Loading...
Specifications (11) 6G(PM(-1 - Oa)/ � 9 3 D Sw Csv-cr4'ir 1E/1 7650 S.W.Beveland St. TM RIPPEY Tigard,Oregon 97223 Phone: (503)4433900 CONSULTING ENGINEERS Fax: (5031443--3700 STRUCTURAL CALCULATIONS PROJECT: THE COMMONS—GRANT BUILDING—NEW OPENING LOCATION: TIGARD,OREGON CLIENT: OREGON BUSINESS ARCHITECTURE DATE: OCTOBER 24,2013 PROJECT NUMBER: 13364 TABLE OF CONTENTS: ITEM SHEET NUMBER GENERAL NOTES N1-N2 BUILDING PLAN SK1 STRONGBACK ELEVATION SK2 STRONGBACK DETAIL SK3 HEADER SECTION SK4 CALCULATIONS Cl-C12 444 ac72. _ 71. 9 O•a I • ,. 3 6/ 20,le\f?Z ti TURte' EXPIRf_'3: GENERAL STRUCTURAL NOTES CODE REQUIREMENTS: CONFORM TO THE 2009 INTERNATIONAL BUILDING CODE AS AMENDED BY THE 2010 OREGON STRUCTURAL SPECIALTY CODE,REFERENCED HEREAFTER AS IBC. DESIGN CRITERIA: DESIGN WAS BASED ON THE STRENGTH AND DEFLECTION CRITERIA OF THE IBC. IN ADDITION TO THE DEAD LOADS,THE FOLLOWING LOADS WERE USED FOR DESIGN,WITH LIVE LOADS REDUCED PER IBC: BASIC WIND SPEED(3-SEC GUST): 95 MPH WIND EXPOSURE:B SITE CLASS:D SDS=0.710 EXISTING CONDITIONS: THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS,DIMENSIONS AND ELEVATIONS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FROM CONDITIONS SHOWN ON THE DRAWINGS PRIOR TO THE START OF THE WORK. TEMPORARY CONDITIONS: THE CONTRACTOR SHALL BE RESPONSIBLE FOR STRUCTURAL STABILITY OF THE NEW AND EXISTING STRUCTURES AND WALLS DURING CONSTRUCTION. THE STRUCTURE SHOWN ON THE DRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER THE FINAL CONFIGURATION ONLY. SUBMITTALS: SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER PRIOR TO FABRICATION AND CONSTRUCTION REGARDING ALL STRUCTURAL ITEMS,INCLUDING THE FOLLOWING: A: STRUCTURAL STEEL IF THE SHOP DRAWINGS DIFFER FROM,OR ADD TO THE DESIGN OF THE STRUCTURAL DRAWINGS,THEY SHALL BE CLEARLY IDENTIFIED. ANY CHANGES TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER AND ARE SUBJECT TO REVIEW AND ACCEPTANCE BY THE ENGINEER. CONCRETE AND CMU ACCESSORIES: CONCRETE SCREW ANCHORS SHALL BE "HILTI KWIK HUS-EZ"OR ENGINEER APPROVED EQUIVALENT. METALS: ALL MISCELLANEOUS STEEL:ASTM A36(Fy=36,000 PSI),OR AS NOTED ASTM A572(Fy=50 KSI). CHANNELS: ASTM A572(Fy= 50,000 PSI)OR ENGINEER APPROVED EQUAL. SQUARE AND RECTANGULAR HSS:ASTM A500,GRADE "B" (Fy=46,000 PSI). WELDING:PER AWS STANDARDS. E70XX ELECTRODE AND BY CERTIFIED WELDERS. ALL STEEL TO HAVE SHOP COAT. DESIGN,FABRICATION,AND ERECTION SHALL BE IN ACCORDANCE WITH THE "AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS". WELDING SHALL CONFORM TO THE AWS CODES FOR ARC AND GAS WELDING IN BUILDING CONSTRUCTION AND SHALL BE 3/16"MINIMUM UNLESS OTHERWISE NOTED. WELDING SHALL BE BY AWS CERTIFIED WELDERS. PREQUALIFIED WELDING PROCEDURES ARE TO BE