Plans (3) BUP2013 00287 0100 00 GENERAL DATA 5. COMPLY WITH USG GYPSUM CONSTRUCTION HANDBOOK AND MANUFACTURER'S RECOMMENDATIONS. INDIVIDUAL ROOMS WITH AN EXHAUST REQUIREMENT GREATER THAN 250 CFM,WILL REQUIRE THE USE OF A ROOFTOP MOUNTED FAN. GENERAL REQUIREMENTS 6. FINISH QUALITY: 24.HVAC TESTING. 1. ALL CONSTRUCTION WORK SHALL BE DONE IN COMPLIANCE WITH THE LATEST EDITION OF THE OREGON AREA PROCESS TRADE NOMENCLATURE a. CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT CONTROL DEVICES,COMPONENTS, " "� STRUCTURAL SPECIALTY CODE,AND ALL OTHER STATE OR LOCAL CODE REQUIREMENTS THAT APPLY. WAREHOUSE TAPE/FINISH COAT• TIGHT DOUBLE EQUIPMENT AND SYSTEMS ARE CALIBRATED,ADJUSTED AND OPERATE IN ACCORDANCE WITH y #3082 2. VERIFY ALL DIMENSIONS AND CONDIT IONS SHOWN ON DRAWINGS AND AT THE EXISTING BUILDING AND OFFICE/OTHER AREAS TAPE/2 FINISH COATS"/ SMOOTH FINISH TAPED APPROVED PIANS AND SPECIFICATIONS. `,t; � MARTIN W. HANSOM NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO STARTING THE WORK. b. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN 3. CONTRACTOR AND ALL SUBCONTRACTORS SHALL PERFORM DUE DILIGENCE INSPECTION OF ALL EXISTING USG"FIRST COAT" SAND AFTER TAPE/FINISH COAT(S) ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. TENANT IMPROVEMENT fO L ' CONDITIONS PRIOR TO SUBMITTAL OF A PROPOSAL.SUBMITTAL OF A PROPOSAL SHALL BE CONSIDERED 7. FINISH EXPOSED INTERIOR GYPSUM BOARD WALLS AND CEILINGS SMOOTH STRAIGHT READY FOR FINISH AS CONFIRMATION THAT SUCH INSPECTION HAS BEEN MADE,AND NO FURTHER COMPENSATION SHALL BE DUE SHOWN ON PLANS. c. A COMPLETE COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SMALL BE PREPARED ANDI I � CLA KAM S, OREGON,y THE CONTRACTOR FOR CLAIMS ARISING AS A RESULT OF FAILURE TO PERFORM SUCH INSPECTION. FILED WITH PACTRUST. 09 53 00 SUSPENDED ACOUSTICAL CEILING 25.13ROJECT CLOSE OUT DOCUMENTS REQUIRED: / f 4. BY SUBMITTING A PROPOSAL,CONTRACTOR AND ALL SUBCONTRACTORS CERTIFY THAT THEY HAVE MINUS 0.5 INCHES OF LEVEL EXAMINED THE SITE AND INCLUDED IN THEIR PROPOSAL ALL WORK NECESSARY TO COMPLETE THE WORK 1. TUNE UP GRID SYSTEM TO WITHIN PLUS OR a. AutoCAD FILE SHOWING AS-BUILT INFORMATION. SCRIBED OR REASONABLY IMPLIED IN THESE DOCUMENTS. THIS INCLUDES BUT MAY NOT BE LIMITED TO 2. BENT OR DAMAGED T-BARS TO BE REPLACED. b. ELECTRONIC PDF FILE OF THE AutoCAD FILE ABOVE. O� O ALL MATERIALS AND INSTALLATION,DISPOSAL OF EXCESS MATERIALS(USEABLE FINISH MATERIALS SHALL BE 3. REPAIR HOLES IN GRID FROM REMOVED WALLS. USE OF ARMSTRONG"BP ES-4"EXPANSION SLEEVE BRIDGEPORT LEFT IN THE TENANT SPACE AS DIRECTED BY PACTRUST),CLEANING AND ALL PREPARATION OF SUBSTRATE ACCEPTABLE. c. HARD COPY OF AutoCAD FILE ABOVE. L,t SURFACES PRIOR TO INSTALLATION,AS WELL AS FINAL CLEAN UR d. OPERATIONS MANUALS FOR ALL EQUIPMENT,INCLUDINGTSTATS. PROJECT 13f)4O 5. IT IS THE INTENT OF THESE CONTRACT DOCUMENTS TO MATCH AND MAINTAIN EXISTING BUILDING 09 8519 RESILIENT FLOORING-SHEET VINYL FLOORING e. COLORED ZONE MAP WITH THERMOSTAT LOCATIONS INDICATED. STANDARDS FOR ALL EXISTING PRODUCTS AND SYSTEMS. UPON DISCOVERY OF A DISCREPANCY TO THIS 1. SEAL THE EDGES OF THE SHEET VINYL FLOORING TO THE CONCRETE FLOOR WITH A CONTINUOUS BEAD OF INTENSION,THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY. APPROVED SEALANT. SET THE 6"VINYL COVE BASE INTO A FRESH BED OF SEALANT TO SEAL THE BASE TO 26 00 00 ELECTRICAL :DESIGN/BUILD 6. FURNISH ALL NEW MATERIALS EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. THE SHEET VINYL. MITER THE CORNERS AND APPLY A BEAD OF SEALANT TO SEAL THE JOINT. GENERAL DISTRIBUTION 7. COORDINATE THE WORK OF ALL TRADES. PROVIDE CARPET"WALK-OFF MATS"TO PROTECT EXISTING 09 6519 RESILIENT FLOORING-VINYL COMPOSITION TILE 1. ALL ELECTRICAL FEEDS TO OUTLET,SWITCHES,ETC.MUST BE VERTICAL DROPS FROM CEILINGS U.N.O. CARPETS. 1. EXTEND FINISH FLOORING UNDER CASEWORK. EXCEPT FOR HORIZONTAL RUNS UNDER WINDOWS AND FIXTURES ON THE SAME STUD. 8. ALL ROOF PENETRATIONS FROM ABANDONED EQUIPMENT TO BE REMOVED. PATCH AND REPAIR ROOF 2. INSTALL TILES IN QUARTER TURN PATTERN. 2. ALL ELECTRICAL FEEDS TO OUTLETS AND DATA BELOW WINDOW SILLS TO BE ROUTED THROUGH BUILDING MEMBRANE AS NEEDED. 09 9123 PAINTING SHELL WALLS. DO NOT FEED FROM PERPENDICULAR INTERIOR PARTITIONS. 