Report 7 TRANE' Submittal /u �'cs - Ov 1 U (r `'(C36c/ &Ll Prepared For: Date:January 29, 2015 RECEIVED n e f • All Bidders R G V �/ Customer P.O. Number: Customer Project Number: FEB 2 6 2015 Sold To: Job Number: CITY OF TIGARD Job Name: BUILDING DIVISION IFly Portland OR Trane U.S. Inc. dba Trane is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 Air-Cooled Helical Rotary Water Chillers 12 Split System Air Conditioning Units (Small) 1 Split System Air Conditioning Units(Large) 2 Cabinet Unit Heaters The attached information describes the equipment we propose to ° furnish for this project,and is submitted for your approval. Ethan Kinsey Trane 1400 Valwood Parkway, Suite 100 Carrollton, TX 75006-8336 Phone: (972)406-6000 Cell: Fax: (972)243-1398 • • J:UOBS16312115461511F1y Portland OR.doc a Table Of Contents Product Summary 1 Air-Cooled Helical Rotary Water Chillers (Item Al) 3 Tag Data 3 Product Data 3 Performance Data 3 Mechanical Specifications 5 Unit Dimensions 8 Weight, Clearance&Rigging Diagram 13 Accessory 14 Field Wiring 15 Split System'Air,Conditioning Units(Small) (Items B1 -B12) 17 Tag Data 17 Product Data 17 Performance Data 20 Mechanical Specifications 22 Unit Dimensions 24 Weight, Clearance&Rigging Diagram 49 Accessory 50 Split System Air Conditioning Units(Large) (Item C1) 51 Tag Data 51 Product Data 51 Performance Data 51 Mechanical Specifications 53 Unit Dimensions 56 Weight, Clearance&Rigging Diagram 60 Accessory 62 Field Wiring 64 Cabinet Unit Heaters(Item D1) 65 Tag Data 65 Product Data 65 Performance Data 65 Mechanical Specifications 67 Unit Dimensions 69 Field Wiring 72 Field Installed Options-Part/Order Number Summary 73 Air-Cooled Helical Rotary Water Chillers 73 Split System Air Conditioning Units(Small) 73 Split System Air Conditioning Units(Large) 74 • IFly Portland OR January 29,2015 Tag Data-Air-Cooled Helical Rotary Water Chillers Qty: 1) Item Tag(s) Qty Description Model Number Al CH-1 1 Air-Cooled Series R(TM) RTAC170 Product Data -Air-Cooled Helical Rotary Water Chillers Item: Al Qty: 1 Tag(s): CH-1 Air cooled Series R(TM) model RTAC Startup Included -Trane Service must start equipment for warranty to be honored 170 nominal tons 460v/60 hz/3 ph High efficiency configuration C/UL listing ASHRAE 90.1 all versions compliant AHRI certified ASME Standard 40-60F leaving, with evaporator heaters 2 pass arrangement, 1.25" insulation Fluid type =water Low ambient capability Aluminum slit fins Condenser fans with TEAO motors Wye-delta closed transition starter Single point power connection Circuit breaker(s)- HACR rated BACnet interface Remote current limit setpoint Alarm relay 65,000 amp SCWR Factory installed flow switch-for use when evap fluid type=water 15A 115V convenience outlet(60 Hz) Refrigerant isolation valves Factory installed sound attenuator Architectural louvered panels Elastomeric isolators(Fid) 1st Year Labor Warranty Whole Unit 1st Year Refrigerant Warranty NOT INCLUDED: - Isolation/insulation - Specialties/piping - NEC 2011 requirements - Specialties/piping - Owner training/maintenance - Any other items not listed in unit detail Performance Data-Air-Cooled Helical Rotary Water Chillers Tags CH-1 Capacity (tons) 151.90 Compressor power(kW) 177.50 Unit power(kW) 195.70 Efficiency(EER) 9.3 IPLV(EER) 14.5 NPLV(EER) 13.6 Evap entering temp(F) 44.10 Evap flow rate (gpm) 875.00 Evap leaving temp (F) 40.00 Evap pressure drop (ft H2O) 36.70 Evap fouling factor(hr-sq ft-deg F/Btu) 0.00010 Evap fluid concentration (%) 0.00 FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 3 of 74 Installed by Others IFly Portland OR January 29,2015 Tags CH-1 Evap fluid freeze point(F) 32.00 Min evap flow rate(gpm) 241.00 Press drop min evap flow(ft H2O) 3.40 Max evap flow rate(gpm) 883.00 Press drop max evap flow(ft H2O) 37.30 Saturated evap temp-ckt 1 (F) 36.70 Saturated evap temp-ckt 2 (F) 37.00 Ambient air temp(F) 100.00 Saturated cond temp-ckt 1 (F) 131.50 Saturated cond temp-ckt 2 (F) 131.60 Elevation (ft) 0.00 RLA-compressor A(A) 133.00 LRA-compressor A(A) 285.00 RLA-compressor B (A) 133.00 LRA-compressor B (A) 285.00 Number of condenser fans (Each) 12.00 Number of cond fans-NFN1 -ckt 1 (Each) 6.00 Number of cond fans-NFN2-ckt 2 (Each) 6.00 RLA-condenser fan (each) (A) 2.70 Single point power MCA(A) 338.00 Single point power MOP (A) 450.00 Short circuit current rating (A) 65000.00 A-weighted sound power(dBA) 101 Refrig (HFC-134a) -ckt 1 (Ib) 215.0 Refrig (HFC-134a)-ckt 2 (Ib) 215.0 Oil charge-ckt 1 (gal) 1.30 Oil charge-ckt 2 (gal) 1.30 Shipping weight(Ib) 12171.0 Operating weight(Ib) 12585.0 Rated capacity (AHRI) (tons) 171.30 Rated efficiency(AHRI) (EER) 10.5 COP (COP) 2.73 FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 4 of 74 Installed by Others IFly Portland OR January 29,2015 Mechanical Specifications -Air-Cooled Helical Rotary Water Chillers • Item: Al Qty: 1 Tag(s): CH-1 General Units are leak and pressure tested at 390 psig (2689 kPa) high side, 250 psig (1724 kPa) low side, then evacuated and charged. All Air-cooled Series R(TM)chillers are factory tested to confirm operation prior to shipment. Packaged units ship with full operating charge of oil and refrigerant. Unit panels, structural elements and control boxes are constructed of galvanized steel and mounted on a welded structural steel base. Unit panels and control boxes are finished with a baked-on powder paint, and the structural base with an air dry paint. All paint meets the requirement for outdoor equipment of the U.S. Navy and other Federal Government Agencies and meets ASTM 8117 500 hours salt spray fog test. Anytime water only is present in the evaporator, the Trane CH530 must have flow control of the chilled water system. Flow control can be done either directly or through an input to a building automation system to conduct an action resulting in minimum flow through the chiller evaporator barrel to avoid potentially catastrophic damage to the evaporator due to freezing. If the system has sufficient glycol to protect down to the lowest expected ambient, flow control is optional. Evaporator The evaporator is a tube-in-shell heat exchanger design with internally and externally finned copper tubes roller expanded into the tube sheet. The evaporator is designed, tested and stamped in accordance with ASME Pressure Vessel Code Section VIII for a refrigerant side working pressure of 200 psig (1379 kPa). The evaporator is designed for a water side working pressure of 150 psig(1034 kPa). Water connections are grooved pipe. Each shell includes a vent, a drain and fittings for temperature control sensors and is insulated with UV resistant 1.25 inch Armaflex II or equal insulation (K=0.28). Insulation also covers the liquid and suction line and evaporator heads. Heaters, with thermostat, are provided to help protect the evaporator from freezing at ambient temperatures down to-20 F(-29 C), depending on application. • Note: A separate field supplied low voltage power source is required to power the freeze protection. Operating Temperature Unit is designed for operation in standard leaving evaporator temperature(equal to or greater than 40 F, 4 C) modes. Chilled Water Reset Provides the control logic and factory-installed sensors to reset leaving chilled water temperature. The setpoint can be reset based on ambient temperature or return evaporator water temperature. Pressure Vessel Code Chiller complies with ASME Pressure Vessel Code Section VIII.ASME nameplates are attached to applicable pressure vessels including oil separators. Condenser and Fans Air-cooled condenser coils have lanced aluminum fins mechanically bonded to internally finned copper tubes. The condenser coil has an integral subcooling circuit. Condensers are factory proof and leak tested at 506 psig (3489 kPa). Direct drive vertical discharge condenser fans are dynamically balanced. Three phase condenser fan motors with permanently lubricated ball bearing and internal thermal protection are provided. Units will start and operate down to 0 F (-18 C) ambient. Totally Enclosed Air-Over(TEAO) motors completely seal motor windings, preventing exposure to ambient conditions. TEAO fan motor insulation class F. Unit is also designed to start and operate in upper ambient conditions, up to 115 degrees F (46 C). High Efficiency/Performance Provides oversized heat exchangers for two purposes: One, it allows the unit to be more energy efficient. Two, the unit will have enhanced operation in high ambient conditions. Architectural Louvered Panels Full architecturally pleasing, 1/2"engineered composite material, cover the complete condensing coil and service area beneath the condenser, providing protection from outside objects and louvered profile for chiller. FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 5 of 74 Installed by Others 1 IFly Portland OR January 29,2015 Low Ambient Option The factory installed low ambient option consists of special control logic and variable frequency drive fans to permit low temperature start-up and operation to 0 F (-18 C). Compressor Starter-Y delta Starter is a wye-delta closed transition configuration. The wye-delta closed transition starter reduces inrush current (Locked Rotor Amps) by 66%. The starter is factory mounted and completely prewired to the compressor motor. Starters are housed in a weathertight enclosure per UL 1995. Compressor and Lube Oil System The rotary screw compressor is semi-hermetic, direct drive, 3600 rpm,with step and variable load and unloader valves for capacity control, rolling element bearings, differential refrigerant pressure oil pump and oil heater. The motor is a suction gas cooled, hermetically sealed, two pole squirrel cage induction motor. Oil separation is provided separate from the compressor. Automatically controlled valves are provided on the compressor discharge and lube oil system. A solenoid valve in the lube oil return system is also provided. Oil filtration is accomplished by an integral oil filter located within the compressor. Refrigerant Circuits Each unit has two refrigerant circuits, with one or two rotary screw compressor per circuit. Each refrigerant circuit includes compressor suction and discharge service valves, liquid line shutoff valve (except remote evap), removable core filter, liquid line sight glass, charging port and one electronic expansion valve per circuit. Fully modulating compressors and electronic expansion valves provide variable capacity modulation over the entire operating range. Unit Controls All unit controls are housed in a outdoor rated enclosure per UL 1995 with removable plates to allow for customer connection of power wiring and remote interlocks. All controls, including sensors, are factory mounted and tested prior to shipment. Microcomputer controls provide all control functions including start up and shutdown, leaving chilled water temperature control, compressor and electronic expansion valve modulation, fan sequencing, anti-recycle logic, automatic lead/lag compressor starting, load limiting and chilled water pump control. The unit control module with Rapid Restart(TM), utilizing Adaptive Control (TM) microprocessor automatically takes action to avoid unit shutdown due to abnormal operating conditions associated with low refrigerant pressure, high condensing pressure and motor current overload. Should the abnormal operating condition continue until a protective limit is violated, the unit will be shut down. A control power transformer is factory installed and wired. Controls Function Data Unit protective functions include loss of chilled water flow, evaporator freezing, loss of refrigerant, low refrigerant pressure, high refrigerant pressure, compressor starting and running over current, phase loss, phase imbalance, phase reversal, under/over voltage protection and loss of oil flow. A menu driven digital display indicates over 20 operating data points including chilled water set point, current limit set point, entering and leaving chilled water temperature, evaporator and condenser refrigerant pressures and temperatures. Over 60 diagnostic checks are made and displayed when a problem is detected. The digital display can be read and advanced on the unit without opening any control panel doors. Touch screen LCD, allows for easy access of all important chiller operating information. Short Circuit Current Rating (SCCR) A short circuit current rating offers a measure of safety for what the starter panel enclosure is able to withstand in the event of an explosion caused by a short circuit. 115V Convenience Outlet(60 Hz) Convenience outlet is provided for 115V power service at the chiller.A separate 115 volt power source is required in the control panel to power the outlet. Circuit Breaker A standard interrupting molded case circuit breaker is provided with through-the-door lockable handle to disconnect the main power and comes pre-wired from the factory with terminal block power connections. FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 6 of 74 Installed by Others IFly Portland OR January 29,2015 Power Connection Unit is provided with single-point electrical power connection. Field wiring connection point will be on the bottom right corner of the electrical panel. Control Inputs Building Automation System Communication Interface permits remote current limit set point by accepting a 4-20 mA or 2-10 Vdc analog signal. Control Outputs Relay board with four dry contacts for alarms will be provided to notify a Building Automation System of certain events or states of the chiller. Requires separate field supplied power source. BACnet BCI-C Interface BACNet Interface allows the user to easily interface with using BACNet MS/TP via a single twisted-pair wiring to a factory-installed and tested communication board. Compressor Sound Enhancement Provides a weatherproof compressor enclosure to reduce compressor sound levels. Flow Switch There is a factory installed flow switch with a velocity setpoint of 35 cm/sec included on this chiller. Unit Isolation Elastomeric isolators are provided for structure isolation from unit. Unit Isolation Seismic elastomeric isolators are provided for structure isolation from unit. Warranty A First Year Parts Warranty is included, covering the whole unit. The warranty is valid for 12 months after start-up or 18 months after shipment. FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 7 of 74 Installed by Others y 11 MOUNTING HOLE DIAMETER 11/16" WATER VOLUME STORAGE 40 GAL(151 LITERS) CD = -71 m O WATER CONNECTION DIAMETER 3 '*4 6 in (152. II .4 mm) NPS p v n c LIFTING PLATE DIMENSIONS 6" X 5 1/2" g. 3: 3 M 0? D = a c4 43- 7 4 m D c • 9) ' �`-''-.