Specifications (19) -W vt3 . C S!7G SSW S4r r ri 'w � ( HYDRAULIC CALCULATIONS RECEIVED for Job Information OCT 2 8 2013 Project Name:Arlington Heights#56 CITY OF TIGARD Contract No.: City: Tigard, OR 97223 BUILDING DIVISION Project Location: 15176 SW Sumerview Dr Date: 10/28/2013 Contractor Information Name of Contractor: Wyatt Fire Protection Address: 9095 SW Burnham Dr City: Tigard, OR 97223 Phone Number: (503)684-2928 E-mail:a.payne@wyattfire.com Name of Designer: Ashley Payne Authority Having Jurisdiction: City of Portland Design Remote Area Name Master Bedroom Remote Area Location Occupancy Classification Residential_NewCommodityl Density(gpm/ft2) 0.04 Area of Application(ft2) 648 Coverage per Sprinkler(ft2) 324 Number of Calculated Sprinklers 2 In-Rack Demand(gpm) 0 Special Heads Hose Streams(gpm) 0 Total Water Required(incl. Hose Streams)(gpm) 26.7 Required Pressure at Source(psi) 62.2 Type of System Wet Volume-Entire System (gal) 2.9 gal Water Supply Information Date Location Source Notes File:C:\Users\Ashley\Documents\Projects\Arlington\56Wrlington 56 Calcs.tyc3 Date 10/28/2013 Copyright©2002-2012 Tyco Fire Protection Products Page 1 i z Job:Arlington Heights#56 Hydraulic Analysis for : Master Bedroom - Calculation Info Calculation Mode Demand Hydraulic Model Hazen-Williams Fluid Name Water @ 60F (15.6C) Fluid Weight, (Ib/ft3) N/A for Hazen-Williams calculation. Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation. Water Supply Parameters Supply 1 : srcl Flow(gpm) Pressure(psi) 0 118 1230 54 Hoses Inside Hose Flow/Standpipe Demand(gpm) Outside Hose Flow(gpm) Additional Outside Hose Flow(gpm) Other(custom defined) Hose Flow(gpm) Total Hose Flow(gpm) Sprinklers Ovehead Sprinkler Flow(gpm) 26.7 InRack Sprinkler Flow(gpm) 0 Other(custom defined)Sprinkler Flow(gpm) 0 Total Sprinkler Flow(gpm) 26.7 Other Required Margin of Safety(psi) 0 Base of Riser -Pressure(psi) 62.2 Base of Riser -Flow(gpm) 26.7 Demand w/o System Pump(s) N/A File:C:\Users\Ashley\Documents\Projects\Arlington\56\Arlington 56 Calcs.tyc3 Date 10/28/2013 Copyright©2002-2012 Tyco Fire Protection Products Page 2 Amoommie • Job:Arlington Heights#56 Hydraulic Analysis for : Master Bedroom f Supply f System Demand 150 140 --------- 13 S1 is 120 ---{-- 110 100 .12. 90 ---------- ice• ai 80 L \ D2 lan 60 ---------- \ S2 47.099 50 --_--------- 40 ------- 30 2 D1 ------ 10 r---- �— -- 0 0 400 500 600 700 800 900 1000 1100 1200 1300 Flow, gpm File:C:\Users\Ashley\Documents\Projects\Arlington\56\Arlington 56 Calcs.tyc3 Date 10/28/2013 Copyright©2002-2012 Tyco Fire Protection Products Page 3 i 4 Job:Arlington Heights#56 Hydraulic Analysis for : Master Bedroom Graph Labels • Label Description Values Flow (gpm) Pressure (psi) S1 Supply point#1 -Static 0 118 S2 Supply point#2-Residual 1230 54 D1 Elevation Pressure 0 8.2 D2 System Demand 26.7 62.2 Curve Intersections & Safety Margins Intersection Safety Margin Curve Name Pressure (psi) Flow m Pressure (gP ) (psi) @ Flow (gpm) Supply 117.9 39.1 55.8 26.7 Open Heads Required Calculated Head Ref. Head Type Coverage K-Factor Density Flow Pressure Density Flow Pressure (ft2) (gpm/psi1/2) (gpm/ft2) (gpm) (psi) (gpm/ft2) (gpm) (psi) h3 Overhead 324 4.9 0.04 13 7 0.042 13.7 7.8 Sprinkler h4 Overhead 324 4.9 0.04 13 7 0.04 13 7 Sprinkler File:C:\Users\Ashley\Documents\Projects\Arlington\56\Arlington 56 Calcs.tyc3 Date 10/28/2013 Copyright©2002-2012 Tyco Fire Protection Products Page 4 Job:Arlington Heights#56 Hydraulic Calculations/Fluid Delivery Time Analysis Node Data Node# Type K-Fact. Discharge Coverage Tot. Pres. Req. Pres. Elev Hgroup Open/Closed Overdischarge Density Elev. Pres. Req. Discharge • gP m 2 psi psi ft Spm/psi'h gpm gpm/ft2 psi gpm n2 Node 56.5 4 NODE -1.3 n32 Node 57.4 3 NODE -0.9 srcl Supply -26.7 62.2 1 SUPPLY 0 n33 Node 51.1 10 NODE -3.9 n34 Node 48.4 10 NODE -3.9 n36 Node 39.1 10 NODE -3.9 n37 Node 34.1 10 NODE -3.9 n38 Node 24.8 20 NODE _8.2 n40 Node 17 20 NODE -8.2 n41 Node 12.4 20 NODE -8.2 n42 Node 10.3 20 NODE -8.2 h3 Overhead Sprinkler 4.9 13.7 324 7.8 7 20 HEAD Open 0.7 0.042 -8.2 13 h4 Overhead Sprinkler 4.9 13 324 7 7 , 20 HEAD Open 0 0.04 -8.2 13 File:C:\Users\Ashley\Documents\Projects\Arlington\56\Arlington 56 Calcs.tyc3 Date 10/28/2013 Copyright©2002-2012 Tyco Fire Protection Products Page 5 Job name:Arlington Heights#56 Sheet number: PIPE INFORMATION Node 1 Elev 1 K-Factor 1 Flow added(q)* Nominal ID Fittings L C Factor total (Pt) Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES T frict (Pf) (ft) (gPm/PsiVZ) (gpm) (in) (ft) (ft) (psi) (psi) h4 20 4.9 13 .75 8 150 7 h3 20 4.9 13 0.874 0 0.0939 0 8 0.8 h3 20 4.9 13.7 .75 lx(BM.90)=4 3 150 7.8 n42 20 26.7 0.874 4 0.3557 0 7 2.5 n42 20 0 .75 lx(BM.90)=4 2 150 10.3 n41 20 26.7 0.874 4 0.3557 0 6 2.1 n41 20 0 .75 lx(BM.90)=4 9 150 12.4 n40 20 26.7 0.874 4 0.3557 0 13 4.6 n40 20 0 .75 lx(BM.Tee-Br)=3 18.75 150 17 n38 20 26.7 0.874 3 0.3557 0 21.75 7.7 n38 20 0 .75 lx(BM.90)=4 10 150 24.8 n37 10 26.7 0.874 4 0.3557 . 4.3 14 5 n37 10 0 .75 lx(BM.90)=4 10 150 34.1 n36 10 26.7 0.874 4 0.3557 0 14 5 n36 10 0 .75 lx(BM.90)=4 22.25 150 39.1 n34 10 26.7 0.874 4 0.3557 0 26.25 9.3 n34 10 0 .75 lx(BM.90)=4 3.5 150 48.4 n33 10 26.7 0.874 4 0.3557 0 7.5 2.7 • n33 10 0 .75 lx(coupling)=2.01 6 150 51.1 n2 4 26.7 0.874 2.01 0.3557 2.6 8.01 2.8 n2 4 0 1 lx(coupling)=1 1 120 56.5 n32 3 26.7 1.049 1 0.2211 0.4 2 0.4 n32 3 0 1 2 0 57.4 Ames 200B 1" srcl 1 26.7 0 0 1.9619 0.9 2 3.9 * Discharge shown for flowing nodes only ©2006 National Fire Protection Association Page 6 0 tco Fire Suppression Building Products rapid response® Technical Services 800-381-9312 l+1-401-781-8220 HOME FIRE SPRINKLER SYSTEM www.tyco-fire.com Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General The Series LFII Residential Flat-Plate Concealed Pendent Sprinkler has a 4.9 Description (60,5)K-factor that provides the required residential flow rates at reduced pres- The TYCO RAPID RESPONSE Series sures,enabling smaller pipe sizes and .� .r LFII Residential Flat-Plate Concealed water supply requirements. ,. � ,_. Pendent Sprinklers(TY2524)are decora- tive,fast response,fusible solder sprin- This sprinkler has been designed with e_ `. , heat sensitivity and water distribution klers designed for use in residential oc- characteristics proven to help in the con- ' cupancies such as homes, apartments, trot of residential fires and to improve ' 4,s dormitories, and hotels. the chance for occupants to escape or The Cover Plate/Retainer Assembly con- be evacuated ,y r �, + ` . ceals the sprinkler operating compo- = " � ' The Series LFII Residential Flat-Plate "° " lath "o-+ nents above the ceiling.The flat profile Concealed Pendent Sprinklers are of the Cover Plate provides the optimum shipped with a Disposable Protective aesthetically appealing sprinkler design. Cap.The Protective Cap protects the Additionally,the concealed design of the sprinkler during ceiling installation or _ _. _Series_LFIIResidential-Flat-Flate.C_o_n-__-__—finish:::After beiling mstallation-iscom _-- Technical pealed Pendent Sprinklers provides 1/2 plete, the Protective Cap is removed inch(12,8 mm)vertical adjustment.This and the Cover Plate/Retainer Assem- Data adjustment provides a measure of flex- bly is installed. Removing the Protec- ibility when cutting fixed pipe drops. tive Cap is required for proper sprinkler Approvals The