USED, UNLESS AWS QUALIFICATION IS SUBMITTED TO THE ARCHITECT/ENGINEER PRIOR TO FABRICATION. � K TM RIPPEY �2ki•fC I3wt�l l�� 11 Consulting Engineers By: (y11. Date: 7650 SW Beveland Street Chk By: Date: Suite 100 _ Tigard,Oregon 97223 Job#: � 3 6t-t Phone:(503)443-3900 Sheet: NA Of: FLASHING AND WATERPROOFING: ALL FLASHING AND WATERPROOFING SHALL BE BY OTHERS UNLESS NOTED OTHERWISE ON THE PLANS. INSPECTION: SPECIAL INSPECTIONS:IN ACCORDANCE WITH SECTION 1704 OF THE IBC AND APPLICABLE SECTIONS OF THE PROJECT SPECIFICATIONS. SPECIAL INSPECTIONS ARE TO BE PERFORMED BY AN INDEPENDENT TESTING LABORATORY EMPLOYED BY THE OWNER FOR THE AREAS INDICATED BELOW: A: WELDING B: INSTALLATION OF CONCRETE SCREW ANCHORS PER ESR-3027 THE CONTRACTOR AND SPECIAL INSPECTOR SHALL NOTIFY THE ENGINEER OF RECORD OF ANY ITEM NOT COMPLYING WITH THE PROJECT SPECIFICATIONS AND/OR APPLICABLE CODES BEFORE PROCEEDING WITH ANY WORK INVOLVING THAT ITEM. THE ENGINEER OF RECORD WILL REVIEW THE ITEM AND DETERMINE ACCEPTABILITY. IF WORK INVOLVING THAT ITEM PROCEEDS WITHOUT THE APPROVAL OF THE ENGINEER OF RECORD THEN THE WORK WILL BE CONSIDERED NON-COMPLIANT. IMKTM RII'PEY & ra'� B+n t L.at t JC Consulting Engineers By: �f Date: 7650 SW Beveland Street Chk By: Date: Suite 100 Tigard,Oregon 97223 Job#: 11021(,. Phone:(503)443-3900 Sheet: tJ/ Of: (IS) 1.ctT)F '27c.:1 b-TS (61 ger:* 24,1S-1 - rtlf..-K0k1F:31., vPi7rwsi t 1( • 7 ,1(. - A .4 • , , 5 L�3 // `E � / . ®AI t ...... id- \-- _ + b + I- + + }J l I\ ]\ G 12x 20,1 Wr - 1455 �'/zx3��x I .- C£�,'[ o{i- M bc. C ; 1 li'-0"eg . Mix C • J`-o" ill\ / i ' 1,..I " i 2/-6'11 12,_.-I" M 31 6.,a I i ! I / 31v IS� i"L_1�P1i 10,,) (=)- -1210 ._ ) (2 si;z 1/ N_/-Q" C 1M ATM RIPPEY (7V/kt-Y - 1 L'1 N)c., BY 1( DATE CONSULTING ENGINEERS {� lV ZV`) e3 6,-N\I--ft, CHK BY DATE -7650 S.W. Beveland St, Suite 100 JOB NO /53 6 II Tigard, Oregon 97223 Phone(503)443-3900 SHEET Srl- OF 1 ` Z B.5r—r't l-- e.-1---- MJL , - 1--3 x5 x 1,-1 k411 ti IA-'!45 k -all, IT-AILD Cil L-S• :&V.4-1-- rlr ^k Ft 1t-1 t 'Kw,k t-Iv s.-4a.' _c��w �5 lAi"e r r'L TYP,c.P kl,. 1rvckitor.15 SI-1vww Prtz 111L6 vs;Tto hi, (6) Tort"-t- t rL. - . -- S"Clz.oaV1 tl.- —All 1/Ai I I I d HSS 5-r9�0.).1t71 -K- 'i s.R- II 1 GI-k�aav_k. t'-s,R --i' • 41 t : I I f • I I I 1 ____---q-- ../—Ne-f,I II > I 1 fzD�rz_ c t= N1r,,J o �a —$ t I ' + /•I%' M«1, 1 I O SE'S« • .1 I 1 +1 7 ice- Y-2 >- ti fzx O'-q'12: W1 ltf (2) V Nii, I fi"0 x .'' Elnesp 1411--ii . k111 . HOS-F----t: It-_tJ +cNc tkOtzS t'1 R IC2-0h-)Zv13k-e_Az Drz-r0.4 SY'5 1"-:. 11--o " 1mTM1:\_ RIPPEY k 1 I,LCC 1 BY DATE YYCONSULTING ENGINEERS i l� V7-U1 G lori >114 e., CHK BY DATE 7650 S.W.Beveland St, Suite 100 JOB NO ( 's 3 6H, Tigard,Oregon 97223 Phone(503)443-3900 SHEET 5.... OF • ion, I QE.) e."v1/4, a a Fti-1-- 14RN 1.mx_. ? t2 l�l.,k o Zcx_'rr-i To C.c>ti1C,, t iter J L i/ - 7�r'� x 41iF�'W-i-D 141VTI `Kwir 71+v -.