Specifications Project Design Criteria Design per 2009 International Building Code as revised by the State of Oregon. Provide vertical and lateral analysis of freestanding indoor cooler/freezer combo box structure constructed using a panelized system. Concrete foundation to be designed by others for loads designated on drawings. a) Floor live load: N/A b) Roof Live Load: 10 psf c) Roof Snow Load: N/A d) Wind Design: N/A e) Earthquake Design: Ie = 1.0 Occupancy Category = II Ss = .936; S1 = .338 Site Class =D Sds = .71 Sdl = .39 Seismic Design Category =D Force resisting system= Light framed shearwalls Base Shear= .109*W Cs = .109 R= 6.5 Procedure =Equivalent Lateral Force Procedure ASCE-05 Section 12.8 1 L\2r1% 2 t` � Y 4T 307/s8 IT" wN1bs 7 } w,s m W13 4w2 ... vin y —� COOLER / �(� Z e f ? FREEZER w = m s i / ( ,' vn r`;' /t / — 22 5/10 —47 00 l� 1� } �• `,, r J \ o.H. Wei WALL 5(;;r-ytc- ✓cL Project Name St. Anthony Catholic Church 013-CD-58965) Project# 13-148 LTA Location 9905 SW McKenzie St., Tigard, Oregon LAUREN THOMAS CONSULTNG.LIC Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8/13 Page 1 of L tatruc tural®gma il.com Calculation for Seismic Forces, using Analysis per ASCE 7-05 (For Buildings, per section 12.8, "Equivalent Lateral Force procedure") Spectral Response Accelerations: (from maps) Ss= 0.936 0.2 sec. S1 = 0.338 1.0 sec Determine Site Coefficients: (from Table 11.4-1 and 2) Fa= 1.1256 F„= 1.724 Sms= SS X Fa = 1.054 Sm1 = S1 x Fv= 0.583 Sps = (2/3) Sm5= 0.71 SD1 = (2/3) Smi 0.39 Site Class: D (Use Site Class D unless Geotech Report available) Occupancy Category: II (From Table IBC table 1604.5) Seismic Design Category (SDC): D (From Tables 11.6-1 and 2) Compute Approximate Fundamental Period: For Buildings: Ta= (CO (h„)x Ct= 0.02 hn = 8.83 x= 0.75 Ta = 0.102 Structure Type(from Table 9.5.5.3.2) C, x Steel Moment-resisting Frame 0.028 0.8 Reinf.Conc.Moment-resisting Frame 0.016 0.9 Eccent. Braced Steel Frame 0.03 0.75 All other structural systems 0.02 0.75 To= 0.2SD1/SDs= 0.111 If Ta > To, < T0, Use Sps for design Ts = SD1/SDs= 0.553 T�= 16.00 per Fig 22-15 Calculate Base Shear: V= Cs W (Eq. 12.8-1) Response Coef. R = 6.5 (From Table 12.2-1) Structure Weight W= 1798 lbs Importance Factor I = 1.0 Cs = Sps/(R/I) = 0.109 (Eq. 12.8-2) V= Cs W= 0.109 W= 195 lbs \;-3— 2 V�I (Eq. 12.8-1) V= SD1/T(R/I) = 0.586 W(Max.)= 1054 lbs (Eq. 12.8-3) V= .01 W= 0.010 W(Min.)= 18 lbs (Eq. 12.8-6) Uf' ,2 ( r , s ) t ,10 ' Project Name St. Anthony Catholic Church (#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN THOMIAS CONSUL7NG.uc Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 501317-1023 By LMT Date 11/8//13 Page 2_ of Ltcstruc rural@gmaiLcom 4 ( )(1(0 .ro ( —)‘2-) )[cz>(\kk,,z_ c . )(--7 — • \/V 2 \ yJ kz \—r 11 \<r 2 Z� Z� � 2r> 4t 1?-11 222 (2_��C (� .� 1 2 �( 2 5� o rz)c---? r, _ (4) --4 ( : �c ,ti (C0)( -1 ) (4)(3_ )( 0(-7 ) Project Name St. Anthony Catholic Church (#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon L UREN TMonws CON501714G,lLc Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8//13 Page 3 of Licstr uc t u ra l(a�g mail ca m r i (2_ 2, c L\--\`'-'\ - As; 4e — 7 z(0444--r .e to di__ 1(0 - r ,) -2 5,1 0 II ( 'k) L' ' v v 4 Imo (---F• 1t 22 : It\ O� 31 -7 ---C 5e r: tom . 