Loading...
Report (23) Wsaloi S - &Ul oo/ 7i Sc.() j7 t ilf_7L, t1110Worldwide Fire Protection Contac, w'tyco-fire.com Products j{f\ CEIVEp Model BFV-N Butterfly Valve JUL 2 2015 Grooved End OFTIGARU 2-1/2 to 10 Inch (DN65 to DN250) BUILDING DIvr,Sf General Technical Description Data The Model BFV-N Grooved End But- Approvals ----"" terfly Valves(Ref. Figure 1)are indicat- UL and C-UL Listed ing type valves designed for use in fire FM Approved protection systems where a visual in- dication is required as to whether the Listed by California State Fire Marshall valve is open or closed.They are used, under Listing No.7770-1670:100 for example, as system, sectional, and All laboratory listings and approvals are pump water control valves. They have for indoor and outdoor use. cut groove inlet and outlet connections that are suitable for use with grooved Maximum Working Pressure end pipe couplings that are listed and 2-1/2 to 8 Inch(DN65 to DN200) approved for fire protection systems. 300 psi(20,7)bar For applications requiring supervision 10 Inch(DN250) of the open position of the valve, the 175 psi(12,0 bar) Gear Operators for the Model BFV-N Materials of Construction Butterfly Valves are provided with two sets of factory installed inter- Body nal switches each having SPDT con- Ductile iron conforming to ASTM A395 tacts (Ref. Figure 3). The supervisory Body Coating switches transfer their electrical con- Polyamide tacts when there is movement from the valve's normal open position dur- Disc ing the first two revolutions of the Ductile iron conforming to ASTM A395 handwheel. Disc Seal NOTICE Grade EPDM "E" encapsulated rubber conforming to ASTM D2000 The Model BFV-N Grooved End But- U er&Lower Stem terfly Valves described herein must Type p 416 Stainless Steel conformingto be installed and maintained in com- AM 582 g pliance with this document, as well as with the applicable standards of the Lower Plug National Fire Protection Association,in PVC addition to the standards of any other O erator authorities having jurisdiction. Failure Oper operator with iron housing to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Page 1 of 4 JANUARY 2015 TFP1510 , TFPISIO Page 2 of 4 r Nominal Nominal Installation Dimensions Valve O�e Inches(mm) Weight Sizes Inches Lbs. Inches (mm) A B C D E F G H (kg) (DN) 2-1/2 2.88 3.85 11.94 3.25 5.67 5.90 5.82 2.13 22 (65) (73,0) (98,0) (303,3) (83,0) (144,0) (149,9) (147,8) (54,1) 0 (10,0) 3 3.50 3.85 12.48 3.54 5.94 5.90 5.82 2.13 23 (80) (88,9) (98,0) (317,0) (90,0) (150,9) (149,9) (147,8) (54,1) 0 (10,4) 4 4.50 4.56 14.18 4.35 6.31 5.90 7.64 2.13 28 (100) (114,3) (116,0) (360,2) (110,0) (160,3) (149,9) (194,1) (54,1) 0 (12,7) 5 5.56 5.86 15.17 4.84 7.32 5.90 7.64 2.13 0 31 (125) (141,3) (149,0) (385,3) (123,0) (185,9) (149,9) (194,1) (54,1) (14,1) 6 6.63 5.86 17.54 5.93 8.62 5.90 7.64 2.13 0.67 41 (150) (168,3) (149,0) (445,5) (151,0) (218,9) (149,9) (194,1) (54,1) (17,0) (18,6) 8 8.63 5.26 19.42 6.87 9.80 9.80 7.91 2.13 5.86 53 (200) (219,1) (134,0) (493,3) (174,0) (248,9) (248,9) (200,9) (54,1) (148,8) (24,1) 10 10.75 6.29 24.03 9.17 11.61 18.00 9.49 3.03 7.41 88 (250) (273,1) (160,0) (610,4) (233,0) (294,9) (457,2) (241,0) (77,0) (188,2) (40,0) -- G r F HANDWHEEL INDICATOR FLAG 1/2" NPT CONDUIT - —� CONNECTION GEAR 1 e •, / Q OPERATOR E 0014 •1 , i 1 BODY Lr v B _ D `�, - , DISC H r \_ -_ / C 1- L1 —A FIGURE 1 MODEL BFV-N GROOVED END BUTTERFLY VALVE NOMINAL DIMENSIONS Installation switch is intended for connection to the supervisory circuit of a fire alarm The Model BFV-N Grooved End But- control panel in accordance with NFPA terfly Valves may be installed with flow 72.The auxiliary switch is intended for in either direction and can be posi- the unsupervised connection to aux- to•C% tioned either horizontally or vertically. iliary equipment in accordance with NFPA 70, National Electric Code. A C The grooved end pipe couplings used •11100 _ with the Model BFV-N must be listed NOTE: For outdoor applications with P/ or approved for fire protection service internal supervisory switches, it is rec- OPEN B /'-e- and and installed in accordance with the ommended that wiring connections manufacturers instructions. be made at a temperature above 15°F (-9 C), in order to insure sufficient flex- A SHUT The Model BFV-N Butterfly Valve may ibility of the wire lead insulation. be installed with any schedule of pres- FIGURE 2 sure class of pipe or tubing that is list- Stop Adjustment MODEL BFV-N GROOVED END ed or approved for fire protection. Procedure BUTTERFLY VALVE As applicable, refer to Figure 3 for the The gear operator's OPEN and SHUT OPERATOR ADJUSTMENT internal switch wiring diagram. position have been factory set. The Step 2. Remove two lockscrews (A) following procedure should be used if from the gear operator body. Conduit and electrical connections slight adjustments are needed. Refer are to be made in accordance with to Figure 2. Step 3. Turn the Shut Stop Screw (B) the authority having jurisdiction and/ Step 1. Turn the Handwheel until the clockwise until snug. or the National Electrical Code. With valve is fully closed. Step 4. Turn the Handwheel until the reference to Figure 3, the supervisory valve is fully open. TFP151O Page 3 of 4 • FLOW RATE IN LITRES PER MINUTE(LPM) (1 GPM=3,785 LPM) 300 400 600 1000 2000 4000 6000 10000 20000 40000 5.0 fill II/111111MJJIIJIIJlllll l 1 IIII IIII11IIJJI1 l�lliiIJ IIt/7t020 IUi_ 4.0 _ /T/ 0,30 3.0 ,_ 2.0 - cc N - ¢ 0 -- y / 11111 -0,10 Z 0,08 O¢ ww CC CC1.0 �h o h o o�--� - ccm uJ> 0.8 ` 2 2 2 2 2 p� ¢ co v�0 ? `O/ `O O O -0,05 0 o CC ZV�VZ Z 2 Z Vii CO o Cl-s 0.6 ti� ZV�,C.) ' �V �V ? =0,04 EL u Zu 0.5 a� <n/ w p z 0.4 / -0,03 a- Z 0.3 z =0,02 z 0.2 -- / -0,01 0.1 / 60 100 200 400 600 1000 2000 4000 6000 10000 15000 FLOW RATE IN GALLONS PER MINUTE(GPM) GRAPH A DN65 THROUGH DN250 MODEL BFV-N BUTTERFLY VALVE NOMINAL PRESSURE DROP VERSUS FLOW r , r II • I I I- SUPERVISORY I I— AUXILIARY CONTACT RATING: I I SWITCH I GND I SWITCH I I 1/2A @ 125 VDC I I I • I 1/4A @ 250 VDC I I SWITCH SHOWN I I SWITCH SHOWN 15.1A/12HP @ 125,250 VAC I I WITH VALVE I I WITH VALVE 5A @ 125 VAC"L" - --- -- --- -J FULL OPEN `- J FULL OPEN w w C7 C7 Z O O zz w J w J T1 w w CC 0 CO >- >- 0 0 1 • + n • BELL END OF LINE PANEL RESISTOR POWER • + FIGURE 3 MODEL BFV-N BUTTERFLY VALVE INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION Step 5.Turn the Open Stop Screw(C) Step 7. Replace two lockscrews (A) clockwise until snug. into the gear Operator body locking Step 6. Close the valve by turning the the stops into position. _ Handwheel until the valve is fully in the closed position. Ensure the disc has returned to the fully closed position and the disc is centered in the seat . area. Readjust the Shut Stop Screw if necessary. TFPISIO Page 4 of 4 Care and Limited Maintenance Warranty Before closing a fire protection sys- For warranty terms and conditions, tern control valve for maintenance or visit www.tyco-fire.com. inspection work on either the valve or fire protection system which it con- Ordering trots, permission to shut down the af- fected fire protection systems must be Procedure obtained from the proper authorities and all personnel who may be affected Grooved End Butterfly Valves by this decision must be notified. Specify:(specify inch size)Model BFV- The owner is responsible for the in- N Grooved End Butterfly Valve with spection, testing, and maintenance internal supervisory switches, P/N of their fire protection system and de- (specify) vices in accordance with the appli- Valve Size Valve Part Number cable standards of the National Fire Protection Association (e.g., NFPA 2-1/2 59-300-F-025N 25), in addition to the standards of 3 59-300-F-030N ) 4 59-300-F-040N any authority having jurisdiction. 