Loading...
Plans (9)LOWER FLOOR PLAN 225 SQ. FT. 0 FT 2 FT 4 FT 6 FT 8 FT 10 FT 12 FT I NOTES All piping and fittings to be 1" CPVC. All hangers to be CPVC Standoff type and located per NFPA 13D requirements. Max. sprinkler spacing to be 16' x 16' w/ 8'-0" off walls. All CPVC piping to be 1" w/ Riser to be 1" black steel piping. Meets design requirements of NFPA 13D 2013 edition. All piping to be installed before insulation and protected with a medium weight plastic barrier (to be provided by others). Riser to be connected to domestic water prior to hot water heater. Double check to be provided by Wyatt Fire but installed, permitted and tested by plumber (contact Stonebridge Homes for information on plumber). APPROVALS AND INSPECTIONS DATE DESCRIPTION MAIN FLOOR PLAN 1'U99 S;Q. f 1. 0 FT 2 FT 4 FT 6 FT 8 FT 10 FT 12 FT SPRINKLER SYMBOLS O Concealed Pendant, 4.9 K—factor, 160% Quick Response, White Qty. 20 A I I I I I I UPPER FLOOR PLAN 1,196 SQ. FT. 0 FT 2 FT 4 FT 6 FT 8 FT 10 FT 12 FT WYA T FIRE PROTECTION, INC, 9095 S.W. Burnham Tigard, OR 97223 (503) 684-2928 ............ ... - ...... ........ ........... ......................... FLOW TEST DATA Static Pressure 60 psi Flaw 1230 gpm Residual Pressure 48 psi Test Date 15 Dec 2014 HYDRAULIC DEMAND Density .05 gpm/sgft Area 2 heads Required now 27.2 gpm Required Pressure BOR 32.3 psi Hose Flow Included 0 gpm HECE'VED MAR 2 5 2015 BUIC"YRD NG DIOF VIStO ON CITYOPTIGARID RENVIEiiD FOR CODE COMPLIANCE Approved: OTC: Permit #t Address: 1Tyt—m7( o Suite #: By: Date ti OFFICE COPY SOUTHVIEW HEIGHTS LOT 17 Ri PERMIT NO. 12053 SW AUTUMNVIEW STREET CONTRACT NO. TIGARD, OREGON 97223 APPROVAL DRAWN BY SCALE DATE STONEBRIDGE HOMES, 4230 GALEWOOD ST, #100, LAKE OSWEGO, OR 97035 REVISED PI nTTFn FP -1 A PAYNE 1/4" = 1'-0" 21 MAR 2015 FP1of2 TO SYSTEM 1" CPVC PRESSURE GUAGE 1" DCVA AMES SERIES 2000B 1" DYNA-THREAD FLOOR B- RISER DETAIL NOT TO SCALE 'TER VSR-S FERFLOW RM SWITCH 1BLIC SUPPLY / 12" OF BATT OR 'N INSULATION EDIUM WEIGHT PLASTIC 4RRIER OVER LINE PIPING 1" x DROP (SEE PLAN) C- TYPICAL INSULATION COVER NOT TO SCALE— TO BE PROVIDED BY OTHERS AFTER PIPING INSTALLATION A- CROSS SECTION NOTES All piping and fittings to be CPVC. All hangers to be CPVC Standoff type and located per NFPA 13D requirements. Max. sprinkler spacing to be 16'x 16'w/ 8'-0" off walls. All CPVC piping to be 1" w/ Riser to be 1" black steel piping. Meets design requirements of NFPA 13D 2013 edition. All piping to be installed before insulation and protected with a medium weight plastic barrier (to be provided by others). Riser to be connected to domestic water prior to hot water heater. Double check to be provided by Wyatt Fire but installed, permitted and tested by plumber (contact Stonebridge Homes for information on plumber). 11 1 APPROVALS AND INSPECTIONS DATE I DESCRIPTION SPRINKLER SYMBOLS LOT' 18 PLOT 3/32"=1'-0" 3aE� WWWANMWOI 1 �i 12053 VIE J ST. WYAT FIRE PROTECTION, INC. 9095 S.W. Burnham Tigard, OR 97223 (503) 684-2928 1) Ck M -,,v✓ ERL INE rMM� M SOUTHVIEW HEIGHTS LOT 17 12053 SW AUTUMNVIEW STREET TIGARD, OREGON 97223 STONEBRIDGE HOMES, 4230 GALEWOOD ST, #100, LAKE OSWEGO, OR 97035 160 FP -2 CRM SECTION -I- DETAILS PERMIT NO. CONTRACT NO. APPROVAL DRAWN BY A PAYNE SCALE 1/4" = 1'-0" DATE 21 MAR 2015 REVISED PI OTTFn FP 2 of 2