Plans (8) 2014 - 00105 GENERAL NOTES 1. DO NOT SCALE DRAWINGS. FIELD VERIFY RECEIVED DIMENSIONS PRIOR TO FABRICATION AND MAR 06 2014 HVAC LEGEND ABBREVIATIONS - EQUIPMENT SCHEDULE INSTALLATION OF COMPONENTS. 2. DRAWINGS ARE DIAGRAMMATIC ONLY. ACTUAL CITY OFTIGARD ® MARK MFG MODEL TONNAGE HEATING COOLING EER SUPPLY ESP OSA MCA/ MOTOR VOLTAGE OPR WT NOTES SIZE AND LOCATION OF EQUIPMENT, DUCT WORK PLANNING/ENGINEERING ZO CONTROLLED AND PIPING MAY VARY DUE TO MANUFACTURER OR NECK SIZE - SUPPLY AIR R CAPACITY CAPACITY (SEER) CFM CFM MOCP HP /PHASE (LB) THROW PATTERN .� AFF ABOVE FINISHED FLOOR MBTU MBTU MIN FIELD CONDITIONS. COORDINATE INSTALLATION OF xx- AHU AIR HANDLING UNIT MECHANICAL SYSTEMS WITH OTHER TRADES TO RETURN AIR ROOM THERMOSTAT OR SENSOR RTU-1 CARRIER 48HCFD14A2A5 12.5 195 150 14 5000 1 15 61/70 2.82 230/3 1725 2, 3, 4, 6, 7, 8 PROVIDE ADEQUATE CLEARANCE AND ACCESSIBILITY TSE OUTSIDE AIR BTU BRITISH THERMAL UNITS AS REQUIRED BY MANUFACTURERS. EQUIPMENT . RTU-2 CARRIER 48HCFD14A2A5 12.5 195 150 14 5000 1 15 61/70 2.82 230/3 1725 2, 3, 4, 6, 7, 8 CFM NUMBER CFH CUBIC FEET PER HOUR RTU-3 CARRIER 48HCFD14A2A5 12.5 195 150 14 5000 1 15 61 70 2.82 230 3 1725 2, 3, 4, 6, 7, 8 3. INSTALLATION SHALL COMPLY WITH THE TERMINAL CFM CUBIC FEET PER MINUTE AN REGULATIONS. EXHAUST AIR COND CONDENSER RTU-4 CARRIER 48HCEA05A2A5 4 93 50 15.6 1600 1 15 26/30 1 230/3 709 2, 3, 6, 8 GOVERNING CODES D EQUIPMENT SYMBOL CU CONDENSING UNIT RTU-5 CARRIER 48HCFD14A2A5 12.5 195 150 14 5000 1 15 61/70 2.82 230/3 1725 2 3 4 6 7 8 4. CONCEAL ALL DUCTWORK INSIDE WALLS AND/OR CONSTRUCTION STANDARDS DN DOWRTU-6 CARRIER 48HCFD14A2A5 12.5 195 150 14 5000 1 15 61 70 2.82 230/3 1725 2, 3, 4, 6, 7, 8 ABOVE CEILINGS, UNO. E S IN G RTU-7 CARRIER 48HCEA05A2A5 4 93 50 15.6 1600 1 15 26/30 1 230/3 709 2, 3, 6, 8 RECTANGULAR DUCT: 32x20=32"Wx20"H EF EXHAUST FAN RTU-8 CARRIER 48HCFD14A2A5 12.5 195 150 14 5000 1 15 61/70 2.82 230/3 1725 2, 3, 4, 6, 7, 8 5. ALL SHARP RADIUS (R<1.5) ELBOWS SHALL BE RECTANGULAR FURNISHED WITH TURNING VANES.' ROUND DUCT: 200=20"ROUND OFFSET LESS FC FAN COIL UNIT RTU-9 CARRIER 48HCED09A3A5 8.5 148 105 12 4000 1 1 15 49/60 3 208/3 1 104 2, 3, 4, 6, 8 THAN 15' FD FIRE DAMPER NOTES 1) FACTORY CURB 4) AIR SMOKE DETECTOR 7) 2-SPEED MOTOR 6: DUCTWORK SHALL BE FABRICATED AND SUPPLY AIR FLOW FPM FEET PER MINUTE DIRECTION RECTANGULAR FPS FEET