Report RECEIVED
ED
LIYORICJUN Y 2016
It's time to get comfortable. Bu,L0/NG GARD
DIVISION
SUBMITTAL DATA
For: Approval
Order#: Date: 05/10/2016
Project: PIZZA CABOOSE
Project#: TSJ05102016-05
Location: OREGON
Purchaser: CALIBER MECH- DAN
Submitter: YORK NW-TYLER
CITY OF TIGARD
REVIEWED FOR CODE COMPLIANCE
Approved: [
OTQ [
Permit#: aCi4 —09
Address: Ilti7c) kir z-Fa-r lhw-t
Suite#:
Br .�....�...� Date= e f /l f
OFFICE COPY
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
Date
05/10/2016
Project Name YORK®
PIZZA CABOOSE
Project Number It's time to get comfortable.
TSJ05102016-05
Client/Purchaser
CALIBER MECH-DAN
Submittal Summary Page
Qty Tag# Model# Description
1 D7NQ060N11006NXY 5 Ton Single Stage, York Affinity Single Packaged R-410A Air
Conditioner, 14.0 SEER/ 12.0 EER, Microchannel Condenser Coil,
108 MBH Output Single Stage Aluminized Steel Natural Gas Heat,
208/230-1-60
• LowNOx with York Corner Post
1 MM-838DNZ2460HEC ECONOMIZER,HORIZ,AFFINITY
1 S1-2EC06700124 Transformer Kit
Equipment and commissioningbya factorytrained technician is recommended.
start-up
Contact your supplying distributor or sales representative for additional information &guidance.
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
• -
• If ® Affinity Page:3
IORK DNQ-14 SEER Single Pkg.G/E R-410A YAC
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Cooling Performance
Total capacity 56.5 MBH
Sensible capacity 442 MBH sr.''
Refrigerant type R-410A ;
Seasonal Efficiency(at ARI) 14.00 SEER :gg_.Ig .-.,..gEfficiency(at ARI) 12.00 EER =
Ambient DB temp. 95.0 °F
Entering DB temp. 80.0 °F
Entering WB temp. 67.0 °F
Leaving DB temp. 59.5 °F
Leaving WB temp. 58.2 °F
Power input 4.00 kW
Sound power 81 dB(A)
Gas Heating Performance
Entering DB temp. 60 °F
Heating output capacity(Max) 107 MBH .."`
Supply air 2000 CFM
Ext.static pressure 0.6 IWG
Heating input capacity(Max) 135 MBH 5 Ton
Duct location Bottom • YORK Affinity Series Units are Manufactured at an ISO 9001 Registered
DB temp. 118.3 °F
Air temp.rise 58.3 °F Facility and Each Rooftop is Completely Computer-Run Tested Prior to
Air
AFUE 81.0 % Shipment.
Stages 1 Unit Features
Supply Air Blower Performance • Unit Cabinet shall be Constructed of G-90,Pre-Paint Textured Steel,
Supply air 2000 CFM Certified at 500 Hours Salt Spray Test per ASTM-B117 Standards
Ext.static pressure 0.6 IWG • Bottom and Side Electrical and Gas Utility Connections
Duct location Bottom • Easy Access to all Components
Motor rating 1.00 HP
Power input 1.13 kW • Single Piece Water-Shed Top Cover and Drip Edge
Elevation 0 ft. • Field Convertible Duct Connections from Horizontal to Downflow Allows
Drive type DIRECT Greater Flexibility
Speed tap COOL-D • Full Perimeter,Removable Base Rails with Built in Rigging and Access
_ Electrical Data Provisions
Power supply 230-1-60 • Non-Corrosive Condensate Pan Internally Sloped to Meet Strict
Unit min circuit ampacity 43.2 Amps Requirements of ASHRAE 62-89 Indoor Air Quality Standard
Unit max over-current protection 60 Amps • Scroll Compressor
Dimensions&Weight • Advanced Microchannel Technology Used on Cooling and Gas Units.High
Hgt 42 in. Len 49 in. Wth 49 in. Efficiency Rifled Tube with Enhanced Fin Used on Evaporator Coils and
Weight with factory installed options 530 lbs. Select OD Coils.
