Loading...
Report (39) 1, )--(4s= O6c(i3 . ' 1 3 S-3 Si.) 72.L.0 REC QED JAN 2015 Nac #1 Battery Calculations 4009-9201 CITY OFTIG BUILDING DON �N Stand By(hrs): 24 Alarm Time(min): 15 PART# DESCRIPTION QTY STAND BY STAND BY TOTAL ALARM ALARM TOTAL 4906-9127 Horn/Strobe 110cd 4 0 0 190mA 760mA 4906-9127 Horn/Strobe 75cd 3 0 0 147mA 241mA 4906-9101 Horn/Strobe 15cd 4 0 0 50mA 200mA Stand by AMPS= 0 Alarm AMPS= 1.401 AMPS Stand By Ah= 0 Alarm AH= 0.35Ah NAC #2 PART# DESCRIPTION QTY STAND BY STAND BY TOTAL ALARM ALARM TOTAL 4906-9127 Horn/Strobe 110cd 3 0 0 190mA 760mA 4906-9127 Horn/Strobe 75cd 2 0 0 147mA 241mA 4906-9101 Horn/Strobe 30cd 2 0 0 77mA 154mA 4906-9101 Horn/Strobe 15cd 2 0 0 50mA 100mA Stand by AMPS= 0 Alarm AMPS= 1.12AMPS Stand By Ah= 0 Alarm AH= 0.28Ah Amp Hours Required=0.63Ah Batteries To Be Installed= No Change To Be Assumed t iw RCTi�/�^ f3® N1 Simplex JAN1 Alert Multi-Candela Notification Appliances �� UL, ULC, CSFM Listgi�f�l rQved,415 SmartSyncTM Opel ation AudibleMsib'e Notification Jk MEA (NYC)Acceptan0/N //GAR with Horn and S;nchronizad F!ash, Non-Addressable __ Features Audible/visible(AN) notification appliances with ,;•'- _.=-"` "„;, "' ... .... efficient electronic horn and high output xenon #• t strobe,available for wall or ceiling mount: ;- �� • . „..,----- • '"---' — • Operation is compatible with ADA requirements(refer to important installation information on page 3) ✓i • Rugged,high impact,flame retardant thermoplastic i i 1 --________j housings are available in red or white with clear lens ; Operates over a two-wire SmartSync circuit to provide: , • Horns that are controlled separately from strobes on the F I di i same two-wire circuit • "On-until-silenced”and'ion-until-reset"operation on the same two-wire pair • SmartSync horn activation of Temporal pattern,March Time pattern(at 60 BPM),or on continuously — --- -- II • Strobe appliances on the same circuit operating at a 11.-1111)1 synchronized 1 Hz flash rate • Operation requires connection to a compatible SmartSync operation NAC or to SmartSync Control Wall and Ceiling Mount A/Vs Module(SCM)4905-9938 Descri.tion Wall mount ANs features: • Wiring terminals are accessible from the front of the Multi-Candela TrueAlert ANs with horn and housing providing easy access for installation, synchronized strobe provide convenient installation inspection,and testing to standard electrical boxes.The enclosure designs are both impact and vandal resistant and provide a convenient j • Covers are available separately to convert housing color strobe intensity selection.Since each model can be • Optional UL/ULC listed sound damper for locations selected for strobe intensity output,on-site model requiring attenuation of 5 to 6 dBA(stairwells,small inventory is minimized and changes encountered during rooms,highly reverberant areas,etc.) construction can be easily accommodated. Optional adapters and wire guards: Wall mount AN housings are a one-piece assembly • Wall mount AN adapters are available to cover surface (including lens)that mounts to a single or double gang.or mounted electrical boxes and to adapt to Simplex' 4"square standard electrical box.The cover can be 2975-9145 boxes quickly removed(a tool is required)and covers are • UL listed red wire guards are available for wall or available separately for color conversion. ceiling mount ANs* Ceiling mount ANs install using standard 4"electrical Visible notification appliance(strobe): boxes.Color choice is determined by model number. • 24 VDC xenon strobe;intensity is selectable as 15.30, Strobe Intensit Selection 75,or 110 candela with visible selection jumper secured behind strobe housing During installation,a selection plug at the back of the • Regulated circuit design ensures consistent flash output housing determines the desired strobe intensity.An and provides controlled inrush current attached flag