�.' w C) 0 0 0 0 0 0o '.'.' I CL -ftm.°Q. fllo 1 = eo cr co n—I 0 ° RI 4 .41 . 0 0 0 0 0 0 4410a imorn It. e lg. C) W TOP(PLAN)VIEW ISOMETRIC VIEW ? 4. CD co a e a 3 d 1i••.1 I.••■I mom! 1.■•■1 Immo! uuumi 1■...i I■...1 !INIMIE11.01 111.1711,:%\l, I�■ ■ I I o`� -„ ,!,7 co a ( co O O% NO SIDE VIEW END VIEW cn • IFly Portland OR January 29,2015 Unit Dimensions -Air-Cooled Helical Rotary Water Chillers Item: Al Qty: 1 Tag(s): CH-1 6 + fV c 2 = tiJ t\' wO N N U, - W D.CO Uj w ZU ca. Y J ty, FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 9 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions-Air-Cooled Helical Rotary Water Chillers Item: Al Qty: 1 Tag(s): CH-1 O H y0 H �11 O W �2 >EJ WO u_ LL JU wcOW 0)< cmN 0w O Z UZ LL9 P' 5 E >m LL w� Jr J > W 5 w C L J Lc a W 0 a O ci N H c N jj E .a w W LL WLL U) JE 0 >EJ LLNLL w o� Jc W W aDQ �cZ+v1 FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 10 of 74 Installed by Others XC mo 3 7.:4c-- H p a� o � 3 a o. D � a a)�a o 2 � - w Note: Add 2"(51 mm)to overall width for louvered panels and coil protection. 0 D to 7 n •• o n 1 :? Q" m = -1 M 035 i/8" n y 0 8) Q VICTAULIC WATER c OC CONNECTION(OUTLET) l 4 CD C VICTAULIC WATER CONNECTION(INLET) O 3 93 7/16" 7 M CO O' " 101/16" i to li" L „ /8" ' - - • 441/4" • 86 3/16" 88 3/16" • r f- 0) m c w CO -a N D O END VIEW o a C IFly Portland OR January 29,2015 Unit Dimensions-Air-Cooled Helical Rotary Water Chillers Item: Al Qty: 1 Tag(s): CH-1 N 4/A\ 12V Ai\ u; rew \ ` i uJ ZO_W o. 0 z ') 1 ' JZZO�O Q Oliiii , w ZCl- L ' D w v u. 0 VROm2 i-00 UOa .. _1 . .-¢ u. 0/ I\ I ` w U_ II— ILli 02 I Ar co OY / / �\ w z le/ < 0 CC Iz z 0 0 FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 12 of 74 Installed by Others LIFTING WEIGHTS TOTAL y r FOR OBSTRUCTIONS OR MULTIPLE UNITS, W1 W2 W3VV4 WEIGHT C T .-O REFER TO THE CLOSE SPACING BULLETIN. 3 .z it NO OBSTRUCTIONS ABOVE THE CONDENSER 3124.0 lb 3524.0 b 2561.0 lb 2962.0 lb 12171.0 Ib •• S O fa.Ii •- 3 WORKING CLEARANCE PER NATIONAL ELECTRIC CODE ARTICLE 110-26. 7 A d O. cb Q .1O y,. T i 48" 0 m Z 1 01 Po 000000 109" —_ -AM y —I 000000 44. 24 3 r i , -I 48" �`1�' `.�.P 41 TUBELA REMOVAL `• ,r\ 3 CLEARANCE AREA. ,�� � /\ / c (NON CONTROL PANEL 1 ,,1 l' ` a NO OBSTRUCTIONS RECOMMENDED. END) / AREA REQUIRED FOR UNIT OPERATION, Pe- 6 MAINTENANCE,ACCESS PANEL AND AIR pli �%c 0 FLOW. i 0 E. I/ CD C. "' CONTROL PANEL 3 TOP(PLAN)VIEW ISOMETRIC VIEW CD C) Cl) Ol 3 0 ff 96" 8 Iv 0 CD I IIIIIIIR C) s CG I �I�I CG II■ I,I 7 351/7, 00 .000.10. 1011 I W1 NEAR SIDE W3 NEAR SIDE W2 FAR SIDE W4 FAR SIDE c- 45" 45" 0) 3 lb 106" N CD (1 IVcD 0 N SIDE VIEW BACK VIEW C) v3, r MOUNTING LOCATIONS AND POINT LOAD WEIGHTS TOTAL 3 0 roci UNR OPERATING "" II SIZE 1 2 3 4 5 6 7 8 9 10 WEIGHTD y o Ct.11 —I 0 a O 64170 TON 1657.0 Ib 1652.0 lb 1565.0 Ib 1622.0 Ib 1515.0 Ib 1579.0 Ib 1465.0 Ib 1530.0 Ib N/A N/A 12585.0 Ib A Z a m a a O UNITai MOUNTING LOCATIONS AND ISOLATOR PART NUMBER MAX -I 0 P SIZE 1 2 3 4 5 6 7 8 9 10 LOAD y a - 0 v I 170 TON RDP4-WR RDP4-WR RDP4-WR RDP4-WR RDP4-WR RDP4-WR RDP4-WR RDP4-WR N/A N/A 2250.0 lb • 0n REDD RED RED RED RED RED RED RED n = a C1 MOUNTING LOCATION 1 IS DIMENSIONED FROM -a 01 m THE EDGE OF THE UNIT BASE(NOT THE EDGE OF THE CONTROL PANEL) O cu tD 1/4" CONTROL PANEL 15 1/16" C ' 1 2 ° pik IQ 5„ d 1 W 48" 0 R1 a--3" C 7' G '3 4° 4D- -0 C O' 76" 9%1 ) 4 5 8" Oi ' 5 6° JJ 76" 1/2"(13mm)DIA <I-2 1/2"-CI ' 7 8° n3V N/A 2 3/4" I 5 11 I-1I C. 9 10 ° m IC 3/8" m N UNIT TOP(PLAN)VIEW `z IQ . 10 is 0 1" A IFly Portland OR January 29,2015 Field Wiring -Air-Cooled Helical Rotary Water Chillers Item: Al Qty: 1 Tag(s): CH-1 d W w cwZ9yUpZ p d 3 O , rca 2,o H�¢ 5 w i u .9-R O OOoU OypOOZ 1 UPp gVLLH 41110 �— D z1 U a O W E.31"NN OM O 1 VzpKOW?K wOWO .,___:-.2._4- — fi Op gw .za8aot w ,... -o 3 32, 6-o< 3 UJ > ,IS 3 o?Whic $p LLm? 01 000000000oe0e000e13 1 , .IIIIIIIIIIMMIE r I � I. 58 fl ish Eal L'` ig Lt Ito 6gg6gg6ggggg gg glgg gggg tss :7-- 15- I!!.11.•I ..I 'ft!!! I"'-Ir C S 0 £ 1 I Ath. po°ohnvoq sail opo°3111 opo° " 6'I Px Bryryg PP = PP = � S 1--:•I I C i-4l o©oo glg kitt -li■i ! ! i i l § iP oi ko g gIg i g gg@g S g I ggp WV, € i Ili eL .� iX iY =10(12 Z ®` ® 1111111111 5 Oil Oil 1 it gig E 0 J ! W LL COM COS FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 15 of 74 Installed by Others r IFly Portland OR January 29,2015 Field Wiring -Air-Cooled Helical Rotary Water Chillers Item: Al Qty: 1 Tag(s): CH-1 FIELD WIRING PAGE 2 OF 2 CUSTOMER WIRE SELECTION TABLE SHORT CIRCUIT WITHSTAND RATING POWER WIRE SELECTION TO CIRCUIT BREAKER(1061) 65000.00 A UNIT SIZE 170 LUG WIRE SIZE RANGE(PER PHASE) UNIT VOLTAGE 460A CIRC 1&2(SNGL PT PWR) (2)2/0-500MCM GENERAL NOTES: 1. CAUTION DO NOT ENERGIZE THE UNIT UNTIL CHECK OUT AND STARTUP PROCEDURES HAVE BEEN COMPLETED. 2. ALL MOTORS ARE PROTECTED FROM PRIMARY SINGLE PHASE FAILURES. D CAUTION-TRANE PUMP CONTROL MUST BE USED TO PROVIDE PUMP CONTROL EVAPORATOR CHILLED WATER PUMP MUST BE CONTROLLED BY THE CHILLER OUTPUT.FAILURE TO COMPLY WITH THIS REOUIREMENT MAY RESULT IN DAMAGE TO THE UNIT. THE FOLLOWING FEATURES ARE OPTIONAL AND MAY OR MAY NOT BE PROVIDED.CUSTOMER PROVIDED WRING FOR ALL STANDARD FEATURES AND OPTIONS IS SHOWN ON THIS DIAGRAM.OPTIONAL FEATURES ARE SO NOTED. LOW VOLTAGE OPTIONS(CLASS 2) TRACER COMMUNICATION INTERFACE OR OTHER BUILDING AUTOMATION SYSTEM COMMUNICATION INTERFACE ICE MAKING START/STOP EXTERNAL CUR ENT LIMIT AND EXTERNAL CHILLED WATER SETPOINT 115 VOLT OPTIONS FOR 80H2 UNITS OR 220 VOLT OPTIONS FOR 50H2 UNITS. ICE MAKING STATUS UNIT OPERATING STATUS MODULE EVAPORATOR HEATER(FREEZE PROTECTION).STANDARD WITH UNIT- MOUNTED EVAPORATOR.NOT USED WITH REMOTE EVAPORATOR OPTION. UNE VOLTAGE OPTIONS UNIT MOUNTED TERMINAL BLOCK.DISCONNECT SWITCH OR HACR CIRCUIT BREAKER(TB.SW OR CB) WRING REQUIREMENTS 6. RECOMMENDED FIELD WRING CONNECTIONS ARE SHOWN BY DOTTED LINES 7 ALL FIELD WRING MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE ANS STATE AND LOCAL REQUIREMENTS.EXPORT UNIT WRING MUST COMPLY WITH LOCAL APPLICABLE CODES. DPOWER FOR THE EVAPORATOR HEATER AND/OR OPTIONAL CONVENIENCE OUTLET IS SUPPUED BYA COMMON CUSTOMER PROVIDED POWER SUPPLY.WHEN POWERED.THE MEAT TAPE WILL USE 1640 VA OF THE TOTAL AVAILABLE SUPPLY ON 80 HZ UNITS AND APPROXIMATELY 1380 VA ON 50 HZ UNITS.EVAPORATOR HEATERS ARE NOT PROVIDED WITH REMOTE EVAPORATOR UNITS. 10 ALL CUSTOMER CONTROL CIRCUIT WRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM INSULATION RATING OF 300 VOLTS. EXCEPT AS NOTED ALL CUSTOMER WRING CONNECTIONS ARE MADE TO CIRCUIT BOARD MOUNTED BOX LUGS WITH A WIRE RANGE OF 14 TO 18 AWG.THE HEAT TAPE AND/OR CONVENIENCE OUTLET AND THE GROUND SIDE OF THE FLOW SWITCH GO TO TERMINAL STRIPS WITH A I10 SET SCREW WHICH WILL ACCEPT RING OR FORK TERMINALS OR STRIPPED WIRE LEADS. DO NOT RUN LOW VOLTAGE CONTROL WIRING(30 VOLTS OR LESS)IN CONDUIT WITH 110 VOLT OR HIGHER WRING.DO NOT EXCEED THE 11 FOLLOWING MAXIMUM RUN LENGTHS FOR A GIVEN SIZE:14 AWG.5000 FT;16 AWG.2000 FT;18 AWG,1000 FT. SHIELDED TWISTED PAIR LEADS ARE REQUIRED FOR CONNECTIONS TO THE COMMUNICATIONS INTERFACE MODULE(1U8).THE SHIELD 12 SHOULD BE GROUNDED AT THE CHILLER CONTROL PANEL END. D. THE CONTACTS FOR THESE FEATURES ARE JUMPERED AT THE FACTORY BY JUMPERS W1 8 W2 TO ENABLE UNIT OPERATION.IF REMOTE CONTROL IS DESIRED REMOVE THE JUMPERS AND CONNECT TO THE DESIRED CONTROL CIRCUIT. 11 AS SHIPPED THE NORMAL 400 VOLT UNIT CONTROL POWER TRANSFORMERS ARE WIRED ON THE 100 VOLT TAP(H3).TRANSFORMER LEADS 128A&128B SHOULD BE RECONNECTED TO THE APPROPRIATE TAP FOR THE 380(H2)OR 415(HI)VOLT POWER SUPPLIES. FE's, GROUND ALL CUSTOMER PROVIDED 115 VOLT POWER SUPPLIES AS REQUIRED BY CODES.GREEN GROUND SCREWS ARE PROVIDED IN THE UNIT CONTROL PANEL CONTACT RATINGS AND REQUIREMENTS: D. UNIT PROVIDED DRY CONTACTS FOR THE EVAPORATOR PUMP CONTROL THE UNIT OPERATING STATUS RELAYS&THE ICE MAKING STATUS RELAY (1U10.1U12.8 1U13)ARE RATED FOR 72 AMPS RESISTIVE,2.88 AMPS PILOT DUTY.OR 1(3 HP,7.2 FLA AT 120 VOLTS 80 HZ.CONTACTS ARE RATED FOR 5 AMPS GENERAL PURPOSE DUTY AT 240 VOLTS.THE MAX FUSE SIZE FOR ANY OF THESE CIRCUITS IS 15 AMPS. D. CUSTOMER SUPPUED CONTACTS FOR ALL LOW VOLTAGE CONNECTIONS MUST BE COMPATABLE WITH DRY CIRCUIT 24 VOLTS DC FOR A 12 MA RESISTIVE LOAD.SILVER OR GOLD PLATED CONTACTS ARE RECOMMENDED. ® FLOW SWITCH AND INTERLOCK CONTACTS MUST BE ACCEPTABLE FOR USE IN A 24 VOLT 12,M CIRCUIT.REMOVE JUMPER BETWEEN 1TB65 AND 17863 WHEN SKI AUX CONTACT IS USED. 21 THE FIELD PROVIDED INDICATORS MAY BE RELAYS(AS SHOWN).LIGHTS OR AUDIBLE DEVICES.FOUR DUPUCATE FUNCTIONS ARE SHOWN. THE DUPLICATE FUNCTIONS MAY BE CONNECTED TO EITHER OR BOTH OF THE NORMALLY OPEN OR NORMALLY CLOSED RELAY CONTACTS OF EACH OF THE 4 SPDT RELAYS ON THE OPTIONAL UNIT OPERATING STATUS MODULE. ® OPTIONAL COMPONENT-CHECK MODEL NUMBER TO DETERMINE IF USED OR NOT. D. THE FUNCTIONS OF THE OPERATING STATUS MODULE RELAYS ARE PROGRAMABLE.DEFAULT FUNCTIONS ARE SHOWN.SEE 1091 FOR DETAILS. • FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 16 of 74 Installed by Others IFly Portland OR January 29,2015 Tag Data -Split System Air Conditioning Units (Small) (Qty: 12) Item Tag(s) Qty Description Model Number B1 AHU/CU1-1 1 5 Ton Unitary Split Systems 4TTA3060D3000-TAM4A0000S-1S-0----000-0--0 B2 AHU/CU1-2 1 2 Ton Unitary Split Systems 4TTR3024G1000-TAM4A0A04S-1S-0----000-0--0 B3 AHU/CU1-3 1 5 Ton Unitary Split Systems 4TTA3060D3000-TAM4A0C60S-1S-0----000-0-0 B4 AHU/CU1-4 1 5 Ton Unitary Split Systems 4TTA3060D3000-TAM4A0000S-1S-0----000-0--0 • B5 AHU/CU-2-1 1 2 Ton Unitary Split Systems 4TTR3024G1000-TAM4A0000S-1S-0--000-0--0 B6 AHU/CU2-2 1 3 Ton Unitary Split Systems 4TTR3036E1000-TAM4A0A36S-1S-0---000-0-0 B7 AHU/CU2-3 1 3 Ton Unitary Split Systems 4TTR3036E1000-TAM4A0000S-1S-0----000-0--0 B8 AHU/CU2-4 1 2.5 Ton Unitary Split Systems 4TTR3030G1000-TAM4A0A30S-1S-0-000-0-0 B9 AHU/CU2-5 1 2.5 Ton Unitary Split Systems 4TTR3030G1000-TAM4A0000S-1S-0----000-0--0 B10 AHU/CU3-1 1 3.5 Ton Unitary Split Systems 4TTA3042D3000-TAM4A0B02S-1S-0----000-0--0 B11 AHU/CU3-2 1 2 Ton Unitary Split Systems 4TTR3024G1000-TAM4A0A04S-1S-0-000-0-0 B12 AHU/CU3-3 1 4 Ton Unitary Split Systems 4TTA3048D3000-TAM4A0000S-1S-0---000-0--0 Product Data -Split System Air Conditioning Units (Small) Item: B1, B3, B4 Qty: 3 Tag(s): AHU/CU1-1, AHU/CU1-3,AHU/CU1-4 Split System Cooling Outdoor Unit 5 Ton Nominal Cooling Capacity 200-230 Volt 3 Phase 60 Hertz Trane Multi-poise 4-way Better, Retail replacement Mid EFF Major designs sequence • 23.5"wide x 21.5"deep 5 Ton air handler Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(FId) Vibration Isolators (FId) Evaporator defrost control (Fld) Head pressure control (Fld) Crankcase heater kit(Fld) Item: B2, B5 Qty: 2 Tag(s): AHU/CU1-2, AHU/CU-2-1 Split System Cooling Outdoor Unit 2 Ton Nominal Cooling Capacity 200-230 Volt 1 Phase 60 Hertz Trane Multi-poise 4-way Better, Retail replacement Mid EFF Major designs sequence 17.5"wide x 21.5" deep 2 Ton air handler Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(FId) Vibration Isolators (Fld) Evaporator defrost control (Fld) Head pressure control (FId) Crankcase heater kit(FId) 5.77/7.68 kW Electric Htr w/Ckt Brk for 208/240V 1 Phase 60 Hz (Fld) Item: B6, B7 Qty: 2 Tag(s): AHU/CU2-2,AHU/CU2-3 Split System Cooling Outdoor Unit 3 Ton Nominal Cooling Capacity 200-230 Volt 1 Phase 60 Hertz Trane Multi-poise 4-way FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 17 of 74 Installed by Others IFly Portland OR January 29,2015 Better, Retail replacement Mid EFF Major designs sequence 17.5"wide x 21.5"deep 3 Ton air handler • Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(FId) Vibration Isolators (FId) Evaporator defrost control (FId) Head pressure control (FId) Crankcase heater kit(FId) 5.77/7.68 kW Electric Htr w/Ckt Brk for 208/240V 1 Phase 60 Hz (FId) Item: B8 Qty: 1 Tag(s): AHU/CU2-4 Split System Cooling Outdoor Unit 2.5 Ton Nominal Cooling Capacity 200-230 Volt 1 Phase 60 Hertz Trane Multi-poise 4-way Better, Retail replacement Mid EFF Major designs sequence 17.5"wide x 21.5" deep 2.5 Ton air handler Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(Fid) Vibration Isolators (Fid) Evaporator defrost control (FId) Head pressure control (FId) Crankcase heater kit(FId) 5.77/7.68 kW Electric Htr w/Ckt Brk for 208/240V 1 Phase 60 Hz (Fld) Item: B9 Qty: 1 Tag(s): AHU/CU2-5 Split System Cooling Outdoor Unit 2.5 Ton Nominal Cooling Capacity 200-230 Volt 1 Phase 60 Hertz Trane Multi-poise 4-way Better, Retail replacement Mid EFF Major designs sequence 17.5"wide x 21.5" deep 2.5 Ton air handler Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(FId) Vibration Isolators (Fld) Evaporator defrost control (FId) Head pressure control (FId) Crankcase heater kit(Fid) 7.21/9.60 kW Electric Htr w/Ckt Brk for 208/240V 1 Phase 60 Hz (Fld) Item: B10 Qty: 1 