5 59-300-F-050N Contact the installing contractor or 6 59-300-F-060N product manufacturer with any ques- 8 59 300-F-080N tions.Any impairment must be imme- diately 10 59-300-F-100N corrected. It is recommended that automatic sprinkler systems be inspected, test- ed, and maintained by a qualified in- - spection service. GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. tgcc, Fire Protection Products fico Worldwide Fire Protection Contacts www.tyco-fire.com Products Model CV-1FR Grooved-End Riser Check Valves 2 to 12 Inch (DN50 to DN300) General NOTICE The Model CV-1FR Riser Check Valve ' Description described herein must be installed and maintained in compliance with this �' "~ ' The TYCO Model CV-1 FR Grooved- document and with the applicable stan- 4 =,y0 4. • End Riser Check Valve is a compact dards of the National Fire Protection e and rugged swing-type unit that al- Association, in addition to the stan- lows water flow in one direction and dards of any authorities having juris- prevents flow in the opposite direc- diction.Failure to do so may impair the tion. A resilient elastomer seal fac- performance of this device. t•; ing on the spring-loaded clapper ensures a leak-tight seal and non- Never remove any piping component sticking operation.The Model CV-1 FR nor correct or modify any piping defi- Riser Check Valves are designed to ciencies without first de-pressurizing minimize water hammer caused by flow and draining the system. Failure to do . reversal. so may result in serious personal injury, 0 C 0 property damage,and/or impaired de- APPROVED The Model CV-1FR Riser Check vice performance. Valve is furnished with grooved ' ends and can be installed using The owner is responsible for maintain- GRINNELL Grooved Couplings or ing their fire protection system and Installation GRINNELL Figure 71 Flange Adapters. devices in proper operating condition. The Model CV-1 FR Riser Check Contact the installing contractor or The Model CV-1 FR Riser Check Valves Valves have been designed with a manufacturer with any questions. are to be installed in accordance with removable cover for ease of field main- this section: tenance.These valves can be installed Technical 1.The arrow cast on the Body must horizontally(with cover in the upward point in the direction of the flow. position)or vertically with the flow in the Data 2.Valves installed vertically must be upward direction. Refer to Figure 6. positioned with the flow in the up- To facilitate their use in wet-type auto- Approvals ward direction. matic sprinkler system risers,the Model UL,C-UL Listed CV-1 FR Riser Check Valves are provid- FM Approved 3.Valves installed horizontally must be ed with threaded outlets for pressure positioned with the Cover facing up. gauges and a drain connection.They Sizes Refer to Figure 6. provide a more compact and economi- 2 to 12 Inch (DN50 to DN300) 4.Grooved-end pipe couplings cal alternative to an alarm check valve Maximum Working Pressure used with the Model CV-1FR Riser where a water motor alarm is not re- 300 psi(20,7 bar) Check Valve must be installed in quired. Provisions must be made for accordance with manufacturer's a local alarm using an approved flow Valve Assembly Finish instructions. switch(not included). Red, non-lead paint NOTE: Valves should be installed a The Model CV-1 FR Riser Check Valve reasonable distance downstream from is also Listed for use in conjunction pumps, elbows, expanders, reducers, with the TYCO DV-5 Deluge Valve in or other similar devices to extend the Preaction Systems under air pressure valve life. Standard piping practices call without the use of prime water. for a minimum of five(5)times the pipe The Model CV-1 FR Riser Check Valves diameter for general use. are a redesign for the Central Figure 590FR and GRINNELL Figure 590FR. Page 1 of 6 JULY 2014 TFP950 TFP95O Page 2 of 6 A ' - B - 1/4" 1/4" . NPT ■■ ■■ NPT 1110 illtillin ArraIlk O.D. 1141111 C :: ( ' I p 111 Will -_.._ J K E - F - Nominal Dimensions Nominal Pipe Size Inches (mm) CoverBoltApprox. Torque Weight ANSI O.D. K Lbs.-ft. Lbs. Inches Inches A B C D E F J Inches (Nm) (kg) DN (mm) NPT 2 2.375 6.75 4.38 1.96 2.57 3.25 4.37 1.561 18 9.0 DN50 (60,3) (171,5) (111,3) (49,8) (65,3) (82,3) (111,0) (39,6) (25) (4,5) _ 2-1/2 2.875 8.00 5.38 2.63 3.09 3.87 5.12 1.73 1-1/4 39 10.0 DN65 (73,0) (203,2) (136,7) (66,8) (78,5) (98,3) (130,0) (43,9) (54) (4,5) 76,1 - 8.00 5.38 2.63 3.09 3.87 5.12 1.72 1-1/4 39 10.0 DN65 (76,1) (203,2) (136,7) (66,8) (78,5) (98,3) (130,0) (43,7) (54) (4,5) 3 3.500 8.37 5.72 2.81 3.31 3.87 5.12 1.72 39 11.0 DN80 (88,9) (212,6) (145,3) (71,4) (84,1) (98,3) (130,0) (43,7) 1-1/4 (54) (5,0) 4 4.500 9.63 6.68 3.80 3.63 4.53 5.78 2.12 50 25.0 DN100 (114,3) (245,6) (169,7) (96,5) (92,2) (115,4) (146,8) (53,8) 2 (69) (11,3) 139.7 - 10.50 7.40 4.46 4.13 4.90 7.00 2.092 39 29.0 DN125 (139,7) (266,7) (188,0) (113,2) (104,9) (124,5) (177,8) (53,1) (54) (13,2) 5 5.563 10.50 7.40 4.46 4.13 4.90 7.00 2.09 39 29.0 DN125 (141,3) (266,7) (188,0) (113,2) (104,9) (124,5) (177,8) (53,1) 2 (54) (13,2) 165.1 - 11.50 8.00 4.62 4.50 5.00 7.25 2.002 60 47.0 DN150 (165,1) (292,1) (203,2) (117,4) (114,3) (127,0) (184,2) (50,8) (82) (21,3) 6 6.625 11.50 8.00 4.62 4.50 5.00 7.25 2.00 60 47.0 DN150 (168,3) (292,1) (203,2) (117,4) (114,3) (127,0) (184,2) (50,8) 2 (82) (21,3) 8 8.625 14.00 10.14 6.67 5.52 5.46 10.50 2.432 120 66.0 DN200 (219,1) (355,6) (257,6) (169,4) (140,2) (138,7) (266,7) (61,7) (164) (30,0) 10 10.750 18.00 12.38 8.62 6.41 7.50 10.75 3.382 130 109.7 DN250 (273,1) (457,2) (314,5) (218,9) (162,8) (190,5) (273,1) (85,9) (178) (49,4) 12 12.750 21.0 14.28 9.93 7.27 7.62 10.00 3.13 130 151.0 DN300 323 9 533 4 362 7 252 2 (184,7)( ) ( ) ( ) ( ) (193,5) (254,0) (79,5) (178) (68,0) FIGURE 1 MODEL CV-1FR RISER CHECK VALVES NOMINAL DIMENSIONS TFP9SO Page 3 of 6 8 8 ` 4,15 17 16 9 111111I1111111114I I 5� } • ��"I'llIIIN l) 1 VEWA ���/ A 2 7 9 2 7 5 3 �i ��I,'■ 2"-8" 10"-12" ilmwrik `1 ! (DN50 DN200) (DN250 DN300) �"����1►`, ��5 +"' VIEW A AlI lib, fr"\1ll5 I I •1 S 1 11 ■i�11 14,15 /YYYY. ���mo 41.11141N.- ! I ����� SEE 6 % / 18 Ill �� ,�� DETAIL B 5 1 6 hind 1 2"-8" 10"-12" (DN50 DN200) (DN250-DN300) DETAIL B Detail Part Material Qty. Detail Part Material Qty. Detail Part Material Qty. 1 Body Ductile Iron 1 6 Clapper EPDM 1 14 Locknut Stainless 1 Facing Grade"E" Steel 2 Cover Ductile Iron 1 7 Spring Stainless 1 15 Adhesive Thread AR Steel Sealer 3 Cover Nitrile Rubber 1 8 Hinge Stainless 1 16 Nameplate Aluminum 1 Gasket Shaft Steel Hex Cap Steel,Zinc Retaining Stainless 4 Screw Plated AR 9 Ring Steel AR 17 Rivet Steel 2 Clapper Stainless Retention Stainless Stainless 2" 8" Steel 11 Bolt Steel 1 18 Spacer Steel 1 5 (DN50-200) 1 . Clapper Retaining Stainless 10" 12" Ductile Iron 13 Disc Steel 1 (DN250-300) FIGURE 2 MODEL CV-1FR RISER CHECK VALVES ASSEMBLY FLOW RATE IN LITRES PER MINUTE(LPM) (1 GPM=3,785 LPM) 500 700 1000 2000 3000 5000 7000 10000 20000 30000 50000 5.0 l 'JiJlllll l ��I I I J I t 1 1 lAil Williit 1J IJf �JIll l l 1 ll l 1 l lll 11111 U'_ 4.0 o r 'o`'C� �C0,30 _..43 AI / a Z •Z 2 0 �. 3.0 O o V O= ?U A ..I 2 aimisir mom h' 0,20 m cc U N I G O ,ti - z o I 2 h _ Z cc Q 2.0 .ii... ! a0 CJZ `O2 ryoo�I I III -" 0 rn w 0 �Iiiiii h UZ ) ho o D`o° CC _/MUNN `y o \-0 10 o Z 2 cn aJ cc W -���% d c0 2V `O 02�� 0,09 w ii o a ''� o VZ _-0,08 a a 2 1.0 2U! - -0,07 --1 z j 0.9 / ^o >\`� 0,06 z v a 0.8 - - z 0.7 _ . . `-0,05 z 0.6 0,04 0.5 - • 100 200 300 400 600 1000 2000 3000 4000 6000 10000 15000 FLOW RATE IN GALLONS PER MINUTE(GPM) FIGURE 3 • MODEL CV-1FR RISER CHECK VALVES PRESSURE LOSS DATA TFP95O Page 4 of 6 ) 1 1 *OP- A11I _. 1U' ' . ,..,..,.„,lt ...... _,‘,, nE B D Nominal Dimensions Nominal Pipe Size Inches (mm) ANSI O.D. E Inches Inches A B C D Inches DN (mm) NPT 2 2.375 6.75 5.87 3.25 9.52 DN50 (60,3) (171,5) (149,1) (82,6) (241,9) 1 2-1/2 2.875 8.00 6.66 3.87 10.80 DN65 (73,0) (203,2) (169,2) (98,3) (274,3) 1-1/4 76,1 - 8.00 6.66 3.87 10.80 1_1/4 DN65 (76,1) (203,2) (169,2) (98,3) (274,3) 3 3.500 8.37 6.88 3.87 11.02 1-1/4 DN80 (88,9) (212,6) (174,8) (98,3) (279,9) 4 4.500 9.63 7.63 4.53 11.92 2 DN100 (114,3) (244,6) (193,7) (115,1) (302,7) 139,7 - 10.50 8.13 4.90 12.42 DN125 (139,7) (266,7) (206,4) (124,5) (315,4) 2 5 5.563 10.50 8.13 4.90 12.42 2 DN125 (141,3) (266,7) (206,4) (124,5) (315,4) 165,1 - 11.50 8.50 5.00 12.79 DN150 (165,1) (292,1) (215,8) (127,0) (324,8) 2 6 6.625 11.50 8.50 5.00 12.79 2 DN150 (168,3) (292,1) (215,8) (127,0) (324,8) 8 8.625 14.00 9.52 5.46 13.81 DN200 (219,1) (355,6) (241,7) (138,7) (350,7) 2 10 10.750 18.00 10.41 7.50 14.70 2 DN250 (273,1) (457,2) (264,3) (190,5) (373,3) 12 12.750 21.00 11.27 7.62 15.56 DN300 (323,9) (533,4) (286,1) (193,5) (395,2) 2 FIGURE 4 MODEL CV-1FR RISER CHECK VALVE WITH TRIM COMPONENTS NOMINAL DIMENSIONS TFP95O Page 5 of 6 P/N 59-591-1-020 2 Inch(DN50) NO. DESCRIPTION QTY. P/N 1 300 psi/2000 kPa NOTES: MAIN Water Pressure Gauge . .2 92-343-1-005 1. All Fittings and Nipples are DRAIN VALVE _ 2 1/4"Gauge Test Valve . .2 46-005-1-002 galvanized(Standard Order). (NORMALLY 3 1/4"Plu 2 CH CLOSED)9 2. CH:Common Hardware. tp,% �1 4 1"Angle Valve 1 46-048-1-006 \ �`�\,�'I l 5 1/4"x 2"Nipple 1 CH �` �`� 6 1/4"x 5"Nipple 1 CH 7 1"x 3" Nipple 1 CH 7 1 , 4 P/N 59-591-1-030 \\Ak -./ 2-1/2 Inch(DN65)through 3 Inch(DN80) e,.....,.,‘ NO. DESCRIPTION QTY. P/N 1 300 psi/2000 kPa SYSTEM Water Pressure Gauge . .2 92-343-1-005 PRESSURE 2 1/4"Gauge Test Valve . .2 46-005-1-002 ' �' 1 GAUGE ii1113 1/4"Plug 2 CH ,• /� 4 1-1/4"Angle Valve 1 46-048-1-007 SUPPLY 5 1/4"x 2"Nipple 1 CH 0 / — 2 PRESSURE 6 1/4"x 5"Nipple 1 CH ® GAUGE 7 1-1/4"x 3"Nipple 1 CH �; -/� 5 ��1.Mr 3 P/N 59-591-1-080 4 Inch(DN100)through 12 Inch(DN300) NO. DESCRIPTION QTY. P/N MODEL CV 1 FR /� 1 RISER CHECK 1 300 psi/2000 kPa VALVE 2 Water Pressure Gauge ..2 92-343-1-005 6 �< 2 1/4"Gauge Test Valve ..2 46-005-1-002 y��� � 3 - 3 1/4" Plug 2 CH k41' •�_/ 4 2"Angle Valve 1 46-048-1-009 ���� T® 5 1/4"x 2"Nipple 1 CH 6 1/4"x 5"Nipple 1 CH 7 2"x 3" Nipple 1 CH FIGURE 5 MODEL CV-1FR RISER CHECK VALVES TRIM PARTS LIST COVER OUTLET INLET N OUTLET 0.0 f FLOW dL•7 �� COVER INM �'�11111111"1 FLOW .