Plans (7) ME,iC2012 - 00342 PR MECHANICAL SYMBOL LIST EQUIPMENT SCHEDULE GENERAL NOTES '� GINEF SYMBOL DESCRIPTION ELECTRICAL DUCTWORK 1. PROVIDE AND INSTALL 1Y" INSULATION ON REFRIGERANT PIPING. CD CEILING DIFFUSER RTU-1, RTU-2 PACKAGED ROOFTOP GAS/ELECTRIC AIRCONDITIONER: 208 V/1 PH ® ® SUPPLY OR OUTSIDE AIR CND CONDENSATE DRAIN AIRFLOW: 1,850 CFM AT.7 E.S.P. SEE VENTILATION SCHEDULE FOR OSA[REQUIREMENTS. 38 FLA 2. PROVIDE AND INSTALL R-5 MINIMUM DUCT INSULATION ON J COOLING: 60.0 MBH TOTAL,48.0 MBH SENSIBLE, 13 SEER MINIMUM. 38.5 MCA ALL SUPPLY DUCTS. RETURN DUCTS ARE NOT INSULATED CFM CUBIC FEET PER MINUTE HEATING: 72.0 MBH, 59.0 MBH OUTPUT, 81%AFUE MINIMUM. 60 MOCP UNLESS OTHERWISE NOTED. EXPIRES: 06-30-2014 21 (2 RETURN AIR COP COEFFICIENT OF PERFORMANCE PROVIDE WITH ECONOMIZER AND ROOF CURB. 3. PROVIDE O&M MANUALS TO OWNER ON ALL MECHANICAL APPROXIMATE OPERATING WEIGHT: 750 LBS. EQUIPMENT. ® ® EXHAUST AIR CONT. CONTINUATION BASIS OF DESIGN: CARRIER 48TDCA06A2A30BOA0. CU CONDENSING UNIT w O1 ROOM THERMOSTAT EF-1 THRU EF-12 CENTRIFUGAL CEILING MOUNTED EXHAUST FAN: 115 V/1 PH D DROP 75 CFM AT.375 IN. T.S.P.WITH BACKDRAFT DAMPER. .3 FLA RECEIVED ;' I v W DB DECIBEL SONES: 1.0 MAXIMUM JUL s, 2012 Q SENSOR APPROXIMATE OPERATING WEIGHT: 15 LBS. CI7YOFTIG�p„ > . 00cn DB DRY BULB BASIS OF DESIGN: BROAN QTXE110. CONTROL: WALL SWITCHf1��77tt�tJJA! pz GE) EQUIPMENT IDENTIFICATION �lll FYti Y 1j,J1Q - DIA DIAMETER ( } W LIJ1 CD-1 100 DIFFUSER OR GRILLE IDENTIFICATION DX DIRECT EXPANSION Y ° LL 6"0-4 ( LuO EAT ENTERING AIR TEMPERATURE DIFFUSER, REGISTER AND GRILLE SCHEDULE O DAMPERS EDH ELECTRIC DUCT HEATER ° Cf) SYMBOL TYPE FACE FRAME DAMPER FINISH BASIS OF DESIGN �_ > EER ENERGY EFFICIENCY RATING CD-1 CEILING DIFFUSER LOUVERED LAY-IN NONE WHITE TITUS TDC 0 VOLUME DAMPER Q CD-2 CEILING DIFFUSER LOUVERED SURFACE OBD WHITE TITUS TDC EF EXHAUST FAN CRG-1 CEILING RETURN GRILLE EGGCRATE LAY-IN NONE WHITE TITUS 5OR FIRE DAMPER EEF EFFICIENT CRG-2 CEILING RETURN GRILLE EGGCRATE SURFACE NONE WHITE TITUS 5OR r FD FIRE/SMOKE DAMPER EL ELEVATION FSD ELEC ELECTRICAL THIS DRAWING DATA AND DESIGNS THEREON SHALL NOT BE