Report (3) [ u--23(%, se-,) / 3 0 RECEIVED OCT 09 2012 Advanced Security & Fire CITY OFTIGARD 2218 NE Sunrise Lane, Hillsboro OR 97124 BUILDING DIVISION (503) 519-4550 Fax (503) 640-8311 October 5th 2012 Fire Alarm Operational Matrix General Overview The fire alarm system will have battery back up to sustain it in the case of an AC power failure. Alarm system will have dual phone lines, a primary and secondary, if the primary fails the secondary will transmit signals to central station. All functions of the fire alarm system are supervised, (AC power, low battery,phone line integrity, and all alarm circuits. )Fire alarm troubles and alarms are both transmitted to the central station and annunciated locally at the keypad and horn/strobes. Specific Operation • Troubles are annunciated at keypad in English text, at the same time they are transmitted to the central station. Operator at central station will call a predetermined response list to notify of trouble. Advanced Security& Fire will be notified of system troubles at the same time. • Alarms will be transmitted to the central station as well as annunciated locally. Central station will notify fire dept. dispatch center of fire alarm, and then call premises to try and verify alarm. Response list will be called to notify users of alarm. • Alarms can be silenced at the keypad by pressing fire silence button. • Fire system will be in trouble until fire alarm system is reset by pressing the fire reset button. • Common area smoke detectors, and sprinkler water flow switch monitor for fire conditions and trigger a fire alarm. • Upon trigger of fire alarm by any smoke detector, sprinkler water flow, or manual fire pull station, alarm will be annunciated locally via horn/strobe devices, central station will be signaled,HVAC units and fire smoke dampers will be shut down by the fire alarm panel. • Elevator will be recalled to the second floor-doors will open and functionality of elevator will stop until fire system is reset. If new second floor fire protection devices activate than elevator will be recalled to first floor, doors will open and elevator will cease to function until fire alarm system is reset. Elevator. Company Information Advanced Security& Fire is located in Hillsboro, Oregon and is owned and operated by David Moravik. I have been in the alarm industry since 1981 and licensed as a journeyman low voltage electrician since 1984, (license# 611LEA). My state of Oregon electrical license is (CLE-8 ). Advanced Security&Fire is registered with the state of Oregon contractor's board(contractor's board# 166176). We are a member of the NFPA, and the local fire and burglary alarm association. Central Station Information Advanced Security&Fire monitors its alarm systems through Central Station Monitoring in Estacada, Oregon. They are certified to monitor all alarm system types. Phone#is ( 503-630-2896). Sincerely, Advanced Security&Fire ,Ute •� - //9/?S,� 'v 5-" !' Wes•ate Baptist Chur Ph#4 = 60 �"`S KNI(;II l t 5 •t?1ep04i*' Advanced Security&Fire IJ 1.2 I 12/2/2010 Wdtap4 mp Panel la is K-5208 Model:SK-5208 Fire Alarm Cont tioinlep: NAC current: 3.0 Amp s (: n'-JSecurity Closet ;' Yotts: 24111 Panel Curre.* 6.0 Amps'. r;rtirrent Dmiro WIrerAli?Y6 €h ms,Per'..Len.100' .Actuat Volts ss y. r y� Alert(' &Type 1000 Ft � Et L 8K.8208 . SK-5208 Main Control t, 0.140 0.160 r41(1' SK-5208 Prgm'd NAC's .4; 0.000 0.160 -A IA,'LY SK-5208 Pgm Alm Rly 0.000 0.000 • SK-E217 SK-5217 Zone Expdr I7 0.060 0.260 5235. SK-5235 LCD Remote 1 0.035 0.050 ° SK-5280 SK-5280 Display Mod 0.000 0.000 SK-5220 SK-5220 Dir Con Mod 0.000 0.000 SK-7181 SK-7181 Zn Cnvtr 0.000 0.000 , 5624 Serial/Parallel Cnvtr 0.000 0.000 100-1 1st Floor S Side-Ckt 1 0.001 0.095 `r 100-2 '1st Floor N Side-Ckt 2 0.001 0.095 Initiating Device Ckt 3 0.000 0095 lam. Initiating Device Ckt 4 0.000 0.095 100-5 Initiating Device Ckt 5 0.000 0 000 = Initiating Device Ckt 6 0.000 0 000 i 7 Initiating Device Ckt 7 0.000 0.000 100-8 Initiating Device Ckt 8 0.000 0.000 1DC-9 Initiating Device Ckt 9 IOC-10' Initiating Device Ckt 10 0.000 0.000 I0G-11 Initiating Device Ckt 11 0.000 0.000 IDC-12 Initiating Device Ckt 12 0.000 0.000 100-13 Initiating Device Ckt 13 0.000 0.000 /00.