Plans (3)BUP2014 00247 ---- GENERAL NOTE5: GENERAL REQUIREMENTS C. VAPOR BARRIERS. CONTINUOUS APPROVED VAPOR BARRIERS SHALL BE INSTALLED ON THE HEATED SIDE Of A. DRAWING5, THE DRAWINGS ARE INTENDED TO DESCRIBE A TENANT IMPROVEMMENT OR THE THERMAL INSULATION INSTALLED. THE OVERALL SCOPE OF WORK. CONTRACTORS SHALL FIELD VERIFY THE EXISTING CONDITIONS AND ALERT THE D. INSULATION. PROVIDE INSULATION PER 2010 0550, ARCHITECT TO ANY UNFORESEEN CONSTRUCTION COMPONENT PERFORMANCE APPROACH, DAY ROAD DESIGN, LLC DIFFICULTIES BEFORE BEGINNING THEIR WORK. B. PRE -CONSTRUCTION MEETING. PRIOR TO ANY GENERAL NOTES RONALD L. KlEf CONSTRUCTION OR DEVELOPMENT ACTIVITY, THE 9825 5W DAY ROAD CONTRACTORS SHALL SCHEDULE, WITH OWNERS I VERIFY IN THE FIELD PRIOR TO DEMOLITION Of EXISTING WALLS 5HERWOOD, OR 97140 APPROVAL, A PRE -CONSTRUCTION MEETING WITH THE IF ANY STRUCTURAL COLUMNS EXIST. If 50 CONTACT LOCAL BUILDING DEPT... OR LOCAL PUBLIC WORKS ARCHITECT IMMEDIATELY. AT$ T CELL I=HONE 5TORE P: 503-320-09 16 DEPT.., VERIFY WHICH AGENCY WOULD BE INVOLVED, THE 2. CONTRACTOR TO MAINTAIN PROPER LIGHTING, SANITATION AND CONTRACTOR SHALL PROVIDE LOCAL INSPECTOR WITH 24 VENTILATION AT ALL TIMES. f: 503-972-1848 HOUR NOTICE PRIOR TO INSPECTION, 3. ALL WORK MUST BE APPROVED BY THE JURISDICTION HAVING RonKief@comca5t.net AUTHORITY. TIGARD PROMENADE C. REPETITIVE. TYPICAL WALL SECTIONS, FINISHES, AND 4. IT 15 THE SOLE RESPONSIBILITY Of THE CONTRACTOR TO DETAILS ARE NOT INDICATED EVERYWHERE THEY OCCUR MAINTAIN A WATER AND WEATHER TIGHT BUILDING. ON PLANS, ELEVATIONS AND SECTIONS. REFER TO 5. ALL WORK TO BE PERFORMED TO CODE BY A LICENSED CON5ULTANT5 DETAILED DRAWINGS, CONTRACTOR TO PROVIDE AS If CONTRACTOR PERFORMING THE WORK IN THEIR RESPECTIVE DRAWN IN FULL, TRADE ONLY, 15532 5W FACI f IC HWY, 5TE C-7 G. ALL DESIGN, DRAWINGS AND DETAILS REPRESENT COMPLETE D. CODES 0 PERMITS f REGULATIONS, ALL EXTERIOR WORK IN PLACE, ARCHITECT SHALL HAVE NO CONTROL OR CHANGE Of AND SHALL NOT BE RESPONSIBLE FOR SIGNAGE MUST BE SUBMITTED AND REVIEWED UNDER CONSTRUCTION SEPARATE PERMIT APPLICATION. TIGARDOF\ 97224 7. INTERIOR PARTITION DIMEN51ON5 NOTED ON PLANS MAY BE , SHOWN A NOMINAL DIMENSION, SUCH AS 5" INTERIOR WALL AT T STORE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS REFERS TO -5/6" GYP. BD. EACH SIDE OVER 35/a" STUDS. STUD AJ.f TIGARD PROMENADE SPACING 15 24" O,C. UNLESS OTHERWISE STATED.NFCF55ARY OTHER THAN THE BUILDING PERMIT. 15532 SW PACIFIC HIGHWAY, STf C-7 CONTRACTOR SHALL ALSO PAY FOR ALL OTHER 8. ALL DEBRIS GENERATED FROM CONSTRUCTION MUST BE KEPT TIGARD. OR e)7224 CHARGES, FEES OR COSTS CHARGED 13Y THE BUILDING ON SITE IN EITHER AN ENCLOSED AREA OR HAULED AWAY DAILY, 0 AND CONSTRUCTION DEPARTMENTS, UTILITY AGENCIES OR AND DISPOSED Of LEGALLY Off SITE. PRIVATE COMPANIES WHICH REQUIRE SUCH COSTS FOR 9. KEEP ALL PIPING AND CONDUIT AS CL05F TO WALLS AND ROOF z PRIOR TO INSTALLATIONS, DECK AS POSSIBLE AND ALL DUCTWORK AS CLOSE TO ROOF AS POSSIBLE. WHERE EXPOSED ALL PIPING CONDUIT AND RL..'fERENCE 5YME3OL5 PROJECT DATA NOTHING IN THE DRAWINGS SHALL BE CONSTRUCTED TO DUCTWORK SHALL BE PAINTED UNLESS OTHERWISE NOTED. ALL PERMIT AN INSTALLATION IN VIOLATION Of APPLICABLE PIPING AND CONDUIT SHALL BE ORGANIZED IN A NEAT MANNER BUILDING ELEVATION RUNNING PARALLEL OR PERPENDICULAR TO ROOF FRAMING DOOR TAG m CODE AND / OR RESTRICTIONS. SHOULD ANY CHANGE IN THE DRAWINGS BE NECESSARY IN ORDER TO COMPLY MEMBERS. REFERENCE WITH APPLICABLE CODES AND / OR REQUIREMENTS, THE 10. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR TO CONSTRUCTION AND COORDINATE WITH ARCHITECT ANY CONFLICT WITH THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AT ONCE PRJECT NAME: ATT T CELL PHONE STORE AND CEASE WORK. ALL PARTS REFORMED UNDER THIS PLANS. 1 1. PERFORM THE REMOVAL, CUTTING AND DRILLING WITH THE CARE WO CONTRACT SHALL BE IN FULL ACCORDANCE WITH THE ROOM TAG ALL SECTIN PROJECT ADDRESS: 15532 5W PACIFIC HIGHWAY, 5TE C-7 LATEST RULES, REGULATIONS, RESTRICTIONS, USE Of THE SMALLEST TOOLS 50 AS NOT TO DAMAGE THE REFERENCE REQUIREMENTS AND CODES, R STRUCTURAL INTEGRITY Of THE BUILDING. TIGARD, O 97224 12. TO SAW CUT ALL PLUMBING / ELECTRICAL TRENCHE5 USE SAWS AMENDED BY GOVERNING CITY ALL JURISDICTION AND CORE DRILLS, DO NOT USE JACKHAMMERS UNDER ANY CIRCUMSTANCE, CITY Of TIGARD RULES AND REGULATIONS. LOCAL JURISDICTION: w 13. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND DETAIL REFERENCE EQUIPMENT E201AV Alft T Of T R T T T HCOMMUNITY DEVELOPMENT NOTIFY THE OWNER AND ARCHITECT PRIOR START E. DIMENSIONS ARE SHOWN FACE Of MASONRY OR u i CENTERLINE Of OPENING, UNLESS DETAILED OTHERWISE WORK If DISCREPANCY OCCURS BETWEEN DRAWINGS AND 13 125 5W HALL BLVD ON THE DRAWINGS, ACTUAL CONDITIONS. 