Report 41/
BGG SAv ccs 4
VAV Box
• Project: -Untitled111 05/26/2016
Prepared By: 12:06PM.
1
RECEIVED
JUN 162016
CITY OF TIGARD
VAV Box BUILDING DIVISION
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Acoustic Summary
r
Air Terminals Builder 2.09i Page 1 of 5
•
Unit Report For VAV Box
Project: -Untitled111 05/26/2016
Prepared By: 12:06PM
r
I
Unit Parameters
Tag Name• VAV Box
Quantity. 1
Model Type• Analog Electronic Controls
Model. 35E Single Duct Terminals
Control Type• 2111:Analog Clg w/EH Auto Changeover
Unit and Inlet Size. 14 Inch
Part Number 35EA3300L140211100000S000000E6210.0K0000120006000600
Reheat Option' Electric Reheat
Insulation Lining• Standard(1/2 inch Fiberglass Liner)
Outlet 20x17.5
Dimensions
Unit Depth 39.5 in
Unit Width• 20.0 in
Unit Height 18.0 in
Unit Operating Weight• 70 lb
"' Weights and Dimensions are approximate.Weight does not include curbs
and accessories.Approximate dimensions are provided primarily for
shipping purposes.For exact dimensions,refer to certified drawings.
Warranty Information
1 Year Parts Only Warranty
Ordering Information
Part Number Description Quantity
Base Unit
35EA3300L140211100000S0 35E Single Duct Terminals 1
00000E6210.0K0000120006
000600
Base Unit
Attenuator
22 Gauge, Left Hand Ctrl, No Access Panel
2111:Analog Clg w/EH Auto Changeover
208v/3Ph/2S (3-Wire)
LineaCross(4 quadrant)
10.0 kW
Hangers
Door-Interlocking Fused Disconnect
Accessories
FAST SHIP CHARGES Quick Ship Premium for 35E 1
r
Air Terminals Builder 2.09i Page 2 of 5
Certified Drawing for VAV Box
Project: -Untitled111 05/26/2016
Prepared By: 12:06PM
rrF TM LOCu.EN 1ST.PRCPERTM 6 s SICEI CF TI-ESEBASE UNIT WITH
(iitr,—
CPf R cCRPORA Wfn IS CEuvErEo CRANMGS OR CCO.PENTS
Carrier hEC E%PRESS Rr CORS F o ANALOGORDIGFiAL
ceZE,Z, uar�usa�o P� reTSPCE CONTR OLS ANO
CATALOG# A United Technologies Company useo amara �wEa nc�rrucE a
' "E" ELECTRIC REHEAT
CHARTED 'A' DIMENSION INCLUDES INLET
6 1/4 ADAPTER PROVIDED ON SIZES 4 & 5.
W (159) —O- 39 1/2 (1003) —1/2 (13)
AIR FLOW TVP SLIP & DRIVE OUTLET
SENSOR DUCT CONNECTION
�`� INLET DISCHARGE
H _ 12 (305) ♦ �
r\`` TYP AIR
�. AIR
FLOW FLOW
DAMPER D II I ~
DIGITAL & REHEAT
IJ.ETVEWSIMS6-16 CONTROL ENCLOSURES
SZEZAPECTAN3ULARNLEI)
(1636 5/8 (930) L B-
PROVIDE 36" MINIMUM ACCESS
PER NEC RF„QoffUIREMENT
SENSOR -Cariertstsindardheartniltpepthailaysersorisstandationaltriswilticigialendwarrokccolds,
Ortt]7r1.1'IisMI1mcnids.
LINER- 12'(13TmMdualdenstyiteklizrtwihabodydadlyorl.5bshiFt
Rin ') 181art FPA 90A.Opicnat1"
(25trm)flickrodaltrimedirgsaneTecikationsas12'..Optionat i itstbbons1613m,1316etkig i
Malian -strps..Opticosi NoirerisUelich
systmArnoiri3nsinsiticnExbinairolirrisEcrmmeniedlopmentoncisusalicn
.41icnal:Celdarinsdalicrwsham,3fflhicklheirnatrulabonccnsislivofdosackelelastarettisdalionviAha
smoolhsubce.