Clearances • Compressor is Internally Protected Against high Pressure and Temperature
Right 24 in. Front 12 in. Back 0 in. • Standard Cooling Operation Down to 45°F
`op 36 in. Bottom 0 in. Left 24 in. / • Variable Speed Direct Drive High Static Motor and Slide out Blower
Note: Please refer to the tech guide
for listed maximum static pressures Assembly
arr
Ilia ; � „ii. 7�,�Lv) ^'��"°"`'° •Ext ended Ten(10)Year Limited Parts Warranty when product is registered
us /.:-. online within 90 days of purchase for replacement or closing for new home
construction.This Warranty does not apply for R-22 or 3-Phase Systems.
• Ten(10)Year Compressor Warranty
• Twenty(20)Year Heat Exchanger Warranty on Residential Applications/Ten
(10)Year Heat Exchanger Warranty on All Other Applications
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
inity
- YORK® DNQ-14 SEER SSiinglee Pkg.G/E R-410A YAC Page:4
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Factory Installed Options
D7NQ060N11006NXY
1
Product Category: D York Affinity Single Packaged R-410A Air Conditioner
Product Generation: 7
Product Identifier: NQ 14.0 SEER/12.0 EER
5 Ton Single Stage
Nominal Cooling Capacity: 060
Microchannel Condenser Coil
Heat Type and Capacity: N 110
108 MBH Output Single Stage Aluminized Steel Natural
Voltage: 06 208/230-1-60.
Additional Options: N Y' LowNOx with York Corner Post
Field Installed Accessories
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
YORKA® Affinity Page:5
ffinity DNQ-14 SEER Single Pkg.G/E R-410A YAC
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Typical Application
Unit Typical Duct Applications
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
4-, .,: .„ii:i:i:i
I 1
"c"—: I I 1 _
•
- i —
1 i +---'.. 1)
I I I 1
1 1 1 l
SLAB ON GROUND
INSTALLATION
Roof Curb Cross Section
3/4"x 1"WIDE GASKETING FOR CURB FRAME
AND ALL DUCT SUPPORT SURFACES
UNIT BASE
• 3lli -UNIT BASE RAIL
WOOD NAILER--
COUNTERFLASHING
8'MIN.ABOVE FINISHED ROOF------- ;-� /�
I t
fil
;ttt
stt
14'
I ':ri's°
1 CANT STRIP
:tt
CURB FRAME - 1 -i$1' f INSULATION AND ROOFING MATERIAL
I it
INSULATION
i I I /4
1\ 4
ROOF DECK AND ROOFING MATERIAL
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
•
• ' aYORK® Affinity Page:6
DNQ-14 SEER Single Pkg.G/E R-410A YAC
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Roof Curb Typical Application
Unit Typical Roof Curb Installation (Gas Model Shown)
MANUAL GAS
SHUT-OFF VALVE
_........„..../- ripir . 4 4 4 ..... . ...„. „,
------,..„.„..,„
FIELD SUPPLIED 8
DISCONNECT SWITCH yI m y
MOUNTED ON UNIT \\T *73
/
I I
,
8
ll , r ,'��o
TO POWER 10 ilili11111111111111111 111
SUPPLY 1 1111111111111'1
111
111111
TO GAS
SUPPLY LINE
CONTROL WIRING TO
INDOOR THERMOSTAT RETURN T3.
AIR DUCT
SUPPLY
AIR DUCT
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
•
• - . yOligRK® Affinity Page:7
DNQ-14 SEER Single Pkg.G/E R-410A YAC
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Roof Curb On Ground Installation
Unit Typical Slab on Ground Installation (Gas Model Shown)
FIELD SUPPLIED TO POWER SUPPLY CONTROL WIRING TO
DISCONNECT SWITCH INDOOR THERMOSTAT
LOCATED TO REAR OF UNIT /
c� /� RETURN AIR
\-
DUCT
-.••••••\ ----' 0 SUPPLY AIR
DUCT
TO GAS :00. � 1) .
'
SUPPLY LINE
0 ,
j .?'fe., N Aporokr
,-.L.. N N ,.
./
.s,,,, Iiii.„.1c== '
0,.1
MANUAL GAS o
SHUT-OFF VALVE o
N ,. , ••/00
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
. .
•
" rayoRK® Affinity Page:8
DNQ-14 SEER Single Pkg.G/E R-410A YAC
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Dimensions&Clearances
Gas Unit Dimensions
VENT AIR OUTLET HOOD
GAS SUPPLY BLOWER SERVICE ACCESS
1-1/4"DIAMETER HOLE COMPARTMENT PANEL CONDENSER COIL
(1/2"NPTF CONNECTION)
llr�i1
UNIT CONDENSATE (l`�t„`t!