14. ALL MATERIALS, PRODUCTS, AND SYSTEMS SMALL BE INSTALLED TIGARD, OR 97223 AS PER MANUFACTURER'S SPECIFICATIONS AND ARCHITECT'S (503) G39-4171 DO NOT SCALE DRAWINGS. THE CONTRACTOR SHALL USE AE3E3Rj=VIA_\TION5 DIMENSIONS SHOWN ON THE DRAWINGS AND ACTUAL SUPPLEMENTAL INSTRUCTIONS. REPLACE ALL DEFECTIVE l�:w. FIELD MEASUREMENT5, NOTIFY ARCHITECT If ANY MATERIALS. MATERIALS SMALL BE NEW UNLESS OTHERWISE DISCREPANCIES ARE FOUND, DIRECTED BY THE OWNER. ALL MATERIALS SMALL BE STORED IN AB ANCHOR BOLT GALV GALVANIZED PLYWD PLYWOOD cc A MANNER WHICH WILL PREVENT DAMAGE, THEFT AND PREVENT ABP ALTERNATE BRACED PANEL GL GLASS / GLAZING POLY POLYETHYLENE CODES UTILIZED: 2014 OREGON STRUCTURAL SPECIALTY CODE THE CONTRACTOR SHALL VERIFY ALL ROUGH -IN CONTACT WITH MOISTURE, VERIFY STORAGE LOCATION WITH AFF ABOVE FINISH FLOOR GLB GLU-LAMINATED BEAM PR PAIR 2014 OREGON MECHANICAL CODE w DIMENSIONS FOR THE EQUIPMENT FURNISHED AND OWNER. ALUM ALUMINUM GYP BD GYPSUM BOARD PSL PARALLAM BEAM 15. OWNER SMALL 13E RESPONSIBLE FOR REMOVING FURNISHINGS 2014 OREGON PLUMBING CODE INSTALLED BY HIMSELF/HERSELF OR OTHERS, AND FIXTURES PRIOR TO START Of WORK, CONTRACTOR SHALL ANDD ANODIZED HB HOSE BIBB PT PRESSURE TREATED 2014 OREGON ELECTRICAL CODE THE CONTRACTOR SHALL CONSULT THE PLANS Of ALL BE RESPONSIBLE FOR PROTECTING EXISTING PERMANENT ITEMS BALC BALCONY HC HOLLOW CORE (DOOR) RAD RADIUS TRADES FOR OPENINGS THROUGH SLABS, WALLS SUCH AS BUILT-INS, TRIM, APPLIANCES, FIXTURES, WALL BLKG BLOCKING (2x MATERIAL) HD SIMPSON HOEDOWN REF REFRIGERATOR SURFACES, RAILINGS, ETC... CEILINGS AND R.001`5� MERCANTILE RETAIL PROPOSED USE: I G. ALL CONTRACTORS / SUBCONTRACTORS SHALL MAINTAIN CLEAN BP BRACED PANEL HDG HOT DIPPED GALVANIZED REQD REQUIRED F. SHOP DRAWING REVIEW, PROVIDE SHOP DRAWINGS FOR AND SAFE WORKING CONDITIONS FOR ALL PER50NNEL AND CB CATCH BASIN HDR HEADER RM ROOM OWNER DURING ALL PHASES OF CONSTRUCTION, REMOVE THE ARCHITECT / OWNERS AND AS REQUIRED 13Y THE CEIL CEILING HDWD HARDWOOD RO ROUGH OPENING DEBRIS FROM BUILDING AND 51TE AS IT ACCUMULATES. 111-5 (SPRINKLED) CITY PRIOR TO CONSTRUCTION. ci CONTROL JOINT HGR HANGER (METAL) SC SOLID CORE (DOOR) CONSTRUCTION TYPE: PROJECT PROVIDE PLASTIC SHEETING DUST BARRIERS BETWEEN ALL G. CONTRACTOR TO FRAME OPENINGS IN WALLS, CEILINGS COIL COLUMN HT HEIGHT SHTHG SHEATHING WORK AREAS AND EXISTING LIVABLE SPACE, 17� CONTRACTOR SMALL 13E RESPONSIBLE FOR ALL SHORING AND COMP COMPOSITION HVAC HEATING, VENTING, A/C SHTRK SHEET ROCK AND FLOORS FOR HVAC AND OTHER MECHANICAL OR m OCCUPANCY GROUP: ELECTRICAL WORK WHERE REQUIRED AND NOT OTHERWISE BRACING TO ENSURE SAFE CONDITIONS FOR STRUCTURAL CONN CONNECTOR I.D. INSIDE DIAMETER SHWIR SHOWER SYSTEMS DURING ALL PHASES Of CONSTRUCTION. SHOWN ON THE PLANS. CONST CONSTRUCTION INSUL INSULATION SPEC SPECIFICATIONS 18. CONTRACTOR SMALL FURNISH TEMPORARY SANITARY FACILITIES RETAIL SALES AREA: 1,337 5Q.fT. 30 45 AT T STORE CONT CONTINUOUS INT INTERIOR STL STEEL (ASTM 36) AS ALLOWED BY LOCAL CODE AND COVENANTS. OWNER SHALL H. COMPLY WITH APPLICABLE REGULATIONS FOR 5TORAGE/5ERVICE AREA: 274 5Q. fT, 300 = I TIGARD PROMENADE CONC CAST IN PLACE CONCRETE JT JOINT STRUC STRUCTURAL BARRIER -FREE FACILITIES (20 10 OREGON SPECIALTY FURNISH WATER AND ELECTRICAL POWER UNLESS NOTED 15532 SW PACIf IC HIGHWAY, ATE G-7 OTHERWISE IN CONTRACTOR / OWNER AGREEMENT. DIM DIMENSION KD KILN DRIED T & G TONGUE & GROOVE 186 5Q,fT. 0 = 0.0 MALLWAY/RE5TROOM5: TIGARD, OR 07224 STRUCTURAL CODE) AND AN5f-A 1 17. 1 LATEST EDITION. 19. IF WEATHER CONDITIONS CAUSE DELAYS OR WORK STOPPAGE, DS DOWNSPOUT LAM LAMINATED GLASS TB TOWEL BAR CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. DURING BREAK ROOM: I I SQ. 30 4 DOORS WINDOWS INCLEMENT WEATHER, CONTRACTOR 15 RESPONSIBLE FOR DW DISHWASHER LAV LAVATORY TEMP TEMPERED MAKING ARRANGEMENTS TO PROTECT AND SECURE EXPOSED EIEC ELECTRICAL LT LIGHT FIXTURE Til TRUSS JOIST (I -JOIST) A. GLAZING. PROVIDE GLAZING PER 2010 055C:TOTAL OCCUPANT LOAD: 50 INSULATED UNITS SHALL BE CLASS 40 GLAZING WITH WALL AND ROOF CONSTRUCTION MATERIALS TO PREVENT ELEV ELEVATION LVL LAM VENEER LUMBER T. 0. TOP OF LOW E ARGON GAS, DAMAGE, ENG ENGINEER MB MOISTURE BARRIER TYP TYPICAL 20. BIDS AND NEGOTIATED PRICE5 SHALL LAINCLUDE ALL MATERIALS, BOR, EQUIENT, AND OTHER COMPONENTS NECE55ARY FOR EPS EXTRUDED POLYSTYRENE MECH MECHANICAL UNDRLYMT UNDERLAYMENT (2) EXIT REQUIRED, (2) EXIT(5) PROVIDED (OCCUPANT <50) 5HEET TITLE GLAZING IN LOCATIONS SUBJECT TO HUMAN IMPACT PMEXIST EXISTING MO MASONRY OPENING VAC VACUUM 5UCM AS PANES IN DOORS, GLAZING WITHIN 24" ARC Of COMPLETION Of THE DESCRIBED PROJECT, MATERIALS (1) R175TROOM5 REQUIRED, (1) RF5TROOM5 PROVIDED CONSIDERED TO BE STANDARD AND CUSTOMARY FOR TH15 TYPE FBGL FIBERGLASS MTL METAL vs VAPOR BARRIER A DOOR OPENING, GLAZING WITHIN 18" Of THE FLOOR Of BUILDING / CONSTRUCTION MUST BE INCLUDED. FD FLOOR DRAIN NOM NOMINAL VGDF VERT GRAIN DOUG. FIR (AND 15 OVER 9 5Q... IT, PER PANEL) SMALL BE 21. CONTRACTORS, OWNER, AND OTHER PARTIES SHALL NOT MAKE FDN FOUNDATION NWCB N.W. WALL & CEILING BUREAU W/ WITH TEMPERED GA -95 OR LAMINATED SAFETY GASB PER CHANGES TO THE DRAWINGS. REQUESTS FOR CHANGES SMALL CODE, BE MADE IN WRITING AND BE SUBMITTED TO THE OWNER AND FO FACE OF O/C ON CENTER WC WATER CLOSET NO 5TRUCTURAL WORK 15 TO BE PERFORMED UNDER TH15 PERMIT. ARCHITECT FOR REVIEW. FP FIRE PROOFING OH OVERHANG WD WOOD GLAZING U -VALUE (AMMA TESTED) U-40 MAXIMUM. 