-E N‘44-1012,S f t p-o" �. SND C-0" F r-ik a-wt�S, 1 A+ MIN. / - 7PI • LE-) G" cDNc-. p�tir - T I0P oa., P •e 0 y ,,, TM RIPPEY (-,113,o.-11 -1n v1/4-4 \L1-6, BY I��/L- DATE CONSULTING ENGINEERS Q Ulki ✓/�PE J N C., CHK BY DATE -7650 S.W.Beveland St, Suite 100 JOB NO i�"c56711 Tigard, Oregon 97223 Phone(503) 443-3900 SHEET,4k,k OF NSW wrcLL o�rL,,al AZT l! _ 0 _ J`- Fir . I3 t -- f 7 V ��r<r�� � �nn1� G� �n�� SW- S', l2, 1-{, 1 ) vk,- 0,004,S,70k o.1 x1,0 xc ,OS k 415 MPytbelta k'b tCZ/b r '1 1 s. -f 12,E i] 1 t> I31 FT t- �' ( F a, - Ilk, t^ sN-5( \00E--1q--- P--= F��P- F ( 0,15 ) = Nil /5 Pr- 11\A p_ TM RIPPEY l/\-lz�� �Vlp� -J( BY fCS.� DATE CONSULTING ENGINEERS �1gAn 1 CD Ft CHK BY DATE -7650 S.W. Beveland St, Suite 100 JOB NO Tigard, Oregon 97223 Phone (503) 443-3900 SHEET .\ OF Fi v, yX011(0 xwV1I0 Fe =o,Zv >< t F- 2l (km--nPAK,m. t•D N w a. im t LL. co 1-71V-0 t- 1>g, c_ra o1` �Il�reac��3kt-1.� Iz�Sf�3 k Z t 1, 11 5 PI-F D Wki Qt. 2- OID VVI. SAA v 7.,I 'k 1MKTM RIPPEY BY 1'ly� DATE CONSULTING ENGINEERS CHK BY DATE -7650 S.W. Beveland St, Suite 100 JOB NO Tigard, Oregon 97223 Phone(503) 443-3900 SHEET GZ OF I '6f4,- Cr- (u.) 11.11 ILL If�r-tel L -r Pp-edit-1' WT' r PANr,..st. GJ < l'st- PG--F k ,5 'Jk ' ` - 4 fur- K i OA : -10 rt_r It. g�I T- 11�,A= v�Of4L2�1�f `rK V� - ,LQPL` hI4 ►-_ - 5 ,88 0K 9-�c•A o ` .°' 4-' r, l2 k YLv�t7 ' '- i,4,zt„� 3cc k .4 Vli .... G 1 -x 7.O AA 1,,3 . Gk Ov\-( cDi= FLK r-t-- Q-c,,_�ct 1 vi vi N\w ; °V., Pl. -tc4W zZ Z�52 _4- g, 1a= `i"( PU=x l 4 617, �� l2 2. 5'2.'-14- kl' , r o, >l iv,3 '. 1 `-1-1 JV d)V- ILAK ��r\TM RIPPEY BY r\ DATE CONSULTING ONSULTING ENGINEERS CHK BY DATE 7650 S.W.Beveland St, Suite 100 JOB NO l 3 S(....'i Tigard, Oregon 97223 Phone(503)443-3900 SHEET A n > OF I , 131- 'I p czr.ca „per- )wk`vi Psr l-I-x r'VV71,(N1,5 I SF M�� l;o PSS SAY i PSt= • J Ucgp wtcl.t. , IS ?sF rs '. le = 0 11e, O, I-1 X 55 sf- Y 132 4 75 i SF r. 1` -P A5 ,:yr:p `) '] VASS' w r C.5- va �... `(- rt—r= r Ltcrt ft-12' / 1015 TM RIPPEY BY h C-- DATE CONSULTING ENGINEERS CHK BY DATE -7650 S.W. Beveland St, Suite 100 JOB NO 3'S Tigard, Oregon 97223 [1 Phone(503) 443-3900 SHEET ` OF P= e(11, ( v� - &erg ) CPmv...v v.s GletKcc.- t n J - - , I'a _ G. q. F tki = I tl,`5 r' >e 11' = V��; til" x } c— - 1.51 pLr- (vn--c.) O ZS\ S<-ilSNSl - e wF p,S0 1I TM RIPPEY BY I\ 1�\� DATE CONSULTING ENGINEERS CHK BY DATE • 7650 S.W.Beveland St, Suite 100 JOB NO I""S""3 4.4—f Tigard, Oregon 97223 SHEET LS Phone (503)443-3900 A OF ( , �_ _ 0 L _., E EXISTING NORTH ELEVATION 122,25 ' 9.15' / ' ISL` / Lo 71...14 511"'1 ' Le>L10 - &31 b.7 4; Ho,1 5*k"/ , .),,c)2'? X iZ x �, o t,-1 , s PRO NORTH EEAIII 'IION 1 I. -g\ N3�W �rND T aeece L-o — '51.1 Z 4 12,5M' = 1 t 1-I S ` I- tf04-1 n = S-47. 