Series LFII Residential Flat-Plate performance. UL and C-UL Listed Concealed Pendent Sprinklers are in- NSF-61 Certified tended for use in the following systems: NOTICE The Series LFII Residential Flat Plate • per NFPA 13D, wet pipe residential The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only sprinkler systems for one- and two- Concealed Pendent Sprinklers(TY2524) listed with the Series LFII Concealed family dwellings and mobile homes; described herein must be installed and Cover Plates having a factory-applied •per NFPA 13R, wet pipe residential maintained in compliance with this doc- finish. sprinkler systems for residential oc- ument and with the applicable standards cupancies up to and including four of the National Fire Protection Associa- Working Pressure stories in height;and tion,in addition to the standards of any 175 psi(12,1 bar) authorities having jurisdiction. Failure •per NFPA 13, wet pipe sprinkler sys- to do so may impair the performance Discharge Coefficient K=4.9 GPM/psi'" (70,6 LPM/bar1"2) tems for the residential portions of of these devices. any occupancy. Owners are responsible for maintaining Temperature Rating their fire protection system and devices Sprinkler: 160°F(71°C). in proper operating condition. The in Cover Plate: 139°F(59°C) IMPORTANT stalling contractor or sprinkler manu- facturer Vertical Adjustment Always refer to Technical Data Ser should be contacted with any questi1/2 inch (12,7 mm)Sheet TFP700 for the "INSTALLER , questions. WARNING" that provides cautions Finishes with respect to handling and instal- Model/Sprinkler Refer to the Ordering Procedure lation of sprinkler systems and com- �C section. ponents. Improper handling and in- Identification i cati on Ph • stallation can permanently damage ysical Characteristics a sprinkler system or its components • Cover Plate/Retainer Assembly: and cause the sprinkler to fail to Number (SIN) Cover Plate Copper operate in a fire situation or cause it TY2524 Ejection Spring . . . . Stainless Steel to operate prematurely. Retainer Brass i . • TFP443 Page 2 of 6 • • Horizontal Ceiling Sloped Ceiling Sloped Ceiling Minimum FlowNand Minimum FlowIbland Minimum Flow(b)and Residual Pressure Residual Pressure Residual Pressure Maximum Maximum (Maximum 2-inch rise (Greater than 2-inch rise (Greater than 4-inch rise Coverage Spacing for 12-inch run) upto maximum 4-inch up to maximum 8-inch Area i° se for 12-inch run) rise for 12-inch run) 160°F(71°C) 160°F(71°C) 160°F(71°C) Sprinkler Sprinkler Sprinkler 12'x 12' 12' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (3,7 m x 3,7 m) (3,7 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 14'x 14' 14' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,3 m x 4,3 m) (4,3 m) 7.0 psi(0,48 bar) 12.0 si(0,83 bar) 12.0 psi(0,83 bar) 16'x 16' 16' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM (4,9 m x 4,9 m) (4,9 m) 7.0 psi(0,48 bar) 12.0psi(0,83 • bar) 12.0 psi(0,83 bar) 18'x 18' 18' 17 GPM(64,3 LPM) 22 GPM(83,3 LPM) 22 GPM(83,3 LPM) (5,5 m x 5,5 m) (5,5 m) 12.0 psi(0,83 bar) 20.2 psi(1,39 bar) 20.2 psi(1,39 bar) 20'x20' 20' 20 GPM(75,7 LPM) 24 GPM(90,8 LPM) 24 GPM(90,8 LPM) (6,1 m x 6,1 m) (6,1 m) 16.7 psi(1,15 bar) 24.0si(1,65 bar) 24.0 psi(1,65 bar) (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b)The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures---.- --- are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. TABLE A SERIES LFII RESIDENT/AL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS •Bodynkler/Support Cup Assembly: Design For systems designed to NFPA 13,the Ca _-_- - - - Brass _ _ _number of deli n-s rinklers_is_to_be ._ Cap . . . .... . . . .. . . . Bronze== g P Saddle Brass 4i�,fer/c�` -the our most hydraulically demanding sprinklers.The minimum required dis- Sealing Assembly Beryllium • Nickel w/Teflon' The TYCO RAPID RESPONSE Series charge from each of the four sprinklers Soldered Link Halves Nickel LFII Residential Flat Plate Concealed is to be the greater of the following: • Lever Bronze Pendent Sprinklers (TY2524) are UL ••flow rates given in Table A for NFPA • Compression Screw Brnze and C-UL Listed for installation in ac- 13D and 13R as a function of tem- Deflector Bronze cordance with the following criteria. perature rating and the maximum al- Guide Pin Housing . Bronze lowable coverage area GuideinsBronze NOTICE • minimum discharge of 0.1 GPM/ Support Cup Steel When conditions exist that are outside sq. ft. over the "design area" com- the scope of the provided criteria, re- prised of the four most hydraulically fer to the Residential Sprinkler Design demanding sprinklers for actual coy- Operation Guide TFP49 I for the manufacturer's erage areas protected by the four recommendations that may be accept- sprinklers When exposed to heat from a fire,the able to the Authority Having Jurisdiction. Cover Plate,which is normally soldered Obstruction To Water Distribution to the Retainer at three points, falls away The Series LFII Residential Flat Plate Locate sprinklers in accordance with the to expose the Sprinkler/Support Cup As- Concealed Pendent Sprinklers must to .At this point,the Deflector,sup not be used in applications where the obstruction rules of NFPA for residential air pressure above the ceiling is greater ported by the Guide Pins, drops down sprinklers as well as obstruction criteria than that below. Down drafts through described within TYCO technical data to its operated position, sheet TFP490. the Support Cup can delay sprinkler op- The Solder Link Element of the Sprinkler/ eration in a fire situation. Support Cup Assembly is comprised of Operational Sensitivity two link halves that are soldered togeth- System Type Install sprinklers relative to the ceiling er with a thin layer of solder. When the Only wet pipe systems may be utilized. mounting surface as shown in Figure 3. rated temperature is reached, the sol- Sprinkler der melts and the two link halves sopa Hydraulic Design P Spacing rate, allowing the sprinkler to activate Table A provides the minimum required The minimum spacing between sprin klers is 8 feet(2,4 m). and flow water. sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R as a function The maximum spacing between sprin- of temperature rating and the maximum klers cannot exceed the length of the allowable coverage areas.The sprinkler coverage area(Table A)being hydrau- flow rate is the minimum required dis- lically calculated;for example, a maxi- charge from each of the total number of mum of 12 feet for a 12 ft.x 12 ft. cov- 1 Registered trademark of Dupont "design sprinklers"as specified in NFPA erage area or 20 feet for a 20 ft.x 20 ft. 13D or NFPA 13R. coverage area. , • TFP443 . Page 3 of 6 BODY imp: SEALING (1/2 NPT) ASSEMBLY ►/i CAP �,M - "1 ( 7�w //��.0.Y`t`.6— 1 SPRINKLER psi� ����'� , j WRENCHING SADDLE i ,= �`` :; 1 AREA ���� SUPPORT � , ,I� COMPRESSION CUP WITH 1 I SCREW ROLL FORMED ) , 4 i THREADS 41 i_ ..\ ( LEVER WRENCH lm ii��� ) RECESS GUIDE i PIN ■,�.��■— _MI,.. I rI �r? I I iI SOLDER LINK • I ELEMENT GUIDE PIN HOUSING I .--�- -' - --,i DEFLECTOR \/ DEFLECTOR (OPERATED PUSH WRENCH POSITION) IN TO ENSURE ENGAGEMENT I SPRINKLER/SUPPORT CUP ASSEMBLY WITH SPRINKLER i WRENCHING AREA • THREAD INTO � RETAINER SUPPORT CUP I WITH THREAD UNTIL MOUNTING ) I DIMPLES FIGURE2 SURFACE IS \ p I� W-TYPE 18 FLUSH WITH J EJECTION SPRINKLER WRENCH ------ ------ --- --CEILING__-----.