22. AT JOB COMPLETION, CONTRACTOR, OWNER t ARCHITECT SHALL FIR FIRE RESISTANT OPNG OPENING WH WATER HEATER NO 51TE WORK 15 TO BE DONE UNDER TH15 PERMIT. MEET AT THE 51TE FOR A FINAL WALK-THROUGH TO VERIFY THAT FRMG FRAMING PA POST ABOVE WP WATER PROOF FIRE PROTECTION ALL WORK 15 COMPLETE PER PLANS, SPECIFICATIONS AND CODE. FT FOOT PL PLATE WR WATER RESISTANT EX-ITE RIOR 51GN UNDER A SEPARATE PERMIT A. EXTEND THE EXISTING AUTOMATIC FIRE SPRINKLER CEILING HEIGHT CONDITIONS FTG FOOTING P LAM PLASTIC LAMINATE SYSTEM AS REQUIRED. GET SYSTEM DESIGN APPROVED FURN FURNACE (FORCED AIR) BY GOVERNING CITY5 BUILDING DEPARTMENT AND FIRE OWNER MUST FIELD VERIFY ALL CEILING HEIGHT DIMENSIONS. ANY DEPARTMENT PRIOR TO INSTALLATION, VARIANCES BETWEEN THESE APPROVED DIMENSIONS AND ACTUAL SITE CONDITIONS AND EXISTING CONDITIONS SMALL BE THE SOLE E 5 B. PROVIDE FIRE EXTINGUISHERS AS REQUIRED BY 2010 RESPONSIBILITY Of THE OWNER/ TENANT. ALL COSTS ASSOCIATED CONTACT NfORM ATION INDEX Of 51-IFET5TITLHT 0550 AND LOCATE PER FIRE MARSHALL'S DIRECTIONS. WITH REVISIONS AND CHANGE ORDERS SHALL BE THE SOLE ONE FIRE EXTINGUISHER PER 3M0 5Q... ff. Of BLDG... RESPONSIBILITY Of THE OWNER /TENANT. TENANT INFORMATION AREA WITH 75' MAX... TRAVEL DISTANCE BETWEEN AT t T CELL PHONE STORE A I TITLE 5HEET MY OF TIGARD EXTINGUISHERS. LOCATION TO BE VERIFIED 13Y THE VERIFICATION Of SITE CONDITIONS V113WEAj FOR CODE ComPLIANCH LOCAL FIRE MARSHALL. A2 51TE PLAN DEMOLITION OWNER TENANT 15 REQUIRED TO PERFORM A 51TE SURVEY Of THE A C. MAINTAIN STRUCTURAL AND FIRE RESISTIVE INTEGRITY ENTIRE PREMISES PRIOR TO COMPLETION Of THE TENANT'S A3 5COPE Of WORK Appro"& AT EXTERIOR AND RATED INTERIOR WALL PENETRATIONS CONSTRUCTION DOCUMENTS. ANY VARIANCES BETWEEN THESE A4 FLOOR PLAN OTQ FOR ELECTRICAL, MECHANICAL, PLUMBING AND APPROVED PLANS AND ACTUAL SITE CONDITIONS SHALL BE THE pe; #g COMMUNICATIONS CONDUITS, PIPED AND SIMILAR 50LE RESPONSIBILITY Of THE OWNER / TENANT, ALL COSTS AS REFLECTED CEILING PLAN Addmsw SYSTEMS PER 2010 055C. ASSOCIATED WITH RFV1510NS AND CHANGE ORDERS SHALL BE THE is 50LE RESPONSIBILITY Of THE OWNER TENANT, AG FIN 15HE5 ELEVATION5 swte A C",,��,,,,,,,, THERMAL MOISTURE PROTECTION DaW tnj-,-2�IA LANDLORD INFORMATION GENERAL CONTRACTOR A. OPENINGS, ALL OPENINGS TO BE CAULKED, SEALED OR TERRAMAR RETAIL CENTER CPS CONSTRUCTION, INC WEATHER-STRIPPED. 5973 AVENIDA ENCINA5, 5TE 300 RON KIEF OFFICE COPY PAGE NUMBER CARLSBAD, CA 92006 9625 5W DAY ROAD B. CAULKING AND SEALANT. USE PRIMER AS REQUIRED BY GREG DALLAL, TENANT COORDINATOR SHERWOOD, OR 97140 MANUFACTURER. BACKING ROD OR TAPE AS RECOMMENDED BY MANUFACTURER, USE POLYURETHANE (760) 476- 1 146 (503) 320-0918 1 SEALANT AT CONCRETE FLOOR AND SIDEWALK JOINTS. RonKief@comca5t.net A ALL OTHER LOCATIONS USE POLY5ULfIDE OR SILICONE. - - ---------- --- — --- . ..... - --------- ------- — - ------- - DEMOLITION PLAN Any variations from conditions and dimensions shown on the drawings shall be reported to Ronald L. Kief, for resolution prior to proceeding with the work; otherwise, the contractor shall be solely responsible for the cost of any necessary work. R DAY ROAD Df-51GN, LLC RONALD L. KlEf 9825 5W DAY ROAD 5HERWOOD, OR 97140 P: 503-320-0918 P: 503-972-1846 P,onKief@comca5t.net z LL W APO% UJI W a. PROJECT AT * T 5TOKE TIGARD PROMENADE 15532 5W PACIFIC HIGHWAY, STE C-7 TIGARD, OR 97224 5 H f ET TITLE DEMOLITION VICINITY MAP 5CALE N,T,5. PAGE NUMBER A-2 STOREFRONT LANDLORD SHALL PROVIDE A COMPLETE STOREFRONT W1TH A 51NGLE DOOR CENTERED WITHIN THE STOREFRONT, INCLUDING DOOR FRAMES, CASINGS AND HARDWARE, AND A HOLLOW METAL REAR SERVICE DOOR, INCLUDING FRAME, CASING HARDWARE. ALL REQUIRED EXIT DOORS AND HARDWARE SHALL BE THE PROPER RATING FOR THE REOUIRED ASSEMBLY AND MEET PREVAILING BUILDING CODE REQUIREMENTS FOR EGRESS DOOR SWING AND HARDWARE. THE STOREFRONT SHALL INCLUDE CLEAR TEMPERED PLATE 6LA55. AN OVERHANG, AWNING OR CANOPY SHALL EXIST ABOVE THE EXTERIOR 6LA55. LANDLORD SHALL REPLACE DAMAGED GLASS, IF NECESSARY. DOOR 4 WALLS ALL EXTERIOR, INTERIOR AND DEM151N6 WALL5 SHALL BE METAL FRAMED, 