Plans (9)LOWER FLOOR PLAN
225 SQ. FT.
0 FT 2 FT 4 FT 6 FT 8 FT 10 FT 12 FT
I NOTES
All piping and fittings to be 1" CPVC.
All hangers to be CPVC Standoff type and located per NFPA 13D requirements.
Max. sprinkler spacing to be 16' x 16' w/ 8'-0" off walls.
All CPVC piping to be 1" w/ Riser to be 1" black steel piping.
Meets design requirements of NFPA 13D 2013 edition.
All piping to be installed before insulation and protected with a medium weight plastic barrier (to be provided by others).
Riser to be connected to domestic water prior to hot water heater.
Double check to be provided by Wyatt Fire but installed, permitted and tested by plumber (contact Stonebridge Homes for information on
plumber).
APPROVALS AND INSPECTIONS
DATE DESCRIPTION
MAIN FLOOR PLAN
1'U99 S;Q. f 1.
0 FT 2 FT 4 FT 6 FT 8 FT 10 FT 12 FT
SPRINKLER SYMBOLS
O Concealed Pendant, 4.9 K—factor, 160% Quick Response, White Qty. 20
A
I
I
I
I
I
I
UPPER FLOOR PLAN
1,196 SQ. FT.
0 FT 2 FT 4 FT 6 FT 8 FT 10 FT 12 FT
WYA T
FIRE PROTECTION, INC,
9095 S.W. Burnham
Tigard, OR 97223
(503) 684-2928
............ ... -
...... ........
........... .........................
FLOW TEST
DATA
Static Pressure
60 psi
Flaw
1230 gpm
Residual Pressure
48 psi
Test Date
15 Dec 2014
HYDRAULIC
DEMAND
Density
.05 gpm/sgft
Area
2 heads
Required now
27.2 gpm
Required Pressure BOR
32.3 psi
Hose Flow Included
0 gpm
HECE'VED
MAR 2 5 2015
BUIC"YRD
NG DIOF VIStO
ON
CITYOPTIGARID
RENVIEiiD FOR CODE COMPLIANCE
Approved:
OTC:
Permit #t
Address: 1Tyt—m7( o
Suite #:
By: Date
ti
OFFICE COPY
SOUTHVIEW HEIGHTS LOT 17 Ri
PERMIT NO.
12053 SW AUTUMNVIEW STREET CONTRACT NO.
TIGARD, OREGON 97223 APPROVAL
DRAWN BY
SCALE
DATE
STONEBRIDGE HOMES, 4230 GALEWOOD ST, #100, LAKE OSWEGO, OR 97035 REVISED
PI nTTFn
FP -1
A PAYNE
1/4" = 1'-0"
21 MAR 2015
FP1of2
TO SYSTEM 1" CPVC
PRESSURE GUAGE
1" DCVA AMES
SERIES 2000B
1" DYNA-THREAD
FLOOR
B- RISER DETAIL
NOT TO SCALE
'TER VSR-S
FERFLOW
RM SWITCH
1BLIC SUPPLY
/ 12" OF BATT OR
'N INSULATION
EDIUM WEIGHT PLASTIC
4RRIER OVER LINE PIPING
1" x DROP
(SEE PLAN)
C- TYPICAL INSULATION COVER
NOT TO SCALE— TO BE PROVIDED BY OTHERS AFTER PIPING INSTALLATION
A- CROSS SECTION
NOTES
All piping and fittings to be CPVC.
All hangers to be CPVC Standoff type and located per NFPA 13D requirements.
Max. sprinkler spacing to be 16'x 16'w/ 8'-0" off walls.
All CPVC piping to be 1" w/ Riser to be 1" black steel piping.
Meets design requirements of NFPA 13D 2013 edition.
All piping to be installed before insulation and protected with a medium weight plastic barrier (to be provided by others).
Riser to be connected to domestic water prior to hot water heater.
Double check to be provided by Wyatt Fire but installed, permitted and tested by plumber (contact Stonebridge Homes for information on
plumber).
11 1 APPROVALS AND INSPECTIONS
DATE I DESCRIPTION
SPRINKLER SYMBOLS
LOT' 18
PLOT
3/32"=1'-0"
3aE�
WWWANMWOI 1 �i
12053
VIE J ST.
WYAT
FIRE PROTECTION, INC.
9095 S.W. Burnham
Tigard, OR 97223
(503) 684-2928
1) Ck M
-,,v✓
ERL INE
rMM� M
SOUTHVIEW HEIGHTS LOT 17
12053 SW AUTUMNVIEW STREET
TIGARD, OREGON 97223
STONEBRIDGE HOMES, 4230 GALEWOOD ST, #100, LAKE OSWEGO, OR 97035
160
FP -2
CRM SECTION -I- DETAILS
PERMIT NO.
CONTRACT NO.
APPROVAL
DRAWN BY A PAYNE
SCALE 1/4" = 1'-0"
DATE 21 MAR 2015
REVISED
PI OTTFn FP 2 of 2