----- ---- _---- - — — - —- -SPRING - . 3_1.11111.11111.11.11.1•111111.11•1111.1 hil -alldilmlb--- ----47" SOLDER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE • FIGURE 1 • . FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) ASSEMBLY 2-1/2"DIA. SPRINKLER- (63,5 mm) 1/2"(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING / OPERATED • ��t �� SPRINKLER t=t Mr 1 7/8"t1/8" COVERJ�PLATESmaI I 1/8"GAP f9,2 mm) RETAINER om (3,2 mm) f I COVER- SPRINKLER- 1 i 7/8" (22,2 mm) MOUNTING RETAINER SUPPORT CUP 3/16" SURFACE 1-1/8"(28,6 mm) ASSEMBLY ASSEMBLYmm) t '_���•' • 3-3/16" DIA. DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 PROTECTIVE CAP AND ACTIVATED DEFLECTOR • INSTALLATION DIMENSIONS ,, . TFP443 Page 4 of 6 Installation 6. Screw on the Cover Plate/Retainer Replace sprinklers that: Assembly until its flange contacts The TYCO RAPID RESPONSE Series the ceiling. • were damaged by dropping,striking, LFII Residential Flat-Plate Concealed Do not continue to screw on the trench twisting, wrench slippage, or h Pendent Sprinklers must be installed Cover Plate/Retainer Assembly such the like. in accordance with the following that it lifts a ceiling panel out of its • were modified or over-heated. instructions. normal position. • are leaking or exhibiting visible signs NOTICE If the Cover Plate/Retainer Assembly of corrosion. cannot be engaged with the Mounting Responsibility lies with owners for the Damage to the Solder Link Element dur- Cup or the Cover Plate/Retainer As- inspection,testing,and maintenance of ing installation can be avoided by han- sembly cannot be engaged sufficiently their fire protection system and devices dling the sprinkler by the Support Cup to contact the ceiling,the Sprinkler in compliance with this document, as only;that is, do not apply pressure to the Fitting must be repositioned. well as with the applicable standards of Solder Link Element(Figure 1). the National Fire Protection Association Obtain a leak-tight 1/2 inch NPT sprinkler Care and (for example, NFPA 25),in addition to joint by applying a minimum-to-maxi- the standards of any other authorities mum torque of 7 to.14 ft.-lbs.(9,5 to 19,0 Maintenance having jurisdiction.Contact the install- Nm). Higher levels of torque can distort ing contractor or sprinkler manufacturer the sprinkler inlet with consequent leak- The TYCO RAPID RESPONSE Series regarding any questions. age or impairment of the sprinkler. LFII Residential Flat-Plate Concealed Automatic sprinkler systems are rec- Pendent Sprinkler (TY2524) must be Do not attempt to compensate for in- maintained and serviced in accordance ied to be inspected, tested, sufficient adjustment in the Cover Plate/ andnd maintained by a qualified - Retainer Assembly by under-or over- with the following instructions. tion Service in accordance withth local tightening the sprinkler.Re-adjust the requirements and/or national codes. position of the sprinkler fitting to suit. NOTICE • 1. Install pendent sprinklers in the Before closing a fire protection system pendent position, with the centermain control valve for maintenance work line of the sprinkler perpendicular on the fire protection system that it Ion- to the mounting surface. trots,obtain permission to shut down the affected fire protection system from the 2. Remove the Protective Cap. proper authorities and notify all person- 3. With pipe-thread sealant applied ne/who may affected by this action. ,.. „td the pipe threads and,using the .. When_pro erly_installed_there is-a-nomi----- .--_ --'- . --- — WType 18 Wrench shown in Figure nal 1/8 inch (3,2 mm)air gap between – –" 2, install and tighten the Sprinkler/ the lip of the Cover Plate and the cell- - Support Cup Assembly into the fit- ing,as shown in Figure 3.This air gap ting. The W-Type 18 Wrench ac- is necessary for proper operation of the cepts a 1/2 inch ratchet drive. sprinkler by allowing heat flow from a 4. Replace the Protective Cap by fire to pass below and above the Cover pushing it upwards until it bottoms Plate to help assure appropriate release out against the Support Cup. The of the Cover Plate in a fire situation.If the Protective Cap helps prevent dam- ceiling needs repainting after sprinkler age to the Deflector and Guide installation,exercise care to ensure that Pins during ceiling installation and/ the new paint does NOT seal off any of or during application of the finish the air gap. Failure to do so may impair coating of the ceiling. sprinkler operation. Absence of a Cover Plate can delay the • NOTICE sprinkler operation in a fire situation. As long as the protective Cap re- Do not pull the Cover Plate relative to mains in place, the system is con- the Enclosure.Separation may result. sidered"Out Of Service': • Exercise care to avoid damage to sprin- 5. After the ceiling has been corn- kiers before, during,and after installa- pleted with the 2-1/2 inch (63 mm) tion.Never paint, plate, coat, or other- diameter clearance hole and in wise alter automatic sprinklers after they preparation for installing the Cover leave the factory. Plate/Retainer Assembly, remove Never repaint factory-painted Cover and discard the Protective Cap, Plates.When necessary,replace cover and verify that the Deflector moves plates with factory-painted units. Non- up and down freely. factory applied paint can adversely de- If the Sprinkler has been damaged lay or prevent sprinkler operation in the and the Deflector does not move up event of a fire. • and down freely, replace the entire Sprinkler assembly.Do not attempt to modify or repair a damaged sprinkler. TFP443 Page 5 of 6 Limited Ordering Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression & Building Products ability. When placing an order, indicate (TFSBP)are warranted solely to the orig- the full product description and Part inal Buyer for ten(10)years against de- Number(P/N). fects in material and workmanship when paid for and properly installed and main- Sprinkler/Support Cup Assembly Specify: Series LFII Residential Flat tained under normal use and service. This warranty will expire ten (10)years Plate Concealed Pendent Sprinkler from date of shipment by TFSBP. No (TY2524), K=4.9, without Cover Plate/ warranty is given for products or com Retainer Assembly, P/N 51-114-1-160. ponents manufactured by companies Cover Plate/Retainer Assembly not affiliated by ownership with TFSBP Specify: Cover Plate/Retainer Assem- or for products and components which bly with finish (below) for the Series have been subject to misuse, improper LFII Residential Flat-Plate Concealed installation,corrosion,or which have not Pendent Sprinkler(TY2524),K=4.9, P/N been installed, maintained, modified or (below): repaired in accordance with applicable Standards of the National Fire Protection Chrome P/N 56-201-9-135 Association,and/or the standards of any Custom P/N 56-201-X-135 other Authorities Having Jurisdiction, Off White Materials found by TFSBP to be defec- P/N 56-201-0-135 five shall be either repaired or replaced, Pure White' at TFSBP's sole option. TFSBP neither (RAL 9010) P/N 56-201-3-135 assumes, nor authorizes any person to Signal White' assume for it, any other obligation in (RAL 9003) P/N 56-201-4-135 connection with the sale of products or Standard White(Grey White) parts of products.TFSBP shall not