Report (2) NAC EOL VOLTAGE CALCULATION 1L' 7 S�✓�S7k CAPITOL ELECTRIC CO., INC. RECEIIIFD (S03) 255-9488 Office JUN 19 , 3 (503) 255-1966 Fax CITY OF if -L) Job Name: Tigard Corporate Center, Building-C BUILDING DIVISION Job Address: 12447 SW 69th Ave. Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 6/13/2013 Cable Length In Feet (source to end of line) 489 Total Circuit Current 1.658 Nominal System Voltage 20.4 Panel Description: Silent Knight 5495 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.2 Output No.: 1 Point To Point Method EOLv 17.86 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 17.91 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 Floor-2 Electric Room DSM-12/24-R ( 1 CKT ONLY ) NA 0.0275 3 20.37 2 Floor-2 West RSS-24MCW-FW (75) STB WHT 75 Cd 0.165 40 19.97 3 Floor-2 West RSS-24MCW-FW (75) STB WHT 75 Cd 0.165 51 19.51 4 Floor-2 West AS-24MCW-FW(110)H/S WHT-H 110 Cd - 0.267 38 19.21 5 Floor-2 North AS-24MCW-FW(110)H/S WHT-H 110 Cd 0.267 _ 99 18.58 6 Floor-2 North AS-24MCW-FW(110)H/S WHT-H 110 Cd 0.267 59 18.30 7 Floor-2 North STW(15) Strobe-Wall, White 15 Cd 0.057 25 18.23 8 Floor-2 North STW (15) Strobe-Wall, White 15 Cd 0.057 25 18.16 9 Floor-2 North RSS-24MCW-FW (110) STB WHT 110 Cd 0.220 _ 105 17.91 10 Floor-2 North RSS-24MCW-FW (75) STB WHT 75 Cd 0.165 44 17.86 11 17.86 12 17.86 13 17.86 14 17.86 15 17.86 16 17.86 17 17.86 18 17.86 19 17.86 20 17.86 zTCC-C NAC 2.2 EOLv Calc.xls OUTPUT 1 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503)255-9488 Office (503)255-1966 Fax Job Name: Tigard Corporate Center, Building-C Job Address: 12447 SW 69th Ave. Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 6/13/2013 Cable Length In Feet (source to end of line) 467 Total Circuit Current 1.329 Nominal System Voltage 20.4 Panel Description: Silent Knight 5495 Power Supply Minimum Device Voltage 16 Panel No.: NAC 2.2 Output No.: 4 Point To Point Method EOLv 18.19 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 18.50 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) t ! 'r a mo-,:iM*- r ,} 5..� *'? fs, �,t y',�� ��'�at� ,-x Ikf k�x`,5,.'��.s3a�.' C�`ar"�fir. "...u. .w ._y'�x "'�_ _,.4 `� �:7r$: f�w�M,'�5 ;' 10si;#+.. 1 Floor-2 Electric Room DSM-12/24-R( 1 CKT ONLY ) NA 0.0275 3 20.38 2 Floor 2 Center AS-24MCW-FW (75) H/S WHT-H 75 Cd 0.200 60 19.90 3 Floor 2 East AS-24MCW-FW(75) H/S WHT-H 75 Cd 0.200 66 19.45 4 Floor 2 South West AS-24MCW-FW(110)H/S WHT-H 110 Cd 0.267 110 18.84 5 Floor 2 South West STW(15) Strobe-Wall, White 15 Cd 0.057 26 18.74 6 Floor 2 South West STW(15) Strobe-Wall, White 15 Cd 0.057 26 18.65 7 Floor 2 South West AS-24MCW-FW (75) H/S WHT-H 75 Cd 0.200 110 18.30 8 Floor 2 South RSS-24MCW-FW(15) STB WHT 15 Cd 0.060 19 18.26 9 Floor 2 South RSS-24MCW-FW(15) STB WHT 15 Cd 0.060 25 18.22 10 Floor 2 South AS-24MCW-FW(75) H/S WHT-H 75 Cd 0.200 22 18.19 11 18.19 12 18.19 13 18.19 14 18.19 15 18.19 16 18.19 17 18.19 18 18.19 19 18.19 20 18.19 zTCC-C NAC 2.2 EOLv Calc.xls OUTPUT 4 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office, (503)255-1966 Fax JOB NAME: Tigard Corporate Center, Building-C ADDRESS: 12447 SW 69th Ave. Tigard,OR 97223 DATE: 6/13/14 PANEL DESCRIPTION: NAC2 PREPARED BY: Dan Wilson DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER Silent Knight 5495 NAC Panel 1 0.075 0.075 0.205 0.205 CIRCUIT#1 Floor-2 Wheelock DSM-12/24-R Synch Module(1/2) 1 0.0275 0.028 Whlk STW 15 Cd Strobe-Wall 2 0.057 0.114 Wheelock AS-24MCW-FW 110 Cd HIS (H) 3 0.267 0.801 Wheelock AS-24MCW-FW 75 Cd H/S (H) 0.200 0.000 Wheelock AS-24MCW-FW 15 Cd H/S (H) 0.088 0.000 Wheelock RSS-24MCW-FW 110 Cd Strobe 1 0.220 0.220 Wheelock RSS-24MCW-FW 75 Cd Strobe 3 0.165 0.495 Wheelock RSS-24MCW-FW 15 Cd Strobe 0.060 0.000 0.000 TOTAL 1.658 CIRCUIT#2 Floor-2 Wheelock DSM-12/24-R Synch Module(1/2) 1 0.0275 0.028 Whlk STW 15 Cd Strobe-Wall 0.057 0.000 Wheelock AS-24MCW-FW 110 Cd H/S (H) 2 0.267 0.534 Wheelock AS-24MCW-FW 75 Cd H/S (H) 2 0.200 