PER SECOND 2) FACTORY ISOLATION CURB 5) BAROMETRIC RELIEF 8) HONEYWELL VISION PRO 8000 INSTALLED PER SMACNA STANDARDS. SUPPORT OFFSET w/ FSD FIRE SMOKE DAMPER 3) ECONOMIZER 6) POWER EXHAUST HEATING CAPACITY= INPUT DUCT WORK PER GMSC 603.10. SEAL DUCTWORK RELEASED R RETURN//EXAUST AIR " 0 ---d`� FLOW DIRECTION STANDARD PER RS-18, 1/2" SP TO 1 SP SEAL TRANSVERSE FITTINGS IT NGS LS LINEAR SLOT DIFFUSER SEE GENERAL NOTE #20 JOINTS. LR LINEAR RETURN DIFFUSER I EIR MLIT vOLUME DAMPER ROUND7. ALL SUPPLY, RETURN AND OUTSIDE AIR DUCTS WYE MBH BTU PER HOUR (THOUSAND) SHALL BE INSULATED AND SEALED PER 2010 M MD MOTORIZED DAMPER PROJ MOTORIZED DAMPER OREGON ENERGY EFFICIENCY SPECIALTY CODE MGR OSA OUTSIDE AIR 503.2.7. INTERIOR DUCTS SHALL BE INSULATED ELBOW WITH BELLMOUTH PSI POUNDS PER SQUARE INCH ABOVE THE BUILDING BARRIER. TURNING VANES RA RETURN AIR 8. INSTALL VOLUME DAMPERS IN ALL DUCT RUNS tj RL REFRIGERANT LIQUID LINE TO FINAL SUPPLY TERMINALS. RawRADIUS ELBOW IF15' MAX. RS REFRIGERANT SUCTION LINE r CONCENTRIC O SMOKE DETECTOR 9. ALL ROUND DUCTS SHALL E� RIGID, EXCEPT THE ROUND SA SUPPLY AIR LAST 5'0 WHICH MAY BE FLEX ABOVE A T-BAR TRANSITION W SWE SIDEWALL EXHAUST GRILLE CEILING. FLEXIBLE SWS SIDEWALL SUPPLY REGISTER (4) PLATED #10 TEK 10. ALL MOTORIZED OUTDOOR AND EXHAUST 15' MAX CONNECTION SWR SIDEWALL RETURN GRILLE UNIT X 3/4" SCREWS DAMPERS SHALL HAVE A MAXIMUM LEAK RATE OF CONCENTRIC SWT SIDEWALL TRANSFER GRILLE 4 CFM PER SOFT @ 1 WG PER AMCA 500-1998, SQUARE TO ROUND RECTANGULAR ` DUCT TIE IN POINT VIBRATION PAD EXCEPT PACKAGED EQUIPMENT SHALL BE ZO RECTANGULAR s, SQUARE TEEEj MAIN WITH TYP TYPICAL STRUCTURAL MEMBERS CFM/FT @1" WG. B W _y SIDEWALL 16 GA X 6" SEISMIC CLIP , VAV VARIABLE VOLUME EACH SIDE (TOTAL 4) FORCONNECTIONr 2"x2" 16 GA. DI ALL BRANCH DUCTS FEEDING INDIVIDUAL DOUBLE FORMED GRILLE 1 r ANGLE VERTICAL DIFFUSERS SHALL HAVE DAMPERS AT TAKE-OFFS TURNING VANES TYPES rr' SUPPORT FOR BALANCING. PROVIDE ACCESS PANELS TO PERIMETER RAIL TRANSVERSE BRACE —� I� DAMPERS. —�� PERIMETER FLASHING 2"x2" 16 GA LONGITUDINAL BRACE 12. LINE FIRST 10 FT. OF SUPPLY RETURN AND LINE 'TYPES ANGLE ANGLE 2"x 16 GA EXHAUST DUCTS FOR SOUND. AN NEW WORK -HVS__H+¢--WSW- (HWS) HEATING WATER SUPPLY 2" STATIC DEFLECTION BULB SEAL 13. SMOKE DETECTORS SHALL BE INSTALLED IN EXISTING WORK -HVR=Hv�—►+vR- (HWR) HEATING WATER RETURN ISOLATOR AND