Loading...
Report (40) ops `s i70o Z 1 Ce ?Z o Sw 7- k.r tL,CD Worldwide Fire Protection Contacts I www.tyco-flre.com Products Model K17-231 — 16.8 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General NOTICE The 16.8 K-factor,Model K17-231 Up- Description right and Pendent Sprinklers described _` The TYCO 16.8 K-factor, Model herein must be Installed and maintained 1 i , A. in compliance with this.document and K17-231,Standard Response,Standard with the applicable standards of the Na- Coverage,Upright and Pendent Sprin- tional Fire Protection Association,in ad- kiers(Ref.Figure 1)are automatic sprin- dition to the standards of any authori- '; klers of the frangible bulb type.They ties having jurisdiction.Failure to do so are "standard response spray sprin- may impair the performance of these 4 kiers"which produce a hemispherical devices. ', water distribution pattern below the deflector. The owner is responsible for main- taining their fire protection system The 16.8 K-factor, K17-231 Sprinklers and devices in proper operating con- were subjected to full scale,high-piled dition. Contact the installing contrac- storage, fire tests to qualify their use tor or product manufacturer with any in lieu of 8.0 or 11.2 K-Factor standard questions. spray sprinklers for the protection of ,,,. high-piled storage. , � Sprinkler Higher flow rates can be achieved at " much lower pressures with the 16.8 K- Identification factor, K17-231 Sprinklers — making their use highly advantageous in high Number (SIN) r. density applications,such as the pro- tection of high-piled storage. TY7151 -Upright,16.8K Applications for the 16.8 K-factor,Mod- TY7251 -Pendent,16.8K I el K17-231 Pendent and Upright Sprin- TY7151 is a redesignation for C7151, kiers are expanding beyond the cur- g rent listings/approvals.For information G1888,and S8040. regarding research fire tests which may TY7251 is a redesignation for C7251, be acceptable to an authority having ju- G1889,and S8041 risdiction,please contact the Technical - . Services Department. Technical Data Temperature Ratings Refer to Table A. Approvals Finish UL and C-UL Listed.FM and NYC Ap- Natural Brass proved.(Specific details for laboratory physical Characteristics listings and approvals given in Table A. Frame Bronze The approvals apply to the service con- Button Bronze ditions indicated in the Design Criteria Sealing Assembly Beryllium section.) Nickel w/TEFLON IMPORTANT Bulb(5 mm) Glass Always refer to Technical Data Maximum Working Pressure Compression Screw Brass Sheet TFP700 for the"INSTALLER 175 psi(12,1 bar) Deflector Brass WARNING"that provides cautions Pipe Thread Connection with respect to handling and instal- 3/4 inch NPT lation of sprinkler systems and com- ponents.Improper handling and in- Discharge Coefficient stallation can permanently damage K=16.8 gpm/psi12 , a sprinkler system or Its compo- (241,9Ipm/bar112) nents and cause the sprinkler to fail to operate in a fire situation or cause It to operate prematurely. Page 1 of 4 SIPTIMBIR 2014 TPP332 TFP332 Page 2 of 4 TYPE TEMPERATURE BULB SPRINKLER FINISH LIQUID NATURAL BRASS 155°F(68°C) Red UPRIGHT 200°F(93°C) Green 1,2,3,4 K=18.8(TY7151) 286°F(141°C) Blue 155°F(68°C) Red PENDENT 200°F(93°C) Green 1,2,4 K=16.8(TY7251) 286°F(141°C) Blue NOTES: (1) Listed by Underwriters Laboratories,Inc.(UL Listed). (2) Listed by Underwriters Laboratories,Inc.for use in Canada(C-UL Listed). (3) Approved by Factory Mutual Research Corporation(FM Approved). (4) Approved by the City of New York under MEA 177-03-E. TABLE A LABORATORY LISTINGS AND APPROVALS (Refer To The Design Criteria Section) Design Example 1:NFPA 13 provides ceiling Example 2:NFPA 13 provides ceiling only protection(that is,no in-rack sprin- only protection(that is,no in-rack sprin- Criteria kiers)criteria using open frame(that is, kiers)criteria using open frame(that is, no solid shelves)single,double,multi- no solid