.Cptiarlal:S9 26mlationl2ttl*blaiat pe,encteadoehmaenatcmat leetrretal
.CptilonatPetr dDatiewalins/aiorr23°/mal.
CASING ga‘mizEdsbE
MgejQ°/ (1.491ea)Pgecknat20C T.gAier v.
DAMPERASSEMBUES D/coharitalCFNIEC(1.49Pa)F
Size 4through 16
Size22 -T •: • .. S:V:01111rur-O:Z.rr 'u is Z. - ;S:
ELECTRIC HEATER -EFL Uste:1.1uuu W1 4
SystiTsaapecied. x:.120410,2061/10,
240410,277v10,2C6V3034the,.481n54-wieOpknEttneltuyochtezios,.iselloziehtfusestaprinay
aerbedprotscikrts sccrrEcts+ i1es,. .dtsEfi910oort�ulm
UNFTACCESSORIES -.0pionakingerbrarkets.opionalccrticIsequ2noas,saesirnttls.
35E WITH OPTIONAL ELECTRIC HEAT
INLET NOM MAX
SIZE CFM(Us) W H A B D C
4 230(109) 12(305) 8(203) 5 3/8(136) 5 15/16(151) 3 7/8(98) 2(51)
5 360(170) 12(305) 8(203) 5 3/8(136) 5 15/16(151) 4 7/8(124) 2(51)
6 515(243) 12(305) 8(203) 3 3/8(86) 5 15/16(151) 5 7/8(149) 2(51)
7 700(330) 12(305) 10(254) 3 3/8(86) 5 15/16(151) 6 7/8(175) 1(25)
NOTE: 8 920(434) 12(305) 10(254) 3 3/8(86) 5 15/16(151) 7 7/8(200) 1(25)
1. Righthandconfgurationshanm. 9 1160(547) 14(356) 12 1/2(318) 3 3/8(86) 3 15/16(100) 8 7/8(225)
Left hand is available. -
2 Dimensionsaregiven as inches(mm). 10 1430(675) 14(356) 12 1/2(318) 3 3/8(86) 3 15/16(100) 9 7/8(251) -
3. See Drawing 35E-202-1Cfor basic
unitirdormation. 12 2060(972) 16(406) 15(381) 3 3/8(86) 3 15/16(100) 11 7/8(302) -
4.
See Dra 1ng35E-202-11forcortrols 14 2800(1321) 20(508) 17 1/2(445) 3 3/8(86) 1 15/16(49) 13 7/8(352) -
specification data
5 Size 22 control enclosure 16 3660(1727) 24(610) 18(457) 3 3/8(86) 1 15/16(49) 15 7/8(403) -
325r8"(829mm)by 101/4"(260mm).
22 7000(3304) 38(965) 18(457) 4 1/4(108) - See Above 1 1/8(29)
PRODUCT INFORMATIONISSUBJECT TOCHANOEWTHOUT NOTICE. C6/1&2003
�,aR. R �� B .EET 35E-2024
Air Terminals Builder 2.09i Page 3 of 5
ti
Performance Summary For VAV Box
Project: —Untitled111 05/26/2016
Prepared By: 12:06PM
Unit Parameters
Tag Name VAV Box
Quantity. 1
Model Type' Analog Electronic Controls
Model. 35E Single Duct Terminals
Control Type' 2111:Analog Clg w/EH Auto Changeover
Unit and Inlet Size' 14 Inch
Part Number 35EA3300L140211100000S000000E6210.0K0000120006000600
Reheat Option' Electric Reheat
Outlet. 20x17.5
Unit Performance
Altitude' 0 ft
Max. Primary Airflow. 1,200.0 CFM
Min. Primary Airflow' 600.0 CFM
Inlet Static Pressure' 1.000 in wg
Downstream Static Pressure' 0.200 in wg
Minimum Static Pressure Drop' 0.041 in wg
Motor Voltage. 2111:Analog CIg w/EH Auto Changeover
Note' Inlet Static Pressure includes downstream pressure drop.
