Report (28) l 2J-?2 Stu (s (/, 0 ivvo u p 1 k....- Model Number YSC060E3EHA**C00000000300000000000000000 Customer: HvAC Inc. Project : Name : Greenway Y4C General Unit function DX cooling,gas heat Unit efficiency Standard efficiency Airflow Convertible configuration Airflow Application Downflow Design Airflow 2000 Evaporator rows 4.00 Fresh air selection Econ-dry bulb 0-100% 3hp Evaporator fin spacing 192 Evaporator face area 7.71 Tonnage 5 Ton Evaporator face velocity 259 Min.unit operating weight 613.0 Cooling Entering DB 80.00 Max.unit operating weight 824.0 Cooling Entering WB 67.00 Ent Air Relative Humidity 51.08 ASHRAE 90.1 Yes Ambient Temp 95.00 Rated capacity(AHRI) 60.00 Heating capacity High gas heat 3ph Heating EAT 70.00 Voltage 208-230/60/3 Design ESP 0.500 Major design sequence E-R-410A Main Cooling Tonnage 5 Ton Cooling Entering DB 80.00 Cooling Entering WB 67.00 Ent Air Relative Humidity 51.08 Ambient Temp 95.00 Evap Coil Leaving Air Temp(DB) 57.73 Evap Coil Leaving Air Temp(WB) 56.93 Cooling Leaving Unit DB 59.59 Cooling Leaving Unit WB 57.65 Gross Total Capacity 62.27 Gross Sensible Capacity 48.11 Gross Latent Capacity 14.16 Net Total Capacity 59.03 Net Sensible Capacity 44.87 Net Sensible Heat Ratio 0.76 Fan motor heat 3.24 Dew Point 56.41 Refrig charge(HFC-410A)-ckt 1 9.4 Refrig charge(HFC-410A)-ckt 2 0.0 Saturated Discharge Temp Circuit 1 121.07 Saturated Suction Temp Circuit 1 52.21 Saturated Discharge Temp Circuit 2 0.00 Saturated Suction Temp Circuit 2 0.00 Main Heating Heating capacity High gas heat 3ph Input Heating Capacity 130000.00 Output Heating Capacity 103000.00 Output Heating Cap.w/Fan 106238.99 Heating EAT 70.00 Heating LAT 117.90 Heating Delta T 47.90 Motor/Electrical Page 1 L Voltage 208-230/60/3 Design ESP 0.500 Component SP 0.180 Total Static Pressure 0.680 Field supplied drive kit required None Indoor mtr operating power 0.988 Indoor RPM 1091 Indoor Motor Power 0.74 Outdoor Motor Power 402.6 Compressor Power 4.34 System Power 5.48 SEER @ AHRI 13.00 MCA 27.40 MOP 40.00 Compressor 1 RLA 15.90 Compressor 2 RLA 0.00 Condenser fan FLA 2.50 Evaporator fan FLA 5.00 Exhaust fan power 0.870 DX Cooling, Gas Heat 3-10 Ton Unit controls Electro mechanical controls 3ph Refrigeration controls Frostat and crankcase heater 3ph Field installed accessories Barometric relief Barometric relief Page 2 Y4C Job Information Greenway TRAM' HvAC Inc. Tag Y4C Quantity 1 Model number YSC060E3EHA**C00000 00030000000000000000 0 - _ -- - — ---Meets Unit Information Tonnage 5 Ton Unit function DX cooling,gas heat Min. unit operating weight 613.0 lb Max. unit operating weight 824.0 lb Design Airflow 2000 cfm Cooling Information Gross Total Capacity 62.27 MBh Gross Sensible Capacity 48.11 MBh Gross Latent Capacity 14.16 MBh Net Total Capacity 59.03 MBh Net Sensible Capacity 44.87 MBh Net Sensible Heat Ratio 0.76 Number Cooling Entering DB 80.00 F Cooling Entering WB 67.00 F Cooling Leaving Unit DB 59.59 F Cooling Leaving Unit WB 57.65 F Ambient Temp 95.00 F Heating Information Heating capacity High gas heat 3ph Input Heating Capacity 130000.00 Btuh _ Output Heating Capacity 103000.00 Btuh Heating EAT 70.00 F Heating LAT 117.90 F Heating Delta T 47.90 F Motor/Electrical Information Voltage 208-230/60/3 Design ESP 0.500 in H2O Indoor Motor Power 0.74 kW Indoor mtr operating power 0.988 hp Indoor RPM 1091 rpm Outdoor Motor Power 402.6 W Compressor Power 4.34 kW System Power 5.48 kW MCA 27.40 A MOP 40.00 A Compressor 1 RLA 15.90 A Evaporator fan FLA 5.00 A Condenser fan FLA 2.50 A Electrical valuesprovided are estimated onlyand are subjectto change without notice and may differ from nameplate values. Field installed low or high static drive kits may be needed. Please check the fan performance tables in the product catalog for application ranges. 