-14 Initiating Device Ckt 14 0.000 0000 -1S Initiating Device Ckt 15 0.000 0000 11 18 Initiating Device Ckt 16 0.000 0.000 100 7" Initiating Device Ckt 17 0.000 0000 MIC-18 Initiating Device Ckt 18 0.000 0.000 .- 11111O=19 `Initiating Device Ckt 19 0.000 0.000 100-20 '"Initiating Device Ckt 20 0.000 0.000 IDC-21 Inactive, Add SK-5217 0.000 0.000 IDC-22 Inactive, Add SK-5217 0.000 0.000 10C-23 Inactive, Add SK-5217 0.000 0.000 IDC-24 Inactive, Add SK-5217 0.000 0.000 1025 Inactive, Add SK-5217 0.000 0.000 =100-26 " Inactive, Add SK-5217 0.000 0.000 1000-27 Inactive, Add SK-5217 0.000 0.000 1DC-28 Inactive, Add SK-5217 0.000 0.000 1DC-29 Inactive, Add SK-5217 0.000 0.000 100-30" Inactive, Add SK-5217 • 0.000 0.000 NAC-1 1st Floor S Side 0.000 1.125 #16 Solid 4.02 200 1.81 18:50 ' 8.87% NAC-2 1st Floor S Side 0.000 0.875 #16 Solid 4;02 179 1.44 19,14 6.17% NAC-3 lst Floor N Side 0.000 0.750 #16 Solid 4.02 260 2.09 18.83 7.69% NAC-4 1st Floor N Side 0.000 0.750 #16 Solid 4.02 290 2.33 18.65 8.57% Aux Aux Power Out 0.000 0.000 #12 Solid 1.59 , 0.00 20.40 0.00% Total StaridbY Current(A► 0.237 4.510 Tam Alarm Curr (Amps) • , 14114041111 60 0.083 1, tiln"time Intrilralbra t+1t0 (S# ) Tr4gliStar Atl Ftimareril.142205 0.3?4"`late Alarm All Reauaed Total Combined AH Regi irree 14.58 Command Shortcuts Multiply By The Derating Factor 1.20 Print Page Minimum Battery Hours Required17.50 Configure Circuits .- 2--)----) ,40 i •Yld ' /-,e,i,e ,i, ,zi,i,d Pi7W,5-. 'z's- , I. /-Z-Z-4;-),-2AS - SII,1�;'N 1 �y� IIWestgate Baptist Church Ph#5 � 1 1'\I t;1 I 1' ""5 Advanced Securtiy&Fire , 1.2 6.•.:_,-;,,,:,,,,y•-,,,.'.,,,:••<,J-3f,_- • � 10J4/2012 Stt Tr. d% j P :ID J S K-5208 -: H[O4$" fi t lit t T.nt 3 ttA 1 .: Fire/Security Closet 31 � Max Pabel.Cint60 S SK-5208 Main Control ••i,,-.i„, 0.140 0•160 N XT SK-5208 Prgm'd NAC's � 0.000 0160 A RI Y y SK-5208 Pgm Alm RIy ,-..-,,!„!..4›?;, 0.000 0.000 k 5 SK-5217 Zone Expdr 0.060 0.260 SI SK-5235 LCD Remote ;' 0.035 0.050 ` 8K428Q ,SK-5280 Display Mod `f 0.000 0.000 r. SK-5220 SK-5220 Dir Con Mod .• 0.000 0.000 SK4IB1 SK-7181 Zn Cnvtr = 0.000 0.000 ;' Serial/Parallel Cnvtr 0.000 0.000 IDC-i 1st Floor S Side-Ckt 1 0.001 0.095 IOC-2 1st Floor N Side-Ckt 2 0.001 0.095 *' l';'1';'''' ''Initiating Device Ckt 3 0.000 0095 v Initiatin. Device Ckt 4 0.000 0.� r t x 1I Initiating Device Ckt 6 0.000 0000 w - . . 7' Initiating Device Ckt 7 0.000r 0000 • -064-:'-:--:-Initiating Device Ckt 8 0.000 0.000 10C-9 Initiating Device Ckt 9 0.000 0.000 •IEC-'IO " Initiating Device Ckt 10 0.000 0.000 IOC•11 ,Initiating Device Ckt 11 0.000 0.000 IDC-12 Initiating Device Ckt 12 0.000 0.000 tDC.13 ' Initiating Device Ckt 13 0.000 0.000 ;,Initiating Device Ckt 14 0.000 0000 �'$. Initiating Device Ckt 15 0.000 0.000 X:0 Initiating Device Ckt 16 0.000 0.000 TM tO', Initiating Device Ckt 17 0.000 0 000 y ::::'---..-1•1136'1-66.-I;;"1; 1Initiating Device C 18 0.000 0000 11bc l I Initiating Device Cktkt 19 0.000 0.000 :' IDC-20 ;'Initiating Device Ckt 20 0.000 0.000 2t Inactive, Add SK 5217 0.000 0.000 • 11 2 .Inactive, Add SK:5217 0.000 0.000 • fD C-23.. Inactive, Add SK-5217 0.000 0.000 4 Inactive, Add SK5217 0.000 0.000 Inactive, Add SK-5217 0.000 0.000 t0C;-26..' Inactive, Add SK-5217 0.000 0.000 I 7° ;Inactive, Add SK-5217 0.000 0.000 '-'6X.,,1:48..''•-...'Inactive, Add SK-5217 0.000 0.000 II0C-2B Inactive, Add SK-5217 0.000 0.000 f0C i Inactive, Add SK-5217 0.000 0.000 NAC-1 1st Floor S Side 0.000 1.125 #16 Solid 4. 200 1.61 1.8:x; 8.87% NAG=2 1st Floor S Side 0.000 0.875 #16 Solid 4 Q2 179 x,44; 1€i14 6.17% NAC-3 1st Floor N Side 0.000 0.750 #16 Solid 402 260 2,09 18» 7.69% ILIAC-sI 1st Floor N Side 0.000 0.750 #16 Solid A 2 290 2 18;x`,' 8.57% Aux Aux Power Out 0.000 0.000 #12 Solid 1x58 Q.09 2044, 0.00% T Ar } 0-23T t AIS Gurre ,� Mann AH I nr er1 T i btned AH flie d •14;61 Command Shortcuts M SY TIe Oerairig Fact 1.20 , nHirn•��icaly Required; 1t• Configure Circuits Print Page • • ,e/e;Lt , ,e 1 I/ 2 1#/9-St- ` S //02 /,,,,Gt - ti I I,I';\ IWestgate Baptist Ph#5 24 I N F \I(..II"I' �1Advanced Security&Fire g� 1.2 I Pn.+.e'F• - n-1-r _a ( 10/4/2012 Y :C GpW> 10 .. r 10 54 ;Power Maxfiwcult Cohn 3Arms; Fire/Security Closet 24 VD Panel Cures 6 Ate; Cltt'; .Edetrre N `" ■zireAWG' (Per {t) Y 1 - :` . '. &Type I000 Ft 10 ay" a.. 1�OL 0.000 0.290 #16 Solid 4.02 350 2.81 - 19.5$ 4.01% 2 5496(1)Circuit 2 0.000 0.000 #16 Solid 4.02 000.'" 