shelves)single,double,multi- ULand C-UL Listing Requirements multi- ple-row,or portable rack storage(with- pie-row,or portable rack storage(with- UL LULKsting Model ReqK17-uirements out the need for in-rack sprinkler pro- out the need for in-rack sprinkler pro- The TYCO1 &T 16.8 K-factor, tor,Model ers may be tection)of cartoned unexpanded Group tection)of cartoned unexpanded Group (TYinstalled in accordanceSwith NFPA 13 A or B plastics,or,cartoned expanded A or B plastics,or,cartoned expanded standard sprinkler position and area/ Group A or B plastics,with: Group A or B plastics,with: density flow calculation requirements • a storage height of up to 20 feet • a storage height of up to 25 feet for light,ordinary,or extra hazard oc- (6,1 m); (7,6 m); cupancies with a minimum residual • a maximum ceiling height of 27 feet • a maximum ceiling height of 30 feet (flowing)pressure of 7 psi (0,5 bar)in (8,2 m); (9,1 m); wet or dry pipe sprinkler systems, or they may be installed in accordance • a minimum deflector to top of • a minimum deflector to top of with NFPA 13 standard sprinkler posi- storage clearance of 18 inches storage clearance of 18 inches tion and area/density flow calculation (457 mm); (457 mm); requirements for high piled storage oc- • a minimum design density of 0.60 • a minimum design density of cupancies(solid piled,palletized,rack gpm/ft2(24,4 mm/min); 0.80 gpm/ft2(32,6 mm/min); storage,bin box,and shelf storage in- • • a minimum residual(flowing) but not limited to Class l-IV and • a minimum residual(flowing) ( g) Group A plastics)with a minimum resid- pressure of 7 psi(0,5 bar); pressure of 7 psi(0,5 bar); ual(flowing)pressure of 7 psi(0,5 bar) • a minimum design area of 2000 ft2 • a minimum design area of 2000 ft2 for wet or dry pipe systems. (186 m2)for wet systems or 2600 ft2 (186 m2)for wet systems or 4500 ft2 The following two examples are typical (242 m2)for dry pipe systems (418 m2)for dry pipe systems of the types of arrangements permit- FM Approval Requirements ted by NFPA 13. For all combinations The TYCO 16.8 K-factor,Model K17-231 of lesser and greater building heights, (TY7151)Upright Sprinklers may be in- lesser and greater storage heights, stalled in accordance with the applica- storage arrangements, commodity tile control mode density/area guide- classifications,and lesser or greater re- lines provided by Factory Mutual.(FM quired design densities,refer to NFPA guidelines may differ from UL and C-UL 13 for specifics. Listing criteria.) TFP332 Page 3 of 4iii5 1 Frame 6 i l ig 110511111111114111t"\ / 11 2 - Button 5* --------------------- amil 3- Sealing Assembly 4 1/2" 4 - BulbII 5- Deflector* (12,7 mm) 2-3/8" 6- Compression 3 I V.- NOMINAL �� (80,3 mm) Screw 2 Veil r MAKE-IN 'u. 111110111 * Temperature rating is d IIIIIIIIE indicated on deflector. 1 1 o�-� I WRENCH 3/4" FLAT NPT CROSS SECTION UPRIGHT PENDENT FIGURE 1 MODEL K17-231 UPRIGHT(TY7151)AND PENDENT(TY7251)SPRINKLERS Operation Care and The glass bulb contains a fluid that ex- Maintenance pands when exposed to heat.When the 1111111111rated temperature is reached,the fluid The TYCO Ultra K17 Sprinklers must be \ expands sufficiently to shatter the glass maintained and serviced in accordance \ bulb,allowing the sprinkler to activate with this section. and flow water. Before closing a fire protection system \ WRENCH main control valve for maintenance RECESS Installation work on the fire protection system that it controls,permission to shut down the The TYCO Model K17-231 Sprinklers affected fire protection systems must must be installed in accordance with be obtained from the proper authorities 008 this section. and all personnel who may be affected General Instructions by this action must be notified. Do not install any bulb type sprinkler if Sprinklers that are found to be leaking FIGURE 2 the bulb is cracked or there is a loss or exhibiting visible signs of corrosion W-TYPE 