9. ALL ROOF WORK TO BE PERFORMED BY PACTRUST APPROVED ROOFING COMPANIES. APPROVED INTERIOR: 3. PROVIDE LABELS AT EACH ELECTRICAL RECEPTACLE IDENTIFYING CORRESPONDING PANEL AND BREAKER. COMPANIES INCLUDE: 3. PROVIDE UPDATED SCHEDULE AT PANEL TO IDENTIFY CIRCUIT BREAKERS. a. ANDERSON ROOFING, (503)294-0202 1. WALLS: . PRIME NEW DRYWALL WITH MILLER'S HIGH-BUILD"SUPER SEAL"PRIMER. 4. VERIFY ELECTRICAL METER AND TAG METER WITH THE TENANTS ADDRESS OR SUITE NUMBER. METER a b. PACIFIC ROOFING (503)640-3163 IDENTIFICATION NUMBER AND TENANT ADDRESS INFORMATION SHALL BE GIVEN TO PACTRUST PRIOR TO PROJECT NARRATIVE c. GRIFFITH ROOFING (503)643-1598 b. NEW AND EXISTING DRYWALL TO BE FINISHED TO ACHIEVE UNIFORM COVERAGE WITH MILLER'S WW OR TENANTS MOVE-IN. 4480 WITH A TIGHT ROLLER STIPPLE FINISH. RESTROOM FINISHES TO BE MILLER'S SIG LATEX ENAMEL. 5. ELECTRICAL CONTRACTOR TO PROVIDE EMERGENCY LIGHTING IN PATH SHOWN ON PLAN EQUAL TO 1-FOOT PROJECT CONSISTS OF REMOVAL OF OFFICE IMPROVEMENTS, NEW DEMISING WALL,AND 10.KEEP THE AREA OF WORK FREE OF GARBAGE AND DEBRIS ON A DAILY BASIS INCLUDING DOCK ACCESS 2. DOORS AND FRAMES: CANDLE. AREAS AND COMMON AREA. FLOORS TO BE SWEPT OR VACUUMED DAILY. UTILITY SPLIT WORK TO 53,137 SF OF OFFICE AND WAREHOUSE SPACE. WORK SHALL 11.PROVIDE ADEQUATE PROTECTION TO ALL EXISTING IMPROVEMENTS INCLUDING BUT NOT LIMITED TO a. NEW HOLLOW METAL-PRIME,SAND,AND FINISH WITH TWO COATS OF SEMI-GLOSS OIL. 6. EXIT LIGHTS:RUUD LIGHTING"PLASTIC LED EXIT SIGN"MODEL EXPBURWH RED LETTERS,WHITE HOUSING, INCLUDE BUT NOT BE LIMITED TO DRYWALL/METAL STUDS, DOORS/FRAMES AND COMMON CORRIDORS AND STAIRS,BUILDING ENTRANCES,SUITE ENTRANCES,ETC. THE CONTRACTOR WILL b. EXISTING HOLLOW METAL-SAND,FILL IMPERFECTIONS WITH RONDO,SAND AND PRIME PATCHES WITH WITH BATTERY BACKUP. PAINTING. ALL WORK TO MEET ADA REQUIREMENTS. BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGES TO EXISTING IMPROVEMENTS DUE TO CONSTRUCTION ALKYD PRIMER,AND FINISH WITH SEMI-GLOSS OIL ENAMEL. 7. WHERE NEEDED,CONTRACTOR TO FURNISH AND INSTALL NEW DRY TYPE TRANSFORMERS TO PROVIDE ACTIVITIES. c. NEW WOOD-PRIME WITH ALKYD OIL UNDER-COATER,SAND,FILL ALL FASTENING HOLES WITH 2O8V/120V POWER FROM THE 48OV277V SYSTEM. SIZE TO BE BIDDER DESIGN. WORK INCLUDED BUT PERFORMED UNDER SEP. PERMIT 12.STORAGE AND STAGING OF CONSTRUCTION MATERIALS SHALL BE LIMITED TO AREAS AS DESIGNATED AT PAINTER'S PUTTY,CAULK ALL CRACKS IN CASINGS AND BETWEEN JAMBS AND WALLS USING DAP LATEX a. TRANSFORMERS TO BE ENERGY STAR LABELED. PRE-CONSTRUCTION MEETING. UNDER NO CIRCUMSTANCES SHALL BUILDING UTILITY AREAS OR ANY OTHER CAULK,AND FINISH WITH SATIN OIL ENAMEL. b. CASE TO BE TOTALLY ENCLOSED WITH LOUVERS TO PREVENT FOREIGN OBJECTS INTO THE INTERIOR. COMMON BUILDING AREA BE USED FOR STORAGE. d. EXISTING WOOD-PREP,REPAIR IMPERFECTIONS,PRIME AS REQUIRED,AND REPAINT WITH SATIN OIL c. ENCLOSED AND VENTILATED,AIR COOLED TYPE,CLASS H INSULATION,DESIGNED FOR 115 DEGREES C FIRE PROTECTION SPR NK I 13.KEEP THE ROOF FREE OF DEBRIS(I.E.NAILS,SCREWS,BOTTLES,ETC.)AT ALL TIMES. ENAMEL. IF FINISH IS NOT PAINTED,TOUCH UP STAIN,SEAL AS REQUIRED,AND RE VARNISH WITH SATIN TEMPERATURE RISE ABOVE 40 DEGREES C AMBIENT TEMPERATURE AT FULL LOAD CONTINUOUS HEATING,VENTILATION&AIR CONDITIONING WORK H 14.ALL DIMENSIONS ARE TO FACE OF GYPSUM BOARD UNLESS OTHERWISE NOTED. VARNISH. OPERATION. EQUIP WITH 2-112 PERCENT ANFC TAPS AND FOUR 2-12 PERCENT BNFC TAPS. MAXIMUM ELECTRICAL WORK, BOTH LINE VOLTAGE AND LOW VOLTAGE ►�•1 15.CONFIRM SIZES OF ALL OPENINGS REQUIRED FOR THE INSTALLATION OF STRUCTURAL,MECHANICAL, 3. CEILINGS: SOUND LEVEL SHALL BE NEMA STANDARD WITH ISOLATION DAMPERS BETWEEN THE CORE AND COIL F+� ELECTRICAL AND PLUMBING WORK PRIOR TO FRAMING OR CUTTING FOR INSTALLATION. a. EXISTING GYP BOARD/PLASTER-SAND,SPACKLE ALL IMPERFECTIONS,SPOT PRIME AND FINISH TO ASSEMBLY AND CASE, 16.LEAVE THE PROJECT CLEAN AND READY FOR OCCUPANCY. ACHIEVE UNIFORM COVERAGE WITH MILLER'S 620008 4480. 9. FOR FLOOR POWER AND DATA ACCESS IN BUILDINGS WITH ACCESS BELOW FLOOR,USE WIREMOLD RC7 b. NEW GYP BOARD /PLASTER -CRIME WITH SUPER SEAL AND FINISH TO ACHIEVE UNIFORM COVERAGE FLUSH POKE-THRU SERIES OR EQUAL. FOR SLAB ON GRADE INSTALLATIONS USE RAC0#5511,2 AT EACH 17.CLEAN ADJACENT EXTERIOR AREA,I.E.WALKS,EXTERIOR GLASS,ETC. LOCATION TO SEPARATE POWER AND DATA WITH 1"CONDUIT FOR POWER AND 2"CONDUIT FOR DATA. WITH MILLER'S 620008 4480. n'c p /� t 18.FILL ALL PAPER AND SOAP DISPENSERS IN RESTROOMS AND BREAK AREAS. 