Tag(s): AHU/CU3-1 Split System Cooling Outdoor Unit 3.5 Ton Nominal Cooling Capacity 200-230 Volt 3 Phase 60 Hertz Trane Multi-poise 4-way Better, Retail replacement Mid EFF Major designs sequence 21.0"wide x 21.5" deep FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 18 of 74 Installed by Others IFly Portland OR January 29,2015 3.5 Ton air handler Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(FId) Vibration Isolators (FId) Evaporator defrost control (FId) Head pressure control (FId) Crankcase heater kit(FId) Item: B11 Qty: 1 Tag(s): AHU/CU3-2 Split System Cooling Outdoor Unit 2 Ton Nominal Cooling Capacity 200-230 Volt 1 Phase 60 Hertz Trane Multi-poise 4-way Better, Retail replacement Mid EFF Major designs sequence 17.5"wide x 21.5" deep 2 Ton air handler Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(FId) Vibration Isolators (FId) Evaporator defrost control (FId) Head pressure control (FId) Crankcase heater kit(FId) 7.21/9.60 kW Electric Htr w/Ckt Brk for 208/240V 1 Phase 60 Hz (FId) Item: B12 Qty: 1 Tag(s): AHU/CU3-3 Split System Cooling Outdoor Unit 4 Ton Nominal Cooling Capacity 200-230 Volt 3 Phase 60 Hertz Trane Multi-poise 4-way Better, Retail replacement Mid EFF Major designs sequence 23.5"wide x 21.5" deep 4 Ton air handler Low EFF PSC Power Supply System Control Type Programmable 7 day , 3 heat/2 cool thermostat(FId) Vibration Isolators (Fld) Evaporator defrost control (FId) Head pressure control (FId) Crankcase heater kit(FId) 10.80/14.40 kW Htr w/Ckt Brk 208/240/1 (Fld) NOT INCLUDED: - Any controls wiring not listed - Wiring - Vibration isolation for indoor air handlers • - Condensate pumps - Auxiliary drainpan float switch - Outside air dampers/actuators and any associated wiring - Insulation - Disconnects/circuit breakers - Fan interlocks - Additional filters/belts/sheaves FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 19 of 74 Installed by Others IFly Portland OR January 29,2015 - Refrigerant specialties/piping/line sets - Smoke detectors, remote test stations, annunciator panels - Owner training/maintenance - Extended warranties not specifically listed above - Startup - NEC 2011 requirements - Any other items not listed in unit detail . Performance Data-Split System Air Conditioning Units (Small) Tags AHU/CU1 AHU/CU1 AHU/CU1 AHU/CU- AHU/CU2 AHU/CU2 -1 -2 -3, 2-1 -2 -3 AHU/CU1 -4 Design clg outdoor DB (F) 105.00 105.00 105.00 105.00 105.00 105.00 Cooling EDB (F) 78.00 72.00 80.00 75.70 78.00 73.40 Cooling EWB (F) 65.00 60.20 67.00 65.00 65.00 63.80 Rated gross capacity(AHRI) (Btuh) 58500.00 24000.00 58500.00 24000.00 34000.00 34000.00 Clg net total capacity (Btuh) 56600.00 20070.00 58500.00 21400.00 31650.00 31020.00 Clg net sensible capacity(Btuh) 43850.00 16109.00 43600.00 14974.00 24800.00 21050.00 Clg net latent capacity (Btuh) 12750.00 3960.00 14900.00 6425.00 6850.00 9969.00 Calc clg LDB (F) 57.50 53.30 59.50 58.20 58.60 57.10 Calc clg LWB (F) 55.40 51.00 57.50 56.00 56.10 55.00 SEER @ AHRI (btuh/watt) 13.50 13.50 13.50 13.50 13.25 13.25 EER @ AHRI (EER) 11.5 11.5 11.5 11.5 11.0 11.0 Cooling airflow(cfm) 2000 800 2000 800 1200 1200 Min system airflow clg (cfm) 1550 700 1550 700 1050 1050 Max system airflow clg (cfm) 2450 900 2450 900 1350 1350 AHRI airflow(cfm) 1550 775 1550 775 1100 1100 AHRI reference number( ) 4669520 5593772 4669520 5593772 5347727 5347727 Compressor power @(specific Ambient) (W) 4483.0 1725.0 4483.0 1725.0 2573.0 2573.0 Condenser fan power @ (specific SP) (W) 214.0 128.0 214.0 128.0 129.0 129.0 Supply fan power @ (specified SP) (W) 390.0 234.0 390.0 234.0 389.0 389.0 ASHRAE 90.1 S6.4.1 compliant Yes Yes Yes Yes Yes Yes Blower capability 5.0 ton 2.0 ton to 5.0 ton 2.0 ton to 3.0 ton to 3.0 ton to airflow 2.5 ton airflow 2.5 ton 3.5 ton 3.5 ton airflow airflow airflow airflow 80 to 90 second blower off delay Required Required Required Required Required Required OD AHRI Model (Each) -1.00 -1.00 -1.00 -1.00 -1.00 -1.00 Tags AHU/CU2-4 AHU/CU2-5 AHU/CU3-1 AHU/CU3-2 AHU/CU3-3 Design clg outdoor DB (F) 105.00 105.00 105.00 105.00 105.00 Cooling EDB (F) 78.00 78.00 78.00 72.00 78.00 Cooling EWB (F) 65.00 65.00 65.00 61.50 65.00 Rated gross capacity(AHRI) (Btuh) 33400.00 29200.00 42000.00 24000.00 47500.00 Clg net total capacity(Btuh) 31195.00 27200.00 38949.00 20036.00 43650.00 Clg net sensible capacity(Btuh) 22244.00 21250.00 29280.00 14195.00 33550.00 Clg net latent capacity(Btuh) 8950.00 5950.00 9669.00 5841.00 10100.00 Calc clg LDB (F) 57.20 58.10 56.90 53.70 58.40 Calc clg LWB (F) 54.30 55.80 54.80 51.50 55.80 SEER @ AHRI (btuh/watt) 13.50 13.00 13.50 13.50 13.00 EER @ AHRI (EER) 11.0 11.0 11.5 11.5 11.0 Cooling airflow(cfm) 1000 1000 1300 720 1600 Min system airflow clg (cfm) 975 875 1225 700 1400 Max system airflow clg (cfm) 1425 1125 1575 900 1800 AHRI airflow(cfm) 975 950 1300 775 1550 FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 20 of 74 Installed by Others IFly Portland OR January 29,2015 _ Tags AHU/CU2-4 AHU/CU2-5 AHU/CU3-1 AHU/CU3-2 AHU/CU3-3 AHRI reference number( ) 5728975 5724169 4669516 5593772 4669519 Compressor power @ (specific Ambient) (W) 2587.0 2237.0 3021.0 1725.0 3443.0 Condenser fan power @ (specific SP) (W) 150.0 124.0 221.0 128.0 228.0 Supply fan power @ (specified SP) (W) 299.0 294.0 410.0 234.0 647.0 ASHRAE 90.1 S6.4.1 compliant Yes Yes Yes Yes Yes • Blower capability 2.0 ton to 2.5 2.0 ton to 2.5 3.0 ton to 3.5 2.0 ton to 2.5 3.5 ton to 4.0 ton airflow ton airflow ton airflow ton airflow ton airflow 80 to 90 second blower off delay Required Required Required Required Required OD AHRI Model (Each) -1.00 -1.00 -1.00 -1.00 -1.00 Electric heat capacity @ 208 Volts(Btuh) - - - - 36900.00 Electric heat capacity @ 240 Volts (Btuh) - - - - 49200.00 FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 21 of 74 Installed by Others IFly Portland OR January 29,2015 Mechanical Specifications -Split System Air Conditioning Units (Small) Item: B1 -B12 Qty: 12 Tag(s): AHU/CU1-1, AHU/CU1-2,AHU/CU1-3,AHU/CU1-4,AHU/CU-2-1, AHU/CU2-2, AHU/CU2-3,AHU/CU2-4, AHU/CU2-5, AHU/CU3-1,AHU/CU3-2, AHU/CU3-3 4TTA3 -General This unit is fully charged from the factory for matched indoor section and up to 180"of piping. Unit is designed to operate at outdoor ambient temperatures as high as 115.0 F]. Cooling capacities matched with a wide selection of air handlers and furnace coils that are A.R.I certified. The unit shall be UL listed. Exterior must be designed for outdoor application. 4TTA3-Casing Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Corrosion and weatherproof CMBP-G30 Duratuff base. 4TTA3-Compressor The Climatuff compressor features internal over temperature and pressure protector, total dipped hermetic motor. Other features include: centrifugal oil pump, and low vibration and noise. 4TTA3-Condenser Coil The Spine Fin coil is continuously wrapped, corrosion resistant, all aluminum with minimum brazed joints. The coil is 3/8" O.D. seamless aluminum glued to a continuous aluminum fin. Coils are lab tested to withstand 2000.0 lb of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. 4TTA3 -Refrigerant controls Refrigeration system controls include condenser fan and compressor contactor. High and low pressure protection is inherent to the compressor. Another standard feature is the factory installed liquid line drier. General -4TTR3 The 4TTR3 shall be fully charged from the factory for matched indoor section and up to 15 feet of piping. This unit must be designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities shall be matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior must be designed for outdoor application. Casing -4TTR3 Unit casing is constructed of heavy gauge, galvanized steel and painted with a weather-resistant powder paint. Corrosion and weatherproof CMBP-G30 DuraTuff base. Compressor-4TTR3 The Climatuff compressor features internal over temperature and pressure protector, total dipped hermetic motor and thermostatically controlled sump heater. Other features include centrifugal oil pump, and low vibration and noise. Condenser Coil -4TTR3 The Spine Fin coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. This coil is 3/8"O.D. seamless aluminum glued to a continuous aluminum fin. Coils are lab tested to withstand 2,000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Low Ambient Cooling -4TTR3 As manufactured, this unit has a cooling capability to 55°F. The addition of an evaporator defrost control permits operation to 30°F. The addition of a low ambient kit with TXV permits low ambient cooling to 0°F. Refrigerant Controls -4TTR3 Refrigeration system controls include condenser fan and compressor contactor. High and low pressure controls are inherent to the compressor.Another standard feature is the liquid line dryer. TAM4 Air-Tite IITM Cabinet Double Wall Foamed and Formed Cabinet System Water Proof Cabinet Design R-4.2 Insulating Value Composite Foamed Cabinet Doors Sweat Eliminating Cabinet Design FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 22 of 74 Installed by Others IFly Portland OR January 29,2015 Loose Fiber Eliminating Cabinet Design Smooth Cleanable Cabinet Design 2% or Less air leakage Precision Durable Door Seals Quarter Turn Phillips Head Door Fasteners 5/16"Allen Wrench "Quick Latch" Modular Cabinet Multi-Position UP/Down Flow Horizontal Left/Right Side Return Option Braze in Refrigerant Connection Primary/Secondary Condensate Connections Conduit Connection with Easy Removal Plugs Alert Port to view Codes without door removal Vortica Blower with Integrated Slide Deck for Easy Removal Polarized Plug connections on Blower Control Protection Pocket Aluminum Coil with Integrated Slide Deck for Easy Removal Polarized Plug connections on Coil EEV Slide in Electric Heaters Polarized Plug connections for Electric Heater Labeled Panels and connections 1 1/4"to 1"and 1 3/4"to 1/2" Conduit connection on Left, Right and Top Molded in 1"Standard Filter rail Electronic Expansion Valve (EEV)With Low Dual Refrigerant Compatible as Shipped Low Voltage Terminal Connection Point 8 Alert Codes Enhanced Coil Fin Patented Blow Through Design PSC 3 Speed Motor Maximum Width of 24 1/2" Compact 20 13/16"depth with doors removed Integrated Horizontal Drain pans Single Color Fused 24V Power Safety Door Switch 1 Year Warranty 10 Year Warranty Registered Warranty Mirrors Outdoor Optional extended warranty available Heater Section -1 Phase Vertical Air Handler A compartment is provided in the blower section for field installation of supplementary heater. Polarized plugs are provided for making electrical connections to the air handler control box from the supplementary heater. Vibration Isolators Neoprene-in-shear vibration isolators will be included to reduce transmission of noise and vibration to building structures, equipment and adjacent space. Head Pressure Control Accessory The Head Pressure Control (BAYLOAM***)accessory is a low voltage(24 Volts)electronic head pressure control that cycles the condenser fan motor based on liquid temperature. The addition of this field installed Head Pressure Control accessory permits cooling operation to 0 deg F [-17.8 deg C] providing that non-bleed TXV's, quick start components, and compressor crankcase heat are provided with the system when required. Head Pressure Control Controls fan motor(on/off) in response to outdoor ambient temperature in conjunction with liquid line temperature. Accessory provides unit cooling operation to outdoor temperatures of OF FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 23 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions-Split System Air Conditioning Units(Small) _ Item: B1, B3, B4 Qty: 3 Tag(s): AHU/CU1-1,AHU/CU1-3, AHU/CU1-4 NOTES: 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH 21 13/16" - INSTALLER DOCUMENTS BEFORE INSTALLATION 1 12" - 143/8" - - 515/16" rt 1/2" V4 oT 1 231/2" 201/2" LH11 .M.1 '• 1 1/2" LIQUID LINE 3/8" GAS LINE 7/8 -a 10 5/16" • 3" r • O. ❑ � ,Jdrl . ® . 61 11/16" Ill e 511/2' •� 112' L . . 1 21 13/16" 27" 1 1/2" - 17 1/8" - - 3 1/8" F1 1/2" I 20 1/2" 1 0 1 12"J4 AIRHANDLER-TAM4AOA60 DRAWING FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 24 of 74 Installed by Others • IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B1, B3, B4 Qty: 3 Tag(s): AHU/CU1-1, AHU/CU1-3, AHU/CU1-4 'ELECTRICAL/GENERAL DATA • 'GENERAL I1x2x4t INDOOR MOTOR Itl FILTERS (3) Model: TAM4AOC60S51SA Number: '1 Type: Throwaway Horsepower: 1.0 Furnished: No Unit Primary Voltage: 208 Motor Speed(RPM): 1050 Number: 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 22'k20'k1" Unit Hertz 60 Full Load Amps: 7.6 Unit Phase: 1 Locked Rotor Amps: - STANDARD (5) REFRIGERANT Weights 230 Vok/208 Volt Type: R-410A Shipping: 171.0 lb REF.Line Connections Net: 159.0 lb Minimum Circuit Ampacity: '10.0/10.0 Coupling or Conn.Size-Gas: 7/8"Overload Protection: 15.0/15.0 „ Coupling or Conn.Size-Liq.: ELECTRIC HEAT 240 Volt/208 VoltNOTES: Capacity Circuit#1: N/A 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (ori standard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: N/A 3.Minimum filter size for horizontal applications will be based on airflow selection Phase: N/A and will be calculated as follows: low velocity filter face area(sq.ft.)=cfm/300 Heater Amps Per Circuit Circuit#1: N/A high velocity filter.face area(sq.ft.)