Report (72) cc e c Oo)S? lz3�3 6ifeet l c p in MEMORANDUM T I GARD TO: Brian Blalock, Interim Building Official FROM: Val Henzel, Plans Examiner RE: Grant Street Elite Care DA l'E: August 23, 2006 Application received January 18, 2006 Project Information Building Permit: BUP2006-00053 Construction Type: V-A Sprinklers Tenant Name: Grant Street Elite Care Occupancy Type: SR-2 Address: 12353 SW Grant St. Occupant Load: unk Area: 31,279 sq ft Stories: 3 The building as submitted on January 18, 2006 did not meet code as submitted per SR101.3.1 and Table 503, there for could not be built as submitted. History The Plans were submitted as SR-2, 5A construction,the code requires SR-2 be built per I-2 requirements and SR appendix (SR101.2.1 (2)),Table 503 requires I-2 construction of a 3 story building to be Type I construction.After a quick review of building submittal the building did not meet code,therefore this building could not be reviewed as submitted and without the documentation from the State classifying the building as a different classification as required per SR101.3 we have to classify and review this building under a Group SR-2 per SR101.3.1. Requested information from Elite Care LLC,Bill Reed to submit documentation from the state classifying the building as SR-1 for review under I-lcatagory as they are requesting. Received letter dated March 9, 2006,with City of Tigard received stamp of March 13, 2006 from the State of Oregon classifying the building use as SR-1 under Section requirements SR101.3. GENERAL BUILDING HEIGHTS AND AREAS TABLE 503 ALLOWABLE HEIGH • .D BUILDING AREAS Height limitations shown :: stories :nd feet above grade plane. Area limitations as determined by t •e inition of"Area,building,"per floor. TYPE OF CONSTRUCTION TYPE I TYPE II TYPE III TYPE IV TYPE V A B A B A B HT A B • Hgt(feep GROUP Hgt(S)NC My!moi / UL 160 65 55 65 55 ' 65 50 40 A-1 (S UL 5 3 2 3 2 3 2 1 UL UL 15,500 8,500 14,000 8,500 15,000 11,500 5,500 A-2 S UL Il 3 2 3 2 3 2 1 A UL UL 15,500 9,500 14,000 9,500 15,000 I1,500 6,000 A-3 S UL II 3 2 3 2 3 2 I A UL UL 15,500 9,500 14,000 9,500 r 15,000 11,500 6,000 A-4 S UL II 3 2 3 2 3 2 1 A UL UL 15,500 9,500 14,000 9,500 15,000 11,500 0,000 A-5 S UL UL UL UL UL UL UL UL UL A UL UL UL UL UL UL UL UL UL , B S UL 11 5 4 5 4 5 3 2 ' A UL UL 37,500 23,000 28,500 19,000 36,000 18,000 9,000 E S UL 5 3 2 3 2 3 I 1 A UL UL 26,500 14,500 23,500 14,500 25,500 18,500 9,500 S UL II 4 2 3 2 F-1 4 2 1 A UL UL 25,000 15,500 19000 12,000 33,500 14,000 8,500 S UL 11 5 3 F-2 4 3 5 3 2 A UL UL 37,500 23,000 28,500 18,000 50,500 21,000 13,000 H-1 S 1 I I I I I I I NP A 21,000 16,500 11,000 7,000 9,500 7,000 10,500 7,500 NP H-2 S UL 3 2 I 2 1 2 1 1 A 21,000 16,500 11,000 7,000 9,500 7,000 10,500 7,500 3,000 S UL 6 4 2 4 2 4 2 1 H-3 A UL 60,000 26,500 14,000 17,500 13,000 25,500 10,000 5,000 H-4S UL 7 5 3 5 3 5 3 2 A UL UL 37,500 17,500 28,500 17,500 36,000 18,000 6,500 H-5 S 3 3 3 3 3 3 3 3 2 A UL UL 37,500 23,000 28,500 19,000 36,000 18,000 9,000 SQ 1_I S UL 9 4 3 4 3 4 3) - 2 I` A UL 55,000 19,000 10,000 16,500 10,000 18,000 10,500 4,500 S UL 4 2 • l I NP 1 NP SR 2 1-2 A UL UL l 15,000 11,000 12,000 NP 12,000 NP 1-3 S UL 4 2 I 2 1 2 2 I A UL UL 15,000 10,000 10,500 7,500 12,000 7,500 5,000 1-4 S UL 5 3 2 3 2 3 I 1 A UL 60,500 26,500 13,000 23,500 13,000 25,500 18,500 9,000 M S UL I1 4 4 4 4 4 3 1 A UL UL 21,500 12,500 18,500 12,500 20,500 14,000 9,000 R-I S UL II 4 4 4 4 4 3 2 A UL UL 24,000 16,000 24,000 16,000 