5-.N\0, - 53 L 7 L c 4t, ' ( • ., If ,--+--- -i, 1l 1 (6c) *-Z `-' ' . ) is i =! /r Project Name St. Anthony Catholic Church (#13-CD-58965) Project# 13-148 1 T LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN 1 NOMAS CON LING LLC Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8//13 Page4—of Ltcstructural@gmail.com J $PT-'5E 0 r, fitw) .....„,.... _ Ai- I e --- -r . . \,......_ ---- _ .... - 7 7 . , /.7/,,./.., - , pt_i- cur- l 0 ic ikNr ) F-70\.--e\--- 0 -- cv)- (... ( C ..., 1 u C:5) -' — '' • . t' '''\.• ,. (\ Project Name St. Anthony Catholic Church (#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN THORNS CONSULTING LIG Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 Ltcstructural@gmail.com By LMT Date 11/8//13 Page 5' of Anchor Calculations Anchor Selector (Version 4.12.0.0) • Job Name : St, Anthony Catholic Church Date/Time : 11/8/2013 3:48:27 PM 1) Input Calculation Method : ACI 318 Appendix D For Cracked Concrete Code : ACI 318-05 Calculation Type : Analysis Code Report : ICC-ES ESR-2713 a) Layout Anchor : 3/8" Titen HD Number of Anchors : 1 Embedment Depth : 2.5 in Built-up Grout Pads : No cx1 ext t Vuay Cyt (—)MuY b � by Wuax bx cy1 1 ANCHOR *Nue IS POSITIVE FOR TENSION AND NEGATIVE FOR COMPRESSION. +INDICATES CENTER OF THE ANCHOR Anchor Layout Dimensions : cxl : 6in ext : 60 in cy1 : 6in Project Name St. Anthony Catholic Church(#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN THOMAS CONSULTING tic Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 Ltcstructara @gmaitcom By LMT Date 11/8//13 Page of cy2 : 6 in bx� : 1.5in bx2 : 1.5 in by1 : 1.5 in bye : 1.5 in b) Base Material Concrete :Normal weight f : 2500.0 psi Cracked Concrete : Yes To, : 1.00 Condition : B tension and shear 4 Fp : 1381.3 psi Thickness, ha : 4.25 in Supplementary edge reinforcement :No c) Factored Loads Load factor source : ACI 318 Appendix C Nua : 0 lb Vaax : 0 lb Vuay : 150 lb Mux : 0 lb*ft May : 0 lb*ft ex : 0in e : 0in Moderate/high seismic risk or intermediate/high design category : Yes Apply entire shear load at front row for breakout : No d) Anchor Parameters From ICC-ES ESR-2713 • Anchor Model = THD37 do=0.375 in Category= 1 hef= 1.77 in hm;n =4.25 in cac =2.6875 in Cm111 = 1.75 in sum,= 3 in Ductile=No 2) Tension Force on Each Individual Anchor Project Name St. Anthony Catholic Church (#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN THCMAS ComuiTMfluc Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 S03-317-1023 By LMT Date 11/8//13 Page 7 of L tc s l r u c l u ra l@g m a i 1.c o m Anchor#1 N ual = 0.00 lb Sum of Anchor Tension ENua= 0.00 lb aX = 0.00in ay= 0.00 in e'NX= 0.00 in e'Ny = 0.00 in 3) Shear Force on Each Individual Anchor Resultant shear forces in each anchor: Anchor #1 V ual = 150.00 lb (V uaix= 0.00 lb , V ualy= 150.00 lb ) Sum of Anchor Shear EVuaX=0.00 lb, EVuay= 150.00 lb e'vX= 0.00 in e'vy= 