8 of liquid from the bulb.With the sprin- must be replaced. SPRINKLER WRENCH kler held horizontal,a small air bubble Automatic sprinklers must never be should be present.The diameter of the painted, plated, coated, or otherwise The owner is responsible for the in- air bubble is approximately 1/16 inch altered after leaving the factory.Modi- spection,testing,and maintenance of (1,6 mm). fled sprinklers must be replaced.Sprin- their fire protection system and devices Step 1. With pipe thread sealant ap- kiers that have been exposed to corro- in compliance with this document, as plied to the pipe threads,hand tighten sive products of combustion,but have well as with the applicable standards the Model K17-231 Sprinkler into the not operated, should be replaced if of the National Fire Protection Asso- sprinkler fitting. they cannot be completely cleaned by ciation (e.g., NFPA 25), in addition to wiping the sprinkler with a cloth or by the standards of any other authorities Step 2. Using the W-Type 8 Sprin- brushing it with a soft bristle brush. having Jurisdiction.Contact the install- kler Wrench(Ref. Fig.2)applied to the ing contractor or product manufacturer sprinkler Wrench Flats (Ref. Fig. 1), Care must be exercised to avoid dam- with any questions. tighten the Model K17-231 Sprinkler into age to the sprinklers before,during,and the sprinkler fitting. after installation.Sprinklers damaged Automatic sprinkler systems are recom- by dropping, striking, wrench twist/ mended to be inspected,tested, and NOTICE slippage,or the like,must be replaced. maintained by a qualified Inspection Also, replace any sprinkler that has a Service In accordance with local re- A leak tight 3/4 inch NPT sprinkler joint cracked bulb or that has lost liquid from quirements and/or national codes. should be obtained with a torque of 10 its bulb.(Ref. Installation Section). to 20 ft.lbs. (13,4 to 26,8 Nm). Higher levels of torque may distort the sprin- kler inlet with consequent leakage or impairment of the sprinkler. tI,130 Worldwide �tyco-fire.com Fire Protection contacts I Products Model K17-231 — 16.8 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General NOTICE The 16.8 K-factor, Model K17-231 Up- Description right and Pendent Sprinklers described The TYCO 16.8 K-factor, Model herein must be Installed and maintained i aai , in compliance with this document and K17-231,Standard Response,Standard with the applicable standards of the Na- Coverage,Upright and Pendent Sprin- tional Fire Protection Association,in ad- , klers(Ref.Figure 1)are automatic sprin- dition to the standards of any authori- klers of the frangible bulb type. They ties having jurisdiction.Failure to do so are "standard response spray sprin- may impair the performance of these { klers"which produce a hemispherical devices. Ya" water distribution pattern below the deflector. The owner is responsible for main- u`"" The 16.8 K-factor, K17-231 Sprinklers taining their fire protection system P and devices in proper operating con- , were subjected to full scale,high-piled dition. Contact the installing contrac- storage, fire tests to qualifytheir use 9 tor or product manufacturer with any in lieu of 8.0 or 11.2 K-Factor standard questions. spray sprinklers for the protection of high-piled storage. Sprinkler Higher flow rates can be achieved at much lower pressures with the 16.8 K- Identification factor, K17-231 Sprinklers — making their use highly advantageous in high Number (SIN) 1,1*.' * density applications,such as the pro- tection of high-piled storage. TY7151 -Upright,16.8K Applications for the 16.8 K-factor,Mod- TY7251 -Pendent,16.8K el K17-231 Pendent and Upright Sprin- klers are expanding beyond the cur- TY7151 is a redesignation for C7151, )' rent listings/approvals.For information G1888,and S8040. regarding research fire tests which may TY7251 Is a redesignation for C7251, be acceptable to an authority having ju- G1889,and S8041 ,r` risdiction,please contact the Technical %, ►,...:1. Services Department. Technical Data Temperature Ratings Refer to Table A. Approvals Finish UL and C-UL Listed.FM and NYC Ap- Natural Brass proved.