EARTHQUAKE CEN OF BOLTS RETURN DROP AND SHALL DEACTIVATE THE RESTRAINT EQUAL 1" x 12 GA. EQUIPMENT UPON SENSING SMOKE. INSTALL SMOKE --------------- DEMO WORK -HVRr VIL -►wre-- (HWRc) HEATING WATER RETURN- RECIRC. CEN OF ANGLE STRAP DETECTOR IN SUPPLY AIR DUCT ONLY WHERE REF-REF ��� R-FRIGERANT (CS) CONDENSOR WATER SUPPLY NAILER STRIP SEE ARCH. DWGS. REQUIRED BY LOCAL AUTHOR17,1. SMOKE DETECTORS �``' -� —�—� FOR FLASHING. -c —c —c - C CONDENSATE DRAIN - —cit—ca - (CR CONDENSOR WATER RETURN REFER TO SMACNA REQUIRED IN ALL SYSTEMS >2000 CFM. OMSC O ) UNIT CURB (1) STRUCTURAL MEMBERS FOR CONNECTION 606.2. ALL AIR MOVING SYSTE S >2000 CFM SHALL - GAS-GAS (L) GAS -�—�—�- (CHS) CHILLED WATER SUPPLY ',� CANT STRIPBE � -�—�—�- (CHR) CHILLED WATER RETURN 1 1/2 RIGID ;; � , 11 TYPES 606EQUIPPED WITH AUTOMATIC SHUTOFF PER GMSC INSULATION 0 1 II ATLERNATE: (4) A34 o- 2"x2" 16 GIA—, III TRANSVERSE BRACE " a ' II " " 14. FIRE SMOKE DETECTOR INDICATOR SHALL SIMPSON 1/4 SDS SCREW � EACH SIDE OF RTU � N ANGLE VERTICAL � Z x2 16 GA BE INSTALLED WHERE SHOWN. INSTALL INNOVAIR MIN 2.5 IMBED & 3 PER SIDE � � SUPPORT ANGLE SSK451 WITH PS24L0 AND PS12/24LSW. REQUIRED #10 SCREW C� -,; = U LONGITUDINAL BRACE " 0 5 MACHINE " " WHERE CFM >2000 AND NO BL ILDING ALARM I- SYSTEM B.A.S. IS PRESENT. -)MSC 606.4.1 12 O.C. PT LEVELER ___/ ;,;-; , ,-, � � BOLTS T'YP ANGLE 16 GA ( ) _ ) �' ' NOTE: 2-1" x 12 GA. DUCT THIS SUPPORT DETAIL IS 15. INSTALL HVAC UNITS ON LEVEL CURBS. SECURE STRAP FOR DUCT 20"0 AND LARGER ALL UNITS >400 LBS WITH SEISMIC RESTRAINT. SEE PLANS FOR DETAILS. ROOF OPENING 2X4 W/ Z-CLIP 16. ALL OUT SIDE AIR INTAKE: SHALL BE A ' BY OTHERS (2) 2X6 W/ REFER TO SMACNA SEISMIC RESTRAINT MANUAL TABLE 5-6, 6-6 AND 7-6 FOR MINIMUM OF 10 FT FROM EXHp'.IST FANS OR SIMPSON HANGERS VERTICAL HANGERS AND HORIZONTAL BRACES, BOLT SIZE TO SUPPORTING PLUMBING VENTS. BY OTHERS STRUCTURE AND SPACING OF BRACING. (E) JOIST 17. PROVIDE PROTECTIVE GUAF:OS FOR ALL HVAC UNITS LOCATED WITHIN 10 FT OF A ROOF EDGE W N OR LEDGE GREATER THAN 30 INCHES FROM THE W N FLOOR. A/ h ALL STRUCTURAL AND CURB LEVELING BY OTHERS. 2 SEISMIC RESTRAINT FOR LARGE DUCT -25���1 18. OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS l SHALL HAVE MOTORIZED DAMP.-RS THAT CLOSE !