'S. ' A _ 1.1V :15 kr-/ I 11,?. f 51 so, 5 ) 1�r1) ' dye, - Z .\ �6_ b,,, A bo 4 5 1r9--- S-112 s-S 1,3 LA-L-L- c..)k 1TM RIPPEY BY_,l\Yi\'Z_ DATE ]YL 1\ CONSULTING ENGINEERS CHK BY DATE 7650 S.W. Beveland St,Suite 100 JOB NO I 7Y3 L Tigard, Oregon 97223 /� Phone (503)443-3900 SHEET GE6 OF www.hilti.us Profis Anchor 2.4.3 Company: Page: 1 Specifier: Project: Address: Sub-Project I Pos. No.: Phone I Fax: I Date: 10/24/2013 E-Mail: Specifiers comments: 1 Input data ��. Anchor type and diameter: KWIK HUS-EZ(KH-EZ)1/2(3) "'w Effective embedment depth: he=2.160 in.,hnom=3.000 in. <i= Material: Carbon Steel Evaluation Service Report: ESR-3027 Issued I Valid: 8/1/2012112/1/2013 Proof: design method ACI 318/AC193 Stand-off installation: eb=0.000 in.(no stand-off);t=0.500 in. Anchor plate: lx x ly x t=4.000 in.x 9.500 in.x 0.500 in.;(Recommended plate thickness:not calculated) Profile: no profile Base material: cracked concrete,2500,fc'=2500 psi;h=5.000 in. Reinforcement: tension:condition B,shear:condition B;no supplemental splitting reinforcement present edge reinforcement:none or<No.4 bar Seismic loads(cat. C,D, E,or F) no Geometry[in.]&Loading[Ib,in.Ib] Z 4 0 ___---- 010,,.....-4, i �r�' tp,,,,* 3 k ,4,,,,,, ::.:,,,:;,5 ,.;.-:,:',••••, ..:•.,,,,.:, u ,dS . i� F Y f i °`�k k . t S w'i'n , "...,a, yesd' ss ` ' ,� , •s i*4Q � f � wRY0S4 7. . 3 = e '.. www.hilti.us Profis Anchor 2.4.3 Company: Page: 2 Specifier: Project: Address: Sub-Project I Pos. No.: Phone I Fax: I Date: 10/24/2013 E-Mail: 2 Proof I Utilization (Governing Cases) Design values[Ib] Utilization Loading Proof Load Capacity 13N/13v I%] Status Tension - _ Shear Concrete edge failure in direction x- 1440 2077 -/70 OK Loading 13N fiv Utilization RN,v[%] Status Combined tension and shear loads - - - - - 3 Warnings • Please consider all details and hints/warnings given in the detailed report! Fastening meets the design criteria! 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and security regulations in accordance with Hilti's technical directions and operating,mounting and assembly instructions,etc.,that must be strictly complied with by the user. All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you.Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to compliance with applicable norms and permits,prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular,you must arrange for the regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences,such as the recovery of lost or damaged data or programs,arising from a culpable breach of duty by you. j.