be (RAL9002) P/N 56-201-5-135 responsible for sprinkler system design errors or inaccurate or incomplete in- ' Eastery Hemisphere ales only.White.. formation supplied by Buyer or Buyer's " Previously known as Bright representatives. Note: All Custom Cover Plates are painted=using Sherwin Williams Interior— In no event shall TFSBP be liable,in con- Latex Paint. Contact TYCO Customer tract,tort,strict liability or under any oth- Service with any questions related to er legal theory,for incidental, indirect, custom orders. • special or consequential damages,in- cluding but not limited to labor charg- Sprinkler Wrench es, regardless of whether TFSBP was Specify W-Type 18 Sprinkler Wrench, informed about the possibility of such P/N 56-000-1-265. damages,and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied,including warranties of mer- chantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on fail- ure of or defect in products, materials or components, whether the claim is made in contract,tort,strict liability or any oth- er legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. , . .. ttjccitqcol Flow Tyco /tire Control Products • BlazeMaster FIRE SPRINKLER PIPE & PITTINGS SUBMITTAL SHEET TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 www.tyco-fire.com TECHNICAL SERVICES TEL: (800) 381-9312 • FAX: (800) 791-5500 E-MAIL:techserv@tycofp.com F g7 rg n ,n-,F:'fig..„' µ t No. 19-1.5 TD915 r , le Introduction Tyco Fire Products (TFP) BlazeMaster°CPVC pipe and the same time, they provide superior heat resistance and fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping . automatic fire sprinkler systems. They are made from a materials used in the plumbing trade. Various adapters are specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability. the art additives. TFP BlazeMaster"CPVC products are Grooved adapters connect directly to grooved end valves easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings. Technical Data Sizes: 3/4"-3" Manufacture Source: U.S.A. Maximum Working Pressure: 175 psi Material: Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDR 13.5 MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and Note: See current TFP BlazeMaster Installation Instructions and ASTM F439 (Sch. 80) Technical Manual,for exact listing/approval information Color: Orange Pipe Nom.Pipe Size Avg. O.U.Inches Avg.I.Q. Inches Wt.Lbs./Ft. Wt.M21:1 filled Pipe Lbs./Ft. Ft. of Pipe per Lift Wt.per Lift Lbs. 3/4" 1.050 0.874 0.17 0.26 0.42 0.55 0.43 7875 1413 1" 1.315 1.101 0.67 5040 1320 11/4" 1.660 1.394 1.07 2835 1191 1'/2" 1.900 1.598 1.40 2.20 2205 1136 2" 2.375 2.003 0.86 1260 1063 1531 2 '/2" 2.875 2.423 1.26 3.22 1215 3" c 3.500 2.952 1.87 4.79 720 1344 - Fittings T/O TJO' 1111 T/O ..�.o mss : ° o T/O 45 Elbow . II. Reducing pt.,t 90° Elbow 90 Elbow ,}, _T/oz- - - - - - -- ----T/o --- „i i uu I ! e i 1 . Pe T/O Wt. Part No. Size Sch. T/O Wt. 80050artNo. 3/SizSch.4" 40 3/T/O" 0.08Wt.Ib. Part No. 80051 1" 40 Size Sch. 1 I 2 lb. 80025 3/," 40 9/,6" 0.09 lb. 3/6" 0.11 lb. 80032 1"x3/4" 40 "/,6" 13/,6 0.16 80026 1" 40 3/," 0.14 lb. 80052 11/4" 40 3/4" 0.20 lb. 80027 1'/a" 40 '/a" 0.21 lb. 80053 1'/2" 80 '/,s' 0.31 lb. 80028 1'/z" 80 1'/,s" 0.40 lb. 80054 2" 80 3/4" 0.56 lb. 80029 2" 80 I'/40 0.79 lb. 80055 2'/z" 80 3/4" 0.89 lb. 80030 2'/2" 80 1'/2" 1.14 lb. 80056 3" 80 1" 1.19 lb. 80031 3" 80 1 13/16" 1.82 lb. •, T/0' I T/O i , I llirTee _._._._._ ._.+._. _._._. _ Reducing : _ Cross _ ' Cross 11111....nrillIIIIIMOIllT/O' •lT/O I I T/O T/0 s T/O' MI T/O' T/O MN T/O Part No. Size Sch. T/O Wt. I Part T/O Wt. Part No. Size Sch. T/O Wt. 80000 3/," 40 5/6" 0.11 lb. No. Size Sch. 1 2 lb. 80009 3/," 40 9/ " 0.13 lb. 80001 1" 40 3/4" 0.19 lb. 80015 1"x 3/4" 40 11/,6" "/,6" 0.28 80010 1" 40 5/,6" 0.23 lb. 80002 1'/4" 40 '/6" 0.26 lb. 80003 17z" 80 1" 0.51 lb. 80004 2" 80 13/6" 0.90 lb. „ 15 80011 1 /, 40 /i6" 0.34 lb. 80012 1'/z" 80 1'/.6" 0.67 lb. ' 80013 2" 80 13/6" 1.00 lb. 80005 2'/2" 80 19/,6" 1.59 Ib. a nein OI/_" an 491." 4 0i 1k , . , • > YS O - ----I I----T/O TIO -1 no . Coupling _.Ef_. ._. Cap _ II i Reducer Bushing 1C Part No. Size Sch. 170 Wt. Part No. Size Sch. T/O Wt. Part No. Size Sch. T5//On Wt. 80200 1"x 3/4" 40 7/16" 0.04 lb. 80075 3/" 40 /6" 0.07 Ib. 80100 3/," 40 5/ " 0.04 Ib. 80201 1'/4"x3/4" 40 3/46" 0.11 lb. 80076 1" 40 1/e" 0.11 lb. 80101 1" 40 3/e" 0.06 lb. 80202 11/4"x 1" 40 5/,6" 0.12 lb. 80077 11/4" 40 3/16" 0.12 lb. 80102 11/4" 40 '/2" 0.10 lb. 80203 11/2"x'/4" 80 5/8" 0.16 lb. 80078 11/2" 80 3/16" 0.25 lb. 80103 11/2" 80 5/6" 0.20 lb. 80204 11/2"x 1" 80 '/2" 0.14 lb. 80079 2" 80 3/,6" 0.38 lb. 80104 2" 80 5/9" 0.31 lb. 80205 11/2"x 11/4" 80 3/8" 0.17 lb. 80080 21/2" 80 3/,6" 0.67 lb. 80105 21/2" 80 'A" 0.58 lb. 80206 2"x 3/4" 80 3/4" 0.27 lb. 80081 3" 80 3/16" 0.91 lb. 80106 3" 80 1" 0.88 lb. 80207 2"x 1" 80 71/16" 0.26 lb. 80208 2"x11/4" 80 9/16" 0.24 lb. I rio 80209 2"x 11/2" 80 7/16" 0.19 lb. Grooved 80215 21/2"x 1" 80 115/16" 0.42 lb. Coupling ___ P;P 0 80214 21/2"x 11/4" 80 13/," 0.45 lb. Adapter - -' ._I 80213 2'/2" " 5/a" p x 1'/2 80 1 0.46 lb. 80211 21/2"x 2" 80 19/,6" 0.29 lb. Part No. Size Sch. T/0 Wt. Pipe OD 80210 3"x 2" 80 2 3/16" 0.72 lb. 80160 11/4"x 1'/4" Grooved 40 2 5/16" 0.78 lb. 1'/4"(1.660") 80212 3"x 2'/2" 80 115/16" 0.47 lb. 80161 1'/2"x 1'/2' Grooved 80 2 5/16" 0.95 lb. 1'/2"(1.900") 80162 2"x 2" Grooved .80 2 5/16" 1.42 lb. 2"(2.375") 80163 2'/z"x 2'/2" Grooved 80 2 5/16" 2.28 lb. 23/2"(2.875") -Ail 80164 3"x 3" Grooved 80 21/4" 3.00 lb. 3"(3.500") Reducing 11110.21T/°' �' 80168 3"x 76.1mm Grooved 80 21/4" 2.72 lb. 76.1mm (3.000") Tee 0 T/0' II0 T/0` - -_---: _- =`Part` -- --- - - - - -T/O-- ----=Wt- • No. Size' Sch. 1 2 3 . lb. Female l tale _ 8032 3/4"X 3/46 x 1" 40 3I4" 3/4" 5/6" 0.14 Adapter irld 80133 1"x 3/4"x 3/440 1/2., 11 " 3 " /,s /4 0.14 80134 1"x 3/4"x 1" 40 5/E" 3/d' 3/," 0.17 Part No. Size Sch. T/0 Wt. 80260 1"x 1"x 3/4" 40 3h" 3/4" 16" 0.16 80142 3/4"x 3/4"NPT 40 5/a" 0.41 lb. 80135 1'14"x 1"x 3/," 40 '/16" 3/4"11:518// ,6" 0.21 80145 1"x 1" NPT 40 3/4" 0.63 lb. 80136 1'/,"x 1"x 1" 40 "/,a" 3/," 15/,6" 0.22 80.146 11/4"x 1'/+" NPT 40 '/6" 1.03 lb. 80137 11/4"x 1"x 11/4" 40 "/,6" 15/,6" 13/,6" 0.26 80147 11/2"x 11/2" NPT 80 1" 1.42 lb. 80261 1'/+"x 1'/4' x 3/4" 40 5/6". 5/6" '/6" 0.23 80148 2"x 2" NPT 80 13/6" 2.66 lb. 80262 11/4"x 1'/4"x 1" 40 3/4" 3/4" 7/8" 0.26 80138 174"X 11/4"X 11/2" 80 1" 1" 1" 0.43 noI. 80140 172"x 11/4"x 3/," 80 1/2" 5/6" 1" 0.36 80141 1'/z"X 1'/4"x 1" 80 '/2" 5/6" 1'/a" 0.38 Male _._ _ 80263 11/2"x 11/2"x 3/4" 80 9/,e' 91,6" 1" 0.36 Adapter 80264 11/2"x 11/2"x 1" 80 9/16" 9/16" 1" 0.38 80275 1'/2"x 11/2"x 1'/4" 80 '/a" '/8" 1" 0.45 I Part No. I Size Sch. T/0 ( Wt. 80265 2"x 2"x 3/4" 80 3/," 3/:" 13/e 0.61 80157 3/4" x 3/+" NPT 40 15/,6" 0.33 lb. 80266 2"x 2"x 1" 80 '/a" '/a" 13/a" 0.66 ' 80158 1"x 1" NPT 40 13/6" 0.56 lb. " 80274 2"x 2"x 11/4" 80 1" 1" 13/8" 0.74 80267 2"x 2"x 11/2" 80 1'/8" 11/8" 13/a" 0.78 - -{ Tio 80271 21/2"x 21/2"x 1" 80 1"/16" 1"/,6"" 19/,6" 1.43 1 80272 21/2"x 21/2" x 11/4" 80 111/18" 1" 19/16" 1.46 Reducing _ _._ •_ _ 80273 21/2" x 2'/z" x 1'/2" 80 1"/18" 1"/16" 19/,6" 1.48 Coupling 80276 21/2"x 2'/2"x 2" 80 113/48" 1"/18" 16/16" 1.50 80270 3"x 3"x 11/2" 80 13/4" 13/+" 113/16" 2.28 I D.