Report (21) •
16/0 -3 (2 Ge` i gc-mss
vlir LEAR ELECTRIC CO., INC.
CONTRACTING AND DESIGN RECEIVED
6002 NE 112th Ave.
Portland,OR 97220 OCT 1 t1
(503)255-0733 Fax(503)255-0676
CCB#52278 / ESB#7112 cITY OF TIGARD
BUILDING DIVISION
VACANT SPACE
FANNO CREEK BUILDING - B
16083 SW Upper Boones Ferry Rd. Suite 320
Tigard, OR 97224
FIRE ALARM EXTENSION
October 9, 2013
Lear Job No.
PO# 13-564
Project Manager: Oleg Primachenko
SYSTEM
$ SENSOR® 71ii`Vg
iy
Indoor Selectable-
Output Strobes and ,
Horn Strobes for
tottiv.
Ceiling Applications � )
SpectrAlert®Advance audible visible notification products
are rich with features guaranteed to cut installation times PECTR�
and maximize profits. SS v a lert
s c E
Features The SpectrAlert Advance series offers the most versatile and
• Plug-in design with minimal intrusion into the back box easy-to-use line of horns,strobes,and horn strobes in the industry.
With white and red plastic housings,wall and ceiling mounting
• Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance
• Automatic selection of 12-or 24-volt operation at 15 and can meet virtually any application requirement.
15/75 candela
• Field-selectable candela settings on ceiling units: 15, 15/75,30, Like the entire SpectrAlert Advance product line,ceiling-mount
strobes and horn strobes include a variety of features that increase
75,95. 110, 115, 135, 150, 177,and 185
their application versatility while simplifying installation.All devices
• Horn rated at 88+dL3A at 16 volts feature plug-in designs with minimal intrusion into the back box.
• Rotary switch for horn tone and three volume selections making installations fast and foolproof while virtually eliminating
costly and time-consuming ground faults.
• Universal mounting plate for ceiling units
• Mounting plate shorting spring checks wiring continuity before To further simplify installation and protect devices from construction
device installation damage.SpectrAlert Advance utilizes a universal mounting plate
• Electrically Compatible with legacy SpectrAlert devices with an onboard shorting spring,so installers can test wiring
• Compatible with MDL sync module continuity before the device is installed.
• Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12-or 24-volt operation,and a rotary switch
for horn tones with three volume selections.
Agency Listings
SIGNALING
® MEA
approved 71112Z211::
12,-653186;;ndoor s:moesl
LISTED APPROVED pP 71 25-1 653 1 68!hem 5110336.
34011(chimes,Flom shores,-erns) 30230.72 M_A452-05-E ;;^hime strobe;)
S5512(s-obes) :'135-'653 1833 horns.ch mes)
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-
gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for
mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert
Advance products,when used with the Sync•Circuit°Module accessory,shall be powered from a non-coded notification appliance circuit
output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit
outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.
Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified
unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135,
150, 177,and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light
shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire
products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns
on horn strobe models over a single pair of wires.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also
control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more
synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F(0°C to 49°C)
Humidity Range 10 to 93%non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1
Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal)
InputTerminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high)
Ceiling-Mount Back Box Skirt Dimensions(BBSC-2,BBSCW-2) 7.1"diameter x 2.2"high(180 mm diameter x 57 mm high)
Ceiling-Mount Trim Ring Dimensions(sold as a 5 pack)(TRC-HS, 6.9"diameter x 0.35"high(175 mm diameter x 9 mm high)
TRCW-HS)
Notes:
1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs.
2,P,S,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
AVGSU0s°,
UL Current Draw Data
UL Max.Strobe Current Draw(mA RMS)
8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR
Standard Candela Range 15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High 135 NA NA 228 207
Candela Range 150 NA NA 246 220
177 NA NA 281 251
185 NA NA 2.86 258
UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,Standard Candela Range(15-115 cd)
8-17.5 Volts 16-33 Volts
DC Input 15 15/75 15 15175 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 1218 I
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
UL Max.Current Draw(mA RMS),2-Wire Horn Strobe,High Candela Range(135-185 cd)
16-33 Volts 16-33 Volts
DC Input
135 150 177 185 FWR Input 135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Horn Strobe Tones and Sound Output Data
Horn Strobe Output(dBA)
8-17.5 16-33 24-Volt Nominal
Switch Volts Volts Reverberant Anechoic
Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 74 74 80 80 86 86 96 96
3 Temporal Low 71 73 76 76 83 80 94 89
4 Non-Temporal High 82 82 88 88 93 92 100 100
5 Non-Temporal Medium 78 78 85 85 90 90 98 98
6 Non-Temporal Low 75 75 81 81 88 84 96 92
7t Coded High 82 82 88 88 93 92 101 101
8t Coded Medium 78 78 85 85 90 90 97 98
9t Coded Low 75 75 81 81 88 85 96 92
tSettings 7,8,and 9 are not available on 2-wire horn strobes.
AVDSG0501
SpectrAlert Advance Dimensions
7.1" 14-2.25
6.8" i Dia. r
• jail Dia. /p f0 \
.--.-''''''''\\1. ^Q \ c
/.; :5(a-7- cc H
O /
,._...1___IL,1 2 \.%b Cy
Ceiling-mount horn strobes Ceiling back box skirt
SpectrAlert Advance Ordering Information
Model Description Model Description
Ceiling Horn Strobes Ceiling Strobes
PC2R* 2-Wire Horn Strobe,Standard cd,Red SCR Strobe,Standard cd,Red
PC2RH 2-Wire Horn Strobe,High cd,Red SCRH Strobe,High cd,Red
I PC2W't 2-Wire Horn Strobe,Standard cd,White I SCW* Strobe,Standard cd,White
PC2WH` 2-Wire Horn Strobe,High cd.White SCWH Strobe,High cd,White
PC4R 4-Wire Horn Strobe,Standard cd,Red Accessories
PC4RH 4-Wire Horn Strobe,High cd,Red BBSC-2 Back Box Skirt,Ceiling,Red
PC4W 4-Wire Horn Strobe,Standard cd,White Back Box Skirt,Ceiling,White
TRC-HS Trim Ring,Ceiling,Red
TRCW- Trim Ring,Ceiling,White
HS
Notes:
"Add"-P"to model number for plain housing(no"FIRE"marking on cover).e.g.,P2R-P.
t Add"-SP"to model number for"FUEGO"marking on cover,e.g.,P2R-SP.
t"Standard cd"refers to strobes that include 15,15/75,30,75.95.110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185
candela settings.
• V_ SYSTEM .2012 Swed,Sensor.
3825 Ohio Avenue•St.Charles,IL 60174 ar:aua specrticat.ons suQucno mange without nonce.Vsz systemsensor.co-
. SENSOR" Phone:800-SENSOR2•Fax:630-377-6495 to tuned p'oduct rtorrnanon,rcludrg the latest verso of!hls data sheet.