• I .7, or sm.. '■ um INLET VERTICAL ORIENTATION HORIZONTAL ORIENTATION FIGURE 6 MODEL CV-1FR RISER CHECK VALVES INSTALLATION TFP95O Page 6 of 6 Care and Limited Maintenance Warranty Before closing a fire protection system For warranty terms and conditions,visit main control valve for maintenance www.tyco-fire.com. work on the fire protection system that it controls, obtain permission to shut down the affected fire protection sys- Ordering tem from the proper authorities and no- tify all personnel who may be affected Procedure by this decision. Contact your local distributor for avail- After placing a fire protection system ability.When placing an order, indicate in service, notify the proper authorities the full product name and Part Number and advise those responsible for moni- (P/N). toring proprietary and/or central station alarms. Model CV-1FR Check Valves Specify:Size and P/N(below). The owner is responsible for the in- spection,testing, and maintenance of 2"(DN50) P/N 59-590-1-020 their fire protection system and devic- 2-1/2"(DN65) P/N 59-590-1-025 es in compliance with this document, 76,1 mm(DN65) P/N 59-590-1-076 3"(DN80) P/N 59-590-1-030 as well as with the applicable stan- 4"(DN100) P/N 59-590-1-040 dards of the National Fire Protection 139,7 mm(DN125) P/N 59-590-1-139 Association(e.g., NFPA 25), in addition 5"(DN125) P/N 59-590-1-050 to the standards of any authority having 165,1 mm(DN150) P/N 59-590-1-165 jurisdiction. Contact the installing con- 6"(DN150) P/N 59-590-1-060 tractor or product manufacturer with 8"(DN200) P/N 59-590-1-080 any questions.Any impairments must 10"(DN250) P/N 59-590-1-100 be immediately corrected. 12"(DN300) P/N 59-590-1-120 Automatic sprinkler systems are recom- Model CV-1FR mended to be inspected, tested, and Riser Check Valve Trim Assembly maintained by a qualified Inspection Specify:Size and P/N(below). Service in accordance with local re- quirements and/or national codes. 2"(DN50) P/N 59-591-1-020 2-1/2"(DN65) P/N 59-591-1-030 76,1 mm(DN65) P/N 59-591-1-030 3"(DN80) P/N 59-591-1-030 4"(DN100) P/N 59-591-1-080 139,7 mm(DN125) P/N 59-591-1-080 5"(DN125) P/N 59-591-1-080 165,1 mm(DN150) P/N 59-591-1-080 6"(DN150) P/N 59-591-1-080 8"(DN200) P/N 59-591-1-080 10"(DN250) P/N 59-591-1-080 12"(DN300) P/N 59-591-1-080 GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. Vico Fire Protection Products tqcci 'Fire & Building Products Technical Services: Tel: (800)381-9312/Fax: (800)791-5500 www.tyco-fire.com Grinnell Grooved Fire Protection Products Grooved Fittings General Material: Limited Cast:Figures:201,210,219,250,260,501,510, Description 519,510DE,501S,510S and 519S- Warranty See Fire Protection Ductile iron conforming to ASTM A-536, Products manufactured by Tyco Fire Products are Vd S Submittal Sheet for Grade 65-45-12 warranted solely to the original Buyer for ten(10) ' Pressure Rating and Fabricated Steel: Figures 391, 392, 393, 312, years against defects in material and workmanship 45® Listing/Approval Information 313,321,327,341 and 350 Carbon Steel, when paid for and properly installed and maintained (Sizes 11/4"-6"are Schedule 40); ® (Sizes 8"-12"are Schedule 30), under normal use and service. This warranty will conforming to ASTM A-53 Grade B expire ten(10)years from date of shipment by Tyco The grooved fittings provide an economical Protective Coatings: Fire Products. Na manufacturedwarranty is gien for productsaesor and efficient method of changing direction, •Non-lead orange paint componby ents rshipwthTyco by companies s not addingan outlet, reducing, or capping •Fire brigade red(optional)non-leadpaint affiliated omson ntswhichh have eensubject pp g g ( p ) products and components which have been subject grooved piping systems. Grooved fittings •Hot dipped galvanized conforming to ASTM to misuse,improper installation,corrosion,orwhich are available in durable ductile iron or A-153 have not been installed, maintained, modified or fabricated steel as indicated. repaired in accordance with applicable Standards of Note: Figure 510S and 519S fittings are Ordering the National Fire Protection Association (NFPA), special short radius fittings with smaller and/orthe standards of any otherAuthorities Having center to end dimensions than standard Procedure Jurisdiction. Materials found by Tyco Fire Products grooved fittings. Depending on the size and When placing an order,indicate the full product to be defective shall be either repaired orreplaced,at coupling used,there may be interferences at name.Please specifythe quantity,figure number, Tyco Fire Products'sole option.Tyco Fire Products the bolt pads that require repositioning of the wall thickness,and size. neither assumes, nor authorizes any person to coupling orientation. The use of flange Grinnell Grooved Piping Products, valves, assumeforit,anyotherobligationinconnectionwith adapters is not recommended with Figures accessories and other products are available the sale of products or parts of products. Tyco Fire 510S and 519S fittings. Contact Tyco Fire throughout the U.S.,Canada,and internationally, Productsshallnotberesponsibleforsprinklersystem Products for details. through a network of distribution centers.You designerrorsorinaccurateorincompleteinformation WARNING may write directly or call 215-362-0700 for the supplied by Buyer or Buyer's representatives. The Fittings described herein must be installed distributor nearest you. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE and maintained in compliance with this document, LIABLE,IN CONTRACT,TORT,STRICT LIABILITY as well as with the applicable standards of the Care and OR UNDER ANY OTHER LEGAL THEORY, FOR National Fire Protection Association,in addition Maintenance INCIDENTAL, INDIRECT, SPECIAL OR to the standards of any other authorities having CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT jurisdiction. Failure to do so may impair the The owner is responsible for the inspection, LIMITED TO LABOR CHARGES,REGARDLESS OF performance of this device. testing,and maintenance of their fire protection WHETHERTYCOFIREPRODUCTSWASINFORMED The owner is responsible for maintaining their system and devices in accordance with the ABOUT THE POSSIBILITY OF SUCH DAMAGES, fire protection system and devices in proper applicable standards of the National Fire Protection AND IN NO EVENT SHALL TYCO FIRE PRODUCTS' operating condition. The installing contractor or Association (e.g., NFPA 25), in addition to the LIABILITY EXCEED AN AMOUNT EQUAL TO THE sprinkler manufacturer should be contacted with standards of any authority having jurisdiction. SALES PRICE. any questions. The installing contractor or product manufacturer 11EFOREGONGWARRANTY ISMADE INLIEU OF should be contacted relative to any questions. ANY MID ML O11AtWAMRANTIESEXPRESS OR Technical Any impairment must be immediately corrected. IMPLIED, INCLUDING WARRANTIES QF It is recommended that automatic sprinkler MERCHANTABILITY AND FITNESS FOR A Data systems be inspected,tested,and maintained by PARTICULAR PISPOSE. Approvals: a qualified Inspection Service. UL,FM,ULC,VdS,and LPCB; . Note: See Fire Protection Submittal Sheet for exact Listing/Approval information. Page 1 of 6 MARCH 2011 TFP1810 Page 2 of 6 TFP1810 Figures 201 , 210, 219, and 260 C to E 011-1-- , and 2 201 Elbow 90°Figure Elbow 210 Figure 219 Tee FigureEndCap 260$ _ Nominal C to E Appx.Wt. C to E Appx.Wt. C to E Appx.Wt. E to E Appx.Wt. Size Inches Lbs. Inches Lbs. Inches Lbs. Inches Lbs. Cie C to E mm Kg. mm Kg. mm Kg. mm Kg. L v =mom 1 1'/4" 1.75 0.9 2.75 1.0 2.75 1.4 0.88 0.4 i-C to E ,I 44.5 0.4 69.9 0.5 69.9 0.6 22.4 0.2 Fi ure 201 1'/2° 1.75 1.1 2.75 1.2 2.75 1.8 0.88 0.6 g Figure 210 44.5 0.5 69.9 0.5 69.9 0.8 22.4 0.3 2„ 2.00 1.8 3.25 2.0 3.25 2.7 0.88 0.9 50.8 0.8 82.6 0.9 82.6 1.2 22.4 0.4 2'/2" 2.25 2.2 3.75 3.0 3.75 5.8 0.88 0.9 !