-...4 Al I . I C;-. I I T,/l I I , l IPSO (-T/o rro Sprinkler Head Adapter _MaiSprinkler Head Adapter III with Brass Threaded Insert M _ with Brass Threaded Insert Part No. Size 1 Sch. TIO 1 Wt. 1 I Part No, i Size Sch. TIO 1 Wt. 80175E 3/4"x1/2" NPT 80 7A6" 0.20 lb. 80175W 3/4"x '/2" NPT 40 7/,6" 0.19 lb. 80176E 1"x 1/2" NPT 80 7/16" 0.22 lb. 80176W 1"x'/2" NPT 40 7/16" 0.18 lb. 80177WL 3/4"x1/2" NPT 40 9/,6" 0.16 lb. 80179 1 x 3/4" NPT 40 3/4" 0.43 Ib. i I/O' '''T';''e: .ttar Back-to-Back Cross -1111 ._ Sprinkler Head Adapter -.,-.,,Ti ,� CSN •+� with Brass Threaded Insert (Spigot) TIO' with Brass Threaded Insert lit ^ I/O' T/O' Part No. Size Sch.I T/0 I Wt. Part T/0 Wt. 80177L 3/4"x1/2" NPT 40 1/2" 0.16 Ib. No. Size Sch. 1 2 lb. 80178 1"x '/2"NPT 40 '/2" 0.20 lb. 80462 1"x 1"x'/2"NPT x'/2"NPT 40 5/e" 11/e" 0.46 80463 1"x 1"x 1/2"NPT x'/2"NPT 40 6/e" 15/16" 0.47 Sprinkler Head Adapterail T/°' 4 90° Elbow � ., no k. j , .. : with Brass Threaded Insert ' Back-to-Back Tee T'O_ �C� _,_ Q�� si INKwith Brass Threaded Insert Iwl. - i I/O' I/O' Part T/0 Wt. Part Size Sch. T/0 Wt. No. Size :.._ Sc .h1 2__ _Ibt _ _No. — — -- _-.. — 1 2 Ib: 80199 3/4"x '/2" NPT 40 5/8" 15/,6" 0.20 80459 1"x 1/2"NPT x1/2"NPT 40 11/,6" 15/,6" 0.48 80189 1"x 1/2' NPT 40 13/16" 13/16" 0.26 80460 1"x'/2° NPT x 1/20 NPT 40- 11/16" 1'/8" 0.46 Part Size Sch. T/0 Wt. No. 1 2 3 Ib, 80250 3/4"x 3/4"X 1/2"NPT 40 5/e" 5/6" 13" 0.22 i 80251 1"x 1"x'/2"NPT 40 11/58" 11/16" t3/1e" 0.29 80249 1"x 1"x 1"NPT 40 15/18" 15/18" 17/18" 0.73 } Sprinkler Head Adapter '"� T 11" , 1 /6 p p -� 80256 1 /4' x X /2„NPT 40 7/,e” 9/,6" ' " 0.30 Tee - 80252 11/4"x 11/4'x '/2"NPT 40 7/18" 7/18" 11/8" 0.31 with Brass Threaded Insert - ..-- - 80257 1'/2"x 11/4"x 1/2"NPT 80 9/l8' 5/9" 17/18" 0.43 T/o' 1 T/0' 80254 11/2" x 11/2"X '/2"NPT 80 9/18" 9/,6" 17/16" 0.46 80258 2"x 11/2"x 1/2"NPT 80 1/2" 5/5" 15/8" 0.56 80253 2" x 2"x 1/2"NPT 80 '/2" 1/2" 15/8" 0.62 Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in material and workmanship when paid for and•properly installed and maintained under normal use and service. This warranty will expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse,improper installation,corrosion,or which have not been installed,maintained,modified or repaired in accordance with applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced,at Tyco Fire Products sole option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it,any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. • IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE,IN CONTRACT,TORT,STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY,FOR INCIDENTAL,INDIRECT,SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LIMITED TO LABOR CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCT'S LIABILITY EXCh D AN AMOUNT EQUAL TO THE SALES PRICE. 11 THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED,INCLUDING ` WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DynaThread . Full Line Sch-40 Replacement Dyna-thread°offers the fife expectancy of Sch40 with superior hydraulics and greater value. Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry,It combines the safety and Iongevity of traditional Sch-40 pipe with quality and superior hydraulic advantages. Coi»pai ison to Scbleduft 40' `: Gainparisnnao L W T.`Pipes', ' Dyne-Thread's inside diameter is up • mat its increased strength and lighter • More wall thickness at the thread to 3.6%0 larger than Soh-40 giving it weight,Dyna-Thread reduces (CRR--1.00)gives D superior hydraulics.And,when used S'th T � in ation with Dyne-Flow pipe, ii teallation fatigue and is ideal for better Life expectancy than lightwall Yn P p , retro-fitapplications. threadablc pipe joints. down sizing often occurs, Corrosion Resistance Ratio(CRR)is a • Unlike lightwall threadable pipe, • Dyna-Thread is filly listed and tiL(Underwriters Laboratory)term for Dyna-Thread has no thread gauge approved by UL,ULC,and FM fir the estimated life expectancy of a pipe warning, fire sprinkler applications. joint This is based on the calculated •• The life expectancy of Dyna-Thread wall thickness at the base of the first Dyne-Thread is approved for and Sch-40 are equal bayed on the exposed thread„assumed to be the standard hanger spac as (15$ • calculated wall thicknesses per UL. weakest poi °f11113 pipe length.Dyna- 0.C.),can be used as earthquake Thread and Sch-40 have the same sway bracing, and is safe w use ag • The consistent quality of steel used to calculated wall thicknesses at this point APs' make Dyna-Thread t$ot7itates smooth and are both assigned the same CRR of • threading and lower maintenance I,00. Ryna-Thread is safer to Weld on, caste, • Dyna-Thread is more widely • The exterior of Dyna-Thread is 'The internal suri'aae of all black Allied accepted than lightwall threada151e protected by aprintcicr pipe clean,durable mill Tube&Conduit Fire S where Soh-40 is specified. coating for extended shelf life and products up to 4.5000"in diameter is easy paint application. coated with our new,Ant anterial ------._.._- - __ - _ - _ _Formula;"ASF":Inscientific laboratory- - test,ABS proved to have superior Specifications ifications & A resistance to microbial colonization of ! Np�ov:�ls,; (Di 4itio- 1110 pipe was,thereby delaying or possibly Supercun-ed e-Tread pipe is preventing the onset of manufactured to meet:ASTM A-135, Listed Approved Listed Microbiologioally Influenced corrosion Grade A and is in compliance with (MIC)when the First Sprinkler System NFPA•13.All sizes of Super 40/Dyna- (MX) is fust installed. Thread are rated at 300 psi working pressure.Super 40/Dyna-Thread is UL - . Specifications and ULC Listed for wet,dry deluge and NPS Hcmtna!I,O, Nit. Wt.(N20 Filled) PA/ WI)tlpt i` pre-action sprinlder systems and FM M;?S In;mm LbsAW�Kyltr Lbs12l KLitt Us;Kg ) Fitt(24') WI/Lllt(25' Approved for use in wet systems.Super bs'Kg Lbs;Kg 40/Dyna-Tread can be"hot-dip" 1° 1.060 1.330 1,75 73 1965 2234 2327 galvanized to meet FM requirement for 25 27.4 2.0 2.80 70 987 1013 105: dry systems, Super 40/Dyna-Thread is 1W 1,408 1,870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 358 2.8 3,78 51 908 1038 108 welded outlets and is suitable for all 1A' 1.639 2.290 3.22 44 2115 2418 251. roll-grooved,and plain-cad fittfu�. 40 41.6 3.4 4,79 44 959 7097 114 (See Hating infarMafion). 2" 2.104 3.050 4.57 30 1921 2195 2267 50 53.4 4.5 a80 30 871 995 103 tiler 1IRc".conuci P allied 16100 S. Lathrop•Harvey, IL 60428 Customer Service: [j 11350 Noreen Rd.•Philadelphia,PA 19154 (800)882'5543 ru9E a=Noun- 2525 N,27 th Ave.•Phoenix,AZ 65009 Fax 708-339-1608 83-3 Submittal Data Sheet Dyna-ThreadSump Here Full Line Sch-40 Replacement Dyna-Thread sprinkler pipe repreamis en cnginccrias advanocateat for the sprinkler pipe industry.It combines the safety and longevity of traditional Soh-40 pipe with quality and superior hydraulic edvanragcs. Comparison to Schedule 40 Dyna-Threads inside diameter is up to 3.6%larger than. Sch-40 giving it superior hydraulioa,Also,when used in combination with Dyna.Flow pipe, down siring°flea occurs.Dyna-Thread is fully listed and approved UL,ULC, - ,a-,.a-_ -_ and FM for fire sprinkler applications.The life expectancy of Dyna-Thread and Sch-40 •• - = : -` are equal based on the calculated wall thicknesses per UL.The consistent quality of : '� �- steel used to make Dyna-Thread facilitates smooth threading and lower maintenance costs.The exterior of Dyne-Thread is protected by a clean,durable mill coating for 'h..