring both switches from one conduit entrance. C:Common I: Closed when installed lit _ under normal system �rs�— pressure. p��\ �nj �njrlj �° �° 2: Open when installed under normal system I bl fi© o o ® pressure.Closes on LI 1111��110� Terminal W/O PRESSURE APPLIED '� 4- -� l: Open with no pressure � � El supplied.Closes upon �� �' EMIdetection of pressure. ��� � � Use for waterflow indication. ��� Dwcn 928-4 2: Closed with no DWG#928-5 pressure applied. DWGN928-6 •Installation must be performed by qualified personnel and in ice.. •Do not tighten by grasping the switch enclosure.Use wrenching accordance with all national and local codes and ordinances. flats on the bushing only.Failure to install properly could damage •Shock hazard.Disconnect power source before servicing. the switch and cause improper operation resulting in damage to Serious injury or death could result. equipment andproperty. •Read all instructions carefully and understand them before •To seal threads,apply Teflon tape to male threads only. Using starting installation.Save instructions for future use.Failure to joint compounds or cement can obstruct the pressure port inlet read and understand instructions could result in improper and result in improper device operation and damage to equipment. operation of device resulting in serious injury or death. •Do not over tighten the device,standard piping practices apply. •Risk of explosion.Not for use is hazardous locations.Serious injury or death could result. Engineer/Architect Specifications Pressure Type Waterflow Switch Pressure type waterflow switches;shall be a Model PS 10 asPressure switch shall have one or two form C contacts,switch contact manufactured by Potter Electric Signal Company,St Louis MO., rating 10.1 Amps at 125/250 VAC,2.0 Amps at 30 VDC. and shall be installed on the fire sprinkler system as shown and or Pressure type waterflow switches shall have two conduit entrances specified herein. one for each individual switch compartment to facilitate the use of Switches shall be provided with a'/2"NPT male pressure connection dissimilar voltages for each individual switch. and shall be connected to the alarm port outlet of;Wet Pipe Alarm The cover of the pressure type waterflow switch shall be Zinc die-cast Valves,Dry Pipe Valves,Pre-Action Valves,or Deluge Valves.The with rain lip and shall attach with one tamper resistant screw.The pressure switch shall be actuated when the alarm line pressure reaches Pressure type waterflow switch shall be suitable for indoor or outdoor 4-8 PSI(0,27-0,55 BAR). service with a NEMA 4/IP66 rating. Pressure type waterflow switches shall have a maximum service The pressure type waterflow switch shall be UL Ulc and CSFM listed, pressure rating of 300 PSI(20,68 BAR)and shall be factory adjusted FM and LPC approved and NYMEA accepted. to operate on a pressure increase of 4-8 PSI(0,27-0,55 BAR) PRINTED IN USA MFG.45400928-REV D-1 PAGE 3 OF 3 12/10 . P POTTER ® The Symbol of Protection PBA-AC & MBBELLSA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC 120VAC 12VDC(10.2 to 15.6)Polarized " 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm .... '''''',40,.' ' General Signaling 4.75 Burglar Alarm •, Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) _ Termination: AC Bells-4 No. 18 AWG stranded wires 0 ® .P<Mo (0) DC Bells-Terminal strip * Finish: Red powder coating Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No. 1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA-6-12 1750070 .12A 85 76 8(200) 12VDC MBA-8-12 1750080 .12A 90 77 10(250) 12VDC MBA-10-12 1750060 .12A 92 78 6(150) 24VDC MBA-6-24 1750100 .06A 87 77 8(200) 24VDC MBA-8-24 1750110 .06A 91 79 10(250) 24VDC MBA-10-24 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing. In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company, LLC • St. Louis, MO, • Phone: 866-572-3005/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 1 OF 2 01/13 , P POTTER BELLS e The Symbol of Protection PBA-AC & MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C.BELLS WHITE(IN) WHITE(OUT) (25O) $" PROM CON:ORTROL CPT161%) _(200) 6„ AEL(� I PRECEDING BELL (150) CAUPTION 1 BLACK(IN) l/ BLACK(OUT) WHEN ELECTRICAL SUPERVISION IS REQUIRED USF.IN AND OUT LEADS AS SHOWN. 