Report (20) 1-PS ?D(Z- U Iv
i, 4.1 - - i
;,.,„•',,,,,,.:;:-,;, -P..V;,. ;:-- 9.Fd:,. r I,v: , aZ. . r3K«9�Da4rs,2 � bi,_ "3,:v, Y.
BL <> ® LPCB E ® E
vepvo
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
Standard Spray; Upright, Pendent and Recessed Pendent
• MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE i
ifil
MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE
These Model V27 standard spray sprinklers are designed to produce a ,.,-;�
hemispherical spray pattern for standard commercial applications.They are '' `.
available with either standard or quick response bulbs.The design incorporates ,1 -; tti,
state-of-the-art, heat responsive,frangible glass bulb design(standard or quick
response)for prompt,precise operation. UPRIGHT PENDENT RECESSED
(V2703 AND (V2707 AND PENDENT
The die cast frame is more streamlined and attractive than traditional sand cast v2704) V27013) (V2707 AND
V2708)
frames.It is cast with a hex-shaped wrench boss to allow easy tightening from many
angles,reducing assembly effort.This sprinkler is available in various temperature
ratings(see chart on page 2)and finishes to meet many design requirements.
The recessed pendent should be utilized with a Model V27 recessed escutcheon I
which provides up to W/19mm of adjustments.
SPRINKLER OPERATION The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a
fire,the ambient temperature rises causing the liquid in the bulb to expand.When the ambient tem-
perature reaches the rated temperature of the sprinkler,the bulb shatters.As a result,the waterway
is cleared of all sealing parts and water is discharged towards the deflector.The deflector is designed
to distribute the water in a pattern that is most effective in controlling the fire.
COVERAGE For coverage area and sprinkler placement, refer to NFPA 13 standards.
TECHNICAL SPECIFICATIONS Models/S.I.N.:V2703,V2704,V2707,V2708
Style:Pendent,Upright or Recessed Pendent ACCESSORIES
® Nominal Orifice Size: 1 '/13 mm Installation Wrench:
K-Factor:5.61mp./8.1 S.I.^
• Open End:V27
Nominal Thread Size: 1/2'NPT/15mm
Max.Working Pressure: • Recessed:V27-2
175 psi/1200kPa FM Global Finishes:
i250 psi/1725kPa UL Plain brass
•
Factory Hydrostatic Test: • Chrome plated
100%®500psi/3450kPa • White painted**
• Black painted**
aMin.Operating Pressure:7psi/48 kPa • Custom painted**
1� Temperature Rating:See charts on page 2&3. • Proprietary nickel Teflon*coating**
414 I MATERIAL SPECIFICATIONS
For or cabinets and other accessories refer to
' ►�� Upright Deflector: Bronze per UNS C22000 separate sheet.
—'<`° Pendent Deflector: Bronze per UNS C51000
NOTE:Weather resistant recessed escutcheons
Bulb:Glass with glycerin solution. available upon request.
i Bulb Nominal Diameter:
• Standard: 5.0 mm A For K-Factor when pressure is measured in
I • Quick Response:3.0mm Bar, multiply S.I.units by 10.0.
Load Screw:Bronze per UNS C65100 * Teflon is a registered trademark of Dupont Co.
Pip Cap:Bronze per UNS C65100 **UL Listed for corrosion resistance in all
Spring:Beryllium nickel configurations.
Exaggerated for clarity Seal:Teflon*tape
Frame:Die cast brass 65-30
Lodgement Spring:Stainless steel per UNS
S30200
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para
• Location Date Approved
Date
www.victaulic.com -CtalJliC'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY 02012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ........,.,,w..,,,..........,,...
EA... r;0,>i.'
VTQA,1 w •
7N4.
® Oct
UST®
Dry Type Standard Spray
Pendent, Intermediate Level Pendent hit
lOr
&Recessed Pendent
V3605 STANDARD RESPONSE
V3606 QUICK RESPONSE
11 11"i
FLUSH SLEEVE AND PLAIN BARREL INTERMEDIATE EXTENDED RECESSED
SKIRT
The Model V36 Series Dry Type Pendent and Recessed Pendent Sprinklers have been redesigned
utilizing stainless steel internal components.The V36 Dry Sprinkler is used in special applications
such as freezing environments and conditions where sediment or foreign materials might accumulate
in ordinary drop nipples.
The Model V3606 and V3605 Intermediate Level Pendent sprinklers incorporate a water shield plate
to prevent water from higher level sprinklers from interfering with normal operation.These intermedi-
ate level sprinklers are designed for use in intermediate levels of rack storage or other open grate
storage arrangements,where they may be exposed to upper level or ceiling level sprinklers.
Available in either standard or quick response versions,the Model V36 Dry Type Pendent Sprinkler
utilizes a frangible glass bulb.At the bulb's rated temperature,the sprinkler opens releasing the bulb
seat assembly,causing the inner tube assembly to move,allowing the spring assembly to pivot along-
side the inner tube.At this time,water flows through the sprinkler and is distributed by the deflector,
in an approved discharge pattern.