CONNECTION 3/4"NPTF 4-----.... ```...._ ��J A
(TRAP RECOMMENDED) - �
/ ;;;
B , 2-3/8
•::::!:
CONN.1-3/8"DIA. + 4
.HIGH VOLTAGE
` ��;-
KNOCKOUT .'- Illr-- Al
� ) 0 '
REFRIGERANT
2-1/2 4� CONNECTIONS
It t COMBUSTION AIR
GAS SUPPLY `� ,
�� INLET LOUVERS
1-1/4"DIA.KNOCKOUT `\� ,�'l ; 'V
1/2"NPTF CONNECTION) ATV's-4°- FRONT
LOW VOLTAGE I���5 3/8
CONN.1-3/8"DIA. 1-1/2 GAS/ELECTRIC CONTROL
KNOCKOUT x 7/8"HOLE 11 12-3/4 SERVICE ACCESS
47-1/4 49-1/8 COMPARTMENT PANEL
(OVERALL)
(OVERALL) 3-1/3 N 2.5/8
Gas Unit Dimensions
Unit Size Dimensions
'A" „B„
024,030,0361 33-1/2 18-1/4
0362, 042,048,060 41-1/2 23-1/8
1. DNQ,DNZ Models.
2. DNX Models.
Gas Unit Clearances1 2
Direction Distance Direction Distance
(in.) (in.)
Top' 36 Right • 12
Front 36 Left 24
Rear 0 Bottom4 0
1. A 1"clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3. Units must be installed outdoors.Over hanging structure or shrubs should not obscure condenser air
discharge outlet.
4. Units may be installed on combustable floors made from wood or class A,B or C roof covering
materials.
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
• r - rayORK® fiff//�/�/ Page:9
DNQ-14 SEER Single Pkg.G/E R-410A YAC
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Unit Dimensions
Unit Dimensions Front and Bottom
0
0
N 1-7/819-1/4
HIGH VOLTAGE p 8-7/8 '
CONN. 1-3/32" d
DIA.KNOCKOUT lit- F
'' RONT
` GAS SUPPLY 1-5/8"
l ___.---DIA.KNOCKOUT(1/2"
� -4:- .41111�`t NPTF CONNECTION)
LOW VOLTAGE P�
CONN.7/8"DIA. R, f \ 4
moo. I,
KNOCKOUT
LOW VOLTAGE
KNOCKOUT �\i; CONN.7/8"DIA.
HIGH VOLTAGE ��'0 \ \ �e�l KNOCKOUT
CONN.1-31/32"x 7/8" %� Nr �
KNOCKOUT N. ,I VT,- \N .7
\�
, dige 2-5/8
CONDENSATE �1:` o
DRAIN 3/4"NPTF
lj
Of
-1/2 26-3/4 7
43-112NX NsN22-112
NN‘N. ,7" V
Unit Dimensions Back and Bottom SIDE SUPPLY 14-1/2
AIR OPENINGN.
CONDENSER 28-3/8
COIL `� ls 1410ti. BACK
BOTTOM SUPPLY ���� \AIR OPENING �% 3/8
e'% �/ 1 NO \ AIR OPEN NG
N
11/ 1.--1," 7"
14-112
C
/�` N0 4 '4-1/4
1-3/4 ` c •� 15 f 1
N.
`' 1544 ,4e. 1-3/4
\ \ BOTTOM RETURN
28-9/16 / 171/ AIR OPENING
// /1-3/4
f
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
. ,
. .
•
✓ YORK® Affinity Page: 10
DNQ-14 SEER Single Pkg.G/E R-410A YAC
Project Name: PIZZA CABOOSE Unit Model#: D7NQ060N11006NXY
Quantity: 1 System: D7NQ060N11006NXY
Sound Performance
Sound Performance
Outdoor Sound Power Levels
Size Model Sound Rating Octave Band Centerline Frequency(Hz)
(Tons) dB(A) 125 250 500 1000 2000 4000 8000
024 DNZ 77 64 65.5 68 72.5 64.5 60.5 48.5
(2.0) • DNQ 80 66 70.5 74 74.5 72.5 67.5 64.5
DNX 80 66 70.5 74 74.5 72.5 67.5 64.5
030 DNZ 74 63.5 64.5 66.5 67 63 57.5 51.5
(2.5) DNQ
DNZ 74 66.5 66.5 69.5 68 63 59 49.5
036 DNQ 79.5 69 71.5 74 74 70.5 67 61
(3.0) DNX 80 70.5 71 74.5 74 71 67.5 64
042 DNZ 79 70 70.5 73.5 73 69.5 67 66
(3.5) DNQ
DNZ 79 70.5 71 73.5 73 70 66 66
048 DNQ 80 71.5 71.5 73.5 74 69.5 65 63.5
(4.0)