20,500 12,000 7,000 R-2a S UL II 4 4 4 4 4 3 2 A UL UL 24,000 16,000 24,000 16,000 20,500 12,000 7,000 R-38 S UL II 4 4 4 4 4 3 3 A UL UL UL UL UL UL UL UL UL R-4S UL lI 4 4 4 4 4 3 2 A UL UL 24,000 16,000 24,000 16,000 20,500 12,000 7,000 S-I S UL II 4 3 3 3 4 3 1 A UL 48,000 26,000 17,500 26,000 17,500 25,500 14,000 9,000 S-2b c S UL I I 5 4 4 4 5 4 2 A UL 79,000 39,000 26,000 39,000 26,000 38,500 21,000 13,500 ticS UL 5 4 2 3 2 4 2 1 A UL 35,500 19,000 8,500 14,000 8,500 18,000 9,000 5,500 For SI: 1 foot=304.8 mm, I square foot=0.0929 m2. UL=Unlimited,NP=Not permitted. a. As applicable in Section 101.2. Ib. For open parking structures,see Section 406.3. c. For private garages,see Section 406.1. 74 2003 INTERNATIONAL BUILDING CODE® Page 1 of 1 Val Henzel -RE: Structural Response for the Tigard Grant street Elite Care From: "scott" <palmhill2@mindspring.com> To: "'Val Henzel " <Val@tigard-or.gov>, "'Brian Blalock' <brianb@tigard-or.gov> Date: 8/9/2006 3:32 PM Subject: RE: Structural Response for the Tigard Grant street Elite Care CC: <CPMARCH@aol.com>, "Scott Churchill" <palmhill2@mindspring.com> Thank you for your direction. We will proceed with that understanding. Original Message From: Val Henzel [mailto:Val@tigard-or.gov] Sent: Wednesday, August 09, 2006 2:41 PM To: palmhill2@mindspring.com; Brian Blalock Cc: CPMARCH@aol.com Subject: RE: Structural Response for the Tigard Grant street Elite Care Please route 2 copies of the response comments and calculations to this office so we can rout 1 copy to Miller Consulting and have 1 copy for our office. Thank you in advance for your assistance in this. Val Henzel Senior Plans Examiner 13125 SW Hall Blvd. Tigard, OR 97223 (503) 718-2436 val(aDti and-orgov file://C:\Documents and Settings\val.000\Local Settings\Temp\GW}00001.HTM 8/10/2006 Page 1 of 2 Val Henzel - RE: Exit Corridor Width on ground floor for Grant Street Elite Care From: Val Henzel To: Blalock, Brian; scott 144%Date: 8/9/2006 7:52 AM OD � Subject: RE: Exit Corridor Width on ground floor for Grant Street Elite Care ,, r\, CC: Churchill', 'Scott; CPMARCH@aol.com J �' 0.4 SR108.2 would require the 72" if serving residential sleeping areas with an occupant load'ovet t rased on the plan showing direct exits from first floor residential rooms the corridor would not be servingri 3 from this floor and therefore could remain 36"based on chapter 10 section 1005 and 1016.2 ex(2). Val Henzel Senior Plans Examiner 13125 SW Hall Blvd. Tigard, OR 97223 (503)718-2436 val(a)tigard.or.gov >>> "scott"<palmhill2@mindspring.com>08/09 1:05 AM >>> Val, As a separate issue in our counter meeting today of 8/8/06 you are in agreement With our exit corridor width of 36" on the ground floor(rather than 72"wide)with the understanding And commitment by Ownership that the ground floor units are for staff and employees only And that all Assisted Care Residents will reside on the upper two floors. Per our discussion,you will confirm this with a reply to my email. Regards, Scott Original Message From: scott[mailto:palmhill2@mindspring.com] Sent: Wednesday,August 09, 2006 12:55 AM To: val@tigard-or.gov; brianb@tigard-or.gov Cc: CPMARCH@aol.com; Scott Churchill Subject: RE: Occupancy load calculations for Grant Street Elite Care Val, Per our counter meeting today 8/8/06 you are in agreement with our calculations For Occupancy Loads to the building. (see attached file) Per our discussion,you will confirm this with a reply to my email. Regards, Scott Churchill