Report l514IA1 - vvI //4feA.a3 - Gvioc
RECEIVED
COMcheckSoftware Version 3.9.1 OCT 1 7 2012
Interior Lighting Compliance BUIDI D,�
Certificate IVISION
2010 Oregon Energy Efficiency Specialty Code
Section 1: Project Information
Project Type:New Construction
Project Title:
Construction Site: Owner/Agent: Designer/Contractor:
Section 2: Interior Lighting and Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts I ft2 (B x C)
Retail:Sales Area(Ceiling Height 1211) 873 1.5 1310
Allowance:Furniture,clothing,cosmetics highlighting/Fix.ID:A 459(a) 1.4 576(b)
Total Allowed Watts= 1886
(a)Area claimed must not exceed the Illuminated area permitted for this allowance type.
(b) Allowance Is(B x C)or the actual wattage of the fixtures given in Section 2,whichever is less.
(e) Additional controls/switching allowances are based on number of fixtures or wattage controlled,not floor area of allowance.
Section 3: interior Lighting Fixture Schedule
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ ft of Fixture (C X D)
• Fixture Fixtures Watt.
Retail:Sales Area(873 sq.ft.)
HID 1:A:Ceramic Metal Halide 20W/Standard 2 12 48 576
Halogen 1:B:Halogen MR-16 35W 1 13 35 455
Linear Fluorescent 1:C:48`T8 28W(Super T8)I Electronic 2 3 52 156
Track lighting 1:E:Wattage based on 14.0 feet of tract 0 0 0 Exempt
Exemption:Retail Display Window
Halogen 2:H:Halogen MR-16 35W 1 2 35 70
Compact Fluorescent 1:P1:14 watt self ballast ctl/Other/Electronic 5 2 70 140
Total Proposed Watts= 1397
Section 4: Requirements Checklist
In the following requirements,the relevant code section reference is shown In(j.+'denotes that more details exist in the specified code
section.Checkboxes identify requirements that the applicant has not acknowledged as being met Check marked requirements identify those
the applicant acknowledges are met or excepted from compliance.plans reference page/section'Identifies where In the plans/specs the
requirement can be verged as being satisfied.
Lighting Wattage:
• 1. [505.1+3 Total proposed watts must be less than or equal to total allowed watts.
Mowed Wattage:1888 Proposed Wattage:1397
Complies:YES
Mandatory Requirements:
• 2. (505.4)Exit signs.Internally Illuminated exit signs shall not exceed 5 watts per side.
Plans reference page/section:
• 3. (505.2.2.3+)Daylight zone control.All daylight zones are provided with individual controls that control the lights independent of general
area lighting In the non-daylight zone.In all Individual daylight zones larger than 350 sq.ft.,automatic daylight controls Is provided.
Automatic daylight sensing controls reduce the light output of the controlled luminaires at least 50 percent,and provide an automatic
Project Title: Report date: 10/15/12
Data filename:K:1Projects13292.0051 TAOS Washington Square-Portland,OR\Electrica113292.0051 portland.cck Page 1 of 4
OFF control,while maintaining a uniform level of illumination.Contiguous daylight zones adjacent to vertical fenestration may be
controlled by a single controlling device provided that they do not Include zones facing more than two adjacent cardinal orientations
(i.e.,north.east,south,west).Daylight zones under skylights shall be Controlled separately from daylight zones adjacent to vertical
fenestration.
Exception(s):
•
❑ Retail spaces adjacent to vertical glazing(retail spaces under overhead glazing are not exempt).
❑ Display,exhibition and specialty lighting
❑ MID lamps 150 watts or lees.
p Spaces required to have occupancy sensors.
Plans reference page/section:
a 4. [505.2.1+]interior lighting controls.At least one local shutoff lighting control has been provided for every 2,000 square feet of lit floor
area and each area enclosed by walls or floor-to-ceiing partitions.The required controls are located within the area served by the
controls or are a remote switch that identifies the lights served and indicates their statue.
ExceptIon(a):
❑
Lighting systems serving ariasdesignated as security or emergency areas that must be continuously lighted.
❑ Lifting In public areas such as concourses,stairways or corridors that are elements of the means of egress with switches that
are accessible only to authorized personnel.
❑ Lighting for warehouses,parking garages or spaces using less than 0.5 watts per square foot.
❑
Lighting for contiguous,single-tenant retail spaces.
Plans reference page section:
❑ 5. [505.2.3+]Sleeping unit controls.Master switch at entry to hotel/motel guest room.
Plans reference page/section:
❑ 6. [505.2.1.1)Egress lighting.Egress illumination is controlled by a combination of listed emergency relay and occupancy sensors to shut
off during periods that the building space served by the means of egress is unoccupied.
CKs):
p Building exits as defined In Section 1002 of the Oregon Structural Specialty Code.
Plans reference page/section:
❑ 7. [505.2.2+]Additional controls.Each area that is required to have a manual control shall have additional controls that meet the
requirements of Sections 505.2.2.1 and 505.2.2.2.
Plans reference page/section:
❑ 8. [505.2.2.1+]Light reduction controls.Each space required to have a manual control also allows for reducing the connected lighting load
by at least 50 percent by either
1)controlling(dimming or multi-level switching)ail luminaires;or
2)dual switching of alternate rows of luminaires,alternate luminaires,or alternate lamps;or
3)switching the middle lamp luminaires independently of other lamps;or
4)switching each luminaire or each lamp.