=cfm/500 Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of filter maintenance,it a recommended that a properly sized,remote filter and grille be Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used Minimum Circuit Ampacity Circuit#1: N/A 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#2: N/A Minimum Circuit Ampacity Circuit#3: N/A Maximum Overload Protection Circuit#1: N/A Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLO=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 25 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B1, B3, B4 Qty: 3 Tag(s): AHU/CU1-1, AHU/CU1-3,AHU/CU1-4 - 371/4" NOTES 1.TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT.UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, 40,10"'"---7,,,,- I �`t N AND SHOULD BE AT LEAST 12"FROM WALL AND ALL ALL SURROUNDING SHRUBBERY ON TWO SIDES. 7 / OTHER TWO SIDES UNRESTRICTED. 2.ELECTRICAL AND REFRIGERANT COMPONENT � I CLEARANCES PER PREVAILING CODES. SERVICE PANEL - ;` _ ( I SEE NOTE 2 '- .`� 341/4" �. I III 1li• 1„ j- Ij - - - - - - ELECTRICAL , SERVICE PANEL ii• II 7/8"DIA.HOLE 20r� LOW VOLTAGE '�.- v• 37 1/4" UOUID UNE SERVICE VALVE, 1 1/8"DIA.K.O.WITH ' "E"I.D.FEMALE BRAZE CONNECTION WITH 1/4"SAE 7/8"DIA.HOLE IN CONTROL 1" 1 FLARE PRESSURE TAP FITTING. BOX BOTTOM FOR ELECTRICAL POWER SUPPLY N '''l 8 5/8" �i 8`5/8" �, ill 6" 1111. 1 LIQUID UNE SERVICE VALVE, 111- _ I 3/8"I.D.FEMALE BRAZE 33/9" •S UNE 1/4"TURN BALL 33/6' CONNECTION WITH 1/4"SAE SERVICE VALVE,7/8"I.D.FEMALE 3 7/8" FLARE PRESSURE TAP FITTING. 3 7/8" - - BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. GAS UNE SERVICE VALVE, "D"I.D.FEMALE BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. • FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 26 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B1, B3, B4 Qty: 3 Tag(s): AHU/CU1-1, AHU/CU1-3,AHU/CU1-4 'ELECTRICAL/GENERAL DATA 'GENERAL POWER CONN. COMPRESSOR Model: 4TTA3060* Minimum Circuit Ampacity '21.0 Number '1 Operating Voltage: 187-253 Maximum Circuit Breaker: 35.0 Phase: 3 Unit Primary Voltage: 208 Minimum Protection Rating: 35.0 Rated Load Amps: 15.6 Unit Secondary Voltage 230 Locked Rotor Amps: 110.0 Unit Hertz: 60 Unit Phase: 3 OUTDOOR MOTOR NOTES: Number: 1 1.Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on Horsepower: 0.20 AHRI Standard 210/240. Motor Speed(RPM): 825 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. Phase: 33.Standard line lengths-60'.Standard lift-60'Suction and Liquid line. Full Load Amps: 0'93 For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 Locked Rotor Amps: 4.'=15,20,25,30,40 and 50 foot lineset available. REFRIGERANT Type: R-410 Charge: 8.0 Ib Line Size O.D.Gas: 7/83/8" Line Size O.D.LIQ: Cl WEIGHT L NET '226.0 lb SHIPPING '261.0 lb W C7 NOTES: Cl.TOP DISCHARGE SHOULD BE UNRESTRICTED = FOR AT LEAST 60"ABOVE UNIT U C2.PLACE UNIT FROM WALL C3.PLACE SHRUBBERY AT LEAST 12" C4 FROM UNIT ON TWO SIDES,OTHER SIDES UNRESTRICTED C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT ',11111M' `•••.,,.>- --,////111\\\,.. iamsmaell �C2 C3 WEIGHT AND CLEARANCE FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 27 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Small) Item: B2, B5, B8, B9, B11 Qty: 5 Tag(s): AHU/CU1-2,AHU/CU-2-1,AHU/CU2-4, AHU/CU2-5,AHU/CU3-2 - NOTES: 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 21 3/4" 1 12" - 143/8" - 5 15/16" r 12" i 17 12" 141/2" • ...1_3_ Iissm.s4.4 ' 1 1n" LIQUID LINE 3/8" GAS LINE 3/4" 7 5/16 3" N—Nsk O� ,ND F 49 7/8" I LO JV,r1 11/2"I o o 39 5/8" Ii _....: 21 13/16" 1 12" - 17 1/8" - - 3 1/8" r1 12" i 14 12" AIRHANDLER-TAM4A0A18/24/30 DRAWING 112"J4 FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 28 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B2, B5 Qty: 2 Tag(s): AHU/CUI-2,AHU/CU-2-1 'ELECTRICAL/GENERAL DATA 'GENERAL tIx2x41 INDOOR MOTOR tt1 FILTERS la> Model: TAM4A0A24S21SA Number: '1 Type 'Throwaway Horsepower: 0.25 Furnished: No Unit Primary Voltage: 208 Motor Speed(RPM): 1075 Number: 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 16'k20"x1" Unit Hertz: 60 Full Load Amps: 1.3 Unit Phase: 1 Locked Rotor Amps: 2.6 STANDARD le> REFRIGERANT Weights 230 Volt/208 Volt Type: R-410A Shipping: 126.0 lb REF.Line Connections Net: 116.0 lb Minimum Circuit Ampacity: '2.0/2.0 3/4" Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas: Coupling or Conn.Size-Liq.: 3/8" ELECTRIC HEAT 240 Volt/208 Volt NOTES: 68 Capacity Circuit#1: N//A/5.76 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (ori standard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: 1 3.Mininum filter size for horizontal applications will be based on airflow selection Phase: 1 and will be calculated as follows: low velocity filter:face area(sq.ft.)=cfm/300 Heater Amps Per Circuit Circuit#1: 32.0/27.70 high velocity filter face area(sq.ft)=cfm/500 Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of filter maintenance,it is recommended that a properly sized,remote filter and grille be - Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used 42.0/36.0 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#1: Minimum Circuit Ampacity Circuit#2: N/A N/A Minimum Circuit Ampacity Circuit#3: Maximum Overload Protection Circuit#1: 45.0/40.0 Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 29 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B2, B5, B11 Qty: 3 Tag(s): AHU/CU1-2, AHU/CU-2-1,AHU/CU3-2 32 518" UNIT DIMENSTIONS I DIM-D I 5/8" I I DIM-E 3/8" I Iflip��-' l itiIIt-' NOTES 1.TOP DISCHARGE AREA SHOULD BE �� ��/` UNRESTRICTED FOR AT LEAST 60" � ABOVE UNIT.UNIT SHOULD BE PLACED SO ROOF SERVICE PANEL /— / RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, SEE NOTE 2 Ir�� I\ —�� 29 3/4" AND SHOULD BE AT LEAST 12"FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. `l OTHER TWO SIDES UNRESTRICTED. 1 t 2.ELECTRICAL AND REFRIGERANT COMPONENT ``\ CLEARANCES PER PREVAILING CODES. iii l'11�/ 1" — — — — — — i . ELECTRICAL SERVICE PANEL Ill 7/8"DIA.HOLE 20" LOW VOLTAGE ill 28 3/4" LIQUID LINE SERVICE VALVE, " "E"I.D.FEMALE BRAZE 1 1/8"DIA.K.O.WITH CONNECTION WITH 1/4"SAE 7/8"DIA.HOLE IN CONTROL 1" FLARE PRESSURE TAP FITTING. BOX BOTTOM FOR ELECTRICAL POWER SUPPLY •t:7 81/4" III 8 1/4" �I;' 5 5/8" I 5 3/8" ..... Jf:!1--i- Q V ■u-mow UQUID UNE SERVICE VALVE, I "E"I.D.FEMALE BRAZE 3 1/8'b S UNE 1/4"TURN BALL 3 1/8" CONNECTION WITH 1/4"SAE SERVICE VALVE,"D"I.D.FEMALE 3 „ FLARE PRESSURE TAP FITTING. 3 5/8" BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. GAS UNE SERVICE VALVE, "D"I.D.FEMALE BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 30 of 74 Installed by Others • IFly Portland OR January 29,2015 Unit Dimensions-Split System Air Conditioning Units (Small) Item: B2, B5, B11 Qty: 3 Tag(s): AHU/CU1-2, AHU/CU-2-1, AHU/CU3-2 'ELECTRICAL/GENERAL DATA 'GENERAL POWER CONN. COMPRESSOR Model: '4TTR3024 Minimum CircuitAmpaclty '17.0 Number. '1 Voltage: Maximum Circuit Breaker: 25.0 Phase: 1 Unit Hertz: Minimum Protection Rating: 25.0 Rated Load Amps: 8.3 Unit Phase: Locked Rotor Amps: 58.0 OUTDOOR MOTOR NOTES: Number: '1 1.Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on Horsepower: 0.125 AHRI Standard 210/240. Motor Speed(RPM): 825 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. Phase: 1 3.Standard line lengths-60'.Standard lift-60'Suction and Liquid line. Full Load Amps: 0.7 For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 Locked Rotor Amps: - 4.'=15,20,25,30,40 and 50 foot lineset available. REFRIGERANT Type: -R-410 Charge: 5.1 lb Line Size O.D.Gas: 5/8" Line Size O.D.LIQ: 3/8" Cl WEIGHT _NET '169.0 lb SHIPPING '196.0 lb LU NOTES: Q Cl.TOP DISCHARGE SHOULD BE UNRESTRICTED = FOR AT LEAST 60"ABOVE UNIT to C2.PLACE UNIT FROM WALL p C3.PLACE SHRUBBERY AT LEAST 12" FROM UNIT ON TWO SIDES,OTHER SIDES UNRESTRICTED C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT �,����)I����i � /1111\��. mamma C3 02 C3 WEIGHT AND CLEARANCE FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 31 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Small) Item: B6, B7 Qty: 2 Tag(s): AHU/CU2-2, AHU/CU2-3 - NOTES: 21 13/16" - 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 11/2" r3- - 143/8' - - 515/16" r1 1/2" i I 17 1/2" 14 1/2" I_______ ' 1 1/2" LIQUID LINE 3/8" GAS LINE 3/4" 00 I ❑ II 1 i �' . i t 49 7/8" I O L . 4� 39518" i, 12L1.1/2"1/2'J 26 11/16" 21 13/16" El 11/2"-m- - 17 1/8" - - 3 1/8" 1 1/2" i 14 1/T I 0 11 1 1/2"J AIRHANDLER-TAM4AOA36 DRAWING FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 32 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) ` Item: B6, B7 Qty: 2 Tag(s): AHU/CU2-2, AHU/CU2-3 'ELECTRICAL/GENERAL DATA 'GENERAL (1X2X4) INDOOR MOTOR (1) FILTERS (3) Model: TAM4A0A36S31SA Number: '1 Type: Throwaway Horsepower: 0.50 Furnished: No Unit Primary Voltage: 208 Motor Speed(RPM): 1075 Number 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 16'520'x1" Unit Hertz 60 Full Load Amps: 2.4 Unit Phase: 1 Locked Rotor Amps: 3.8 STANDARD (5) REFRIGERANT Weights 230 Volt/208 Volt Type: R-410A Shipping: 123.0 lb REF.Line Connections Net: 113.0 lb Minimum Circuit Ampacity: 3.0/3.0 3/4„ Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas: Coupling or Conn.Size-Liq.: „ ELECTRIC HEAT 240 Volt/208 von NOTES: Capacity Circuit#1: 7.68 A/5'76 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (ari standard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: 1 3.Minimum filter size for horizontal applications will be based on airflow selection Phase: 1 and will be calculated as follows: low velocity filter:face area(sq.ft)=cfm/300 32.0/27.70 high velocityfilter face areaft) cfm/500 Heater Amps Per Circuit Circuit#1: g (sq. = Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of filter maintenance,it is recommended that a properly sized,remote filter and grille be Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used Minimum Circuit Ampacity Circuit#1: 43.0/38.0 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#2: N/A Minimum Circuit Ampacity Circuit#3: N/A Maximum Overload Protection Circuit#1: 45.0/40.0 Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 33 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Small) Item: B6, B7 Qty: 2 Tag(s): AHU/CU2-2, AHU/CU2-3 32 5/8" UNIT DIMENSTIONS I DIM-D I 3/4" I DIM-E I 5/16" I y 4 NOTES !� /, � 1.TOP DISCHARGE AREA SHOULD BE I .y �'^ UNRESTRICTED FOR AT LEAST 60" • ABOVE UNIT.UNIT SHOULD BE PLACED SO ROOF nri RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, SERVICE PANEL - • .:-:. SEE NOTE 2 . 29 3/4" TWO SHOULD BE AT LEAST 12"FROM WALL AND ALL SURROUNDING SHRUBBERY ON TO SIDES. a.. OTHER TWO SIDES UNRESTRICTED. 2.ELECTRICAL AND REFRIGERANT COMPONENT *,, , I CLEARANCES PER PREVAILING CODES. I 1" — — — — — — i ELECTRICAL SERVICE PANEL — 7/8"DIA.HOLE 20" LOW VOLTAGE ' 32 5/8" LIQUID LINE SERVICE VALVE, 1 1/8"DIA.K.O.WITH 4 , CONNECTION WITH 1/4"SAE 7/8"DIA.HOLE IN CONTROL 1" • FLARE PRESSURE TAP FITTING. BOX BOTTOM FOR III ELECTRICAL POWER SUPPLY 8 1/4" s Sre V 8 1/4"55/8" , . J j b A ■i,.. LIQUID UNE SERVICE VALVE, I "E"I.D.FEMALE BRAZE 31/8'b _ .S UNE 1/4"TURN BALL 3 1/6' _ _ CONNECTION WITH 1/4"SAE SERVICE VALVE,"D"I.D.FEMALE 3 „ FLARE PRESSURE TAP FITTING. 3 5/8" BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. GAS UNE SERVICE VALVE, "D"I.D.FEMALE BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 34 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B6, B7 Qty: 2 Tag(s): AHU/CU2-2,AHU/CU2-3 'ELECTRICAL/GENERAL DATA 'GENERAL POWER CONN. COMPRESSOR Model: .4TTR3036 Minimum Circuit Ampacity: '18.0 Number: '1 Voltage: Maximum Circuit Breaker: 30.0 Phase: 1 Unit Hertz: Minimum Protection Rating: 30.0 Rated Load Amps: 14.0 Unit Phase: Locked Rotor Amps: 63.0 OUTDOOR MOTOR NOTES: Number: '1 1.Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on Horsepower: 0.125 AHRI Standard 210/240. Motor Speed(RPM): 825 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. Phase' 1 3.Standard line lengths-60'.Standard lift-60'Suction and Liquid line. Full Load Amps: 0.7 For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 Locked Rotor Amps: - 4.'=15,20,25,30,40 and 50 foot lineset available. REFRIGERANT Type: R-410 Charge: 6.1 lb Line Size O.D.Gas: 3/4" Line Size O.D.LIQ: 3/8" Cl WEIGHT NET '190.0 lb SHIPPING '217.0 lb UJ NOTES: Cl.TOP DISCHARGE SHOULD BE UNRESTRICTED = FOR AT LEAST 60"ABOVE UNIT cn U C2.PLACE UNIT FROM WALL p C3.PLACE SHRUBBERY AT LEAST 12" C4 FROM UNIT ON TWO SIDES,OTHER SIDES UNRESTRICTED C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT .��\\\SII///,'' 111111 C3 .s::z=7.. 11! 4I ansasimi C2 C3 WEIGHT AND CLEARANCE FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 35 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Small) Item: B8 Qty: 1 Tag(s): AHU/CU2-4 - 'ELECTRICAL/GENERAL DATA 'GENERAL t�x2x4( INDOOR MOTOR Itl FILTERS (3) Model: TAM4A0A30S21SA Number: '1 Type: Throwaway Horsepower: 0.33 Furnished: No Unit Primary Voltage: 208 Motor Speed(RPM): 1025 Number 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 16'520"x1" Unit Hertz 60 Full Load Amps: 1.7 Unit Phase: 1 Locked Rotor Amps: 3.5 STANDARD (5) REFRIGERANT Weights 230 Volt/208 Volt Type: R-410A Shipping: 127.0 lb Minimum Circuit Ampacity: '2.02.0 REF.Line Connections Net: 117.0 lb Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas: 3/4., Coupling or Conn.Size-Liq.: " ELECTRIC HEAT NOTES: 240 Volt/208 Von 7.68/5.76 Capacity Circuit#1: N/A 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (adstandard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: 1 3.Minimum filter size for horizontal applications will be based on airflow selection Phase: 1 and will be calculated as follows: low velocity filter:face area(sq.ft.)=cfm/300 32.0/27.70 Heater Amps Per Circuit Circuit#1: high velocityfilter:face area(sq.ft)=cfm/500 Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of fitter maintenance,it is recommended that a properly sized,remote filter and grille be Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used 0/37.0 5.Standard mca and mop without electric heat t. Minimum Circuit Ampacity Circuit#1: 42. Minimum Circuit Ampacity Circuit#2: Minimum Circuit Ampacity Circuit#3: N/A Maximum Overload Protection Circuit#1: 45.0/40.0 Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 36 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) ' Item: B8, B9 Qty: 2 Tag(s): AHU/CU2-4,AHU/CU2-5 32 5/8" UNIT DIMENSTIONS DIM-D I 3/8" - - I DIM-E I 3/8" I Iii"-----117-7-84., � ��.