211/16" (68) NOTES: DWG#776-1 I.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2.END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS. "W0#776-, Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded 1/2"conduit entrance ill ArIll 13 3/8" 5" J To Next 5 3/4" 0 — (86) (127) (146) Device or End-of-Line Resistor I1jw-'r 3(38/68;3/8" 1 5/8" (86) (41) f_ 4 1/4" _,.... (108) Installation DWG#776-2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and I not less than 6"below the ceiling. 2. Remove the gong. 3. Connect wiring(see Fig.3). 4. Mount bell mechanism to backbox(bell mechanism must be mounted with the striker pointing down). D 5. Reinstall the gong(be sure that the gong positioning pin,in the mechanism housing,is in the hole in the gong). 6. Test all bells for proper operation and observe that they can ° �,,‘,\0 "1be heard where required(bells must be heard in all areas as sax-1 designated by the authority having jurisdiction). Failure to install striker down will prevent bell from operating. PRINTED IN USA MFG.#5400776-REV v-1 PAGE 2 OF 2 01/13 Pipe Clamps Fig.28M - Offset Hanger& Restrainer for CPVC Plastic Pipe and IPS Steel Pipe** COTtl.co- Size Range: 3/4° (20mm)thru 2" (32mm) Suz Material: Steel, Pre-Galvanized Function: Designed to be used as a hanger and restrainer for CPVC piping or steel piping where the "stand-off" design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces • Unique snap-on design holds pipe firmly in place and allows retrofit type of installation •The "Stand-Off" design eliminates the need for wood block extension •Can be installed on horizontal or vertical piping regardless of mounting surface orientation A •Attaches easily to wood structure with two hex head self-threading screws furnished with product • Installs easily using rechargeable electrical driver with 5/16" (7.9mm)extension socket eliminating impact tool damage to pipe •Attaches easily to steel, minimum 18 gauge (1.024mm)with (2) 1/4" x 1" tek type self I' drilling tapping screws c •cULus Listed as a hanger and a restrainer for fire sprinkler piping Installation Note: When installed in wood structural members and threads from the #10 x 1"screws are exposed, use Fig. 27B speed nut to secure B Approvals: Underwriters Laboratory Listed in the USA(UL)and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fasteners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. { f' Order By: Figure number and pipe size Fig.27B Patent#7,744,042 (2)Required r **With reduced spacing, consult factory. / F?� ss,,,,,,,,-;---- I, , -• ;u _ mss, T t d ° ' ' n A d ---+_-- J U—y ° ---Y Hanger and Restraint a r 1 Application d a 4 d enL__- _____J ----5 / Restraint Fig'276 E -----1 (1)Required U --A High Side of Hangera. a Restraint tg Detail A Hanger Application Pipe Size A Hole Dia.B C Max Spacing* Approx.Wt./100 Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) 28M-3/4 .3/4" (20) 2" (50.8) 3/16" (4.8) 35/16" (84.1) . 5'-6" (1676) 9 (4.1) 28M-1 1" (25) 21/8" (54.0) 3/16" (4.8) 31/2" (88.9) 6"-0" (1829) 12 (5.4) 28M-11/4 11/4" (32) 25/1(' (58.7) 3/16" 14.8) 31/2" (88.9) 6'-6" (1981) 13 (5.9) 28M-11/2 11/2" (49) 27/16" (61.9) 3/16" (4.8) 37/8" (98.4) T-0" 12133) 14 (6.3) 28M-2 2'" (50) 25/8" (66.7) 3/16°' (4.8) 47/16"(112.7) 8'-0" (2438) 15 (6.8) • Required per NFPA 13 for CPVC plastic pipe All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 41 B-Line by E:Ton Pipe Clamps Fig. 23 - Hanger for CPVC Plastic Pipe& IPS Steel Pipe** ®TOLca Double Fastener Strap (B-Line B3182) C®418 Size Range: 3/4"(20mm)thru 3"(80mm) CPVC pipe LISTS Material: Pre-Galvanized Steel Function: Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. Fig.23 can be installed on the top, bottom or side of a beam. Approvals: Underwriters Laboratories Listed in the USA(UL) and Canada (cUL)sizes 3/4"(20mm)thru 2"(50mm)to support fire sprinkler piping. May be installed in wood using fasteners supplied r„ ‘,- -.7(.0 with product, or into minimum 20 gauge(0.9mm)steel using(2) 1/4"x 1"tek type screw. Meets and exceeds the requirements of NFPA 13, 13R and 13D.Features: Fig. 23 incorporates features which protect the pipeB and ease installation.The flared edge design protects the CPVC pipe from any rough surface. It also incorporates snap restrainers allowing easier and faster installation. Easily attaches to the building B A structure using the two UL Listed hex head self threading screws* c furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer)are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish: Pre-Galvanized Order By: Figure number and pipe size * Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. 