0.00 in 4) Steel Strength of Anchor in Tension [Sec. D.5.1] Nsa=nA se futa [Eq. D-3] Number of anchors acting in tension,n=0 Nsa= 10890 lb (for a single anchor) [ ICC-ES ESR-2713 ] = 0.70 [D.4.5] ONsa= 7623.00 lb (for a single anchor) 5) Concrete Breakout Strength of Anchor in Tension [Sec. D.5.2] Ncb=ANc/ANco'Ped,N'Fc,Nfcp,NNb [Eq. D-4] Number of influencing edges = 0 hef= 1.77 in ANco= 28.20 in2 [Eq. D-6] ANc = 28.20 in2 Smallest edge distance, ca,m;fl= 6.00 in `I'ed,N = 1.0000 [Eq. D-10 or D-11] Note: Cracking shall be controlled per D.5.2.6 Tc,N = 1.0000 [Sec. D.5.2.6] LI'cp,N = 1.0000 [Eq. D-12 or D-13] Project Name St. Anthony Catholic Church 0113-CD-58965) Project # 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN Toorroa co1TMe, « Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8//13 Page of L tcstr uc t u ra IQg mail.com • Nb = f' c hef''s = 2001.61 lb [Eq. D-7] kc = 17 [Sec. D.5.2.6] Ncb = 2001.61 lb [Eq. D-4] ( = 0.75 [D.4.5] 4)seis = 0.75 ONcb = 1125.90 lb (for a single anchor) 6) Pullout Strength of Anchor in Tension [Sec. D.5.3] Neq = 12351b (fe/2,500 psi)0'5 = 1235.00 lb = 0.75 4)seis = 0.75 4)Neq = 694.69 lb (for a single anchor) 7) Side Face Blowout of Anchor in Tension [Sec. D.5.4] Concrete side face blowout strength is only calculated for headed anchors in tension close to an edge, cal < 0.4hef.Not applicable in this case. 8) Steel Strength of Anchor in Shear [Sec D.6.1] Veq = 2855.00 lb (for a single anchor) [ ICC-ES ESR-2713 ] = 0.65 [D.4.5] Veq = 1855.75 lb (for a single anchor) 9) Concrete Breakout Strength of Anchor in Shear [Sec D.6.2] Case 1: Anchor checked against total shear load In x-direction... Vcbx =Avcx/AvcoxVed,V'Pc,V Vbx [Eq. D-21] cal = 4.00 in (adjusted for edges per D.6.2.4) Avcx = 51.00 in2 Avcox = 72.00 in2 [Eq. D-23] 'fay = 1.0000 [Eq. D-27 or D-28] Project Name St. Anthony Catholic Church (#13-CD-58965) Project# 13-148 • LTC Location 9905 SW McKenzie St., Tigard, Oregon Uu0.EN THO'S con�LTMG,uc Client Imperial Brown 10372 SW Booaoza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8//13 Page 9 of L tcstru ct u ral(a�gmaiL com Tey = 1.0000 [Sec. D.6.2.7] Vbx = 7(le/do )°.2.4 dok fc(cai)' 5 [Eq. D-24] le= 1.77 in Vbx = 2338.63 lb Vcbx= 1656.53 lb [Eq. D-21] = 0.75 4)seis = 0.75 Vcbx = 931.80 lb (for a single anchor) In y-direction... Vcby=Avcy/Avcoy'Ped,vTc,v Vby [Eq. D-21] cal = 6.00 in Agcy= 63.75 in2 Aveoy= 162.00 in2 [Eq. D-23] 'I`ea,v = 0.9000 [Eq. D-27 or D-281 = 1.0000 [Sec. D.6.2.7] Vby = 7(le/do )°2'N/ dok f c(cai)t.5 [Eq. D-24] le= 1.77 in Vby=4296.34 lb Vcby= 1521.62 lb [Eq. D-21] = 0.75 Oseis = 0.75 4)Vcby= 855.91 lb (for a single anchor) Case 2: This case does not apply to single anchor layout Case 3: Anchor checked for parallel to edge condition Check anchors at cxi edge Vcbx=Avcx/Avcox'Ped,VPc,V Vbx [Eq. D-21] Cal =4.00 in (adjusted for edges per D.6.2.4) Ave),= 51.00 in2 Avcox = 72.00 in2 [Eq. D-23] 1.0000 [Sec. D.6.2.1(c)] Project Name St. Anthony Catholic Church (#13-CD-58965) Project # 13-148 11 LTC Location 9905 SW McKenzie St., Tigard, Oregon L,UR=THOMAS