Series TY-FRB — 2.8, �M;NU��; end 8.0 K-Factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General spheres.Although corrosion-resistant
coated sprinklers have passed the
Description standard corrosion tests of the appli-
cable approval agencies,the testing is 7 d#
IN
The TYCO Series TY-FRB, 2.8, 4.2, not representative of all possible cor- '. •
5.6, and 8.0 K-factor, Upright, Pen- rosive atmospheres. Consequently, i !
dent, and Recessed Pendent Sprin-
it is recommended that the end user 1'
klers described in this data sheet are be consulted with respect to the suit- t , ,.
quick response, standard coverage, ability of these coatings for any given -
decorative 3 mm glass bulb-type spray corrosive environment.The effects of ;II �' -
sprinklers designed for use in light or ambient temperature,concentration of . _ _ t
ordinary hazard,commercial occupan- chemicals,and gas/chemical velocity,
cies such as banks, hotels, and shop- should be considered, as a minimum,
ping malls. along with the corrosive nature of the
chemical td which the sprinklers will be
The recessed version of the Series TY- exposed.
FRB Pendent Sprinkler,where applica-
ble, is intended for use in areas with a An intermediate level of the Series TY- '
finished ceiling.This recessed pendent FRB Pendent Sprinklers is detailed
sprinkler uses one of the following: in Technical Data Sheet TFP356, and f uUe.
Sprinkler Guards are detailed in Tech- ,- u:.
• A two-piece Style 10(1/2 inch NPT) nical Data Sheet TFP780. i
or Style 40(3/4 inch NPT) Recessed ' 1 j!:4
- Escutcheon with 1/2 inch(12,7 mm)of NOTICE !
recessed adjustment or up to 3/4 inch .g
(19,1 mm)of total adjustment from the The Series TY-FRB, 2.8, 4.2, 5.6, -, ,---, ., j
flush pendent position,or a and 8.0 K-factor, Upright, Pendent,
and Recessed Pendent Sprinklers
• A two-piece Style 20 (1/2 inch NPT) described herein must be installed
or Style 30(3/4 inch NPT)Recessed and maintained in compliance with Sprinkler
Escutcheon with 1/4 inch(6,4 mm)of this document and with the applica-
recessed
p
adjustment or up to 1/2 inch ble standards of the National Fire Pro- Identification
(12,7 mm)of total adjustment from the tection Association, in addition to the
flush pendent position. standards of any authorities having Number (SIN)
The adjustment provided by the jurisdiction.Failure to do so may impair
Recessed Escutcheon reduces the the performance of these devices. TY1131: Upright 2.8K, 1/2"NPT
accuracy to which the fixed pipe drops The owner is responsible for maintain- TY1231: Pendent 2.8K, 1/2"NPT
to the sprinklers must be cut. ing their fire protection system and TY2131: Upright 4.2K, 1/2"NPT
Corrosion-resistant coatings, where devices in proper operating condition. TY2231: Pendent 4.2K, 1/2"NPT
applicable, are utilized to extend the The installing contractor or sprinkler TY3131: Upright 5.6K, 1/2"NPT
life of copper alloy sprinklers beyond manufacturer should be contacted with TY3231: Pendent 5.6K,1/2"NPT
that which would otherwise be obtained any questions. TY4131: Upright 8.0K,3/4"NPT
when exposed to corrosive atmo- TY4231: Pendent 8.0K,3/4"NPT
TY4831: Upright 8.0K, 1/2"NPT
TY4931: Pendent 8.0K, 1/2"NPT
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the `INSTALLER
WARNING"that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10 OCTOBER 2013 TFP171
VII
TFP171 «
Page 2 of 10 .
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE 7 - Bushing
I /
1
7/16"0 ��1' .
(11,1 mm) �;1,1�'` 3
i NOMINAL ,
2-1/4"
��L iii i �r 2
°1
MAKE-IN (57,2 mm) I •
II 2-3/16" 4
1 (55,6 mm) I if 1-9/16". (39,7 mm)
11 r5
- \ ii ■% 1� ii-■ '� :- i --6*
1/2"NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY1131)AND PENDENT(TY1231)SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
T1\
7/16" ��1'(11,1 mm) A 1 NOMINAL 2-3/16"1 / rMAKE IN 1 (55,6 mm) Iiif ; 0� 2 3/16" 1-1/2"
41 !=,
(55,6mm) li (38,1mm) • 5
In
1/2"NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT(7Y2131)AND PENDENT(TY2231)SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
TFP171
Page 3 of 10
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on 2 - Button Assembly Screw
Deflector. special request. ESCUTCHEON 4 - Bulb 6 - Deflector*
PLATE SEATING
SURFACE
7/16" ——--—---- 11111Wii--
._------------------
Emir_ P pt 3
(11,1 mm) .
rr
NOMINAL I � 2 3/16" � � 42
MAKE-IN (55,6 mm)
IN I�� 2-3/16" 1-1/2"
(55,6 mm) (38,1 mm)
I=_!-------5
_ - 6*
1/2" NPT** t WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA.
