Loading...
Report (52) ,zOl c- c-)ooL1t ri p S(4� rn /r-it-t. 1 t RECEIVE Worldwide Contacts www.tyco-fire.com Fire Protection MAR 24 2015 Products CITY OF TIGARD Series TY-L — 5.6 and 8.aKtadtbi Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General rosive environment.The effects of am- bient temperature, concentration of Description chemicals, and gas/chemical velocity, should be considered, as a minimum, ' The TYCO Series TY L, 5.6 and 8.0 along with the corrosive nature of the ,' chemical to which the sprinklers will i- "' K-factor, Upright and Pendent Sprin- I klers described in this data sheet are be exposed. standard response -standard cover- An intermediate level version of the �' age, solder type spray sprinklers de- Series TY-L Pendent Sprinkler can be signed for use in light, ordinary, and obtained by utilizing the Series TY-L e extra hazard, commercial occupan- Pendent Sprinkler in combination with .,„. cies such as banks, hotels, shopping the Model S Shield. . . ' malls, factories, refineries, chemical ' plants, etc. NOTICE The recessed version of the Series The TYCO Series TY-L, 5.6 and 8.0 K- TY-L Pendent Sprinkler, where appli- factor, Upright and Pendent Sprinklers cable,is intended for use in areas with described herein must be installed a finished ceiling. It uses a two-piece and maintained in compliance with . --�. Style 20 (1/2 inch NPT) or Style 30 this document, as well as with the ap- ,....""'" } (3/4 inch NPT) Recessed Escutcheon. plicable standards of the National Fire 9 ,. I The Recessed Escutcheon provides Protection Association, in addition to ° � 1/4 in. (6,4 mm) of recessed adjust- the standards of any other authorities ( • m ment or up to 1/2 in. (12,7 mm) of to- having jurisdiction. Failure to do so tal adjustment from the flush pendent may impair the performance of these position. The adjustment provided by devices. / the Recessed Escutcheon reduces the accuracy to which the fixed pipe The owner is responsible for maintain ing their fire protection system and de- drops to the sprinklers must be cut. vices in proper operating condition. Corrosion resistant coatings, where The installing contractor or sprinkler applicable, are utilized to extend the manufacturer should be contacted life of copper alloy sprinklers beyond with any questions. that which would otherwise be ob- tained when exposed to corrosive at- Sprinkler mospheres. Although corrosion resis- tant coated sprinklers have passed the Identification standard corrosion tests of the appli- cable approval agencies,the testing is Number (SIN) not representative of all possible cor- rosive atmospheres. Consequently, it TY3111 Upright 5.6K, 1/2" NPT is recommended that the end user be TY3211 . . . .Pendent 5.6K, 1/2" NPT consulted with respect to the suitabil- TY4111 Upright 8.0K, 3/4" NPT 1 ity of these coatings for any given cor- TY4211 Pendent 8.0K,3/4" NPT TY4811 Upright 8.0K, 1/2" NPT IMPORTANT TY4911 . . . .Pendent 8.0K, 1/2" NPT Always refer to Technical Data TY3111 is a re-designation for S1800 Sheet TFP700 for the "INSTALLER and G3111. WARNING" that provides cau- TY3211 is a re-designation for S1801 tions with respect to handling and G3112. and installation of sprinkler sys- TY4111 is a re-designation for S1810 tems and components. Improp- and G3101. v er handling and installation can TY4211 is a re-designation for S1811 permanently damage a sprin- and G3102. kler system or its components TY4811 is a re-designation for S1805. 