Products
Model WS Specific Application Window Sprinklers
Horizontal and Pendent Vertical Sidewall
5.6 K-factor
General the Model WS Window Sprinklers
can be used as an open sprinkler for
Description "Outside Sprinkler Protection against
p Exposure Fire", using the design ,.
The TYCO Model WS Specific requirements of NFPA.
Application Window Sprinklers are fast As with any specific application sprinly-
response, glass bulb-type spray sprin- kler, the installation instructions �1° ,
klers available in Horizontal Sidewall included in this data sheet must be v.
and Pendent Vertical Sidewall models. precisely followed. If there are addi- y y' ;'' s, it;
tional local orjurisdictional installation y, ►
These sprinklers are the first to be `
specifically Listed to provide complete standards/codes for window sprinklers l
wetting and coverage for heat strength- on glazed window systems,this docu-
ened, tempered, or ceramic glass ment does not relieve the designer/
windows using closed sprinklers. installer from these requirements.
As part of the testing, the gas flow Consult your local jurisdiction to verify
required to achieve the time/temper- if or when these additional guidelines
ature relationship specified in ASTM must be followed.
E119 was established in a test furnace
without sprinkler protection.A window NOTICE .wi
assembly protected with the TYCO TYCO Model WS Specific Application
Model WS Window Sprinklers was Window Sprinklers described herein j ,.
then installed in the test furnace, and must be installed and maintained in
the same gas flow conditions were compliance with this document, as
maintained for a two-hour test period. well as with the applicable standards , ; ,
No cracking or visible damage to the recognized by the approval agency, in
window was permitted during the test addition to the standards of any author-
period, even when a hose stream was ities having jurisdiction.Failure to do so
directed at the window. may impair the performance of these
The success of the Model WS Window devices.
Sprinklers is based on their fast The owner is responsible for main-
response thermal sensitivity and on taining their fire protection system and
their specially designed deflectors that devices in proper operating condition.
ensure that the spray pattern wets the The installing contractor or manufac-
entire surface of the window. turer should be contacted with any
Based on successful testing, the questions.
Model WS Window Sprinklers can be
used as interior protection of windows Sprinkler
or glazing in a sprinklered building or
non-sprinklered building in accordance Identification
with Section 104 of the IBC("Alternate
Materials, Design and Methods of Number (SIN)
Construction and Equipment"). Also,
TY3388-Horizontal Sidewall
IMPORTANT TY3488-Pendent Vertical Sidewall
Always refer to Technical Data TY3388 is a re-designation for C3388
Sheet TFP700 for the "INSTALLER TY3488 is a re-designation for C3488
WARNING"that provides cautions
with respect to handling and instal-
. lation of sprinkler systems and
components.Improper handling and
installation can permanently damage
a sprinkler system or its compo-
' nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8 MAY 2014 TFP620
TFP620
Page 2 of 8
Technical Components:
Data 1 - Frame
2 - Button `'��r\���\�� *Temperature
Approvals 3 Sealing i ���— ratingis
pP Assembly w��-----Rail indicted on
UL and C-UL Listed
4 - Bulb �1Deflector.
NYC under MEA 289-04-E 5 - Compression
Screw
Approvals only apply to the service 6 - Deflector*
conditions indicated in the Design 1 2 3 4 5 6*
Criteria section.
Additional Recognition CROSS SECTION PLAN
ICC Evaluation Service(ESR-2397)
Ontario Building Code THREAD SPRINKLER INDICATED TOP
Pipe Thread Connection RELIEF FRAME ARMS OF SPRINKLER
1/2 inch NPT DEFLECTOR
Discharge Coefficient 1/2"
K=5.6 GPM/psis/2(80,6 LPM/barli2) NPT
Temperature Ratings �� 13/16"
155°F(68°C) g CENTERLINE liillionii�) � (20,6 mm)
200°F(93°C) OFSPRINKLERFinish WATERWAY 1 / DIA.