20.40 >' 0.00% 3 5496(1)Circuit 3 0.000 0.000 #12 Solid 1,59 000 20,40 0.00% 4 ' 5496(1)Circuit 4 0.000 0.000 #12 Solid ,1 #. 20.E 0.00% Aux5496(1)Aux Power Out 0.000 0.000 #12 Solidi. _ 20.40 0.00% Aw(P *1 #of NAC's Used ( 0.000 0.000 i7 - ''C F' " ! '' r�, 'y �x,' f _ 0190 TOW at� (M $�� oW��rm( ) � �Rr1 ; ,y,'. = .. i!1, Ar X ,,.,•, rl •r t eein.liif_ 1.60 8,' ) T9 AH R , 0 ' r Aly mAft Re imd• . Total Corribirted AH Required ` 1.00 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By DeratingFactor 1;20 the minimal difference between solid and stranded wire no differential was made. Minimum Battery AmpHours Required 1.20 *1. A vallue must be entered if you have selected any output as Aux.Power. P1[);15496(2) model 51tt49lPawer ,CciirtAt>Tp8 4V0C tParisiR ra* mc : 1 ' 1Avivo i . , is P�pr yr) . y + .u 1 t + ty EOLY° ry 7 �V �. Awn &Typt 1 . 5496(2)Circuit 1 0.000 0.000 #12 Solid } . . = 2 5496(2)Circuit 2 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 3 5496(2)Circuit 3 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 4 5496(2)Circuit 4 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% Aux 5496(2)Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% Aux owret *1 #of NAC's Used 0.000 0.000 , 5496 Pt r oder `-0.040 "0.160.1 0.000 �(An )Tote 0>Eitpgt Polder Requle d e, Total S ,C fl l*( )1 L1040 0.160 'Total Alarm Current(Amps) Stamp`i ttein tion, 24 \;0.083 Alarm Time In Mimes 160 (5 Mins) • Tole( " . titteo 0:013 Total Maim AH Required Total Combinad AH Required- 0.97 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By The Derating 1.20 the minimal difference between solid and stranded wire no differential was made. Mfrlimum Battery AmpHours Required 1 '17 *1. A vallue must be entered if you hawe selected any output as Aux.Power. Circuit Configuration .roj nor • .n Project Name: Westgate Baptist Ph#5 Project ID: 0 Prepared By: Advanced Security&Fire Date: 10/4!2012 Gkt. umber 1 Panel ID '5496(4) . . Ckt.Name:2nd Floor RrnPs S";Side-=GGt 1 Max Circ Currant: 3 0 rt �' fi.nett DrawTotal `ot ir Standby A Alam x#, 0.000 .0.0/7 0 0.231 }r P2R 110c. 0.000 0.t ,'0 - 0.000 0.059 Unuse. 0.000 11000 0. 0.t00 Unused 0.000 0.000 000 0.000 0000 `v 0.000 Totals 0.000 0.290 �Number 2 l 1)` C i�tame:.€f49€i(1 2 t � 3 Unused 0.0� Ot30 0 ;, 4000 Unused 0.000 Unused 0.000 0 000 t}000 - 0.000 Unused 0.000 0,000 0.000 0,000- 0.000 0.000 Totals 0.000 0.000 Ckt.Number: 3 Panel ID';�1) Scutt 3,.. t 3 Qty Dom. At' 7.` 6 Unused 0.000._.; 4 ". '<0.000 `_ 0.000 Unused 0.000 11.000 0.0 0.000 Unused0.0011 0.000 0.000. 0.000 Unused0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0.000 Gkt Number: 4 Panel ID: 5496(1) Cid.Name:"5496(1)t tuft 4 Max Circuit Current: 3 Amps Qty Device CurrentDra�n►:taach Current Draw Total Standby Alarm Standby Alarm Unused 0.000 0.000 0.000 ' 0.000 Unused 0.000 0.000 0.000" 0.000 Unused 0.040 0.000 0.000 0.000 Unused0.000 . . .. 0 O t,_,'Y 0.00 I 0.000 0.000 Totals 0.000 0.000 FIRE ALARI,,1 CONTROL PANEL SILENT Model 5208 y ` KNIGHT Fire Alarm Control Panel by Honeywell with Digital Communicator The Fire Alarm Control Designed to Grow with Your Systems Needs, Without The Growing Pains. The SK-5208 is a microprocessor based control panel with built-in UL listed communicator designed for applications requiring smoke detection, manual pull stations, and sprinkler supervision. It features an easy to read LCD display with programmable English readout and user friendly tactile keys. The basic unit offers 10 zones of initiation and is expandable up to 30 zones for larger applications. The SK-5208 has a complete line of supervised accessories that provide remote annunciation, auxiliary control zone expansion. Ideal for new and retrofit applications, the SK-5208 delivers the performance to handle your installation. Features • Built-in synchronization for • 10 zones,8 Class B (Style B)and 2 appliances from AMSECO®, Class A(Style D)or Class B(Style Gentex®, Faraday, System Sensor®, B)zones,expandable to 30 zones and Wheelock® • Supervised zone expanders and I/O • Programmable date settings for modules can be mounted remotely Daylight Saving Time from the main control panel • Clock source setting options for 50 • Event History Buffer(150 events) Hz,60 Hz,or internal (uses