Loading...
Report (20) l �v tf?i// GJ W September 29, 2014 RE: MECHANICAL Proiect Information Building Permit: MEC2014-00403 Construction Type: VA Tenant Name: Bonaventure Occupancy Type: I-1 cond.1 Address: 15000 SW Hall Blvd Occupant Load: NA Area: 157,067 Sq. Ft. Stories: 3 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2014 edition; and the State of Oregon Fire Code (OFC) 2014 edition. The submitted plans are approved subject to the following. 1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) 2. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 3. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 4. Permanent equipment supported by the structure, 400 lbs and over, shall have their attachments designed in accordance with the Building Code. 301.16 OMSC 5. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 6. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC • 7. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC 8. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down the air distribution system. Smoke detectors shall be connected to a fire alarm system or shall activate an audible and visible alarm at a constantly attended location. 606.2.1, 606.2.2, 606.2.3 OMSC 4 0- 9. Every refrigerant-containing part of every system that is erected on the premises shall be tested and proved tight after complete installation, and before operation. Tests shall include both the high and low-pressure sides of each system. 10.Fire and smoke dampers shall be provided with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating parts. Access points shall be permanently identified on the exterior by a label. Access doors in ducts shall be tight fitting and suitable for the required duct construction. 11.Inspector may require additional sway bracing at the final installation inspection. 12.Through penetrations in rated horizontal assemblies shall comply with OSSC 717.6.1. 13.Grease ducts shall be inspected by The City Inspector prior to installation. 14.Clothes dryer rooms shall have make up air as required by OMSC 504.5. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, Dan Nelson, Senior Plans Examiner (503)718-2436 • dann@tigard-or.com