Loading...
Report (2) Ovv/ / TvAtTualatin Valley Fire & Rescue Tualatin Valley Fire Flow and Hydrant Worksheet Fire & Rescue North Operating Center Central Operating Center South Operating Center 20665 SW Blanton Street 11945 SW 70th Avenue 8445 SW Elligsen Road Aloha,OR 97007 Tigard,OR 97223 Wilsonville OR 97070 Phone:503-259-1400 Phone: 503-649-8577 Phone: 503-259-1500 Fax:503-259-1224 Fax: 503-642-4814 Fax: 503-259-1520 Fire Flow and Hydrant Worksheet This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction(AHJ)before any permits for new building construction, building expansion or fire hydrants will be issued by any building department within the TVF&R District. For assistance completing this form,see the Fire Flow and Hydrant Worksheet Instructions or call the Operating Center nearest you. SECTION 1 - Preparer Information a. Preparer Name: [Jim ciarkson Date: I 9/10/2014 I Phone:1503/373-3186 Fax:In/a I E-mail:I iclarksonPlivebsl.com b. Architect I Engineer of Record: Ijim Clarkson Phone:1503/373-3165 I Fax:I I E-mail:I1 jclarkson@livebsl.com SECTION 2-General Building Information a. Project Name: 1Bonaventure of Tigard Senior Living Project Address: 115000 sw hall City:Itigard I County:lwashington Zip:197217 I b. Construction Type: 1 Type IV and V-A c. Total Bldg Area: 157,224 sq ft(as defined by the OSSC) Total Fire Area: 157,224 sq ft(as defined by the OFC) Bldg Fire Flow: 7250 GPM (base amount without adjustment for occupancy hazard classification) d. Describe Fire Area:(if more than one fire area,include an 8 1/2 x 11 or 11 x 17 drawing indicating the various fire areas) bldg separated by fire wall into 2 -bldg a/b=92,476sf and bldg c=64748sf; bldg A/B includes commerical; kicteh =2000sf e. Type of Occupancy or Use of Building: lassited living - 1-1 condition 1 per 2014 ossc Page 1 Revised: October 2011 Fire Flow and Hydrant Worksheet(continued) I SECTION 3-Occupancy Hazard a. Percentage of Occupancy Hazard Classifications(see Worksheet Instructions-tables 1 and 2) Occupancy Hazard Classification Are Area Total Fire Area Percent of Fire Area Light Hazard 155224 SF / 157,224 SF x 100 = 98.73 % Ordinary Hazard Grp 1 2000 SF / 157,224 SF x 100 = 1.27 % Ordinary Hazard Grp 2(HPCS I& II) 0 SF / 157,224 SF x 100 = 0 % Extra Hazard Gm 1 (HPCS III) 0 SF / 157,224 SF x 100 = 0 % Extra Hazard Grp 2(HPCS IV&HH) 0 SF / 157,224 SF x 100 = 0 % Total must equal 100% I 100 I°% b. Calculated Fire Flow Occupancy Hazard Classification Factor Fire Area Fire Flow Bldg Fire Flow Light Hazard 0.75 x 99 % x 7250 GPM = 5368 GPM Ordinary Hazard Grp 1 0.85 x 1 °A) x 7250 GPM = 78 GPM Ordinary Hazard Grp 2 1 x 0 % x 7250 GPM = 0 GPM Extra Hazard Grp 1 1.15 x 0 % x 7250 GPM = 0 GPM Extra Hazard Grp 2 1.25 x 0 °A) x 7250 GPM = 0 GPM c. Required Fire Flow with Occupancy Hazard Adjustment I 5446 IGPM . SECTION 4-Minimum Number of Fire Hydrants Required Refer to Table C105.1 below(2010 OR Fire Code, Appendix C)for the minimum number of hydrants required. Required Fire Flow: I 5446 IGPM TABLE C105.1 NUMBER AND DISTRIBUTION OF FIRE HYDRANTS FIRE-FLOW REQUIREMENT MINIMUM NUMBER Wm) OF HYDRANTS 1.750 or less 1 2,000-2,250 2 2,500 3 3,000 3 3.500-4.000 4 I 4,500-5,000 5 5.500 6 -- 6,000 6 6,.50()-7.0()0 7 7.500 or more i 8 or more Page 2 Revised: October 2011 Fire Flow and Hydrant Worksheet(continued) SECTION 5-Reduction of Fire Flow Reduced by 75%for an approved automatic sprinkler system, installed in accordance with NFPA 13 or NFPA 13R(choose multiplier 0.25 in Section 6). SECTION 6-Required Fire Flow Fire Flow: 5446 GPM x I 0.25 I 1500 IGPM (Min.=1500,Max.=3000) SECTION 7-Available Fire Flow to the Building Manually enter available fire flow here. Please attach documentation of the flow test that was conducted. It must include date, time and location of static/residual and flow hydrants, as well as the tester's name, phone number and address. Test Results: I 9394 I GPM Page 3 Revised: October 2011