FLATS RECESSED
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY3131)AND PENDENT(TY3231)SPRINKLERS -
5.6 K-FACTOR, 1/2 INCH NPT
*Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression
is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Button Assembly Screw
Deflector. special request. PLATE SEATING 4 - Bulb 6 - Deflector*
SURFACE
1/2" I / off
�� 4 F 3
(12,7 mm) A
MAKE-
NOMINAL
..0 2-5/16" �� d 2
1 (58,7 mm)OA
s 1 2-1/4" I 1-9/16" 1 4
(57,2 mm) . (39,7 mm) .
f`___________5
3/4"NPT** t WRENCH STYLE 30 or 40 6
FLATS RECESSED 2-7/8"(73,0 mm)DIA.
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS
8.0 K-FACTOR,3/4 INCH NPT
ti
TFP171
Page 4 of 10
CEILING PLATE 1 - Frame 5 - Compression
SEATING SURFACE 2 - Button Screw
1 3 - Sealing 6 - Deflector* -
��•� —-�y� Assembly
,E �f 3 4 - Bulb
7/16" /72-1/4" J f*
1 (11,1 mm) I (57,2 mm) %� A 2
NOMINAL I
— MAKE IN I I * Temperature rating is
r
�1 2 3/16" 1 9/16" 4 indicated on Deflector.
(55,6 mm) i ii (39,7 mm)
C1,--5 ** Pipe thread connections
-__-•
_„'iii`\` * per ISO 7 1 can be
6 provided on special
1/2"NPT** t WRENCH request.
FLATS
UPRIGHT PENDENT CROSS SECTION
FIGURE 5
QUICK RESPONSE SERIES 7Y-FRB UPRIGHT(7Y4831)AND PENDENT(TY4931)SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical Design torque can distort the sprinkler Inlet
with consequent leakage or impairment
Data Criteria of the sprinkler.
Do not attempt to compensate for '
Approvals The TYCO Series TY-FRB, 2.8, 4.2, insufficient adjustment in the Escutch-
UL and C-UL Listed 5.6, and 8.0 K-factor, Upright, Pen- eon Plate by under-or over-tightening
FM, LPCB, and NYC Approved dent,and Recessed Pendent Sprinklers the sprinkler. Re-adjust the position of
Refer to Table A and B for complete are intended for fire protection sys- the sprinkler fitting to suit. -
approval information including tems designed in accordance with the
corrosion-resistant status. standard installation rules recognized Series TY-FRB Upright and Pendent
by the applicable Listing or Approval Sprinklers
Maximum Working Pressure agency (such as, UL Listing is based The Series TY-FRB Pendent and
Refer to Table C. on the requirements of NFPA 13, and Upright Sprinklers must be installed
FM Approval is based on the require- in accordance with the following
Discharge Coefficient ments of FM's Loss Prevention Data instructions.
K=2.8 GPM/psilI2 (40,3 LPM/barl12) Sheets). Only the Style 10, 20, 30, or Step 1.Install Pendent sprinklers in the
K=4.2 GPM/psi1i2 (60,5 LPM/barl'2) 40 Recessed Escutcheon,as applica pendent position. Install upright sprin-
K=5.6 GPM/psi112 (80,6 LPM/bar112) ble,is to be used for recessed pendent
K=8.0 GPM/psi112 (115,2 LPM/bars/2) installations. klers in the upright position.
Step 2. With pipe-thread sealant
Temperature Rating Installation applied to the pipe threads, hand-
Refer to Table A and B. tighten the sprinkler into the sprinkler
The TYCO Series TY-FRB, 2.8, 4.2, fitting.
Finishes 5.6,and 8.0 K-factor,Upright, Pendent, Step 3.Tighten the sprinkler into the
Sprinkler: Refer to Table D. Recessed and Recessed Pendent Sprinklersmust sprinkler ighg using ri thekW-Type 6
Escutcheon:White Coated, Chrome be installed in accordance with this Sprinkler Wrenchg onlynigure 14).With refer-
ence
..