Natural Brass, Signal White(RAL9003)
(41,3mm)
Polyester,and Chrome Plated
7/16"(11,1 mm) WRENCH
Physical Characteristics NOMINAL MAKE-IN FLATS ORIENT
Frame Brass
Button Bronze/Copper DEFLECTOR
Sealing Assembly Beryllium Nickel - 2-1/8" _ , TOWARDS
w/TEFLON (54,0 mm) WINDOW
Bulb Glass
(3 mm dia.) SIDE ELEVATION
Compression Screw Brass FIGURE 1
Deflector Brass/Bronze MODEL WS WINDOW SPRINKLER
Operation HORIZONTAL SIDEWALL
The glass bulb contains a fluid that Components:
expands when exposed to heat. When
the rated temperature is reached,the 1 Frame 4 Bulb *Temperature
fluid expands sufficiently to shatter the 2 - Button 5 - Compression rating is indicated
glass bulb, allowing the sprinkler to 3 - Sealing Screw on Deflector. 1/2' 7/16"(11,1 mm)
activate and water to flow. Assembly 6 - Deflector* NPT NOMINAL MAKE-IN
1
WRENCH
FLATS
2 % ON
`1 ORIENT
3 %�� % FLOW ARROW SPRINKLER
i/4111n_ _
(INDICATED ON FRAME 2-1/8"
I DEFLECTOR) ARMS (54,0 mm)
4 TOWARDS
5 "I i WINDOW
iliTi■
11=1
INE
CENTERLINE TOP OF
OF SPRINKLER — 6* SPRINKLER 1-1/32"
WATERWAY DEFLECTOR (26,2 mm) f
5/8" f 2-1/16"
(15,9 mm) (52,4 mm)
CROSS SECTION TOWARDS WINDOW ELEVATION
FIGURE 2
MODEL WS WINDOW SPRINKLER
PENDENT VERTICAL SIDEWALL
TFP620
Page 3 of 8
Design Criteria NOTE: Refer to FireLite Plus WS Intermediate Horizontal Mullions
ceramic glass technical data sheet for Intermediate Horizontal Mullions were
The TYCO Model WS Specific other classification limitations at www. not tested with the Model WS Window
Application Window Sprinklers are UL fireglass.com. Sprinklers. Their use is outside the
and C-UL Listed and NYC Approved • Nonoperable,stronger glass window scope of the "Specific Application"
(MEA 335-01-E) for use as "Specific assemblies, not less than 1/4 in. (6 to Figure Listing for thewindow sprinklers. Refer
3B-3.
Application Window Sprinkler"and as mm)thick.
open sprinklers for"Outside"use. Deflector Location
Theses sprinklers are also recognized byType of Window Frame/Mullion Sprinkler Deflectors must be located as
These s rinklrs Laboratories ogn zed Non-combustible Frame with a stan- described below in order to ensure that
dard EPDM rubber gasket seal the entire surface of the glass window
(ULC), and the Ontario Building Code
for use in the Province of Ontario, Vertical joints of glass panes must be is covered. Sprinkler Deflectors are
Canada as providing a two-hour equiv- connected by butt-joints using a sili- positioned with respect to the window
alency for a fire separation assembly cone sealant between the individual frame, not the ceiling.
when installed in accordance with this panes or by Noncombustible Mullions. • Horizontal Sidewall:Locate within the
code. (Refer to Figures 3B-1 and 3B-2) outside edge of the window frame
Area of Use from 1/2 to 4 in. (12,7 mm to 101,6
When acceptable to the Authority Maximum Length of Window mm) away from the glass and 2 ± 1
Assembly in. (50,8 mm ± 25,4 mm) down from
Having Jurisdiction and unless modi- Unlimited '
fied by a local jurisdictional standard or the top of the exposed glass. Refer
code mentioned previously,the TYCO Maximum Height of Window to Figure 3C.