2/6/2014 Page 1 of 1 Page 3 TOP PANEL CONDENSER FAN EVAPORATOR SECTION ACCESS PANEL — r,,,,,,..,,,,,,.,, 11 trrr 11 i CONDENSATE DRAIN(ALT) I i, l`t`v41, i i 314'-14 NPTDIA.HQLE �,-'` �``�'� i I CONDENSERCOIL I `\ i 4 114' ICONTROL WIRE 718DIA HOLE 421/41..ijIA % SERVICE GAUGE PORT ACCESS 1 318°DIA.HOLE UNIT POWER WIRE CONTROL AND COMPRE SSOR ACCESS PANE L 112"NPT GAS CONNECTION THROUGH THE BASE CONDENSATE 231/2" NOTES: 1.TH RU-THE-BASE GAS AND ELECTRICAL IS N OT STANDARD ON ALL UNITS. 2.VERIFY WEIGHT,CONNECTION,AND ALL DIMENSION WITH 4 3/16INSTALLER DOCUMENTS BEFORE INSTALLATION 1 ---- ( 41.141P `�I � 18" RETURN SUPPLY i I I –– . 4" 151/2 91/4" - 14" - LT:8" PLAN VIEW UNIT DIMENSION DRAWING 0 361f4" J RETURN 23114" HORIZONTAL SUPPLY 143/4" AIR FLOW 201/4" Q . o ___9____9_ 1 o s s/s" f 00 O �oo I`ir" d 5¢8" I (--1 � LI 171/4" 8 M 131/4" 33/16" 4 1/4'-- CONDENSATE 76/8" - .0 441/4" PACKAGED GAS/ELECTRICAL DIMENSION DRAWING Page 4 • %%44 111. 111.441 RETURN �\ 3/4"-14 NPT ® DRAIN CONNECTION 23 9/1w 1J4 SOM[TRIG-PACKAGED COOLING Page 5 • TWIE $ ELECTRICAL/GENERAL DATA GENERAL (2)(4 R3) HEATING PERFORMANCE Model: YSCO6OF Oversized Motor HEATING-GENE RAL DATA Unit Operating Voltage: 187-253 M CA: N/A Heat ng Model: High Unit P ranary Voltage: 208 MFS: N/A Unit HecandaryVoltage 230 MCBH eating Input(BTU): 130,000 : N/A H eating Output(BTU): 104,000 Unit R ertz: 60 Unit Phase: 3 Na.Burners: 3 No.Stages 1 .SE ER Standard M(tor Field Instated Oversized Motor Gas Inlet Pressure MCA 27.4 MCA NIA Natural Gas(Min/MBc): 4.5/14.0 MFS: 40.0 MFS: N/A LP(Min/Max) 11.0/14.0 MC II: 40.0 MCB: N/A Gas Pipe Connection Size: if? INDOOR MOTOR Standard Motor Oversized Motor Feld Instated Oversized Motor Number. 1 Number: N/A Number: WA Horsepower 1.0 Horsepower N/A Harsepovrer N/A MotorSpeed(RPM) — Motor Speed(RPM): 14/A MotorSpeed(RPMr N/A Phase 3 Phase N/A Phase N/A Full Load Amps: 5.0 FvilLoad Amps: N/A Full Load Amps N/A LodcedRotor Amps: 32.2 LodkedRotor Amps: N/A LodcedRotor Amps: N/A COMPRESSOR Circuit 1/2 OUTDOOR MOTOR Number: 1 Number. 1 Horsepower: 4.3 Horsepower: 0.40 Phase: 3 M oto r Speed(RPM): 1075 Rated Load Amps 15.9 Phase: 1 Locked Rotor Amps: 110.0 Ful Load Amps: 2.5 Locked Rotor Am ps: 6.6 POWER EXHAUST ACCESSORY P) FILTERS REFRIGERANT (2) (Field Installed Power Exhaust) Type R-410 Phase: N/A Type: Throwaway Horsepower: N/A Furnished: Yes Factory Charge MotorSpeed(RPM): NIA Number 2 Cccuit#1 9.5 Full Load Amps: N/A Recommended 20'x30''x2 Circuit#2 N/A Locked Rotor Amps: N/A NOTES: 1.Maximum(HAC R)Circuit Breaker sizing is for installations in the U n led States only. 2.Refrigerant charge is an approximate value.Fara mom precise value,see unit nameplate and service instructions 3.Value does not include Power Exhaust Accessory. 4.Value includes oversized motor. 5.Value does not include Power Exhaust Accessory. 6.EER is rated at MRI conditions and in accordance with DOE test procedures. Page 6 INSTALLED ACCESSORIES NET WEIGHT DATA ACCESSORY WEIGHTS ECONOMIZER 26.0 lb MOTORIZED OUTSIDE AIR DAMPER Q lu7 M.4NUALOUTSIDE AIR DAMPER \\\ BAROMETRIC RELIEF 7.0 lb OVERSIZED MOTOR BELT DRIVE MOTOR ��r�1 POWER EXHAUST p p flllli//�itlf.