� M1 SCALE: NTS WHEN THE SYSTEM IS SHUT 017, DURING BUILDING iJi WARM-UP, COOL DOWN AND/UR SETBACK. Z o ri �NNI_SOLATION CURB 19. ALL INDIVIDUAL HVAC SYS'I'EMS SHALL HAVE (1) O V M1 SCALE: NTS HONEYWELL VISION PRO 8000 oROGRAMMABLE W t, THERMOSTAT UNLESS NOTIFIED OTHERWISE. MOUNT STAT AT 48" A.F.F., EXCEPTIONS: UQ„ 19A) FOR TEMP HEAT UNITS (.TELL BUILDINGS) o USE HONNEYWELL T81001136; 19B) FOR UNIT HEATERS (FR€ :Z€ PROTECTION' T 0 ONLY) USE TEMP STAT MODEL TS41 SET AT 41 DEG Z F AND MOUNTED NO LOWER TI IAN THE UNIT HEATER. 20. ELECTRICAL CONTRACTORS SHALL COORDINATE CIO ELECTRICAL REQUIREMENTS WI"H THE MOST RECENT REVISION OF THESE PLANS Ati0 THE SUBMITTALS OC) PRIOR TO CONSTRUCTION. HVAC INC SHALL NOT BE o RESPONSIBLE FOR ELECTRICAL CONTRACTORS FAILURE TO REVIEW AND CLAP r Y ANY DISCREPANCIES PRIOR TO .ANY CONSTRUCTION. 1986 2013 6600 SW HAMPTON ST �-• • in � SW HAMPTON ST Q` HVAC incorporated H E A T I N G �198rc) Q 5188 INTERNATIONAL WAY MILWAUKIE,OR 97222 to FAX: (503) 462-6555 PHONE: (503) 462-4822 OR CCB # 50897 WA HVACI * * 125J6 FILE NAME. 5519 PACIFIC PARKWAY I PROJECT MANAGER: CONWAY ENGINEER: FROELKE DATE:. 3/3/14 SHEET TITLE:- SCHEDULE, ITLE:SCHEDULE, DETAILS r_3'N\V1Q1N[1TY PLAN M1 SCALE: NTS N REVISION:. N/A REVISION:. N/A REVISION:. All drawings prepared by HVAC INC N/A are the exclusive property of HVAC INC and, unless otherwise agreed in writing, REVISION:. SA N`. I HVAC INC shall be deemed the author of them and shall retain all common law, statutory and other reserved rights, in addition to SHEET p:.� of the copyright. Any use thereof without the express 1 written consent of HVAC INC is prohibited. SINGLE -PLY ME LAP OV SELF -ADHERING SHEET UNDERI LAP OVER TOP OF NEW C ME 6 T.O. ROOF VARIES 2 E' 07 54 23 SELF -ADHERING SHEET UNDERLAYMENT LAP OVER TOP AND BOTH SIDES OF NEW 2X4 CURB 07 54 23 SLOPING TOP SHIM SINGLE -PLY MEMBRANE LAP OVER CURB DIM PTmg g 07 62 00 N N SHEET METAL COPING 1 N 0610 00 STACKED 2X6 STUDS 061000 PLYWOOD SHEATHING I� 07 54 23 SINGLE -PLY MEMBRANE ROOFING DIM PT T.O. (E) WALL — — ' OVER R-30 RIGID INSULATION 00 I T.O. ROOF VARIES T.O. INSULATION FIELD VERIFY `,/C ✓�X yam' /,/x/"� (x. ''�4v ✓ti:!�j( "�'l�x`;�lY? `v' ,, ��YryZ�iA PC0X,`>� Y /X�tz yy7C'f�.