0.400 Wheelock AS-24MCW-FW 15 Cd H/S (H) 0.088 0.000 Wheelock RSS-24MCW-FW 110 Cd Strobe 0.220 0.000 Wheelock RSS-24MCW-FW 75 Cd Strobe 2 0.165 0.330 Wheelock RSS-24MCW-FW 15 Cd Strobe 1 0.060 0.060 0.000 TOTAL 1.352 CIRCUIT#3 Floor-2 Wheelock DSM-12/24-R Synch Module(1/2) 1 0.0275 0.028 Whlk STW 15 Cd Strobe-Wall 0.057 0.000 Wheelock AS-24MCW-FW 110 Cd H/S (H) 0.267 0.000 Wheelock AS-24MCW-FW 75 Cd H/S (H) 1 0.200 0.200 Wheelock AS-24MCW-FW 15 Cd H/S (H) 0.088 0.000 Wheelock RSS-24MCW-FW 110 Cd Strobe 0.220 0.000 Wheelock RSS-24MCW-FW 75 Cd Strobe 3 "'" 0.165 0.495 Wheelock RSS-24MCW-FW 15 Cd Strobe 3 0.060 0.180 0.000 w -t*- . TOTAL 0.903 CIRCUIT#4 Floor-2 Wheelock DSM-12/24-R Synch Module(1/2) 1 `t' " r": 0.0275 0.028 Whlk STW 15 Cd Strobe-Wall 2 .y, 4 ' : 0.057 0.114 Wheelock AS-24MCW-FW 110 Cd H/S (H) 1 st 0.267 0.267 Wheelock AS-24MCW-FW 75 Cd H/S (H) 4 " 0.200 0.800 Wheelock AS-24MCW-FW 15 Cd H/S (H) r",° ;, ,, 0.088 0.000 Wheelock RSS-24MCW-FW 110 Cd Strobe * -r-' 0.220 0.000 Wheelock RSS-24MCW-FW 75 Cd Strobe '" ") 1 0.165 0.000 Wheelock RSS-24MCW-FW 15 Cd Strobe 2 �, tIltn a'- / 0.060 0.120 0.000 :r i -,! '`._ s w'' ' TOTAL 1.329 zTCC-C NAC 2.2 Batt Calc.xls Page 1 of 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. (503)255-9488 Office, (503)255-1966 Fax JOB NAME: Tigard Corporate Center,Building-C ADDRESS: 12447 SW 69th Ave. Tigard,OR 97223 DATE: 6/13/14 PANEL DESCRIPTION: NAC2 PREPARED BY:Dan Wilson DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT AUXILIARY DEVICES • 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 STANDBY TOTAL CURRENT: 0.075 STANDBY HOURS: 24 STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT 5.240 ALARM TOTAL CURRENT: 5.445 ALARM MINUTES: 5 ALARM AMP HOURS: 0.454 TOTAL CALCULATED AMP HOURS 2.254 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQURED 2.705 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES zTCC-C NAC 2.2 Batt Calc.xls Page 2 of 2 Wheelock° ExcederTM Series COOPER Notification EEDERM Finally, Design and Safety Meet... 4,} • - .� 111 t� rl... Ceiling - - Wall Description: The Wheelock®ExcederTM Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw,no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points,12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. - Save up to 14% cost of installation** The Wheelock®ExcederTM Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings,can be set without the use of a tool and are located behind the appliance to prevent tampering. Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTM Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting IVpc Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a 90,95,99 dB shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while 8 Candela Settings#** it is on the UMB. When the Contact Cover is removed the circuit Wall-15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows Ceiling-15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if ,,,, required. Wall models provide an optional locking screw for extraLO Universal Mounting Base secure installation, while the ceiling models provide a captivated Ceiling and Wall Mounts to 5 Backbox Types screw to prevent the screw from falling during installation. U Environmentally Friendly • Low Current Draw Compatibility and Requirements -Synchronize using the Wheelock®Sync Modules or panels with built-in Wheelock®Patented Sync Protocol -Compatible with UL"Regulated Voltage"using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage"range •Compared to competitive models *`"Patented *"Compared to previous models NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. L. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: •Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. •Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32*F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%)UL 464(85%UL 1971). •Series Exceder horns are under UL Standard 464 for audible signal appliances(Indoor use only). Low Current Draw = Fewer Power Supplies Strobe Ratings per UL Standard 1971 UL Max Current* 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 &UL 464 at 24 VDC UL Max Current*at 99 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125 UL Max Current*at 95 dBA 24 VDC 12 VDC Model Regulated Voltage e 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 s 0.230 }y 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 1-." 0.186 "tt,}t; 0.230 0.272 `' 0.122 UL Max Current*at 90 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 „' 0.184 0.226 0.267 0.120 Horn Ratings per UL 464 i 44746. . 'AIN" Model Regulated Voltage 99 dB 95 dB 90 dB Range VDC HN 16-33.0 0.064 0.044 0.022 • HNC 16-33.0 0.084 0.044 0.022 . .t° ANN,. HN 8.0-17.5 0.047 0.026 0.017 HNC 8.0-17.5 0.047 0.026 0.017 • its *UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage(16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. . ~ y .ti lw...1 h�^�'_. i.'... 'ci' � .mac_ I1Cj r t, i ; SERIES AS SINGLE & MULTI-CANDELA AUDIBLE STROBE APPLIANCES SERIES AH AUDIBLES Description l Wheelock's patented 2-wire Series AS Audible Strobe "R Appliances and Series AH Audibles offer more features t.. with low current draw. �i Strobe options for wall mount models include 1575cd or SERIES AS SERIES AH Wheelock's patented MCW multi-candela wall strobes with field selectable candela settings of 15/30/75/110cd, or the high intensity MCWH strobe with field selectable 135/185cd. 15 3Q Ceiling mount models incorporate Wheelock's patented .-' '°4"110 I MCC multi-candela ceiling strobe with field selectable 11111111111, # intensities of 15/30/75/95cd or the high intensity MCCH Multi-Candela Indicator strobe with field selectable 115/177cd. (bottom of lens) The audible provides a selectable choice of either a Features continuous horn or temporal pattern (Code 3) when • Approvals include: UL Standard 1971, UL Standard 464 constant voltage from a Fire Alarm Panel (FACP) is New York City(MEA),California State Fire Marshal(CSFM), applied. Each tone has 3 dBA settings to choose from. Factory Mutual(FM),and Chicago(BFP). See approvals by model in Specifications and Ordering Information. When used with the Wheelock Series SM or DSM Sync • ADA/NFPA/UFC/ANSI Compliant Module or Wheelock PS-12/24-8CP and PS-12/24-8MP • Wall mount models are available with Field Selectable Power Supplies with Patented Sync Protocol, Candela Settings of 15/30/75/110cd or 135/185cd synchronization of the continuous horn tone provides the (Multi-Candela models) or 1575cd (single candela temporal (code 3) tone (mandated by NFPA 72) model) • Ceiling mount models are available with field selectable simultaneously for all audible appliances. This ensures a candela settings of 15/30/75/95cd or 115/177cd distinct temporal(code 3)pattern when 2 or more audibles (multi-candela ceiling models) are within hearing distance. If not synchronized the • Selectable Continuous Horn or Temporal (Code 3). temporal sound could overlap and not be distinctive. At • 3 Selectable dBA settings (99, 95 and 90 dBA) in both the same time the strobes will be synchronized. This tones provides the ability to comply with ADA guidelines • Patented 2-Wire Audible Strobe Appliance. concerning photosensitive epilepsy and the NFPA • Patented Universal Mounting Plate standards when installing 2 or more visual appliances • Weatherproof models are available for outdoor use • within the field of view all of this plus the ability to silence Strobes produce 1 flash per second over the regulated voltage range the audible is achieved by using only 2 wire. • 12 and 24 VDC models with wide UL "Regulated • Voltage Range" using filtered DC or unfiltered FWR input voltage • The strobes can be synchronized using Wheelock's sync modules or power supplies with built in sync protocol • Fast installation with IN/OUT screw terminals using For Weatherproof Series AS, See Datasheet S9004 #12 to#18 AWG wires Copyright 2004 Wheelock Inc. All rights reserved. NOTE: All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT.FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER - APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes • • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA-72(1999)specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series AS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120° F(0°C to 49°C)and maximum humidity of 93% (±2%). • Series AH-24 horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). • Series AH-24WP audible appliances are listed under UL Standard 464 for indoor/outdoor use with a temperature range of-31°F to 150°F (-35°C to 66°C)and maximum humidity of 95%. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range". Table 1: Ratings Per UL 1971 Model Input Voltage VDC Regulated Voltage Strobe Candela(cd) Range VDC/FWR AS-24MCW 24 16.0-33.0 15/30/75/110 AS-24MCCH 24 16.0-33.0 115/177 AS-241575W 24 16.0-33.0 15(75 on Axis) AS-121575W 12 8.0-17.5 15(75 on Axis) AS-24MCC 24 16.0-33.0 15/30/75/95 AS-24MCWH 24 16.0-33.0 135/185 ASWP-2475W 24 16.0-33.0 75 @-31'F Table 2:dBA Ratings for 12 VDC and 24 VDC Series AS/AH 12 and 24 VDC Audible Description Volume Reverberant dBA Anechoic Per UL 464 @ 10 ft. dBA@10 ft. High 91 99 Continuous Horn Medium 88 95 Low 83 90 High 87 99 Code 3 Horn _ Medium 84 95 Low 79 90 Table 3: Average RMS Current Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models 24 VDC Models AH-24 AS-241575W AS-24MCW AS-24MCWH AS-24MCC AS-24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320 High(99)dBA UL max' 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480 ' 24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305 Med(95)dBA UL max' 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465 24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295 Low(90)dBA - UL max° 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460 Audible Wall Mount 12 VDC Models Audible Strobe AH-12 AS-121575W *RMS current ratings are per UL average RMS method. UL max current 12 vdc 0.163 0.260 rating is the maximum RMS current within the listed voltage range (16- High(99)dBA 33v for 24v units). For strobes the UL max current is usuallyat the UL max` 0.192 0.320 ) • minimum listed voltage(16v for 24v units). For audibles the max current 12 vdc 0.076 0.195 is usually at the maximum listed voltage(33v for 24v units). For unfiltered Med(95)dBA FWR ratings, see installation instructions. UL max° 0.108 0.275 12 vdc 0.039 0.175 Low(90)dBA UL max° 0.058 0.265 g • .s `k Y' 6R. �a. is rr CE 'k=r�� r em t F 4. SERIES RSS & RSSP SINGLE & MULTI-CANDELA STROBES & STROBE PLATES r • • DESCRIPTIONS- : • Wheelock's patented Series RSS Strobe Appliances and 1 Series RSSP Strobe Plates have lower current draw while ,7 FIRE ' i{1-_,-- _ ; maintaining outstanding performance,reliability and cost 1 effectiveness. These versatile appliances will satisfy FIRE virtually all requirements for indoor,wall or ceiling mount Series RSS RSS Round applications. Series RSSP Strobe options for wall mount models include 1575 or ,4.._ _ Wheelock's Patented MCW multi-candela strobe with field ,rT • selectable candela settings of 15/30/75/110cd or the high - ---y1 intensity MCWH strobe with field selectable 135/185cd. 114x'.5.1 r �ito 4 Mk Ceiling mount models include the patented MCC multi _1111111111 - candela ceiling strobe with field selectable intensities of Multi-Candela Indicator 15/30/75/95cd or the high intensity MCCH strobe with (bottom of Strobe Lens) field selectable 115/177cd. Features All models may be synchronized using the Wheelock • Approvals include: UL Standard 1971, New York City SM, DSM Sync Modules or the PS-12/24-8CP and (MEA),California State Fire Marshal(CSFM), Factory PS-12/24-8MP Power Supplies with Wheelock's Patented Mutual(FM),and Chicago(BFP) See approvals by Sync Protocol. Synchronized strobes can eliminate model in Specifications and Ordering Information possible restrictions on the number of strobes in the field • ADA/NFPA/UFC/ANSI compliant. Meets OSHA 29 of view.Wheelock's synchronized strobes offer an easy Part 1910.165 way to comply with ADA recommendations concerning • Wall mount Multi-Candela models are available photosensitive epilepsy as well as meeting the with Field Selectable Candela Settings of 15/30/ requirements of NFPA72. 