-c2t—'L 5 -cc, (79..kv tTy l.Gh 13 r3 t•-rtes G8 www.hilti.us Profis Anchor 2.4.3 Company: Page: 1 Specifier: Project: Address: Sub-Project I Pos.No.: Phone I Fax: Date: 10/24/2013 E-Mail: Specifiers comments: 1 Input data Anchor type and diameter: KWIK HUS-EZ(KH-EZ)3/4(4) Effective embedment depth: hef=2.920 in.,hnom=4.000 in. Material: Carbon Steel Evaluation Service Report: ESR-3027 Issued I Valid: 8/1/2012 1 12/1/2013 Proof: design method ACI 318/AC193 Stand-off installation: eb=0.000 in.(no stand-off);t=0.282 in. Anchor plate: Ix x 1,x t=4.000 in.x 20.000 in.x 0.282 in.;(Recommended plate thickness:not calculated) Profile: no profile Base material: cracked concrete,3000,fc'=3000 psi;h=6.000 in. Reinforcement: tension:condition B,shear:condition B;no supplemental splitting reinforcement present edge reinforcement:none or<No.4 bar Seismic loads(cat. C,D,E,or F) no Geometry(in.]&Loading[Ib,in.ib] z V 11 z " .''a,.i wry 3 '< i < .2 x o u 7 . Y-X"^n'dyY r fl ii,"ka ` :, X.'" L'y. YX'" 5 a a &+2 �f �`�, ar,3y", • Lt i •/1 6- LaiLL=LIIIll www.hilti.us Profis Anchor 2.4.3 Company: Page: 2 Specifier: Project: Address: Sub-Project I Pos. No.: Phone I Fax: I Date: 10/24/2013 E-Mail: 2 Proof I Utilization (Governing Cases) Design values[Ib] Utilization Loading Proof Load Capacity RN/pv[^/o] Status Tension Concrete Breakout Strength 192 2029 10/- OK Shear Concrete edge failure in direction x+ 1680 1997 -/85 OK Loading YN �v c Utilization YN,v[%j Status Combined tension and shear loads 0.095 0.841 5/3 77 OK 3 Warnings • Please consider all details and hints/warnings given in the detailed report! Fastening meets the design criteria! 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and security regulations in accordance with Hilti's technical directions and operating,mounting and assembly instructions,etc.,that must be strictly complied with by the user. All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you. Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to compliance with applicable norms and permits,prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular,you must arrange for the regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences,such as the recovery of lost or damaged data or programs,arising from a culpable breach of duty by you. 610 I _ ii - I www.hilti.us • Profis Anchor 2.4.3 Company: Page: 1 Specifier: Project: Address: Sub-Project I Pos. No.: Phone I Fax: I Date: 10/24/2013 E-Mail: Specifier's comments: 1 Input data Anchor type and diameter: KWIK HUS-EZ(KH-EZ)1/2(3) "" > x Effective embedment depth: he{=2.160 in.,hnom=3.000 in. s Material: Carbon Steel Evaluation Service Report: ESR-3027 Issued I Valid: 8/1/2012112/1/2013 Proof: design method ACI 318/AC193 Stand-off installation: eb=0.000 in.