--ctoE� EtoE-1 572 1.0 95.3 1.4 95.3 2.6 22.4 0.4 " 76.1 mm 2.25 2.2 3.75 3.0 3.75 5.8 0.94 1.1 II 57.2 1.0 95.3 1.4 95.3 2.6 23.9 0.5 - -s o 2.50 3.5 4.25 4.5 4.25 7.0 0.88 1.1 0 63.5 1.6 108.0 2.0 108.0 3.2 22.4 0.5 C to E 108.0mm 2.88 5.5 4.75 8.5 4.75 11.5 - �� 1 Figure 260 73.0 2.5 120.7 3.9 120.7 5.2 3.00 5.2 5.00 8.5 5.00 11.8 1.00 2.6 4„ 76.2 2.4 1270 3.9 127.0 5.4 25.4 1.2 Figure 219 133.0mm 3.25 7.7 5.25 11.3 5.25 10.6 82.6 3.5 133.4 5.1 133.4 4.8 139.7mm 3.25 7.7 5.50 11.3 5.50 15.3 0.92 4.7 82.6 3.5 139.7 5.1 139.7 6.9 23.4 2.1 3.25 8.5 5.50 13.5 5.50 17.0 1.00 5.0 Friction Resistance* 5" 82.6 3.9 139.7 6.1 139.7 7.7 25.4 2.3 (Expressed as Equivalent Straight Pipe) 3.50 12.0 6.00 14.6 6.00 13.9 Elbow Tee 159.Omm 88.9 5.4 152.4 6.6 152.4 6.3 - - Size 90° 45° Branch Run 165.1 mm 3.50 12.0 6.50 18.5 6.50 26.0 1.00 7.5 Inches Feet Feet Feet Feet 88.9 5.4 165.1 8.4 165.1 11.8 25.4 3.4 . mm Meters Meters Meters Meters 3.50 12.0 6.50 18.5 6.50 26.0 1.00 7.5 11/4 1.9 1.0 4.8 1.9 6" 88.9 5.4 165.1 8.4 165.1 11.8 25.4 3.4 42.4 0.6 0.3 1.5 0.6 4.25 23.0 7.75 36.5 7.75 45.0 11/2 2.3 1.2 5.8 2.3 216.3mm 108.0 10.4 196.9 16.6 196.9 20.4 48.3 0.7 0.4 1.8 0.7 4.25 23.0 7.75 36.5 7.75 45.0 1.19 12.8 2 3.2 1.6 8.0 3.2 8" 108.0 10.4 196.9 16.6 196.9 20.4 30.2 5.8 60.3 1.0 0.5 2.5 1.0 4.75 31.0 9.00 60.0 9.00 72.1 1.25 20.0 21/2 3.9 2.0 9.8 3.9 10 120.7 14.1 228.6 27.2 228.6 32.7 31.8 9.1 73.0 1.2 0.6 3.0 1.2 5.25 40.0 10.00 67.0 10.00 92.5 1.25 36.0 4.1 2.1 10.3 4.1 12" 133.4 18.1 254.0 30.4 254.0 42.0 31.8 16.3 76.1 mm 1.2 0.6 3.1 1.2 3 4.9 2.4 12.2 4.9 # •Available with tapped plugs,contact Tyco Fire&Building Products. 88.9 1.5 0.7 3.7 1.5 108.0mm 6.5 3.3 16.3 6.5 2.0 1.0 5.0 2.0 4 6.5 3.3 16.3 6.5 114.3 2.0 1.0 5.0 2.0 133.0. 8.0 4.0 20.0 8.0 2.4 1.2 6.1 2.4 139.7mm 8.0 4.1 20.0 8.0 2.4 1.3 6.1 2.4 5 8.2 4.1 20.5 8.2 141.3 2.5 1.3 6.3 2.5 159.0. 9.5 4.8 23.8 9.5 2.9 1.4 7.2 2.9 9.5 4.8 23.8 9.5 I 165.1.m 2.9 1.4 7.2 2.9 6 9.9 5.0 24.8 9.9 _168.3 3.0 1.5 7.6 3.0 216.3mm 13.1 6.6 32.8 13.1 4.0 2.0 10.0 4.0 8 13.1 6.6 32.8 13.1 219.1 4.0 2.0 10.0 4.0 10 16.5 8.3 41.3 16.5 273.0 5.0 2.5 12.6 5.0 12 19.9 9.9 49.7 19.9 323.4 6.1 3.0 15.1 6.1 For reducing tees and branches,use the value that is corrosponding to the branch size.Example:for 8'x 8'x 2'tee,the branch value 2'is 8.0 feet. ' Friction resistance for all elbows and tees except Figures 510S and 519S. Page 3 of 6 TFP1810 Figures 501 , 510, 519 and 51 ODE CtoE aPI !�CtoE -I I I.. CtoIE GtoE f i- C v 1 CtoE D L --E 1 �� j A��E_11 • Figure 501 Figure 510 Figure 519 Figure 510DE Figure 501 Figure 510 Figure 519 Figure 510DE 45°Elbow 90°Elbow Tee 90°Drain Elbow Nominal C to E Appx.Wt. C to E Appx.Wt. C to E Appx.Wt. C to E A B Appx.Wt. Size Inches Lbs. Inches Lbs. Inches Lbs. Inches Inches Inches Lbs. mm Kg. mm Kg. mm Kg. mm mm mm Kg. 1,/0" 1.75 0.9 2.75 1.0 2.75 1.4 44.5 0.4 69.9 0.5 69.9 0.6 1'/2° 1.75 1.1 2.75 1.2 2.75 1.8 - - - - 44.5 0.5 69.9 0.5 69.9 0.8 2„ 2.00 1.8 3.25 2.0 3.25 2.7 - - - - 50.8 0.8 82.6 0.9 82.6 1.2 2'/z° 2.25 2.2 3.75 3.0 3.75 5.8 3.75 2.00 2.75 2.7 57.2 1.0 95.3 1.4 95.3 2.6 95.3 50.8 69.9 1.2 3„ 2.50 3.5 4.25 4.5 4.25 7.0 4.25 2.34 2.75 3.7 63.5 1.6 108.0 2.0 108.0 3.2 108.0 59.4 69.9 1.7 4„ 3.00 5.2 5.00 8.5 5.00 11.8 5.00 2.85 2.75 7.0 76.2 2.4 127.0 3.9 127.0 5.4 127.0 72.4 69.9 3.2 5„ 3.25 8.5 5.50 13.5 5.50 17.0 5.50 3.38 2.75 13.0 82.6 3.9 139.7 6.1 139.7 7.7 139.7 85.9 69.9 5.9 6„ 3.50 12.0 6.50 18.5 6.50 26.0 6.50 3.92 2.75 13.4 - 88.9 5.4 165.1 8.4 165.1 11.8 165.1 99.6 69.9 6.1 8„ 4.25 23.0 7.75 36.5 7.75 45.0 7.75 4.95 2.75 26.3 108.0 10.4 196.9 16.6 196.9 20.4 196.9 125.7 69.9 11.9 Figures 501S, 51OS and 519S CtoE ll- !iCtoEi CtoE CtoE L alt%�� Wil• 1 ' CtoE ice-C to E �� Figure 501S Figure 510S° Figure 519S° Figure 501S Figure 510S Figure 519S Friction Resistance 501S,510S&519S 45°Elbow 90°Elbow Tee (Expressed as Equivalent Straight Pipe) Nominal C to E Appx Wt. C to E Appx.Wt. C to E Appx.Wt. Elbow Tee Size Inches Lbs. Inches Lbs. Inches Lbs. Size 90° 45° Branch Run mm Kg. mm Kg. mm Kg. Inches Feet Feet Feet Feet 2" 2.00 1.8 2.75 1.5 2.75 2.1 mm Meters _ Meters Meters Meters 50.8 0.8 69.9 0.7 69.9 1.0 2 3.2 1.6 8.0 3.2 21/2° 2.25 2.2 3.00 2.2 3.00 3.0 60.3 1.0 0.5 2.5 1.0 57.2 1.0 76.2 1.0 76.2 1.4 21/2 3.9 2.0 9.8 3.9 76.1mm 2.25 2.2 3.00 2.3 3.00 3.1 73.0 1.2 0.6 3.0 1.2 57.2 1.0 76.2 1.0 76.2 1.4 4.1 2.1 10.3 4.1 3" 2.50 3.5 3.38 3.0 3.38 4.1 76.1 mm 1.2 0.6 3.1 1.2 63.5 1.6 85.9 1.3 85.9 1.9 3 4.9 2.4 12.2 4.9 4" 3.00 5.2 4.00 5.6 4.00 7.7 88.9 1.5 0.7 3.7 1.5 76.2 2.4 101.6 2.6 101.6 3.5 4 6.5 3.3 16.3 6.5 139.7mm 3.25 7.7 4.88 8.6 4.88 12.0 114.3 2.0 1.0 5.0 2.0 82.6 3.5 124.0 3.9 124.0 5.4 8.0 4.1 20.0 8.0 5„ 3.25 8.5 4.88 8.8 4.88 12.0 139.7mm 2.4 1.3 6.1 2.4 82.6 3.9 124.0 3.9 124.0 5.4 5 8.2 4.1 20.5 8.2 165.1 mm 3.50 12.0 5.50 11.00 5.50 15.0 141.3 2.5 1.3 6.3 2.5 88.9 5.4 139.7 5.0 139.7 6.8 9.5 4.8 23.8 9.5 6" 3.50 12.0 5.50 11.2 5.50 15.2 165.1 mm 2.9 1.4 7.2 2.9 88.9 5.4 139.7 5.1 139.7 6.9 6 9.9 5.0 24.8 9.9 8" 4.25 23.0 6.88 23.4 6.88 31.2 . 168.3 3.0 1.5 7.6 3.0 108.0 10.4 174.8 10.6 174.8 14.2 8 13.1 6.6 32.8 13.1 'Note:Figure 510S and 5195 fittings are special short radius fittings with smaller center to end dimensions 219.1 4.0 2.0 10.0 4.0 than standard grooved fittings.Depending on the size and coupling used,there may be Interferences at the bolt pads which requires repositioning of the coupling orientation.The use of flange adapters Is not recommended with Figures 510S and 519S fittings.Contact Tyco Fire Products for details. Page 4 of 6 TFP1810 Figures 250 and 350 Figures 250 and 350 Concentric Reducer-Groove x Groove Nominal E to E Appx.Wt. Nominal E to E Appx.Wt. Nominal E to E Appx.Wt. [4--E --. f- E to ESize Inches Lbs. Size Inches Lbs. Size Inches Lbs. II Inches mm Kg. Inches mm Kg. Inches mm Kg. - 2.50 1.0 3.50 4.2 4.00 5.8 '2x1'/4 63.5 0.5 '139.7mmx3 88.9 1.9 *6x5 101.6 2.6 12.2 '2x1,/z 2.50 1.3 *139.7mmX4 3.50 4.4 8x2 5.00 63.5 0.6 88.9 2.0 127.0 5.5 Figure *21/2x2 x 2.50 1.2 51/z 3.50 4.6 2,/z 5.00 12.1 g63.5 0.5 88.9 2.1 8 X 127.0 5.5 Cast 2.50 1.5 3.50 4.6 5.00 12.0 *76.1mmx11/2 63.5 0.7 5 x 2 88.9 2.1 8 x 3 127.0 5.5 2.50 1.6 3.50 4.5 5.00 11.9 �EtoE� *76.1mmx2 63.5 0.8 5X2'/z 88.9 2.0 8 x 4 127.0 5.4 3x1Y4 2.50 1.3 5 x 3 3.50 4.4 8 x 5 5.00 11.3 63.5 0.6 88.9 2.0 127.0 5.1 _-_------ 3x1Yz 2.50 1.3 *5 x 4 3.50 4.5 8 x 6 5.00 10.8 ___ 63.5 0.6 88.9 2.0 127.0 4.9 *3x2 2.50 1.3 *165.1mmx3 4.00 5.5 10x4 6.00 21.9 Figure 350 63.5 0.6 101.6 2.5 152.4 10.0 Fabricated *3 x 2Yz 3.00 1.5 *165.1mm x 4 4.00 6.0 10 x 5 6.00 21.6 Sizes 3"to 6" 76.2 0.7 101.6 2.7 152.4 9.8 *3 x 76.1 mm 3.00 2.0 '1651 1397 4.00 5.6 6 6.00 21.1 76.2 0.9 . mn x . m� 10 x 101.6 2.5 152.4 9.6 E to E-1 3.00 2.2 4.00 6.0 6.00 19.5 4x11/4 76.2 1.0 *6x2 101.6 2.7 10x8 152.4 8.9 �_�� 4 x 1'/z 3.00 2.3 6 x 2'/z 4.00 6.0 12 x 4 7.00 28.0 I 76.2 1.0 101.6 2.7 177.8 12.7 30.0 '4x2 3.00 2.3 *6x76.1 mm 4.00 6.0 12x6 7.00 76.2 1.0 101.6 2.7 177.8 13.6 Figure 350 • 3.00 2.3 4.00 6.0 7.00 28.0 Fabricated *4 x 21/2 76.2 1.0 6 x 3 101.6 2.7 12 x 8 177.8 12.7 Sizes 8"to 12" 3.00 • 3.2 4.00 5.9 7.00 33.0 *4x76.1mm 76.2 1.5 *6x4 101.6 2.7 12 X 10 177.8 15.0 . 4 x 3 3.00 2.6 '6 139.7mm 4.00 6.3 x 76.2 1.2 101.6 2.9 Note:Sizes marked with an asterisk(')are only available in Figure 250 Cast. Sizes without an asterisk are only available in Figure 350 Fabricated. ADA CAP® Pipe Nominal Dimensions Size Outlet t 0.D. TakBeout Center to EDnd Wt. Inches NPT* Inches Inches Inches Inches Lbs. Dpi Inchesmm mm mm mm Kg• 1-----== 1/2 1.25 1.75 1.89 0.77 } 31.8 44.5 48.0 0.3 1.900 1.25 1.75 1.89 0.77 AmeC 1'/2 3/4 48.3 31.8 44.5 48.0 0.3 B 1 1.37 2.00 2.02 0.88 34.8 50.8 51.3 0.4 EI. 1.25 1.75 1.89 0.92 1/2 31.8 44.5 48.0 0.4 2 3/4 2.375 1.25 1.75 1.89 0.92 60.3 31.8 44.5 48.0 0.4 1 1.37 2.00 2.02 1.06 34.8 50.8 51.3 0.5 1/2 1.47 1.97 1.89 1.28 37.3 50.0 48.0 0.6 21/2 3/4 2.875 1.47 1.97 1.89 1.28 73.0 37.3 50.0 48.0 0.6 1 1.37 2.00 2.02 1.50 34.8 50.8 51.3 0.7 • ISO-7 threaded outlets are available upon request. Page 5 of 6 TFP1810 Figures 391 , 392, 393, 312 and 313 1 E to E--.{ Figures 391, Figure 312 Figure 313 -_ 392 and 393 221/2°Elbow 111/4°Elbow Adapter Nipples Figure E to E Appx.Wt. C to E Appx.Wt. C to E Appx.Wt. Nominal Inches Lbs. Inches Lbs. Inches Lbs. Size mm Kg. mm Kg. mm Kg. 4.0'-'~ E to E� 11/4• 101.6 0.8 44.1.75 0.4 35.11.38 0.4 0.4 44.5 0.2 35.1 0.2 _ 11/z" 4.00 0.9 1.75 0.5 1.38 0.5 Figure 101.6 0.4 44.5 0.2 35.1 0.2 392 - - - - - - 2„ 4.00 1.2 1.88 0.6 1.38 0.6 101.6 0.5 47.8 0.3 35.1 0.3 2'/z" 4.00 1.9 2.00 0.7 1.50 1.1 he -,- 101.6 0.9 50.8 0.3 38.1 0.5 3„ 4.00 2.5 2.25 1.4 1.50 1.2 101.6 1.1 57.2 0.6 38.1 0.5 Figure 6.00 5.5 2.63 2.4 1.75 2.2 393 4„ 152.4 2.5 66.8 1.1 44.5 1.0 2.00 3.3 5„ 6.00 7.4 2.88 4.1 152.4 3.4 73.2 1.9 50.8 1.5 C to E 6° 6.00 9.5 3.13 5.6 2.00 4.6 c to* 6" 152.4 4.3 79.5 2.5 50.8 2.1 Figure 6.00 14.2 3.88 11.1 2.00 8.7 312 8 152.4 6.4 98.6 5.0 50.8 3.9 CtoE� 8.00 27.0 4.38 14.0 2.13 9.1 I- 10 203.2 12.2 11.3 6.4 54.1 4.1 8.00 33.0 4.88 22.0 2.25 C to E 12 Figure 203.2 15.0 124.0 10.0 57.2 16.7 7.6 - CtoE 313 Figures 327 and 341 --C to E--,- Figure 327 Figure 341 I1 i Cross 150 lbs. Flange Adapter Nominal C to E Appx.Wt. E to E Appx.Wt. Size nches Lbs. Inches Lbs. mm kg. mm kg. t 11/4" 2.75 2.0 4.00 2.8 69.6 0.9 101.6 1.3 C to E 11/2, 2.75 2.2 4.00 3.2 69.9 2.0 101.6 1.5 1 2„ 3.25 2.7 4.0 5.2 Figure 327 82.6 1.2 101.6 2.4 21/2" 3.75 5.0 4.00 8.0 95.3 2.3 101.6 3.6 4.25 7.1 4.00 10.2 3„ 108.0 3.2 101.6 4.6 5.00 11.9 6.00 17.2 II 1 II 4„ 127.0 5.4 152.4 7.8 I i 5„ 5.50 17.1 6.00 21.4 E to E 139.7 7.8 152.4 9.7 6.50 i i I 6 165.1 12.527.5 152.46.0026.0 11.8 7.75 47.0 6.00 38.4 8„ Figure 341 196.9 21.3 152.4 17.4 9.00 68.0 8.00 65.0 10" 228.6 30.8 203.2 29.5 12" 10.00 107.0 8.00 91.0 . 