5HEETROCKED, FIREPROOFED IF REQUIRED BY CODE., FINISHED, TAPED AND SANDED SMOOTH, PRIMED AND READY FOR PAINT CONDITION. DEM151N6 WALL SHALL BE A5-15. THE ROOF DECK SHALL BE A5 -I5. ALL RESTROOM WALL5 AND RESTROOM CEILING SHALL BE A5-15 CONDITION. LANDLORD SHALL INSTALL A 6ALE5/6TOCK ROOM WALL AND RESTROOM WALL, INCLUDING A DOOR PER PROTOTYPICAL PLANS FROM FAIRWOOD 5HOPPING CENTER. THE SALE5/5TOCK WALL SHALL EXTEND UP TO THE EXI5TIN6 CEILING GRID. OTHER THAN AROUND THE RESTROOM AND 5ALE5/5TOC:K ROOM WALLS, NO OTHER INTERIOR PARTITIONS SHALL EXISTING WITHIN THE PREMISES. THE INTERIOR PARTITIONS AROUND THE RESTROOM AND SALES/STOCK WALL SHALL BE METAL FRAMED WITH 5 5/5" 5TUD5, 5HEETROCKED, FINISHED, TAPED AND SANDED 5MOOTH, PRIMED AND IN READY FOR PAINT CONDITION. ALL INTERIOR DOORS SHALL BE V-0" X -'-0", 1 5/4" THICK, PAINT GRADE, SOLID—CORE WOOD WITH METAL FRAMES AND COMMERCIAL GRADE LEVER HARDWARE AND LOCKSET (KEYED LOCK5ET FOR 5ALE5/5TOCK DOOR AND PRIVACY LOCK FOR RESTROOM, HYDRAULIC DOOR CLOSERS AND 8" BRUSHED ALUMINUM KICK—PLATES ON DOOR TO STOCKROOM ONLY. FLOORS, CEILING 4 LIGHTING SALES FLOOR — TENANT SHALL PROVIDE AND LANDLORD SHALL INSTALL A SILVERTONE #052 COLORED 2' X 2' U5G #414 FR05T CLIMAPLU5, 5HADOWLINE BEVEL (5LB) LAIN—IN CEILING TILE AND 2' CROSS T'S, INSTALLED WITHIN AN USG DONN DX 15'/e," 5ILVERTONE COLORED CEILING GRID, 12' AFF WITHIN THE SALES AREA. IF 15/1 e," CEILING GRID 15 EXISTING AND NOT NEW, IT SHALL BE IN "LIKE NEW CONDITION AND PAINTED WITH BENJAMIN MOORE #2125-50 "5WEET INNOCENCE" EGGSHELL FINISH. ALL HVAC GRILLS AND DIFFUSERS SHALL BE PAINTED WITH THE SAME PAINT SPECIFICATION. ALL LIGHT FIXTURES WITHIN THE 5ALF-5 FLOOR (EXCEPT EMERGENCY LIGHTS) SHALL BE PROVIDED BY THE TENANT BUT INSTALLED, INCLUDING ALL ASSOCIATED WIRING, BY LANDLORD PER PROTOTYIPICAL PLAN FROM FAIRWOOD SHOPPING CENTER. TH15 LIGHTING SHALL INCLUDE THE LIGHT FIXTURE TYPES SHOWN WITHIN THE ATTACHED EXAMPLE, (SAMPLE FROM FAIRWOOD SHOPPING CENTER) BUT OUANTITIE5 WILL DIFFER DEPENDING ON THE 51ZE AND DE516N OF THE SALES FLOOR. LANDLORD SHALL PROVIDE AND INSTALL ALL EMERGENCY LIGHTING AS REQUIRED BY CODE. IF A SPRINKLED BUILDING, SPRINKLER HEADS SHALL BE A5-15. BACK OF HOUSE AREA - LANDLORD SHALL PROVIDE A STANDARD WHITE 2'X 4' CEILING GRID AND TILE FOR NON -SALES FLOOR AREA (LOCATED 1 2' AFF A5 -I5), AND A 8' AFF DRYWALL CEILING WITHIN THE RESTROOM. LANDLORD SHALL INSTALL STANDARD 2'X *FLUORESCENT LIGHTING IN ALL NON-5ALE5 FLOOR AREAS AS PER THE APPROVED TENANT'S PLAN. RESTROOM LIGHTING SHALL BE A5-15 BUT MUST PROVIDE SUFFICIENT LIGHTING. ALL FLOOR FINISHES THROUGHOUT THE SALES FLOOR SHALL BE REMOVED TO A SMOOTH BASE CONCRETE SLAB WITHOUT SLOPE, AND SUCH FLOOR SHALL BE CLEANED, PREPARED, AND SUITABLE FOR NEW FLOOR FIN15H INSTALLATION. IF IN GOOD CONDITION, THE EXISTING FLOOR MAY REMAIN FOR ALL "BACK OF HOUSE" AREAS. IF NOT, BOH AREA SHALL RECEIVE NEW 12" X 12" VCT WITH 4" BLACK COVE BASE. INTERIOR RE5TROOM FLOORS SHALL REMAIN SHEET VINYL, A5-15. HVAC; SYSTEM LANDLORD SHALL PROVIDE THE EXISTING FULLY FUNCTIONAL AND CODE COMPLIANT HVAC SYSTEM, 51ZED AT 557 SQUARE FEET PER TON, DESIGNED BY LANDLORD TO ACCOMODATE TENANTS FLOOR PLAN. RESTROOM THE PREMISES SHALL BE PROVIDED WITH ONE RESTROOM THAT 15 COMPLETELY FUNCTIONAL, WITH COMMERCIAL GRADE FIXTURES, AND THAT MEETS ALL APPLICABLE BUILDING CODES, INCLUDING ADA REOUIR.EMENT5. THE RESTROOM MUST include (1) ADA COMPLIANT WALL HUNG LAVATORY WITH HOT AND COLD WATER, (1) ADA COMPLIANT TOILET, GRAB BARS, SIGNAGE, TOILET ROLL HOLDER, PAPER TOWEL DISPENSER, MIRROR, GFI OUTLET, SWITCHED LIGHTING AND OPERATIONAL EXHAUST FAN. THE RESTROOM SHALL BE COMPLETED, FINISHED AND OPERATIONAL. ELECTRICAL SERVICE: BASED ON PROTOTYPICAL FAIRWOOD PLAN EXHIBIT THE LANDLORD SHALL PROVIDE (1) 200 AMP, 120 / 208 VOLT, 5—PHA5E, 4—WIRE ELECTRICAL SERVICE WITH A 42 CIRCUIT PANEL. THE LANDLORD SHALL PROVIDE THE FOLLOWING PER CODE: ELECTRICAL CONNECTION TO THE HVAC (RTU), DUPLEX CONVENIENCE OUTLETS AT ROOFTOP EG2UIPMENT, GFI ELECTRICAL OUTLET IN THE RESTROOM, ELECTRICAL CONNECTION TO THE EXISTING WATER HEATER, A DEDICATED 20 AMP CIRCUIT FOR EACH EXTERIOR 5167N LOCATION INCLUDING A '7 —DAY PROGRAMMABLE 5167NA6E TIME CLOCK LOCATED NEXT TO THE ELECTRICAL PANEL, AND ADDITIONAL CIRCUITS TO SUPPORT THE ELECTRICAL REQUIREMENTS BASED PROTOTYPICAL FAIRWOOD SHOPPING CENTER PLANS. LANDLORD UP TO (1 5) FLUSH MOUNTED SOUAD ELECTRICAL WALL OUTLETS LOCATED AS PER TENANTS PLAN. UP TO ELEVEN OF THESE OUTLETS SHALL FEATURE (2) PLUG5 ON A SWITCH AND THE OTHER (2) PLUG5 NON-5WITCHED, WITH THE SY41TCHEV FLU65 WIRED BACK TO MAIN SWITCH BANK AS PER TENANTS PLAN. LANDLORD SHALL INSTALL UP TO (8) FLUSH MOUNTED DUPLEX OUTLETS LOCATED AS PER TENANT'S PLAN. LANDLORD SHALL INSTALL UP TO (1 