DUPLICATED, USED OR TFR SMOKE DAMPER CHAPTER 4 VENTILATION SCHEDULE PROCUUREMENTOSED OR OTO RTHERS PURPOSE, SD EXH EXHAUST EXCEPT AS OTHERWISE AUTHORIZED BY CONTRACT,WITHOUT PERMISSION OF ( MOTORIZED DAMPER F FAHRENHEIT ° JET INDUSTRIES, INC. /o OCCUPANCY AREA LOAD OSA PER OSA PER OCCUPANT MECHANICAL ROOM OSA OSA OSA ZONE SYSTEM POPULATION 1935 SILVERTON RD. SALEM,OR 97301 M FD FIRE DAMPER ROOM NAME CLASSIFICATION SQ FT PER 1000 PERSON SQ FT LOAD UNIT# CFM CFM PROVIDED REQUIRED EFFECT EFFICENCY DIVERSITY NOTES TEL: (503)3944,15 4 FAX: (1662 8,170922 OR CCB#�S 3944,156944,158633,166248,170982 ALL REPRODUCTIONS SHALL BEAR THIS DUCTWORK FITTINGS FLA FULL LOAD AMPS BUSINESS MANAGER 105 OFFICE 145 5 5 0.06 0.7 RTU-1 300 18.9% 57 15 0.8 NOTICE. RECEPTION 104 RECEPTION AREA 208 30 5 0.06 6.2 RTU-1 225 18.9% 43 55 0.8 FT FEET MITERED ELBOW WITH WAITING 100 MAIN ENTRY LOBBY 300 10 5 0.06 3.0 RTU-1 600 18.9% 113 41 0.8 TURNING VANES HP HEAT PUMP STAFF ROOM 127 CONFERENCE 174 25 5 0.06 4.4 RTU-1 275 18.9% 52 40 0.8 a N HP HORSEPOWER HALL 102 CORRIDOR 220 0 0 0.06 0.0 RTU-1 150 18.9% 28 17 0.8 RADIUSED ELBOW KIDS 101 MAIN ENTRY LOBBY 63 10 5 0.06 0.6 RTU-1 50 18.9% 9 9 0.8 HTR HEATER STERILE 112 WORKROOM 114 5 5 0.06 0.6 RTU-1 100 18.9% 19 12 0.8 04O RECTANGULAR MAIN WITH IE INVERT ELEVATION LAB 113 WORKROOM 56 10 5 0.18 0.6 RTU-1 50 18.9% 9 16 0.8 HALL 120 CORRIDOR 56 0 0 0.06 0.0 RTU-1 100 18.9% 19 4 0.8 c ROUND BRANCH 'iz IN INCHES X-RAY 115 WORKROOM 59 10 5 0.18 0.6 RTU-1 125 18.9% 24 17 0.8 c RECTANGULAR MAIN WITH KW KILOWATT PANO 121 WORKROOM 59 10 5 0.18 0.6 RTU-1 125 18.9% 24 17 0.8 .O RECTANGULAR BRANCH 1454 17.3 RTU-1 1850 18.9% W LAT LEAVING AIR TEMPERATURE 350 202 0.96 0.80 d ROUND MAIN REDUCING WITH LBS. POUNDS OP#3 MEDICAL PROCEDURE 130 20 15 0 2.6 RTU-2 175 18.9% 33 49 0.8 ROUND BRANCH OP#2 MEDICAL PROCEDURE 88 20 15 0 1.8 RTU-2 250 18.9% 47 33 0.8 MA MIXED AIR HYGIENE#2 MEDICAL PROCEDURE 238 20 15 0 4.8 RTU-2 275 18.9% 52 89 0.8 CONCENTRIC SQUARE TO MAX MAXIMUM HYGIENE#1 MEDICAL PROCEDURE 238 20 15 0 4.8 RTU-2 350 18.9% 66 89 0.8 ROUND OP#1 MEDICAL PROCEDURE 131 20 15 0 2.6 RTU-2 175 18.9% 33 49 0.8 W MBH THOUSAND