Fire Flow and Hydrant Worksheet
This worksheet is required to be submitted to and approved by the Authority Having Jurisdiction(AHJ)before any permits for
new building construction, building expansion or fire hydrants will be issued by any building department within the TVF&R
District. For assistance completing this form,see the Fire Flow and Hydrant Worksheet Instructions or call the Operating
Center nearest you.
SECTION 1 - Preparer Information
a. Preparer Name: [Jim ciarkson Date: I 9/10/2014 I
Phone:1503/373-3186 Fax:In/a I E-mail:I iclarksonPlivebsl.com
b. Architect I Engineer of Record: Ijim Clarkson
Phone:1503/373-3165 I Fax:I I E-mail:I1 jclarkson@livebsl.com
SECTION 2-General Building Information
a. Project Name: 1Bonaventure of Tigard Senior Living
Project Address: 115000 sw hall
City:Itigard I County:lwashington Zip:197217 I
b. Construction Type: 1 Type IV and V-A
c. Total Bldg Area: 157,224 sq ft(as defined by the OSSC)
Total Fire Area: 157,224 sq ft(as defined by the OFC)
Bldg Fire Flow: 7250 GPM (base amount without adjustment for occupancy hazard classification)
d. Describe Fire Area:(if more than one fire area,include an 8 1/2 x 11 or 11 x 17 drawing indicating the various fire areas)
bldg separated by fire wall into 2 -bldg a/b=92,476sf and bldg c=64748sf; bldg A/B includes commerical;
kicteh =2000sf
e. Type of Occupancy or Use of Building: lassited living - 1-1 condition 1 per 2014 ossc
Page 1 Revised: October 2011
Fire Flow and Hydrant Worksheet(continued) I
SECTION 3-Occupancy Hazard
a. Percentage of Occupancy Hazard Classifications(see Worksheet Instructions-tables 1 and 2)
Occupancy Hazard Classification Are Area Total Fire Area Percent of Fire Area
Light Hazard 155224 SF / 157,224 SF x 100 = 98.73 %
Ordinary Hazard Grp 1 2000 SF / 157,224 SF x 100 = 1.27 %
Ordinary Hazard Grp 2(HPCS I& II) 0 SF / 157,224 SF x 100 = 0 %
Extra Hazard Gm 1 (HPCS III) 0 SF / 157,224 SF x 100 = 0 %
Extra Hazard Grp 2(HPCS IV&HH) 0 SF / 157,224 SF x 100 = 0 %
Total must equal 100% I 100 I°%
b. Calculated Fire Flow
Occupancy Hazard Classification Factor Fire Area Fire Flow Bldg Fire Flow
Light Hazard 0.75 x 99 % x 7250 GPM = 5368 GPM
Ordinary Hazard Grp 1 0.85 x 1 °A) x 7250 GPM = 78 GPM
Ordinary Hazard Grp 2 1 x 0 % x 7250 GPM = 0 GPM
Extra Hazard Grp 1 1.15 x 0 % x 7250 GPM = 0 GPM
Extra Hazard Grp 2 1.25 x 0 °A) x 7250 GPM = 0 GPM
c. Required Fire Flow with Occupancy Hazard Adjustment I 5446 IGPM
. SECTION 4-Minimum Number of Fire Hydrants Required
Refer to Table C105.1 below(2010 OR Fire Code, Appendix C)for the minimum number of hydrants required.
Required Fire Flow: I 5446 IGPM
TABLE C105.1
NUMBER AND DISTRIBUTION OF FIRE HYDRANTS
FIRE-FLOW REQUIREMENT MINIMUM NUMBER
Wm) OF HYDRANTS
1.750 or less 1
2,000-2,250 2
2,500 3
3,000 3
3.500-4.000 4 I
4,500-5,000 5
5.500 6
--
6,000 6
6,.50()-7.0()0 7
7.500 or more i 8 or more
Page 2 Revised: October 2011
Fire Flow and Hydrant Worksheet(continued)
SECTION 5-Reduction of Fire Flow
Reduced by 75%for an approved automatic sprinkler system, installed in accordance with NFPA 13 or
NFPA 13R(choose multiplier 0.25 in Section 6).
SECTION 6-Required Fire Flow
Fire Flow: 5446 GPM x I 0.25 I 1500 IGPM
(Min.=1500,Max.=3000)
SECTION 7-Available Fire Flow to the Building
Manually enter available fire flow here. Please attach documentation of the flow test that was conducted. It
must include date, time and location of static/residual and flow hydrants, as well as the tester's name, phone
number and address.
Test Results: I 9394 I GPM
Page 3 Revised: October 2011