Electric Heating Coil Insulation:
Coil Airflow' 600.0 CFM Lining' Standard(1/2 inch Fiberglass Liner)
Capacity- 34.13 MBH Attenuator Yes
Entering Air Temp' 55.00 F
Leaving Air Temp' 107.67 F
Coil PD. 0.008 in wg
Voltage- 208-3-60
kW' 10.0 kW
Steps' 2
MCA. 34.70
MOCP. 35.0
Other Information: Acoustic Summary:
Maximum Airflow. 2,800.0 CFM Sound Power Levels, dB re 10E-12 watts
Design Airflow. 1,200.0 CFM Primary Airflow' 1,200.0 CFM
Safety Factor 57 %
Unit LxWxH' 39.5 x 20 x 18
Octave Bands(dB)
Radiated Sound 2 3 4 5 6 7 NC
Primary Sound(Pwl) 48 45 35 35 32 27
Total Attenuation 17 18 20 23 25 26
Room Sound Level(Spl) 31 27 15 12 < 10 < 10 13
Discharge Sound
Primary Sound(Pwl) 61 55 47 42 39 41 *
Total Attenuation 29 30 41 53 55 41 *
Room Sound Level(Spl) 32 25 < 10 < 10 < 10 < 10 11
Notes:
1. Room NC level shown Includes attenuation transfer functions obtained from tests In AHRI Standard 885.
2. Sound data obtained from test conducted in accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer,and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Air Terminals Builder 2.09i Page 4 of 5
Acoustics Summary For VAV Box
Project: —Untitled111 05/26/2016
Prepared By: 12:06PM
Unit Parameters
Tag Name. VAV Box
Quantity. 1
Model Type Analog Electronic Controls
Model. 35E Single Duct Terminals
Control Type- 2111:Analog CIg w/EH Auto Changeover
Unit and Inlet Size- 14 Inch
Part Number 35EA3300L140211100000S000000E6210.0K0000120006000600
Reheat Option Electric Reheat
Outlet' 20x17.5
Insulation: Other Information:
Lining- Standard (1/2 inch Fiberglass Liner) Maximum Airflow- 2,800.0 CFM
Attenuator Yes Design Airflow' 1,200.0 CFM
Safety Factor 57 %
Unit LxWxH• 39.5 x 20 x 18
Acoustic Summary:
Sound Power Levels, dB re 10E-12 watts
Primary Airflow. 1,200.0 CFM
Octave Bands(dB)
Radiated Sound 2 3 4 5 6 7 NC
Primary Sound(Pwl) 48 45 35 35 32 27
Total Attenuation 17 18 20 23 25 26 *
Room Sound Level (Spl) 31 27 15 12 < 10 < 10 13
Discharge Sound
Primary Sound(Pwl) 61 55 47 42 39 41 *
Total Attenuation 29 30 41 53 55 41 *
Room Sound Level (Spl) 32 25 < 10 < 10 < 10 < 10 11
Notes:
1. Room NC level shown includes attenuation transfer functions obtained from tests in AHRI Standard 885.
2. Sound data obtained from test conducted In accordante with AHRI Standard 880-11 and corrected for end reflection.
The results of this program are only an aid to the designer,and are not a substitute for professional services.
Carrier Corporation accepts no liability for the adequacy of any resulting design or installation.
All data subject to change without notice.
Air Terminals Builder 2.09i Page 5 of 5
•
RECEIVE[
JUN 16 2016
BRON s e- SPECiBa ftjl , ,T
LOSONE SELECT® 41, •
CEILING MOUNT VENTILATORSi
L100 SERIES & L150 SERIES
Incredibly reliable.Unbelievably quiet.Offering the CFM TYPICAL SPECIFICATION
choices you need atthe lowestsoundlevels intheindustry. Ventilator shall be Broan Model L100, (L100MG), (L150),
(L150MG).