>>>1111� IV/Pi/4 _ THROUGHT THE BASE ELECTRICAL/GAS(FIOPS) u \ UNIT MOUNTED CIRCUIT BREAKER¢TOPS) UNIT MOUNTED DISCONNECT(HOPS) POWERED CONVENIENCE OUTLET(FIOP5) HINGED DOORS(HOPS) B O HAIL GUARD SMOKE DETECTOR,SUPPLY/RETURN NO VAR CONTROL PACKAGED GAS/ELECTRICAL CORNER WEIGHT STAINLE SS STEEL HEAT EXCHANGER REHEAT ROOF CURB BASIC UNIT WEIGHTS CORNER WEIGHTS CENTER OF GRAVITIY SHIPPING NET AO 190.0 lb © 116.01h (E)LENGHT (F)WIDTH 688.0 lb 613.0 lb a 158.OIb O 155.OIb 31" 19" NOTE: 1.CORNER WEIGHTS ARE GIVEN FOR INFORMATION ONLY. 2.TO ESTIMATE SHIPPING WEIGHT ADD 5 LBS TO NET WEIGHT. 3.BASIC UNIT WEIGHT DOES NOT INCLUDE ACC E SSORYWE IG HT.TO OBTAIN TOTAL WEIGHT,ADD ACCESSORYNET WEIGHT TO BASIC U NIT WEIGHT. C.WEIGHTS FOR OPTIONS NOT LISTED ARE<5 LBS. WitIoN ,40:00.00000; • kerli'-‘111 ,,/" PACKAGED GAS!ELECTRICAL RIGGING AND CENTER OF GRAVITY Page 7 • TWF CLEARANCE FROM TOP OF UNIT 72" CLEARANCE 36" • CLEARANCE 48" it1 Iii$ i DOWN FLOW CLEARANCE 36" HORIZONTAL CLEARANCE 18" CLEARANCE 36" PACKAGED GAS/ELECTRIC CLEARANCE ROOF OPENING I ' 1 UNIT OUTLINES I I \\vjlll7 3T a41/2' I I ____J 40' --] 1 .1--:L--- 68 3/16' PACKAGED GAS/ELECTRIC OOWNFLOW TYPICAL ROOF OPE KING Page 8 • TRPJIE `L�fllir.r__�.0,,_j� `` 1'la ` . ii CONOMIZER HOOD BAROMETRIC RELIEF HOOD r r BAROMETRIC RELIEF HOOD 4 _,,_ , 6 15/16" 9 Mr --a ACCESSORY-BAROMETRIC RELIEF DAMPER HOOD Page 9 . 0 MANE i iiiiiiiiiiisisItli !rte\ itliiiilitsit it ' CONOM IZE R HOOD CONOMIZER HOOD 1111 --11L-11 o ______T 12112-—a- ACCESSORY-ECONONAZER HOOD Page 10 MANE General The units shall be convertible airflow.The operating range shall be between 115°F and 0°F in cooling as standard from the factory for units with microprocessor controls.Operating range for units with electromechanical controls shall be between 115°F and 40°F.Cooling performance shall be rated in accordance with ARI testing procedures.All units shall be factory assembled,internally wired,fully charged with R-410A,and 100 percent run tested to check cooling operation,fan and blower rotation,and control sequence before leaving the factory.Wiring internal to the unit shall be colored and numbered for simplified identification.Units shall be cULus listed and labeled,classified in accordance for Central Cooling Air Conditioners. Casing Unit casing shall be constructed of zinc coated,heavy gauge,galvanized steel.Exterior surfaces shall be cleaned,phosphatized,and finished with a weather-resistant baked enamel finish.Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117.Cabinet construction shall allow for all maintenance on one side of the unit.Service panels shall have lifting handles and be removed and reinstalled by removing two fasteners while providing a water and air tight seal.All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil-faced, fire-retardant permanent,odorless glass fiber material.The base of the unit shall be insulated with 1/8 inch,foil-faced,closed-cell insulation.All insulation edges shall be either captured or sealed.The unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8 inch high downflow supply/return openings to provide an added water integrity precaution,if the condensate drain backs up.The base of the unit shall have provisions for forklift and crane lifting,with forklift capabilities on three sides of the unit. Unit Top The top cover shall be one piece construction or,where seams exist,it shall be double-hemmed and gasket-sealed. The ribbed top adds extra strength and enhances water removal from unit top. Filters Throwaway filters shall be standard on all units.Optional 2-inch MERV 8 and MERV 13 filters shall also be available. Compressors All units shall have direct-drive,hermetic,scroll type compressors with centrifugal type oil pumps.Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage.Internal overloads shall be provided with the scroll compressors. Dual compressors are outstanding for humidity control,light load cooling conditions and system back-up applications.Dual compressors are available on 7/-10 ton models and allow for efficient cooling utilizing 3-stages of compressor operation for all high efficiency models. Notes: Crankcase heaters are optional on YSC(036,048,060,072,090,102,120);standard on YHC(036,048,060,072,092,102,120). Indoor Fan The following units shall be equipped with a direct drive plenum fan design(T/YSC120E,T/YHC092,102,120E).Plenum fan design shall include a backward-curved fan wheel along with an external rotor direct drive variable speed indoor motor.All plenum fan designs will have a variable speed adjustment potentiometer located in the control box.3-5 ton units(standard efficiency 3-phase or high efficiency 3-phase with optional motor)are belt driven,FC centrifugal fans with adjustable motor sheaves.3-5 ton units(1-phase or high efficiency 3-phase)have multispeed,direct drive motors.All 6-81/2 ton units(standard efficiency)shall have belt drive motors with an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves.All motors shall be thermally protected.All 10 tons and 71/-81/2(high efficiency)have variable speed direct drive motors.All indoor fan motors meet the U.S. Energy Policy Act of 1992(EPACT). Outdoor Fans The outdoor fan shall be direct-drive,statically and dynamically balanced,draw-through in the vertical discharge position.The fan motor shall be permanently lubricated and shall have built-in thermal overload protection. Evaporator and Condenser Coils Internally finned,5/16"copper tubes mechanically bonded to a configured aluminum plate fin shall be standard.The microchannel type condenser coil is standard for the T/YSC 10 ton models and 71/2 ton high efficiency models.The microchannel type condenser coil is not offered on the 71/2 ton dehumidification model.Due to flat streamlined tubes with small ports,and metallurgical tube-to-fin bond,microchannel coil has better heat transfer performance.Microchannel condenser coil can reduce system refrigerant charge by up to 50%because of smaller internal volume,which leads to better compressor reliability.Compact all-aluminum microchannel coils also help to reduce the unit weight.All-aluminum construction improves re-cyclability. Galvanic corrosion is also minimized due to all aluminum construction.Strong aluminum brazed structure provides better fin protection.In addition,flat streamlined tubes also make microchannel coils more dust resistant and easier to clean.Coils shall be leak tested at the factory to ensure the pressure integrity.The evaporator coil and condenser coil shall be leak tested to 600 psig.The assembled unit shall be leak tested to 465 psig.The condenser coil shall have a patent pending 1+1+1 hybrid coil designed with slight gaps for ease of cleaning.A