the with date/time stamp panel's internal clock) • All zones are compatible with 2-or Specifications 4-wire detectors Operating Voltage: 24 VDC • 8 selectable/programmable output patterns for notification appliance Primary AC: 120 Vrms @ 60Hz,2A circuits Total DC Load: 6 Amp • Built-in Digital Alarm Communicator Current Draw: Transmitter(DACT) Standby: 140 mA • 4 Notification Appliance Circuits Alarm: 460 mA • 4 programmable general purpose Flush Mounting Dimensions: relays Height: 24.75"(62.9 cm) • Programmable smoke verification, Width: 14.5"(36.8 cm) pre-alarm delay,cross zoning and Depth: 3-7/16"(8.73 cm) enhanced verification mode features with 5/8"protruding that can help minimize false alarms Overall Dimensions: SK-5208 • Programmable from the built-in Height: 26-3/8"(67 cm) control panel touchpad,remote Width: 17-3/16"(43.66 cm) • SKSS Downloading Software annunciator,or Windows®SKSS Total Depth: 4"(10.16 cm) • Plex-2 Door Option downloading software Operating Temp: 32°to 120° F • Direct connect port for on-site (0°to 49°C) Listings and Approvals • UL Listed up/downloading with Windows® Humidity: 10-93% noncondensing • CSFM Listed SKSS downloading software • Built-in walk test feature Optional Accessories • MEA approval 429-92-E Vol. XIII • Single or dual interlock water • SK-5235 LCD Remote Annunciator releasing capability • SK-5217 10 Zone Expander • Plex door option combines a dead (2 max. per system) front cabinet door with a clear • SK-5280 Status Display Module(8 window, limiting access to the panel max. per system) while providing single button • 7181 Fire Zone Converter operation of the reset and silence • 5220 Direct Connect Module functions • 5824 Serial/Parallel Printer Interface • Programmable AC trouble relay Module FIRE ,LARI 1 CONTROL PANEL Model 5208 Fire Alarm Control Panel with Digital Communicator Engineering Specification The system shall contain a fire alarm control panel to supervise and operate heat and smoke detection devices, 1 • manual fire alarm devices, alarm notification devices and visual annunciators. The system shall also be capable of monitoring for sprinkler supervisory and water flow conditions. The system must have a built in UL listed fire communicator that can be enabled/disabled as needed on a per job basis. In addition, the system will sound alarms locally for purpose of evacuation. Telephone Line 1 Telephone Line 2 Direct Connect - For On-Site Programming 2 Class A(Style D) U 1111 1 or Class B (Style B)-- 4 Initiation Circuits 4. —,Programmable .; , .. Form C Relays r- 8 Class B (Style B) _ i. 411__ ' Notification Initiation Circuits "`"" & a * 3 Appliance Circuits ,, IJ "�♦ k NM i 5235 Remote is II Annunciators 0 0 ' -I 00 i` ....._♦f--11 i , SBUS Devices ~:p 5280, 5217, & 5824 To AC SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA '' y� to keep our product information up-to-date and accurate.We cannot cover NI KNIGHT all specific applications or anticipate all requirements.All specifications are FORM#350318 Rev C subject to change without notice.For more information,contact Silent ©2010 Honeywell International Inc. by Honeywell Knight 12 Clintonville Road,Northford,CT 06472-1610 Phone:(800)328-0103,Fax:(203)484-7118. www.silentknight.com FIRE SYSTEM ACCESSORY 410 SILENT 5496 Intelligent 4. KNIGHT Power Module v by Honeywell A dynamic combination of power and intelligence for your notification expansion needs. The Model 5496 Intelligent Power Module by Silent Knight is the most-powerful and cost-effective power supply , available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensor®, Gentex®, Faraday,AMSECO and Wheelock®—what you need to drive power-hungry components like ADA notification appliances. The 5496's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. For the most sophisticated and cost-effective notification power supply available, you need Model 5496. Call Silent Knight today for more information at 1-800-328-0103. Model 5496 • 3 amps per output circuit Intelligent Power Module • Ground fault detector The model 5496 is a 6 amp notification • Communicates to the FACP via 4- power expander that provides its own wire SBUS(wire runs up to 6000 ft) AC power connection, battery charging • AC loss delay option shuts off power circuit,and backup battery for