FEATURES Ventilator shall have galvanized steel housing insulated with
GRILLE: at least 1/2"of acoustic insulation.Housing to have adjustable
• Conceals interior mounting brackets.
• Low profile styling blends with any decor Automatic backdraft damper to be located within duct
• White polymeric ("MG"models-metal,finished with connector.Duct connector,blower assembly and wiring plate
white painted enamel) shall be adjustable for either horizontal or vertical installation.
BLOWER: Blower unit shall be removable from housing and will have a
• Low for quiet operation polymeric, dynamically balanced centrifugal-type blower
• LowResRPMt for quiet on mounts wheel.Motor to be permanently lubricated and mounted with
resilient anti-vibration mounts. RPM not to exceed number
• Dynamically-balanced, polymeric, centrifugal blower listed for each model.
wheel for quiet, efficient performance
• Permanently lubricated, thermally protected motor Air delivery shall be less and sound levels greater than
• Plug-in motor rated at 120 VAC listed for each model.
. All air and sound ratings shall be
• Designed for continuous operation certified by AMCA.Units to be UL and cUL listed.
HOUSING:
• Rugged, 20 gauge galvanized steel
• 6" round duct connector rmca "— `Bruen-NuToneLLC certifies that
CERTIFIED the models shown herein are
• 1/2" acoustic insulation inside 8 111111 8 5 licensed to bear the AMCA Seal.
• May be installed in ceiling or wall (size permitting) I The ratings shown are based on
/OUnn tests and procedures performed
• 8-position mounting brackets for easy installation and in accordance with AMCA
greater adaptability to various mounting requirements �„pl>», Publication 211 (and AMCA
Publication 311 i1 sound Is also
• Automatic backdraft damper located within duct connector narrr•m certified) and comply with the
FiglOCOPIkert requirements or the AMCA
• Factory-shipped in horizontal discharge position-easily
Certified Ratings Program"
converted to vertical discharge
• May be installed as an in-line ventilator with addition of
accessory kit Model 961L (see"Accessories")
ACCESSORIES (purchase all separately):
• Model 57V(Ivory)/57W(White)Electronic Variable SpeedCI)
Control C CD)
• Model 59V(Ivory)/59W(White)60-Minute Time Control
• Model 61V(Ivory)/61W(White) 15-Minute Time Control Models L100 and L150 are
• Model 71V(Ivory)/71W(White) 12-Hour Time Control UL listed for use over
• Electronic Variable Speed Controls–Model 72V(120 VAC) bathtubs and showers when
• Model 961 L In-line Adapter Plate connected to a GFCI-
• Model RD1 Radiation Damper protected branch circuit.
• Model 80L Electronic Speed Control (Internal)
Broan-NuTone LLC,926 West State Street, Hartford,Wisconsin 53027(1-800-637-1453)
Broan-NuTone Canada, 1140 Tristar Drive, Mississauga,Ontario, L5T 1H9(1-888-882-7626)
REFERENCE QTY. REMARKS Project
Location
CEF1 & 2 2 100 @ .2" SP, MODEL L100 Architect
Engineer
Contractor
r
Submitted by Date
50J 99042731G
PERFORMANCE RATINGS - LOSONE SELECT®
CEILING MOUNT VENTILATORS .