- extended shelf life end easy paint application.With its increased strength and lighter !"'S weight,Dyne-Thread reduces installation fatigue anti is ideal for retro-fit applications. Corrosion Resistance Ratio(CRR)is a UL(Underwriters laboratory)term far the '. eatimated life tecpeotano of a pipeof tu.This is based * -:s ... ; . ,i.:::: y j the calattIe�d wall thickness �:>� :- ,::�:::: at the brie of the first exposed thread,swanned to be the weakest point of the pipe ' length.Dyne-Thread and Soh-40 have the same calculated wall thickneseea at thin : point and are both assigned the same CRR of 1.00. _:k. .,r tea" t1 o'-'-i tt,,i I €r,:Y. - 5 PQM • Comparison to L.W.T.Pipe More wall thickness at the thread(CRR=1.00)gives " - Dyna.Thrcad better life expectancy than lightwa l threadeblc pipe joints.Unlace �` 'fir. t. 4 l !H 4 lighcwnll tbmadablc pipe Dyna-Thr=ad has no thread gauge warning.Dyna-Thread is - � ;L ,;w approved for standard d hangers (15 ft.Q.C. cm be used as earthquake awaypa.b•4-: t >,, P� ), qu ,�''�� *. - ... �'.}'• °• braoing,and is safe to use as drops.Dyna-Thread Is safer to weld on than many zinc- .,,a,7''.''`' . °a, „a.r ':;l Ili; ,1€;'` coated lighttval thrcadable pipe products.Dyna-Thread is more widely accepted than 'a Y:,as ` .s„ _ l'l.`,!:,,,,a'• lightwall threadabk where Soh-40 is specified, •Y' r.ta,4. . .°:Nati';;!: Specifications&Approvals Super 40/ Dyna-Thread pipe is manufactured to Specifications meet:ASTM A 135,Grade A and is in NP8 Ntmisal La. Wt. Wt.(H20 Filled). Per/ Wt4J1t(21') WVLiII(21') WI/L1111251 compliance with NFPA-13.All sizes of in:mm kr mm LhvFF Kahn LbsiFt Kgfn Luff Lbs.'Kg Lbs;Kg Lbs;Kg Super 40/Dyna-Thread are rated at 300 1' 1.080 1.330 1.75 70 1955 2234 2327 psi working pressure.Super 40/Dyne- 25 27.4 2.0 2.60 70 887 1013 1056 Thread is U _L and ULC listed for wet,. — -- We _:= 1.408= 1.870 264 51 2002 2288 2384 dry and pro-action sprinkler systems and32 8 48 578 51 taAB 1098 1081 FM Approved far use in wet systems. Super 40/Dyna-Thread can be"hot-dip" 11S' 1.639 2.290 3,22 44 2115 2418 2519 galvanized to meet FM requirement for 40 41.6 3.4 4.79 44 959 1097 1143 dry systems.Sopor 40/Dyna-Thread is 2' . 2,104 3.050 4,67 30 1921 2196 2287 approved far all threaded couplings and 60 53.4 45 6.80 30 871 995 1032 welded outlets and is suitable for all roll- grooved,and plain-end fittings.(Seo American Tube and Pipe was acquired by Allied Tube and Conduit on February 1, listing information). 1997.Tho engineered lightwall and tctaaderd wall family of produots although they Tho internal surface of all black Fite havedtffercrt names arc the same in all respects with regard to attength,weight, Sprinlder pipe up to 4.5000"in diameter bundle count,listings and approvals.For example, shall be coated with Allied Tube& Dyna-Flow and Super Flo arc the same product as 0 4010 41) Conduit Antibacterial Formula"ABF", tutee Thread and Super 40.XL is manufaotnred with Exterior galvanized coating.BLT is manafaatured with Black lacquer coating Listed Approved listed Project; Sprinkler contractor: Data: Eneinaor: Specification Reference: System Type: • Locations: Comments: S3-4 , 1 . FOR SMALL PIPE 'SR- 1 --. :: POTFER VANE TYPE WATERFL4«' The Symbol of Protection ALARM SWITCH WITH RETARD EL,ULC,CSFM Listed and NYMEA Accepted Service Pressure: Up to 300 PSI(20,7 BAR) Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)UL Maximum Surge: 18 FPS(5,5 m/s) Enclosure: Die-cast,red enamel finish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT(Form C) +. 10.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Resistive 10mAmps min.at 24 VDC Conduit Entrances:Two openings provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic,copper and schedule 40 iron pipe. Fits pipe sizes-1"(25mm), 1 1/4"(32mm),1 1/2"(38mm)and 2"(50mm) Stock No. 1144440 Note: 12 paddles are furnished with each unit,one for each pipe size of threaded and sweat TEE,one for 1"(25mm)CPVC, one for 1"(25mm)CPVC(Central),one for 1"threaded Nibco CPVC,and one for 1 1/2"(38mm)threaded(Japan). UUARNINiaG Environmental Specifications: • NEM A-4/1P54 Rated enclosure suitable for indoor or outdoor Installation must be perfomed by qualified personnel and in use with factory installed gasket and die-cast housing when used accordance with all national and local codes and ordinances. with appropriate conduit fitting. Shock hazard. Disconnect power source before servicing. • Temperature range:40°F to 120°F,(4,5°C to 49°C)UL Serious injury or death could result. Service Use: Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler NEPA-13 injury or death could result. One or two family dwelling NEPA-13D Residential occupancy up to four stories NEPA-13R National Fire Alarm Code NFPA-72 Optional:Cover Tamper Switch Kit,Stock No.0090148 (See Fig.7 for terminations) Replaceable Components:Retard/Switch Assembly,stock no. 1029030 The Model VSR-S is a vane type waterflow switch for use on wet Installation sprinkler systems that use 1"(25mm),P.4"(32mm).1'/"(38mm)or 2" These devices may be mounted in horizontal or vertical pipe. On (50nun)pipe size.The unit may also be used as a sectional waterfiow horizontal pipe they should he installed on the top side of the pipe where detector on large systems. they will be accessible.The units should not be installed within 6"(15em) The unit contains two single pole double throw snap action switches and of a valve,drain or fitting which changes the direction of the waterfiow. an adjustable, instantly recycling pneumatic retard.The switches are Select the proper paddle for the pipe size and type of TEE used see Fig. actuated when a flow of 10 gallons per minute(38 LPM)or more occurs 1 for instructions on changing paddle.The runt has a 1"NPT bushing downstream of the device.The flow condition must exist for a period of for threading into anon-cor non-corrosive TEE.See Fig.2 for proper TEE size, time necessary to overcome the selected retard period. type and installation.Use no more than three wraps of teflon tape. Enclosure Screw the device into the TEE fitting as shown in Fig.2.Care must be The VSR S switches and retard device are enclosed in a general purpose. taken to properly orient the device for the direction of wateriow. die-cast housing.The cover is held in place with two tamper resistant The vane Hurst not rub the inside of the TEE or bind in any way.The screws which require a special key for removal.A field installable cover stem should move freely when operated by hand. tamper switch is available as an option which may be used to indicate The device can also be used in copper or plastic pipe installations with unauthorized removal of the cover. See bulletin number 5401103 for the proper adapters so that the specified TEE fitting may be installed installation instructions of this switch. on the pipe run. .'Note:Do not leave cover off for an extended period of time. Potter Electric Signal Company.LLC•2081 Craig Road.St.Louis,MO,6314o-4161•Phone:800-325-3936'Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.45401206-REV G PAGE 1 OF 3 12,05 1 A . p FOR SMALL PIPE V S —S VANE TYPE WTERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Fig.1 Fig.2 1 Retard Adjustment 130NOT kn r,0\LR Off FOR EA TENDED P133001 III 11 FAW The time delay is factory set at 30 i 10 seconds. 