Model WS Window Sprinklers may be Assembly • Pendent Vertical Sidewall: Locate
used in either a sprinklered or unsprin- 13 ft. (3,96 m) 4 to 12 in. (101,6 mm to 304,8 mm)
klered building to protect non-operable (Refer to Figures 3C and 3D) from the face of the glass and 3 ± 1
window openings that are part of a fire in. (76,2 mm ± 25,4 mm) down from
separation provided: Maximum Distance Between the top of exposed glass. Refer to
• in an interior fire separation, the Window Sprinklers Figure 3D.
window sprinklers are installed on 8 ft. (2,44 m) Minimum Clearance from Face of
both sides of the window in the fire (Refer to Figures 3B-1 and 3B-2) Glass to Combustible Materials
separation(Figure 3A-1), For glass types other than FireLite
Minimum Distance Between Plus WS ceramic glass by TGP, all
• in jurisdictions where exterior spatial Window Sprinklers
separation (that is, separation 6 ft. (1,83 m) unless separated by a combustible materials shall be kept
2 in. (50,8 mm)from the front face of
from adjacent space) is defined as baffle or mullion of sufficient depth to
protecting an adjacent building from act as a baffle. the glass. This can be accomplished
a fire in your building,window sprin- bA mullion will act as a baffle, when wall or other method a minimum 36 in.acceptable mm)toothe
klers are installed on the interior side in the case of the Pendent Vertical authorityhavingjurisdiction.
of the building (Figure 3A-2),or
Sidewall, the mullion extends to the
• in jurisdictions where exterior spatial back of the sprinkler deflector, and in Escutcheon Assemblies
separation is defined as protecting the case of the Horizontal Sidewall,the The Model WS Window Sprinklers
your building from a fire in an adja- mullion extends to the sprinkler wrench can be used with any metallic flush or
cent building (that is, exposure flat. extended escutcheons, provided the
protection), open window sprinklers (Refer to Figures 3B-1 and 3B-2) dimensions from the sprinkler deflector
are installed on the exterior side of to the window frame and glass surface
the building (Figure 3A-3). Minimum Distance from Standard as specified in this data sheet are
System Protection Type Sprinklers maintained. These sprinklers are not
• Iterior:Wet Systems 6 ft. (1,83 m) unless separated by a listed for recessed applications.
baffle Recommended Hydraulic
• Outside Exposure: Deluge Sprinkler Location Requirements
Glass Type • Mullioned Glazing Assemblies: The authority having jurisdiction should
The following types and thicknesses of Locate window sprinklers within each be consulted to determine the hydraulic
glass are recognized for use with TYCO mullioned glazing segment. Refer to requirements for each installation.
Model WS Window Sprinklers: Figure 3B-1.
Interior Protection Sprinklered
• Non-operable, heat-strengthened, • Butt-Jointed Glazing Assemblies: Building
tempered, single-glazed (single Locate window sprinklers on Identify which compartmented area
pane), not less than 1/4 in. (6 mm) maximum 8 ft.(2,44 m)centers.Refer has the most hydraulically demanding
thick; to Figure 3B-2. window sprinklers.Calculate up to the
• Non-operable, heat-strengthened, Maximum Distance from Vertical most demanding 46.5 linear feet of
tempered, double-glazed (double Mullion Model WS Window Sprinklers on one
pane or insulated), not less than 1/4 4 ft. (1,22 m) side of the glazing.The 46.5 linear feet
in.(6 mm)thick; (14,2 linear meters) is based upon 1.2
(Refer to Figure 3B-1) x the square root of the system area
• Non-operable, UL Classified and Minimum Distance from Vertical of operation,when the system area of
labeled FireLite Plus WS ceramic Mullions operation is 1500 sq.-ft.in accordance
glass by Technical Glass Products 4 in. (101,6 mm) with NFPA 13 Light/Ordinary Hazard
(TGP), not less than 5/16 in. (8 mm) density curves.
thick; or, (Refer to Figure 3B-1)
•
TFP62O
Page 4 of 8
Where the area of Glazing is less than When acceptable to the Authority Having Jurisdiction the Model WS Specific
14.2 linear meters,all window sprinklers p Application
on one side shall be calculated. Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are in an interior fire separation,the window sprinklers
If an area reduction for quick response are installed on both sides of the window in the fire separation.
sprinklers is utilized,the linear length of
the calculated window sprinklers may
be reduced,but in no case shall be less
than 36 linear feet(1.2 x (900).