L100 SERIES & L150 SERIES
AMCA LICENSED PERFORMANCE
CFM/SONES-AT STATIC PRESSURES (Ps-inches of H20)
MODEL NOMINAL 0.0" .10" .125" .250" .375" .50" .625" .750" .875" 1.0" NOMINAL AMPS WATTS
NO. VOLTAGE Ps Ps Ps Ps Ps Ps Ps Ps Ps Ps RPM 060 Hz
L100 120 VAC CFM Hor. 136 115 109 93 80 65 44 12 640 1.1 87
SONES Hor. 0.5 0.8 0.9 1.3 1.8 2.3 3.0 3.2
CFM Ver. 138 117 112 94 80 67 46 13 650 1.1 87
SONES Ver. 0.7 0.9 1.0 1.3 1.8 2.2 2.8 3.0
L1001410 tt!?if'AO arm 14,,,, 144 In 113 W 88 88 48 li Q30 1.1 D7
SONES Hor. 0.5 0.8 0.9 1.2 1.8 2.4 3.0 3.3
CFM Ver. 142 119 115 95 80 67 45 13 640 1.1 87
SONES Ver. 0.5 0.8 0.9 1.4 1.8 2.3 2.9 3.1
L150 120 VAC CFM Hor. 181 161 157 141 132 124 114 94 62 710 1.3 100
SONES Hor. 1.3 1.4 1.5 2.2 2.6 3.1 3.6 4.1 4.6
CFM Ver. 179 163 160 149 142 133 122 105 73 23 750 1.3 100
SONES Ver. 1.4 1.6 1.6 2.0 2.5 3.0 3.3 3.6 3.9 4.2
L150MG 120 VAC CFM Hor. 184 165 161 148 141 135 126 108 74 19 710 1.3 100
SONES Hor. 1.1 1.4 1.4 1.9 2.3 2.8 3.2 3.8 4.1 4.5
CFM Ver. 183 165 162 151 143 135 124 107 76 26 725 1.3 100
SONES Ver. 1.4 1.6 1.6 2.0 2.5 3.0 3.3 3.6 4.0 4.4
Performance ratings include the effects of inlet guile and backdraft damper In the airstream.Speed(RPM)shown is nominal.Performance is based on actual speed of test.The
sound ratings shown are loudness values in fan sones at 5'(1.5m)in a hemispherical free field calculated per AMCA Std.301.Values shown are for Installation Type B:Free inlet
fan sone levels.Performance shown is for Installation Type B:Free inlet,Ducted outlet.
1.00 -
AMCA -Broan-NuTone LLC certifies!hal
CERTIREO the models shown herein are li- 0.90
/MEMOS tensed to bear the AMCA Seal. (70.
The ratings shown are based on 0
lOUIIO tests and procedures performed in01 ^ 0.80 t,9�
.wpnip..<. accordance with AMCA Publica- C (I) 3 (7 SSS
tion 211 (and AMCA Publication • 0.70 0
AN
ISIO311 if sound is also certified)and Models L100 and L150 areZ+
anoconraor comply with the requirements
assatianon.tna, P Y of UL listed for use over w o eo ;
•,....-......,,°'a"' the AMCA Certified Ratings Pro- bathtubs and showers when a los
gram.' connected to a GFCI- a 0 so
protected branch circuit. ui
p�ND I �\ w a.4o
6''AOGT00 �Z- J<I F•t 030
Gp��EG1 . ` Hata
0cn
010
oQ
\\.
(I1 0.00 -
1 Q 0 20 40 60 80 100 120 140 160 180 200
POLYMERIC GRILLE - ` AIR FLOW RATE (C FM )
MODELS \ METAL GRILLE
^ / WEIGHT
L100 MODELS
L150 �� I,. 1A' ,1q. L100MG MODEL NO. SHIPPING WT.
� �\• 1<� '�� L150MG L100 22.8 lbs.
,-----%=.:----,-.--,--:.-...„ ��� L100MG 23.7 lbs.
• j� L150 23.7 lbs.
c:.
L150MG 23.7 lbs.
-,
B RIV} Broan-NuTone LLC,926 West State Street, Hartford,Wisconsin 53027(1-800-637-1453)
_ Broan-NuTone Canada, 1140 Tristar Drive, Mississauga,Ontario, L5T 1H9 (1-888 882-7626)
/