4. GENERAL NOTES: 10.TELECOMMUNICATION SYSTEM BY FUTURE TENANT. BUILDING I 1 V 1 O R MAT(O N 19.PROVIDE"AS-BUILT"DRAWINGS OF THE WORK AT THE CONCLUSION OF CONSTRUCTION."AS-BUILT' 11.LIGHTING ENERGY MANAGEMENT IS REQUIRED IN ALL BUILDINGS. DRAWINGS MAY BE IN THE FORM OF TWO COPIES OF CONSTRUCTION DOCUMENTS MARKED-UP WITH RED a. KEEP ALL HARDWARE,HINGES,AND DOOR KNOBS CLEAN OF ALL PAINT SPLATTERS,DRIPS,OR ROLLER BUILDING OWNER: PACIFIC REALTY ASSOCIATES, L.P. PEN.DELIVER RECORD DRAWINGS TOTHE ARCHITECT. COMPLETE OPERATION AND MAINTENANCE MANUALS SPRAY. 12.OCCUPANCY CONTROL DEVICES SHALL BE LEVITON OR WATT STOP. SHALL BE PROVIDED FOR ALL MECHANICAL,ELECTRICAL AND PLUMBING EQUIPMENT.PACTRUST MAY HOLD b. ALL SURFACES TO BE SANDED BETWEEN COATS,PRIOR TO INSTALLATION OF NEXT COAT. 13.TEST ALL LIGHTING CONTROL SYSTEMS TO ENSURE THAT CONTROL DEVICES,COMPONENTS,EQUIPMENT 15350 SW `SEQUOIA PKWY #3OO O CONTRACTOR'S FINAL PAYMENT UNTIL"AS-BUILT'DRAWINGS AND O&M MANUALS HAVE BEEN RECEIVED c. DURING PROGRESS OF WORK,KEEP JOB SITE CLEAN OF ALL PAINT MATERIALS,RUBBISH,CANS,AND AND SYSTEMS ARE CALIBRATED,ADJUSTED AND OPERATE IN ACCORDANCE WITH APPROVED PLANS AND PORTLAND, ORE 97224 M AND APPROVED. SPECIFICATIONS. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THAY OPERATE O RAGS AT THE END OF EACH DAY. IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. 20.17 IS THE INTENT OF THE CONTRACT DOCUMENTS THAT THE CONTRACTOR PROVIDE A COMPLETE, d. UPON COMPLETION OF WORK,CLEAN ANY PAINT SPLATTER BY USING PROPER METHODS OF WASHING FUNCTIONING PROJECT INCLUDING ALL GENERAL,MECHANICAL AND ELECTRICAL CONSTRUCTION REQUIRED 14.REQUIRED IN DIVISION 15,PROVIDE MONITORING OF HVAC EQUIPMENT PER CODE. (503) 624-6300 (PHONE) �V TO FULFILL THAT INTENT. ALL ITEMS REQUIRED SHALL BE FURNISHED AND INSTALLED,REGARDLESS OF AND SCRAPING,USING CARE i`iOT TO SCRATCH OR DAMAGE FINISHED SURFACES. 15.REMOVE ALL UNUSED DATA AND POWER BOXES AND INFILL WITH GYP BOARD. EXCEPTION-UNUSED DATA WHETHER OR NOT SHOWN ON THE DRAWINGS. e. PROTECT WORK OF OTHER TRADES. BOXES UNDER WINDOW SILLS TO REMAIN. ALL BLANK COVER PLATES TO BE BUILDING STANDARD FINISH. (5O3) 624•-7755 (FAX) N 21.ITEMS OR WORK NOT TO BE FURNISHED OR ACCOMPLISHED BY CONTRACTOR ARE NOTED"N.I.0". f. PROVIDE"WET PAINT'SIGNS AS REQUIRED TO PROTECT NEWLY PAINTED FINISHES. 16.REMOVE ALL UNUSED LOW VOLTAGE WIRING(TELEPHONE AND DATA)FROM THE RECEPTACLE TO THE 22."ALIGN"AS USED IN THESE DOCUMENTS,MEANS TO ALIGN THE FINISHED FACES OF ELEMENTS IN THE SAME 1000 00 SPECIALTIES DISTRIBUTION BOARD.LEAVE PULL STRINGS FROM THE BOX TO THE SPACE ABOVE THE CEILING. A SECTION BLDG. #: 5, 6, 7, & 10 (PTR110) PLANE,EITHER IMMEDIATELY ADJACENT TO ONE ANOTHER OR ACROSS AN OPENING. 10 4418 FIRE EXTINGUISHERS OF THE EXISITNG LOW VOLTAGE WIRE MAY BE LEFT IN LIEU OF A PULL STRING 23.130 NOT DISASSEMBLE SETS OF CONSTRUCTION DRAWINGS.DRAWINGS ARE INTERRELATED. OFFICE LIGHTING1. GROUP RE-LAMP EXISTING FLUORESCENT LIGHTS AS NEEDED. O M 1. FIRE EXTINGUISHER 2A10 BC (WALL MOUNTED OR IN SEMI RECESSED CABINET AS INDICATED ON PLAN) d 24.SUSMIT SAMPLES OR DRAW DOWNS FOR ALL FINISHES REQUESTED TO THE ARCHITECT OF RECORD WITHIN CONST. TYPE.: III-B (FULLY SPRINKLED) F.y A TWO WEEKS OF PROJECT AWARD.PRODUCTS INSTALLED WITHOUT APPROVED SAMPLES ARE SUBJECTTO 2. FIRE EXTINGUISHER CABINET: JL INDUSTRIES ACADEMY SERIES MODELlI C102N10. , ' REPLACEMENT AT CONTRACTOR COST. 2. OFFICE LIGHT FIXTURES- LITHONIA 2PM3N G B 3 32 18113 MVOLT ADVANCE OR EQUAL.(NO SYLVANIA 11 00 00 EQUIPMENT BALLASTS) 3 .� 25.SUBMIT COMPLETE SHOP DRAWINGS FOR MILLWORK,SPECIAL SYSTEMS,MECHANICAL,ELECTRICAL AND 1. DOCK LEVELERS: IN ALL CASES INCLUDE TRANSITION PLATE RHE2001/4 X 108 X 12 WITH BEND WELDED TO WAREHOUSE LIGHTING OSSC SECTION 5OZ UNLIMITED AREA BUILDINGS VJ a M M PLUMBING SYSTEMS(INCLUDING FIRE PROTECTION SYSTEMS). SUBMIT A MINIMUM OF TWO COPIES OF ALL EXISTING ANGLE IRON AND BOLTED TO FLOOR AT INSIDE EDGE 8"O.0 . REMOVE EXISTING DOCK BUMPERS. SHOP DRAWINGS FOR REVIEW AND APPROVAL TO THE ARCHITECT OF RECORD.ARCHITECT WILL RETAIN ONE SEE PIAN FOR LOCATIONS. PACTRUST APPROVED OPTIONS INCLUDE: 1. LITHONIA FOUR LAMP,IS 454L MVOLT ADVANCE,54W,T5HO FLUORESCENT 277V.LIGHT LEVEL 10TO 15 FC AT h f COPY AND ONE COPY WILL BE RETURNED TO THE CONTRACTOR. 