1 and cause the sprinkler to fail TY4911 is a re-designation for S1806. to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 MAY 2014 TFP11O TFP11O Page 2 of 6 M 7 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Ejection 5 - Strut is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Sealing Spring 6 - Hook Deflector. special request. PLATE SEATING Button 4 - Fusible 7 - Deflector* SURFACE Element 1 4/1111.r," W -= WRENCH 372 5/8" AREA t 2 4 (66,7 mm) •ig � �� A 7/16" rte, (66,7 mm) ��, 3 .�i�._ (11,1 mm) 11, IL1II �.�i:MAKE NNOMINAL 2 STYLE 20 ; 5 (50,8 mm) RECESSED %, -.-- Ill. ESCUTCHEON t j 1/2" NPT** I WRENCH 2-7/8"(73,0 mm)DIA. 7* FLANGES UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION FIGURE 1 STANDARD RESPONSE SERIES TY-L UPRIGHT(TY3111)AND PENDENT(TY3211)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Ejection 5 - Strut is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Sealing Spring 6 - Hook Deflector. special request. PLATE SEATING Button 4 - Fusible 7 - Deflector* SURFACE Element nt __� E WRENCH2-11/16" �� AREA 92 (68,3 mm) - 2-11/16" 4. (12,7 mm) I�=I 71 (68,3 mm) I�, 3NOMINAL MAKE- 2�� STYLE 30 1I (50,8 mm) RECESSED ; ESCUTCHEON % / ' Az.; .. • --- •--- • --.. -.. 6 3/4" NPT** } WRENCH 2-7/8"(73,0 mm)DIA. 7* FLANGES UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION FIGURE 2 STANDARD RESPONSE SERIES TY-L UPRIGHT(TY4111)AND PENDENT(TY4211)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT q 1 TFP11O r Page 3 of 6 A- *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Ejection 5 - Strut is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Sealing Spring 6 - Hook Deflector. special request. PLATE SEATING Button 4 - Fusible 7 - Deflector* SURFACE Element 1 ( 1" MWRENCH2 2-5/81.r� AREA(66,7 mm) I7/16" � .1 2-5/8" i _�l� (11.1 mm) � (66,7 mm)NOMINAL 2"MAKE-IN STYLE 20" (50,8 mm) RECESSED —II ESCUTCHEON "/ 6 \ I II 11111 * 1/2" NPT** f WRENCH 2-7/8"(73,0 mm)DIA. 7 FLANGES UPRIGHT PENDENT RECESSED PENDENT CROSS SECTION FIGURE 3 STANDARD RESPONSE SERIES TY-L UPRIGHT(TY4811)AND PENDENT(TY4911)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT Technical Design Series TY-L Pendent and Upright 7 Sprinkler Installation Data Criteria The Series TY-L Pendent and Upright Sprinklers must be installed in accor- Approvals The TYCO Series TY-L, 5.6 and 8.0 K- dance with this section. factor,Upright and Pendent Sprinklers Step 1. Pendent sprinklers are to be UL and C-UL Listed. FM, and LPCB are intended for fire protection sys- installed in the pendent position, and Approved. (Refer to Table A for corn- tems designed in accordance with the plete approval information including standard installation rules recognized Step 2. With pipe thread sealant ap- corrosion resistant status.) by the applicable Listing or Approv- plied to the pipe threads, hand tighten Maximum Working Pressure al agency (e.g., UL Listing is based the sprinkler into the sprinkler fitting. 175 psi(12,1 bar) on the requirements of NFPA 13, and Step 3. Tighten the sprinkler into the FM Approval is based on the require- sprinkler fitting using only the W-Type Discharge Coefficient ments of FM's Loss Prevention Data 9 Sprinkler rinkler Wrench (Ref. Figure 7), ex- K=5.6 GPM/psi1/2(80,6 LPM/bar1/2) Sheets). Only the Style 20 or 30 Re- cept that an 8 or 0 inch had adjustable K= 8.0 GPM/psi112(115,2 LPM/bar1/2) cessed Escutcheon, as applicable, Crescent wrench is to be used for Temperature Ratings are to be used for recessed pendent wax coated sprinklers. With reference i Refer to Table A installations. to Figures 1, 2, and 3, the W-Type 9 Sprinkler Wrench is to be applied to Finishes Sprinkler: Refer to Table A Recessed Installation the wrench area, or as applicable, the adjustable Crescent wrench is to be Escutcheon: White Coated, Chrome The TYCO Series TY-L, 5.6 and 8.0 K- applied to the wrenching flanges. Plated, or Brass Plated factor,Upright