with black letters on a highly visible yellow background allows the selected intensity to be seen at the • Listed to UL 1971 and ULC S526 side of the strobe lens. Audible notification appliance(horn): * Refer to page 2 for guard fisting.This product has been approved by the California State • Low current,24 VDC electronic horn with harmonically fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code.See CSFM Listing 7125-0026:317 for allowable values and/or conditions concerning rich sound output suitable for either steady or coded material presented in this document.It is subject to re-examination.revision.and possible operation(Temporal or 60 BPM March Time pattern) cancellation.Accepted for use—City of New York Department of Buildings—MEA35-93E. Refer to page 2 for listing status of wire guards.Additional listings may be applicable: • Listed to UL 464 and ULC S525 contact your local Simplex product supplier for the latest status.Listings and approvals under Simplex Time Recorder Co.are the property of Tyco Safety Products Westminster. ** Simplex multi-candela SmartSync two-wire horn/strobe appliance operation is protected under one or more of the following U.S.Patent Numbers:5,559,492:5.622.427: 5,865,527;5,886,620;6281,789:6.954,137;7.005,971;and 7.006.003 S4906-0002-5 9/2009 F .41 A/V S•ecifications - Wall Mount or Ceiling Mount,Common Specifications _ Rated Voltage Range Regulated 24 DC;see Note 1 beiow - - Flash Rate and Synchronized NAC Loading 1 Hz;with up to 35 synchronized strobes maximum per NAC - Environmental;Temperature and Humidity 32°to 122'F(0°to 50°C);10%to 93%,non-condensing at 100°F(38'C) Connections Terminal blocks for 18 AWG to 12 AWG(0.82 mm2 to 3.31 mm2);two wires per terminal for in/out wiring _ _- Horn Output Characteristics 2400 to 3700 Hz sweep,modulated at 120 F't rate __ - _ _ Model Type Wall Mount _ �C' li ftp Mount Horn Output Sound Type(see Note 2) Steady Coded Steady Coded Ratings (see Note 2 for Reverberant Chamber Test, 86 dBA 82 dBA 87 dBA 83 dBA polar dispersion per UL 464 @ 10 ft(-3 m) reference) Anechoic Chamber Test,per 88 dBA 94 dBA 90 dBA 98 dBA ULC S525 @ 3 m(-10 ft) Housing Dimensions(with lens) 5-1/8"H x 5"W x 2-3/4"D(130 mm x 127 mm x 70 mm) Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Wall MOUnt Strobe Setting(see Note 3 below) 75 mA 116 mA 221 mA 285 mA Reference RMS Currents 18 VDC 67 mA 103 mA 196 mA 253 mA at other voltages 24 VDC 50 mA 77 mA 147 mA 190 mA Housing Dimensions(with lens) 4-3/4 L"x 6-7/8"W x 2-5/8"D(121 mm x 175 mm x 67 mm) Ceiling Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Mount Strobe Setting(see Note 3 below) 86 mA 132 mA 250 mA 320 mA Reference RMS Currents 18 VDC 76 mA 117 mA 222 mA 284 mA at other voltages 24 VDC 57 mA 88 mA 167 mA 213 mA NOTES: - 1. "Regulated 24 DC"refers to the voltage range of 16 to 33 VDC per UL Standard 1971,Signaling Devices for the Hearing Impaired, changes effective May 1,2004.This voltage range is the absolute operating range.Operation outside of this range may cause permanent damage to the appliance.Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. Coded values are typical of the output measured with a Temporal coded or a March Time coded pulse and with a sound level meter reading on a"fast"setting.Polar dispersion per ULC S525 testing= -3 dBA at+/-40°off-axis;-6 dBA at+/-50°off-axis. 3. Currents are with horn on steady.The maximum RMS current listed is the device nameplate rating.Strobe designs are constant wattage and the maximum RMS current rating occurs at the lowest allowable operating voltage.(RMS is root mean square and refers to the effective value of a varying current waveform.) Installation Reference, Surface or Semi-Flush Mounting /�Th �_ cT/ > Mounting is compatible with o (� single gang,double gang,and 0 4"(102 mm)square boxes, C. ( " ° ( 1 1 ( ; IMPORTANT!WALL MOUNT 1-1/2"(38 mm)deep,by others - INSTALLATION HEIGHT REFERENCE Optional 4905-9838 ° � �� (0 11 Sound Damper,field attached I Bottom of lens to attenuate sound 5 to 6 dBA I is either even .,9 _ v with,or slightly Electrical Wiring access hole ® .