�� �� �� NOTES I ���� 1 ' '��j 1.TOP DISCHARGE AREA SHOULD BE �l I UNRESTRICTED FOR AT LEAST 60" I `� �\ ABOVE UNIT.UNIT SHOULD BE PLACED SO ROOF SERVICE PANEL I` _. � RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, SEE NOTE 2 Imo— --- ...111 29 3/4" AND SHOULD BE AT LEAST 12"FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. � OTHER TWO SIDES UNRESTRICTED. ' 2.ELECTRICAL AND REFRIGERANT COMPONENT \*-,' I CLEARANCES PER PREVAILING CODES. 1 .' I. 1„ i ELECTRICAL SERVICE PANEL II 7/8"DIA.HOLE 20" LOW VOLTAGE "a ' - 28 3/4" LIQUID UNE SERVICE VALVE, 1 1/8"DIA.KO.WITH I "E"I.D.FEMALE BRAZE 7/8"DIA.HOLE IN CONTROL 1" CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. BOX BOTTOM FOR ELECTRICAL POWER SUPPLY 4\ _l 1 [.�7 81/4" 7 ; • 81/4" `viii 55/8" 5 3/8" NM .....1""ILIJ inik UQUID UNE SERVICE VALVE, _ "E"I.D.FEMALE BRAZE 31/8 _ •S LINE 1/4"TURN BALL 3 1/8 I. CONNECTION WITH 1/4"SAE SERVICE VALVE,"D"I.D.FEMALE 3 5/8" FLARE PRESSURE TAP FITTING. 3 5/8" BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. GAS LINE SERVICE VALVE, "D"I.D.FEMALE BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 37 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B8, B9 Qty: 2 Tag(s): AHU/CU2-4, AHU/CU2-5 ELECTRICAL/GENERAL DATA 'GENERAL POWER CONN. COMPRESSOR Model: '4TTR3030 Minimum Circuit Ampacity '15.0 Number. '1 Voltage: Maximum Circuit Breaker: 25.0 Phase: 1 Unit Hertz Minimum Protection Rating: 25.0 Rated Load Amps: 11.3 Unit Phase: Locked Rotor Amps: 68.2 OUTDOOR MOTOR NOTES: Number: '1 1.Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on Horsepower. 0.125 AHRI Standard 2101240. Motor Speed(RPM): 825 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. Phase' 1 3.Standard line lengths-60'.Standard lift-60'Suction and Liquid line. Full Load Amps: 0.7 Locked Rotor Amps: For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 4.*=15,20,25,30,40 and 50 foot lineset available. REFRIGERANT Type: *R-410 Charge: 5.0 b Line Size O.D.Gas: 3/4" Line Size O.D.LIQ: 3/8" Cl WEIGHT NET '173.0 lb SHIPPING '200.0 lb CO NOTES: Cl.TOP DISCHARGE SHOULD BE UNRESTRICTED = FOR AT LEAST 60"ABOVE UNIT cn U C2.PLACE UNIT FROM WALL p C3.PLACE SHRUBBERY AT LEAST 12" C4 FROM UNIT ON TWO SIDES,OTHER SIDES UNRESTRICTED C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT 11w\\WIPP/ ii/11111\��... #10#014.11. C3 C2 C3 WEIGHT AND CLEARANCE FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 38 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) • Item: B9 Qty: 1 Tag(s): AHU/CU2-5 'ELECTRICAL/GENERAL DATA 'GENERAL (1x2X4) INDOOR MOTOR (7) FILTERS (3) Model: 7AM4A0A30S21SA Number: '1 Horsepower: 0.33 Type: 'Throwaway No Unit Primary Voltage: 208 Motor Speed(RPM): 1025 Num1 Unit Secondary Voltage: Phase: 1 Number: 1 230 Recommended: 16'k20k1" Unit Hertz: 80 Full Load Amps: 1.7 Unit Phase: 1 Locked Rotor Amps: 3.5 STANDARD (5) REFRIGERANT Weights 230 Volt/208 Volt Type: R-410A Shipping: 127.0 Ib Minimum Circuit Ampacity: '2.02.0 REF.Line Connections Net: 117.0 lb Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas: 3/4" Coupling or Conn.Size-Lig.: 3/8" ELECTRIC HEAT 240 Vott/208 Volt NOTES: 60Capacity Circuit#1: N/A 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (ari standard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: 1 3.Minimum fitter size for horizontal applications will be based on airflow selection Phase: 1 and will be calculated as follows: low velocity filter:face area(sq.ft.)=cfm/300 40.0/34.60 high velocityfilter:face areaft)= Heater Amps Per Circuit Circuit#1: 9 (sq. cfm/500 Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of filter maintenance,it is recommended that a properly sized,remote filter and grille be - Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used Minimum Circuit Ampacity Circuit#1: 52.0/45.0 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#2: N/A Minimum Circuit Ampacity Circuit#3: N/A Maximum Overload Protection Circuit#1: 60.0/45.0 Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 39 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Small) Item: B10 Qty: 1 Tag(s): AHU/CU3-1 NOTES: 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH 21 13/16" - INSTALLER DOCUMENTS BEFORE INSTALLATION 11/2" - 143/8' - - 515/16" F1 1/2" 1 21 5/16" 18 3/8" 1 1/2"J LIQUID LINE 3/8" GAS LINE 7/8" 93/16" - - 3" r . • op. I4-17 r [ i 5511/16" I n 4� 451/7' l' M 1 1/2"J L . . 24 13/16" 21 13/16" ,, 1 1/2"—m- - 17 1/8" - - 3 1/8" F1 1/2" i 18 3/8" 1 1/2"J AIRHANDLER-TAM4A0A42 DRAWING FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 40 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions-Split System Air Conditioning Units (Small) Item: B10 Qty: 1 Tag(s): AHU/CU3-1 'ELECTRICAL/GENERAL DATA GENERAL (1x21(4) INDOOR MOTOR (t) FILTERS (3) Model: TAM4A0B42S31SA Number: '1 Type: 'Throwaway Horsepower: 0.50 Furnished: No Unit Primary Voltage: 208 Motor Speed(RPM): 1075 Number: 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 20"x20"x1" Unit Hertz: 60 Full Load Amps: 2.7 Unit Phase: 1 Locked Rotor Amps: 5.0 STANDARD (5) REFRIGERANT Weights 230 Volt/208 Volt Type: R-410A Shipping: 144.0 lb Minimum Circuit Ampacity: '3.0/3.0 REF.Line Connections Net: 133.0 lb Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas: 7/8" Coupling or Conn.Size-Liq.: 3/8" ELECTRIC HEAT 240 Volt/208 Volt NOTES: Capacity Circuit#1: N/A 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (ari standard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: N/A 3.Minimum filter size for horizontal applications will be based on airflow selection Phase: N/A and will be calculated as follows: low velocity filter:face area(sq.ft.)=cfm/300 Heater Amps Per Circuit Circuit#1: N/A high velocity fitter.face area(sq.ft)=cfm/500 Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of filter maintenance,it is recommended that a properly sized,remote fitter and grille be • Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the fitter being used Minimum Circuit Ampacity Circuit#1: N/A 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#2: N/A Minimum Circuit Ampacity Circuit#3: N/A Maximum Overload Protection Circuit#1: N/A Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 41 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Small) Item: B10 Qty: 1 Tag(s): AHU/CU3-1 37 1/4" UNIT DIMENSTIONS DIM-D I 3/4" I DIM-E I 3/8" I i€ii ,.. NOTES 1. OP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT.UNIT SHOULD BE PLACED SO ROOF •SERVICE PANEL RUN-OFF WATER DOES NOT POUR DIRECTLY D UNIT, SEE NOTE 2 ` 341/4" AND SHOULD BEAT LEAST 12"FROM WALL AND-, ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED. 2.ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES. 1�1 t 1" - - - - - - 1 ELECTRICAL SERVICE PANEL Lam• 1 a L 7111111k, 7/8"DIA.HOLE 20" LOW VOLTAGE 29 1/8" LIQUID LINE SERVICE VALVE, 4 "E"I.D.FEMALE BRAZE 1 1I8"DIA.K.O.WITH CONNECTION WITH 1/4"SAE 7/8"DIA.HOLE IN CONTROL 1" ' FLARE PRESSURE TAP FITTING. BOX BOTTOM FOR ELECTRICAL POWER SUPPLY • q 41 :] II :::.:,,, ii 85/8" 6. .., 85/8" CI►� L b { t{ 0 �u..w LIQUID UNE SERVICE VALVE, I "E"I.D.FEMALE BRAZE 3 3/8"b S UNE 1/4"TURN BALL 3 3/8" - CONNECTION WITH 1/4"SAE SERVICE VALVE,"D"I.D.FEMALE 3 7/8" - FLARE PRESSURE TAP FITTING. 3 7/8" A a BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. GAS UNE SERVICE VALVE, "D"I.D.FEMALE BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. FLD=Fumished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 42 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B10 Qty: 1 Tag(s): AHU/CU3-1 'ELECTRICAL/GENERAL DATA 'GENERAL POWER CONN. COMPRESSOR Model: 4TTA3042* Minimum Circuit Ampacity '18.0 Number: '1 Operating Voltage: 187-253 Maximum Circuit Breaker: 30.0 Phase: 3 Unit Primary Voltage: 208 Minimum Protection Rating: 30.0 Rated Load Amps: 13.6 Unit Secondary Voltage 230 Locked Rotor Amps: 83.0 Unit Hertz 60 Unit Phase: 3 OUTDOOR MOTOR NOTES: Number: 1 1 Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on Horsepower: 0.2 AHRI Standard 210/240. Motor Speed(RPM): 825 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. Phase: 3 3.Standard line lengths-60'.Standard lift-60'Suction and Liquid line. Full Load Amps: 0.93 For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 Locked Rotor Amps: 4.•=15,20,25,30,40 and 50 foot lineset available. REFRIGERANT Type: R-410 Charge: 6.1 lb Line Size O.D.Gas: 3/43/8" Line Size O.D.LIQ: Cl WEIGHT NET '196" SHIPPING '228.0 lb LU CC NOTES: Cl.TOP DISCHARGE SHOULD BE UNRESTRICTED FOR AT LEAST 60"ABOVE UNIT to C2.PLACE UNIT FROM WALL p C3.PLACE SHRUBBERY AT LEAST 12" C4 FROM UNIT ON TWO SIDES,OTHER SIDES UNRESTRICTED C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT 4111.00 1.1 ‘ammowell C3� l yC2 C3 WEIGHT AND CLEARANCE FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 43 of 74 Installed by Others IFlyPortland OR January 29,2015 Unit Dimensions-Split System Air Conditioning Units(Small) Item: B11 Qty: 1 Tag(s): AHU/CU3-2 'ELECTRICAL/GENERAL DATA 'GENERAL (1)(254) (I)MOTOR trl (3) FILTERS Model: TAM4A0A24S21SA Number: '1 Type: Throwaway Horsepower: 0.25 Furnished: No Unit Primary Voltage: 208 Motor Speed(RPM): 1075 Number: 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 16'k20"x1" Unit Hertz: 60 Full Load Amps: 1.3 Unit Phase: 1 Locked Rotor Amps: 2.6 STANDARD (e) REFRIGERANT Weights 230 Volt/208 Volt Type: R-410A Shipping: 126.0 lb Minimum Circuit Ampacity: '2.0/2.0 REF.Line Connections 3/4 Net: 116.0 lb Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas: Coupling or Conn.Size-Liq.: 3/8" ELECTRIC HEAT 240 Volt/208 Volt NOTES: 9.60/7.20 Capacity Circuit#1: N/A 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A (ari standard 210/240).refer tothesplit system outdoor unit product data guides for performance data. Capacity Circuit#3: 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: 1 3.Minimum filter size for horizontal applications will be based on airflow selection Phase: 1 and will be calculated as follows: low velocity filter face area(sq.ft)=cfm/300 40.0/34.60 high velocityfilter:face area(sq.ft.) cfm/500 Heater Amps Per Circuit Circuit#1: = Heater Amps Per Circuit Circuit#2: N/A 4.For customer ease of filter maintenance,it is recommended that a properly sized,remote filter and grille be Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used 52.0/45.0 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#1: Minimum Circuit Ampacity Circuit#2: Minimum Circuit Ampacity Circuit#3: N/A • Maximum Overload Protection Circuit#1: 60.0/45.0 Maximum Overload Protection Circuit#2: N/A Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 44 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B12 Qty: 1 Tag(s): AHU/CU3-3 NOTES: 1.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION Fr: ' 213/16" -1 1/2" - 143/8" - - 5 15/16" r1 1/T'231/2" 201/T' 1 1/2" LIQUID LINE 3/8" GAS LINE 7/8" 1105/16'- - 3" • •• O° • / ❑ • 56 7/8" I 4 4611/16" 9 1 1/2"J 1 lii 21 13/16" E 241/2" 11/2"--v - 17 1/8" - - 3 1/8" r11/2" V4 olionwi A 201/2" 4, 0 1 1/2"J AIRHANDLER-TAM4A0A48 _ DRAWING FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 45 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Small) Item: B12 Qty: 1 Tag(s): AHU/CU3-3 'ELECTRICAL/GENERAL DATA 'GENERAL(1 x2x4) INDOOR MOTOR (1) FILTERS (3) Model: 'TAM4A0C48S41SA Number: '1 Type: Throwaway Horsepower: 0.50 Furnished: No Unit Primary Voltage: Y08 Motor Speed(RPM): 1075 Number. 1 Unit Secondary Voltage: 230 Phase: 1 Recommended: 22'k20"x1" Unit Hertz: 60 Full Load Amps: 3.1 Unit Phase: 1 Locked Rotor Amps: 5.5 STANDARD (5) REFRIGERANT Weights 230 Volt/208 Volt Type: R-410A Shipping: 155.0 lb Minimum Circuit Ampacity: '4.0/4.0 REF.Line Connections 7/8 Net: 143.0 lb Maximum Overload Protection: 15.0/15.0 Coupling or Conn.Size-Gas: Coupling or Conn.Size-Liq.: 3/8" ELECTRIC HEAT NOTES: 240 Volt/208 Volt Capacity Circuit#1: 9.60/7.204.80/3.60 .80/1.60 1.These air handlers are a.r.i.certified with various split system air conditioners and heat pumps Capacity Circuit#2: N/A80/3.60 (ad standard 210/240).refer tothesplit system outdoor unitproduct data guides for performance data. Capacity Circuit#3: ( p 2.3/4"male plastic pipe(ref.:astm 1785-76) #of Circuit: 1 3.Minimum filter size for horizontal applications will be based on airflow selection Phase: 1 and will be calculated as follows: low velocity filter face area(sq.ft.)=cfm/300 40.0/34.60 high velocityfilter face areacfm/500 Heater Amps Per Circuit Circuit#1: 20.0/17.3 (sq.ft) Heater Amps Per Circuit Circuit#2: 4.For customer ease of filter maintenance,it is recommended that a properly sized,remote filter and grille be Heater Amps Per Circuit Circuit#3: N/A installed for horizontal applications.airflow should not exceed the face value of the filter being used - 5.Standard mca and mop without electric heat. Minimum Circuit Ampacity Circuit#1: 54.0/47.0 Minimum Circuit Ampacity Circuit#2: 25.0/22.0 Minimum Circuit Ampacity Circuit#3: N/A Maximum Overload Protection Circuit#1: 60.0/50.0 ' Maximum Overload Protection Circuit#2: 25.0/25.0 Maximum Overload Protection Circuit#3: N/A FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 46 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Small) Item: B12 Qty: 1 Tag(s): AHU/CU3-3 37 1/4" UNIT DIMENSTIONS DIM-D I 7/8" I DIM-E I 3/8" 1, / ,.