254.0 48.5 203.2 41.3 Page 6 of 6 TFP1810 Figure 321 • I---ctoE---H Figure 321 Reducing Tee I - Nominal C to E Appx.Wt. Nominal C to E Appx.Wt. --I________ Size Inches Lbs. Size Inches Lbs. -I Inches mm Kg. Inches mm Kg. j 11/2x11/2x11/4 3.25 2.0 6x6x4 6.50 26.6 C to E 82.6 0.9 165.1 12.1 t i3.25 2.7 6.50 27.0 2x2x1,/z 82.6 1.2 6x6x5 165.1 12.2 Figure 321 2Y2x2Y2x1'/a 3.75 4.2 8x8x2 7.75 36.2 95.3 1.9 196.9 16.4 21/2x2'x11/2 3.75 4.2 8x8x3 7.75 36.5 95.3 1.9 196.9 16.6 21/2x21/2x2 3.75 4.3 8x8x4 7.75 36.6 95.3 2.0 196.9 16.6 3x3x1'/z 4.25 5.3 gx8x5 7.75 36.8 108.0 2.4 196.9 16.7 4.25 5.5 7.75 37.0 3x3x2 108.0 P.5 8x8x6 196.9 16.8 3x3x2'/2 4.25 5.8 10x10x2 9.00 57.1 108.0 2.6 228.6 25.9 4x4x1'/a 5.00 9.8 10x10x3 9.00 57.4 127.0 4.4 228.6 26.0 4x4x11/2 5.00 9.9 10x10x4 9.00 57.6 127.0 4.5 228.6 26.1 4x4x2 5.00 10.1 10x10x5 9.00 57.8 127.0 4.6 228.6 26.2 4x4x2' 5.00 10.3 10x10x6 9.00 58.0 127.0 4.7 228.6 26.3 4x4x3 5.00 10.5 10x10x8 9.00 58.4 127.0 4.8 228.6 26.5 5x5x2 5.50 14.5 12x12x3 10.00 80.2 139.7 6.6 254.0 36.4 5x5x21/2 5.50 14.8 12x12x4 10.00 80.5 139.7 6.7 254.0 36.5 - 5x5x3 5.50 15.2 12x12x5 10.00 80.7 139.7 6.9 254.0 36.6 5x 5x4 5.50 15.8 12 x 12 x 6 10.00 80.9 139.7 7.2 254.0 36.7 6x6x2 6.50 26.5 12x12x8 10.00 91.4 165.1 11.9 254.0 41.5 6x6x21/2 6.50 26.5 12 x 12 x 10 10.00 91.8 165.1 12.0 254.0 41.6 6x6x3 6.50 26.5 165.1 12.0 General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure ISO that pressure ratings and performance data is not exceeded.Always read and understand the installation instructions 9001' / (IH-1000). Never remove any piping component or correct or modify any piping deficiencies without first icy` depressurizing and draining the system. Material and gasket selection should be verified to be compatible for the `/ specific application. Certified Company TYCO FIRE PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19946 Printed U.S.A. tilcoWorldwide Fire Protection Contacts www.tyco-fire.com Products GRINNELL G-FIRE Figure 705 Grooved Flexible Coupling 1 to 12 Inch (DN25 to DN300) General Technical Description Data The GRINNELL G-FIRE Figure 705 Approvals Grooved Flexible Couplings, when UL and ULC Listed properly installed, provide a depend- FM Approved VdS A able method of joining pipe, allowing App Nos. 669a and for angular and linear deflection, ther- LPCB(Cert. 673a) mal expansion and contraction, and Refer to Table A for details misalignments of the pipe. Sizes Figure 705 couplings are rated at pres- 1 to 12 Inch(DN25 to DN300) sures up to 300 psi (20,7 bar)depend- ing on pipe size and wall thickness Housing when used in fire protection service Ductile Iron conforming to ASTM applications.(Refer to Table A.) A536,Grade 65-45-12 1),L 41) 11111> Finish APPROVED NOTICE • Orange, non-lead paint VdS LPCB The GRINNELL G-FIRE Figure 705 • Red, non-lead paint Grooved Flexible Coupling described • Hot-dipped,Galvanized conforming herein must be installed and main- For Fire Protection pressure rating, tamed in compliance with this docu- to ASTM A153 listing,and approval information,contact pyour TYCO Representative. ment and with the applicable stan- Bolts/Nuts dards of the National Fire Protection • ANSI: Association, in addition to the stan- Carbon Steel oval neck track head Gaskets dards of any authorities having juris- bolts are heat-treated and conform • Pre-lubricated Grade"A"EPDM, diction. Failure to do so may impair the to the physical properties of ASTM Violet color code, performance of these devices. A183 Grade 2 and SAE J429 Grade -30°F to 150°F(-34°C to 66°C) Never remove any piping component 5 with a minimum tensile strength of For dry and freezer systems,lubrica- nor correct or modif anyi in defi- 110,000 psi. tion is required. Refer to Installation y p ping ciencies without first de-pressurizing Carbon Steel heavy hex nuts con- Manual IH-1000FP for details. and draining the system. Failure to do form to the physical properties of • Tri-Seal Grade"E" EPDM, so may result in serious personal inju- ASTM A183 Grade 2 and SAE J995 Green color code, ry, property damage, and/or impaired Grade 5. Bolts and nuts are zinc- -30°F to 230°F(-34°C to 110°C) device performance. electroplated conforming to ASTM B633. For proper gasket selection, refer to It is the designer's responsibility to se- Technical Data Sheet TFP1895. lect products suitable for the intended Stainless Steel Bolts and Nuts are service and to ensure that pressure available upon request. ratings and performance data are not • Metric: exceeded. Material and gasket selec- Carbon Steel oval neck track head tion should be verified to be compat- bolts(Gold color coded) are heat- Thole for the specific application.Always treated and conform to the physical read and understand the installation properties of ASTM F568M with a instructions. minimum tensile strength of 760 The owner is responsible for main- MPa. taining their fire protection system Carbon Steel heavy hex nuts con- and devices in proper operating con- form to the physical properties of dition. Contact the installing contrac- ASTM A563 M Class 9. Bolts and tor or sprinkler manufacturer with any nuts are zinc-electroplated con questions. forming to ASTM B633. Page 1 of 4 NOVEMBER 2014 TFP1820 TFP182O Page 2 of 4 'ii Nominal Pipe Size d Deflections Nominal Dimensions Coupling Bolts Max.b Max.b Max. Approx. ANSI O.D. Pressures End Load Gap Degrees Inches/ A B C Sized Weight Inches Inches psi Lbs. Inches per Foot Inches Inches Inches Qty. Inches Lbs. (DN) (mm) (bar) (kN) (mm) Coupling (mm/m) (mm) (mm) (mm) (metric) (kg) 1 1.315 300 407 0.135°30' 1.16 2.24 3.94 1.81 2 3/8 x 2-1/4 1.3 (25) (33,7) (20,7) (1,81) (3,3) (96,7) (56,9) (100,1) (46,0) (M10 x 57) (0,6) 1-1/4 1.660 300 649 0.134°19, 0.90 2.56 4.19 1.81 2 3/8 x 2-1/4 1.5 (32) (42,4) (20,7) (2,88) (3,3) (75,0) (65,0) (106,4) (46,0) (M10 x 57) (0,7) 1-1/2 1.900 300 850 0.133°46' 0.79 2.75 4.44 1.81 2 3/8 x 2-1/4 1.6 (40) (48,3) (20,7) (3,78) (3,3) (65,8) (69,9) (112,8) (46,0) (M10 x 57) (0,7) 2 2.375 300 1,328 0.133°1, 0.63 3.25 4.88 1.88 2 3/8 x 2-1/4 1.7 (50) (60,3) (20,7) (5,90) (3,3) (52,5) (82,6) (124,0) (47,8) (M10 x 57) (0,8) 2-1/2 2.875 300 1,947 0.132°29. 0.52 3.69 5.50 1.88 2 3/8 x 2-1/4 2.0 (65) (73,0) (20,7) (8,66) (3,3) (43,3) (93,7) (139,7) (47,8) (M10 x 57) (0,9) 76,1mm 3.000 300 2,120 0.132°23' 0.50 4.00 5.75 1.88 2 (M12 x 76) 3.1 (65) (76,1) (20,7) (9,43) (3,3) (41,7) (101,6) (146,10) (47,8) (1,4) 3 3.500 300 2,885 0.130.43 4.38 6.50 1.88 1/2 x 3 3.1 (80) (88,9) (20,7) (12,83) (3,3) 2°3 (35,8) (111,3) (165,1) (47,8) 2 (M12 x 76) (1,4) 108,0mm 4.250 300 4,256 0.250.70 5.50 7.50 2.06 (M12 x 76) 4.2 (100) (108,0) (20,7) (18,93) (6,4) 3°22' (58,3) (139,7) (190,5) (52,3) 2 (1,9) . 