75/110cd or 135/185cd. Single Candela models are available in 1575cd Wheelock's Series RSS Strobes employ a Patented • Ceiling mount Multi-Candela models are Integral Strobe Mounting Plate that can be mounted to a available with field selectable candela settings of single gang,double gang,4"square, 100mm European 15/30/75/95cd or 115/177cd. (Round or Square) backboxes or the SHBB surface backbox. If the flush • Strobes produce 1 flash per second over the backbox has side or top space between it and the finished regulated voltage range wall,the NATP(Notification Appliance Trimplate)may be • 12 and 24 VDC models with wide UL"Regulated used.It provides an additional.65"of trim for the Appliance. Voltage"using filtered(DC)or unfiltered VRMS input An attractive cover plate is provided for a clean,finished voltage appearance on all models. • Synchronize using Wheelock's sync modules or power supplies with built-in sync protocol The Series RSSP Multi-Candela Strobe Plates are a cost • Fast installation with IN/OUT screw terminals using effective way to retrofit required wall strobe appliances to #12 to#18 AWG wire bells, horns, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with Wheelock's SBL2 surface backbox. For Weatherproof Series RSS See Datatsheet S9004 Copyright 2004 Wheelock, Inc. All rights reserved. NOTE: All CAUTIONS and WARNINGS are identified by the symbol a. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes • Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series RSS&RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%). • "Regulated Voltage Range"is the newest terminology used by UL to identify the voltage range. Prior to this change,UL used the terminology"Listed Voltage Range". Table 1: Average RMS Current* RSS/RSSP RSS/RSSP -Wall Mount RSS -Ceiling Mount 24VDC 241575W 24MCW 24MCWH 24MCC 24MCCH Models 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 RSS/RSSP RSS/RSSP * RMS current ratings are per UL average RMS method. UL max current 24VDC Wall Mount rating is the maximum RMS current within the listed voltage range(16-33v Models 121575W for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage(16v for 24v units). For audibles the max current is usually at the maximum listed voltage(33v for 24v units). For unfiltered FWR ratings, UL max* 0.255 see installation instructions. • Table 2: Audibles/Speakers for RSSP Strobe Plate • Product Series Multitone Appliances AMT, MT Horns AH, NH,HS Motor Bells MB-G6/G10 Speakers ET-1010/1080, E70, ET70 Chimes CH70 WARNING:CONTACT WHEELOCK FOR THE CURRENT"INSTALLATION INSTRUCTIONS" AND"GENERAL INFORMATION"SHEET(P82380)ON THESE PRODUCTS.THESE DOCUMENTS UNDERGO PERIODIC CHANGES.IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS,INCLUDING: • TOTAL CURRENT REQUIRED BYALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. • ADDING,REPLACING OR CHANGING APPLIANCES OR CHANGING CANDELA SETTINGS WILL AFFECT CURRENT DRAW. RECALCULATE CURRENT DRAW TO INSURE THAT THE TOTAL AVERAGE CURRENT AND TOTAL PEAK REQUIRED BY ALL APPLIANCES DO NOT EXCEED THE RATED CAPACITY OF THE POWER SOURCE OR FUSES. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR"REGULATED VOLTAGE RANGE". • • INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBES MAY NOT FLASH. • • FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION,APPLICATION,AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. • CONDUCTOR SIZE(AWG),LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS,PARTICULARLY IN RETROFIT INSTALLATIONS.