44. **With reduced spacing, consult factory. CPVC Max.Hanger Fastener Hex Approx. Pipe Size A B C Spacing Head Size Wt./100 Part No. in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) in. (mm) Lbs. (kg) E 23-3/4 3/4' 120) 31/8" (79.4) 19/16° 139.7) 13/16" (30.2) 51/2 (1.67) 5/16': (7.9) 9 {4.1) cj 23-1 1" 1251 33/8" 185.7) 111/16" (42.9) 13/16" (30.2) 6 (1,83) 5/t6' (7.91 9 (4.1) a 23-11/4 11/4" (32) 33 3 1 5 ¢ ,,$/16"(106.4) 2/32" :153.1) 1 /16" (30.21 6/2 (1.981 /i6" (7.9) 11 (5.0) 23-11/2 11/2" (401 42/16" (112.71 22/32" (56.3) 13/16" (30.2) 7 (2.13) 5f16" (7.91 12 (5.41 23-2 2' (501 47/8".1123.8) 27/16" 161.9) 13/16" (30.2) 8 12.44) 5/16" 17.9). n 15 (6.8) 23-21/2 21/2" (651 53/8" (136.51 211/16" (68.31 13/16" (30.2) Consult Factory 5/16" (7.9) 22 (10.0) 23-3 3" (80) 6" (152.4) 3" (76.2) 13/16" (30.2) Consult Factory 5/is' (7.9) 25,(1131 All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. {� r. Fire Protection Solutions 37 B-Line w Pipe Hangers Fig.200 - "Trimline"Adjustable Band Hanger (B-Line Fig.B317ONF) eiroLcri Fig. 200F- "Trimline"Adjustable Band Hanger with Felt Lining (B-Line Fig.B317ONFF) CC)1111 Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) tlrEo Fig.200S - "Trimline"Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications s Function: For fire sprinkler and othergeneral piping V p p�p g purposes. Knurled swivel nut design permits hanger adjustment after installation. �% Features: • (1/2" (15mm)thru 2" (5omm)) Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design i keeps adjusting nut from separating with hanger. Hanger is easily o \ B installed around pipe. . For hanger with non captured nut order Fig. 200S. a • (21/2" (65mm)thru 8" (20omm))Spring tension on nut holds it securely in hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed (1/2" (15mm)thru 8" (2oomm)) in the USA(UL)and Canada (cUL)for steel and CPVC plastic pipe and Fig.2oo-t/z.?°°-3/0 Factory Mutual Engineering Approved(FM)(3/4" (20mm)thru 8" (200mm)). Fig200-1 to 200-2 Fig.200-21/2 to 200-8 Conforms to Federal Specifications\MN-H-171 E&A-A-1 192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, Type 10. i- Maximum Temperature: 650°F(343°C) 1 1 Finish: Pre Galvanized. Stainless Steel q materials will be supplied with (2) hex nuts " in place of a knurl nut. Order By: Figure number and pipe size Designed to meet or exceed requirements of FM DS 2-0. Fig.200 Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 , Part No. in. (mm) in. (mm) in. (mm) lbs. (kg) '; 1 200-1/2 1/2" (15) 3/8"-16 31/8" (79.4) 25/8° (66.7) 11 (5.0) ::,L,,,, 200-3/4 3/4" (20) 3/8"-16 31/8 (79.4) 21/2" (63.5) 11 (5.0) 200-1 1° (25) 3 «- 3 5 �, /8 16 3/8 (85.71 2/8« (66:7) 12. (5.6) 200-11/4 11/4" (32) 3/8"-16 33/4" (94.0) 27/8" (73.0) 13 (5.91 200-11/2 11/2" (40) 3/t"-16 37/8" (98.4) 27/8" 173.0) 14 (6.4) I` .. 200-2 2" (50) 3/8"-16 41/2' (114.31 3" (76.3) 15 (6.9) 200-21/2 21/2` (65) 3/8"-16. 55/8" (142.9) 41/8" (104.7) 27 (12.3) 200-3 3" (75) 3/8"-16 57/8 (149.1) 4" (101.6) 29 (13.31 Fig.200S 200-31/2 31/2" (90) 3/8"-16 73/8« (187.3) 51/4" (133.3) 34 (15.6) 200-4 4" (100) 3/8"-16 73/8" 1187.3) 5" (127.0) 35 (16.0) 200-5 " 1125) 1/2°-13 91/8 (231.8) 61/4« (158.7) 66 (30.2) it 200-6 6" (150) 1/2"-13 101/8" (257.2) 63/4" (171.4) 73 (33.4) 200-8. 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 21 B-Line by Eallt' a 1 1,,a i::1"4:7—'4:';I:;:• i< ;I T. .,x, '= 7 ; zfi17 ,r-xs yam, 7 .5,'::,:3e:-.':',:'-'-..7,,,,,,,,,." ._,.,...,....„.„,:,,,..„.,,,,,,,,,,.....,.,.,,,,;,,,,..... .„,...,....;,..„2„,„,,. ..,.,,,:,,,,,:„,,,,..,...,...,,,....7.,...::.„.,..„......„,„,,,,,.,...,-„,„,.. .,...„„.„.::,:fr.,,,,,,,.."