4 4.500 300 4,769 0.250.67 5.69 7.75 2.06 1/2 x 3 4.0 (100) (114,3) (20,7) (21,21) (6,4) 3°11' (55,8) (144,5) (196,9) (52,3) 2 (M12 x 76) (1,8) 133,0mm 5.250 300 6,494 0.250.56 6.56 9.50 2.06 7.2 (125) (133,0) (20,7) (28,88) (6,4) 2°44' (46,7) (166,6) (241,3) (52,3) 2 (M16 x 83) (3,3) 139,7mm 5.500 300 7,127 0.250.55 6.81 9.75 2.06 (M16 x 83) 7.2 (125) (139,7) (20,7) (31,70) (6,4) 2°36' (45,5) (173,0) (247,7) (52,3) 2 (3,3) 5 5.563 300 7,288 0.252°35 0.54 6.88 9.75 2.06 2 5/8 x 3-1/4 7.1 (125) (141,3) (20,7) (32,41) (6,4) (45,0) (174,8) (247,7) (52,3) (M16 x 83) (3,2) 159,0mm 6.250 300 9,204 0.252°17, 0.48 7.56 10.31 2.06 2 (M16 x 83) 7.4 (150) (159,0) (20,7) (40,93) (6,4) (40,0) (192,0) (261,9) (52,3) (3,4) 165,1mm 6.500 300 9,950 0.252°12' 0.46 7.75 10.69 2.06 2 (M16 x 83) 7.1 (150) (165,1) (20,7) (44,25) (6,4) (38,3) (196,9) (271,5) (52,3) (3,2) 6 6.625 300 10,336 0.250.45 7.94 10.69 2.06 5/8 x 3-1/4 7.1 (150) (168,3) (20,7) (45,97) (6,4) 2°10' (37,5) (201,7) (271,5) (52,3) 2 (M16 x 83) (3,2) 8 8.625 300 17,519 0.251°40, 0.35 10.19 13.56 2.50 2 3/4 x 4-3/4 14.5 (200) (219,1) (20,7) (77,92) (6,4) (29,2) (258,8) (344,4) (63,5) (M20 x 121) (6,6) 10e 10.750 250 22,679 0.25 1°20' 0.28 12.69 16.38 2.63 2 1 x 6-1/2 28.0 (250) (273,0) (17,2) (100,8) (6,4) (23,3) (322,3) (416,1) (66,8) (M24 x 165) (12,7) 12e 12.750 250 31,903 0.250 23 14.94 18.88 2.63 1 x 6-1/2 36.5 (300) (323,9) (17,2) (141,9) (6,4) 1°7 (19,2) (379,5) (479,6) (66,8) 2 (M24 x 165) (16,6) a. Maximum available gap between pipe ends.Minimum gap=0. b. Maximum pressure and end load are total from all loads based on standard weight steel pipe.Pressure ratings and end loads may differ for other pipe materials and/or wall thickness.Contact your TYCO Representative for details. c. Gold color coded metric bolts and nuts are available upon request. d. Max End Gap and Deflection is for cut grooved standard weight pipe.Values for roll grooved pipe will be 12 that of cut grooved. e. For 10 and 12 inch sizes where VdS Approval or LPCB Certification is required,refer to Figure 707,Technical Data Sheet TFP1840. FIGURE 1 G-FIRE FIGURE 705 GROOVED FLEXIBLE COUPLING, 1 TO 12 INCH(DN25 TO DN300) NOMINAL DIMENSIONS TFP182O Page 3 of 4 Pressure Rating Pipe Sizes Pipe psi Nominal ANSI Inches Schedule° (bar) (0.D.mm) UL ULC FM 300 300 300 1 (33,7); 1-1/4(42,4);1-1/2(48,3); 10 (20,7) (20,7) (20,7) 2(60,3);2-1/2(73,0);3(88,9);4(114,3); 5(141,3);6(168,3);8(219,1)a 40 300 00 300 (20,7) (20,7) 10 250 250 300 10(273,0)8 (17,2) (17,2) (20,7) 40 250 250 300 (17,2) (17,2) (20,7) 10 250 250 250 12(323,9)b (17,2) (17,2) (17,2) 40 250 250 250 (17,2) (17,2) (17,2) Pressure Rating Pipe O.D. Pipe psi (bar) mm Specification` UL FM ISO 4200 Type D and E 300 - (20,7) 76,1 EN 10255 Heavy - 300 (20,7) EN 10255 Medium - 300 (20,7) ISO 4200 Type E 300 - (20,7) 108,0;133,0;139,7;159,0 EN 10255 Heavy - 300 (20,7) EN 10255 Medium - 300 (20,7) 2.5 mm Wall Thickness 300 - (20,7) 165,1 EN 10255 Heavy - 300 (20,7) EN 10255 Medium - 300 (20,7) Pressure Rating Pipe Sizes Pipe psi Nominal ANSI Inches bar) (O.D.mm) Specifications LPCB VdS 1-1/4(42,4);1-1/2(48,3);2(60,3); ISO 65 Medium 290 -(76,1);3(88,9);4(114,3); -(165,1) (20) 6(168,3);8(219,1) ISO 4200 Wall Thickness 5,4 mm 290 - (20) 1-1/4(42,4);1-1/2(48,3);2(60,3); - (76,1); DIN 2448 or 2548 232 3(88,9);4(114,3); -(139,7);6(168,3);8(219,1) (16) a. For 8 and 10 inch sizes,minimum allowed pipe wall thickness is 0.188 inches b. For 12 Inch,Schedule 30 is minimum allowed pipe wall thickness by UL and ULC.0.250 inch wall thickness is the minimum allowed by FM c. See Agency website for Listing/Approvals of other pipe specifications: UL Website-see Online Certificate Directory,www.ul.com FM Global Website-www.approvalguide.com d. See Agency website for Listing/Approvals of other pipe specifications: LPCB Website-see Search Our Listings-Automatic Sprinklers,Water Spray and Deluge Systems,www.redbooklive.com VdS Website-see certifications,www.vds.de TABLE A LISTED/APPROVED PRESSURE RATINGS TFP182O Page 4 of 4 Care and Limited Maintenance Warranty The GRINNELL G-FIRE Figure 705 For warranty terms and conditions, Grooved Flexible Coupling must be visit www.tyco-fire.com. maintained in accordance with this section. Ordering Before closing a fire protection system main control valve for maintenance Procedure work on the fire protection system that it controls, obtain permission to shut GRINNELL Products are available down the affected fire protection sys- globally through a network of distribu- tem from the proper authorities and tion centers. For the nearest distribu- notify all personnel who may be affect- tor, visit www.tyco-fire.com. When ed by this decision. placing an order, indicate the full prod- After placing a fire protection system uct name. in service, notify the proper authorities Specify: G-FIRE Figure 705 Grooved and advise those responsible for moni- Flexible Coupling, quantity, pipe size toring proprietary and/or central sta- (Nominal ANSI or O.D.), finish (Or- tion alarms. ange, Red, or Galvanized), and type of The owner is responsible for the in- gasket: spection, testing, and maintenance of • Pre-lubricated Grade"A"EPDM their fire protection system and devic- • Tri-Seal Grade"E"EPDM es in compliance with this document, as well as with the applicable stan- dards of the National Fire Protection Association(e.g., NFPA 25), in addition to the standards of any authority hav- ing jurisdiction. Contact the installing contractor or product manufacturer with any questions. Any impairments must be immediately corrected. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. Niko Fire Protection Products - tLICIS Worldwide www.tyco-fire.com Fire Protection Contacts Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers " " -,- Description described herein must be installed and .-.-- maintained in compliance with this doc- ` The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable Upright(TY313)and Pendent(TY323) standards of the National Fire Protec- Sprinklers described in this data sheet tion Association,in addition to the stan- ' 't' k are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair ',,,- k . sprinklers designed for use in light or the performance of these devices. "!~ -•• ordinary hazard,commercial occupan • - cies such as banks, hotels,and shop- The owner is responsible for maintain ' fillt4St- - ping malls. ing their fire protection system and devices in proper operating condition. The recessed version of the Series TY- The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: S rinkler .� • A two-piece Style 15 Recessed p Escutcheon with recessed adjust- Identification `� x ment up to 5/8 inch (15,9 mm)from ` 4`'' �_ the flush pendent position. Number (SIN) �1� n�:,�� • A two-piece Style 20 Recessed Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2"NPT ft. , ment up to 1/2 inch (12,7 mm)from TY323 Pendent 5.6K, 1/2"NPT x- the flush pendent position. , , --- The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series Approvals 175°F(79°C) TY-FRB Sprinklers are described in UL and C-UL Listed 286°F(9 1 C)) Technical Data Sheet TFP357. Sprin- FM,LPCB,and VdS Approved kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler: Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi(12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper *The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psi112(80,6 LPM/bar112) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- • ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* firei$ 0-M:. ' irp-r—LET—i-\m -_..-_.—..--:---- / 5 =l 7/16" i. �R_ 4 I NOMINAL 2" ��I c R v MAKE IN 14 (50,8 mm) \ 1 2 p! r, 2" \_ [I/ 1-3/8" 3 fi (50,8 mm) (34,9 mm) I WRENCH 1 / , 1 _ FLATS - 1/2" NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(7Y323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE L. Operation Installation WRENCH RECESS The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, ,...17°. expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. glass bulb, allowing the sprinkler to activate and water to flow. General Instructions FIGURE 2 Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air WRENCH bub- Criteria ble should be present. The diameter RECESSRof the air bubble is approximately 1/16 The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and Upright(TY313)and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) ��1 Sprinklers are intended for fire protec- temperature ratings. /� tion systems designed in accordance with the standard installation rules rec A leak-tight 1/2 inch NPT sprinkler joint ognized by the applicable Listing or should be obtained by applying amin- Approval agency(such as, UL Listing min- imum to maximum torque of 7 to 14 is based on the requirements of NFPA ft.-lbs. (9,5 to 19,0 Nm). Higher levels �rill. t � 13, and FM Approval is based on the of torque can distort the sprinkler Inlet requirements of FM's Loss Prevention with consequent leakage or impairment PUSH WRENCH Data Sheets).Only the Style 15 or Style of the sprinkler. IN TO ENSURE 20 Recessed Escutcheon is to be used Do not attempt to compensate for ENGAGEMENT for recessed pendent installations. insufficient adjustment in the Escutch- WITH SPRINKLER WRENCHING AREA eon Plate by under-or over-tightening the sprinkler. Re-adjust the position of FIGURE 3 the sprinkler fitting to suit. W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP772 Page 3 of 4 Step 3. Tighten the sprinkler into the 2-7/8" DIA. sprinkler fittingusingonlythe W-Type - P YP 6 Sprinkler Wrench(Figure 2.With ref- erence (73,0mm) P ( 9 ) to Figure 1,apply the W-Type 6 2-1/4" DIA. Sprinkler Wrench to the wrench flats. - FACE OF (57,2 mm) Torque sprinklers 7 to 14 ft.-lbs.