If a single fire can be expected to INSIDE
operate Model WS Window Sprinklers `
and sprinklers within the design area of
a hydraulically calculated system,the INSIDE
water demand of the window sprinklers
shall be added to the water demand
of the hydraulic calculations and shall c .
be balanced to the calculated area
demand. FIGURE 3A-1 -INTERIOR FIRE SEPARATION
If the window sprinklers are located in
an area other than the hydraulic design
area,the demand of the window sprin- When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
klers is not required to be added to Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
the demand of the remote hydraulic nonoperable window openings that are part of a fire separation provided in jurisdictions
design area. However, it is necessary where exterior spatial separation is defined as protecting an adjacent building from a fire
to prove hydraulically the simultaneous in your building,window sprinklers are installed on the interior side of the glass.
operation of the Model WS Window
Sprinklers and the ceiling sprinklers
adjacent to the window sprinklers.
OUTSIDE
Interior Protection Non-Sprinklered
Building /
Calculate all sprinklers on the most
demanding side of the glazing INSIDE
assembly within the enclosure.
EXPOSURE
Exterior Exposure Protection SIDE
Calculate all sprinklers controlled by the
deluge valve using the design require- FIGURE 3A-2-EXTERIOR FIRE SEPARATION-SPRINKLERS INSIDE
ments of NFPA.
Duration of Water Supply When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Duration
of water
opply muff w ndomst w Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
sprinklers are used to provide the nonoperable window openings that are part of a fire separation provided in jurisdictions
equivalency of a fire rating, the water where exterior spatial separation is defined as protecting your building from a fire in an
supply must be capable of supplying adjacent building,open window sprinklers are installed on the exterior side of the glass.
water for the required rating period.
Minimum Flow per Sprinkler INSIDE
20 GPM (75,7 LPM) for sprinkler
spacing of 6 to 8 ft. (1,83 to 2,44 m)
or 15 GPM (56,8 LPM) for sprinkler
spacing less than 6 ft. (1,83 m).
OUTSIDE
Maximum Pressure per Sprinkler EXPOSURE
• Horizontal Sidewall:70 psi(4,83 bar)* SIDE
*The 70 psi is onlyfor cold solder
purposes. If there issa baffle or a FIGURE 3A-3-EXTERIOR FIRE SEPARATION-SPRINKLERS OUTSIDE
mullion of sufficient depth to act as a
baffle, separating the sprinklers, the FIGURE 3A(A-1 TOA-3)
maximum pressure is 175 psi (12,07 TYPICAL NON-OPERABLE WINDOW OPENINGS
bar).
• Vertical Sidewall: 175 psi(12,07 bar)
•
TFP620
Page 5 of 8
HORIZONTAL
6'-0"(1,83 m) i OR VERTICAL 8'-0"(2,44 m)
MINIMUM* MODEL WS MAXIMUM
SPRINKLER
*Minimum distance between \ \
Window Sprinklers is 6'-0"
(1,83 m)unless separated \ MULLION----"- ---. . 4'-0"(1,22 m)MAXIMUM
by a baffle or mullion of \ 0'-4"(101,6 mm)MINIMUM
sufficient depth to act as a \
baffle. // �\ \ /
FIGURE 3B-1-MULTIPLE WINDOWS SEPARATED BY MULLIONS
•
'Ni A x A
HORIZONTAL
6'-0"(1,83 m) OR VERTICAL 8'-0"(2,44 m) _
MINIMUM MODEL WS MAXIMUM
SPRINKLER
I MULLION
Window Sprinklers are NOT
required to be located with BUTT JOINT
respect to horizontal or 4'-0"(1,22 m)MAXIMUM
vertical butt joints. 0'-4"(101,6 mm)MINIMUM
FIGURE 3B-2-MULTIPLE WINDOWS SEPARATED BY BUTT JOINTS
HORIZONTAL OR
VERTICAL MODEL /—MULLION
WS SPRINKLER
Window Sprinklers are NOT
listed to protect windows INTERMEDIATE
when intermediate horizontal MULLION
mullions are present. / �/
7
