Inspections (25)Location:
Record Type:
Inspection Type:
Result:
Comments:
Inspection Date:
Record ID:
Inspector:
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223 Tel: 503.718.2439
7807 SW DUNE GRASS LN, TIGARD, OR, 97224
Residential - Mechanical
699 Mechanical final
FAIL
MEC2016-00364
David Young
Maximum fuse or circuit breaker to be 20 amp per listing on unit.
30 amp breaker installed in panel, non fused disconnect.
Minor label installation for electrical reconnect failed.
Provide electrical permit and approved inspection from city of Tigard for electrical
reconnect.
Re inspection required after correction complete.
Copper tubing with line let to be protected from direct contact with metal clamps in
garage. M1309, G2305.2
Violation Summary:
Inspector Contractor
Location:
Record Type:
Inspection Type:
Result:
Comments:
Inspection Date:
Record ID:
Inspector:
City of Tigard
13125 SW Hall Blvd.
Tigard, OR 97223 Tel: 503.718.2439
7807 SW DUNE GRASS LN, TIGARD, OR, 97224
Residential - Mechanical
699 Mechanical final
PASS - No C of O
MEC2016-00364
David Young
Corrections complete.
Violation Summary:
Inspector Contractor