removable,reversible,double-sloped condensate drain pan with through the base condensate drain is standard. Page 12 TIMM* Controls unit shall be completely factory-wired with necessary controls and contactor pressure lugs or terminal block for power wiring.Unit shall provide an external location for mounting a fused disconnect device.A choice of microprocessor or electromechanical controls shall be available.Microprocessor controls provide for all 24V control functions.The resident control algorithms shall make all heating,cooling,and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures.The control algorithm maintains accurate temperature control,minimizes drift from set point,and provides better building comfort.A centralized microprocessor shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.24-volt electromechanical control circuit shall include control transformer and contactor High Pressure Control All units include High Pressure Cutout as standard. Phase monitor Phase monitor shall provide 100%protection for motors and compressors against problems caused by phase loss,phase imbalance,and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator. There are no field adjustments.The module will automatically reset from a fault condition. Refrigerant Circuits Each refrigerant circuit offer thermal expansion valve as standard.Service pressure ports,and refrigerant line filter driers are factory-installed as standard. An area shall be provided for replacement suction line driers. Gas Heating Section The heating section shall have a progressive tubular heat exchanger design using stainless steel burners and corrosion resistant steel throughout.An induced draft combustion blower shall be used to pull the combustion products through the firing tubes.The heater shall use a direct spark ignition(DSI)system.On initial call for heat,the combustion blower shall purge the heat exchanger for 20 seconds before ignition After three unsuccessful ignition attempts,the entire heating system shall be locked out until manually reset at the thermostat/zone sensor.Units shall be suitable for use with natural gas or propane(field-installed kit)and also comply with the California requirement for low NOx emissions (Gas/Electric Only). Economizer This accessory shall be available with or without barometric relief.The assembly includes fully modulating 0-100 percent motor and dampers,minimum position setting,preset linkage,wiring harness with plug,spring return actuator and fixed dry bulb control.The barometric relief shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment off cycle.Optional solid state or differential enthalpy control shall be available for either factory or field installation.The economizer arrives in the shipping position and shall be moved to the operating position by the installing contractor. Frostat This option is to be utilized as a safety device.The Frostat opens when temperatures on the evaporator coil fall below 10°F.The temperature will need to rise to 50°F before closing.This option should be utilized in low airflow or high outside air applications.(Cooling with Electric Heat Only.) Frostat This option is to be utilized as a safety device.The Frostat opens when temperatures on the evaporator coil fall below 10°F.The temperature will need to rise to 50°F before closing.This feature should be utilized in low airflow or high outside air applications(cooling only). Page 13