use with to non-essential high-current fire and security controls such as the accessories like magnetic door IntelliKnight Model 5808 Fire Control holders /Communicator.The 5496 is the cost- • Lightweight design adds to ease of effective solution for powering installation and reduces shipping notification appliances required by the costs Americans with Disabilities Act(ADA). ▪ UL 864,1481 & 1971 listed The 5496 has built-in ANSI cadence • pattern,which can upgrade older ANSI Cadence pattern output control panels that lack cadence capability built-in capability.The Output circuits can be Specifications programmed as Notification Appliance AC Input 120 VAC at 2.7 A Circuits,or as Auxiliary Power fC I� '°�' (configurable for,constant,resettable, Output: 24 VDC at 6 amps or door holder power). Current: Model 5496 Intelligent Features Standby 40 mA Power Module • UL Listed for 6 amps of notification Alarm 160 mA power Ambient Temp.: 32°to 120° F Notification/Aux. 0°to 49°C • Power supply's advanced switch Power circuits: 4 mode design reduces damaging Dimensions: 12.25"W x 16"H x heat and manages power up to 50% Output 3"D(30.88 cm W configuration: 2 Class A(Style Z) x 40.64 cm H x more efficiently than other systems 4 Class B(Style Y) 7.62 D cm) • Built-in synchronization for (1 Class A& appliances from AMSECO, Gentex®, 2 Class B) Approvals: UL Faraday, System Sensor®,and Amps per CSFM Wheelock® output circuit: 3.0(6.0 amps total) MEA 429-92-E vol.XIV • 24 VDC filtered output voltage Notification • Four power-limited notification circuit output: 20.4 to 27.3 VDC Compatible FACPs outputs;2 Class A or 4 Class B,or 1 @ 3.0 amps each, • IntelliKnight 5700 Class A and 2 Class B 4.7k EOL resistor • • NACs are programmable as required •on each IntelliKnight 5808 Notification Appliance Circuits,or as Class B circuit • IntelliKnight 5820XL auxiliary power to be used as Battery charging constant,resettable,or door holder capacity: 35.0 AH power FIRS SYSTEI.1 ACCESSORY Firepower 5496 Distributed Power Module Engineering Specifications The contractor shall supply a power module compatible with the Silent Knight FACP. The power module must have 6.0 amps of output power.The power module shall connect to the main FACP via an RS 485 system bus (SBUS). The Outputs shall be programmable as Notification Appliance Circuits, or as Auxiliary Power (configurable for, constant, resettable, or door holder power). The power module shall have four separate outputs. The power module RS 485 bus shall be optically isolated providing ground loop isolation and transient protection. 4 Outputs Programmable as Notification Appliance Circuits, or as Auxiliary Power Output 1 . SBUS Communication To a Compatible Output 2 -11111111Silent Knight FACP Output 3 . , 10- Output 4 -41111 Auxiliary Power Can Be Programmed To Be Constant, Resettable, or Door Holder Power SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA Nvp KNIGHT to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350387 Rev D subject to change without notice.For more information,contact ©2010 Honeywell International Inc. by Honeywell Silent Knight 12 Clintonville Road,Northford, CT 06472-1610 Phone:(800)328-0103,Fax:(203)484-7118.www.silentknight.com CONVENTIONAL FIRE CONTROL PANEL ACCESSORY PS-DA and PS-SA Ar Conventional Pull-stations t r • Easy to Install and Operate The PS-DA/PS-SA Pull Stations are non-coded manual pull stations which " provide a Fire Alarm Control Panel (FACP)with a single alarm initiating input signal. The PS-DA/PS-SA pull stations includes both single-action and dual-action models equipped with key lock/reset. It was designed to meet multiple applications with the installer and end-user in mind. Its innovative design, durable construction, and mul- tiple mounting options make the PS-DA and PS-SA simple to install, maintain, and operate. Operation 1 The single-action pull-station is FIRE4 activated by a single pull-down of FUEGOIFi,RE the alarm handle. The dual-action versions require pushing in the 00A T!VATEDe l 1 handle, then pulling the handle down for activation. The PS- DA/PS-SA manual pull stations are 1 ' r', 1 UL listed and meet the ADA requirement of a 5-lbs. maximum pull force to activate. Operating - instructions are molded into the handle along with Braille