„ ,„:::„., ,,:::,:k,!,_„'?1,„,,,,,c „.:.::....,,,,,,:-..:•:-,,,, ,..,,,:;,,,,,,;:. ..",,,.°.'.::::1 'i,',': ::"0'.14•14f4i'''''' "i i YIS::7-'4:'':V • :: -,,l''' ,rp 3 :r ...c:-.-.:-,14,-,...--,--.:,'„.. -':.....,..:.-•it....:,,,- ='_--", ',1'.:T.: .:-..7::'.:". ...':'...'f',.';'':',:"':'..;'.....,...,:'-:::: ''''.;43',Y;'.!.'ir'..::';',......it:',;;;;:'.':-..':':.,,,,,,. SAMMYS° FOR WOOD - Vertical Application Application Product Features Not less than Wood Flooring 2"nominal width •No pre-drilling required. (t� •Quick to install using the Sammy • Not less than Nut Driver with an 18V cordless 3"nominal drill/driver. thickness(2-1/2") (depth or side Wood Joist I jot vertical member) &SW •Saves time from traditional ®v methods. ' Double Sheetrodc For vertical use- Ceiling •Reduces installation costs. install in center of lower face. Minimum 2"embedment into base •Manufactured in the U.S.A. material for NFPA 13 compliance. Composite/Truss Consult truss manufacturer for recommended installation point. *Pre-drilling may be required for GST ' 25-380.Tool available on page 11. ! Watch a video demonstm8on at " .itwbuildexcom Approvals Rart w timte UL esM Sizeod Number Model DescriptionsScrePullout a(lbs) Load Tbt(ls) Load FTt Box(lbs) Qty CaseQty VERTICAL MOUNT 1/4" 8002957 GST 100 1/4 x 1" 210(7/16"OSB) 25 125 670 (3/4"Ply) .'1/4" £4.. ',57,!.,' y :...i--.M0714 `vM 117•,°. , ; `, -, ;- 3/8" 8007957 GST 10 1/4 x 1" 2670 (3/46PIOy)B) 300 25 125 , " ..:, - ' :'; 114= r g` ", . Q. 3/8" 8068925 GST 20 SS 1/4 x 2 1760 (Fir) 850 25 125 #14 Blackire''''..«;-''',07.4,4..$::,--,, r tgat 1i' r} ria s Nut Driver 4i1 ea> Part#Driver811390 3/8" 8010957 GST 30 1/4 x 3 2060 (Fir) 1500 1475 25 125 1/2 8013925 GST2 1/4x2 1760(Fir) 25 125 #14 SW Red Nut Driver Part#8114910 t� MANUFACiUREDUS.ATe es. SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. For the most up to date information,visit www.itwbuildex.com 4 ZAMENVZ' SIDEWINDER® FOR WOOD -Horizontal Application Application Product Features Not less than 2"nominal width •No pre-drilling required. (1-1/2°)up to 3-1/2°pipe;not less than 3"(2-1/2°)nominal width4°&5"pipe •Quick to install using the Sammy Floor Joist Nut Driver with an 18V cordless Minimum 2-1/2"from bottom for drill/driver. Ibranch lines.Minimum 3°from bot- tom for main lines.Exception:This •Saves time from traditional requirement shall not apply to 2"or methods. thicker nailing strips resting on top of steel beams. •Reduces installation costs. •Made in the U.S.A. 1" Composite I Truss Consult truss manufacturer for recommended installation point. ' `Pre-drilling may be required for Model SWG 25-380.Tool available on page 11. Watch a video demonstration at n. wwwitwbuildex.com Approvals Rod Part Model Screw Ultimate UL Test Box Case Size Number Descriptions Pullout(lbs) Load(lbs) Qty Qty HORIZONTAL MOUNT 1/4" 8019957 SWG 200 1/4 x 2" 1725(Fir) 25 125 3/8" 8021957 SWG 20 1/4 x 2 1725 (Fir) 1050 25 125 } Q 3/8 8022925 SWG 25-380 3/8 x 2-1/2" 2249(Fir) 1500 25 125 #14SWRed '# t ., ° rf• _ 0.: ..• n .,r8 'W...,...t. ur :.?0!` ,.S. ..<:-,'W" . ;;,`' . fry '12:',s.,:'-', Nut Driver ' Part#8114910 "May require pre-drilling;consult joist manufacturer. W Ct SAMMYS SWIVEL HEAD— FOR WOOD -Swivel Application Application Product Features V mconsT �wanrn •Eliminates distortion of threaded rod. •Accommodates up to 3%"x 12 pitch roof. ' *Allows 17°deflection from vertical. Cl) ` WO •Saves time from traditional methods. W •Reduces installation costs. 4i 1 aLl ,t, M •Made in the U.S.A. 0 P Cl) Rod Part Screw Ultimate UL Test Load FM Test Min Box Case W Approvals Model Size Number Descriptions Pullout(lbs) (lbs) Load(lbs) Thickness Qty Qty SWIVEL MOUNT #14 DBlrivacker — ,Q 3/8" 8139957 SH GST 20 1/4 x 2" 1257(Fir) 1050 1475 25 125 R Nut .art#8113910 , t v'- i ., „,,,i '' :_a_,. , s.:: 1903 Dim.Lumber 3/8"" 8269957 SH-GST/CST 20 5/16 x 1-3/4" 1406 @ 45°off vertical 8500 @ 45° 25 125 Dim.Lumber !w .: Y a '4,Fief u § a 1 Psa M ` ,J,, require pre-drilkng;consult joist manufacturer. O #14 SH Orange 0 Nut Driver Part#8273910 4 Q 5 To find a distributor near you call 800-BUILDEX Seismic Bracing Fig. 1001 - Sway Brace Attachment ®TOL D Size Range: Pipe size to be