DNX 81 72.5 73 76 1 75.5 71 67.5 65
060 DNZ 80 73 71.5 74.5 75 70.5 67 62.5
(5.0) DNQ 81 73.5 73 76 75.5 71 66.5 61.5
1. Rated in accordance with ARI 270 standard.
Unitary Sales Tool v1.5.9.0 Information is subject to change without notice.Check local codes. Printed 05/10/2016
r ,. ---.' (......c, V i 0
• Model 580D
• I b r y a n tl S NGCOMIE PACKAGE ROOFTOPERCIAL Sizes 036-150
SAPP
BUILDING DIVISION 121/2 Tons
®
GAS HEATING/ELECTRIC COOLING
JUN 1 2016
CITY OF TIGARD
_ .__..._.---_-_.. ___..___.__.__.__.______
II 1 rill1W--- .....Mik„,_,
IT--------:
* LqOMIIIIPPIIII1____t--..---- -------1-____---
,.....211.1.1.57 .1^- :---------- -
580D036-072 580D090-150
Standard-Efficiency Rooftop Units with: QUIET, EFFICIENT OPERATION AND DEPENDABLE PER-
• Exclusive integrated gas control board with diagnostics FORMANCE—Compressors have vibration isolators for quiet
• AlumagardTM heat exchanger coating operation. Efficient fan and motor design permits operation at
• Induced-draft fan for gas combustion low sound levels and all 580D units are mounted either on
• Tubular,dimpled heat exchangers mounting plate (036-072) or on an exclusive polycore plate
• Pre-painted galvanized steel cabinet for long life and quality (090-150).
appearance The 580D090-150 units offer lower utility costs through part-
• Commercial strength base rails with built-in rigging capability load operation using 2 stages of cooling.
• Convertible design to horizontal supply/return Quiet and efficient operation is provided by belt-driven evapo-
• Non-corrosive, sloped condensate drain pan, meets rator fans (standard on all units over 5 tons). The belt-driven
ASHRAE 62(IAQ) evaporator-fan is equipped with variable-pitch pulleys which
• Two-inch return-air filters allow adjustment within the rpm ranges of the factory-supplied
• A wide assortment of factory-installed options available pulleys.
FEATURES/BENEFITS Increased operating efficiency is achieved through computer-
designed coils featuring staggered internally enhanced copper
Every compact one-piece unit arrives fully assembled, tubes. Fins are ripple-edged for strength, lanced, and double
charged,tested,and ready to run. waved for higher heat transfer.
INTEGRATED GAS CONTROLLER (IGC)—All ignition corn- Tubular, dimpled gas heat exchangers optimize heat transfer
ponents are contained in the compact IGC which is easily for improved efficiency. The tubular design permits hot gases
accessible for servicing. The IGC control board, designed and to make multiple passes across the path of the supply air. The
manufactured exclusively for rooftop units, provides built-in dimpled design creates a turbulent gas flow to maximize heat-
diagnostic capability. An LED (light-emitting diode) simplifies ing efficiency.
troubleshooting by providing visual fault notification and system The California Air Quality Management Districts NOx require-
status confirmation. ment of 40 nanograms/joule or less is met when Low NOx Kit
The IGC also contains an exclusive anti-cycle protection for CRLOWNOX001A00 is installed on 036-060 sizes.
gas heat operation. After 4 continuous cycles on the unit high- The extra thick AlumagardTM heat exchanger coating provides
temperature limit switch, the gas heat operation is disabled, corrosion resistance and ensures long life.
and an error code is issued. This feature greatly improves reli-
ability of the rooftop unit. The unsightly appearance of flue stacks is eliminated and the
effects of wind on heating operations are diminished by the
The IGC also contains burner control logic for accurate and induced draft combustion system. The inducer fan draws hot
dependable gas ignition. The LED is visible without removing combustion gas through the heat exchanger at the optimum
the unit control box access panel. This LED fault-notification rate for the most effective heat transfer. The heat exchanger
system reduces service person troubleshooting time and mini- operates under negative pressure, preventing flue gas leakage
mizes service costs. The IGC also maximizes heating effi- into the indoor supply air.
ciency by controlling evaporator-fan on and off delays.