30"A.F.F. (EMERGENCY BATTERY PACK OPTION EL14)MOTION SENSOR ON EACH LIGHT. THE COMBINED AREAS OF BUILDINGS 5, 6, 7, AND 10 IS �j ,;;O 26.THE DESIGN OF FIRE PROTECTION SYSTEMS IS THE RESPONSIBILITY OF THE FIRE PROTECTION SYSTEMS a. RITE-MITE EDGE OF DOCK LEVELER.72"w 30k 12"LIP PROJECTION W/12 X 13 BUMPERS AND BLOCKS. �' F.1 CONTRACTOR.ALL FIRE PROTECTION SYSTEMS SHALL BE DESIGNED BY PROFESSIONAL ENGINEER b. NEVERLIFT EDGE OF DOCK LEVELER MODEL NL723o WITH BUMPERS. 269,538 SF AND ARE BEING TREATED AS ONE BUILDING. �" Iy �" LICENSED BY THE APPROPRIATE JURISDICTION FOR THE DESIGN OF THIS TYPE OF SYSTEM. COORDINATE 12 00 00 FURNISHINGS ALL BUILDINGS ARE FULLY SPRINKLED ACCORDING TO INTERFACE WITH EXISTING BUILDING SYSTEMS AND WITH ARCHITECT. ALL SPRINKLER HEADS SHALL BE CENTERED IN CEILING TILE(OR 2 x 2 MODULE OF A SECOND LOOK{I TYPE OF CEILING TILE WHERE 1. CLEAN/REFURBISH EXISTING BUILDING STANDARD BLINDS AT ALL EXTERIOR GLASS. OSSC SECTION 903.3.1 .1 AND ARE SURROUNDED BY PUBLIC APPLICABLE). LOCATION OF THOSE IN GYPSUM BOARD CEILINGS SHALL BE PRE-APPROVED IN WRITING BY 2. INSTALL BUILDING STANDARD ADDRESS AND/OR SUITE NUMBER LABELS TO ALL EXTERIOR DOORS. 27.COORDINATE ALL CONSTRUCTION SEQUENCING WITH PACTRUST AND SCHEDULE ALL SERVICE 2100 00 FIRE SUPPRESSION :DESIGN/BUILD WAYS AND YARDS GREATER THAN 60' THE ARCHITECT PRIOR TO INSTALLATION. . INTERRUPTIONS OUTSIDE NORMAL BUSINESS HOURS TO MINIMIZE INCONVENIENCE TO CURRENT TENANTS. 1. ADJUST EXISTING SPRINKLERS BELOW SUSPENDED CEILING PER CODE. SPRINKLER HEADS SHALL BE GENERAL CENTERED IN 2 X 2 CEILING TILE.LAYOUT OF SPRINKLERS BY CONTRACTOR. SPRINKLER LAYOUT IN ALL OSSC SECTION 508.3.2.2 NONSEPERATED OCCUPANCIES. HARD CEILING AREAS(GYPSUM BOARD/PLASTER)TO BE REVIEWED AND APPROVED BY ARCHITECT PRIOR TO �-•. 1. REMOVE ALL EXISTING VCT,SHEET VINYL,ETC.IN AREAS WHERE NEW FLOOR COVERING IS SPECIFIED PRIOR INSTALLATION. TO INSTALLATION OF NEW FLOORING. 2. IN NEW CEILING GRID SYSTEMS OVER 144 SF PROVIDE FLEXIBLE HEADS FOR MINIMUM SEISMIC MOVEMENT. AREA IS UNLIMITED '- 2. ALL ROOF PENETRATIONS FOR ELECTRICAL,LOW VOLTAGE,GAS PIPING,ETC.SHALL BE SLEEVED THROUGH NO"OOPS RINGS ALLOWED". A LEAD ROOF JACK,CLAMPED WITH A STAINLESS STEEL CLAMP AND SEALED WITH VULKEM 921 3. PROVIDE AUTOMATIC FIRE SPRINKLER FLOW INDICATOR SIEMENS CU-MHU-MCS-W OR EQUAL.SEE PLAN FOR O POLYURETHANE SEALANT. SILICONE SEALANT NOT PERMITTED. C 05 00 00 METALS 23 00 00 HVAC :DESIGN/BUILDT INFORMATION (� 1. MISC.NON-GAUGE METAL SUPPLEMENTAL TO STEEL DOCK STAIR. GAS MOMR TENAN a �-+ 2. PIPE RAILINGS FOR ADA RAMP. 1. CONTRACTOR TO VERIFY GAS METER AND TAG METER WITH THE TENANTS ADDRESS OR SUITE NUMBER, TENANT: BRIDGEPORT DISTRIBUTION �i, 08 10 00 DOORS AND WINDOWS METER IDENTIFICATION NUMBER AND TENANT ADDRESS INFORMATION SHALL BE GIVEN TO PACTRUST PRIOR 1. RE-USE EXISTING DOORS AND FRAMES WHERE POSSIBLE TO TENANTS MOVE-IN. O 2. APPROVED DOOR,FRAME,AND HARDWARE SUPPLIERS INCLUDE: HVAC-eiD PROCEDURE OCCUPANCY: TYPE AREA REQ. EXITS � a. BAXTER AND FLAMING. (503)225-0488 1. FOR BIDDING PURPOSES,THE HVAC CONTRACTOR WILL ASSUME THAT EXISTING HVAC EQUIPMENT IS IN B 2,841 SF 1 Z PROPER WORKING ORDER. b. D&D DOOR (503)205.5533 2. INVENTORY EXISTING H.V.A.C.RW-70 Q P UNITS AND SUBMITTDARCHITECTACONDITIONS REPORT OF EACH S-2 50,296 SF 2 0 c. BENSON INDUSTRIES (503)907-2200 UNIT TOTAL 53,137 SF d. GRANT SUPPLY (360)887-0647 3. LIST TONNAGE OF EACH UNIT. 3. DOOR AND RELITE FRAMES SHALL MATCH EXISTING. SUBMITTAL REQUIRED PRIOR TO ORDERING MATERIAL. HVAC-DESIGN PROCEDURE NOTE: SECOND FLOOR AREA IS UNOCCUPIED AT THIS TIME. NEW FRAMES TO BE FACTORY FINISH CUSTOM COLOR. USE EXISTING AND/OR NEW EQUIPMENT TO DESIGN MECHANICAL H.V.A.C.SYSTEM PER DESIGN STANDARDS IMPROVEMENTS WILL BE ON FUTURE PERMITS. 4. EXTERIOR DOORS AND FRAMES TO BE HOLLOW METAL. FRAMES OF ONE-PIECE WELDED CONSTRUCTION, LISTED BELOW. 14-GA.GALV.SHEET STEEL. DOORS,SDI-100,GRADE 11,SEAMLESS EDGES,16 GA.GALV.SHEET STEEL. PRIOR TO AWARD OF CONSTRUCTION CONTRACT,H.V.A.C.CONTRACTOR SHALL SUBMIT TO ARCHITECT FOR FABRICATE DOORS AND FRAMES WITH HARDWARE REINFORCING WELDED IN PLACE. REVIEW AND APPROVAL A FULL DESIGN SCHEMATIC FOR THE TENANT SPACE INCLUDING BOTH 5. FIELD VERIFY EXISTING DOOR,FRAME AND HARDWARE FINISH PRIOR TO ORDERING. ALL NEW DOORS, NEW/RENOVATED WORK AND SYSTEMS UNTOUCHED BY THE TENANT IMPROVEMENT AS APPLICABLE. FRAMES AND HARDWARE TO MATCH EXISTING BUILDING STANDARDS. INCLUDE THE FOLLOWING: 6. ALL INTERIOR DOORS SHALL BE SOLID CORE WOOD UNLESS NOTED OTHERWISE. a. DUCTING AND SIZES 7. DOOR HARDWARE SHALL