CONSUL rivc LLc Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8//13 Page p of Ltcstr u<l u ra I@gmai I.com `Pc,v = 1.0000 [Sec. D.6.2.7] Vbx = 7(le/do )0.2 doh f c(cat)l.s [Eq. D-24] le = 1.77 in V = 2338.63lb Vbx Vox = 1656.53 lb [Eq. D-21] Vcby= 2 * Vcbx [Sec. D.6.2.1(c)] Veby= 3313.06 lb = 0.75 Oseis — 0.75 Veby = 1863.60 lb (for a single anchor) Check anchors at cyj edge Vcby=Avcy/AvcoyTed,v'I'c,v Vby [Eq. D-21] cal = 6.00 in Ave), = 63.75 in2 Ave.), = 162.00 in2 [Eq. D-23] `Ped,V = 1.0000 [Sec. D.6.2.1(c)] Tc,v = 1.0000 [Sec. D.6.2.7] Vby = 7(le/do )0.2 d0 q fc(Cal)l.s [Eq. D-24] le= 1.77 in Vby=4296.34 lb Veby= 1690.69 lb [Eq. D-21] Vcbx= 2 * Vby [Sec. D.6.2.1(c)] Vox= 3381.38 lb = 0.75 4seis = 0.75 4Vebx = 1902.03 lb (for a single anchor) Check anchors at cx2 edge Vox =Avcx/Avcox Ped,VPc,V Vbx [Eq. D-21] cal = 4.00 in (adjusted for edges per D.6.2.4) Aver = 51.00 in2 Avcox = 72.00 in2 [Eq. D-23] Project Name St. Anthony Catholic Church (#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN Trwws CONSUL-G.LLC Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8//13 Page R of LfatractanlQgmail.cam g `I'ed,v = 1.0000 [Eq. D-27 or D-28] [Sec. D.6.2.1(c)] = 1.0000 [Sec. D.6.2.7] Vbx = 7(le/do)O.2\J doX,1 f c(Cal)1.5 [Eq. D-24] le = 1.77 in Vbx = 2338.63 lb Vcbx= 1656.53 lb [Eq. D-21] Vcby = 2 * Vox [Sec. D.6.2.1(c)] Vcby= 3313.06 lb = 0.75 (Oseis = 0.75 4)Vcby= 1863.60 lb (for a single anchor) Check anchors at cy2 edge Vcby= Avcy/Avcoy'Ped,v`I'c,v Vby [Eq. D-21] Cal = 6.00 in Ave),= 63.75 in2 A,,coy= 162.00 in2 [Eq. D-23] '1'ed,v = 1.0000 [Sec. D.6.2.1(c)] `I'c,v = 1.0000 [Sec. D.6.2.7] ' Vby = 7(le/do )0.24 doa. / fc(ca>i)".5 [Eq. D-24] le= 1.77 in Vby = 4296.34 lb Vcby = 1690.69 lb [Eq. D-21] Vcbx = 2 * Vcby [Sec. D.6.2.1(c)] Vebx = 3381.38 lb = 0.75 �seis = 0.75 4)Vcbx = 1902.03 lb (for a single anchor) 10) Concrete Pryout Strength of Anchor in Shear [Sec. D.6.3] Vcp =kcpNcb [Eq. D-29] kelp = 1 [Sec. D.6.3.1] Ncb = 2001.61 lb (from Section (5)of calculations) Project Name St.Anthony Catholic Church (#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN TNows Co JLTM°_ tClient Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 I 503-317-1023 By LMT Date 11/8//13 Page \7 of Ltcstruc tunlQgmail.com • Vep =2001.61 lb = 0.75 [D.4.5] •seis = 0.75 •Vcp= 1125.90 lb (for a single anchor) 11) Check Demand/Capacity Ratios [Sec. D.7] Note: Ratios have been divided by 0.4 factor for brittle failure. Tension - Steel : 0.0000 - Breakout : 0.0000 - Pullout : 0.0000 - Sideface Blowout : N/A Shear - Steel : 0.2021 - Breakout(case 1) : 0.4381 - Breakout (case 2) : N/A - Breakout (case 3) : 0.2012 - Pryout : 0.3331 T.Max(0) <= 0.2 and V.Max(0.44) <= 1.0 [Sec D.7.2] Interaction check: PASS Use 3/8" diameter Titen HD anchor(s)with 2.5 in. embedment • Project Name St. Anthony Catholic Church(#13-CD-58965) Project# 13-148 LTC Location 9905 SW McKenzie St., Tigard, Oregon LAUREN THOMAS CONSRTNG LIC Client Imperial Brown 10372 SW Bonanza Way Tigard,OR 97224 503-317-1023 By LMT Date 11/8//13 Page B of L to st r u z t o ra I Qg ma i I.ro m