Report (11) p
10 BUP2005-00289 10775 SW CANTERBURY LN
11 BUP2005-00291 10769 SW CANTERBURY LN
12 BUP2005-00292 10765 SW CANTERBURY LN /,,----
16 BUP2005-00293 10739 SW CANTERBURY LN
17 BUP2005-00295 10731 SW CANTERBURY LN //id�anl��h�� s�
18 BUP2005-00301 10783 SW CANTERBURY LN _III,iV�V'i��f�(
January 20, 2006 19 BUP2005-00299 10715 SW CANTERBURY LN
26 BUP2005-00284 10797 SW CANTERBURY LN CITY OF TIGARD
IND Fire Sprinkler INC 27 : ::
10793 SW CANTERBURY LN OREGON
10789 SW CANTERBURY LN
12155 SW Grant Ave. Suite D
Tigard,OR 97223 \\ .........____
RE: FIRE SPRINKLER SYSTEM-NFPA 13R SYSTEM REVIEW
Project Information
Building Permit: Varies Buildings: 10-12,16-19,26-28
Occupancy Type: Rl Area: 2 Story 7,748 Sq Ft
Address: Varies Construction Type: VN- Sprinklered
Tenant Name: Canterbury Crest Hazard: Ordinary Group I
The plan review was performed under the State of Oregon Structural Specialty Code(OSSC)
2004 edition, Oregon Fire Code 2004 edition;and NFPA 13. The following information is
required in order to complete the review.
1. Documents for deferred submittal items shall be submitted to the registered design
professional in responsible charge who shall review them and forward them to the building
official with a notation indicating that the deferred submittal documents have been reviewed
and been found to be in general conformance to the design of the building. The deferred
submittal items shall not be installed until the design and submittal documents have been
approved by the building official. OSSC 106.3.4.2
2. The submitted plans are incomplete,the following list indicates what is required on plans,the
** indicates what is not shown on the plans: NFPA 13 R 6.1
6.1.7 Sprinkler plans shall indicate the following:
(1)The name of owner and occupant
(2)The location, including street address
(3)The point of compass
(4)The ceiling construction**
(5)The full height cross section
(6)The location of fire walls**
(7)The location of partitions
(8)The occupancy of each area or room
(9)The location and size of concealed spaces, attics, closets, and bathrooms
(10)Any small enclosures in which no sprinklers are to be installed
(11)The size of the city main in the street,pressure,whether dead-end or circulating and,
if dead-end, the direction and distance to the nearest circulating main, and the city
13125 SW Hall Blvd., Tigard, OR 97223 (503)639-4171 TDD(503)684-2772
main •test results including elevation of the test hydrant**
(12)The make, manufacturer,type, heat-response element,temperature rating, and
nominal orifice size of the sprinkler
(13)The temperature rating and location of high-temperature sprinklers
(14)The number of sprinklers on each riser, per floor**
(15)The kind and location of alarm bells
(16)The type of pipe and fittings
(17)The type of protection for nonmetallic pipe**
(18)*The nominal pipe size with lengths shown to scale
(19)The location and size of riser nipples
(20)The types of fittings and joints and the locations of all welds and bends
(21)The types and locations of hangers, sleeves, and braces,and methods of securing
sprinklers,where applicable**
(22)All control valves, check valves, drain pipes, and test connections
(23)The underground pipe size, length, location, weight,material,and point of
connection to the city main; type of valves, meters, and valve pits; and depth at
which the top of the pipe is laid below grade**
(24)In the case of hydraulically designed systems,the material to be included on the
hydraulic data nameplate
(25)The name and address of the contractor
Please provide an item by item response.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard,Letter of Transmittal.The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectful
go/41l' x c›,?--g/t)
Val Hemel,
Senior Plans Examiner
I10 BUP2005-00289 10775 SW CANTERBURY LN
11 BUP2005-00291 10769 SW CANTERBURY LN
Fire Marshal's 12 BUP2005-00292 10765 SW CANTERBURY LN
$ / North Division-14480 SW Jenkins Rd.,Beaverton,OR 97016 BUP2005-00293 10739 SW CANTERBURY LN
Tualatin Valley South Division-7401 SW Washo Ct.,Ste. 101,Tualatin,Of 17 BUP2005-00295 10731 SW CANTERBURY LN
Fire & Rescue 18 BUP2005-00301 10783 SW CANTERBURY LN
19 BUP2005-00299 10715 SW CANTERBURY LN
26 BUP2005-00284 10797 SW CANTERBURY LN
Building Survey Repol27 BUP2005-00286 10793 SW CANTERBURY LN
28 BUP2005-00287 10789 SW CANTERBURY LN
FMZ : (to be filled out by TVF&R) Code Edition: 98OSSC
Name of Facility: Canterbury Woods
Name of Building: 2 story Townhome Buildings 10-12, 1 6-19, 26-28
Address: SA
Owner: Polygon Northwest Telephone No. (360) 695-7700
Architect: Leonard J. Milbrandt Telephone No. (425) 454-7130
Architect Address:
r ITEM COMM DECR14PTION
1. Occupancy Type R1 Use 4 unit condo Capacity None
2. Construction Type V—N Year Built
3. Area(Sq.Ft.) Total 6878 Largest Floor 2 Basement None
4. Stories No 2 Height 26'-10" High Rise ❑Y ®N
5 a. Exterior Wall Construction WF-Non-rated
b. Opening Protection None
6. Interior Wall Construction GB on WF/GB on WT
7. Floor Construction Carpet-Ply-WGL-GB
8. Roof Construction Class "C" RS-Roof Felt-Ply-WT @ 24" o.c.
9. Attic Draft Stops No. Yes-3
10a. Occ.Sep. Wall Construction No. Yes-3 GB-WF-Insulation-Airspace-WF-GB
b. Opening Protection None
11a. Fire Wall Construction No. None
b. Opening Protection None
12a. Smoke Barrier Wall Construction No. None
b. Opening Protection None
13a. Corridor Wall Construction None
b. Opening Protection None
14a. Corridor Ceiling Construction None .
b. Opening Protection None
15a. Shafts No. None Type
b. Opening Protection None
Building Survey Report
FMZ : (to be filled out by TVF&R)
Name of Facility: Canterbury Woods
3Tm,: COMM DES .tIFI IO NI.
16a. Stair Enclosure No. None I Open stairway/None
b. Opening Protection None
17. Stairs No. 4
18. Ramps No. None
19. Interior Finish Class Room None Exit Enclosure Corridor
20. Exits No. 4 Total WidthNone
per 98OSSC
21. Exit Hardware Type Knob
22a. Exit Signs/Illumination None
b. Emergency Lighting None
23. Auto Sprinkler Coverage Yes-P
24. Standpipe Class/Locations None
25. Fire Alarm Type/Coverage Yes-
26. Heating,Ventilation&Air Conditioning Type Unit Heat I Fuel Electric
27. Electrical Installation Romex-Circuit breaker
28. Stage/Platform None
29. Hazardous Area None
30. Other
Comments:
Alternate Materials&Methods
TVF&R Use Only
Inspected By: Date
No.Attachments
Reviewed By: Date
Updated