BE SCHLAGE AL SATURN OR D RHODES SERIES U.N.O. b. SUPPLY AND RETURN LOCATIONS AND CFM 8. ALL DOOR HARDWARE SHALL BE INSTALLED WITH A 5"BACKSET. c. ROOF EQUIPMENT,SIZES AND LOCATIONS 9. DOOR FINISH SUBMITTAL:CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR DOOR FRAMES,DOOR d. UNITS REQUIRING DUCTED SMOKE DETECTION HARDWARE AND DOORS AS WELL AS A CONTROL SAMPLE OF THE FINISHED DOOR SKIN W/STAIN AND FINISH e. THERMOSTAT LOCATIONS AND ZONEIUNIT ASSOCIATED THEREWITH APPLIED(IF NEW DOORS ARE BEING PROVIDED). BEFORE FINISHING OF DOORS IS COMMENCED ARCHITECT AREA OF WORK SHALL APPROVE CONTROL SAMPLE. FINISHED PRODUCT IS SUBJECT TO REJECTION BY ARCHITECT IF THIS f. ANY SUPPLEMENTAL EXHAUST FANS OR SPECIAL SYSTEMS PROCESS IS NOT FULLY ADHERED TO AND FIELD PRODUCT DOES NOT MATCH THE APPROVED CONTROL SAMPLE. 9, ZONE DIAGRAM 'Nr�RSrAT� r S 10.ALL INTERIOR GLAZING SHALL BE TEMPERED. HVAC DESIGN STANDARDS m A O 11.DEAD BOLT LOCKS AT NEW EXTERIOR DOORS TO BE INSTALLED WITH A SCHLAGE MORTISE DOUBLE THE FOLLOWING ARE MINIMUM DESIGN STANDARDS: ��` 4 8 CYLINDER 20-013C "C'KEYWAY;SOLID BRASS;WITH ADAMS-RITE CAM AND COMPRESSION RING 1 1/g'LENGTH 1. 350 SQUARE FOOT PER TON. A N HARDENED CYLINDER GUARD RING KEEDEX K-24. FINISH TO MATCH BUILDING STANDARD. o FP 1 LAKE oswE WITH HARD2. ADDRESS LOADS BY SPECIFIC LOCATION AND USE AS WELL AS CRITERIA PROVIDED TO PACTRUST BYan 12.PATCH AND REPAIR ALL HOLES OR DAMAGE TO EXISTING STORE FRONT WINDOWS AND DOORS.TOUCH UP TENANT PRIOR TO CONSTRUCTION: EXIT 2sa m d �o�ys 3 7 10 T� Sa�EM FINISH FOR AS NEW LOOK. a a. EXTERIOR EXPOSURE AREA,. 13.TOUCH UP ALL EXISTING INTERIOR DOORS AND FRAMES FOR AS NEW LOOK. b. INTERIOR AREAS,SIZE AND USE \ J P 15 2 � 6 14 OREGON 14.OVERHEAD DOORS;WAYNE DALTON THERMOSPAN 125,EXTERIOR WHITE/STUCCO. FLUSH STEEL INSULATED, c. CONFERENCE/TRAINING ROC%IS 2"THICK;STANDARD LIFT OPERATING STYLE WITH TRACK AND HARDWARE. OPERATION;PULL ROPE FOR d. BUSINESS DOORS TO 10'TALL,CHAIN HOIST FOR TALLER DOORS. COMPUTER/SERVER AND TELEPHONE ROOMS TO HAVE PROVISION FOR LOW AMBIENT OPERATION 1 1 PARK I 15.TUNE UP EXISTING OVERHEAD DOORS FOR SMOOTH OPERATION. WORK INCLUDES: AND 24-HOUR USE. 18 � 5 12 � 16 3. SYSTEM DESIGN CRITERIA-SIZE FOR 3-5 TON UMTS BASEDUSE&EXPOSURE CRITERIA. a. ADJUST OVERHEAD SPRING TENSION TO MEET MANUFACTURER'S SPECIFICATIONS. PACKAGED OR SPLIT SYSTEM EQUI?MEUfaMENT GREATER THAN 5TONS SHALL BE SPLIT INTO MULTIPLE ZONES. b. REPLACE TOP AND BOTTOM DOOR SEALS AS NEEDED. VAV OR WATER SOURCE HEAT PUMP SYSTEMS GREATER THAN 3TONS SHALL BE SPLIT INTO MULTIPLE c. REPLACE BENTTRACKS AND PANEL SECTIONS. ZONES. BUILDING LOCATION d. REPLACE ROLLERS AND HINGES AS NEEDED. 4. ALL ENCLOSED ROOMS OR OFFICEr`TO HAVE DUCTED SUPPLY&RETURN GRILLES. e. REPLACE ROPES AS NEEDED. 5. VACANT SPACE SHALL HAVE DEDICATED GAS SERVICE FOR FUTURE BUILD-OUT OR FREEZE PROTECTION. LOCATION MAP f. LUBRICATE ROLLERS 6. UNITS: LENNOX,TRANE,YORK OR CARRIER-71/2-TON MAXIMUM UNIT SIZE. ANY UNIT IN EXCESS OF 712 Z TONS SHALL HAVE SPECIAL APPROVAL BY BUILDING OWNER. Z A-1 NOT TO SCALE 09 00 00 FINISHES 7. HVAC UNITS WITH EQUAL TO OR GREATER THAN 5-TONS TO HAVE DUCT SMOKE DETECTORS AND BE F� GENERAL CONNECTED TO A MONITORING STATION WITHIN THE BUILDING. 1. CLEAN,SEAL AND WAX ALL RESILIENT FLOORS PER MANUFACTURERS SPECIFICATIONS. 8. ROOFTOP UNITS SHALL BE PLACE.. 24'MINIMUM FROM ROOF EDGE TO CENTER OF UNIT. MULTIPLE UNITS 2. SUBMIT SAMPLES OR DRAW DOWNS FOR THE FOLLOWING: SHALL BE PLACED SYMMETRICALLY IN A LINE BASED ON STRUCTURAL CALCULATIONS BY ENGINEER. 9. CURBS: 14"CURBS. ASSEMBLED AD LEVELED TO ROOF,ANCHORED TO STRUCTURAL MEMBERS BELOW a. FLOOR COVERINGS AND BASE ROOFING. b. PLASTIC LAMINATES a. PROFESSIONALLY ROOF IN ALL CURBS AND PENETRATIONS BY PACTRUST APPROVED ROOF c. ALL NATURAL WOOD(INCLUDING DOORS AND CASEWORK) CONTRACTOR. SEE DIVISION 1 GENERAL NOTES THIS PAGE. d. PAINT b. UNIT MUST BE LEVEL,SEALED WITH NO AIR LEAKS AND COUNTER FLASHED. e. TILE,MARBLE,GRANITE,STONE,AND GROUT c. CONDENSATE MUST BE TRAPPED AT UNIT. f. TOILET PARTITIONS 10.SEISMICALLY ATTACH UNIT TOCUR6 IN CODE-APPROVED METHOD. O g. HARDWARE 11.ALL GAS PIPING SHALL BE STANDARD BLACK STEEL PIPE W/SUPPORTS PER CODE. PIPING SHALL BE RUN 3. EXTEND FINISH FLOORING UNDER ALL NEW CASEWORK INSIDE OF BUILDING W/LEAD FLASHINGS AT ROOF PENETRATIONS. LEAD ROOF JACKS TO BE SEALED AND CLAMPED(S.S.WORM GEAR). ,�~y 09 2100 GYPSUM BOARD 