Bulletin 110 Rev.S
id
1111111.111111111111111111111111111111111111111101111111111011111111 Model G co
rieliabitt Automatic SprinklersCD
Spray Upright, D
Spray Pendent o
And Conventional Jo
1 CD
1
RECLVFD
MAY 30 2013
Product Description UPI psi I b : r
The Reliable Model G Automatic Sprinkler utilizes ttiik l °i+''.r= 5~ g t`'',',,'t
center strut solder in compression principle of ;.*:".7,
construction. The fusible alloy is captured in the ['`
cylinder of the solder capsule by a stainless steel ball. ' ��`� , .
When the fusible alloy melts, the ball moves into the f 1 t
cylinder allowing the cylinder to fall away from the .. » )'
sprinkler. When this happens, the lever is released to ri , 4
spring free from the sprinkler so that all of the operating Rn !`
parts clear from the waterway allowing the deflector to
•distribute the discharging water. — ,
Except for the parts in the cylinder as mentioned
above, the sprinkler components are made from Upright Pendent
copper based alloys for maximum corrosion
protection. Lead plated,wax coated or wax over lead
plated sprinklers are available for specially severe -
environments. Chrome plated sprinklers are available
for decorative purposes. iti at
.
All sprinklers are individually hydrostatically tested. 4 , ,
All sprinklers are identified as to their fusing point by _r �"'"➢
markings that appear on several of the operating parts i t „ `
and by an identifying color that appears on the frame.
r
Sprinkler Types
Standard Upright - This deflector configuration is Small Orifice Upright Conventional
normally used with exposed piping installations.Water
is distributed laterally and downward in a wide pattern
approximating a hemisphere which is completely and
uniformly filled with water in the form of small drops or
spray.
Standard Pendent - This deflector configuration is Application and Installation
normally used where the space above the piping is Standard sprinklers are used in fixed fire protection
I limited or where a concealed piping installation is systems:Wet, Dry, Deluge or Preaction.Care must be
employed. The discharge characteristics of the exercised that the orifice sizes, temperature ratings,
standard pendent are virtually identical to the deflector styles and sprinkler spacings are in
standard upright as described above. accordance with the latest published standards of the
National Fire Protection Association or the approving
Large and Small Orifice—By varying the orifice size, authority having jurisdiction.
a large or small orifice sprinkler is created that will The sprinklers must be installed with the Reliable
distribute as much as 40% more water or 65% less Model D Sprinkler Wrench. Any other type of wrench
water than the normal 1" (15mm)orifice sprinkler. may damage the sprinkler.
The approvals or listings of Reliable Automatic
Conventional—This deflector configuration is used Sprinklers by major approving organizations are
primarily in those countries where the LPC installation shown in the tabulated list provided on the back of this
rules have precedence. The sprinkler is designed to bulletin.
distribute a portion of its water discharge upward
against the ceiling with the balance downward. It may
be installed in either the upright or the pendent
position. Sprinklers with conventional deflectors are
available with orifice sizes corresponding to light, *Patent No.4,440,234
i ordinary and extra-high hazard installations.