braced: 1"(25mm)thru 8"(200mm) IPS. Pipe size used for bracing: 1"(25mm)and 11/4"(32mm) Schedule 40 IPS. C (2) US ti Material: Steel LISTED 3ap ' Function: For bracing pipe against sway and seismic disturbance. E. The pipe attachment component of a sway brace system: EF Fig. 1001 is used in conjunction with a Fig. 900 Series fitting and R. joined together with bracing pipe per NFPA 13, forming a complete 2 sway brace assembly. Features: Can be used to brace schedules 7 through 40 IPS.Field adjustable, making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no threading of bracing *le pipe. Comes assembled and ready for installation. Fig. 1001 has built-in visual verification of correct installation. See installation note below. Installation Note: Position Fig. 1001 over the pipe to be braced Set Bolts and tighten two hex head cone point set bolts until heads bottom t Included out.A minimum of 1"(25mm)pipe extension is recommended. Brace pipe can be installed on top or bottom of pipe to be braced. Approvals: Underwriters Laboratories Listed in the USA(UL) and Canada (cUL). For FM Approval information refer to page 71. ' .r � : Finish: Plain or Electro-Galvanized. Contact B-Line for alternative finishes and materials. d Order By: Order by figure number, pipe size to be braced, followed by pipe size used for bracing (1"(25mm)or 11/4"(32mm)), and finish. Important Note: Fig. 1001 is precision manufactured to perform its *. function as a critical component of a complete bracing assembly.To ensure performance,the UL Listing requires that Fig. 1001 must be used only with other TOLCO bracing products. Pipe I Part Number&Approx.Wt./100 Design Load-Lbs. Size 1"(24mm)Brace Pipe 11/4"(32mm)Brace Pipe For Brace Pipe Size 1"/11/4" Sch.7 Sch.10 Sch.40 in. (mm) Lbs. (kg) Lbs. (kg) 1"111/4" 1"/11/4" 1"/11/4" 1" (25) 1001-1 X 1 100.0 (453) : 1001-1 X 11/4 118.0 (53.5) --/-- 1000/1000 1000/1000 11/4"(32) 1001-11/4 X 1 100.0 (45.3) 1001-11/4 X 11/4 114.0 (51.7) 1000/1000 1000/1000 1000/1000 11/2"(40) 1001-11/2 X 1 100.0 145.3) 1001.11/2 X 11/4 115.0 (52.1) 1000/,1000 1500/1500 f; 1500/1500 2" (501 1001-2 X 1 108.0 (49.0) 1001-2 X 11/4 121.0 (54.8) 1000/1000 2015/2015 2015/2015 21/2"1651 1001-21/2 X 1 138:6 162,8) 1001-21/2 X 11/4 160.4 (72.7) 1600/1600 2015/2765 2015/2765 3" (80) 1001-3 X 1 147.2 (66.7) 1001-3 X 11/4 168.7 (76,5) 1600/1600 2015/2765 2015/2765 4" (100) ' 1001-4 X 1 160.9 (73.0) r 1001-4 X 11/4 182.4 (82.7) 1600/1600 2015/2765 2015/2765 6" (150) 1001-6 X 1 190.0 186.2) 1001-6 X 11/4 211.4 (95.9) 1600/1600 2015/2765 2015/2765 8" (200) j 1001-8 X 1 217.4 (98.6) 1001-8 X 11/4 238.8 (108.3) 1600/1600 2015/2765 2015./2765 .ri co, ..„.„.„...,„, \O'c). 111",111 a 0,, .,.. . BW. u All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. ne Revised 5/9/2014 Fire Protection Solutions by 'ITM 70 Seismic Bracing Fig.4L- Longitudinal In-Line Sway Brace Attachment Size Range: 21/2"(65mm)through 8"(200mm) IPS. litifr Material: Steel APPROVED Function: For bracing pipe against sway and seismic disturbance. Set Bolt&Hardware Included rn c ti Approvals: Approved by Factory Mutual Engineering(FM), 21/2"(65mm) '� co through 8'(200mm)pipe. , m For UL Listed information refer to page 50. �7 '£ Installation Instructions: Fig.4L is the"braced pipe"attachment co component of a longitudinal sway brace assembly. It is intended to be A combined with the"bracing pipe"and TOLCO structural attachment component to form a complete bracing assembly. NFPA 13 and/or FM guidelines should be followed. To Install: Place the Fig.4L over the pipe to be braced and tightenD bolts.Then engage "bracing pipe" into jaw opening and tighten set bolt until head snaps off.Jaw attachment can pivot for adjustment to proper t'glib. ' brace angle. Finish: Plain. Contact B-Line for alternative finishes and materials. c 7i Order By: Figure number, pipe size and finish. Designed to meet or exceed requirements of FM DS 2-8. r , ./.,0 ,_•••••••1'.•••,.---7.'''' -,:,..-.._.............,4, '-:',.'„:..,......,.... ,„ i .'