12.ALL EXISTING AND NEW GAS PIPING EXPOSED TO THE EXTERIOR TO BE PROTECTED FROM RUST AND GENERAL CORROSION WITH OIL BASED PAINT(COLOR GREY). Q 1. ALL GYPSUM BOARD TO BE A MINIMUM OF 51W THICK VERTICALLY ATTACHED TO METAL STUDS 24"O.C.WITH 13.LOW VOLTAGE IN SEALTITE CONDUIT FROM BELOW ROOF LINE DIRECT TO UNIT. DO NOT EXCEED BEND 1"TYPE S-12 SCREWS 12"O.C.UNLESS OTHERWISE NOTED. RADIUS MANUFACTURER'S GUIDELINE. � N I ISH COATS WITH SANDING BETWEEN 1 .ECONOMIZER TO MEET CODE AND AS FOLLOWS: 2. ALL OFFICE GYPSUM BOARD TO RECEIVE ONE TAPE COAT AND TWO F 4 N FINISH COATS. APPLY USG SHEETROCK BRAND FIRST COAT. PAINT AS INDICATED. a. 6 TONS AND ABOVE MUST HAVE ECONOMIZER. 3. ALL OTHER GYPSUM BOARD TO RECEIVE ONE TAPE COAT AND ONE FINISH COAT WITH SANDING AFTER FINISH b. BAROMETRIC RELIEF ON 5-71/2 TON UNITS. Q COAT. PAINT AS INDICATED. � � O 4. ALL ONE HOUR RATED WALLS(WHERE APPLICABLE): ONE LAYER 5/S'TYPE X GYPSUM WALLBOARD,EITHER C. 8 TONS AND ABOVE MUST HAVE POWER EXHAUST. SIDE OF METAL STUDS SPACED AT 24"O.C. FASTEN d. 11/2 THRU 4-TON OSA INTAKE WITH DAMPER. z A I T ANGLES OR PARALLEL TO FRAMING ON EACH S DE ATRGH E O � z � Q WITH 1"TYPE S DRYWALL SCREWS 8"O.C.TO VERTICAL EDGES AND 12"O.C.TO TOP AND BOTTOM RUNNERS 15.ALL UNITS TO MEET OR EXCEED CURRENT ENERGY EFFICIENCY CODE REQUIREMENTS. AND INTERMEDIATE STUDS. STAGGER ALL VERTICAL AND HORIZONTAL JOINTS 24 O.C.(OR ONE STUD 16.DROP CANS TO FULL SIZE OF UNIT CURB OPENING. MINIMUM 26 GAUGE WITH SUPPLY AIR. EDGES OFSUPPLY SPACING),EACH SIDE AND OPPOSITE SIDES. AIR SEALED. DROP CANS TO BE EXTENDED TO WITHIN Z OF CEILING. t W O H 5. IN FINISHED SPACES FURR-OUT BUILDING COLUMNS AND EXTERIOR WALLS WITH 5/8"GYPSUM BOARD OVER METALSTUDS. ITDISTRIBUTION DUCTWORK: O •�-+ P. 6. PROVIDE ACOUSTIC GASKETS WHERE WALL INTERSECTS MULLIONS OR GLAZING. a. SPIRAL ONLY IF EXPOSED. 7. AT ALL EXISTING WALLS,REMOVE ALL NAILS,SCREWS,FASTENERS,ETC.LEFT BY PREVIOUS TENANT AND b. 26 GAUGE OR TO SMACNA STANDARDS IF PIPE IS CONCEALED ABOVE DROP OR HARD CEILING. VISION PATCH HOLES READY FOR PAINT. c. WRAP CONCEALED SUPPLY DUCTWORK IN NOWCONDITIONED AND SEMI-CONDITIONED SPACE WITH 8. UPON REMOVAL OF WALL BASE,REMOVE RESIDUAL ADHESIVE AND PREP WALL TO PAINT READY CONDITION. MINIMUM R4.2 INSULATION W.F H FSK BARRIER. WALL CONSTRUCTION MATERIALS d. HANGERS 12 GAUGE WIRE 04 18-GAUGE 1"WIDE STRAP. EXPOSED DUCT MUST HAVE ALLTHREAD AREA OF WORK 1. PROVIDE STUDS HANGERS AND FULL DIAMETER STRAP UP TO 19'0. LARGER THAN 18"MUST HAVE SADDLE TYPE TRACKS,BRACING,FASTENING AND OTHER ACCESSORIES NECESSARY FOR COMPLETE CI-Ap#p. l� "t 1 INSTALLATION. 2. FRAMING MEMBERS SHALL HAVE THE STRUCTURAL PROPERTIES INDICATED WHERE PHYSICAL STRUCTURAL e. BRANCH DUCTS SHALL BE PLUMB AND SQUARE(NO OCTOPUS). TEES SHALL BE MAXIMUM OF 45 DA-1 BUILDING PLAN " 2' PROPERTIES ARE NOT INDICATED,THEY SHALL BE AS NECESSARY TO WITHSTAND ALL IMPOSED LIVE LOADS. DEGREES. DESIGN FRAMING IN ACCORDANCE WITH ANSI SG-M. L EACH BRANCH DUCT TO HAVE BALANCE DAMPER IN Y BRANCH. 3 SCALE 1"=30' 4. 3. COLD-FORMED FRAMING SHALL BE GALVANIZED METAL CONFORMING TO ASTM A446/A 446 M GRADE A(33000g. ALL DISTRIBUTION DUCT WORK TO BE INSTALLED MIN.24"ABOVE FINISH CEILING. PSI)G60. 18.FLEX DUCT WILL BE NO LONGER THAN V FROM RIGID DUCT DOWN TO DIFFUSER. 5. 4. PROVIDE THE LISTED GYPSUM BOARD PRODUCTS BY U.S.GYPSUM,GEORGIA PACIFIC,NATIONAL GYPSUM OR 19.DIFFUSERS: AN APPROVED EQUAL. a. SUSPENDED CEILING SYSTEM(T-BAR)-PERFORATED FACE ADJUSTABLE CURVED BLADES-DESIGN CITY OF TIGARD 6. 5. STANDARD GYPSUM BOARD SHALL BE TYPE'X',5/8"THICK WITH TAPERED EDGES CONFORMING TO ASTM TITUS PCS SUPPLY AND TITUS PAR RETURN OR APPROVED EQUAL C-36' b. GYP.BD.CEILING;SUPPLY-CURVED BLADE W/OBD DESIGN TITUS 250;RETURN-BAR TYPE-DESIGN r rC Occupancy Typo d -� Approved.."....=.................[�-�� 7. 6. WATER RESISTANT GYPSUM BOARD SHALL BE 5/8"THICK WITH TAPERED EDGES. CONFORMING TO ASTM TITUS 350;EXHAUST-METAL OR ALUMINUM-1/2"x 12"EGG CRATE DESIGN TITUS 50F. C-83o. � Conditionally Approved..............[ ] 1 ERROCK BRAND AQUATOUGH INTERIOR PANEL FROM FLOOR 7048"A.F.F. c. ALL SUPPLY REGISTERS TO HAVE MANUAL VOLUME DAMPERS LOCATED IN DUCT AT/OR NEAR CLOSEST Conupancy 7. AT TOILET ROOMS USE 5/8"USG F B WYE BRANCH. ON WALLS BEHIND OR ADJACENT TO PLUMBING FIXTURES. NO SUBSTITUTES.(EXCEPTION:EXCEPTION AT Construction Typo See Letter to:FC I Now_... ..,..+"..