0 v LR TAMPER Sv.TTCF] �d The d el ay can be adjusted by rotating the retard 1 ---1-- adjustment adjustment knob from 0 to the max setting(60- 1 90 seconds).The time delay should be set at the �� minimum required to prevent false alarms. .I I•\ i firs„ I ��•����_1�� Screw the device into the tee fitting as shown. �� ,V 'Z' a t%10141�� Care must be taken to properly orient the %Ala.no OF 1,IOUNT;6 ��I����0' fSATLRPIUK .i . device for the direction of avaterflow.On sweat .RPOR0\ INDRE POWT h - tees,no threaded bushings inserts,or adapters Nr"� ?re w � � are permitted,unless they comply with the dimensions listed in the chart below. me 1 1 :NPT THREADED HFITTINGECN Important-The depth to the inside bottom of TI9G ON the tee should have the following dimensions: " 1NARNI d tm - - 9 RUN OF men" �� -1Dpz'oxiutate Depth Requirement 111ti BE <......,..,,,,, 101) There are 12 paddles furnished with each unit TORE SDED(>x Ter Size Treaded S„rst CPVC 'FEAT PIPE One for each size of threaded,sweat or plastic 1 s 1" I 21/1C 134" 27 16•. nVi\TE EL or ((�11,, TCE as described in Fig.2.These paddles have 1Y,(ERiN OF \\\\ 1 1' 1 I a :1 27/16" x a raised lettering that shows the pipe size and type I„ ,�,,,, � 1 1 2"�.1 L_'>_]' _Ilan" '_1/1 N A of TEE that they are to be used with.The proper r' 331C 234" N A packllemust.beused.Thepaddlemustbeproperly Shown with optional Cofer Tamper Switch Kir. attached(see(hawing)and the screw that holds ` AWARNING n'- i the paddle must be securely Lightened. Do not use more than three wraps of teflon tape. Fig.3 Switch Terminal Connections Clamping Plate Terminal Fig.7 Cover Tamper Switch Wiring ` o (Shown with cover in place) =� '„ , , ,.WARNING v " GrAc-1 An uninsulated section of a single conductor should not be looped o, around the terminal and serve as two separate connections.The wire must be severed,thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. C N.o. N.C. Failure to sever the wire may render the device inoperable risking (\a11T) (RED) (BLL ) severe property damage and loss of life. u1.,c=rs,am3 Fig.4 Typical Electrical Connections Fig.5 Fig.6 ,� To remove knockouts: Break out thin section ofcoverwhernjitiing M-G97 7J 1X OR •Q• �-�,� EELL HCI,rIc,,L,.c Place screwdriver at edge-of both switches from one conduit entrance. _ °I _ _=� Liockouts,not in the center. ' t'+� t(,C1TI1'F DC Ox ..=- v :u �1 a 'raC h4. j , SII r; ' �, 171 ,slit!! _,A11. 1 nu V hrLISLOtI Z(�NF l\ (•:,..1.--, eIV) ��� 'J l� '7 s ? `\I% 1. The Model SR S has two switches.one can be used to operate a 4i ' central station.proprietary or remote signaling unit while the other is used to operate a local audible ora isual annunciator. 2. For supers ised circuits see"Switch Terminal Connections”drawing and caution note(Fig.3). PRINTTD IN USA MEG..;'5401200-REV G PAGE 2 OF 3 12'08 A FOR• SIALLPIPE - I P0TFER \ANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD Testing Removal The frequency of inspection and testing for the Model VSR-S and its • To prevent accidental water damage,all control valves should associated protective monitoring system should be in accordance with be shut tight and the system completely drained before waterflow applicable NFPA Codes and Standards and/or the authority having detectors are removed or replaced. jurisdiction(manufacturer recommends quarterly or more frequently.) • Turn off electrical power to the detector,then disconnect wiring. An inspector's test valve(usuallylocated at the end ofthe most remote branch • Use a wrench on the flats of the bushing.Turn the switch line)should always be used for test purposes.If there are no provisions for counterclockwise to disengage the pipe threads. testing the operation of the flow detection device on the system.application • Gently lift with your fingers,roll the vane so it will fit through the of the VSR-S is not recommended or advisable. hole while continuing to lift the waterfow detector. A minimum flow of 10 gpm(38 Lpm)is required to activate this device. • Lift detector clear of pipe. NOTICE Please advise the person responsible for testing of the A CAUTION fire protection system that this system must he tested in accordance with the testing instructions. Waterflow switches that are moni toring wet pipe sprinkler systems Maintenance shall not be used as the sole initiating device to discharge AFFF. Inspect detectors monthly for leaks. If leaks are found, replace the deluge,orchemical suppression systems.Waterfl ow switches used detector.The VSR-S aterfiow switch should provide years of trouble- for this application may result in unintended discharges caused 1, free service.The retard and switch assembly are easily field replaceable. by surges,trapped air,or short retard times. in the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock#1029030.There is no maintenance required,only periodic testing and inspection. Mounting Dimensions 3.50" - 5.56" A GROUND SCREWS (89.0 mm) (141.2 mm) A O 2.00" ,41��p .4 _ (50.8 mm) II"I"I-1UI"I"I=1I 111111 2.34"(59.4 mm) I III 1 II IRI 1 111111714.89" _ (52.3 mm) 1E1 O 1"-11 1/2 NPT tll II DWG#1206-5 PRINTED tIN USA MEG.'=5401200-REV G RAGE 3 OF 3 12'08 A • TESTANDRAI p�}�t n,L 4; Y- (t 'iM.t S 4 ; r r ''�P �t S. ex t`'1 i�'�"'�'"� f -c"'y'tny la r Fr 4p,*, 9l[v'!��' r m"'c„ 4 •fT IfF�4P+ NFl S 1 ✓^ f ,-..h` y�a, 12jgg P N�j•') r rw'fc"t sµ¢ cam` 7aJ?it+f�trt(h w k 49i4^`4 rrry td rr�, t „' ,pl. T)R �� t�,±sia�'7 •r'� _! IgG' 1�t Y,7 i'^„s+,r�;,� t9rnz l��+J E_ r,r,t1 ,� trtM 11 4 ,4"��{2� p MV+ ' !� yi N r t (f.4 f'. 'Ari ri '2 G`.�7; �. r fA" !f""�" � 4 4 f L t�&�!FJ�C i t�ti.;' P �s 1 . a t � F �i� � � t 3 _ trf 7� J ��t� g CA,Lt�;tw0 5vo,Fl+iTtr f 9. � �x f Iz yf P � r at � �Vt �� t va pd t,� t; P1 r!dla 4.7;as pros1`e:P to ri or.9 , r 41 i ter� T � S,'.a y�CS sfi ttt dv1 154 C i i VCF,j`'Pii1° S� It avrr;;-,1 ril Fit t7 Is xxA{ 11�Fsfn..t{n'r 1a +i n,7 '55T .a a.yr lin_ . ■ The AGF Manufacturing Co., Inc. Model 1000 has been designed to provide both the Test Function and the Express Drain Function in a multi story installation. • Complies with all requirements of NFPA-13, and NFPA-13R • Complies with all requirements of NFPA-13D (HOUSING) • Positive Shut Off • Single Locking Handle • Tapped '/z" for Pressure Gauge • Tamper Resistant Orifice permanently installed • Available with all required Orifices • Orifice size noted on Indicator Plate • Lightweight and compact (11/4" weighs 5 lbs.) • 300 PSI Ratina 1 • 9 ' MODEL 1000 300 PSI 3, „ =4s , II • 7 1/4 „ • 1 1/2 „ • 2 *'/,"NOT FM APPRO\ PLAN VIEW FRONT VIEW I O FROM BRANCH GAUGE OUTLET e �� PROVIDED 41 /111 Wil < TO DRmi AIN ° 1E11 1 =��I�iillill .■, OFF C alo (..Th ‘..1.._-il la IihIr�O� i .,.... ■ '- STREET EL I, I jRAIN .I is.' FRONT VIEW/HORIZONTAL INSTALLATION. SOREPIPEL�a i TO DRAIN E *I 1 1 'II—V -a T IMO F TO DRAIN Miklint4 FOR RIGHT HAND/STRAIGHT INSTALLATION illi .. - TO DRAIN - - . il ` , ® _..._____:.. _.._ __ __ ._._ _ _. ..___ __..._.. < 1 dC, ► I iil PIR 4110111111 APPROVALS ■0 1UL and ULC Listed ■ FM Approved except 3/4" ■ NYC BD. of 5&A CAL. NO. 720-87-SM ■ CA. State Fire Marshall ORIFICE SIZE PROVIDED-3/8-7/16-1/2-'7/32''$/8*eke'3/4** DIMENSIONS—INCHES MATERIAL LIST SIZE A B C D E F G H PART MATERIAL 3/4 5'/Ib 13/4 23/8 4'/e 33/8 13/4 49116 65/16 HANDLE STEEL STEM BALL BODY ROD BRASS C.P. BRONZE BRONZE 1 5'/16 13/4 23/8 4'A 33/8 13/4 49/16 65/i6 1 '/4 57/16 13/4 2'/R 45/e 35/16 115/16 5'/2 7'/16 VALVE SEAT GLASS 11/2 67/16 13/4 3"/16 57/16 31/2 23/8 8'/16 107/16 INDICATOR PLATE STEEL INPREGNATED TEFLON 2 6'/16 i 3f4 3"/.b 57/16 3'/z 23/a 8'/�6 10'/16 HANDLE L OCK SPRING STEEL SIGHT GLASS (2) FUSED TEMPERED GLASS . ** Available on 11/4"to 2"size units only. AGF MFG. CO. JOB NAME: ( Box 4437, 150 Mt. Bethel Rd. Warren, N.J. 07059-0437 ARCHITECT: MADE IN U.S.A. Telephone (908) 604-6471 ENGINEER: Fax (908) 604-6501 rnnrrnarrnn• S S . 