Form No. PDS 580D.36.9
•
• During the Heating mode, the evaporator-fan relay automati- SIMPLE ELECTRICAL CONNECTIONS — Terminal boards,
cally starts the evaporator fan after the heat exchanger warms located in the base unit control box, facilitate connections to
up to a suitable temperature.The 30-second fan delay prevents room thermostat, outdoor thermostat(s), and economizer. Ser-
. cold air from entering the supply duct system when the condi- vice panels are quickly removed,permitting easy servicing.
tioned space is calling for heat to maximize efficiency. Thru-the-bottom service connection capability (with accessory)
The direct-spark ignition system saves operating expense when allow power, control wiring, and gas to be routed through unit
compared to pilot ignition systems. No crossover tube is base pan, minimizing roof penetrations.Gas,power,and control
required, therefore no sooting or pilot fouling problems can connections are made on the same side of the unit to simplify
occur. installation.
All 580D standard units are designed for natural gas, but an In addition, color-coded wires permit easy tracing and
accessory LP(liquid propane)conversion kit is available. diagnostics.
SAFETY IS BUILT IN—All 580D units have a flame rectifica- PROVEN COMPRESSOR RELIABILITY—Design techniques
tion sensor to quickly sense the burner flame and ignite burners feature computer-programmed balance between compressor,
almost immediately. Fast shutdown is a certainty since the sen- condenser,and evaporator. Bryant-specified hermetic compres-
sor reacts quickly to any flame outage or system failure. In the sors are equipped with compressor overcurrent and overtem-
event of a shutdown,an error code is issued at the IGC board. perature protection to ensure dependability.
Safety is also assured due to the heating safety controls which All 580D units have Bryant's exclusive fixed orifice metering
will shut down the unit if there is a problem.If excessive temper- device which precisely controls refrigerant flow,preventing slug-
atures develop,limit switches shut off the gas valve.After 4 con- ging and flood-back, while maintaining optimum unit perfor-
tinuous short cycles of the high-temperature limit switch, the mance. Filter driers are standard.
IGC board locks out the gas heat cycle to prevent any further INTEGRATED ECONOMIZERS AND OUTDOOR AIR —
short cycles. This safety feature is provided exclusively on Optional economizers and manual outdoor-air dampers intro-
Bryant rooftop units. The rollout switch also deenergizes the duce outdoor air which mixes with the conditioned air, improving
gas valve in the event of a flame rollout. indoor air quality and often reducing energy consumption.
DURABLE, DEPENDABLE CONSTRUCTION—Designed for During a first stage call for cooling, if the outdoor-air tempera-
durability in any climate,the weather-resistant cabinets are con- ture is below the economizer control changeover set point, the
structed of galvanized steel and bonderized, and all exterior discharge-air sensor modulates the economizer outdoor-air
panels are coated with a prepainted baked enamel finish. The damper open to take advantage of free cooling provided by the
paint finish is non-chalking, and is capable of withstanding outside air. When second-stage cooling is called for, the corn-
ASTM (American Society for Testing and Materials) B117 pressor is energized in addition to the economizer. If the
500-hour Salt Spray Test.All internal cabinet panels are primed, outdoor-air temperature is above the changeover set point, the
permitting longer life and a more attractive appearance for the first stage of compression is activated and the economizer stays
entire unit. at vent position. Durablade economizer operation is controlled
In addition, the 580D090-150 units are designed with a single, by a dry-bulb thermostat that senses outdoor-air temperature.
continuous top piece to eliminate any possible leaks. Totally Accessory upgrade kits allow for either outdoor-air enthalpy
enclosed condenser-fan motors and permanently lubricated changeover or for more precise differential enthlapy control.
bearings provide additional unit dependability. The Durablade economizer (option or accessory) on the 580D
EASY INSTALLATION AND CONVERSION — All units are units has a reliable sliding plate damper which is easily adjusted
shipped in the vertical discharge configuration for fit-up to stan- for 100% outdoor air, 100% return air, or any proportions of
dard roof curbs. (Two different curb sizes fit unit sizes 036-072 mixed air.
and 090-150, respectively.)The contractor can order and install The 580D units can also utilize the field or factoryinstalled
the roof curb early in the construction stage, before decisions EconoMi$er.The EconoMi$er is microprocessor controlled and
on size requirements are made. incorporates a parallel,opposed-blade damper system. In addi-
All units feature roll-formed base rail design with forklift slots tion, it has a spring return built into the damper actuator to pro-
and rigging holes for easier maneuvering. (Forklift slots are vide reliable close-on-power-loss. The EconoMi$er comes
found on 3 sides for 580D units.) The standard 580D036-060 equipped with up to 90% barometric relief capability for high
units have operating weights under 500 lb and durable packag- outdoor airflow applications,
ing protects all units during shipment and storage.