[ ] • LOCATIONS TO RELIEVE PLASTIC LAMINATE OR TILE WAINSCOT.) d. CLEAN OR REPLACE ALL SUPPLY AND RETURN AIR GRILLS AND THEIR HOUSINGS AT PROJECT Rated Corridor oft-ow AL1 1 )d S. AT TILE WAINSCOT LOCATIONS INSTALL CEMENT BACKER BOARD'IV THICK WITH SQUARE,REINFORCED, COMPLETION. Y TYPE THERMOSTATS TO BE REPLACED. NEW THERMOSTATS TO BE )Energy Cods Permit Nu ber• - --- SMOOTH EDGES. PROVIDE DUROCK BRAND CEMENT BOARD OR APPROVED EQUAL. 20.THERMOSTAT: ALL EXISTING MERCUR E � � 7 - DRAWN BY: HONEYWELL COMMERCIAL GRADE 1/IS/ONPRO 8000 TOUCH SCREEN MbDEL T88210U100.9 WHERE POSSIBLE Accessibility Add SS: By: >'z1tC: R.M.T. 9. AT FRP,PLASTIC LAMINATE,ETC.,WAINSCOT PANELING INSTALL WATER-RESISTANT GYPSUM BOARD. APPROVED SUBSTITUTE: TOTAL-LEVE SIGNATURE COMMERCIAL THERMOSTAT MODEL NO P374-28W -7 DAY 10.TRIM ACCESSORIES SHALL COMPLY WITH ASTM C-1047. PROGRAMMABLE WITH LOCKOUT FUNCTION-AUTO CHANGEOVER ONLY. MOUNT AT ADA HE (MAY REQUIRE CHANGING HEIGHT AT"REPLACEMENT"LOCATIONS). CONTRACTOR SHALL PROGRAM 11.USE GEORGIA PACIFIC DENSGLAS GOLD ON EXTERIOR FACE of EXTERIOR WALLS AND COAT WITH STO FINISH , pCQVEd plans 11/20/13 THERMOSTATS AND BALANCE SYSTEM. shall be on JOb site. PERMIT SET SYSTEM. 21.THERMOSTAT LOCATIONS TO BE REVIEWED BY ARCHITECT PRIOR TO INSTALLATION. WALL CONSTRUCTION EXECUTION 22.WAREHOUSE HEAT: 1. FASTEN FRAMING MEMBERS TOGETHER BY WELDING OR BY USING SELF-DRILLING OR SELF TAPPING SCREWS. WELDING SHALL CONFORM TO AWS D13 WELDING PROCEDURE. ELECTRODES AND SCREW a. GAS FIRED UNIT HEATERS USED IN NON-CONDITIONED AREAS SHALL COMPLY WITH CURRENT STATE CONNECTIONS SHALL BE AS REQUIRED AND INDICATED IN THE DESIGN CALCULATIONS. DO NOT FIELD WELD ENERGY CODE REQUIREMENTS. PROVIDE ADJUSTABLE TSTAT FOR EACH UNIT. OFFICE C MATERIALS LIGHTER THAN 18 GA. 23.EXHAUST FANS: 2. PROVIDE ACCURATELY ALIGNED RUNNERS AT TOP AND BOTTOM OF PARTITIONS. ANCHOR TRACKS AS a. CEILING MOUNTED EXHAUST FANS SHALL HAVE A MINIMUM PERFORMANCE TO MEET THE CURRENT INDICATED IN THE DESIGN CALCULATIONS. BUTT WELD JOINTS IN TRACKS OR SPLICE WITH STUD INSERTS. CODE REQUIREMENTS INCLUDING INTEGRAL BACKDRAFT DAMPER AND VENTING TO THE EXTERIOR. FASTENERS SHALL BE AT LEAST 3 INCHES FROM THE EDGE OF CONCRETE SLABS. COOK GEMINI SERIES 100 OR EQUAL;80 CFM WITH A SONE RATING OF 1.6 OR LESS,100 CFM WITH A 3. CUT STUDS SQUARE AND SET WITH FIRM BEARING AGAINST WEBS OF TOP AND BOTTOM TRACKS. POSITION SONE RATING OF.9 OR LESS,200 CFM WITH A SONE RATING OF 1.6 OR LESS. STUDS VERTICALLY IN TRACKS AND SPACE AS INDICATED IN DESIGN. DO NOT SPLICE STUDS. PROVIDE AT b. SINGLE FIXTURE RESTROOMS,JANITOR'S CLOSETS OR SINGLE SHOWER ROOMS TO HAVE CEILING LEAST TWO FULL HEIGHT KING STUDS AT DOORS AND OTHER OPENINGS 2 FEET WIDE OR LARGER. PROVIDE MOUNTED EXHAUST FANS,WIRED PER DIVISION 16 AND SWITCHED WITH THE LIGHTS. JACK STUDS OVER OPENINGS,AS NECESSARY,TO MAINTAIN INDICATED STUD SPACING. PROVIDE TRIPLE c. MULTIPLE FIXTURE RESTROOMS,COMBINATION RESTROOM&SHOWER,AND LOCKER ROOMS TO HAVE AND BOTTOM TRACKS BY WELDING OR SCREWING BOTH FLANGESGES TO THE TRACKS. STUDS AT CORNERS,POSITIONED TO RECEIVE INTERIOR AND EXTERIOR FINISHES. FASTEN STUDS AT TOP ROOFTOP MOUNTED EXHAUST FAN,FACTORY CURB AND BACKDRAFT DAMPER,WIRED PER DIVISION 16, CONTROLS AS REQUIRED BY DESIGN.COOK ACE-D SERIES OR EQUAL 4. INSTALL ALL INTERIOR AND EXTERIOR GYPSUM BOARD PRODUCTS AND ACCESSORIES AS REQUIRED FOR BUII,DING DEPARTMENT USE THE PROJECT. d. SPECIALTY ROOMS REQUIRING EXHAUST SHALL MEET THE ABOVE MINIMUM REQUIREMENTS- #3082 MARTIN W. HANSON ' t Zf1C LA KAM S, OREGON, BLDG.STRUCTURE ABOVE CAULKING IN 1/2'SPACE ff� 1 O� ------------- DEFLECTION CHANNEL Li L cl 0 I NEW OPENING. PROJECT #13640 CENTER LINE OF STUD 6'MTL.STUDS @ 24'O.C. ONE LAYER 516'SHEETROCK BRAND FIRECODE CORE GYPSUM PANEL ON EACH co Lu SIDE OF METAL STUDS 24"O.C.WITH TYPE S DRYWALL SCREWS a O.C.AT VERTICAL EDGES AND 12"O.C.TO TOP AND BOTTOM RUNNERS AND INTERMEDIATE STUDS. STAGER ALL vr\- JOINTS 24 O.C.VERTICAL AND HORIZONTAL BATT INSUL.PER PLAN ❑ ❑ ❑ 4'RUBBER BASE-TYP. E.y ATTACH BOTTOM TRACK TO FLOOR WITH POWDER DRIVEN ANCHORS AT 12'O.C. r l FINISH PER PLAN F+�1 71 4' H 2 FULL HEIGHT WALL SECTION W/ INS. x A-2 SCALE 1" = F-0" o M • �N dQ O E^ f ❑ ❑ ❑ ~4 00 � a a a o C7 Z RACKING PERMIT Q AND INSTALLATION OF-Me BY OTHERS Q ❑ ❑ ❑ Q 0 DEMO OFFICE AS SHOWN. - I NEW 16' X 12' OPENING. C, Lj REMOVE WINDOWS AND INSTALL NEW OVERHEAD DOOR. N Q1 z Q z CPQ 0 o O O z z �® � U Ooh INSTALL (2) EDGE OF DOCK 0-i "o O LEVELERS. O LOCATIONS T.B.D. REVISION Fo_1 ------------------ ------------®------------------------------------------------------------------ ----------------------------------------------------------------- l. 2. 