• OE III '• 4 0 6 4-Way Riser Brace t ; L. .1 (plan view) Longitudinal Brace Pipe Max.Rec.Load(FM) Approx. Part Size A C D Bolt Size 30°-44° 45°-59° 600-74° 75°-90° WtJ100 No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kg) 4L-2'/2 21/2" (651 67/16" (163.5) 21/2" (63.51 23/4" (69.81 1/2"-13 1030 (4.58) 1180 15.24) 1420 (6.31) 1590 17.07' 253 (114.71 41-3 3" (801 7" (177.8) 23/4' (69.8) 31/16" (77.81 1/2"-13 1030 14.58) 1180 15.241 1420 (6.311 1590 17.07) 268 (121.5) 41-4 4" (100) 81/2" (215.9) 33/8' (85.7) ' 311/16"(93.7) 1/2-13 . 530"12.36) 730 (3.25) " 890 (3.96)"', 990 (4.40) 348 (157.8) 41-5 5" 1125) 93/4" (247.6) 37/8" (98.4) 43/8"(111.1) 1/2"-13 530 (2.36) 730 13.25) 890 (3.96) 990 (4.40) 380 (172.3) 41-6 6' (150) 111/2' (292.1)` 1 5" (127.01 5118"(130,2) 1/2'-13 530'(2.36) .730 (3.25) 890 (3.96) 990 (4.40) 1.140 (290.3) 41-8 8" 1200) 131/4" (336.51 55/8"(142.8) 55/8' 1142.91 1/2"-13 490 (2.18) 680 (3.02) 830 (3.69) 930 (4.13) 728 (330.2) FM Approved when used with 1", 11/4", 11/2"or 2"Sch.40 brace pipe. FM Approved design loads are based on ASD design method. Eaton's B-Line Business seismic bracing components are designed to be compatible only with other B-Line bracing components, resulting in a listed seismic bracing assembly. B-Line's warranty for seismic bracing components will be the warranty provided in B-Line's standard terms and conditions of sale made available by B-Line,except that, in addition to the other exclusions from B-Line's warranty, Eaton's B-line Business makes no warranty relating to B-Line's seismic bracing components that are combined with products not provided by Eaton's B-Line Business. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. .-- • Fire Protection Solutions Line 51 by aril/toll Seismic Bracing @Ta.c - Fig.4LA-In-Line Sway Brace Attachment Size Range: 1"(25mm)through 12"(300mm)IPS. Material: Steel Cf)co Function: For bracing pipe against sway and seismic disturbance. Approvals: For FM Approval information refer to page 53. : 1 r �� Installation Instructions: Fig.4LA can be used as the system attachment 1 , f ); �'` component of a longitudinal or lateral brace assembly. It is intended to be combined with the"bracing member"and TOLCO transitional attachment .. 0 A and structural attachment to form a complete bracing assembly. For fire sprinkler applications NFPA 13 guidelines should be followed. To Install: Place the Fig.4LA pipe clampcomponent over the pipe to be " , p �, �.__-----. braced and tighten down the break-off nuts until the hex head portion breaks off to verify correct installation torque. Next engage brace member(pipe or 4LA-1 thru 4LA-4 strut)with jaw component and tighten break-off head bolt until the hex head breaks off to verify correct installation torque. Pivot jaw for correct angle and attach to structure using TOLCO brand transitional attachment and structural attachment. Finish: Plain or Electro-Galvanized. Contact B-Line for *, �-yre alternative finishes and materials. f 'fr Order By: Figure number, pipe size and finish. ' Longitudinal Brace Lateral W = Z� , Brace z ( 4LA-5thru 4LA-12 © Pipe Max.Rec.Load Approx. Part Size A C D Bolt Size Longitudinal&Lateral Wt./100 No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg) 4LA-1 1" (25) 319/32" 191.2) . 15/16" (33.5) 15/14" (33.5) .,3/8"-16 1000 (4.45) r%: 119 (54.34 4LA-11/4 11/4" (32) 329/32" (99.3) 13/8" (35.3) 13/8" 135.3) 3/8"-16 1000 (4.45) 123 (55.8) 4LA-11/2 11/2" (40) 45/32" 1195.7) 11/2" (38.5) 1112" (38.5) 3/8"-16 1000 .1445) h.: ..1.2.7 (57.6) 4LA-2 2" (50) 511/32" (135.6) 21/32" (51.9) 21/16" (51.9) 3/8"-16 1000 (4.45) 142 (64.4) 4LA-21/2 21/2" (65) 522/32" (148.7) 2`5/16" (58:5); 25/:1x" (58.5) .:3/8"-16 1000 14.45) ' 173 (78.5) 4LA-3 3" (80) 61/2" (164.9) 25/8" (66.6) 25/8" 166.6) 3/8"-16 1000 (4.45) 187 (84.8) 4LA-31/2 ..';:31/2" (90) 7.407'.6 .° 881) 27/8" 173.11 27/8 (73.1) 3/8"-16 1000 14.45) .198 (89.8) 4LA-4 4" (100) 713/32" (190.8) 31/8" (79.5) 31/8" 179.5) 3/8"-16 1000 (4.45) 209 (94.8) 41-/1-5 5" (125) 83/4" 1222.3) 35/8" (92.1) 35/8° (32.1) 1/2"-13 1600"`;(7.12) 298 (135.2) 4LA-6 6" (150) 105/8" (269.9) 49/16"(115.9) 49/16" (115.9) 1/2"-13 1600 (7.12) 521 (236.3) 4LA-13 '8" 1200) 1213/16 1"325.5) :..59/18"(143.7) 521/32" (143.7} 1/2".13 2015 '(7.12) 629 (285.3) 4LA-10 10" (250) 161/2" (419.1) 71/4" (184.2) 71/4" (184.2) 1/2"-13 2765 (8.96) 1320 (598.7) 4LA-12 12" 1300) , 181/2" (469.9) 81/4" (2095) . 