\ r `ANOTES t ��� �� j 1.TOP DISCHARGE AREA SHOULD BE 0"r\ \ UNRESTRICTED FOR AT LEAST 60",,� �� ���1 ABOVE UNIT.UNIT SHOULD BE PLACED SO ROOF SERVICE PANEL I`— --1 RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, SEE NOTE 2 I —I 341/4" AND SHOULD BE AT LEAST 12"FROM WALL AND —��I ' �, ALL SURROUNDING SHRUBBERY ON TWO SIDES. ‘ � � OTHER TWO SIDES UNRESTRICTED. � �/ I/42.ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES. 4 .-'///1 1" — — i ELECTRICAL r SERVICE PANEL m 1 aL. 1 7/8"DIA.HOLE 20" LOW VOLTAGE —_' 29 1/8" LIQUID UNE SERVICE VALVE, 1 1/8"D .K.O.WITH Q "E"I.D.FEMALE BRAZE 7/8"DIA.HOLE IN CONTROL 1" CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. BOX BOTTOM FOR ELECTRICAL POWER SUPPLY q *t` ; 85/8" 8„ " 85/8" 6" Li" UQUID UNE SERVICE VALVE, "E"I.D.FEMALE BRAZE 33/8 GAS UNE 1/4"TURN BALL 33/8" CONNECTION WITH 1/4"SAE SERVICE VALVE,"D"I.D.FEMALE 3 7/8" FLARE PRESSURE TAP FITTING. 3 7/8" - BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. GAS UNE SERVICE VALVE, "D"I.D.FEMALE BRAZED CONNECTION WITH 1/4"SAE FLARE PRESSURE TAP FITTING. FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 47 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions-Split System Air Conditioning Units (Small) Item: B12 Qty: 1 Tag(s): AHU/CU3-3 'ELECTRICAL/GENERAL DATA GENERAL POWER CONN. COMPRESSOR Model: 4TTA3048* Minimum Circuit Ampacity: '18.0 Number '1 Operating Voltage: 187-253 Maximum Circuit Breaker 30.0 Phase: 3 Unit Primary Voltage: 208 Minimum Protection Rating: 30.0 Rated Load Amps: 13.7 Unit Secondary Voltage 230 Locked Rotor Amps: 83.0 Unit Hertz: 60 Unit Phase: 3 OUTDOOR MOTOR NOTES: Number: 1 1.Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on Horsepower: 0.20 AHRI Standard 210/240. Motor Speed(RPM): 825 2.Calculated in accordance with N.E.C.Use only HACR circuit breakers or fuses. Phase: 3 3.Standard line lengths-60'.Standard lift-60'Suction and Liquid line. Full Load Amps: 0.93 For Greater lengths and lifts refer to refrigerant piping software Pub#32-3312-0 Locked Rotor Amps: 4.*=15,20,25,30,40 and 50 foot lineset available. REFRIGERANT Type: R-410 Charge: 6.8 Ib Line Size O.D.Gas: 7/83/8" Line Size O.D.LIQ: Cl WEIGHT NET '203" SHIPPING '235.0 lb UJ C7 NOTES: Q Cl. IX TOP DISCHARGE SHOULD BE UNRESTRICTED = FOR AT LEAST 60"ABOVE UNIT U C2.PLACE UNIT FROM WALL p C3.PLACE SHRUBBERY AT LEAST 12" C4 FROM UNIT ON TWO SIDES,OTHER SIDES UNRESTRICTED C4.PLACE UNIT SO ROOF RUN-OFF DOES NOT FALL DIRECTLY ON UNIT ��`...r••••••�, C3� cdf ==� �C2 C3 WEIGHT AND CLEARANCE FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 48 of 74 Installed by Others IFly Portland OR January 29,2015 Weight, Clearance& Rigging Diagram -Split System Air Conditioning Units (Small) Item: B1 -B12 Qty: 12 Tag(s): AHU/CU1-1,AHU/CU1-2, AHU/CU1-3, AHU/CU1-4, AHU/CU-2-1, AHU/CU2-2, AHU/CU2-3, AHU/CU2-4, AHU/CU2-5, AHU/CU3-1, AHU/CU3-2, AHU/CU3-3 VERTICALDOWNFLOW 111101 ••-• 11uri ®`�I REFRIGERANT ElCONNECTION Din OWNFLOW 11 CONDENSATE ' ll r'41 DRAIN REFRIGERANTTDOWNFLOW CONNECTIO ❑ -� / CONDENSATE DRAIN Ti IJ �L . _ •• jQrt REFRIGERANT CONNECTION VERTICAL UPFLOW R, ® <=11[11HORIZONTAL LEFT FLOW REFRIGERANT CONNECTION = 144.11111 DOWNFLOW CONDENSATE DRAIN • HORIZONTAL RIGHT FLOW t` .. 111.1 DOWNFLOW CONDENSATE DRAIN NOTES MINIMUM UNIT CLEARANCE TABLE 1.NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. TO COMBUSTIBLE SERVICE CLEARANCE 2.BADGE ROTATION WILL BRAND IN CORRECT POSITION MATERIALS(REQUIRED) (RECOMMENDED) SIDE 0 2" FRONT 0 21" BACK 0 0 INLET DUCT 0 0 OUTLET DUCT 0 0 CLEARANCE NOTES: 1"FOR THE FIRST 3 FT.OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALED EXCEPT MODELS BAYHTR1405,1408,AND 1410 ARE APPROVED FOR 0"PLEMUM AND DUCT CLEARANCE IN THE UPFLOW CONFIGURATION ONLY ON TWE-P MODELS. FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 49 of 74 Installed by Others IFly Portland OR January 29,2015 Accessory -Split System Air Conditioning Units (Small) Item: B1 -B12 Qty: 12 Tag(s): AHU/CU1-1, AHU/CU1-2,AHU/CU1-3, AHU/CU1-4,AHU/CU-2-1, AHU/CU2-2, AHU/CU2-3, AHU/CU2-4,AHU/CU2-5,AHU/CU3-1,AHU/CU3-2,AHU/CU3-3 - 1 3/6 ISIVICia II IN ors. 3 5/16" 9/ O p E 0 35/16" I- O I I~I Q )11 LLLI':I .i f I'ri Ii TCONT200 ACCESSORY-THERMOSTAT FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 50 of 74 Installed by Others IFly Portland OR January 29,2015 Tag Data -Split System Air Conditioning Units (Large) (Qty: 1) Item Tag(s) Qty Description Model Number C1 AHU/HP4-1 1 7.5 Ton Unitary Split Systems TWA090D4ORA-TWE090D300A Product Data-Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHUIHP4-1 • TWA Heat Pump Outdoor Unit 7 1/2 Ton Nominal Cooling Capacity Single Compressor- R-410A 460 Volt 3 Phase 60 Hertz ReliaTel Controls Minor design sequence A TWE Air Handler Unit 7 1/2 Ton Nominal Cooling Capacity Single Refrigerant Circuit- R410 208-230 Volt 3 Phase 60 Hertz Minor design sequence A Prog. 7 day, 3 Htg/2 Clg Touchscreen (FId) 1 Low Ambient Modulating (FId) Rubber-in-shear isolators(FId) Condenser Coil HailNandal Guard Kit(FId) NOT INCLUDED: - Any controls wiring not listed - Wiring - Vibration isolation for indoor air handlers - Condensate pumps - Auxiliary drainpan float switch - Outside air dampers/actuators and any associated wiring - Insulation - Disconnects/circuit breakers - Fan interlocks - Additional filters/belts/sheaves - Refrigerant specialties/piping/line sets - Smoke detectors, remote test stations, annunciator panels - Owner training/maintenance - Extended warranties not specifically listed above - Startup - NEC 2011 requirements - Any other items not listed in unit detail Performance Data-Split System Air Conditioning Units (Large) Tags AHU/HP4-1 MCA- heat pump (A) 17.90 MOP-heat pump(A) 25.00 Total power- heat (kW) 7.16 COP (COP) 2.78 Min. H.P. operating weight(lb) 340.0 Max. H.P. operating weight(Ib) 394.0 Condensing unit type Heat pump unit Airflow(cfm) 3000 Cooling EDB (F) 85.00 _ Cooling EWB (F) 70.70 Ambient(F) 105.00 Relative humidity(%) 49.74 Heating EAT(F) 70.00 Heating ambient WB (F) 27.02 FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 51 of 74 Installed by Others IFly Portland OR January 29,2015 Tags AHU/HP4-1 Heating ambient RH (%) 70.00 Heating ambient DB (F) 30.00 Gross total capacity(MBh) 88.99 Gross sensible capacity(MBh) 72.45 Latent capacity(MBh) 16.56 Net total capacity(MBh) 85.03 Net sensible capacity (MBh) 68.47 Cooling LDB (F) 64.27 Cooling LWB (F) 62.48 Saturated suction temp (F) 56.48 Discharge temperature (F) 128.39 Gross heating capacity (MBh) 63.94 Net heating capacity(MBh) 67.93 Heating LAT(F) 91.73 Heating delta T(F) 21.73 Electric Heat Capacity (MBh) 0.00 Electric heat delta T(F) 0.00 Line length-actual (ft) 50.00 Cond. location to A.H. Below air handler Vertical rise (ft) 20.00 Suction line size od (per circuit) 1-1/8 in. Liquid line size od (per circuit) 5/8 in. Est. refrig. chrg/circuit(Ib) 22.5 Sight glass part# GLS00853 Metering device Expansion valve External Static Pressure (in H2O) 0.500 External plus component static pressure (in H2O) 0.500 Supply fan power(bhp) 1.26 Indoor motor RPM (rpm) 807 Field applied voltage 460/3/60 MCA-A.H. (A) 3.10 MOP-A.H. (A) 15.00 MCA-A.H. for 230V w/elect heat(A) 0.00 MOP-A.H. for 230V w/elect heat(A) 0.00 Evaporator motor FLA(A) 2.50 Evaporator face area (sq ft) 8.07 Evaporator face velocity (ft/min) 372 Evaporator fin spacing (Each) 168.00 Evaporator rows(Each) 4.00 Indoor motor power(kW) 1.15 Condenser Fan Power(kW) 0.52 Compressor power(kW) 7.46 Total power(kW) 9.13 EER @ AHRI (with air handler) (EER) 11.0 EER @ AHRI (cond. unit only) (EER) 11.0 IPLV @ AHRI (with Air Handler) (IPLV) 0.0 IPLV @ AHRI (cond. unit only) (IPLV) 0.0 Compressor 1 RLA(A) 13.00 Compressor 2 RLA(A) 0.00 Condenser motor 1 FLA(A) 1.60 • Condenser motor 2 FLA(A) 0.00 Min. A.H. operating weight(lb) 323.0 Max. A.H. operating weight(lb) 360.0 Fan motor heat(MBh) 3.89 Field supplied low static drive Not required FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 52 of 74 Installed by Others IFly Portland OR January 29,2015 Mechanical Specifications -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s):AHU/HP4-1 General -TWA Weatherproofed Steel Mounting/Lifting Rails Hermetic Scroll Compressors Plate Fin Condenser Coils Fans and Motors Standard Operating Range 50-125F (Min. 0°F with Low Ambient Accy) Nitrogen Holding Charge Certified and Rated in Accordance with AHRI and DOE Standards Certified to UL 1995 Casing -TWA Zinc Coated, Heavy Gauge, Galvanized Steel Weather Resistant Baked Enamel Finish Meets 672 hr Salt Spray Test Removable Single Side Maintenance Access Panels Lifting Handles in Maintenance Access Panels Unit Base Provisions for Forklift and/or Crane Lifting Refrigeration System- TWA Single Compressor(TWA073D, TWA090D, TWA120D) Single Refrigeration Circuit with Integral Subcooling Circuit. Single Direct Drive Hermetic Scroll Compressor with Centrifugal Oil Pump Providing Lubrication To Moving Parts Suction Gas-Cooled Motor w/± 10%Voltage Utilization Range of Unit Nameplate Voltage Reversing Valve Crankcase Heater Internal Temperature and Current Sensitive Motor Overloads No Compressor Suction and/or Discharge Valves(Reduced Vibration/Sound) Factory Installed Liquid Line Filter Drier Phase Loss/Reverse Rotation Monitor Liquid Line Service Valve(with gauge port) Suction Line Service Valve (with gauge port) External High Pressure Cutout Device External Low Pressure Cutout Device Evaporator Defrost Control Loss of Charge Protection (Discharge Line Thermostat) Condenser Coil -TWA 3/8" Internally Enhanced Copper Tube Mechanically Bonded to Lanced Aluminum Plate Fins Factory Pressure and Leak Tested to 660 psig. Condenser Fan -TWA 26" or 28" Propeller Fan(s) Direct Drive Statically and Dynamically Balanced Condenser Motor(s) -TWA Permanently Lubricated Totally Enclosed or Open Construction Built-In Current and Thermal Overloads Ball or Sleeve Bearing Type Controls -TWA Centralized MicroProcessor Indoor and Outdoor Temperature Sensors Drive Algorithms Making Decisions for All Heating, Cooling, and Ventilation Integrated Anti-Short Cycle Timer Integrated Time Delay Between Compressors Completely Internally Wired Numbered and Colored Wires Contactor Pressure Lugs or Terminal Block Unit External Mounting Location for Disconnect Device Single Point Power Entry FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 53 of 74 Installed by Others IFly Portland OR January 29,2015 Low Ambient(Modulating)-TWA Provides Unit Cooling Operation to Outdoor Ambient of 0°F Wave-Chopper Discharge Line Pressure Controls Condenser Fan Operation 1 Kit Per Condenser Fan Required Vibration Isolators-TWA Neoprene-In-Shear or Spring Flex Choice Reduce Vibration Transmission to Building Structures, Equipment, and Adjacent Spaces Reduce Noise Transmission to Building Structures, Equipment, and Adjacent Spaces General -TWE Completely Factory Assembled Convertible for Horizontal or Vertical Configuration Convertible for Cooling Only or Heat Pump Application Convertible for Left or Right External Connections (Refrigerant and/or Electrical) Convertible for Front or Bottom Air Return Nitrogen Holding Charge Certified and Rated in Accordance with AHRI and DOE Standards Certified to UL 1995 for Indoor Blower Coil Units Casing -TWE Zinc Coated, Heavy Gauge, Galvanized Steel Weather Resistant Baked Enamel Finish Access Panels with Captive Screws Completely Insulated with Foil Faced, Cleanable, Fire Retardant, Permanent, Odorless Glass Fiber Material Captured or Sealed Insulation Edges Electrical Connection Bushings or Plugs Refrigerant Connection Bushings or Plugs Withstand Elevated Internal Static Pressure Refrigeration System -TWE Single or Dual Circuit Distributor(s) Thermal Expansion Valves (TXVs) Evaporator Coil -TWE 3/8" Internally Enhanced Copper Tube Mechanically Bonded to Lanced Aluminum Plate Fins Factory Pressure and Leak Tested to 449 psig. Draw-Through Airflow Dual Circuits Are Interlaced/Intertwined Double Sloped, Removable, Cleanable, Composite Drain Pan Four Drain Pan Positions Indoor Fan -TWE Double Inlet, Double Width, Forward Curved, Centrifugal Type Fan Dual Fans On 10.4-20.912.5-25 Ton Air Handlers Adjustable Belt Drive Permanently Lubricated Bearings Indoor Motor-TWE Adjustable Motor Sheaves Fixed Motors Sheaves(SZVAV and 2-Speed VFD) Thermal Overload Protection Permanently Lubricated Bearings Meet Energy Policy of 1992 (EPACT) Optional Over Sized Motors for High Static Applications Controls-TWE Completely Internally Wired Numbered and Colored Wires Magnetic Indoor Fan Contactor FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 54 of 74 Installed by Others IFly Portland OR January 29,2015 Low Voltage Terminal Strip Single Point Power Entry Evaporator Defrost Control Filters -TWE Access From Side Coil Panels Filters Slide on Rack One Inch (1"), Throw-Away Filters on 4.6-8.335-10 Ton Units Filter Rack Convertible to Two Inch (2")Capability on 5-10 Ton Units Two Inch (2"), Throw-Away Filters on 10.4-20.912.5-25 Ton Units Hailguards -TWA Condenser Coil Protection from Hail, Vandals, Etc. Perforated, Painted Galvanized Steel Factory or Field Installed FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 55 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units(Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 SEE NOTE 3 NOTES: 1.ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY. 2.MINIMUM CLEARANCE FOR PROPER OPERATION IS 36"FROM WALLS,SHRUBBERY,PRIVACY FENCES ETC.MINIMUM CLEARANCE BETWEEN ADJACENT UNITS IS 72".RECOMMENDED SERVICE SERVICE PANEL i\ CLEARANCE 48" 3.TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" !\I ' MINIMUM.UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT 4.OUTDOOR AIR TEMPERATURE SENSOR OPENING(DO NOT BLOCK OPENING) HAIL GUARD (OPTIONAL) SEE NOTE 4 ll"SERVICE CLEARANCE 48"(SEE NOTE 2 FOR CLEARANCE) HAIL GUARD - 13/16" 36 - HAIL(OPNAL) 4 1/4" WITH HAIL GUARD SEE NOTE 1 LINE VOLTAGE 3315/16"_1 REFRIGERANT ACESS CONTROL WIRING :I II I II Tft 36 3/B„ SERVICE PANEL 39 3/16" 2913/16" 2615/16" . � 14 3/8" 8516" 1•I - ..55/8 ........ @11� n A 1/16" - - 6„ 3 1/16" LIQUID LINE 3 3/4„ 6" 2" - 21 11/16" - SUCTION LINE - - 3 7/16" - 41 1/8" - - 3313/16" - 42 1/8" WITH HAIL GUARD SERVICE PANEL SIDE 3" 4 7/16"DIA.ISOLATOR MOUNTING HOLES(OUTSIDE HOLES-4 PLACES) BOTTOM 40 3/4" 34 3/4" OF UNIT 4 3/16"— - 1 13/16" - 27 11/16" - 2 5/16" 6-7 1/2 TON HEAT PUMP CONDENSER (SINGLE COMPRESSOR) DIMENSIONAL DRAWING - FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 56 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 ELECTRICAL DATA CONDENSER 'ELECTRICAL DATA COMPRESSOR MOTOR CONDENSER FAN MOTOR Model: TWA090D4 No.: '1 No.: '1 Unit Operating Voltage: 414-506 Volts: 460 Volts: 460 Minimum Circuit Ampacity: 17.9 Phase: 3 Phase: 1 Maximun Fuse Size: 25.0 Amp-RLA: 13.0 Amp-FLA: 1.6 Maximun Circuit Breaker: 25.0 Amp-LRA: 100.0 Amp-LRA: 3.8 GENERAL DATA CONDENSER COOLING PERFORMANCE (1x2)(3x4x5) COMPRESSOR Matched Air Handler. .93,000 Number '1 Condensing Unit Only 86,000 Motors/HP(each): 6.9 ARI Net Cooling Capacity: 90,000 Motor RPM: 3500 11.0 Matched Air Handler. 122,2.2 No.Compressor/Tons: 1/6.9 Condensing Unit Only: N/A System Integrated Part Load Value: N/A SYSTEM DATA (r) Condensing Unit Only IPLV: 8.18 System KW Condensing Unit KW: 7.05No.Refrigerant Circuits: 1 Suction Line(in.)OD: 1 3/8" Liquid Line(in.)OD: 5/8" IEER: 11.7 OUTDOOR COIL OUTDOOR FAN Tube Size(in.)OD '3/8" No.Used/Diameter(in.): 1/26" Face Area(sq.ft.) 191/4" Drive Type/No.Speeds: DIRECT/1 Rows/FPI 2/18 CFM: 6,530 No.Motors/HP: 1/0.5 Motor RPM: 1,100 REFRIGERANT CHARGE(Fld Supplied) 17)16) TYPE: R-410A (Circuits#1): 19.6 lb (Circuits#2): N/A NOTES: 1.Cooling performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Ratings shown are tested and certified in accordance with AHRI 2. Standard 340/360 or 365 certification program. 3.Condensing Unit Only Gross Cooling Capacity rate at 45 F saturated suction temperature and at 95 F ambient. 4.ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft.of OD interconnecting tubing. EER is rated at AHRI conditions and in accordance with DOE test procedures. 5.Integrated Part Load Value is based on AHRI Standard 340/360 or 365. Units are rated at 80 F ambient, 80 F entering dry bulb,and 67 F entering wet bulb at AHRI rated CFM. 6.Sound Rating shown is tested in accordance with AHRI Standard 270. 7.Refer to refrigerant piping program for line sizing and line length. 8.Refrigerant(operating)charge is for condensing unit(all circuits)with matching blower coils and 25 ft. of interconnecting refrigerant lines. All units are shipped with a small nitrogen holding charge only. FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 57 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions-Split System Air Conditioning Units(Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 NOTES: 1 PANEL DEPTH 1/2"(TYP.ALL PANELS). 251/2" 2.REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION,PLASTIC DRAIN PAN SUPPLY 70„ ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO - OPEN SLIDE DRAIN PAN OUT OF UNIT CLEANING.ACCESS PLATE MUST BE RE-INSTALLED AFTER 161/4" SLIDING DRAIN PAN BACK INTO UNIT. 3.IF PERIODIC DRAIN PAN CLEANING IS REQUIRED,ALLOW ROOM FOR PARTIAL REMOVAL OF A T DRAIN PAN CHER. 0IONPV T END I UNIT. 4.1"FEMALE SCHED.40 PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION. 11 11/16" 5.1"FEMALE SCHED.40 PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION. iiii 47 1/2" 241/16" LIAl • , 161/16" SIDE RETURN 16 7/8" BOTTOM RETURN 1.- 111 •11]i .11111MENI 11111 DUCT FLANGE 1 9/16" 1 13/16" 1"HEIGHT - 251/2' - 2 3/4"— - 42" - 23/4"--v - 42" - CONTROL WIRING hill. - 3 1/2" LINE VOLTAGE —_ 0 Q COPPER LIQUID LINE — 8 13/16" I FIELD CONNECTION CONTRL BOXPANEL 15 ACCESS PANEL 1 3/16' - COPPER SUCTION LINE DRAIN CONNECTION REMOTE BULB TXV FIELD CONNECTION - FOR HORIZONTAL , (SEE NOTEOTS 2 2,,33,,5) :- SUCTION LINE 22 7/8" I [lUgE 7 16111/16" 17 116 2�, 17�8- 1611/16" 1lai FILTER ACCESS PANEL - a3 5/8" 1 9/16"— ! SEE NOTES 2,3,4 22"MIN.DISTANCE BOTH SIDE - -.1 11/16 3 1/2 - LIQUID LINES SEE NOTES 2,3,4 1 3/16" - 451/8" • (4)-HOLE FOR HORIZONTAL SUSPENSION (4SUPPLY OPENING H FOR HORIZONTAL 6 3/4" ,i �' SUSPENSION • \ r/ BOTTOM RETURN \ 36 7/8" SIDE RETURN—is., –, �� 541/16" HO ' ' 1111 I FILTER �".....„... 1 1111 Ills • 10 7/16" BOTTOM RETURN SIDE RETURN .01 ••�� SUPPLY VERTICAL- SUPPLY HORIZONTAL- RETURN HORIZONTAL/ RETURN VERTICAL/ RETURN VERTICAL RETURN HORIZONTAL 7 1/2 TON AIR HANDLER (SINGLE CIRCUIT) DIMENSIONAL DRAWING - FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 58 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 AIR HANDLER ELECTRICAL DATA CONDENSER ELECTRICAL DATA Convertible 460 Voltages EVAPORATOR FAN MOTOR (s) Convertible 460 Voltages Model: TWE090 TWE090 Vol. 1 1 Unit Operating Voltage: 187-253 414-506 Minimum CircuitAmpacity 6.6-6.3 3.1 Ph208-230 460 Phase: Maximun Fuse Size: 15.0-15.0 15.0 Motor 3 3 Motor HP: 1.50 1.50 Maximun Circuit Breaker. 15.0-15.0 15.0 Amp-FLA 5.3-5.0 2.5 Amp-LRA: 34.3-34.3 17.0 GENERAL DATA SYSTEM DATA INDOOR COIL-TYPE No.Refrigerant Circuits 1 • Tude Size: 3/8" Suction Line(in.)OD 1 1/8" Face Area: 81/8" Liquid Line(in.)OD 12" Row/FPI 4/14 Refrigerant Control EXPANSION VALVE Drain Connection Size 1"PVC INDOOR FAN FILTER Type: CENTRIFUGAL Type: 'THROWAWAY No.Used/Diameter x Width: 1/15"X15" Furnished: YES Drive Type/No.Speed: BELT/ADJUSTABLE No.Size Recommended: (3)16"X25"X1" CFM: 3000 No.Motor: 1 Motor HP-Standard/Oversized: 1.5/2.0/3.0 Motor RPM: 1725 Motor Frame Size: 56H HEATER DATA ELECTRICAL DATA Notes: Heat Rating(kW): 1. KW ratings are at:208240V for 208-230V air handlers Control Stages: 480V for 460V air handlers Power Supply 600V for 575V air handlers Minimum Circuit Ampacity. Maximun Fuse Size: For other than rated voltage.capacity=( Voltam )x 2 Rated Capacity 2. Any power supply and circuits must be wired andnd protected in accordance Maximun Circuit Breaker with local electrical codes. 3. The HACR circuit breaker is for U.S.A.installations only. NOTES: 1.Cooling performance is rated at 95 F ambient,80 F entering dry bulb,67 F entering wet bulb. 2.Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Ratings shown are tested and certified in accordance with AHRI Standard 340/360 or 365 certification program. 3.Condensing Unit Only Gross Cooling Capacity rate at 45 F saturated suction temperature and at 95 F ambient. 4.AHRI Net Cooling Capacity is calculated with matched blower coil and 25 ft.of OD interconnecting tubing. EER is rated at AHRI conditions and in accordance with DOE test procedures. 5.Integrated Part Load Value is based on AHRI Standard 340/360 or 365. Units are rated at 80 F ambient, 80 F entering dry bulb,and 67 F entering wet bulb at AHRI rated CFM. 6.Sound Rating shown is tested in accordance with AHRI Standard 270. 7.Refer to refrigerant piping program for line sizing and line length. 8.Refrigerant(operating)charge is for condensing unit(all circuits)with matching blower coils and 25 ft. of interconnecting refrigerant lines. All units are shipped with a small nitrogen holding charge only. 9.Second Column data Coverable to 460 volt FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 59 of 74 Installed by Others IFly Portland OR January 29,2015 Weight, Clearance& Rigging Diagram -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 .4000111100.. ...........!"'\\'';,.\,‘,,; ,,,„.<-),.i»))))00)/," ,,,!•*" SERVICE PANEL a I I i 1 1/4"DIA LIFTING HOLES(4 PLACES) #2 #3 SERVICE PANEL A A a WEIGHTS AND CORNER WEIGHTS //.r �_` Shipping: 394.0 lb Net• 4Z;rT: \ s Comer 4: 79.0 lb #1 #4 WEIGHTS AND LOAD POINT LOCATION WEIGHT AND RIGGING FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 60 of 74 Installed by Others IFly Portland OR January 29,2015 Weight, Clearance & Rigging Diagram -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 #4 #1 WEIGHTS AND CORNER WEIGHTS B 0 • • Shipping: 360.0 lb ., ..• , Net 323.0 lb VERTICAL Corner 1: 67.0 lb • Comer 2: 99.0 Ib Corner 3: 75.0 lb Corner 4: 82.0 lb . • HORIZOTNAL . Corner A: 56.0 lb Corner B: 92.0 lb T Corner C: 67.0 Ib 0 Comer D: 88.0 Ib 0 • t o o #3 #2 A AIR FLOW HORIZONTAL I I I � HORIZONTAL RETURN ;\ AIRFLOW \\ .J RETURN 4 VERTICAL VERTICAL RETURN RETURN WEIGHTS AND LOAD POINT LOCATION FOR CONDENSOR WEIGHT AND RIGGING FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 61 of 74 Installed by Others IFly Portland OR January 29,2015 '- Accessory -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 3 7/8" 3" (7,-17N\ 2 3/8 O (0) • 3/8"DIA.2 HOLES 3/8"NC TAP 1 3/4" \\ / / OIL RESISTANT \ / NEOPRENE 1 3/4" \ / LiFE1/4" --1 •111111M111111111111111111M=M1111111111111111MMIIIIIIMININIIMIIIMII NOTE S 1.VERIFY WEIGHT,TYPE, AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION. 2.VERIFY NUMBER OF ISOLATORS AND LOCATION BEFORE INSTALLATION. RUBBER FLOOR ISOLATOR BAYISLT004,005,009,010 FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 62 of 74 Installed by Others IFly Portland OR January 29,2015 Accessory -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 6" - 13/8" 1 . ( I 45/8" I I I �II 11 01111 /L 1.'/ 3 5/16" /O .‘\ O - O O 1( m C 3 5/16" 0 4F 1= Q UPJdI ) ri TCONT800/802/803 ACCESSORY-THERMOSTAT FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 63 of 74 Installed by Others IFly Portland OR January 29,2015 - Field Wiring -Split System Air Conditioning Units (Large) Item: Cl Qty: 1 Tag(s): AHU/HP4-1 TO POWER SUPPLY PER LOCAL CODES oI n n n L I 3 PHASE I I ONLY I I 1 I I I I = 0 lS 15 8 -JJ SUPPLY HEATER r----0 CONTROL BOX SEE NOTE 9 L':T , - SEE NOTE 5 8 6 STAGE 1HEAT -- -- S W1 STAGE 2 HEAT -----�®^ FAN - G� COMPRESSOR -® y 24 VAC ® R SEE NOTE 8 24 VAC COMMON ®-B1 TO OUTDOOR UNIT ®-B2 HEAT ANTICIPATOR- ® T COOLING REVERSING VALVE - ® 0 EDC � n� o AIR HANDLER 3 PHASE —P ONLY o TO POWER SUPPLY PER LOCAL CODES INTER-COMPONENT WIRING 24 VOLT FACTORY WIRING I I LINE VOLT ----- I24 VOLT FIELD WIRING C=__c LINE VOLT NOTES: 1.POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES. 2.BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE. 3.LOW VOLTAGE WIRING TO BE 18 A.W.G.MINIMUM CONDUCTOR. 4.USE COPPER CONDUCTORS ONLY. 5.IF TWO STAGE ELECTRIC HEATERS AND THERMOSTAT ARE USED,REMOVE JUMPER BETWEEN W1 AND W2. 6.FOR SINGLE STAGE ELECTRIC HEATER,OMIT WIRE BETWEEN W2 AND THERMOSTAT AND W2 AND ELECTRIC HEATER. 7.FOR COOLING ONLY,OMIT WIRES BETWEEN W1,W2 AND THERMOSTAT AND OMIT ELECTRIC HEATER. 8.IF THE EDC SWITCH IS TO BE CONNECTED IN THE CIRCUIT,THE EDC WIRE MUST BE REMOVED FROM THE B1 TERMINAL AND RECONNECTED TO THE"Y"TERMINAL ON THE INDOOR SECTION LOW VOLTAGE TERMINAL BOARD AS SHOWN. 9.WHEN ELECTRIC HEATER ACCESSORY IS USED,SINGLE POINT POWER ENTRY OR DUAL POINT POWER ENTRY IS FIELD OPTIONAL.SINGLE POINT POWER ENTRY OPTION IS THROUGH ELECTRIC HEATER ONLY. FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 64 of 74 Installed by Others IFly Portland OR January 29,2015 Tag Data -Cabinet Unit Heaters (Qty: 2) Item Tag(s) Qty Description Model Number D1 ECH-1, 2 Unit Cabinet Heater FFBB0403B--B0C10AN00075002000H0000000000 ECH-2 (Force-Flo) 0000 Product Data-Cabinet Unit Heaters Item: D1 Qty: 2 Tag(s): ECH-1, ECH-2 Force-Flo cabinet heater Vertical cabinet Size 040 277v/60hz/1 ph W/o piping, left hand connection, without aux drain pan Front bar grille return Front stamped louver supply Color to be selected from Trane Standard Colors by the Architect Free discharge fan motor Electric heat only, max kW, 1 stage 7.5 KW(5.7KW 208V)electric heat 1" MERV 8 filter None: valve wiring/controls not provided CS T-Stat Interface NOT INCLUDED: - Any controls wiring not listed - Wiring - Vibration isolation for indoor air handlers - Condensate pumps - Auxiliary drainpan float switch - Outside air dampers/actuators and any associated wiring - Insulation - Disconnects/circuit breakers - Fan interlocks - Additional filters/belts/sheaves - Refrigerant specialties/piping/line sets - Smoke detectors, remote test stations, annunciator panels - Owner training/maintenance - Extended warranties not specifically listed above - Startup - NEC 2011 requirements - Any other items not listed in unit detail Performance Data -Cabinet Unit Heaters Tags ECH-1, ECH-2 Design airflow(cfm) 318 Total heating capacity(MBh) 25.61 Heating LAT(F) 73.60 ESP (in H2O) 0.000 Motor speed High Motor rpm#1 (rpm) 1089 Motor hp#1 (hp) 0.240 Motor rpm#2 (rpm) 0 Motor hp#2 (hp) 0.000 Min circuit ampacity (A) 35.84 • Max fuse size (A) 40.00 Motor power(W) 58.0 Acoustics report Standard data FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 65 of 74 Installed by Others IFly Portland OR January 29,2015 Tags ECH-1, ECH-2 Unit length (in) 38.250 Unit width (in) 9.875 Unit height(in) 25.188 Shipping weight(Ib) 112.0 Operating weight(Ib) 125.0 • FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 66 of 74 Installed by Others •• IFly Portland OR January 29,2015 Mechanical Specifications-Cabinet Unit Heaters Item: D1 Qty: 2 Tag(s): ECH-1, ECH-2 Agency Certification All standard units are UL and CUL labeled and approved. Vertical Cabinet Basic Construction The basic unit includes a chassis, coil, fan(s)and fan casing(s), fan board and motor(s). The fan board assembly includes a quick disconnect motor plug. The chassis is the structural frame constructed of 18 gauge galvanized steel. The unit is acoustically insulated with closed cell insulation. The front panel is fabricated from 16 gauge galvanized steel. All other panels are fabricated from 18 gauge galvanized steel. All cabinets are made rigid by channel forming. Side panels are removable for piping access. The hinged access door is flush with the unit. Unit Finish