O) FLUSH MOUNTED JUNCTION BOXES WITH PULL—STRINGS FOR FUTURE DATA CABLING BY TENANT, WITH :5/4" CONDUIT EXTENDED ABOVE CEILING GRID. LOCATION OF TELCO BOARD AND JUNCTION BOXES SHALL BE AS PER TENANTS PLAN. LANDLORD INSTALL (4) 51X GANG FLUSH MOUNTED LIGHT SWITCH BANK IN THE WALL AS PER TENANTS PLAN. LANDLORD SHALL INSTALL SIX (6) TWO—GANG ELECTRICAL. FLOOR BOXES, FLUSH MOUNTED INTO THE CONCRETE FLOOR SLAB AS LOCATED PER TENANTS PLAN. EACH BOX SHALL HAVE A 5/4" CONDUIT WITH PULL -STRING FOR FUTURE DATA CABLING AND BLANK COVER PLATE (STUBBED ABOVE CEILING GRID), NEXT TO AN OPERATIONAL ELECTRICAL OUTLET (FOUR BOXES BEING DUPLEX OUTLETS AND TWO BOXES QUAD ELECTRICAL OUTLETS). THE TWO BOXES SUPPORTING THE LEARNING TABLES (AS NOTED WITHIN TENANTS PLANS) SHALL SHARE A DEDICATED 20 AMP CIRCUIT WITH 150LATED GROUNDS, AND THE TWO BOXES SUPPORTING THE P05 STATIONS (A5 NOTED WITHIN TENANTS PLANS) SHALL SHARE A DEDICATED 20 AMP CIRCUIT WITH 150LATED GROUNDS. THE ELECTRICAL CIRCUITRY ON THE SALES FLOOR SHALL BE A5 PER TENANTS PLANS. ALL FACEPLATES SHALL BE WHITE IN COLOR. IF NOT SHOWN ON TENANTS PLANS, NO BLANK JUNCTION BOXES OR EXI5TIN6 ELECTRICAL OUTLET SHALL EX15T WITH IN THE SALES FLOOR WITH THE FOLLOWING EXCEPTION. EXISTING ELECTRICAL CONVIENGE OUTLETS AT 24" AFF OR LOWER CAN REMAIN AS LONG AS THE FACEPLATES ARE WHITE IN COLOR AND IN "LIKE NEW" CONDITION. LANDLORD SHALL PROVIDE ALL SAW CUTTING AND CONCRETE. TELEPHONE LANDLORD SHALL PROVIDE A MINIMUM 1 " DIAMETER CONDUIT WITH PULL—STRING FOR INCOMING TELEPHONE SERVICE. SAID CONDUIT 15 TO BE ROUTED FROM THE BUILDING TELEPHONE DEMARCATION POINT, TERMINATING INTO A VX 5' PLYWOOD BACKBOARD ON THE BACK WALL NEXT TO THE EXISTING ELECTRICAL PANEL. The Written dimensions on this plan supercede Scaled distances DO NOT SCALE THE DRAWINGS Any variations from conditions and dimensions shown on the drawings shall be reported to Ronald L. Kief, for resolution prig to proceeding with the work; otherwise, the contractor shall be solely responsible for the cost of any necessary work. DAY ROAD Df51GN, LLC RONALD L. KIEP 9825 5W DAY ROAD 5HfRWOOD, OR 97140 P, 503-320-0918 f: 503-972-1(548 RonKlef@comca5t.net UJI (5 z W UJIW CL PROJECT AT * T 5TO RE TIGARD PROMENADE 15532 5W PACIFIC HIGHWAY, 5TE C-7 TIGARD, OR 97224 5hEET TITLE 5COPE OF WORK L.ANPL.ORD5 WORK LETTER SCALE N.T.5. PACE NUIVBER A-5 I N5TALL A / VERTICAL /EXISTING) BREAK ROOM !<(2>a GRAB BAR ALTA t EXISTING R. R. , EXISTING (2)D n E Gi- I „ „i 4,_4"i __-F 7i_7 , i 1 2'-G"" 2'-0" 5'-8'° -- --- 4`-®'" -+3 '- I 111 _ I1- n_7 (MI I}! =_ (2}a 11 OD19 OD N rI m N m o4 + I + u 04 04 1? 0 ` I 1 MEvI45c -i j 1 (2)D C\j( a rzff \ SEE REFLECTED CEILING PLAN k1'_-fOR DETAIL * ELECTRICAL _ I 31_31l 31_311. NOTES THIS PAGE 1 a I (2)D p o2 EX15TING I 1 f � (2)D (2)a �(E) PANIC _ �__ __ _ ____ __ __ _ _ _ __ (4)D DEVICE - EXISTING 7 -Gil t.$I-011 Qi -4,1 i VVV.YYY i �7j EXISTING 24'- 10" RETAIL SALES AREA STORAGE � ' i i r2 In f (2)D CLG C 04 (2)D ELECTRICAL POWER PLAN I I: [AI 9 M ALL OUTLETS ARE NEYN UNLESS OTHERN15E NOTE: (E) INDICATES EXISTING ITEM TO REMAIN) DUPLEX OUTLET, FLUSH kNALL MOUNTED DUPLEX OUTLET, FLUSH kNALL MOUNTED, DEDICATED FOURPLEX OUTLET, FLUSH Y4ALL MOUNTED D FOURPLEX OUTLET, FLUSH kNALL MOUNTED, DEDICATED DUPLEX OUTLET, FLUSH FLOOR MOUNTED FOURPLEX OUTLET, FLUSH FLOOR MOUNTED TELEPHONE/DATA OUTLET, FLUSH YVALL MOUNTED YNITH 1 " CONDUIT TELEPHONE/DATA OUTLET, FLUSH FLOOR MOUNTED ® DATA OUTLET, FLUSH FLOOR MOUNTED ^ITH 1 of CONDUIT ,d TELEPHONE/DATA OUTLET, FLUSH Y4ALL MOUNTED 6 COAXIAL CABLE OUTLET 4 THERM05TA1T A"+" INPICATE5 THAT THE A55OCIATEV DEVICE I5 TO BE INSTALLED 50 THAT THE BOTTOM OF THE COVER PLATE 15 1 " ABOVE THE COUNTERTOP BACK5PLA51-1. SIGN: TH15 DOOR TO REMAIN UNLOCKED WHILE BUILDING 15 OCCUPIED o4 04 t2)D WIRE MOLD —C ''i'll 11 1 101:11 , . ..... 111] llii! ICA j [��LECTRICAL POWER PLAN KEY --NOTES---_ I . EXISTING ELECTRICAL PANEL TO REMAIN 2. LOCATION Of FLOOR BOX fOR COMMUNITY TABLE, MUST LOCATE HERE IN ORDER TO ACCOMMODATE ACCESS HATCH WITHIN FIXTURE. PROVIDE DUAL BRANCH CIRCUIT FOURPLEX RECEPTACLE, NON -SWITCHED. 3. FLOOR SAW CUTTING, CONCRETE REMOVAL, INSTALLATION Of DOWELS AND WIRE MESH REINFORCING, RE -POURING 4" CONCRETE SLAB SHALL BE BY THE G.C. TRENCHING, INSTALLATION OF CONDUITS, BACKFILLING * COMPACTION BY E.C. 4. PROVIDE DUAL BRANCH CIRCUIT FOURPLEX RECEPTACLE; (2) OUTLETS SWITCHED (CONTROL FIXTURE LIGHTING), (2) OUTLETS HOT - PROVIDE BLACK ADHESIVE LABEL WITH f4" LETTERING INDICATING "$WITCHED FOR LTG. ADHERED TO HALF OF THE FOURPLEX PROVIDING POWER TO SWITCHED LIGHTING 5. FIXTURE LIGHTS BEHIND AATV WALL MONITOR TO BE NIGHTLIGHT5 G. RECEIPT PRINTER, 20" AFF DEDICATED CIRCUIT (MULTIPLE PRINTERS CAN SHARE THE SAME CIRCUIT). 