In addition, the EconoMi$er power exhaust accessory can be
The units can be easily converted from a vertical to a horizontal utilized to help maintain proper building pressure.
discharge configuration by relocating the panels supplied with For units without economizer, year-round ventilation is
the unit. enhanced by a manual outdoor-air damper (ordered as an
The non-corrosive sloped condensate pan permits either an accessory or an option).The damper can be preset to admit up
external horizontal side condensate drain (outside the roof to 50%outdoor air.
curb) or an internal vertical bottom drain (inside the roof curb). INDOOR-AIR QUALITY(IAQ)BEGINS WITH BRYANT ROOF-
Both options require an external,field supplied P-trap.Also,the TOPS—Sloped condensate pans minimize biological growth in
condenser coil grille (available on 036-072 sizes as a field rooftop units in accordance with ASH RAE(American Society of
installed accessory) provides a metal plate as an alternate loca-
tion for the field supplied disconnect, if desired. Heating, Refrigeration, and Air Conditioning Engineers) Stan-
dard 62.Two-inch filters with optional dirty filter indicator switch
The 580D units were designed with service technicians in mind. provide for greater particle reduction in the return air.The face-
The single-row condenser coils on the 580D036-072 and 090 split evaporator coils improve the dehumidification capability of
units simplify the cleaning process.The efficient in-shot burners standard units, and enthlapy controls maximize building humid-
and all ignition components are contained in an easily remov- ity control.
able,compact assembly. Optional proportional reacting CO2 sensor is available with the
The 580D units also have a standard filter access panel,which EconoMi$er to aid IAQ benefits.
permits tool-less filter changes, even on units with horizontal
economizers.
2
TABLE OF CONTENTS
Page Page
. Features/Benefits 1-2 Performance Data 16-38
Model Number Nomenclature 3 Electrical Data 39,40
ARI Capacity Ratings 3,4 Typical Piping and Wiring 41
Physical Data 5-8 Controls 42,43
Options and Accessories 9,10 Application Data 44
Base Unit Dimensions 11,12 Typical Wiring Schematic 45,46
Accessory Dimensions 13,14 Guide Specifications 47-49
Selection Procedure 15
MODEL NUMBER NOMENCLATURE
580D E V 090 180 C B
580D — Packaged Rooftop Evaporator-Fan Motor Options
Standard Efficiency A —Standard Motor and Drive
Gas/Electric Unit B —Alternate Motor and/or Drive
Voltage Designation Factory-Installed Outdoor-Air and
J — 208/230-1-60 Other Upgrade Options
P — 208/230-3-60 A —Standard Unit
E — 460-3-60 C —Durablade Economizer
T — 575-3-60 H —25%Manual Damper
M—Durablade Economizer,Controls
Fuel and Control Type Upgrade Package*,and Condenser
V — Natural Gas/Direct Spark Ignition Coil Grille
N —25%Manual Damper,Controls
Upgrade Package*,and Condenser
Nominal Tons Coil Grille
036— 3 090 —7-1/2 T —Controls Upgrade Package*and
048— 4 102 —8-1/2 Condenser Coil Grille
060— 5 120 — 10 P —EconoMi$er
072— 6 150 — 12-1/2 L —EconoMi$er and Controls
Upgrade Package(for use with
Aernate Motor and Drive
Gas Heat Input(Btuh) R —EconoMi$er and Controls)
074— 72,000 180 — 180,000 Upgrade Package(for use with
115— 115,000 224 — 224,000 Standard Motor and Drive)
125— 125,000 250 — 250,000 K—EconoMi$er,Controls Upgrade Package,
150— 150,000 and Condenser
*Contains high pressure, (loss-of-charge) low-pressure, and freeze
protection cutout switches.
NOTE:The example model number 558DEV090180CB designates a
71/2ton 460-3-60 volt gas/electric rooftop unit with 180,000 Btuh nat-
uragas heat,Durablade economizer and alternate drive.