BTU'S PER HOUR SURGERY 117 MEDICAL PROCEDURE 131 20 15 0 2.6 RTU-2 175 18.9% 33 49 0.8 J ECCENTRIC TRANSITION, RECTANGULAR OR ROUND MD MOTORIZED DAMPER DR OFFICE 118 OFFICE 203 5 5 0.06 1.0 RTU-2 250 18.9% 47 22 0.8 HALL#2/ARCADE CORRIDOR 270 0 0 0.06 0.0 RTU-2 200 18.9% 38 20 0.8 Q � MH MOUNTING HEIGHT T/1 NON-SYMMETRICAL WYE 1429 20.1 RTU-2 1850 18.9% 350 333 0.96 0.80 d `/1 W MIN MINIMUM J� SYMMETRICAL WYE N/A NOT APPLICABLE WASH/DRY 126 STORAGE 42 0 0 0.06 0.0 EF-1 75 100.0% 75 3 r , MECHANICAL 125 STORAGE 39 0 0 0.06 0.0 EF-2 75 100.0% 75 2 NTS NOT TO SCALE RECTANGULAR DUCT RISER OA OUTSIDE AIR TRASH 122 STORAGE 12 0 0 0.06 0.0 EF-3 75 100.0% 75 1 \ ROUND DUCT RISER OBD OPPOSED BLADE DAMPER STORAGE 119 STORAGE 45 0 0 0.06 0.0 EF-4 75 100.0% 75 3 ^ z OD OUTSIDE DIAMETER STAFF TOILET 124 TOILET 56 0 0 0 0.0 EF-5 75 100.0% 75 0 b W RECTANGULAR DUCT DROP PENA PH PHASE LAB 113 WORKROOM 56 0 0 0.06 0.0 EF-6 75 100.0% 75 3 IV It= uJ ROUND DUCT DROP QTY QUANTITY PATIENT TOILET 103 TOILET 68 0 0 0 0.0 EF-7 75 100.0% 75 0 b • ��II J RA RETURN AIR SURGERY 117 MEDICAL PROCEDURE 131 20 15 0 2.6 EF-8 75 100.0% 75 39 RECTANGULAR OFFSET CITX1c®��cLT,I�GaA�R�A Q LESS THAN 15° RET RETURN OP#1 MEDICAL PROCEDURE 131 20 15 0 2.6 EF-9 75 100.0% 75 39 Approved.�:�}4. :.: \ Conditionally Approved..............[ ] / RPM REVOLUTIONS PER MINUTE HYGIENE#1 MEDICAL PROCEDURE 238 20 15 0 4.8 EF-10 75 100.0% 75 71 See Letter to:Follow.. .......[ } RECTANGULAR OFFSET MORE THAN 15° SA SUPPLY AIR HYGIENE#2 MEDICAL PROCEDURE 238 20 15 0 4.8 EF-11 75 100.0% 75 71 Atta hed................ ] W PennitN n _ SEER SEASONAL ENERGY EFFICIENCY RATING OP#2 MEDICAL PROCEDURE 88 20 15 0 1.8 EF-12 75 100.0% 75 26 t 116, 1 � ROUND WYE By: Date: SF SQUARE FEET OP#3 MEDICAL PROCEDURE 130 20 15 0 2.6 EF-13 75 100.0% 75 39 p ROUND DUCT WITH ROUND SH SENSIBLE HEAT oved pian: BRANCH SCHEDULE NOTES: 975 Shall be Oft job Sft2. It SP STATIC PRESSURE ItT a. ROOM VENTILATION BASED ON 50%AVERAGE UTILITY PER OMSC 403.3 r CONCENTRIC TRANSITION, TEMP TEMPERATURE b. 75 CFM EXHAUST PER FIXTURE (SHOWER COUNTED AS FIXTURE). OFFICE COPY r-al RECTANGULAR OR ROUND c. TRANSFER