7. LIGHTING @ BACKWRAP TO BE PROVIDED BY FIXTURE VENDOR, AND SHALL BE SET AS NIGHT LIGHTS 8. PROVIDE SHELF AND POWER/DATA OUTLETS FOR TENANT'S PROVIDED AMPLIFIER AND RETAIL RADIO MEDIA PLAYER ABOVE 4'X 4' PLYWOOD TELCO BACKBOARD. 9, ALL CABLING TO TERMINATE WITHIN 48 PORT PATCH PANEL TO BE LOCATED WITHIN TELCO BOARD. AVAILABLE SPACE REMAINS ON TELCO BOARD FOR DEALERS SWITCHES, ROUTERS, SECURITY AND OTHER INSTALLED BY DEALER. 10. CONVENIENCE OUTLETS MAYBE RELOCATED OR ELIMINATED AS PER DEALER DIRECTION 1 1. FLOOR SAW CUTTING REMOVAL 12, (2) DATA PORTS IN THE CEILING FOR 5HOPPERTRAK FURNISHED AND INSTALLED BY OTHERS. CENTER OVER ENTRY DOOR. 13. PROVIDE REMOTE TRANSFORMER/TIME CLOCK FOR FUTURE EXTERIOR SIGN. 14. PROVIDE DATA/POWER IN CEILING FOR RETAIL WI -FI 5Y5TEM 15, PROVIDE QUAD OUTLET FOR TENANTS WI -FI SYSTEM -�13 51GN: TH15 DOOR TO REMAIN UNLOCKED WHILE BUILDING 15 OCCUPIED TYPICAL OUTLET CONFI&URATION5. ?R.OVIDE ADDITIONAL PORTS IF INDICATED ON THE DRANIN65. NOTE: PROVIDE TOTAL NUMBER OF DATA PORTS AS INDICATED ON THE PLAN PRANINC-75 (TYPICAL) (I D)7 0 (2D)C7 ju (31))17 u TYPICAL OUTLET CONFIGURATION UTILIZING CADDY DEVICE AS INDICATED. PROVIDE TOTAL NUMBER OF DATA PORTS AS INDICATED ON DRAKN65. AATV-IL4 (LEVEL 5 TV kNALL) SWiTCf-IED i (2) COAX (2) DATA FOURPLEX RECEPTACLE (INSTALL kNITH CADDY) + DUPLEX RECEPTACLE 5YVITCH ED SWITCHED MY1U NO WITCHED #' Q DATA FOURPLEX RECEPTACLE. .... OUAD TO BE HALF 5NITCHED FOR LI&HTIN6, HALF D FOR FIXTURE NOT v a USED o ® v CPDaY PART #RBS 16 (TYP) DUPLEX RECEPTACLE / (2) DATA ELECTRICAL NOTES' (`-'EE REFLECTED CEILING PLAN) O D FLOOR ♦ ACC.,E55ORY CAN BE I DIN PLACE OF �:.BOX AVAILABLE.r CONDUIT NOULD TERMINATE AT BOX, AND NOT i _ NOTE: IF LEARNIN& TABLES ARE . BE TABLE.TEMPORARILY USED AS P05 STATIONS, THE 2 CONDUIT 5HOkNN IN ENLAR6F.D PLAN REOUIRED IN AMPLIFIER FROM THE BAC10NRAF TO THE I I THE Hr,>mi, U55, AND AMPLIFIER SHOULD BE I ORDERED , _ °R AS REaUIREV ,NOTE: RECEPTACLES @ BACKJoNRAP AND TABLE 0 AMP iPEDICATEP CIRCUIT. DO NOT ADD OTHER _ O N a MED -BCW EQUAL The written dimensions on this plan supersede scaled distances DO NOT SCALE THE DRAWINGS Any variations from conditions and dimensions shown on the drawings shall be reported to Ronald L. Kief, for resolution prior to proceeding with the work; otherwise, the contractor shall be solely responsible for the cost of any necessary work. '! 0 DAY ROAD DE51GN, LLC RONALD L. KIEF 9825 5W DAY ROAD SHERWOOD, OR 97140 P: 503-320-0918 F: 503-972-1646 RonKief@comca5t.net z W Vj W OL. PROJECT AT * T 5TO RE TIGARD PROMENADE 15532 5W PACIFIC HIGHWAY, STE C-7 TIGARD, OR 97224 5NEET TITLE ELECTRICAL POKER PLAN SCALE I"'411 - 1 "-®1, PAGE NUM13ER A-4 REFLECTED CEILING PLAN INDEPENDENT LIGHT FIXTURE 5UPPORT WIRE PER CODE INDEPENDENT SUPPORT CLIP W/THREADED STUD * NUT ATTACHMENT ERICO PART #IDS OR EQUIVALENT. MIN (4) PER FIXTU RE F12 LIGHT FIXTURE EXI5TING W LIGHT FIXTURE WITH RCP CEILING GRID F4A LIGHT FIXTURE � 8 8 LABEL SWITCH LOCATION, ic, 5ALE5 FLOOR CEILING GRID PLYWOOD4'x 4x 3/4" lamm "wk!!'1111111111111 •f' LIGHT FIXTURE SCHEDULE LEGEND (E) 2 X 4 FLUORESCENT LIGHT FIXTURE 0 (N) RECESSED 1 X 4 FLUORESCENT DIRECT LIGHT FIXTURE NJ (N) REGE55ED 1 X 4 FLUORESCENT LIGHT FIXTURE (EMERGENCY FIXTURE) a EMERGENCY EXIT LIGHT q (N) SURPftGE MOUNTED DIRECTIONAL LIGHT FIXTURE (N) 4'VIA. SURFACE MOUNTED FLUORESCENT FIXTURE P 1 2 REF #3 F1 CEILING PLAN KEY NOTES I . CENTERLINE5 ARE U5ED TO LAYOUT 5TORE5, INCLUDING CEILING, POWER/DATA, FIXTURE5, ETC. AND MU5T BE MARKED AND VERIFIED PRIOR TO 5TART OF CON5TRUCTION, CONTACT PION KIEL^ IF THERE ARE DIMEN51ONAL D15CKEPANCIE5 2. PROMOTIONAL P05TER RAIL5 PROVIDED BY FIXTURE VENDOR, PROMOTIONAL P05TER PROVIDED BY OTHER5 3. 5UR.FACE MOUNTED LIGHT FIXTURE. ELECTRICIAN TO U5E MANUFACTURER PROVIDED 5PACER5 WHEN IN5TALLING TO ACOU5TICAL CEILING GRID/TILE5TO MAINTAIN THE INTENDED REVEAL. 5EE DETAIL 4. ELECTRICIAN TO PLACE LIGHT5 A5 CL05E TO THE RECOMMENDED DIMEN51ON A5 P0551BLE 5. FIXTURE BELOW - 5EE DRAWING # I ON A 2.0 FOR MORE INFORMATION AND EXACT PLACEMENT G, LIGHT FIXTURE5 TO BE CENTERED ON FIXTURE BELOW. ELECTRICIAN TO AIM LIGHT ON CENTER 5HELF OF MWU (IF APPLICABLE) 7. LIGHT TO 51-11 NE ON FIXTURE BELOW 8. LIGHT TO BE CENTERED IN CEILING TILE A5 INDICATED ON PLAN. ELECTRICIAN TO AIM LIGHT 5HINE ON THE CENTER OF THE COMMUNITY TABLE COUNTER 5URFACE 9. LIGHT FIXTUPIE'';FOR WINDOW BANNER TO BE CONNECTED TO EXTERIOR 51GNAGE CIRCUIT. HE #2/A-4.0 10. LIGHT TO BE CENTERED ON FIXTURE BELOW. 