ARI*CAPACITY RATINGS
UNIT NOMINAL STANDARD NET COOLING TOTAL SEERt SOUND
580D TONS CFM CAPACITY kW Belt Drive Direct Drive RATING
(Btuh) (Bels)
36 3 1200 35,000 4.0 10.0 9.7 8.1
048 4 1600 47,000 5.5 10.0 9.7----- $.T _..` J
060 5 2000 57,000 6.7 T0.0 9.1 ts.l
See Legend and Notes on page 4.
3
• ARI*CAPACITY RATINGS(cont)
• NET COOLING SOUND
UNIT NOMINAL STANDARD CAPACITY TOTAL EER RATING IPLV
• 580D TONS CFM (Btuh) kW (Bels)
072 6 2100 72,000 8.0 9.0 8.1 **
090 71/2 2800 85,000 9.6 8.9 8.7 9.35
102 81/2 3000 99,000 11.0 9.0 8.7 9.00
120 10 4000 117,000 13.0 9.0 8.8 9.35
150 121/2 4500 145,000 16.1 9.0 8.7 9.20
LEGEND
Bels - Sound Levels(1 bel=10 decibels)
db - Dry Bulb
EER - Energy Efficiency Ratio
IPLV - Integrated Part-Load Values
SEER - Seasonal Energy Efficiency Ratio
wb - Wet Bulb
*Air Conditioning and Refrigeration Institute.
tApplies only to units with capacity of 65,000 Btuh or less.
**The IPLV applies only to two-stage cooling units.
NOTES:
1. Rated in accordance with ARI Standards 210/240,latest revision(for sizes 036-120)or 360,latest revision(for size 150)and 270,
latest revision.
2. ARI ratings are net values,reflecting the effects of circulating fan heat.
3. Ratings are based on:
t. 1451,,
qi..,a r.ccF 9�s>9N„n � S>ANO+P°
Cooling Standard:80 F db,67 F wb indoor entering-air temperature and 95 F db air entering outdoor unit.
IPLV Standard:80 F db,67 F wb indoor entering-air temperature and 80 F db outdoor entering-air temperature.
HEATING CAPACITIES AND EFFICIENCIES
HEATING INPUT TEMPERATURE STEADY-STATE CALIFORNIA
UNIT 580D (Btuh) OUTPUT CAPACITY RISE AFUE° EFFICIENCY SEASONAL
Stage 2/Stage 1 (Btuh) (F) (/°) (°�0) EFFICIENCY
(%)
036 074 -/ 72,000 59,200 25-55 80.0 80.0 77.2
I • 15 HI I : 600 92,000 55-85 81.0 :i
�' 048 074 -/ 72,000 59200 • - 80.0 80.0 77.2
048115- 2, ---� 3555--- _-- -.80:0 ._. -80:0 _.. .._ 77.1. 5".-J
048 150 150,000/120,000 120,000 50-80 80.0 80.0 76.9
060 074 -/ 72,000 59,200 25-55 80.0 80.0 77.2
060115 -/115,000 92,000 35-65 80.0 80.0 77.1
060 150 150,000/120,000 120,000 50-80 80.0 80.0 76.9
072 074 -/ 72,000 59,200 25-55 80.0 80.0 77.2
072 115 -/115,000 92,000 35-65 80.0 80.0 77.1
072 150 150,000/120,000 120,000 50-80 80.0 80.0 76.9
090 125 -/125,000 100,000 20-50 80.0 80.0 75.8
090 180 180,000/120,000 144,000 35-65 80.0 80.0 77.1
090 224 224,000/180,000 179,200 45-75 80.0 80.0 77.1
102 125 -/125,000 100,000 20-50 80.0 80.0 75.8
102 180 180,000/120,000 144,000 35-65 80.0 80.0 77.1
102 224 224,000/180,000 179,200 45-75 80.0 80.0 77.1
120 180 180,000/120,000 144,000 35-65 80.0 80.0 77.1
120 224 224,000/180,000 179,200 35-65 80.0 80.0 77.1
120 250 250,000/200,000 200,000 40-70 80.0 80.0 76.4
150 224 224,000/180,000 179,200 35-65 80.0 80.0 77.1
150 250 250,000/200,000 200,000 40-70 80.0 80.0 76.4
LEGEND
AFUE - Annual Fuel Utilization Efficiency
NOTE:NOx levels are 40 nanograms/joule with the accessory NOx reduction kit(sizes 036-060).
