RE: FIRE SPRINKLER SYSTEM-NFPA 13R SYSTEM REVIEW
Project Information
Building Permit: Varies Buildings: 1,2, 3, 5, 6,& 7
Occupancy Type: R1 Area: 2 Story, 7,748 Sq Ft
Address: 10791 Canterbury Lane Construction Type: V-lhr-Sprinidered
Tenant Name: Canterbury Crest
Hazard: Ordinary Group I
The plan review was performed under the State of Oregon Structural Specialty Code(OSSC)
2004 edition, Oregon Fire Code 2004 edition; and NFPA 13. The following information is
required in order to complete the review.
1. Documents for deferred submittal items shall be submitted to the registered design
professional in responsible charge who shall review them and forward them to the building
official with a notation indicating that the deferred submittal documents have been reviewed
and been found to be in general conformance to the design of the building.The deferred
submittal items shall not be installed until the design and submittal documents have been
approved by the building official. OSSC 106.3.4.2
2. The submitted plans are incomplete,the following list indicates what is required on plans,the
** indicates what is not shown on the plans: NFPA 13 R 6.1
6.1.7 Sprinkler plans shall indicate the following:
(1)The name of owner and occupant
(2)The location, including street address
(3)The point of compass
(4)The ceiling construction**
(5)The full height cross section
(6)The location of fire walls**
(7)The location of partitions
(8)The occupancy of each area or room
(9)The location and size of concealed spaces, attics, closets, and bathrooms
(10)Any small enclosures in which no sprinklers are to be installed
(11)The size of the city main in the street,pressure, whether dead-end or circulating and,
if dead-end, the direction and distance to the nearest circulating main, and the city
13125 SW Hall Blvd., Tigard, OR 97223(503)639-4171 TDD(503)684-2772
main test results including elevation of the test hydrant**
(12)The make, manufacturer,type,heat-response element,temperature rating, and
nominal orifice size of the sprinkler
(13)The temperature rating and location of high-temperature sprinklers
(14)The number of sprinklers on each riser, per floor**
(15)The kind and location of alarm bells
(16)The type of pipe and fittings
(17)The type of protection for nonmetallic pipe*
(18)* The nominal pipe size with lengths shown to scale
(19)The location and size of riser nipples
(20)The types of fittings and joints and the locations of all welds and bends
(21)The types and locations of hangers, sleeves, and braces, and methods of securing
sprinklers,where applicable**
(22)All control valves,check valves, drain pipes, and test connections
(23)The underground pipe size, length, location,weight,material, and point of
connection to the city main;type of valves, meters,and valve pits;and depth at
which the top of the pipe is laid below grade**
(24)In the case of hydraulically designed systems,the material to be included on the
hydraulic data nameplate
(25)The name and address of the contractor
3. The approved plans show Buildings 1,2,3,5,6,&7 are type V-lhour 2 story buildings. Your
submitted plans and sprinkler calculations do not match the approved set of plans.
Please provide an item by item response.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard,Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and processing the documents.
Respectful)
70'". ,„.......
Val Henzel,
Senior Plans Examiner