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Technical Data i
"K"Factor Sprinkler Identification
Sprinkler Number(SIN)
Sprinkler Type US Metric Height Approvals SSU SSP i
Standard-Upright(SSU)and Pendent(SSP)
Deflectors Marked to Indicate Position
X"(15 mm)Standard Orifice with y"NPT(RX)Thread 5.62 81.0 2'/e" (73 mm) 1,2,3,4,5,6,7 R1025 R1015
%fi'(11 mm)Small Orifice with X"NPT(RX)Thread 4.24 61.0 2'/e" (73 mm) 1,3,7 R1023 R1013
X"(10 mm)Small Orifice with X"NPT(Ry)Thread 2.82 40.6 2%" (73 mm) 1,2,3,7 R1021 R1011
Xfi'(8mm)Small Orifice with}2"NPT(RX)Thread 1.98 28.5 2 7/e" (73 mm) 1,3,7 R1022 R1012
1%2"(20 mm)Large Orifice with y"NPT(R%)Thread 7.96 114.7 2 7/8" (73 mm) 1,2,3,7 R1026 R1016
1%2'(20 mm)Large Orifice with X"NPT(RX)Thread 8.20 118.2 2 1%6" (75 mm) 1,2,3,7 R1027 R1017
20 mm XHH with 20 mm Thread 8.20 118.2 75.4 mm 4,5,6 R1027 R1017
10 mm XLH with 10 mm Thread 4.10 59.1 73 mm 4,5,6 R1024 R1014
Conventional—Installed in Upright or Pendent Position
10mm XLH with 10mm Thread 4.10 59.1 73 mm 5 R1074
15mm Standard Orifice with(Ry) Thread 5.62 81.0 73 mm 4,5,6 R1075
20mm XHH with(RX)Thread 8.20 118.2 75.4 mm 4,5 R1077
Temperature Ratings Maintenance
Maximum Model G Sprinklers should be inspected quarterly and the
Sprinkler Ambient sprinkler system maintained in accordance with NFPA 25. Do
Rating Temperature Frame(1) not clean sprinklers with soap and water,ammonia or any other
Classification °F °C °F °C Color cleaning fluids. Remove any sprinkler that has been painted
Ordinary 135 57 100 38 Black (other than factory applied)or damaged in any way.A stock of
Ordinary 165 74 100 38 Uncolored spare sprinklers should be maintained to allow quick replace-
Intermediate 212 100 150 66 White ment of damaged or operated sprinklers. Prior to installation,
High 286 141 225 107 Blue sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
(1)Frame color does not apply to painted or plated sprinklers sprinklers that would cause improper operation or
-Use sprinkler rating as identified on operating parts. non-operation. Use only the Model D Sprinkler Wrench for
sprinkler removal and installation.Any other type of wrench may
damage the sprinkler.
Finishes()
•
Standard Finishes Approval Organizations
Bronze —All Temperature Ratings 1. Underwriters Laboratories, Inc.
Chrom —All Temperature Ratings 2. Factory Mutual Research Corporation
White(4) —All Temperature Ratings 3. Underwriters' Laboratories of Canada
Only Frame and Deflector are Painted 4. Loss Prevention Council
Special Application Finishes _ 5. Pleniere Assemblee
Bright Brass Plated —Onlyframe,deflector and capareplated. 135°F(57°C),165°F 6. N.Y.C.VS SchS&A No. 5 7-g
g 7. NBS&A No. 587-75-SA or
(74°C),212°F(100°C)Temp.Rating. N.Y.C. MEA 258-93-E
Black Plated —Only frame,deflector and cap are plated.Ali Temp.Ratings.
Polyester Coated(2) —Only frame and deflector are coated.
Lead Plated —165°F(74°C),212°F(100°C)and 286°F(141°C)Temp.Ratings. Ordering Information
Wax-Coated(3) —165°F(74°C)Clear Wax,212°F(100°C) Brown Wax. Specify
Wax-Coated Over 1. Model G
Lead Plated(3) —165°F(74°C)Clear Wax,212°F(100°C) Brown Wax. 2. Deflector
•Upright
(1) Other colors and finishes are available.Consult factory for details. •Pendent
(2) UL listed and NYC MEA Approved only. •Conventional
(3) 212°F(100°C)brown wax may be used on 286°F(141°C) 3. Nominal Orifice
sprinklers when maximum ambient temperatures do not exceed 150°F 4. Inlet Thread
(66°C).UL Listed,FM Approved,NYC MEA 258-93-E. 5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association,Factory Mutual I
Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years,and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States,Canada and foreign countries.
Manufactured by
41
The Reliable Automatic Sprinkler Co.,Inc. o
riteliabid (800)431-1588 Sales Faxces Recycled
Paper
(800)848-6051 Sales Fax
(914)829-2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Inter net Address EG.Printed in U.S.A. 11/04 P/N 9999970005