81/4" 1209.6) lit-13 -- -- 1496 1678.61 Eaton's B-Line Business seismic bracing components are designed to be compatible only with other B-Line bracing components, resulting in a listed seismic bracing assembly. B-Line's warranty for seismic bracing components will be the warranty provided in B-Line's standard terms and conditions of sale made available by B-Line,except that,in addition to the other exclusions from B-Line's warranty, Eaton's B-line Business makes no warranty relating to B-Line's seismic bracing components that are combined with products not provided by Eaton's B-Line Business. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line by Ec"t*N 52 Fire Protection Solutions Seismic Bracing LCO- Fig.4LA- In-Line Sway Brace Attachment �� Size Range: 1"(25mm)through 12"(300mm) IPS. Material: Steel , APPROVED Function: For bracing pipe against sway and seismic disturbance. �. Approvals: Approved by Factory Mutual Engineering(FM), 1"(25mm)through 7 12"(300mm)pipe. j ci Installation Instructions: Fig.4LA can be used as the system attachment m 40 component of a longitudinal or lateral brace assembly. It is intended to be U y combined with the"bracing member"and TOLCO transitional attachment A N and structural attachment to form a complete bracing assembly. For fire sprinkler applications NFPA 13 guidelines should be followed. f ,fit To Install: Place the Fig.4LA pipe clamp component over the pipe to be F' braced and tighten down the break-off nuts until the hex head portion 4LA-1 thru 4LA-4 breaks off to verify correct installation torque. Next engage brace member 0 (pipe or strut) with jaw component and tighten break-off head bolt until the hex head breaks off to verify correct installation torque. Pivot jaw 4 for correct angle and attach to structure using TOLCO brand transitional V ,���, attachment and structural attachment. " `* Finish: Plain or Electro Galvanized. Contact B-Line for alternative finishes and materials. o Order By: Figure number, pipe size and finish. 4,, n A ;..........I... :"*. .. ...r 1.'''•, Longitudinal Brace r .. �. l .%. L Lateral Y � s� �, Brace 4LA-5 thru 4LA-12 Pipe FM Max.Rec.Load Approx. Longitudinal&Lateral** Part Size A C D Bolt Size 300-44° 450-59° 600-74° 750-90° Wt./100 No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kg) 4LA--1 1" (25) 319/32" (91.2) 15/16" 133.5) 15/16" (33.5) 3/8'-i6 680 (3:02) 970 (4,31) ';1190 15.291 1320 (5.87) 119 (54.0) 4LA-11/4 11/4 (321 329/32' (99.3) 13/8" (35.3) 13/8" (35.3) ye-16 680 (3.02) 970 (4.311 1190 (5.29) 1320 (5.87) 123 (55.8) 4LA-11/2 11/2' (40) 45/32" (105.71 11/2" (38.5) 11/2" (38.5) 3/8"-16 680 (3.02) 970 (4.31). 1190 15.29) 1320 (5.87) 127 (57,6) 4LA-2 2' (501 511/32" (135.6) 21/32' (51.9) 21/16" (51.9) 3/8"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 142 (64.4) 4LA 21/2 21/2"(65) 527/32".(1483) 25/16" (58,5) 25/16" .(58.51 3/8'-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320'(5.87) . :173 (78.5) 4LA-3 3" (80) 61/2" (164.9) 25/8" (66.6) 25/8" (66.6) 3/8-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 187 (84.8) 4LA-31/2 31/2"(90) 7.407"_(188.1) 27/8" (73.1) 27/8" (73.1) 3/8"-16 680 (3.02) 970 (4.31) '1190 (5.29) 1320(5.87) 198 (89,8) 4LA-4 4" (100) 713/32" (190.8) 31/8" (79.5) 31/8" (79.5) 3/8"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 209 (94.8) 4LA-5 5" (125) :' 83/4" (222.3) .. 35/8 (92.1) 35/8 (92.1) ,_ ..1/2"-13 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87), 298 (135.2) 4LA-6 6" (150) 105/8' (269.9) 49/16' (115.9) 49/16" (115.9) 1/2"-13 1620 (7.20) Note 1 Note 3 Note 5 521 (236.31 4LA--8 8' (200) ' 1213/16"(325.5) 59/16" (143.7) 521/32"(143.7) 1/2-13 1620(7.20) Note 2 Note 4 Note 6 629 (285.3) 4LA-10 10" (2501 161/2" (419.1) 71/4" (184.2) 71/4" (184.2) 1/2"-13 1620 (7.20) Note 2 Note 4 Note 6 1320 (598.7) 4LA-12 12" (300) 181/2" (469.9) ..,81/4" 1209.6) 81/4 (209.61 1/2"-13 1620 (7.20) Note 2 Note 4 Note 6 1496 (678.6) ** Longitudinal and Lateral Loads are the same except where noted in chart. Note 1: Longitudinal Load 2260 lbs.