AIR PROVIDED. UH UNIT HEATER d. OSA REQUIRED TO PROVIDE PRESSURE BALANCE TO OFFSET BUILDING EXHAUST AT 70% (682 CFM CALCULATED). REV. # DATE ACCOUSTICALLY LINED V VOLT DUCT"INSIDE DIMENSION (OUTSIDE DIMENSION)" VD VOLUME DAMPER (HAND OPERATOR) W WATT GAS PIPING CALCULATION ABBREVIATIONS W/ WITH PIPE FLOW RATE PIPE INLET PIPE NOMINAL PIPE PIPE PIPE OUTLET DESIGNATION MBH/HOUR PRESSURE (LBS) LENGTH (FT) SIZE (INCHES) ID (INCHES) PRESSURE A/C AIR CONDITION(ED) WB WET BULB AB 144 2 88 3/4 0.785 1.97 SHEET INDEX AD ACCESS DOOR W/O WITHOUT BC 72 1.97 36 1/2 0.545 1.95 AFF ABOVE FINISHED FLOOR M2.0 HVAC LEGEND/SCHEDULES/SHEETS DATE: 06/27/2012 TOTAL DEVELOPED LENGTH 124 M2.1 HVAC FLOOR PLAN JOB: 12-0206 BDD BACKDRAFT DAMPER M3.1 HVAC DETAILS DESIGN BY: JLS CONTACT: DON OLHEISER TEL. #: 503-363-2334 M20 ■ PLOTTED: SARA MURAWSKI 6/27/2012 2:58 PM PATH: P:\2012\12-0206-DR BRANDON SCHWINDT\ENGINEERING\HEATING NOTES G 1O 4"0 DRYER EXHAUST DUCT TERMINATES ON EXTERIOR WALL WITH ALUMINUM - WALL CAP WITH BACKDRAFT DAMPER. GON O8"0 EXHAUST DUCT UP AND TERMINATE ON ROOF WITH GLOBE VENT. ONN S(P O6"0 EXHAUST DUCT UP AND TERMINATE ON ROOF WITH GLOBE VENT. EXPIRES: 06-30-2014 ONEW 2 LBS GAS METER. 144 MBH AT 124' TDL. O5 Y"2 LBS GAS PIPING PENETRATES ROOF. CONNECT TO ROOFTOP UNIT WITH u.1 SHUT-OFF VALVE AND PRESSURE 0 s REGULATOR. CL 0 Z4 W uj u" U) p CD-1 275 CRG-2 175 CD-1 300 Z 12x12-31 12x12 I12x12-3 TYP. 2cj CD-1 50 - CD-1 50 EF-7 t=-w EF-5 LL. 6x6-2 6x6-2 � � � � Lu Z EF-6 CD-1 100 CRG-1 500 RTU-1 CD-1 225 y p 9x9-4 22x22 12x12-4 U) / ON ROOF o p Q 12"0-1 - / 10,10 ., - -_ WASH/DRY ------- - - - - -Ir THIS DRAWING DATA AND DESIGNS / ;, i_ i �r --- BUS.MNGR. 126 � ORAGE ' -_ _� __ 105 1 i THEREON SHALL NOT BE DUPLICATED, /. 114 I —� ! I USED OR DISCLOSED TO OTHERS FOR / 2 \ , 12 16X14 L 1 I PROCUREMENT OR OTHER PURPOSE, / 6"0 " L. (18x16) I I EXCEPT AS OTHERWISE AUTHORIZED BY - ._ _ I CONTRACT,WITHOUT PERMISSION OF �i 12"0 i JET INDUSTRIES, INC. 1 ' STAFF RM. R WAITING RECEP. 