1 1. PREFERRED LOCATION FOR MAIN LIGHTING 5WITCH BANK, ALL INTERIOR LIGHT5 TO TERMINATE HERE. 12. PROVIDE (2) DATA PORT IN t -BAR GRID CEILING FOR 5HOPPERTRACK, FURNI5HED AND IN5TALLED BY OTHEK5 13. PROVIDE DATA IN CEILING FOR RETAIL WI -FI 5Y5TEM 14. PAINT 5ALE5 FLOOR CEILING GRID P -2E 15. G.C. TO IN5TALL GREY CEILING TILE5, ACP- I FLOOR TRENCH 3/4" CONDUIT FOR POWER I I " CONDUIT FOR DAT 2 CONDUIT FOR (I) HDMI, (2) U5B ALS IT5 TERMINATE -f ' THE FLOOR BOX 2" CONDUIT STUB UP BEHIND -- FIXTURE (OUT5IDE WALL) =_= FLUSH WITH CONCRETE AM 1 ". rol 19110" 1000 CONDUIT DETAIL (5EE ELECTRICAL FOYSIER PLAN) QTY 5°-511 51- 1 1 1 " 54_ I �j 11 51_[�!P /11_/">t4 51-9 _LII 56_7 51- 11 11- 7 I ,�' It MODEL LAMP DESCRIPTION 21 F4A HALO STATIS L50516-20CMH-I-P-L111-LM50515-L973-AH GE CMI-1120MR16/830/FL CANOPY MOUNTED ACCENT LIGHT, LOCKING TILTAND ROTATION, ON-OFF SWITCH, ALUMINUM DIE-CAST HOUSING LITE ENERGY WITH VERTICAL ELECTRONIC BALLAST, SOFT FOCUS LENS AND HOLDER, SQUARE MONOPOINT CANOPY ACCESSORY. 11 F16 COOPER LIGHTING METALUX GC332-UNV-EB81-U-1X4-MILK WHITE (3) GE F32W/T8/SPX35 VX 4' RECESSED FLUORESCENT DIRECT LIGHT, HIGH REFLECTANCE WHITE POWDER COAT PAINT FINISH, TEXTURED LENS FGWO80 FRONTGLAZE ACRLIC LENS, STANDARD FLANGE DESIGN WORKS WITH MOSTACOUSTICAL CEILINGS 3 F16 COOPER LIGHTING METALUX GC332-UNV-EB81-U-1X4-MILK WHITE (3) GE F32W/T8/SPX35 VX 4` RECESSED FLUORESCENT DIRECT LIGHT, HIGH REFLECTANCE WHITE POWDER COAT PAINT FINISH, TEXTURED LENS FGWO80 WITH EMERGENCY EQUIPMENT FRONT GLAZE ACRLIC LENS, STANDARD FLANGE DESIGN WORKS WITH MOST ACOUSTICAL CEILINGS 3 F12 LITHONIA LE/CS-44120-4X25T8-120 (4) HE F2ST8/SPX35/ECO 48" DIAMETER LARGE SCALE SURFACE MOUNTED LUMINAIRE WITH WHITE ACRLYIC DIFFUSER, 20 GAUGE DIEFORMED STEEL HOUSING, ELECTRONIC BALLAST(S), POLYESTER POWDER COAT MATTE WHITE FINISH. ALL A `ICAL � / `� % EXISTING � 7 — ...___ — i �. _. _. — — — — — — — — — — — — — — — — — BAR ADA USE R.R.. LAY XISTING L UT PQ GHTiNG 51BLE , 174AA F4A rt A— F4A— F� F _ 4A F A 6 ,. - - - - - Ln k F16 F16 1 F16 IF16 Ln i I TT PAA , 6 _T,a t1_ I u r -0 F16 IF16 co LG F16 kA F16 � _ 12�_ I I F, 1 10t, - 2 (E) DEVICE PANIC 111 3 H RA F1 F A F16 F1 F16 u F16 - — - -- O F' A 1 : =icv U5E LA�YO 15TING LI T IF F05 HTING IBLE a) ,r, I , 1 u 2 `� �' j _ (2)C► LG 1 } - F F16 I _ F A 7 F16 A I F4 F16 I I I 174A In k 6 . .. ......... __ L. - -------- REFLECTED CEILING PLAN INDEPENDENT LIGHT FIXTURE 5UPPORT WIRE PER CODE INDEPENDENT SUPPORT CLIP W/THREADED STUD * NUT ATTACHMENT ERICO PART #IDS OR EQUIVALENT. MIN (4) PER FIXTU RE F12 LIGHT FIXTURE EXI5TING W LIGHT FIXTURE WITH RCP CEILING GRID F4A LIGHT FIXTURE � 8 8 LABEL SWITCH LOCATION, ic, 5ALE5 FLOOR CEILING GRID PLYWOOD4'x 4x 3/4" lamm "wk!!'1111111111111 •f' LIGHT FIXTURE SCHEDULE LEGEND (E) 2 X 4 FLUORESCENT LIGHT FIXTURE 0 (N) RECESSED 1 X 4 FLUORESCENT DIRECT LIGHT FIXTURE NJ (N) REGE55ED 1 X 4 FLUORESCENT LIGHT FIXTURE (EMERGENCY FIXTURE) a EMERGENCY EXIT LIGHT q (N) SURPftGE MOUNTED DIRECTIONAL LIGHT FIXTURE (N) 4'VIA. SURFACE MOUNTED FLUORESCENT FIXTURE P 1 2 REF #3 F1 CEILING PLAN KEY NOTES I . CENTERLINE5 ARE U5ED TO LAYOUT 5TORE5, INCLUDING CEILING, POWER/DATA, FIXTURE5, ETC. AND MU5T BE MARKED AND VERIFIED PRIOR TO 5TART OF CON5TRUCTION, CONTACT PION KIEL^ IF THERE ARE DIMEN51ONAL D15CKEPANCIE5 2. PROMOTIONAL P05TER RAIL5 PROVIDED BY FIXTURE VENDOR, PROMOTIONAL P05TER PROVIDED BY OTHER5 3. 5UR.FACE MOUNTED LIGHT FIXTURE. ELECTRICIAN TO U5E MANUFACTURER PROVIDED 5PACER5 WHEN IN5TALLING TO ACOU5TICAL CEILING GRID/TILE5TO MAINTAIN THE INTENDED REVEAL. 5EE DETAIL 4. ELECTRICIAN TO PLACE LIGHT5 A5 CL05E TO THE RECOMMENDED DIMEN51ON A5 P0551BLE 5. FIXTURE BELOW - 5EE DRAWING # I ON A 2.0 FOR MORE INFORMATION AND EXACT PLACEMENT G, LIGHT FIXTURE5 TO BE CENTERED ON FIXTURE BELOW. ELECTRICIAN TO AIM LIGHT ON CENTER 5HELF OF MWU (IF APPLICABLE) 7. LIGHT TO 51-11 NE ON FIXTURE BELOW 8. LIGHT TO BE CENTERED IN CEILING TILE A5 INDICATED ON PLAN. ELECTRICIAN TO AIM LIGHT 5HINE ON THE CENTER OF THE COMMUNITY TABLE COUNTER 5URFACE 9. LIGHT FIXTUPIE'';FOR WINDOW BANNER TO BE CONNECTED TO EXTERIOR 51GNAGE CIRCUIT. HE #2/A-4.0 10. LIGHT TO BE CENTERED ON FIXTURE BELOW. 1 1. PREFERRED LOCATION FOR MAIN LIGHTING 5WITCH BANK, ALL INTERIOR LIGHT5 TO TERMINATE HERE. 12. PROVIDE (2) DATA PORT IN t -BAR GRID CEILING FOR 5HOPPERTRACK, FURNI5HED AND IN5TALLED BY OTHEK5 13. PROVIDE DATA IN CEILING FOR RETAIL WI -FI 5Y5TEM 14. PAINT 5ALE5 FLOOR CEILING GRID P -2E 15. G.C. TO IN5TALL GREY CEILING TILE5, ACP- I FLOOR TRENCH 3/4" CONDUIT FOR POWER I I " CONDUIT FOR DAT 2 CONDUIT FOR (I) HDMI, (2) U5B ALS IT5 TERMINATE -f ' THE FLOOR BOX 2" CONDUIT STUB UP BEHIND -- FIXTURE (OUT5IDE WALL) =_= FLUSH WITH CONCRETE AM 1 ". rol 19110" 1000 CONDUIT DETAIL (5EE ELECTRICAL FOYSIER PLAN) QTY MARK MANUFACTURER MODEL LAMP DESCRIPTION 21 F4A HALO STATIS L50516-20CMH-I-P-L111-LM50515-L973-AH GE CMI-1120MR16/830/FL CANOPY MOUNTED ACCENT LIGHT, LOCKING TILTAND ROTATION, ON-OFF SWITCH, ALUMINUM DIE-CAST HOUSING LITE ENERGY WITH VERTICAL ELECTRONIC BALLAST, SOFT FOCUS LENS AND HOLDER, SQUARE MONOPOINT CANOPY ACCESSORY. 