(10.05kN) - Lateral Load 2300 lbs. (10.23kN) Note 2: Longitudinal Load 1660 lbs. (7.38kN) - Lateral Load 2300 lbs. (10.23kN) Note 3: Longitudinal Load 2010 lbs. (8.94kN) - Lateral Load 2820 lbs. (12.54kN) Note 4: Longitudinal Load 1570 lbs. (6.98kN) - Lateral Load 2820 lbs.(12.54kN) Note 5: Longitudinal Load 2220 lbs. (9.87kN) - Lateral Load 3140 lbs. (13.96kN) Note 6: Longitudinal Load 1740 lbs. (7.74kN) - Lateral Load 3140 lbs. (13.96kN) Eaton's B-Line Business seismic bracing components are designed to be compatible only with other B-Line bracing components, resulting in a listed seismic bracing assembly.B-Line's warranty for seismic bracing components will be the warranty provided in B-Line's standard terms and conditions of sale made available by B-Line,except that,in addition to the other exclusions from B-Line's warranty, Eaton's B-line Business makes no warranty relating to B-Line's seismic bracing components that are combined with products not provided by Eaton's B-Line Business. All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Fire Protection Solutions 53 B-Line by E:T*111 w Seismic Bracing Fig. 980- Universal Swivel Sway Brace Attachment-3/8"to 3/4" eT"OtCU' (1.7) Size Range: One size fits bracing pipe 1"(25mm)thru 2"(50mm), B-Line C US 12 gauge (2.6mm)channel, and all structural steel up to 1/4"(31.7mm)thick. ( 'ED to y Material: Steel F,• Function: Multi-functional attachment to structure or braced pipe fitting. ` d Features: This product's design incorporates a concentric attachment g• opening which is critical to the performance of structural seismic connections. NFPA 13 indicates clearly that fastener table load values are based only on ��� concentric loading. Mounts to any surface angle. Break off bolt head assureslo D verification of proper installation. k Installation: Fig.980 is the structural or transitional attachment component A of a longitudinal or lateral sway brace assembly. It is intended to be combined B with the"bracing pipe"and TOLCO"braced pipe"attachment, Fig. 1000, 1001, 2002, 4L, 4A or approved attachment to pipe to form a complete bracing Set Bolt assembly. NFPA 13 guidelines should be followed. Included ware To Install: Place the Fig. 980 onto the"bracingpipe".TightenMountings NtI chHaided the set bolt until Is Not Included the head breaks off.Attachment can pivot for adjustment to proper brace angle. Approvals:—Underwriters Laboratories Listed in the USA(UL)and Canada (cUL). For FM Approval information refer to page 67. ; Note: Fig. 980 Swivel Attachment and Fig. 1001, 1000, 2002, 4A or approved attachment to pipe that make up a sway brace system of UL Listed attachments and bracing materials which satisfies the requirements of Underwriters Laboratories and the National Fire Protection Association (NFPA) "§ Finish: Plain, Electro-Galvanized or Stainless Steel. Contact B-Line for alternative finishes. Order By: Figure number and finish. Pat.#6,273,372,Pat.#6,517,030,Pat.#6,953,174, Fig.980 Pat.#6,708,930,Pat.#7,191,987,Pat.#7,441,730, jI i Pat.#7,669,806 f� Fig.4L ���rrr���""" IV*r ., Lateral Brace Rill Longitudinal Brace Part Mtg.Hdw. Mounting Hole Max.Design Approx. Number Size A B D Load(cULus) Wt./100 in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) 980-3/8 3/8" (9.5) 51/4" (133.3) 17/8" (47.61 13/32"(10.31 2015 (8.96) 149 (67.6): 980-1/2* 1/2" (12.7) 51/4" (133.3) 17/8" (47.61 17/32" (13.5) 2015 (8.96) 148 (67.1) 980-5'/8.. 5/8" (15.91 51/4" 1133.3) 17/13"(47.6) 11/16"" (17.5) 2015 (8.96) 147 (66.7) 980-3/4 3/4" (19.0) 51/4" (133.31 17/8" (47.61 13/16" (20.5) 2015 (8.96) 146 (66.2) *Standard size. Eaton's B-Line Business seismic bracing components are designed to be compatible only with other B-Line bracing components, resulting in a listed seismic bracing assembly. B-Line's warranty for seismic bracing components will be the warranty provided in B-Line's standard terms and conditions of sale made available by B-Line,except that, in addition to the other exclusions from B-Line's warranty, Eaton's B-line Business makes no warranty relating to B-Line's seismic bracing components that are combined with products not provided by Eaton's B-Line Business. -. .� e by F� All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. 66 Fire Protection Solutions