(Specific details for laboratory Physical Characteristics listings and approvals given in Table A. Frame Bronze The approvals apply to the service con- Button Bronze ditions indicated in the Design Criteria Sealing Assembly Beryllium section.) Nickel w/TEFLON IMPORTANT Maximum WorkingPressure Bulb(5 mm) Glass Always refer to Technical Data Compression Screw Brass Sheet TFP700 for the"INSTALLER 175 psi(12,1 bar) Deflector Brass WARNING"that provides cautions Pipe Thread Connection with respect to handling and instal- 3/4 inch NPT letion of sprinkler systems and com- ponents.Improper handling and in- Discharge Coefficient stallation can permanently damage K=16.8 gpm/psi12 . a sprinkler system or Its compo- (241,9 Ipm/bar"2) nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Pogo 1 of 4 SIPT/MBSR 2014 T11P332 TRP332 Page 2 of 4 BULB SPRINKLER FINISH TYPE TEMPERATURE UQUID NATURAL BRASS 155°F(68°C) Red UPK=8 8R1(TY7151)GHT 200°F(93°C) Green 1,2,3,4 286°F(141°C) Blue 155°F(68°C) Red PENDENT 200°F(93°C) Green 1,2,4 K=16.8(TY7251) 286°F(141°C) Blue NOTES: 1 Listed by Underwriters Laboratories,Inc.(UL Listed). by Underwriters Laboratories,Inc.for use in Canada(C-UL Listed). 3 Approved by Factory Mutual Research Corporation(FM Approved). (4) Approved by the City of New York under MEA 177-03-E. TABLE A LABORATORY LISTINGS AND APPROVALS (Refer To The Design Criteria Section) Design Example 1:NFPA 13 provides ceiling Example 2:NFPA 13 provides ceiling only protection(that is,no in-rack sprin- only protection(that is,no in-rack sprin- Criteria kiers)criteria using open frame(that is, klers)criteria using open frame(that is, no solid shelves)single,double,multi- no solid shelves)single,double,UL and C-UL Requirements multi- ple-row,or portable rack storage(with- pie-row,or portable rack storage(with- UL n CO ULK Listing Model ReqK17-uirements out the need for in-rack sprinkler pro- out the need for in-rack sprinkler pro- The TYCO &16.8 K-f) tor,Model rs may be tection)of cartoned unexpanded Group tection)of cartoned unexpanded Group (TYinstalled in Y7251 accordanceSpwith NFPAy 13 A or B plastics,or,cartoned expanded A or B plastics,or,cartoned expanded standard sprinkler position and area/ Group A or B plastics,with: Group A or B plastics,with: density flow calculation requirements • a storage height of up to 20 feet • a storage height of up to 25 feet for light,ordinary,or extra hazard oc- (6,1 m); (7,6 m); cupancies with a minimum residual • a maximum ceiling height of 27 feet • a maximum ceiling height of 30 feet (flowing) pressure of 7 psi (0,5 bar)in (8,2 m); (9,1 m); wet or dry pipe sprinkler systems, or they may be installed in accordance • a minimum deflector to top of • a minimum deflector to top of with NFPA 13 standard sprinkler posi- storage clearance of 18 inches storage clearance of 18 inches tion and area/density flow calculation (457 mm); (457 mm); requirements for high piled storage oc- • a minimum design density of 0.60 • a minimum design density of cupancies(solid piled,palletized,rack gpm/ft2(24,4 mm/min); 0.80 gpm/ft2(32,6 mm/min); storage,bin box,and shelf storage in- cluding but not limited to Class I-IV and • a minimum residual(flowing) • a minimum residual(flowing) Group A plastics)with a minimum resid- pressure of 7 psi(0,5 bar); pressure of 7 psi(0,5 bar); ual(flowing)pressure of 7 psi(0,5 bar) • a minimum design area of 2000 ft2 • a minimum design area of 2000 ft2 for wet or dry pipe systems. (186 m2)for wet systems or 2600 ft2 (186 m2)for wet systems or 4500 ft2 The following two examples are typical (242 m2)for dry pipe systems (418 m2)for dry pipe systems of the types of arrangements permit- FM Approval Requirements ted by NFPA 13. For all combinations The TYCO 16.8 K-factor,Model K17-231 of lesser and greater building heights, (TY7151)Upright Sprinklers may be in- lesser and greater storage heights, stalled in accordance with the appiica- storage arrangements, commodity tile control mode density/area guide- classifications,and lesser or greater re- lines provided by Factory Mutual.