The heart of the Model V36 sprinkler's proven actuating assembly is a hermetically sealed frangible
glass bulb that contains a precisely measured amount of fluid.When heat is absorbed,the liquid
within the bulb expands increasing the internal pressure.At the prescribed temperature the internal
pressure within the bulb exceeds the strength of the glass causing the glass to shatter.This results in
water discharge which is distributed in an approved pattern.
COVERAGE: For coverage area and sprinkler placement, refer to NFPA 13 standards.
JOB OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para
• Location Date Approved
Date
www.victaulic.com
VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ictaulia
_ Fire Protection by Computer Design
Crossfire Sprinkler Company
17400 SE 82nd Drive
Clackamas, Oregon 97015
503 210 5506
Job Name : FM TIGARD NEW GARDEN CANOPY
Building :
Location :
System :
Contract :
Data File : FM-Tigar.WX1
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C) .
Crossfire Sprinkler Company Page 1
FM TIGARD NEW GARDEN CANOPY Date 042612
City Water Supply: Demand:
Cl - Static Pressure 84 D1 - Elevation 6.930
C2 - Residual Pressure 79 D2 - System Flow 804.408
C2 - Residual Flow 1280 D2 - System Pressure 65.396
Hose (Adj City )
Hose Demand )
D3- System Demand 804.408
Safety Margin 16.487
150
140
130
p 120
R110
E 100
S 90 c1
G C2
S 80 - .
U 70 D2
R 60
E 50
40
30
20
10
�,,..4� I.... . .. . . . . . . , . . . . , . . . . . . . . I - . . . . . . , . . . . . . . . . - - - -
200 400 600 800 1000 1200 1400 1600 1800
FLOW( NA1.85 )
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
Crossfire Sprinkler Company Page 2
FM TIGARD NEW GARDEN CANOPY Date 042612
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
52 16.0 5.6 25.4 na 28.22 0.2 130 21.6
53 16.0 5.6 25.48 na 28.27 0.2 130 21.6
54 16.0 5.6 25.74 na 28.41 0.2 130 21.6
55 16.0 5.6 26.31 na 28.72 0.2 130 21.6
56 16.0 5.6 27.27 na 29.24 0.2 130 21.6
57 16.0 5.6 28.75 na 30.03 0.2 130 21.6
58 16.0 5.6 30.85 na 31.1 0.2 130 21.6
59 16.0 30.99 na
48 16.0 5.6 37.81 na 34.43 0.2 130 21.6
49 16.0 5.6 37.91 na 34.48 0.2 130 21.6
50 16.0 5.6 38.3 na 34.66 0.2 130 21.6
51 16.0 38.34 na
32 16.0 5.6 21.6 na 26.03 0.2 130 21.6
33 16.0 21.6 na
34 16.0 5.6 21.65 na 26.06 0.2 130 21.6
35 16.0 5.6 21.83 na 26.17 0.2 130 21.6
36 16.0 5.6 22.22 na 26.4 0.2 130 21.6
37 16.0 5.6 22.89 na 26.79 0.2 130 21.6
38 16.0 5.6 23.9 na 27.38 0.2 130 21.6
39 16.0 5.6 25.34 na 28.19 0.2 130 21.6
40 16.0 5.6 27.28 na 29.25 0.2 130 21.6
41 16.0 5.6 29.83 na 30.58 0.2 130 21.6
42 16.0 30.03 na
43 16.0 39.78 na
44 16.0 39.95 na
45 16.0 40.49 na
46 16.0 42.74 na
47 16.0 51.62 na
2 0.0 58.86 na
1 0.0 64.09 na
TEST 0.0 65.4 na 250.0
The maximum velocity is 23.6 and it occurs in the pipe between nodes 42 and 43
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
•
Final Calculations - Hazen-Williams
Crossfire Sprinkler Company Page 3
FM TIGARD NEW GARDEN CANOPY Date 042612
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
*P-6
52 28.22 2.157 0.0 10.000 25.402 K Factor = 5.60
to 120 0.0 0.0 0.0
53 28.22 0.0074 0.0 10.000 0.074 Vel = 2.48
53 28.27 2.157 0.0 10.000 25.476 K Factor = 5.60
to 120 0.0 0.0 0.0
54 56.49 0.0265 0.0 10.000 0.265 Vel = 4.96
54 28.41 2.157 0.0 10.000 25.741 K Factor = 5.60
to 120 0.0 0.0 0.0
55 84.9 0.0564 0.0 10.000 0.564 Vel = 7.45
55 28.72 2.157 0.0 10.000 26.305 K Factor= 5.60
to 120 0.0 0.0 0.0
56 113.62 0.0967 0.0 10.000 0.967 Vel = 9.98
56 29.25 2.157 0.0 10.000 27.272 K Factor = 5.60
to 120 0.0 0.0 0.0
57 142.87 0.1478 0.0 10.000 1.478 Vel = 12.54
57 30.03 2.157 0.0 10.000 28.750 K Factor= 5.60
to 120 0.0 0.0 0.0
58 172.9 0.2102 0.0 10.000 2.102 Vel = 15.18
58 31.10 2.157 0.0 0.500 30.852 K Factor = 5.60
to- 120 0.0 0.0 0.0
59 204.0 0.2860 0.0 0.500 0.143 Vel = 17.91
59 0.0 2.067 1E 5.0 10.500 30.995
to 120 1T 10.0 15.000 0.0
44 204.0 0.3513 0.0 25.500 8.959 Vel = 19.50
0.0
204.00 39.954 K Factor= 32.27
*P-9
48 34.43 2.157 0.0 10.000 37.808 K Factor = 5.60
to 120 0.0 0.0 0.0
49 34.43 0.0107 0.0 10.000 0.107 Vel = 3.02
49 34.49 2.157 0.0 10.000 37.915 K Factor = 5.60
to 120 0.0 0.0 0.0
50 68.92 0.0383 0.0 10.000 0.383 Vel = 6.05
50 34.65 2.157 0.0 0.500 38.298 K Factor = 5.60
to 120 0.0 0.0 0.0
51 103.57 0.0820 0.0 0.500 0.041 Vel = 9.09
51 0.0 2.067 1E 5.0 6.500 38.339
t6 120 1T 10.0 15.000 0.0
45 103.57 0.1003 0.0 21.500 2.156 Vel = 9.90
0.0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
.