text. crt s art r•.t • Molded terminal numbers can be i+.t+, 41 ! t•.vtc,tr: t c 0 - found adjacent to the wiring termi- ,, bi nals. 11115 Models: PS-DA PS-DASP PS-SA—Single action with `pigtail' connections and a key lock reset. PS-DASP—Same as PS-DA Specification: Pigtail wires are provided for con- except with both English and g Spanish operating instructions. Dimensions: vection to the Fire Alarm Control Height: 5-1/2"(13.97 cm) Panel's (FACP) initiation circuit. Features: Width: 4"(10.16 cm) Depth: 1-7/16"(3.65 cm) PS-DA— Dual action model with • UL Listed o screw terminal connections and a Operating • CSFM Listed temperature: 32°F to 120°F key lock reset. (0°C to 49°C) • Meets ADA requirements PS-DAH—Same as PS-DA except Operating instructions are mold- Electrical: with hex lock reset. p g Switch Contact ed into the handle along with Rating: 0.25 A @ 30 VAC PS-DALOB —Same as PS-DA with Braille text. or VDC "outdoor use" listing. Includes SB- • Made of durable Lexan Accessories: I/O backbox and sealing gasket. • Available in Spanish SB-1/0 Surface Mount SILENT • Key resettable Back-box TS KNIGHT • Easy to Install and operate BG-TR Trim Ring by Honeywell • Single or dual action • Surface mount box available CONOENTIONAL FIRE CONTROL PANEL ACCESSORY PS-DA and PS-SA 1. Conventional Pull-Stations ' Engineering Specification Manual Fire Alarm Stations shall be non-code, with a key-operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key.An operated station shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red colored LEXAN®(or polycarbonate equivalent)with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (25.4 mm)or larger.* Stations shall be suitable for surface mounting on matching back-box SB-10; or semi-flush mounting on a standard single-gang, double-gang, or 4" (10.16 cm)square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act(ADA)or per national/local require- ments. Manual Stations shall be Underwriters Laboratories listed. *NOTE:The words"FIRE/FUEGO"on the PS-DASP shall appear on the front of the station in white letters, approximately 3/4" high. + + FIRE FIRE .,..,.,44 . : 4 1 1 j „, , . • L....... .i j . . � I • 1 rr s. �i .*.,' ..t$"& +; PS-SA Front View PS-DA Front View PS-SA Rear View PS-DA Rear View SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA ICNIGI IT keep our product information up-to-date and accurate.We cannot cover all r ` specific applications or anticipate all requirements.All specifications are sub- P/N 350241 Rev.C ject to change without notice. For more information,contact Silent Knight 12 ©2009 Honeywell International Inc. by Honoyw Clintonville Road Northford,CT 06472-1610 Phone:(800)328-0103, Fax:(203)484-7118.www.silentknight.com SYSTEM • SENSOR aFy Photoelectric Smoke Detectors • System Sensor i3'"series smoke detectors represent • 3 significant advancement in conventional detection. The i3 familyis founded on three principles:installation TM P p ease,intelligence,and instant inspection. Features Installation ease.The i3 line redefines installation ease with its Plug-in detector line,mounting base included plug-in design.This allows an installer to pre-wire bases(included • with heads).The large wire entry port and in-line terminals provide •Large wire entry port ample room for neatly routing the wiring inside the base.The base •In-line terminals with SEMS screws accommodates a variety of back box mounting methods as well as •Mounts to octagonal and single gang back boxes,4 square back direct mounting with drywall anchors.To complete the installation,i3 boxes,or direct to ceiling heads plug into the base with a simple Stop-Drop'N Lock"'action. •Stop-Drop'N Lock attachment to base Intelligence.P detectors offer a number of intelligent features •Removable detector cover and chamber to simplify testing and maintenance.Drift compensation and Built-in remote maintenance signaling smoothing algorithms are standard with the P line to minimize • nuisance alarms.2-wire i3 detectors can generate a remote LED- •Drift compensation and smoothing algorithms indicated maintenance signal when connected to the 2W-MOD2 •Simplified sensitivity measurement loop test/maintenance module or a panel equipped with the i3 Wide angle,dual color LED indication protocol.The SENS-RDR,a wireless