11 F16 COOPER LIGHTING METALUX GC332-UNV-EB81-U-1X4-MILK WHITE (3) GE F32W/T8/SPX35 VX 4' RECESSED FLUORESCENT DIRECT LIGHT, HIGH REFLECTANCE WHITE POWDER COAT PAINT FINISH, TEXTURED LENS FGWO80 FRONTGLAZE ACRLIC LENS, STANDARD FLANGE DESIGN WORKS WITH MOSTACOUSTICAL CEILINGS 3 F16 COOPER LIGHTING METALUX GC332-UNV-EB81-U-1X4-MILK WHITE (3) GE F32W/T8/SPX35 VX 4` RECESSED FLUORESCENT DIRECT LIGHT, HIGH REFLECTANCE WHITE POWDER COAT PAINT FINISH, TEXTURED LENS FGWO80 WITH EMERGENCY EQUIPMENT FRONT GLAZE ACRLIC LENS, STANDARD FLANGE DESIGN WORKS WITH MOST ACOUSTICAL CEILINGS 3 F12 LITHONIA LE/CS-44120-4X25T8-120 (4) HE F2ST8/SPX35/ECO 48" DIAMETER LARGE SCALE SURFACE MOUNTED LUMINAIRE WITH WHITE ACRLYIC DIFFUSER, 20 GAUGE DIEFORMED STEEL HOUSING, ELECTRONIC BALLAST(S), POLYESTER POWDER COAT MATTE WHITE FINISH. The written dimensions on this plan •- d- scaled distances 11 NOT SCALEDRAWINGS Any variations from conditions and dimensions shown on the drawings shall be reported to Ronald L. Kief, for resolution prior to proceeding with the work; otherwise, the contractor shall be solely responsible for the cost of any necessary work. DAY ROAD DE5IGN, LLC RONALD L. KIEF 9825 5W DAY ROAD SHERWOOD, 0R 97 140 P: 503-3 20-09 18 F: 503-972-1848 RonKlef@comoast.net 0 z LL W Uj LL Uj CL P KOJ ECT AT * T 5TO RE TIGARD PROMENADE 15532 5W PACIFIC HIGHWAY, STE C-7 TIGARD, OR 07224 SHEET TITLE REFLECTED GEIL.IN& PLAN SCALE PAGE NUMBER A-5 SALES FLOOR CLG. 12'-0" PAINT LINE OIL FINISH FLOOR 0'-0" OIL SALES FLOOR CLG, 12'-0" FINISH FLOOR 0'-0" O AC r9 4 C P-1 E --I P-1 E ---I P-1 E ---I � I r --rte r -ice N N r -4C r -IC I I 5 U (n Q U m W Y-oo O D U N- F U_ T FE9APKI Uqrlm WIT a I �� Cn Q O N u1 N O M pp U C/E U N rd Y= cc - Y Y22 O V O o�non.4 � d L'; ITIT � a N O O Q fl �U <v �a�a�a�a�a N N f0 m (O D N N N N 'n � 2O J V) LL It I RR_1 P-1 E --I P-1 E ---I P-1 E ---I � I O N N I I 5 U (n Q U m W Y-oo O D U N- F U_ I I �� Cn Q O N u1 N ELEVATION B ELEVATION A SALES FLOOR CLG.P-1 E _=1_ SALES FLOOR C. _ 12'-0" 41 12'-0" IF— OIL PAINT LINE 8'-0., FINISH FLOOR 0'-0" SALES FLOOR CLG.P-1 E_P-4E P. P-1 t _ P -4E 12'-0" ___ 1—=t PAINT LINE 8'-0'- FINISH '-0" FINISH FLOOR ELEVATIONS ( SCALE: 1/4" = V-0" SALES FLOOR ELEVATo- i� ELEVATION C P-4 E FINISH FI RB -1 0'-0" P-4 E SHEET NOTES • PROVIDE FIRE RETARDANT TREATED BACKING/BLOCKING IN WALL, AS REQUIRED. GC TO COORDINATE BACKING/BLOCKING FOR ALL FIXTURE VENDOR -PROVIDED ITEMS. • FOR ALL ADDITIONAL FIXTURE INFORMATION, SEE A-5.0. • REFER TO FINISH LEGEND ON A-2.0 FOR FINISH DESIGNATIONS. FINISH PALETTE P-1 E P -4E ALL WALLS TO HAVE SMOOTH FINISH. RB -1 CPT -1 NOTE: THESE DOCUMENTS CONTAIN INFORMATION PERTAINING TO THE ARCHITECTURAL SCOPE OF WORK ONLY. FOR THIS PROJECT, ENGINEERING DESIGN, DOCUMENT AND SPECIFICATION PREPARATION, AS REQUIRED FOR ALL OTHER DISCIPLINES, HAVE BEEN PREPARED BY OTHERS AND ARE NOT THE RESPONSIBILITY OF THE ARCHITECT/KAMUS + KELLER. INFORMATION INDICATED ON THESE DRAWINGS/DOCUMENTS SHOWING OR REFERENCING MECHANICAL, PLUMBING OR FIRE PROTECTION INFORMATION WHERE IT OCCURS HAS BEEN PROVIDED FOR REFERENCE ONLY. THE ENGINEERING DESIGNER, AS LICENSED AND QUALIFIED PROFESSIONALS, UNDER CONTRACT TO OTHERS, SHALL REMAIN SOLELY RESPONSIBLE FOR ALL DESIGN AND APPLICABLE CODE COMPLIANCE MATTERS RELATIVE TO THEIR RESPECTIVE DISCIPLINES. THIS SHALL INCLUDE ADDRESSING AND RESOLVING ANY PLAN REVIEW COMMENTS RELATIVE TO THEIR SPECIFIC SCOPE OF WORK. THE PROJECT ENGINEERING DESIGNERS SHALL ENDEAVOR TO BRING TO THE ATTENTION OF THE ARCHITECT/KAMUS + KELLER ANY DESIGN CHANGE OR CODE COMPLIANCE ITEMS IMPACTING THE ARCHITECTURAL SCOPE OF WORK AS EXPEDITIOUSLY AS POSSIBLE. ISSUE DATE N O N N 5 U (n Q U m W Y-oo O D U N- F U_ l9 �� Cn Q O N u1 N O M pp U C/E U N rd Y= cc - Y Y22 O V O j N .o Co O N O O Q �U <v N N f0 m (O D N N N N 'n � 2O J V) LL NOT FOR CONSTRUCTION ti i U W W Cn O }' N U 01)ti WHryO Q W U 0 Q U CD Q W N M LO LO T_ These drawings/specifications are the property of Kamus + Keller. They are furnished as contract documents only. The seal(s) and signature(s) apply only to the documents to which they affixed, and expressly displaim any responsibility for all other plans, specifications, estimates, reports or other documents or instruments relating to or intended to be used for any part or parts of the architectural or engineering project. Additionally these drawings and seal(s) shall in no way convey or imply any time of warranty or certification relating to the performance of products and materials beyond those provided by their respective manufacturer. PROJECT NO. 14.0408.00 DRAWN/REVIEWED MS/EC DATE/ISSUE 07.14.2014 SHEET TITLE INTERIOR ELEVATIONS SHEET NO. A-6