3 EXSITING OFFICE TO = 4. REMAIN. - � 5. REMOVE SPECIAL 6. ELECTRICAL AS SHOWN CONSTRUCTION LEGEND - rr 7. CLEAN SPACE AND RE-PAINT. a EXISTING TO REMAIN g EXISTING TO BE REMOVED ® A_2 NEW STANDARD WALL TO ROOF STRUCTURE DRAWN BY: (E) ADTR.M.T. (E} POWER (E)) TELE. a O DISTRIBUTION BOARD Ih DUPLEX RECEPTACLE11/20/173 e ELECTRICAL PANEL T SET FOURPLEX RECEPTACLE POWER J-BOX PERMIT ! - _ BRIDGEPORT - EXISTING r ' 16620 SW 72ND AVE. o� DEDICATED OUTLET FLUSH MOUNT FLOOR MONUMENT W/POWER AND DATA 25,744 SF TOTALEXISTING ELECTRICAL TO REMAIN FER FIRE EXTINGUISHER IN RECESSED CAB. JN A FLOOR MONUMENT W/SERVICES SHOWN FEs FIRE EXTINGUISHER-SURFACE MOUNTED BRIDGEPORT - EXPANSION 1 FLOOR PLAN SPECIAL OUTLET O THERMOSTAT _ 16630 SW 72ND AVE. A-2 SCALE 1"= l0' 27,393 SF TOTAL A TEUDATA MUD RING WITH PULL STRING 2,841 SF OFFICE i #3082 MARTIN W. HANSON ��CLA KAM S, OREGON f� O Og� -------------- F PROJECT #13640 # � 1 ^I ❑ ❑ ❑ ❑ 1 w � 1 Fey ----------- ------_---- --------- :III,: 1 1 1 # � 1 C�---------- -------_-_- c---------- _---------- _ _ ------- ❑ N � 1 Il11 ii # # 1 1 ❑ ❑ � o EL @@I IN i$@I 1H, I$NI iAli Hit- IU �E �7T. iFl @! ----------- m Ili F----[ --- ii i I if 1 , r r RAISE DROP GAMS FROM 1 h/ E EXISTWs HVAC WT5 TO MAX HT. 11 I I { IR; �r._ i if 11 If I II/SII! \It ,I, •.f ' I / ; tr 11p •- I•, !�: ���„�,� ate__ 1 _______ +_____ -�__ __ _____ __ ___t= _ 4 __ i _ N REMOVE METAL HALITE LIGs4TfNG �Ki 5 i � I � c ~ i k "ti' �I.ice � "✓ 1 I I I ( r it - ��iss i =tji---i'- -r�R,I —^---�• -i--•1--r - -J= - --E---r - '!`- ---t--' _ �t_-_' _ -yry=- _ E�l g r 3 _�,.�'•�.__-iy =�-�;- 1 __ys_z.-4_ + _ sem_= -- - -�.= ,li n I _ 1 ms's I - I I!/R�it I i ' I ! I I • I t , - I I + 1- + i \\!/IL-11I.— _ T__--�---f'---'Fr�s`=''"I--7---�'-'_! _ --t_-.Ilt-_. I 1 1 I I I I 1 ' i I 'i77K:7 . ><- 3aI I iia I i I i 1: - W cq 1 !K -S_,--'I , I. w I `� Il I I II I t I 1 -� - •.�� - O O O iLJ i. _____ `y It /�/ L. 3. 4. -- 5. I ! 15 I 6. 7. 8. I U I • w -- - DRAWN BY: IV (E) ADT R.M.T. (E) POWERFE)) TELE. — �` DISTRIBUTION �dARD 00 11/20/13 - ` PERMIT SET BRIDGEPORT - EXISTING - 16620 SW 72ND AVE_ 25,744 SF TOTAL I I L-------- ---------------------- ----------------- -- --------- BRIDGEPORT - EXPANSION 1 REFLECTED CEILING DEMO PLAN 16630 SW 72ND AVE. A'� SCALE I" = 10' T MIIIIIIIIIII 27,393 SF TOTAL 2,841 SF OFFICE #3082 MARTIN W. HANSON CLA KAM S, OREGON,ti -------------- V L— —J PROJECT #13640 Zi - , n , e pp a .. LL.S.. _. .. :. x ,w:al ,Pma_. '.. .r,:..,; ,Gtj"e� .r..,, r,.._ x..0 _ .w,. .,, .+_. ,. - .. .. cy LM l / l l 1 / / ! / �.,.—.-.� Fx,.:S.,.Y - ,:-. to `) :.:! t n�:? ': a �'d� ��.,• r rrt T a,:' rllr t'+ - ! ILI � kNr �� y � r Z A � r r Foal I rSA d F--=a I \/ ' t x a� O n;, t hs• IT, Mr 4h EON! z I \ I /\ i I /\ I I /\ � 2. t iL_J\ II i a ❑ 1 ❑ ❑ o m a t r fI. O Z* /\ I A I I /\ z ! ❑ m ❑ Vii— ! A ❑ I ( 21'43' 18'-I' 1'-2 IS'- 7 I / I I / \ j4111 tl Ll IL_J\ d 1 WIt r _- _. tea, ' . Anil! EQ. I � N 4 eq O O O 3 ¢ Lit V M - -- Ca - f j \A ° VISION ------------------ ----------- ----------------------------------------------------------------- ----------------------------------------------------------------- 1. �- - . . 3. 1 � , �-7 � �-- a 6. zli CEILING LEGEND s. ,, + 2 X 4 FLUOR.FIXTURE ® EXHAUST FAN V " I DRAWN BY: v' f (E) ADT E POWER (E� TELE. 00 2 x 2 R.M.T. DISTRIBUTION BOARD - � $� � 2 X 4 FLUOR.FIXTURE TILE SPRINKLER HEAD 1 lI2O�13 STEADY BURN f9ALLIST e EXIT SIGN(LED RED) PERMIT SET FLE TED CEILING PLAN BRIDGEPORT - EXISTING M \J ® (4)TUBE T FLUORESCENT FIXTURE WAREHOUSE UNIT HEATER • t RE C R 16620 SW 72ND AVE. SCALE 1"= 10' � RECESSED COMPACT FLUORESCENT LIGHT(TYP.) 25,744 SF TOTAL L------- ---------------------- --------- the OSSC 1006.3—egress lighting on emergency power is regUred in waretw ise aisles where ® SUPPLY DIFFUSER — ----------------- —— path of travel Dead-e common 100'spri i isi�e,x spnnldered/75'rtoneprirddered: BRIDGEPORT - EXPANSION ® RETURN DUCT 16630 SW 72ND AVE. Non-dead-end aisles:200'sprinklered/150'nonsprin dared f� 27,393 SF TOTAL 2,841 SF OFFICE INDICATES COMMON PATH OF TRAVEL REQUIREING EMERGENCY r" LIGHTING EQUAL TO 1-FOOT CANDLE.