file://C:\Documents and Settings\va1.000\Local Settings\Temp\GW}00001.HTM 8/9/2006 CR-3 Permit Center-Grant Street Elite Care Facility- Craig Page 1 From: Val Henzel To: -Building OTC; CR- 3 Permit Center; Val Henzel Date: Wed, Mar 1, 2006 Time: 10:30 AM- 11:30 AM Subject: Grant Street Elite Care Facility-Craig Place: CR-3 Permit Center Page 2 of 2 From: scott[mailto:palmhill2@mindspring.com] Sent: Wednesday, August 09, 2006 12:55 AM To: val@tigard-or.gov; brianb@tigard-or.gov Cc: CPMARCH@aol.com; Scott Churchill Subject: RE: Occupancy load calculations for Grant Street Elite Care Val, Per our counter meeting today 8/8/06 you are in agreement with our calculations For Occupancy Loads to the building. (see attached file) Per our discussion,you will confirm this with a reply to my email. Regards, Scott Churchill Original Message 9 9 From: scott[mailto:palmhill2@mindspring.com] Sent: Monday,July 31, 2006 7:02 PM To: val@tigard-or.gov; brianb@tigard-or.gov Cc: CPMARCH@aol.com; Scott Churchill Subject: Occupancy load calculations for Grant Street Elite Care Val, Our project ownership would like to know if you have approved the detailed occupancy calculation response which was submitted earlier at the counter. (see attached.) This is for the Grant Street Elite Care Project for Bill Reed. This submission was to address the two major items # 16& 18 which you felt needed immediate attention before proceeding. This is per your and my meeting in your conference room on July 18. Please let us know via email if you have accepted this detailed confirmation of our occupancy on this project. Regards, Scott Churchill file://C:\Documents and Settings\val.000\Local Settings\Temp\GW)00002.HTM 8/10/2006 Page 1 of 2 Val Henze! -RE: Exit Corridor Width on ground floor for Grant Street EliteCare From: "scott" <palmhill2@mindspring.com> To: "'Val Henzel"' <Val@tigard-or.gov>, "'Brian Blalock" <brianb@tigard-or.gov> Date: 8/9/2006 12:36 PM Subject: RE: Exit Corridor Width on ground floor for Grant Street EliteCare CC: <CPMARCH@aol.com>, <monroestreetassociates@earthlink.net> Thank you for your approval Val.....we can now proceed with the final outstanding items on our list. Regards, Scott Churchill Original Message From: Val Henzel [mailto:Val@tigard-or.gov] Sent: Wednesday, August 09, 2006 7:52 AM To: palmhill2@mindspring.com; Brian Blalock Cc: CPMARCH@aol.com; monroestreetassociates@earthlink.net Subject: RE: Exit Corridor Width on ground floor for Grant Street EliteCare SR108.2 would require the 72" if serving residential sleeping areas with an occupant load over 10. Based on the plan showing direct exits from first floor residential rooms the corridor would not be serving over 10 from this floor and therefore could remain 36"based on chapter 10 section 1005 and 1016.2 ex (2). Val Henzel Senior Plans Examiner 13125 SW Hall Blvd. Tigard, OR 97223 (503)718-2436 val@tigard.or.gov >>> "scott"<palmhill2@mindspring.com>08/09 1:05 AM >>> Val, As a separate issue in our counter meeting today of 8/8/06 you are in agreement With our exit corridor width of 36" on the ground floor(rather than 72"wide)with the understanding And commitment by Ownership that the ground floor units are for staff and employees only And that all Assisted Care Residents will reside on the upper two floors. Per our discussion,you will confirm this with a reply to my email. Regards, Scott Original Message 9 9 file://C:\.Documents and Settings\val.000\Local Settings\Temp\GW}00002.HTM 8/10/2006