device,displays the sensitivityof i3 • detectors in terms of percent-per-foot obscuration. •Loop testing via EZ Walk feature •Built-in test switch Instant inspection.The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition:normal standby,out-of-sensitivity,alarm,or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol,the EZ Walk loop test feature is available on 2-wire i3 detectors.This feature verifies the initiating loop wiring by providing LED status indication at each detector. Agency Listings 14) T , ® 1 ) MEA MSFM �� } LISTED APPROVED 1j1 approved approved c(ill Us 5911 3011446 7272-1653:152 290-01{ 2093 3180932 X11 Smoke Detector Specifications Architectural/Engineering Specifications } Smoke detector shall be a System Sensor i3 Series model number ,listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.The detector shall be a photoelectric type(Model 2W-B,4W-B)or a combination photoelectric/thermal(Model 2WT-B,4WT-B)with thermal sensor rated at 135°F (57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal,single-gang,and 4-inch square back boxes with a plaster ring,or direct mount to the ceiling using drywall anchors.Wring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual- color LED indication that blinks to indicate power up,normal standby,out of sensitivity,alarm,and freeze trouble(Model 2WT-B,4WT-B)conditions.When used in conjunction with the 2W-MOD2 module,2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Electrical Specifications Operating Voltage Nominal: 12/24V non-polarized Minimum: 8.5 V Maximum:35V Maximum Ripple Voltage 30%peak to peak of applied voltage Standby Current 2-wire:50 pA maximum average;4-wire:50pA maximum average Maximum Alarm Current 2-wire:130 mA limited by control panel;4-wire:20 mA @12 V,23 mA @ 24 V Peak Standby Current 2-wire:100 pA;4-wire:n/a Alarm Contact Ratings 2-wire:n/a;4-wire:0.5 A @ 30 V AC/DC Physical Specifications Dimensions(including base) 5.3 inches(127 mm)diameter;2.0 inches(51 mm)height Weight 6.3 oz(178 g) Operating Temperature Range 2W-B and 4W-B:32°F to 120°F(0°C to 49°C);2WT-B and 4Wf-B:32°F to 100°F(0°C to 37.8°C) Operating Humidity Range 0 to 95%RH non-condensing Thermal Sensor 135°F(57.2°C)fixed Freeze Trouble 2Wf-B and 4WT-B only:41°F(5°C) Sensitivity 2.5%/ft nominal Input Terminals 14 to 22 AWG Mounting 31/-inch octagonal back box 4-inch octagonal back box Single-gang back box 4-inch square back box with a plaster ring Direct mount to ceiling LED Modes Power-Up Sequence for LED Indication LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal(standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information Model Thermal Wiring Alarm Current 2W-B No 2-wire 130 mA max.limited by control panel 2WT-B Yes 2-wire 130 mA max.limited by control panel 4W-B No 4-wire 20 mA @ 12 V,23 mA @ 24 V 4WT-B Yes 4-wire 20 mA @ 12 V,23 mA @ 24 V Accessories 2W-MOD2 2-wire loop test/maintenance module RT Removal/replacement tool SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket,6.6 inch(16.76 cm)diameter SYSTEMrJ2009 System Sensor 3825 Ohio Avenue•St Charles,IL 60174 Productspecifications subjectcocnan9e without nonce Vise systermensorcom for SENSOR Phone:800-SENSOR2•Fax:630-377-6495 current product information,including the latostwcsion ot this data sheet AOS-0318-007 r 6/09 r#2169 1 SYSTEM SENSOR 1 i 11. Indoor Selectable- Output Horns, _ Strobes, and• _ Horn Strobes for R r Wall Applications SpectrAlert Advance audible visible notification products SPECTIVklert are rich with features guaranteed to cut installation times ,4 o v a IIV c E and maximize profits. Features The SpectrAlert Advance series offers the most versatile and easy-to-use line of horns,strobes,and horn strobes in the industry. • Plug-in design with minimal intrusion into the back box With white and red plastic housings,wall and ceiling mounting • Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance • Automatic selection of 12-or 24-volt operation at 15 and can meet virtually any application requirement. 