� �=t ^ above bottom box outline �` of compatible W��Lll!�t : , // / boxes Wiring terminals for .ft n p' I `'TT'-1a----v SmartSync operation _ l°` L Mounting Holes: 4square(4) NFPA 72 requires 80"(2.03 m) 9...maw. that the entire lens minimum Single gang(2) G& V i Double gang(3) be not less than — —� i� 80"and not greaterv �1 ✓ than 96"above the Transparent housing finished floor I and lens assembly Intensity selection t-. _ plug,accessible only i e from rear of housing; (5 (� factory setting is 15 cd Removable cover Strobe intensity (tool required) viewing Slot 3 S4906-0002-5 9/2009 051111plex TrueAlert® Multi-Candela Notification Appliances UL, ULC, CSFM Listed; FM Approved; Visible Notification Appliances with Synhronized Flash; MEA (NYC)Acceptance* Non-Addressabls,,S-nartSvacT"" Operation Compatible Features Visible only(V/O)24 VDC notification appliances ' to with high output xenon strobe,available for wall or ceiling mount: ..• r 4 • Intensity is selectable as 15,30,75,or 110 candela with 7- visible selection jumper secured behind strobe housing ,► • Operation is compatible with ADA requirements(refer �.l j I to important installation information on page 3) ll • Polarized input allows connection to compatible reverse polarity,supervised notification appliance circuit(NAC) • Regulated circuit design ensures consistent flash output Wall Mount Strobes and provides controlled inrush current • Rugged,high impact,flame retardant thermoplastic housings are available in red or white with clear lens - • Listed to UL 1971 and ULC S526 WM" Strobes provide synchronized flash for use with: • 4006,4008,4010,and 4100U Series fire alarm control Ceiling Mount Strobes panels with NACs selected to provide strobe synchronization or SmartSync two-wire control** Descri.tion • 4009 IDNetTm NAC Extenders Multi-Candela TrueAlert synchronized strobes • Separate strobe Synchronization Modules that are provide convenient installation to standard electrical available for Class B or Class A operation boxes.The enclosure designs are both impact and vandal • Separate SmartSync Control Modules(SCMs)that resistant and provide a convenient strobe intensity provide Class B or Class A output from conventional selection. Since each model can be selected for intensity NAC inputs output,on-site model inventory is minimized and changes encountered during construction can be easily Strobe housings provides flexible,easy,and accommodated. convenient semi-flush or surface wall mounting: Wall mount strobe housings are a one-piece assembly • Rear of housing does not extend into box (including lens)that mounts to a single or double gang.or • Wall mount strobes easily mount to single gang,double 4"square standard electrical box.The cover can be gang,or 4-inch square outlet box quickly removed(a tool is required)and covers are • Ceiling mount strobes mount to single gang boxes available separately for color conversion. Wall mount strobe features: Ceiling mount strobes install using standard single gang electrical boxes. Color choice is determined by model • Wiring terminals are accessible from the front of the number. housing providing easy access for installation, inspection,and testing Strobe Intensit Selection • Covers are available separately to convert housing color During installation,a selection plug at the back of the Optional adapters and wire guards: housing determines the desired strobe intensity. An attached flag with black letters on a highly visible yellow • Wall mount strobe adapters are available to cover background allows the selected intensity to be seen at the surface mounted electrical boxes and to adapt to side of the strobe lens. Simplex'''2975-9145 boxes • UL listed red wire guards are available for wall or Strobe Application Reference ceiling mount strobes* Proper selection of visible notification is dependent on occupancy,location, local codes.and proper applications of:the National Fire Alamo Code(NFPA 72).ANSI * Refer to page 2 for guard listing.This product has been approved by the California State A117.1;the appropriate model building code: BOCA. Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code.See CSFM Listing 7125-0026:316 for allowable values andlorconditions concerning ICBO,or SBCCI;and the application guidelines of the material presented in this document.It is subject to re-examination,revision,and possible Americans with Disabilities Act(ADA). cancellation.Refer to page 2 for listing status of wire guards.Additional listings may be applicable;contact your local Simplex product supplier for the latest status.Listings and *" Simplex multi-candela SmartSync two-wire homistrobe appliance operation is protected approvals under Simplex Time Recorder Co.are the property of Tyco Safety Products under one or more of the following U.S.Patent Numbers:5,559.492:5.622.427:5.865.527 Westminster. 5.886,620;6,281,789;6.954.137:7.005,971:and 7,006,003 54906-0001-4 9/2009 Strobe S•ecifications - Wall Mount or Ceiling Mount,Common Specifications Rated Voltage Range Regulated 24 VDC;see Not'1-be'ow - - Flash Rate 1 Hz _ Synchronized NAC Loading Up to 35 synchronized strobes maximum per NAC Temperature Range 32°to 122°F(0°to 50°C) Humidity Range 10%to 93%,non-condensing at IOW I-(?8'0) - -_ Connections Terminal blocks for 18 AWG to 12 AWG('1.9'_rm'to.2`.31 i in 2):two wires per terminal for in/out wiring - -- Housing Dimensions(with lens) 5-1/8"H x 5"W x 2-3/4"D(130 mm x 127 mm x 70 mm) Wall Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Strobe Setting(see Note 2 below) 60 mA 94 mA 186 mA 252 mA Mount Reference RMS Currents 18 VDC 53 mA 84 mA 165 mA 224 mA at other voltages 24 VDC 40 mA 63 mA 124 mA 168 mA Housing Dimensions(with lens) 4-3/4"L x 2-5/16"W x 2-5/8"D(121 mm x 75 mm x 67 mm) Ceiling Maximum RMS Current Rating per 15 cd 30 cd 75 cd 110 cd Mount Strobe Setting(see Note 2 below) 75 mA 125 mA 233 mA 316 mA Reference RMS Currents 18 VDC 67 mA 111 mA 207 mA 281 mA at other voltages 24 VDC 50 mA 83 mA 155 mA 211 mA NOTES: 1. "Regulated 24 VDC"refers to the voltage range of 16 to 33 VDC per UL Standard 1971,Signaling Devices for the Hearing Impaired,changes effective May 1,2004.This voltage range is the absolute operating range.Operation outside of this range may cause permanent damage to the strobe.Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the NAC under worst case conditions. 2. The maximum RMS current listed is the device nameplate rating.Strobe designs are constant wattage and the maximum RMS . current rating occurs at the lowest allowable operating voltage.(RMS is root mean square and refers to the effective value of a varying current waveform.) Installation Reference, Surface or Semi-Flush Wall Mounting 7c__Th L_Th 0 0 Mounting is compatible with Ir. 0 single gang,double gang,and �I 4"(102 mm)square boxes, --, -_ 1-1/2"(38 mm)deep,by others of ...?ea-07 o 1 IMPORTANT!WALL MOUNT � i INSTALLATION HEIGHT REFERENCE it Bottom of lens O 0 �nUPo` _ is either even _ f with,or slightly Electrical Wiring access hole ��u._.110.— -t4, I - above bottom box outline / of compatible -...4p ® 1 boxes Wiring terminals ��— I U )° Ik ( �� Mounting Holes: �� 4"square(4) NFPA 72 requires 80"(2.03 m) Single gang(2) that the entire lens minimum v Double gang(3) be not less than III 80"and not greater than 96"above the Transparent housing finished floor and lens assembly • Intensity selection - plug,accessible only . from rear of housing: E E factory setting is 15 cd Removable cover Strobe intensity (tool required) viewing slot 3 S4906-0001-4 9/2009