July 8, 2014 1100 es$V$ ,r�, ,iti#
Fire Alarm Operational Matrix
General Overview
The fire alarm system will have battery back up to sustain it in the case of an AC power
failure. Alarm system will have dual phone lines, a primary and secondary, if the primary
fails the secondary will transmit signals to central station.All functions of the fire alarm
system are supervised, (AC power, low battery,phone line integrity, and all alarm
circuits. )Fire alarm troubles and alarms are both transmitted to the central station and
annunciated locally at the keypad and horn/strobes.
Specific Operation
• Troubles are annunciated at keypad in English text,at the same time they are
transmitted to the central station. Operator at central station will call a
predetermined response list to notify of trouble. Advanced Security& Fire will be
notified of system troubles at the same time.
• Alarms will be transmitted to the central station as well as annunciated locally.
Central station will notify fire dept. dispatch center of fire alarm, and then call
premises to try and verify alarm. Response list will be called to notify users of
alarm.
• Alarms can be silenced at the keypad by pressing fire silence button.
e • Fire system will be in trouble until fire alarm system is reset by pressing the fire
reset button.
• Common area smoke detectors, and sprinkler water flow switch monitor for fire
conditions and trigger a fire alarm.
• Upon trigger of fire alarm by any smoke detector, sprinkler water flow, or manual
fire pull station, alarm will be annunciated locally via horn/strobe devices,
central station will be signaled, HVAC units and fire smoke dampers will be shut
down by the fire alarm panel.
• Elevator will be recalled to the second floor-doors will open and functionality of
elevator will stop until fire system is reset. If new second floor fire protection
devices activate than elevator will be recalled to first floor, doors will open and
elevator will cease to function until fire alarm system is reset. Elevator.
Company Information
Advanced Security& Fire is located in Hillsboro, Oregon and is owned and operated by
David Moravik. I have been in the alarm industry since 1981 and licensed as a
journeyman low voltage electrician since 1984, (license# 611LEA). My state of Oregon
electrical license is (CLE-8 ). Advanced Security&Fire is registered with the state of
Oregon contractor's board(contractor's board# 166176). We are a member of the NFPA,
and the local fire and burglary alarm association.
Central Station Information
Advanced Security& Fire monitors its alarm systems through Central Station Monitoring
in Estacada, Oregon. They are certified to monitor all alarm system types. Phone#is
( 503-630-2896).