4
PHYSICAL DATA-580D_036.07-
lIllt ,
UNIT SIZE 580D 036 048 060 072
NOMINAL CAPACITY(tons) 3 4 5 6
OPERATING WEIGHT(Ib)
Unit l
Al/AI' 460 470 490 565
AI/Cu' 465 (-476 )\ 497 576
Cu/Cu* 468 482 505 587
Economizer
Durablade 34 34 34
EconoMi$er 47 4 47 47
Roof Curbt 115 115 115
COMPRESSOR Reciprocating Reciprocating Reciprocating Scroll
Quantity 1 1 1 1
No.Cylinders(per Circuit) 2 2 2 —
OiI(oz) 50 50 50 54
REFRIGERANT TYPE R-22
Expansion Device Fixed Orific=Metering Device
Operating Charge(Ib-oz)
Circuit 1 3-6 4-11 5-13 7-8
Circuit 2 — — — —
CONDENSER COIL Enhanced Copper Tubes,Aluminum Lanced Fins
Rows...Fins/in. 1...17 1...17 1...17 2...17
Total Face Area(sq ft) 7.36 11.39 13.19 10.42
CONDENSER FAN Propeller Type
Nominal Cfm 3500 4000 4000 4000
Quantity...Diameter(in.) 1...22.0 1...22.0 1...22.0 1...22.0
Motor Hp...Rpm 1/4...1100 1/4...1100 1/4...1100 /4...1100
Watts Input(Total) 325 325 325 325
EVAPORATOR COIL Enhanced Copper Tubes,Aluminum Double-Wavy Fins
Rows...Fins/in. 2...15
12...15 3...15 4...15
Total Face Area(sq ft) 4.17 5.5 5.5 5.5
EVAPORATOR FAN Centrifugal Type
Quantity...Size(in.) Std 1...10x 10 1...10 x10 1...11 x 10 1...10 x 10
Alt 1...10x10 1...10x10 1...10x10 —
Type Drive Std Direct Direct Direct Belt
Alt Belt Belt Belt —
Nominal Cfm 1200 1600 2000 2400
Maximum Continuous Bhp Std .34 .75 1.20 2.40
Alt 1.00 1.00 1.30/2.40" —
Motor Frame Size Std 48 48 48 56
Alt 48 48 56 —
Nominal Rpm High/Low Std 860/800 1075/970 1075/970 —
Alt 1620 1620 1725 —
Fan Rpm Range Std — — — 1070-1460
Alt 760-1000 835-1185 900-1300 —
Motor Bearing Type Ball Ball Ball Ball
Maximum Allowable Rpm 2100 2100 2100 2100
Motor Pulley Pitch Diameter Min/Max(in.) Std — — — 2.8/3.8
Alt 1.9/2.9 1.9/2.9 2.4/3.4 —
Nominal Motor Shaft Diameter(in.) Std 1/2 1/2 1/2 5/s
Alt 1/2 r 1/2 5/8
Fan Pulley Pitch Diameter(in.) Std — — — 4.5
Alt 4.5 4.0 4.5 —
Belt,Quantity...Type...Length(in.) Std — — — 1...A...40
Alt 1..,A...34 1...A...34 1...A...39 —
Pulley Center Line Distance(in.) Std — — — 14.7-15.5
Alt 10.0-12.4 10.0-12.4 14.7-15.5 —
Speed Change per Full Turn of Std — — ! — 80
Movable Pulley Flange(rpm) Alt 48 70 80 —
Movable Pulley Maximum Full Turns Std — — — 5
From Closed Position Alt 5 5 5 —
Factory Setting Std — — — 3
Alt 3 3 3 —
Factory Speed Setting(rpm) Std — — — 1225
Alt 856 975 1060
Fan Shaft Diameter at Pulley(in.) 5/8 5/8 5/8 5/8
LEGEND t ut switch is manually reset by interrupting power to unit or resetting
Al — Aluminum thermo .
Bhp — Brake Horsepower II Requires an optional or accessory Controls Upgrade Kit.
Cu — Copper NOTE:The 580D150 units have a loss-of-charge/low-pressure switch(accessory
*Evaporator coil fin materiaVcondenser coil fin material.Contact your local repre- or option)located in the liquid line.
sentative for details about coated fins.
tWeight of 14-in.roof curb.
**Single-phase/three-phase.
5