0 Toy co INCORPORATED CORONA,CA (909)737-5599 0 C 0 Fig, 27 & 27A "Stand-Off" Hanger/Restrainer for CPVC Plastic Pipe Size Range—3/4" & 1" CPVC Plastic Pipe*. Material— Carbon Steel, Pre-Galvanized. Function—Designed to be used as a hanger/restrainer**for CPVC piping where the "stand-off' design will ease installation by eliminating the need for '- •� ` wood blocking. Features: i �\\ i • Flared edge design protects CPVC from any rough or abrasive surfaces. • Snap-in retainers hold pipe firmly in place during installation. • The "Stand-Off'design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting Fig. 27 surface orientation. • Attaches easily to wood structure with 2 hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16"sockets, eliminating impact tool damage to pipe ° Approvals- Underwriters Laboratories Listed in the U.S. (UL) and Canada fO .(cUL) to support automatic fire sprinkler systems. Meets and exceeds the (,.Tkrrrequirements of NFPA 13, 13R, and 13D. Fig. 27A ``=" **Important Note—When installed in slot opening • -- -_._. on Fig_27, Fig 27A °c:: _ _ provides additional stability and satisfies the UL vertical restraint requirement where needed. o Order By—Fig. 27: By figure number and CPVC pipe size. \I '--/— Fig. 27A: By figure number and CPVC pipe size. I - U.S. and International Patent application in process. *for other sizes consult factory. t \ Fig. 27 and Fig. 27/27A have also been tested by U.L. mounted on 3/8" ' composite wood web material (such as TJI Series/Trus Joist MacMillan) Fig. 27/Fig. 27A without the use of back up wood blocking. When using Fig.27 & 27A in Combination combination on 3/8"web to satisfy the UL requirement for vertical restraint, install 2 reinforcing speed nuts (Fig. 27B). Fig. 27B is UL Listed only when WG.27 W/FIG.27A used with Tolco products. ■_■', FIG.27B w P FIG.27 i W/FIG.27A MO ir ak 61 —' i LS! 11.11.1111 I I FIG.27 FIG.27 FIG.27 FIG.27 W/FIG.27A FIG.27 I_Ho L=fi � ik.iifi Typical Applications to ES-A-2000B Series 2000B - . - ... -::-. . .:. --. ... . . . . . . A 1 Check j..-_7 1 AMES Double Check Valve Assemblies FIRE&WATERWORKS"' Sizes: t/2"—2" (15 —60mm) t :154.----7÷7.-7...--- -----.77" -�. • fi ' ,—. l_s .-- {{-. ��,c Features • Ease of maintenance with only one cover ::. 2"20 . .. DOB HC • Top entry (50mm) • Replaceable seats and seat discs . .. - • ; .--.- '.-: ,.:'. •:--. • • ..- -.=!,,, ..i • Modular construction1 •: Compact design • 7/z 2"..(15 50mm)Cast bronze �� ,y body construction._ ffi S,. f M"2000/3 .:-.!.::Trop mounted ball valve test cocks (20mm) A. Low pressure drop . • No special tools required Series 2000B Double Check Valve Assemblies shall be installed at referenced cross-con- • '/z' 1" (15—25 mm)have nections to prevent the backflow of polluted water into the potable water supply.Only tee handles those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation,frequency of Available Models testing or other installation requirements. t'` Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are ' __ _ .B- Quarterturn.ball_valves__ _ a pproved_bythe_F_oundation_for Cross_Connection_Contcol_and_Nydraulie Research at the LBV- less ball valves University of Southern California. LH- locking handle ball valves(open position) Specmcations SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly HC- 2'/z"inlet/outlet fire hydrant fitting s and rubber seat springs shall consist of two positive seating check modules with captured s (2' valve) p p' g discs.The check module seats and seat discs shall be replaceable.Service of all internal Prefix: components shall be through a single access cover secured with stainless steel bolts.The U- union connections assembly shall also include two resilient seated isolation valves and four top mounted, re- silient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Assembly shall be an Ames Pressure — Temperature Temperature Range:33°F—140°F Company Series 2000B (5°C—60°C) Approvals Maximum Working Pressure: 175psi t ASSE,IAPMO,CSA,UPC (12 bars) A Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Standards • Model LBV is not listed. ASSE Std. 1015,AWWA Std. C510 u UL Classified(LBV models only)3/4"—2"(19—50mm) IAPMO PS31, CSA B64.5 ° Horizontal and vertical'flow up" PP approval on all sizes. Q t--i. &o413 w_ *,uti Job Name Contractor � w Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.corn 4 4 4 Dimensions - Weights 1-4 A T* -.,,,,s.71..11••• CS 111P-4 i..... �.ut- ` 11.1r'--m.'. 1' ` -.�••=�t�- 1�1-��•IN H -► 4- (F - G Suffix HC-Fire Hydrant Fittings dimension"A"=231/2"(594mm) Size(DN) A B F Dimensions Model in. mm in. mm in. mm in. mm in. 6 H mm in. mm in. mI m in. mm lbs.Weighktgs. 2000B 1/2 15 10 254 4% 117 2'/6 62 5 127 33/6 85 25A6 59 21/6 52 4.5 2 2000B M3 3/ 20 111/ 282 4 102 31/6 79 63A6 157 31/26 87 21/6 54 15/16 33 5 2.3 20008 1 25 131/% 337 5'/e 130 4 102 71/2 191 33/6 85 111/6 43 111A6 43 12 5.4 20006 1% 32 16% 416 5 127 35/6 84 91/2 241 5 127 3 76 2 50 15 6.8 20006 11/2 40 16% 425 4% 124 31% 89 9% 248 513/6 148 3% 79 211/6 68 15.86 7.2 2000B 2 50 1912 495 61/a 159 4 102 13% 340 6% 156 3'/16 87 217/6 68 25.75 11.7 Strainer sold separately Capacities bars psi 11/4"(32mm) As compiled from documented Foundation for Cross-Connection Control 1 14 * _ and Hydraulic Research at the University of Southern California lab tests. m .8 12 o `Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) ..J •7 10 .5 8 bars psi %"(15mm) * .4 6 U3 .8 12 y .3 4 O .7 10 a .1 2 �� ' .4 6 0 0 y 4 4 Ai, 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm o MIMI .1 2 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm ; a p p _ ---- __ 7.5__.10-- ° --15 fps a 15.5-23. 3.0 4.6 - mps , • 0 2 4 6 8 10 12 gpm Flow Rate AP 0 7.6 15.2 22.8 30.4 38 45.6 Ipm 5 7.5 10 fps bars psi 11&'(40mm) * 1.5 2.3 3.0 mPs % .8 12 bars psi 3/4"(20mm) Flow Rate o 7 10 o 1.5 22 * m .5 8 tn -1• 1.2' 18 y .4 6 .96 14 m .3 4 �� y .69 10 a .1 2 a .41 6 APO 10 20 30 40 50 60 70 BO 90 100 110 120 gpm .14 2 /P. 's' 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm - 5 7.5 10 15 fps 4P 0 5 10 15 20 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps O 10 38 57 76 95 114 133 152 171 190 Ipm Flow Rate 7.5 15 2.3 4.6 mps bars psi 2"(50mm) Flow Rate rn .8 12 bars psi 1" ) 0rn 25mm * 7 10 N1.1 16 o .8 12 J .58 -J .7 10 6 4 6 -._..rte C .5 8 W .3 4 tn .4 6 1 2 .3 4 a 0 0 o- .1 2 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 Ipm 0 5 10 15 20 25 30 35 40 45 50 55 60 upm AP 0 19 38 57 76 95 114 133 152 171 190 209 228 1pm 52.3 1.5 2.3 3.. 15 fps 5 7.5 10 15 fps 0 4.6 mps Flow Rate 1.5 2.3 3.010 4.6 mps • Flow Rate IMPORTANT:Inquire with governing authorities for local installation requirements. A M E S 1S09001 T FIRE&WATERWORICI" A Division of Watts Industries www.amesfirewater.com CERTIFIED _^ 875 National Drive • Suite #107 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 ES-A-2000B 0313 ©Ames Co.2003 Printed in U.S.A.