(9,5 to SPRINKLER 19,0 Nm). FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers i \ - FLUSH _ The Series TY-FRB Recessed Pendent 3/8±5/16" �` "/ —1 Sprinklers must be installed in accor- (9,5±7,9 mm) L dance with the following instructions. } / i, r' Step A.After installing the Style 15 or MOUNTING '-, 1/8" Style 20 Mounting Plate over the sprin- SURFACE (3,2 mm) kler threads, and with pipe-thread --- I sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the TY-FRB PLATE sprinkler fitting. 3/4"(19,1 mm) Step B. Tighten the sprinkler into the FIGURE4 sprinkler fitting using only the W-Type SERIES TY-FRB RECESSED PENDENNT SPRINKLER ASSEMBLY(TY323) 7 Recessed Sprinkler Wrench (Fpe WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON 3).With reference to Figure 1,apply the W-Type 7 Recessed Sprinkler Wrench 1 to the sprinkler wrench flats. Torque 2-7/8" DIA. - sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 (73,0 mm) Nm). FACE OF Step C.After ceiling installation and fin- SPRINKLER __2-1/4" DIA. - . ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- 5/16±1/4" 1/2"(12,7 kler and push the Closure over the (7,9±6,4 mm) mm) Mounting Plate until its flange comes in + NI FLUSH . contact with the ceiling. Care and 1 / - MOUNTING op 1/8" j Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, -_�_`_. 1 Upright(TY313)and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE 7/8"(22,2 mm) viced in accordance with this section. FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hay- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any questions. Absence of the outer piece of an if they cannot be completely cleaned Automatic sprinkler systems are rec- escutcheon, which is used to cover by wiping the sprinkler with a cloth or ommended to be inspected, tested, a clearance hole, can delay sprinkler by brushing it with a soft bristle brush. and maintained by a qualified Inspec- operation in a fire situation. Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. klers are not used for hanging any after installation. Sprinklers damaged objects and that the sprinklers are only by dropping, striking, wrench twist/ cleaned by means of gently dusting slippage,or the like,must be replaced. with a feather duster; otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad- cracked bulb or that has lost liquid from vertent operation may result. its bulb.(Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the . ing or exhibiting visible signs of corro- inspection,testing,and maintenance of sion must be replaced. their fire protection system and devices in compliance with this document, as Automatic sprinklers must never be well as with the applicable standards - painted, plated, coated, or other- of the National Fire Protection Associa- wise altered after leaving the factory. tion (e.g., NFPA 25), in addition to the TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 g PURE WHITE(RAL9010)"' 155 155°F(68°C) POLYESTER 371 5.6K PENDENT(1/2"NPT) TY323 q SIGNAL WHITE(RAL9003) 175 175°F(79°C) POLYESTER .Use suffix"I"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F(93°C) for example,77-370-4-175-I Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order, indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent(specify) Sprinkler, SIN (specify), K=5.6,Quick Response, (specify)tem- perature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish, P/N(specify*) Specify: Style 20 Recessed Escutch- eon with(specify*)finish,P/N(specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. *ICO TEFLON is trademark of The DuPont Corporation. Fire Protection Products Dyna-Thread® • Full Line Sch-40 Replacement Dyna-Thread® offers the life expectancy of Sch40 with superior hydraulics and greater value. Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages. Comparison to Schedule 40 Comparison to L.W.T. Pipes • Dyna-Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread to 3.6%larger than Sch-40 giving it weight,Dyna-Thread reduces (CRR=1.00)gives Dyna-Thread superior hydraulics.And,when used installation fatigue and is ideal for better life expectancy than lightwall in combination with Dyna-Flow pipe, retro-fit applications. threadable pipe joints. down sizing often occurs. Corrosion Resistance Ratio(CRR)is a • Unlike lightwall threadable pipe, • Dyna-Thread is fully listed and UL(Underwriters Laboratory)term for Dyna-Thread has no thread gauge approved by UL,ULC, and FM for the estimated life expectancy of a pipe warning. fire sprinkler applications. joint.This is based on the calculated wall thickness at the base of the first • DynaThread is approved for • The life expectancy of Dyna-Thread standard hanger spacing(15 ft. based on the exposed thread, assumed to be the and Sch-40 are equal weakest point of the pipe length.Dyna- calculated can be used as earthquake calculated wall thicknesses per UL. sway bracing, and is safe to use as • Thread and Sch-40 have the same drops. • The consistent quality of steel used to calculated wall thicknesses at this point make Dyna-Thread facilitates smooth and are both assigned the same CRR of • Dyna-Thread is safer to weld on. _ threading and lower maintenance 1.00. costs. • Dyna-Thread is more widely accepted than lightwall threadable • The exterior of Dyna-Thread is The internal surface of all black Allied where Sch-40 is specified. protected by a clean, durable mill Tube&Conduit Fire Sprinkler pipe coating for extended shelf life and products up to 4.5000"in diameter is easy paint application. coated with our new Antibacterial Formula, `ABF". In scientific laboratory test,ABS proved to have superior Specifications & Approvals resistance to microbial colonization of 41) ® U LC pipe walls,thereby delaying or possibly Super 40/Dyna-Thread pipe is preventing the onset of manufactured to meet:ASTM A-135, Microbiologically Influenced corrosion Grade A and is in compliance with Listed Approved Listed NFPA-13.All sizes of Super 40/Dyna- (MIC)when the First Sprinkler System is first installed. Thread are rated at 300 psi working pressure. Super 40/Dyna-Thread is UL Specifications and ULC Listed for wet, dry deluge and pre-action sprinkler systems and FM NPS Nominal I.D. Wt. Wt.(H20 Filled) Pcs/ Wt/Lift(211 Wt/Litt(24') Wt/Lift(25') Approved for use in wet systems. Super In;mm In;mm Lbs/Ft,Kg/m Lbs/Ft,•Kg/m Lift Lbs;Kg Lbs;Kg Lbs;Kg 40/Dyna-Thread can be"hot-dip" 1" 1.080 1.330 1.75 70 1955 2234 2327 galvanized to meet FM requirement for 25 274 2.0 2.60 70 887 1013 1056 dry systems. Super 40/Dyna-Thread is 1W 1.408 1.870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 35.8 2.8 3.78 51 908 1038 1081 welded outlets and is suitable for all 11/z" 1.639 2.290 3.22 44 2115 2418 2519 roll-grooved, and plain-end fittings. 40 41.6 3.4 4.79 44 959 1097 1143 (See listing information). 2" 2.104 3.050 4.57 30 1921 2196 2287 50 53.4 4.5 6.80 30 871 996 103? • NCO/Flow Control allied 16100 S. Lathrop• Harvey, IL 60426 Customer Service: `,J 11350 Norcom Rd. • Philadelphia, PA 19154 (800)882-5543 TUBE&CONDUIT 2525 N. 27th Ave. • Phoenix,AZ 85009 Fax 708-339-1806 S3 - 3 Dyna-Flow® High Strength Steel Pipe The original high-strength lightwall sprinkler pipe with hydraulics superior to Schedule-10. Dyna-Flow pipe is the"original"high- Specifications strength lightwall sprinkler pipe. Dyna- Flow has outstanding hydraulic NPS Nominal I.D. W1. Wt.(H20 Filled) Pcs/ Wt/Lift(21') Wt/Lift(24') Wt/Lift(25') capabilities and is recognized as the In;mm /n;mm Lbs/Ft;Kg/m Lbs/Ft,;Kg/m Lift Lbs;Kg Lbs;Kg Lbs;Kg most popular alternative to Schedule-10 1" 1.191 0.830 1.31 91 1,586 1,812 1,888 pipe. Lightweight, easy to cut and easy 25 30.3 1.2 1.95 91 719 822 856 to handle for installation. Dyna-Flow is a 11/4" 1.536 1.059 1.87 61 1,356 1,550 1,615 valuable addition to any fire protection 32 39.0 1.6 2.78 61 615 703 733 system. 1W 1.728 1.667 2.71 61 2,135 2,440 2,542 Superior Hydraulics 40 43.9 2.5 4.03 61 968 1107 1153 2" 2.203 2.104 3.79 37 1,634 1,868 1,946 With an inside diameter of up to 11% 50 56.0 3.1 5.64 37 741 847 883 larger than Schedule-40 and up to 7% 21/2" 2.703 2.564 5.10 30 1,615 1,846 1,923 larger than Schedule-10, Dyna-Flow 65 68.7 3.8 7.59 30 733 837 872 pipe hydraulics are exceptional. Larger 3" 3.314 3.387 7.18 19 1,351 1,544 1,608 I.D.s enable Dyna-Flow,and related 80 84.2 5.0 10.69 19 613 700 729 components,to be down-sized within the 4" 4.310 4.473 10.86 19 1,784 2,039 2,124 system,thus increasing the potential for 90 109.5 6.7 16.16 19 809 925 963 job cost savings. For complete Hazen- Williams charts,refer to "Dyna-Flow Hydraulic Data Tables." . Coatings & Fabrication Specifications & Approvals Additional Benefits Dyna-Flow products are coated with Dyna-Flow/Super Flo pipe is manufac- • Lightweight and easy to install, an environmentally approved and tured to meet ASTM A-795 Type E, resulting in more efficient use of your specially formulated modified-acrylic or Grade A and is in compliance with freight and labor dollars. water-based coating. This durable coating NFPA-13 and NFPA-14.All sizes of is paintable.The black coating acts as Dyna Flow/Super Flo are UL Listed,FM • Provides stability needed to comply Approved and ULC Listed. with standard hanger spacing an excellent primer and is resistant to pp (15 ft O.C.)per NFPA. weathering and U.V. degradation from outdoor storage. 