10°0 ;•; I 1935 SILVERTON RD. SALEM,OR 97301 / 127 0 -' i 100 104 _i _ TEL: (503)363-2334 FAX: (503)363-2622 L CD: -� OR CCB#'S 3944,156944,158633,166248,1TC982 ALL REPRODUCTIONS SHALL BEAR THIS / LAB 14"0 12"0 NOTICE. _ x / ME _ 113 = � --- - - CRG-1 250 5 ��� r �� - _ \� � �� X 12x12 f J-3 N 2 -- ---- -- - r CD-1 N 300 / 6 0 I N RTU-1 G$ 12x12-3 -- -- -- - _ I CO m O� "o� - J �� CRG-1 300 ^/ o - - -- fil I � ( 12x12 STAFF CRG 1 150 O EF-1 � N T3. �� � O 12x12 � 124 I 22x14 L. ;;< ' SIO 'A' � .: � `,, X-RAY I 4x16) 115 3 `-�j - EF-2 - -- — -- - — — 5 CD 1 150 1 - 3 \ ® 9x9-2 I rI ! o I 6"Qf STERILE .�� KIDS 6"0 I 3/a I 112 '`�L 101 C' EF-13 i TRASH I------- I 122 103 14"0 6"0 CD-1 100 1 c9 �� 10„0 I HALL#1 9x9-2 CRG-1 225 HALL#3 0 O o 1/2° 12x12 �- _ 0 102 120 PANG ARCADE NICHE CRG-1 125 121 110 Jr �, •~ 12x12 TYP. 2 - L ____ _._ . GF OP.3 \ \ - � — ——— — ——— _ — —— — —— —————— —— —— —— 106 STORA E 6"0 10"0 14"0 14x14 L. (16x16) 14x14 L. (16x16) 14"0 �� -- -- -- 119 2 ~ HALL#2 1 / 1..` 8„0 8„0 111 8"0 8"0 6"0 8"0 8"0 O T 6„0 \ CED � CD j x HYGIENE 2 0 3 p -' N N 108 \/ CRG-1 225 t -- 2 �" �- /V oP. 2 CD-1 175 T. 0 3 / \ 107 12x12-2 12x12 6"0 1 i o 0 _L\� 6,�0 \ U o _ \ EF 12 - — 14x14 L. 14x14 L. 10"0 12"0 14"0 \ (16x16) �. (16x16) 12"0 \ \/ 10"� CD-1 250 A > o 8„0 ..1. o 12x12-2 Li 3 8"0 8"0 8"3 HYGIENE 1 6"o • DR.OFFICE 109 $��0 8"0 ••I 118 / SURGERY OP. 1 % 117 116 - Li 0 CD-1 250 CD-1 100 CD-1 175 RTU-2 EF-11 12x12-2 9x9-2 9x9-2 TYP. 5 ON ROOF EF-9 EF-10 CD-1 100 d' 9x9-2 t� EF-8 CRG-1 150 CD-1 175 12x12 TYP.6 9x9-4 REV. # DATE (' l _'�� HVAC FLOOR PLAN M2.1 1/4 if - 11-011 DATE: 06/27/2012 JOB: 12-0206 DESIGN BY: JLS CONTACT: DON OLHEISER TEL.#: 503-363-2334 ■ 1 PLOTTED: SARA MURAWSKI 6/27/2012 2:58 PM PATH: P:\2012\12-0206-DR BRANDON SCHWINDT\ENGINEERING\HEATING PR GIN �v EON Yl ��l NN IPJ N1 ON TIR L R�1 EXPIRES: 06-30-2014 1 24 VAC I 24 VAC; I L 2 P1 OP � _ HOT CON1 C715CB MIXED MIN.POSITION + 3 AIR OR 17146AADJUSTMFNT {. 2 ulsr.HARCE T1 T AIR SENSOR T:1 O 1 (D— F 5 2 FO Ql 5 SO+ ACTUATOR I SO SO3 4lz S —� v R+ EF EF1 '` Z l LO wLL C7400 - s Z AOIR D OOR + 620 OHM I IIV I I O ENTHALPY RESISTOR BRANCH DUCT : O SENSOR O SHUTOFF VALVE. PRESSURE TEST TEE 1/4" PIPE I SUPPLY AIR FLOW. N WITH 1/4" BRANCH PLUG (TYP. 2). > .