FIGURE 3B-3- WINDOWS WITH HORIZONTAL MULLIONS
FIGURE 3B(B-1 TO B-3)
• WINDOW MULLIONS AND BUTT JOINTS
TFP62O
Page 6 of 8
"TOP" BUILDING
INDICATED ON STRUCTURE
SPRINKLER DEFLECTOR
NO MAXIMUM
\\ \ DISTANCE
• WINDOW
FRAME
%PIM 2"(50,8 mm)
NO t 1"(25,4 mm)
MAXIMUM
HEIGHT 1/2"(12,7 mm)
TO 4"(101,6 mm) FOR GLASS TYPES
OTHER THAN FIRELITE
PLUS WS CERAMIC GLASS
13'-0" NON-OPERABLE \ BY TGP,ALL COMBUSTIBLE
(3,96 m) GLASS WINDOW MATERIALS SHALL BE
MAXIMUM KEPT 2'(50,8 mm)MINIMUM
EXPOSED FROM SPRINKLERED FACE
GLAZING INSTALLATION NOTE: • OF GLAZING.THIS MAY BE
HEIGHT POSITION SPRINKLER • DONE THROUGH USE OF
WITH FRAME ARMS MINIMUM 3'-0"(0,9 m)
ALIGNED VERTICALLY PONY WALL
AND MARKED SIDE OF
DEFLECTOR FACING
AND PARALLEL MODEL WS SPRINKLER
TO GLAZING SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY
FIGURE 3C
MODEL WS HORIZONTAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION
Installation Step 1.Install the pendent vertical side- Step 4.With reference to Figures 1 or
wall sprinkler only in the pendent posi- 2, apply End A of W-Type 20 Sprinkler
The TYCO Model WS Specific tion with the center-line of the sprinkler Wrench only(Figure 4)to the sprinkler
Application Window Sprinklers must parallel to the glass surface. Orient the wrench flats and tighten the sprinkler
be installed in accordance with this sprinkler so that the direction of flow into the sprinkler fitting.
section. indicated on the sprinkler deflector is
facing the window.
General Instructions Step 2. Install the horizontal side-
Do not install any bulb-type sprinkler if wall sprinkler only in the horizontal
the bulb is cracked or there is a loss position with the center-line of the
of liquid from the bulb. With the sprin- sprinkler perpendicular to the glass
kler held horizontally,a small air bubble surface.Orient the sprinkler so that the
should be present.The diameter of the word "Top" indicated on the sprinkler
air bubble is approximately 1/16 in.(1,6 deflector is facing the top of window
mm).
frame.
A leak-tight 1/2 inch NPT sprinkler Step 3. With pipe-thread sealant
joint should be obtained by applying a applied to the pipe threads, hand-
minimum-to-maximum torque of 7 to tighten the sprinkler into the sprinkler
14 ft.-lbs.(9,5 to 19,0 Nm).Higher levels fitting.
of torque may distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
TFP620
Page 7 of 8
CENTERLINE �-o BUILDING
OF SPRINKLER I STRUCTURE
WATERWAY
I
- NO MAXIMUM
\\\\\\\\ \ DISTANCE
r� �\
FLOW DIRECTION `� WINDOW
FRAME
INDICATED ON
SPRINKLER .`
DEFLECTOR 3"(76,2 mm)
NO ±1"(25,4 mm)
MAXIMUM
HEIGHT 4"(101,6 mm)
TO 12"(304,8 mm) FOR GLASS TYPES
OTHER THAN FIRELITE
PLUS WS CERAMIC GLASS
13'-0" NON-OPERABLE ' BY TGP,ALL COMBUSTIBLE
(3,96 m) GLASS WINDOW MATERIALS SHALL BE
MAXIMUM KEPT 2"(50,8 mm)MINIMUM
EXPOSEDFROM SPRINKLERED FACE
GLAZING INSTALLATION NOTE: ` OF GLAZING.THIS MAY BE
HEIGHT POSITION SPRINKLER • DONE THROUGH USE OF
WITH FRAME ARMS MINIMUM 3'-0"(0,9 m)
ALIGNED PARALLEL PONY WALL
TO GLAZING AND
DEFLECTOR FLOW
ARROW POINTED MODEL WS SPRINKLER
TOWARD GLAZING SHOWN ON ONE SIDE OF
` GLAZING FOR CLARITY
\\\\\\\\\\\\\\\ \
FIGURE 3D
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION
Care and have not operated,should be replaced Automatic sprinkler systems are recom-
if they cannot be completely cleaned mended to be inspected, tested, and
Maintenance by wiping the sprinkler with a cloth or maintained by a qualified Inspection
by brushing it with a soft bristle brush. Service in accordance with local
The TYCO Model WS Specific Care must be exercised to avoid requirements and/or national codes.