1 ® es • Available in Standard lengths for your Metallurgical properties provide excellent Listed Approved Listed convenience,or can be ordered in fabrication characteristics for end prep custom lengths upon approval. finishes,welding and roll grooving. Dyna-Flow/Super Flo is UL/ULC Listed • Fast cutting and welding, as well as for use with roll grooved,plain-end There is no special process or equipment couplings, and welded joints for wet,dry, easy roll grooving and end preparation. needed for fabrication and installation. preaction and deluge systems. It is FM • Available in Factory roll grooved form The internal surface of all black Allied Approved for roll grooved,plain-end,and for quicker shop turnaround. Tube& Conduit Fire Sprinkler pipe welded joints for wet systems. Refer to products up to 4.5000"in diameter is appropriate documentation for up-to-date • Clean,durable mill coating provides coated with our new Antibacterial listing and approval information. Dyna- longer"shelf life"and acts as an Formula, "ABF". In scientific laboratory Flow/Super Flo is now available"hot- excellent primer for custom paint test,ABS proved to have superior dip"galvanized and has been specifically applications. resistance to microbial colonization of approved by FM for dry systems uses. pipe walls,thereby delaying or possibly preventing the onset of Microbiologically Influenced corrosion(MIC)when the First Sprinkler System is first installed. 'NCO/Flow Control 16100 S. Lathrop• Harvey, IL 60426 Customer Service: y / \tel aHcJ11350 Norcom Rd. • Philadelphia, PA 19154 (800)882-5543 TUBE&CONDUIT 2525 N. 27th Ave. • Phoenix,AZ 85009 Fax 708-339-1806 S2 - 3 Vic-Flex® Sprinkler Fittings 4tauiicr Series AH5 Corrugated (Unbraided) Flexible Hose Assembly 10.89 Technical Specifications: Maximum Working Temperature: 225 F/107.2°C Maximum Working Pressure: • 175 psi/1206 kPa Connections: 725 To branch line (inlet)via 1725.4 mm NPT or BSPT male thread To sprinkler head (outlet) via 1/2" or 3/4"/15 mm or 20 mm NPT or BSPT female thread Approvals/Listings: Minimum Bend Radius: u� •47102mm See Victaulic Publication 10.01 for more details. Maximum Number of Bends per Flexible Drop: - — — See friction loss charts later in this document Product Description: - - • Do not bend within 2/763.5 mm from connection nut. Vic-FIexTM sprinkler fittings provide sprinkler installation on suspended ceiling grids utilizing a flexible,stainless Maximum K-Factor of Sprinkler to be Connected to steel hose. Refer to Installation Manual (I-AquaFlex)for all Reducer: applicable ASTM ceiling material and installation standards. • K5.6/8,1 (S.I.) (W reducer) System Components: • K8.O/11,5(S.I.) (3/4" reducer) • Hoses: Series AH5 7/8" Nominal ID Unbraided Hose Material Specifications: Assembly Lengths: 24, 31,36,48, 60, 727610, 790, 914, 1220, 1525, 1830 mm. • Series AH5 Hose: Note: length includes branch-line nipple and 5.57140 mm Corrugated Flexible Hose: Type 304 Stainless Steel straight reducer. Adapter Ring: Nylon • Sprinkler Reducers: lh" and 3/4715 and 20 mm Seal: Nitrile Rubber sprinkler connections in 5.5"/140 straight lengths. Nut and Nipple: Carbon Steel, Zinc-Plated • Branch Connections: 1"/25.4 mm NPT or BSPT branch Reducer(1/2 or 347: Carbon Steel, Zinc-Plated line nipples for attaching to rigid pipe. • Bracket: Carbon Steel, Zinc-Plated • Brackets: Style AB7 for suspended ceilings Job/Owner Engineer System No. Spec Section I Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I VicFlex Sprinkler Fittings I AH5 I Publication 10.89 10.89 6235 Rev.E Updated 01/2014 ©2014 Victaulic Company.All rights reserved. 1 jctaulicr victaulic.com I VicFlex Sprinkler Fittings I AH5 I Publication 10.89 Friction Loss Data—Series AH5 Unbraided Hose for use with Style AB7 VicFlex Brackets and Straight 5.5"Reducers 1 . ' Equivalent Length of Maximum Number of 90° Length of Stainless Actual Length of Stainless 1 inch/33.7mm , Bends at 4 inch/102mm Steel Flexible Hose Steel Flexible Hose Outlet Size Sch.40 Pipe Bend Radius inches feet inches mm inches meters 18 24* 28 /z 5.5 2 700 3/i 32 9.8 31 1/2I _ 82 31 2 780 3/4 33 10.1 h 44 36* 40 13.4 3 1000 48 3/° 14.6 53 48 48 /z 16.2 — 3 12203/4 55 ' 16.8 /z 68 60 61 20.7 3 1 1540 1 3/4 --. 63 19.2 Yz 73 72 22.3 72 1830 76 3 3/4 23.2 UL Notes: 1 The Series AH5 Unbraided Hose has been tested and Listed by UL for use in wet and dry systems per NFPA 13,13R,and 13D.UL 2443 standards for safety include,but are not limited to,pressure cycling,corrosion resistance,flow characterisitics,vibration resistance,leakage,mechanical and hydrostatic strength. Example:A 48-inch Series AH5 Unbraided Hose installed with two 30°bends and two 90°bends at a 4-inch bend radius is permitted and considered equivalent to the data in the table shown above.In this example,the total number of degrees is 240°,which is less than the allowable 270°. *These length hoses are only available in certain regions.Contact Victaulic for details. 10.89 6235 Rev.E Updated 01/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ictalulie victaulic.com I VicFlex Sprinkler Fittings I AH5 I Publication 10.89 Product Details—Series AH5 Unbraided Hose 6 E;'e 0 0 Item Description Hose I l ,,., 2 Adapter Ring ���I11llhhhhl It�ttt (ttltlltltl l�llll i1= �C 3 L Seal �I�IIviII1111111111111111111111111111111 {i 11 III I I I IIT 4 Nut n 5 -NippleSeries AH5 Unbraided Flexible Hose 5.51140 mm straight reducer -- - -- ---- -- (%"Nominal Diameter) VicFlexTM Style AB7 0 • Suspended Ceilings ID tci Item Description r1 24/610mm Stock Bar 2 Patented 1-Bee2 Center bracket al 3 . End Bracket649 � ,...;_tV..,..> 0 +34 Series AH5 Unbraided Hose and Style AB7 Bracket Assembly ‘ 1\�1��� Suspended Ceiling Grid with Recessed Sprinkler �`�1��i�\�\r� NOTE:Hose is permitted to be bent in alternative configurations.What is ��` shown is a typical T-Bar installation and the corresponding minimum clearance dimensions if one 90 bend is imparted to the hose. i ` R See Chart Hose Clearance Chart UL w Minimum I 4 ' �� Dimension end Radius Inches/mm I v........1....-_-,;_ __ See Chart 13% �� A Min. 4 •X•imi 0 11151 tib WI) t -r See Note =___ II«, �L it *I w1l• I';k1� '�) II�N 1 trier ��p�1 V2708'"112.7 mm MAX.RECESS • 10.89 6235 Rev.E Updated 01/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 �ctaulic'' I� - victaulic.com I VicFlex Sprinkler Fittings I AH5 I Publication 10.89 • Series AH5 Unbraided Hose and Style AB7 Bracket Assembly Suspended Ceiling Grid with Concealed Sprinkler %tjt NOTE:Hose is permitted to be bent in alternative configurations.What is - `1`l1? ` shown is typical T-Bar installation and the co `` responding minimum clearance ���`, dimensions if one 90 benddh is imparted to the hose. Hose Clearance Chart R — UL �� See Chart NDimension Inches/mm R Minimum 4 �_ Bend Radius 4 102 �m. A Min. 14s/a �C 372 �� awn v wool _� A _ See Chart me _, .. m_---_--z .,,=E.,„_. --- 1 ------.----.. _____... LA Seeee Note _�_ '`__ril \ mum / ` ..I�IN- -- II II 40110 I r WMII r *lei / linglikia:, , , ., V3802 W/12.7 mm MAX.RECESS 10.89 6235 Rev.E Updated 01/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ictaulie • victaulic.com I VicFlex Sprinkler Fittings I AH5 I Publication 10.89 • Flexible Hose In-Plane Bend Characteristics ONE BEND TWO BENDS THREE BENDS `w` ,mow`, 2X 2X Minimum Minimum Minimum bend radius bend radius bend radius Minimum OR OR bend radius f--...,,,.90° Minimum 1 Minimum 1 bend radius bend radius Minimum Minimum bend radius bend radius Minimum 1 bend radius Note:For out-of-plane(three-dimensional)bends care must be taken to avoid imparting torque on the hose Model Number Correlation Series AH5 Hose Series AQU Series AF Assembly Outlet Hose Assembly ' Hose Assembly Designation Size _ Designation ` DesignationAF AF-31T AHS 31 AU31 � Q - AF-36H a 1 AH5-36 h AF-36T 3/a AQU-36 - • — _ 7 1/2 AH5-48 3/a AQU-48 AF-48T • AH5-60 r/z AQU-60 I AF-60H 3/a AF-60T AF-72H AH5-72 /a 1 AQU-72 AF-72T Installation Note Reference should always be made to the I-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic and VicFlex are registered trademarks of Victaulic Company. • 10.89 6235 Rev.E Updated 01/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 5 ✓ctaulic.