%.,�fiI✓ r�Y�X;i1l!S,'�S ,�j'� (E) PLYWOO D lROOF DECK, in FIELD VERIFY �, rl ��r f� yx`5�ny1>' ✓y pry Tyt; HIGH POINT t , (E) GLULAM BEAMS _ (E) ROOF STRUCTURE ROOF CURB TYPICAL DUCT PENETRATION =1'-0" ��� 3" = 1'-0" 07 54 23 SINGLE -PLY ROOFING MEMBRANE 07 54 23 RIGID INSULATION, R-30 07 54 23 FLASHING SHEET 07 9210 CONTINUOUS SEALANT AROUND DRAIN AND OVERFLOW DRAIN, TYP. 22 10 00 OVERFLOW DRAIN NO OVERFLOW DRAIN AT SIM RECESS AREA AROUND DRAIN 22 10 00 ROOF DRAIN FOR DRAINAGE, SEE PLAN FOR EXTENTS moo �.x�,�,�✓���I�X;�X'CX �z Ya''v�r( �`y`CYX ;,c'���^ ;�✓ ;: ✓ T.O. ROOF BLOCKING AS REQUIRED CLAMPING RING, TYP. 2'- 0" MIN FIXED EXTENSION 0610 00 PLYWOOD ROOF DECK A - TYPICAL SECTION e a 0 07 92 00 CONTINUOUS SEALANT 07 54 23 STAINLESS STEEL CLAMPING RING 07 54 23 SINGLE -PLY MEMBRANE FLASHING 07 54 23 WELDED SPLICE ' 07 54 23 RIGID INSULATION, HEIGHT VARIES, MIN 4" R-21 07 54 23 SINGLE -PLY ROOFING MEMBRANE 061000 PLYWOOD SHEATHING i i 07 2100 VAPOR RETARDER BLOCKING AS REQUIRED PIPE PENETRATION AT ROOF 3" = 1'-0" A ^^ 2'-0" a T.O. ROOF VARIES B - PLAN n ROOF DRAIN AND OVERFLOW DRAIN SKYLIGHT 3" = 1'-0" 1 1/21' = 1'-0" 11/IECHANICAL CURB SEE STRUCTURAL FOR EDGE OF DECK CONNECTIONS MAR 0 6 2014 CITY OF TIGARD .ANNING/ENGINEERING tva architects Inc. 920 sw sixth avenue I suite 1500 porttand, oreyon 97204 phone: 503 220 0668 www.tvaRrchitects.com 'OD A kt T t,» TIC}MPSf}riti OF EXHAUST FAN, MECH UNIT W/ CURB CAP FLASHING, SECURE TO CURB I PROVIDE CONTINUOUS SEALANT AT BASE OF MECH EQUIP. 07 54 23 U SINGLE -PLY MEMBRANE L >m1' _ LAP OVER CWB a Y ` v�l ■ as a U ,yFX 07 62 00 SHEET METAL FLASHING g ;� ( z `>T' 07 62 0018 GA. PREFABRICATED - SHEET METAL CURB 00 `y' 07 54 23 SINGLE-PLY MEMBRANE ROOFING OVER R-30 RIGID INSULATION x 11/IECHANICAL CURB SEE STRUCTURAL FOR EDGE OF DECK CONNECTIONS MAR 0 6 2014 CITY OF TIGARD .ANNING/ENGINEERING tva architects Inc. 920 sw sixth avenue I suite 1500 porttand, oreyon 97204 phone: 503 220 0668 www.tvaRrchitects.com 'OD A kt T t,» TIC}MPSf}riti OF d L C 0 E M = N CD 0 0 4%O %0 CD m 00 Cn a. a. Cna IC No, Date Description 1 12.10.13 ADDENDUM 1 �31pr F©R Croom CQI>3#i 1�it OTO ; Suite #1: iat� �7 14- Y�� 71 cvl I C4�, Approved pians shall be on job site, OFFICE COPY PERMIT SET ROOF DETAILS Project # 13117 Date: 11.08.2013 w z w U H ' >m1' a Y H U � as a U LL U Q a d L C 0 E M = N CD 0 0 4%O %0 CD m 00 Cn a. a. Cna IC No, Date Description 1 12.10.13 ADDENDUM 1 �31pr F©R Croom CQI>3#i 1�it OTO ; Suite #1: iat� �7 14- Y�� 71 cvl I C4�, Approved pians shall be on job site, OFFICE COPY PERMIT SET ROOF DETAILS Project # 13117 Date: 11.08.2013