and Pendent Sprinklers When installing wax coated sprinklers Physical Characteristics must be installed in accordance with with the adjustable Crescent wrench, Frame Brass this section: additional care needs to be exercised Sealing Button Bronze A leak tight 1/2 inch NPT sprinkler to prevent damage to the wax coating w/TEFLON joint should be obtained with a torque on the sprinkler wrench flats or frame Ejection Spring Stainless Steel of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). A arms and, consequently, exposure of Fusible Element Solder,ss St Copper, leak tight 3/4 inch NPT sprinkler joint bare metal to the corrosive environ- StrutStainless Steel 9 p � Monel should be obtained with a torque of 10 ment. The jaws of the wrench should Hook Bronze/Monel to 20 ft.-lbs. (13,4 to 26,8 Nm). Higher be opened sufficiently wide to pass Deflector Bronze levels of torque may distort the sprin- over the wrench flats without damag- Oeration kler inlet and cause leakage or impair- ing the wax coating. Before wrench p ment of the sprinkler. tightening the sprinkler,the jaws of the A copper tube sealed by two stainless Do not attempt to make-up for insuf wrench are to be adjusted to just con steel balls holds a fusible alloy. When ficient adjustment in the escutcheon tact the sprinkler wrench flats. After the rated temperature is reached, the plate by under- or over-tightening the wrench tightening the sprinkler, loos alloy melts, the balls are forced to- sprinkler. Readjust the position of the en the wrench jaws before removing ward each other releasing the tension sprinkler fitting to suit. the wrench. mechanism, allowing the sprinkler to After installation, the sprinkler wrench operate. flats and frame arms must be inspect- ed and the wax coating retouched (repaired) whenever the coating has TFP110 Page4of6 '► Frame Sprinkler Finish K Type Rating Color Natural Chrome Lead Wax Wax Over Code Brass Plated Coated Coated Lead Coated Pendent(TY3211) 165°F(74°C) Unpainted 1,2,3 and 212°F(100°C) White 1,2,3,5 5.6 Upright(TY3111) 1/2" 280°F(138°C) Blue 1,2 4 N/A NPT 165°F(74°C) Unpainted 1,2,3,5 Recessed Pendent N/A (TY3211 w/Style 20) 212°F(100°C) White 1,2,3,5 165°F(74°C) Unpainted 1,2,3 Pendent(TY4211) 212°F(100°C) White 1,2,3 280°F(138°C) Blue 1,2 4 N/A 8.0 165°F(74°C) Unpainted 3/4" 1,2,3 NPT Upright(TY4111) 212°F(100°C) White 1,2,3,5 280°F(138°C) Blue 1,2 4 N/A Recessed Pendent 165°F(74°C) Unpainted (TY4211 w/Style 30) 212°F(100°C) White 1,2,5 N/A Pendent(TY4911) 165°F(74°C) Unpainted 1 2 3 and 212°F(100°C) White 1,2,3,5 � , Upright(TY4811) 280°F(138°C) Blue 1,2 N/A NPT Recessed Pendent 165°F(74°C) Unpainted (TY4911 w/Style 20) 212°F(100°C) White 1,2 N/A NOTES: 1. UL Listed 2. C-UL Listed 3. FM Approved 4. FM Approved for maximum 150°F(68°C)ambient temperatures 5. LPCB Approved(LPCB Ref.No.094a/03) N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS been damaged and bare metal is the time of initial sprinkler installation. Step C. After the ceiling has been in- exposed. The wax coating on the With the steel rod heated as previ- stalled or the finish coat has been ap- wrench flats can be retouched by gen- ously described, touch the rod to the plied, slide on the Style 20 or 30 Clo- tly applying a heated 1/8 in. diameter area requiring additional wax with the sure over the Series TY-L Sprinkler steel rod to the areas of wax that have rod angled downward,and then touch and push the Closure over the Mount- been damaged,to smooth it back over the wax stick to the rod approximately ing Plate until its flange comes in con- areas where bare metal is exposed. one-half inch away from the area re- tact with the ceiling. quiring retouching. The