15/75 candela Like the entire SpectrAlert Advance product line,wall-mount horns, • Field-selectable candela settings on wall units: 15, 15/75,30,75, strobes,and horn strobes include a variety of features that increase 95, 110, 115, 135, 150, 177,and 185 their application versatility while simplifying installation.All devices • Horn rated at 88+dBA at 16 volts feature plug-in designs with minimal intrusion into the back box, • Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating Universal mounting plate for wall units costly and time-consuming ground faults. •• Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction device installation damage,SpectrAlert Advance utilizes a universal mounting plate • Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring,so installers can test wiring continuity before the device is installed. • Compatible with MDL sync module • Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with three volume selections. Agency Listings SIGNALING ® MEA ;.; 2 roved 71`5-1653186(indoor strobes) LISTED APPROVED PP 7125-1653-138(horn strobes, } 53011(c him a5.horn strobes,horns) 300.3572 MEA452-05f chane strobe;) .,551s(strobes) 7135 1653189(horns,chimes) 4 J SpectrAlert Advance Specifications Architect/Engineer Specifications General 1 SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 1 Y-inch back box,4-inch octagon back box,or double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate. Also,SpectrAlert Advance products,when used with the Sync•Circuit'"Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave • rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21B-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' Operating Voltage Range' 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6-L x 4.7"W x 1.3"D(142 mm L x 119 mm W x 33 mm D) Wall-Mount Back Box Skirt Dimensions(BBS-2,BBSW-2) 5.9"L x 5.0"W x 2.2"D(151 mm L x 128 mm W x 56 mm D) Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS,TRW- 5.7-L x 4.8"W x 0.35-D(145 mm L x 122 mm W x 9 mm D) HS) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2. P.S, PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. r AVDS00601 • •r UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) a 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 * Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69 Range 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 • 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 P, Candela 150 NA NA 246 220 Coded Low 40 46 52 50 Range 177 NA NA 281 251 185 NA NA 286 258 _ _..... .. ..... ..:........,......-..:. r,ax3.;ia..,v.•r5,:as. "�'yd+ac. yae�cywr� ...,_:.-_..:.. ............,,,- :.... •.-...;4....ua,:;iauKhalil t.auwield her lye tIriiaco) 8-17.5 Volts 16-33 Votts DC Input 15 15/75 15 30 75 95 Mg 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 97 157 182 iiii 210 Temporal Low 132 143 66lir 93 154 179 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd) 16-33 Volts 16-33 Volts DC Input 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 Horn Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non-Temporal Low 75 75 81 81 88 84 96 92 t 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 tSettings 7,8,and 9 are not available on 2-wire horn strobes. AVDS00601 SpectrAlert Advance Dimensions } 4.7" • 2.5—. r . 505"-� I4. 2.231• y •• • r 5.6" 11110 5.98" Ie==',:= :=C I 1. Wall-mount horn strobes Wall back box skirt P SpectrAlert Advance Ordering Information Model Description Model Description • Wall Horn Strobes Horns P2R*r 2-Wire Horn Strobe,Standard cd1,Red HR Horn,Red P2RH* 2-Wire Horn Strobe,High cd,Red HW Horn,White P2W* 2-Wire Horn Strobe,Standard cd,White Accessories P2WH* 2-Wire Horn Strobe,High cd,White BBS-2 Back Box Skirt,Wall,Red P4R* 4-Wire Horn Strobe,Standard cd,Red BBSW-2 Back Box Skirt,Wall,White P4RH 4-Wire Horn Strobe,High cd,Red TR-HS Trim Ring,Wall,Red P4W 4-Wire Horn Strobe,Standard cd,White TRW-HS Trim Ring,Wall White Wall Strobes SR** Strobe,Standard cd,Red SRH*t Strobe,High cd, Red SW* Strobe,Standard cd,White SWH* Strobe,High cd,White Notes: *Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2R-P. t Add"-SP"to model number for"FUEGO"marking on cover.e.g.,P2R-SP $"Standard cd"refers to strobes that include 15,15/75,30.75,95.110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings. SYSTEM ct to c System Sensor 3825 Ohio Avenue•St.Charles,I L 60174 F�a1na sp�ni�t�ns s�biec��o change without nonce Volisystemsensorcm, SENSOR Phone:800-SENSOR2•Fax:630-377-6495 forcurrentproductinformation,ioCodogthelatestverslonofthisdatasheet AVDS00801•3/12