Application Window Sprinklers must damage to the sprinklers - before,
be maintained and serviced in accor- during,and after installation.Sprinklers
dance with this section. damaged by dropping,striking,wrench
Before closing a fire protection system twist/slippage, or the like, must be
main control-valve for maintenance replaced. Also, replace any sprinkler
work on the fire protection system that has a cracked bulb or that has lost
that it controls, obtain permission to liquid from its bulb. (Ref. Installation
shut down the affected fire protection Section.)
systems from the proper authorities
and notify all personnel who may be The owner is responsible for the
affected by this action. inspection,testing,and maintenance of
Sprinklers which are found to be their fire protection system and devices
leaking or exhibiting visible signs of in compliance with this document, as
corrosion must be replaced. well as with the applicable standards
recognized by the Approval agency
Automatic sprinklers must never be (e.g., NFPA 25), in addition to the stan-
painted, plated, coated, or other- dards of any authorities having jurisdic-
wise altered after leaving the factory. tion.Contact the installing contractor or
- Modified sprinklers must be replaced. sprinkler manufacturer regarding any
Sprinklers that have been exposed to questions.
corrosive products of combustion, but
1
TFP620
•
Page 8 of 8
RECESSED BUILDING
CEILING STRUCTURE
SPACE
.\\
-6\
\\\ O 111
V
G '
WINDOW
rI" FRAME
INSTALLATION NOTE: FOR GLASS TYPES
INSTALL VERTICAL AND OTHER THAN FIRELITE
HORIZONTAL MODEL PLUS WS CERAMIC GLASS
WS SPRINKLERS BY TGP,ALL COMBUSTIBLE
TYPICAL �� INTO RECESSED MATERIALS SHALL BE
KEPT 2"(50,8 mm)MINIMUM
WINDOW CEILING SPACES. FROM SPRINKLERED FACE
COVERING DO NOT PLACE BLINDS, OF GLAZING.THIS MAY BE
CURTAINS OR OTHER DONE THROUGH USE OF
WINDOW COVERINGS MINIMUM 3'-0"(0,9 m)
BETWEEN SPRINKLER PONY WALL
AND GLAZING
NONOPERABLE MODEL WS SPRINKLER
GLASS WINDOW SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY
ci
WA
FIGURE 3E
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
RECESSED CEILING TYPICAL INSTALLATION
OrderingModel WS Pendent Vertical Sidewall
L% Window Sprinkler with NPT Thread
Procedure Specify: Model WS Specific Application
WRENCH RECESS Window Sprinkler TY3488, Pendent
(USE END"A" FOR Contact your local distributor for avail- Vertical Sidewall,with(specify)temper-
..../...
MODEL WS) ability.When placing an order, indicate ature rating, (specify) finish, and P/N
the full product name and Part Number (specify)
FIGURE 4 (P/N). 155°F(68°C)
W-TYPE 20 SPRINKLER Model WS HSW Window Sprinkler Natural Brass P/N 50-304-1-155
WRENCH with NPT Thread Signal White(RAL9003)
Specify:Model WS Specific Application Polyester P/N 50-304-4-155
Limited Window Sprinkler TY3388, Horizontal Chrome Plated P/N 50-304-9-155
Sidewall, with (specify) temperature 200°F(93°C)
Warrant rating,(specify)finish,and P/N(specify) Natural Brass P/N 50-304-1-200
Y Signal White(RAL9003)
(68°C) Polyester P/N 50-304-4-200
155°F
For warranty terms and conditions, Natural Brass) P/N 50-305-1-155 Chrome Plated P/N 50-304-9-200
visit www.tyco-fire.com. Signal White(RAL9003) Sprinkler Wrench
Polyester P/N 50-305-4-155 Specify:W-Type 20 Sprinkler Wrench,
Chrome Plated P/N 50-305-9-155 P/N 56-000-1-106
200°F(93°C)
Natural Brass P/N 50-305-1-200
Signal White(RAL9003)
Polyester P/N 50-305-4-200
Chrome Plated P/N 50-305-9-200