• (TYP.). I I SHEET METAL BRANCH � 0 c: Q NOTE: UNION. DUCT WITH 1"DUCT t.a ----- -------------- -- HP CONV I COORDINATE ALL ROOF DIMENSION AS LINER OR FIBERGLASS C i I SHOWN ON PLANS. I DUCTBOARD. I PENETRATIONS AND FLASHING L O Y1 COOL 1 WITH ROOF MANUFACTURER TO EQUIP. AND INSTALLER. SEE ROOFING 6" MIN. I VOLUME DAMPER. E O PROVIDE WHERE I SPECIFICATIONS AND INDICATED ON THIS DRAWING DATA AND DESIGNS PRESSURE REGULATOR. AUX O I ARCHITECTURAL DETAILS. I FLOOR PLAN OR THEREON SHALL NOT BE DUPLICATED, I SOLDER LEAD COUNTER FLASHING USED OR DISCLOSED TO OTHERS FOR G G O I I TO TAPERED THREADED COUPLING. SPECIFICATIONS. PROCUREMENT OR OTHER PURPOSE, EXCEPT AS OTHERWISE AUTHORIZED BY O/B W — HEAT 1 CONTRACT,WITHOUT PERMISSION OF I CC JET INDUSTRIES, INC. DELAY I MINIMUM 4"OVERLAP. LEAD FLASHING HOT MOP / 1935 SILVERTON RD. SALEM,OR 97301 Y Y RELAY i FLASHING TO ROOF. 6" MIN. I TEL: (503)363-2334 FAX: (503)363-2622 FDR 45o OR CiL'B#'S 3944,156944,158633,166248,17C;982 R R G FAN L21 / I MAIN DUCT. ALL REPRODUCTIONS SHALL BEAR THIS FDRI / I NOTICE. Rc Rc R ----------L1' (HOT) ROOFING. ROOF. SUPPLY AIR THERMOSTAT EQUIPMENT I N HVAC EQUIPMENT — — — ` — — — — — TH6110D TERMINAL STRIP CONTROL BOARD I F RETURN/EXHAUST AIR O� ECONOMIZER CONTROL MAIN RECTANGULAR o 1 WIRING SCHEMATIC 2 GAS PIPE ROOF PENETRATION 3 BRANCH DUCT CONNECTION 1 HEAT/ 1 COOL NO SCALE NO SCALE •may -4mi SEISMIC � CLIPS �/ Q I— W PLAN VIEW U ROOFTOP UNIT 16 GUAGE (4)#10 TEC SCREWSSEISMIC > HOLD DOWN T FACTORY CURB CLIP A J� (EXISTING) (4)#10 TEC SCREWS SHEET METAL DUCT. RIGID CURB VOLUME DAMPER PER INSULATION SPECIFICATIONS (NOT 4x4 BLOCKING FURNISHED W/SPIN-IN). MINIMUM. Y" LAG AT 12" O.C. MINIMUM 2Y2" DEPTH INTO BLOCKING. � FLEXIBLE DUCT- MAX 5-0". ROOF DECK 6" PREMANUFACTURED CONNECT AIR INLET OR OUTLET TO ELBOW TRUSSES CEILING. PER MANUFACTURER'S INSTRUCTIONS. SECTION 7 SEISMIC CLIP HOLD 4 AIR INLET OR OUTLET ROUND NECK 5 DOWN DETAIL - CURBS NEW NO SCALE NO SCALE REV. # DATE DATE: 06/27/2012 JOB: 12-0206 DESIGN BY: JLS CONTACT: DON OLHEISER TEL. #: 503-363-2334 m3m 1 PLOTTED: SARA MURAWSKI 6/27/2012 2:58 PM PATH: P:\2012\12-0206-DR BRANDON SCHWINDT\ENGINEERING\HEATING