•
Final Calculations - Standard
Crossfire Sprinkler Company Page 4
FM TIGARD NEW GARDEN CANOPY Date 042612
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
103.57 40.495 K Factor= 16.28
*P-12
32 26.03 2.067 0.0 0.500 21.600 K Factor = 5.60
to 120 0.0 0.0 0.0
33 26.03 0.0080 0.0 0.500 0.004 Vel = 2.49
33 0.0 2.157 0.0 7.500 21.604
to 120 0.0 0.0 0.0
34 26.03 0.0063 0.0 7.500 0.047 Vel = 2.29
34 26.05 2.157 0.0 8.000 21.651 K Factor= 5.60
to 120 0.0 0.0 0.0
35 52.08 0.0229 0.0 8.000 0.183 Vel = 4.57
35 26.17 2.157 0.0 8.000 21.834 K Factor= 5.60
to 120 0.0 0.0 0.0
36 78.25 0.0485 0.0 8.000 0.388 Vel = 6.87
36 26.40 2.157 0.0 8.000 22.222 K Factor= 5.60
to 120 0.0 0.0 0.0
37 104.65 0.0830 0.0 8.000 0.664 Vel = 9.19
37 26.79 2.157 0.0 8.000 22.886 K Factor = 5.60
to 120 0.0 0.0 0.0
38 131.44 0.1266 0.0 8.000 1.013 Vel = 11.54
38 27.38 2.157 0.0 8.000 23.899 K Factor= 5.60
to 120 0.0 0.0 0.0
39 158.82 0.1798 0.0 8.000 1.438 Vel = 13.94
39 28.18 2.157 0.0 8.000 25.337 K Factor = 5.60
to 120 0.0 0.0 0.0
40 187.0 0.2430 0.0 8.000 1.944 Vel = 16.42
40 29.25 2.157 0.0 8.000 27.281 K Factor = 5.60
to 120 0.0 0.0 0.0
41 216.25 0.3181 0.0 8.000 2.545 Vel = 18.99
41 30.59 2.157 0.0 0.500 29.826 K Factor= 5.60
to 120 0.0 0.0 0.0
42 246.84 0.4060 0.0 0.500 0.203 Vel = 21.67
42 0.0 2.067 1E 5.0 4.500 30.029
to 120 1T 10.0 15.000 0.0
43 246.84 0.4999 0.0 19.500 9.748 Vel = 23.60
43 0.0 4.26 0.0 12.000 39.777
to 120 0.0 0.0 0.0
44 246.84 0.0148 0.0 12.000 0.177 Vel = 5.56
44 204.00 4.26 0.0 12.000 39.954
to 120 0.0 0.0 0.0
45 450.84 0.0451 0.0 12.000 0.541 Vel = 10.15
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Standard
Crossfire Sprinkler Company Page 5
FM TIGARD NEW GARDEN CANOPY Date 042612
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
45 103.57 4.26 1T 26.334 7.660 40.495
to 120 0.0 26.334 0.0
46 554.41 0.0660 0.0 33.994 2.243 Vel = 12.48
46 0.0 4.26 4E 52.668 81.870 42.738
to 120 0.0 52.668 0.0
47 554.41 0.0660 0.0 134.538 8.879 Vel = 12.48
47 0.0 8.27 0.0 120.160 51.617
to 120 0.0 0.0 6.930
2 554.41 0.0026 0.0 120.160 0.313 Vel = 3.31
2 0.0 8.27 1E4378.279 5.000 58.860
to 120 0.0 2000.000 0.0
1 554.41 0.0026 0.0 2005.000 5.231 Vel = 3.31
1 0.0 8.27 0.0 500.000 64.091
to 120 0.0 0.0 0.0
TEST 554.41 0.0026 0.0 500.000 1.305 Vel = 3.31
250.00 Qa = 250.00
804.41 65.396 K Factor = 99.47
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087