Exception(s):
on(s):
❑ Only one luminaire in space.
❑ An occupant-sensing device controls the area.
p The area Is a corridor,storeroom,restroom,public lobby or sleeping unit.
O Electrical and mechanical room.
Areas that use less than 0.6 Watts/sq.ft.
Plans reference page/section;
❑ 9. [505,2.2.2]Buildings larger than 2,000 square feet are equipped with an automatic control device to shut off lighting in those areas.This
automatic control device shall function on either.
1)a scheduled basis,using time-of-day,with an Independent program schedule that controls the interior lighting in areas that do not
exceed 10,000 square feet and are not more than one floor;or
2)an occupant sensor that shall turn lighting off within 30 minutes of an occupant leaving a space;or
3)a signal from another control or alarm system that indicates the area Is unoccupied.
Exception(s):
D Sleeping units,patient care areas;and spaces where automatic shutoff would endanger safety or security.
Plans reference page/section:
❑ 10.(505.22]Occupancy sensors in rooms that include daylight zones are required to have Manual ON activation.
Project Title: Report date: 10/15/12
Data filename:K:1Pro]ects13292.0051 TAOS Washington Square-Portland,OR\EIectrica113292.0051 portland.cck Page 2 of 4
Plans reference page/section:
❑ 11.(505.2.2)An occupant sensor control device Is installed that automatically turns lighting off within 30 minutes of all occupants leaving a
apace.
Exception(s):
0 Classrooms and lecture halls.
❑ Conference,meeting and training rooms.
❑ Employee lunch and break rooms.
O Rooms used for document copying and printing.
❑ Office spaces up to 300 square feet.
❑ Restrooms.
❑ Dressing.fitting and locker rooms.
Plans reference page/section:
O 12.(505.2.2]Additional controls.An occupant sensor control device that automatically hums lighting off within 30 minutes of all occupants
leaving a space or a locally activated switch that automatically turns lighting off within 30 minutes of being activated Is installed in all
storage and supply rooms up to 1000 square feet.
Plans reference page/section:
O 13.(505.2.2.2.1)Occupant override.Automatic lighting shutoff operating on a time-of-day scheduled basis incorporates an override
switching device that 1)is readily accessible,2)is located so that a person using the device can see the lights or the area controlled
by that switch,or so that the area being lit is annunciated,3)is manually operated,4)allows the fighting to remain on for no more than
2 hours when an override is Initiated,and 5)controls an area not exceeding 2.000 square feet
Exception(s):
❑ In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,where captive-key override is
utilized,override time is permitted to exceed 2 hours.
❑ In malls and arcades,auditoriums,single-tenant retail spaces,industrial facilities and arenas,the area controlled shall not exceed
20,000 square feet.
Plans reference page/section.
❑ 14.(505.2.2.2.2)Holiday scheduling.Automatic lighting shutoff operating on a time-of-day scheduled basis has an automatic holiday
scheduling feature that turns off all loads for at least 24 hours,then resumes the normally scheduled operation.
Exception(s):
❑ Retail stores and associated malls,restaurants,grocery stores,places of religious worship,theaters and exterior lighting zones.
❑ Single zone electronic time control devices and self-contained wall box preset lighting controls.
Plans reference page/section:
❑ 15.1505.2.4+)Exterior lighting controls.Lighting not designated for dusk-to-dawn operation shall be controlled by either a combination of a
photosensor and a time switch,or an astronomical time switch.Lighting designated for dusk-to-dawn operation shall be controlled by
an astronomical time switch or photosensor.
Plans reference page/section:
O 18.(505.3)Tandem wiring.The following luminaires located within the same area shall be tandem wired:
1.Fluorescent luminaires equipped with one,three or odd-numbered lamp configurations,that are recess-mounted within 10 feet
center-to-center of each other.
2.Fluorescent luminaires equipped with one,three or any odd-numbered lamp configuration,that are pendant-or surface-mounted
within 1 foot edge-to-edge of each other.
Exception(s):
❑ Where electronic high-frequency ballasts are used.
❑ Luminaires on emergency circuits.
❑ Luminaires with no available pair in the same area.
Plans reference page/section:
O 17.1505.5.1+J Medical task lighting or artlhistoy display lighting claimed to be exempt from compliance has a control device independent
of the control of the nonexempt lighting.
Plans reference page/section:
O 18.(506.7+)Each dwelling unit in a building is metered separately.
Plans reference page/section:
Project Title: Report date: 10/15/12
Data filename:K:\Projects\3292.0051 TAOS Washington Square-Portland,OR\Electrical13292.0051 portland.cck Page 3 of 4
Interior Lighting PASSES than coie.
Section 5: Compliance Statement
• Compliance Statement: The proposed Bghting design represented in this document Is consistent with the building plans,specifications and
other calculations submitted with this permit application.The proposed lighting system has been designed to meet the 2010 Oregon Energy
Efficiency Specialty Code requirements in COMaheck Version 3.9.1 and to comply with the mandatory requirements in the Requirements
Checklist.
t+11 . S, Pb 9'' sol,/ice
Name-Title Signature Date
Project Title: Report date: 10/15/12
Data filename:K:\Projects\3292.0051 TAOS Washington Square-Portland,OR\Electrice1133292.0051 portland.cck Page 4 of 4