(FM quired design densities,refer to NFPA 13 for specifics. guidelines may differ from UL and C-UL Listing criteria.) . TFP332 Page 3 of 4 1 - Frame 6 :l 1+ g7 1-1-6-"---- 6 \111\ ///�% \ R �, ` , 2- Button 5* 1 3- Sealing Assembly 4 1/2" _ 4- BulbflIII-11 5- Deflector* 3 11 (12,7 mm) 2-3/6" � 6- Compression fir__ NOMINAL ��� 60,3 mm) Screw 2i�zta� 00 MAKE-IN .�■ ( * Temperature rating is 1 d M. indicated on deflector. S 0 =c II i WRENCH 3/4' _ FLAT NPT CROSS SECTION UPRIGHT PENDENT MODEL K17-231 UPRIGHT(TY!5 FIGURE AND PENDENT (TY7251)SPRINKLERS Operation Care and The glass bulb contains a fluid that ex- Maintenance pands when exposed to heat.When the �� rated temperature is reached,the fluid The TYCO Ultra K17 Sprinklers must be \ EMI expands sufficiently to shatter the glass maintained and serviced in accordance bulb,allowing the sprinkler to activate with this section. and flow water. N Before closing a fire protection system \ WRENCH Installation main control valve for maintenance RECESS work on the fire protection system that it controls,permission to shut down the \ The TYCO Model K17-231 Sprinklers affected fire protection systems must \\ must be installed in accordance with be obtained from the proper authorities �r this section. and all personnel who may be affected ob �-ii..-1 General Instructions by this action must be notified. Do not install any bulb type sprinkler if Sprinklers that are found to be leaking FIGURE 2 the bulb is cracked or there is a loss or exhibiting visible signs of corrosion W-TYPE 8 of liquid from the bulb.With the sprin- must be replaced. SPRINKLER WRENCH kler held horizontal,a small air bubble Automatic sprinklers must never be should be present.The diameter of the painted, plated, coated, or otherwise The owner is responsible for the in- air bubble Is approximately 1/16 inch altered after leaving the factory.Modi- spection,testing,and maintenance of (1,6 mm). fied sprinklers must be replaced.Sprin- their fire protection system and devices Step 1. With pipe thread sealant ap- kiers that have been exposed to corro- in compliance with this document, as plied to the pipe threads, hand tighten sive products of combustion,but have well as with the applicable standards the Model K17-231 Sprinkler into the not operated, should be replaced if of the National Fire Protection Asso- sprinkler fitting. they cannot be completely cleaned by ciation (e.g., NFPA 25), in addition to Step 2. Using the W-Type 8 Sprin- wiping the sprinkler with a cloth or by the standards of any other authorities brushing it with a soft bristle brush. having jurisdiction.Contact the install- kler Wrench(Ref. Fig.2)applied to the ing contractor or product manufacturer sprinkler Wrench Flats (Ref. Fig. 1), Care must be exercised to avoid dam- with any questions. tighten the Model K17-231 Sprinkler into age to the sprinklers before,during,and the sprinkler fitting. after installation. Sprinklers damaged Automatic sprinkler systems are recom- by dropping, striking, wrench twist! mended to be inspected, tested, and NOTICE slippage,or the like,must be replaced. maintained by a qualified Inspection Also, replace any sprinkler that has a Service in accordance with local re- A leak tight 3/4 inch NPT sprinkler joint cracked bulb or that has lost liquid from quirements and/or national codes. should be obtained with a torque of 10 its bulb.(Ref.Installation Section). to 20 ft.lbs. (13,4 to 26,8 Nm). Higher levels of torque may distort the sprin- kler inlet with consequent leakage or impairment of the sprinkler.