wax will melt NOTICE and run down onto the sprinkler. Only retouching of the wax coating Series TY-L Recessed Pendent applied to the wrench flats and frame Sprinklers Installation arms is permitted, and the retouching The Series TY-L Recessed Pendent is to be performed only at the time of Sprinklers must be installed in accor- the initial sprinkler installation. dance with this section. The steel rod should be heated only to Step A. After installing the Style 20 the point at which it can begin to melt or 30 Mounting Plate, as applicable, the wax, and appropriate precautions over the sprinkler threads and with need to be taken, when handling the pipe thread sealant applied to the pipe heated rod, in order to prevent the in- threads, hand tighten the sprinkler into staller from being burned. the sprinkler fitting. If attempts to retouch the wax coat- Step B. Tighten the sprinkler into the ing with complete coverage are un- sprinkler fitting using only the W-Type successful, additional wax can be or- 10 Recessed Sprinkler Wrench (Ref. dered in the form of a wax stick (the Figure 8). With reference to Figure end of which is color coded). Only 1, 2, or 3, the W-Type 10 Recessed the correct color coded wax is to be Sprinkler Wrench is to be applied to used, and retouching of wrench flats the sprinkler wrenching flanges. and frame arms is only permitted at TFP11 O ., Page Page 5 of 6 7/16±1/8" 2-7/8"DIA. _ 1/2"(12,7 mm) - (11,1±3,2 mm) (73,0 mm) 1/4"(6,4 mm) t FACE OF 2-1/4" DIA. j MOUNTING WRENCH SPRINKLER (57,2 mm) PLATE RECESS FITTING 1/8" 2Y( / ,-7---------- / 1 (3,2 mm) \ r -1�� `i MOUNTING litIJ f FIGURE 7 SURFACE 1-3/4"(44,5 mm) W-TYPE 9 SPRINKLER 1 1/2"(38,1 mm) WRENCH CLOSURE TY-L _-0 j WRENCH FIGURE 4 RECESS SERIES TY-L(TY3211)RECESSED PENDENT SPRINKLER ASSEMBLY 11:F WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT �' 7/16±1/8" 2-7/8"DIA. 1/2"(12,7 mm) - (11,1±3,2 mm) (73,0 mm) 1/4"(6,4 mm) FIGURE 8 FACE OF 2-1/4" DIA. MOUNTING W-TYPE 10 RECESSED SPRINKLER (57,2 mm) PLATE SPRINKLER WRENCH FITTING -( I 1/8" / _ ' = (3,2 mm) Care and f \ = -ft--.4= Maintenance MOUNTING 1'.tIJ 1 I f The TYCO Series TY-L,5.6 and 8.0 K- SURFACE 1-3/4"(44,5 mm) factor, Upright and Pendent Sprinklers 1 1/2"(38,1 mm) must be maintained and serviced in accordance with this section. CLOSURE TY-L ._- a __ Before closing a fire protection sys- tem• FIGURE 5 main control valve for mainte- SERIES TY-L(TY4211)RECESSED PENDENT SPRINKLER ASSEMBLY Hance thatitwocon the fire ppermission to shut tern it controls, permission to shut WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT down the affected fire protection sys- STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR, 3/4 INCH NPT tern must be obtained from the prop- er authorities and all personnel who 7/16±1/8" 2-7/8" DIA. 1/2"(12,7 mm) may be affected by this action must - (11,1±3,2 mm) (73,0 mm) 1/4"(6,4 mm) be notified. FACE OF 2-1/4" DIA. MOUNTING Absence of an escutcheon, which is SPRINKLER (57,2 mm) 1 PLATE used to cover a clearance hole, may FITTINGdelay the time to sprinkler operation in / [___- 1/8" a fire situation. (3,2 mm) Sprinklers that are found to be leaking c� j or exhibiting visible signs of corrosion i����' must be replaced. \U .• } Automatic sprinklers must never be -,------ __.. MOUNTING ��� painted, plated, coated or otherwise SURFACE 1 )J 1-3/4" (44,5 mm) 1-1/2"(38,1 mm) altered after leaving the factory. Modi- fied or over-heated sprinklers must be replaced. Care must be exercised to CLOSURE TY-L ._ avoid damage to the sprinklers -be- FIGURE 6 fore, during, and after installation. SERIES TY-L(TY4911)RECESSED PENDENT SPRINKLER ASSEMBLY Sprinklers damaged ipby ge, or droppthe WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT striking, wrench twist/slippage, or the A STYLE 20 RECESSED ESCUTCHEON 8.0 K-FACTOR, 1/2 INCH NPT like, must be replaced. Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant coated sprin- klers, after the installation has been TFP110 Page 6 of 6 ik.. ,. P/N 53 - XXX - X - XXX r SIN SPRINKLER TEMPERATURE FINISH RATING 111 5.6K UPRIGHT(1/2"NPT) TY3111 1 NATURAL BRASS 165 165°F(74°C) 112 5.6K PENDENT(1/2"NPT) TY3211 6 WAX COATED 212 212°F(100°C) 165°F TO 280°F ONLY 101 8.0K UPRIGHT(3/4"NPT) TY4111 7 LEAD COATED 280 , 280°F(138°C) 102 8.0K PENDENT(3/4"NPT) TY4211 8 WAX OVER LEAD 165°F TO 212°F ONLY 106 8.0K UPRIGHT(1/2"NPT) TY4811 9 CHROME PLATED 107 8.0K PENDENT(1/2"NPT) TY4911 TABLE B SERIES TY-L PENDENT AND UPRIGHT SPRINKLERS PART NUMBER SELECTION completed,to verify the integrity of the Sprinkler Wrench corrosion resistant coating. Thereaf Ordering ter, annual inspections per NFPA 25 Specify: W-Type 9 Sprinkler Wrench, should suffice; however, instead of in- Procedure P/N 56-000-1-849 specting from the floor level,a randomContact your local distributor for avail Specify: W-Type 10 Sprinkler Wrench, sampling of close-up visual inspec- P/N 56-000-1-948 tions should be made, so as to better ability. When placing an order, indi- determine the exact sprinkler condi- cate the full product name and Part Wax Sticks(for retouching wrench tion and the long term integrity of the Number(P/N). damaged wax coating) corrosion resistant coating, as it may Sprinkler Assemblies with NPT Specify: Series TY-L Sprinklers, be affected by the corrosive condi- Thread Connections (specify color), color coded Wax Stick tions present. Specify: Series TY-L (specify SIN), for retouching, (specify) temperature The owner is responsible for the in- (specify K-factor), (specify Upright, rated, P/N (specify): spection, testing, and maintenance Pendent, or Recessed Pendent) Red for 165°F(74°C) P/N 56-065-1-155 of their fire protection system and de- Sprinkler, Standard Response, Stan- Blue for 212°F(100°C)and 280°F(138°C) vices in compliance with this docu- dard Coverage, (specify) temperature P/N 56-065-1-286 ment, as well as with the applicable rating, (specify) finish or coating, P/N NOTES: standards of the National Fire Pro- (specify from Table B) Each wax stick is suitable for retouch- tection Association (e.g., NFPA 25), in Recessed Escutcheon ing up to twenty-five sprinklers. addition to the standards of any oth- er authorities having jurisdiction. The Specify: Style (specify) Recessed Es- The wax used for 280°F(138°C)sprin- installing contractor or sprinkler man- cutcheon with (specify finish), P/N kers is the same as for 212°F(100°C) ufacturer should be contacted relative (specify): sprinklers, and, therefore, the 280°F to any questions. 1/2"(15 mm) (138°C)sprinkler is limited to the same Style 20 maximum ceiling temperature as the It is recommended that automatic Brass Plated P/N 56-705-2-010 212°F (65°C)). 12 (100°C) sprinkler (i.e., 150°F sprinkler systems be inspected, test 1/2"(15 mm) ed, and maintained by a qualified In- Stylm 20 spection Service in accordance with Signal White(RAL9003) local requirements and/or national P/N 56-705-4-010 codes. 1/2"(15 mm) Style 20 Limited Chrome Plated P/N 56-705-9-010 3/4"(20 mm) Warranty Style 30 Brass Plated P/N 56-705-2-011 For warranty terms and conditions, 3/4"(20 mm) visit www.tyco-fire.com. Style 30 Signal White(RAL9003) • P/N 56-705-4-011 3/4"(20 mm) Style 30 Chrome Plated P/N 56-705-9-011 ' GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products, LP. All rights reserved. Vico TEFLON is trademark of The DuPont Corporation Fire Protection Products