(no stand-off);t=0.250 in. Anchor plate: IX x l,x t=4.000 in.x 9.000 in.x 0.250 in.;(Recommended plate thickness:not calculated) Profile: no profile ' Base material: cracked concrete,3000,fc'=3000 psi;h=6.000 in. Reinforcement: tension:condition B,shear:condition B;no supplemental splitting reinforcement present edge reinforcement:none or<No.4 bar Seismic loads(cat. C,D,E,or F) no Geometry[in.]&Loading[lb,in.lb] z lgt i f f f 0 6$ .------as . -'y' i K _ s�. s1 '.' @ . 5 f L� �u5�¢ '.x m� lf„e` ` �,. i + 4,. ,.+s'�f 4 F M:7:b sup" '� _F -e £he err� h''' p z5 Cx. K �` -M H 6 A •f.n.0 ,� Y� `n P q,. • �`� 'g-'�. � i� �ui.t�`i�` is X k :g� Y/ ai �i `,g�g x'13�\ ^c��.i` x�: .c _. �'SC�'`i� iL��� `�� b a.:�,'�`i 6 ,�s -¢i �a v` `tir ... .«%a k �L T i .f ., pi ' sfi -,,,,,,Atn..ill.:a.wioi,amkut,:: xr,A,,.%,,,,. ,,,,,m„,.ft,,,,frwa-..,;;_414,,p-Aipo..,,,ow,,,,,--".y 6 1 l X L_ ii ! iRi www.hilti.us Profis Anchor 2.4.3 Company: Page: 2 Specifier: Project: Address: Sub-Project I Pos.No.: Phone I Fax: I Date: 10/24/2013 E-Mail: 2 Proof I Utilization (Governing Cases) Design values[lb] Utilization Loading Proof Load Capacity YN/riv[%] Status Tension Concrete Breakout Strength 1400 3843 37/- OK Shear - _ _ Loading pN [i Utilization RN.V[%] Status Combined tension and shear loads 3 Warnings • Please consider all details and hints/warnings given in the detailed report! Fastening meets the design criteria! 4 Remarks; Your Cooperation Duties • Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles,formulas and security regulations in accordance with Hilti's technical directions and operating,mounting and assembly instructions,etc.,that must be strictly complied with by the user. All figures contained therein are average figures,and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore,you bear the sole responsibility for the absence of errors,the completeness and the relevance of the data to be put in by you. Moreover,you bear sole responsibility for having the results of the calculation checked and cleared by an expert,particularly with regard to compliance with applicable norms and permits,prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors,the correctness and the relevance of the results or suitability for a specific application. • You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular,you must arrange for the regular backup of programs and data and,if applicable,carry out the updates of the Software offered by Hilti on a regular basis.If you do not use the AutoUpdate function of the Software,you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences,such as the recovery of lost or damaged data or programs,arising from a culpable breach of duty by you.