Correspondence ibU l6av/s--- Ovol /q2ce Skr GGte,5 LS / Dan Nelson From: Kevin Cooper <kcooper@resourcedesign.net> Sent: Monday, March 16, 2015 11:54 AM To: Dan Nelson Cc: 'Kristi Hudnall'; 'Ron Hudnall'; 'Randy Gentz' Subject: FW: Plan review for Journeys Tigard OR Attachments: 20150316 - 6 A7-1.pdf;JY155 City Comments Tigard OR 020315.docx FW: Plan review for Journeys Tigard OR Hello Dan, please find attached ceiling bracing detail for city comment#1 (re word doc attached for ref) regarding the ceiling seismic bracing. See below from our structural engr recommending the compression strut addressing 'the hgt to deck is 30'; note in detail is 16 ga stud. As a reminder,#2 is NA since storefront and soffit framing are existing to remain,they are to receive the new MOZ mtl. panels only. Please advise on approval or if any further clarification is required. Thanks, Kevin L Cooper I Architect AIA ncarb RESOURCE DESIGN I redefining retail 316 South First Street I Rogers, Arkansas 72756 I Ph: 479.633.8181 X103 I Fx:479.633.9204 • www.rede5150.com before printing this e-mail, please consider electronic transfer/storage. From:Andrew Lloret [mailto:alloret@rara.net] Sent:Tuesday, March 3, 2015 8:47 AM To: Kevin Cooper; Kyle Roberts Cc: 'Ron Hudnall'; 'Randy Gentz'; 'Kristi Hudnall' Subject: RE: Plan review for Journeys Tigard OR Kevin, The splay wires will still work, but the compression vertical should be a 3 5/8—16 gage stud for that long of a distance. You could go to a lighter stud but then you would need additional bracing members tying the verticals together. Andrew J. Lloret, P.E. Ronald A. Roberts Associates, Inc. 2948 N. Stemmons Freeway Dallas, TX 7524 7-61 03 Tel. 214-637-6299, ext. 260 Email: alloret( rara.net 1