All cabinet parts are cleaned, bonderized, phosphatized, and painted with one of six decorator colors. Standard finish meets ASTM B117 specifications (salt spray test). Fan The galvanized steel fan wheels are centrifugal forward-curved and double-width. Fan wheels and housings are corrosion resistant. Fan housings are constructed of formed sheet metal. Electronically Commutated Motors (ECM) All motors are brushless DC (BLDC)electronically commutated motors(ECM)factory programmed and run tested in assembled units. The motor controller is mounted in a control box with a built in integrated user interface and LED tachometer. If adjustments are needed, motor parameters can be adjusted through momentary contact switches accessible without factory service personnel on the motor control board. Motors will soft ramp between speeds to lessen the acoustics due to sudden speed changes. Motors can be operated at three speeds or at variable speed with factory supplied or field supplied controllers. The motor will choose the highest speed if there are simultaneous or conflicting speed requests.All motors have integral overload protection with a maximum ambient operating temperature of 104.0 F and use permanently sealed ball bearings. Motors can operate at plus or minus 10 percent of rated voltage on all speed settings. Electric Coil -(LH) An electric heating coil with a left hand coil connection is provided (right hand control box connection). Electric Heat Coil -Single Stage A single stage electric heating coil is provided as the total source of heat. Electric heat coils are open-wire type. The coils are a nickel chromium element design.The electric heat operates at the same voltage as the unit, and only a single power connection is necessary. All units with factory mounted electric heat are UL listed and interlocked with the fan motor switch.A call for Electric heat operation will turn the fan on. Motors controls are synchronized with fan/valve operation to ensure safe operation and that two modes of heat are not operating simultaneously. A transformer is supplied on any voltage unit, eliminating the need for field installation of a step-down transformer. Unit-mounted quiet magnetic relays are supplied on all voltages. A line-break high temperature cutout with automatic reset is provided as an integral part of the elements to de-energize the electric heat in the event of a malfunction. Safety Features All standard electric heat coils are UL and CUL approved and are interlocked with the fan motor switch. Therefore, electric heat operation is possible only when the fan is running.A transformer is supplied on any voltage unit, eliminating the need for field installation of a step-down transformer.A unit-mounted magnetic contactor is supplied on all voltages. A high temperature cutout with automatic reset is provided as an integral part of the elements to de-energize electric heat in the event of an overheat condition. CSTI -Thermostat Interface The control interface is intended to be used with a field-supplied, low-voltage thermostat or controller. The control box contains a relay board which includes a line voltage to 24-volt transformer; quiet contactors(for electric heat units); and an optional disconnect switch. All end devices are wired to a low voltage terminal block and run tested, so the only a power connection and thermostat connection is needed to commission the unit. Changeover sensors and controls are provided whenever a change over coil is selected. When NO valves are selected, inverting relays are provided for use with standard thermostats. FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 67 of 74 Installed by Others IFly Portland OR January 29,2015 End Pockets Standard end pockets are provided. 1" MERV 8 Filter The filter is concealed from sight and easily removable. A 1" MERV 8 filter is provided in the unit. The MERV 8 filters have a rating based on ASHRAE Standard 52.2.The average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with ASHRAE 52.1 atmospheric dust spot method. • FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 68 of 74 Installed by Others IFly Portland OR January 29,2015 Unit Dimensions -Cabinet Unit Heaters Item: D1 Qty: 2 Tag(s): ECH-1, ECH-2 NOTES: WEIGHT 1.ARROW(S)INDICATE THE DIRECTION OF AIRFLOW. 125.0 lb 2.FILTERS ARE ACCESSED THROUGH THE FRONT OF UNIT. 34111111b0.8 1/4" 3.CONTROL WIRES SHOULD ENTER CONTROL BOX THROUGH �� TOP FRONT KNOCKOUT. 4.POWER WIRES ARE TO 144JO A • 11111 (4)5/8"HANGER HOLES 26 5/16" ENTER CONTROL BOX THROUGH FRONT BOTTOM CONDUIT ENTRANCE KNOCKOUTS. 15 1/2" 25 3/16" 24 5/16" /' ISO1 VIEW BACK VIEW 4r3-9 7/6"---1 mum>. BOTTOM VIEW LEFT VIEW RIGHT VIEW FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 69 of 74 Installed by Others IFly Portland OR January 29,2015 • Unit Dimensions -Cabinet Unit Heaters Item: D1 Qty: 2 Tag(s): ECH-1, ECH-2 • FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 70 of 74 Installed by Others a IFly Portland OR January 29,2015 Unit Dimensions-Cabinet Unit Heaters • Item: D1 Qty: 2 Tag(s): ECH-1, ECH-2 BOTTOM VIEW TOP VIEW IztoR ���--- -''ii-''II 6 S/a' -.- MIT LEVELING DEVICES 8 S!13" � 3/32`KD lva"KO POWER (4) LI [I (OPTIONAL) r TTM 7/8'KO BERTON i BKM a , 2- F---i. I II 6 I/4'�I g 1/z• � �� � } .gfi !E7 UNIT � Alf �i TOP OUTLET OtkADRtFUSEA I 1 3/8` 1-�`�I TOP II OR OAR GRILLE I 2 7/a� IIII2 5/9' I C D C—/.-1 DETAIL "A" DETAIL "B" ELECTRIC HEAT ONLY NDN ELECTRIC VET ONLY r6"--.... a 6.--.- 7 FRONT VIEW (4j 5!8"DIA KEYSLOT (2) b/a"BOLT HOLES SIDE FR PIPING 14ANOER HOLES VIEW rR 7/8"--1 lEz 1 5/8" ( EkJUNCTION �„I' is i `,� NON EH°N-Y) , commix. 1 < /Ac. "CILIARYFRONT OUREr LOUVERS CTRL BOX-1\I 1 (OPTIONAL) 11 \`�",FLOW (ELECTRIC ii � HEAT ONLY) X' ,, - 1•-3 1/2' 2'-1 3/16' „ i t 1 i) 1 \--1 1 i1 f I=_____ - - 11i 6 15/16' 1 -- 6 11/16' i FR011T RLET i i 15 1/16' I I` I I OPEN OR BAR GRLLE I I Ili SEE OCTNL-d .MB' FOR FIELD POWER ...--70—... E Lr_... CONNECTIONS A e" F OPTIONAL EXTENDED EMD POCKET FRONT VIEW LH PIPING 77/6'Ro 5NR 200-300 40D 60D 1300 1000-1200 WING COIL CONNECTIONS I NO.OF 1 1 2 2 3 i FANSr— n , INC.OF I+.——'=1——I, '" INDTORSI 1 1 1 1 2 ',==1=I— E A 2'-11 5/16" S'-2 5/1 b' 3'-I1 SSj/6' 4'-e 5/ib" 6'-S S{16' I" , 1/9• t - CONTROL �X - B 1'-9 6/16' 2'-2 S/16" 2'-11 13/16- 3'-B 5/16 S'-3 S/i6" • C 7 5/8' 7 1/8' 8 T{8' 7 1/8' 7 5/8' FLYERS IBJ ' I I I ,��, i E 1'-7 5/16" 2'-0 5/16" 2'-9 13/16' 3'-6 5/16" 5'-1 5/16' ' ------ ____ ------_—�_- I ! F S-5 5/16' 3'-10 5/16' 4'-7 13/16' 5'-4 5/16' 8'-11 5/16' ii NOTE: L_— i I 1 i I.COL CONNECTIONS ME ALWAYS OPPOSITE Tl€CONTROL BOX SIDE. JUNCTION BOX(NON EH ONLY) 2.COL SECTIONS ARE 5/8'0.D.SYIEAT.SEE PAGES XXXXX FOR XLLI AUARY CONTROL BOX (EH ONLY) 3.SOEEE PAGES XXXXXX FOR DIMENSIONS FOR OUTSIDE AIR OPENINGS, FW=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 71 of 74 Installed by Others NOTES: POWER WIRING a CD �_ - S.r 1.ALL FIELD WIRING MUST BE IN ACCORDANCE a) WITH THE NATIONAL ELECTRIC CODE(NEC), 3 C. II 277V180/1 STATE AND LOCAL REQUIREMENTS. 0 0,TILINE VOLTAGE v a a L N 2.DASHED LINES INDICATE RECOMMENDED FIELD 3. D `� I I WIRING BY OTHERS.DASHED LINE ENCLOSURES Q 7 a 0 AND/OR DASHED DEVICE OUTLINES INDICATE �F� St 0 COMPONENTS PROVIDED BY THE FIELD.SOLID AG E 0 y I I 0. I LINES INDICATE WIRING BY TRANE COMPANY. N AV`c y 3.ALL FIELD POWER AND CONTROL WIRING Q 0 I I — SHOULD HAVE AN INSULATION RATING GREATER -I CD SPLICE THAN OR EQUAL TO THE UNIT VOLTAGE RATING. 0 L LUG I LUG (GRN) 4.LINE VOLTAGE CONNECTIONS ARE TO BE (11 SPLICED TO WIRES OR CONNECTED TO TERMINAL n B'* BLOCK INSIDE OF UNIT CONTROL BOX. Ill n2 Cl. (BK) 10,1) 5.WARNING:CUSTOMER CONTROLLER MUST NOT I CD Obi ALLOW ELECTRIC HEAT ACTUATION WITHOUT THE �a D ep FAN BEING ENERGIZED. - CD al ATTACH M a Z GROUND \ I MAIN POWER E N TERMINAL BLOCK m -0 S. 13 NMCA:35.84 A 7 MFS:40.00 A COC 3 NOTICE ®WARNING ff CONTROL WIRING USE COPPER CONDUCTORS ONLY! HAZARDOUS VOLTAGE! POWER UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT O6CO LNG MIN RDISCELEGIANNECIS INCLUDING DI OUT AND TAG PROCEDURES AND OTHER TYPES OF CONDUCTORS. BEFORE LERVIDI ANSURE PROF.,- FAILURE TO DOTHE ABOVE COULD RESULT IN BBQ SERVCIND'BNB ISATA1 EQUIPMENT DAMAGE STORED CAPAOTOAS NAVE DISCHARGED OREE. STD VOLTAGLAM AIM VARIABLE SPEED DRIVE.REFER TO DRIVE CONTROLLER INSTRUCTIONS FCR CAPACITOR GSCIMRGE 24VAC 15VA MAX. TERMINATION BOARD N'UTIUSER DUE DES CONDUCTEURS EN CUIVREI SE ABOVE CR r LES BORNES DE L'UNITE NE SORT PAS CONVUES SERIOUS INJURYPOUR RECEVOIR DAUTREB TYPES DE CONDUCTEURS. eAVERTISSEMENT FAIRE DEFAUT A LA PROCEDURE CI-DESSUS PEUT 24VAC 0-1 —0 1183-1 ENTRAINER DES DOMAAGES A L'EGUIPEMENT. TENSION DANGEREUSE! ^ I AVISO COLIMA TOURS LES TENSIONS ET OUVCOMM o--I —0 1TB3-2 PLR SUlE3 5ES PRCEURS A DRTNNCE. IUTIUCE UMCAMENTE CONDUCTORES DE COBREI Pus OINJ IEE ET DES IE VER SlOANE IR pRoc EmssTTEs AVANT LAS TERMNALES DE LA UNLOAD NO ESTAN DISERADAS TOMEME(NENDONVERIFIER CUE 5055 LES CODENSAIEURS DES MDTEURS SORT FAN HIGH 0— —0178PARA OTROS TWOS DE CONDUCTORES.3-3 DEaoocts.5050 LE us Durres NOSEGUM LAS INSTRUCCIONES ANTERIORES PUEDE CO.PEFNIANTOES EtlTR/JIHAENTS A UX FAN MEDIUM 07 —0 1783.4 PROVOCAR MROS EN EL EOUIPO. INVERSE IONSVARAE LR RAREMREPORTENT PO INSTRUCTIONS ONCENINBAENTPOUR DECHNROER LES CO CENSATEUIS. NE PAS RESPECTER CIES MESURES DE FAN LOW 0--I —0 1TB3-5 PRECAUTON PEUTENDWNER DES BLESSLRES GRAVES POAANT ETRE MORIELLES. I ®ADVERTENCIA I iVOLTAIE PELIGROSO! DESCOIECTE TOM LA DEBRA ELECTRIC.. L FCLUSO LAS DESGGEIOaES REMOVE Y 0 13 ELEC HEAT 0--I —0 1183-10 SRA LOB PRSCRDMENTOS RE CEPRE Y 7 ETISANTES TES DE PROCEOER AL C I SERVICD.ASEBUESE OE ME MOOSLLT VSP 10V l l--N —01784-1 LOS COPOCTTORES DEL MOTOR MYAN Q _ I OESCMOAOO EL VOLTAM ALAACENADO. V VSPO-10V /0-1 —01TB4-2 PARA LASLMOAOES CONEE DE N N I CONS CCIONLAS IN9�IRU COIEEOAD SP Mu 0 VSP DC COM —017134-3 DUCARGA DEL COTDENSACOR. N-4. I_ _I EL NO IVALIZAR LOANTEICORMIENTE O y ICCAIO PLN OCASSIaAR LA MUERTE 4. OSEAAS LESIEFES PERSONALES. 01 IFly Portland OR January 29,2015 Field Installed Options -Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. • Product Family-Air-Cooled Helical Rotary Water Chillers Item Tag(s) Qty Description Model Number Al CH-1 1 Air-Cooled Series R(TM) RTAC170 Field Installed Option Description Part/Ordering Number Elastomeric isolators Product Family-Split System Air Conditioning Units (Small) Item Tag(s) Qty Description Model Number B1 AHU/CU1-1 1 5 Ton Unitary Split Systems 4TTA3060D3000-T AM4A000OS-1 S-O- --000-0--0 B3 AHU/CU1-3 1 5 Ton Unitary Split Systems 4TTA3060D3000-T AM4AOC60S-1 S-O- ---000-0-0 B4 AHU/CU1-4 1 5 Ton Unitary Split Systems 4TTA3060D3000-T AM4A0000S-1 S-0- --000-0--0 Field Installed Option Description Part/Ordering Number Head pressure control BAYLOAM103 Programmable 7 day , 3 heat/2 cool thermostat TCONT802AS32DA Vibration Isolators BAYISLT101 Evaporator defrost control AY28X079 Crankcase heater kit BAYCCHT302 Item Tag(s) Qty Description Model Number B2 AHU/CU1-2 1 2 Ton Unitary Split Systems 4TTR3024G1000- TAM4AOA04S-1 S- 0----000-0--0 B5 AHU/CU-2-1 1 2 Ton Unitary Split Systems 4TTR3024G1000- TAM4A0000S-1 S- 0---000-0-0 B6 AHU/CU2-2 1 3 Ton Unitary Split Systems 4TTR3036E1000-T AM4AOA36S-1 S-0- ---000-0--0 B7 AHU/CU2-3 1 3 Ton Unitary Split Systems 4TTR3036E1000-T AM4A0000S-1 S-0- ---000-0--0 B8 AHU/CU2-4 1 2.5 Ton Unitary Split Systems 4TTR3030G1000- TAM4AOA30S-1 S- 0---000-0--0 Field Installed Option Description Part/Ordering Number 5.77/7.68 kW Electric Htr w/Ckt Brk for 208/240V 1 Phase 60 Hz BAYEAACO8BK1AB • Programmable 7 day , 3 heat/2 cool thermostat TCONT802AS32DA Vibration Isolators BAYISLT101 Head pressure control BAYLOAM103 Crankcase heater kit BAYCCHT302 Evaporator defrost control AY28X079 Item Tag(s) Qty Description Model Number FLD=Furnished by Trane U.S. Inc.dba Trane/ Equipment Submittal Page 73 of 74 Installed by Others IFly Portland OR January 29,2015 $ Item Tag(s) Qty Description Model Number B9 AHU/CU2-5 1 2.5 Ton Unitary Split Systems 4TTR3030G1000- TAM4A0000S-1 S- 0-000-0--0 B11 AHU/CU3-2 1 2 Ton Unitary Split Systems 4TTR3024G1000- TAM4A0A04S-1 S- 0----000-0-0 • Field Installed Option Description Part/Ordering Number 7.21/9.60 kW Electric Htr w/Ckt Brk for 208/240V 1 Phase 60 Hz BAYEAAC10BK1AB Crankcase heater kit BAYCCHT302 Programmable 7 day , 3 heat/2 cool thermostat TCONT802AS32DA Vibration Isolators BAYISLT101 Head pressure control BAYLOAM103 Evaporator defrost control AY28X079 Item Tag(s) Qty Description Model Number B10 AHU/CU3-1 1 3.5 Ton Unitary Split Systems 4TTA3042D3000-T AM4A0B02S-15-0- --000-0--0 Field Installed Option Description Part/Ordering Number Crankcase heater kit BAYCCHT301 Programmable 7 day , 3 heat/2 cool thermostat TCONT802AS32DA Vibration Isolators BAYISLT101 Head pressure control BAYLOAM103 Evaporator defrost control AY28X079 Item Tag(s) Qty Description Model Number B12 AHU/CU3-3 1 4 Ton Unitary Split Systems 4TTA3048D3000-T AM4A0000S-1 S-0- -000-0-0 Field Installed Option Description Part/Ordering Number Evaporator defrost control AY28X079 Programmable 7 day , 3 heat/2 cool thermostat TCONT802AS32DA Vibration Isolators BAYISLT101 Head pressure control BAYLOAM103 Crankcase heater kit BAYCCHT301 10.80/14.40 kW Htr w/Ckt Brk 208/240/1 BAYEABC15BK1AB Product Family-Split System Air Conditioning Units(Large) Item Tag(s) Qty Description Model Number Cl AHU/HP4-1 1 7.5 Ton Unitary Split Systems TWA090D4ORA-TWE090D300A Field Installed Option Description _Part/Ordering Number Prog. 7 day, 3 Htg/2 Clg Touchscreen TCONT802AS32DA Condenser Coil HailNandal Guard Kit BAYGARD058A Low ambient control if using hot gas bypass BAYLOAM435A Rubber-in-shear isolators BAYISLT005A FLD=Furnished by Trane U.S.Inc.dba Trane/ Equipment Submittal Page 74 of 74 Installed by Others