Plated, or Brass Plated. section. to Figures 1 through 5,apply the
Physical Characteristics General Instructions W-Type 6 Sprinkler Wrench to the sprin-
Frame Bronze Do not install any bulb-type sprinkler if kler wrench flats.
Button Brass/Copper the bulb is cracked or there is a loss
Sealing Assembly Beryllium of liquid from the bulb.With the sprin- Series TY-FRB Recessed Pendent
Nickel w/TEFLON kler held horizontally,a small air bub- Sprinklers
Bulb Glass ble should be present. The diameter The Series TY-FRB Recessed Pendent
Compression Screw Bronze Sprinklers must be installed in accor-
Deflector Copper/Bronze of the air bubble is approximately 1/16
pp inch(1,6 mm)for the 135°F(57 C)and dance with the following instructions.
Bushing(K=2.8) Bronze 3/32 inch(2,4 mm)for the 286°F(141°C) Step A.After installing the Style 10,20,
Operation temperature ratings. 30, or 40 Mounting Plate, as applica-
A leak tight 1/2 inch NPT sprinkler joint ble,over the sprinkler threads and with
The glass bulb contains a fluid that shold be obtained by applying a min- pipe-thread sealant applied to the pipe
expands when exposed to heat. When imum to maximum torque of 7 to 14 threads,hand-tighten the sprinkler into
the rated temperature is reached, the ft.-lbs. (9,5 to 19,0 Nm). A leak tight the sprinkler fitting.
fluid expands sufficiently to shatter the 3/4 inch NPT sprinkler joint should be Step B.Tighten the sprinkler into the
glass bulb, allowing the sprinkler to obtained with a torque of 10 to 20 ft.- sprinkler fitting using only the W-Type -
activate and water to flow. lbs. (13,4 to 26,8 Nm). Higher levels of 7 Recessed Sprinkler Wrench (Figure
TFP171
Page 5 of 10
SPRINKLER FINISH(See Note 5)
KBULB LIQUID NATURAL CHROME SIGNAL***
FACTOR TYPE TEMPERATURE COLOR BRASS PLATED WHITE
135°F(57°C) Orange
PENDENT 155°F(68°C) Red
(TY1231)
and 175°F(79°C) Yellow 1,2,3,4
UPRIGHT (93°C) Green 200 F(93
(TY1131) ° °
286°F(141°C) Blue
135°F(57°C) Orange •
2.8 RECESSED C) Red
1/2" 155°F 68
° ( °NPT PENDENT
(TY1231)* 175°F(79°C) Yellow
Figure 6
200°F(93°C) Green
1,2,4
135°F(57°C) Orange
RECESSED °
155F(68 C) Red
PENDENT °
(TY1231)** 175°F(79°C) Yellow
Figure 7
200°F(93°C) Green
135°F(57°C) Orange •
PENDENT
(TY2231) 155°F(68°C) Red
and 175°F(79°C) Yellow
UPRIGHT )
(TY2131) (200°F 93°C Green
286°F(141°C) Blue
135°F(57°C) Orange
4.2 RECESSED 155
1/2" 155°F(68°C) Red 1,2 NPT PENDENT °
(TY2231)* 175°F(79°C) Yellow
Figure 8
•
200°F(93°C) Green
135°F(57°C) Orange
RECESSED F 155 68 C) Red
PENDENT 155°F( °
(TY2231)** 175°F(79°C) Yellow
Figure 9
200°F(93°C) Green
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers.
•Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
**Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable.
—*Frame and Deflector only.Listings and approvals apply to color(Special Order).
N/A:Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2.8 AND 4.2 K-FACTOR SPRINKLERS
15). With reference to Figures 1 to 4,
apply the W-Type 7 Recessed Sprinkler
Wrench to the sprinkler wrench flats.
Step C. After ceiling installation and
finishing, slide on the Style 10,20,30,
or 40 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP171 .
Page 6 of 10
SPRINKLER FINISH(See Note 8)
K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME SIGNAL*** LEAD _
FACTOR COLOR BRASS PLATED WHITE COATED
135°F(57°C) Orange
PENDENT
TY3231) 155°F(68°C) Red
and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5
UPRIGHT 200°F(93°C) Green
(TY3131) 286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
5.6 PENDENT 175°F(79°C) Yellow 1,2,4,5 N/A
1/2 NPT (TY3231)
Figure 10 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
(TY3231NT 175°F(79°C) Yellow 1,2,3,4,5 N/A
Figure 11 200°F(93°C) Green
286°F(141°C) Blue .
135°F(57°C) Orange
PENDET
(TY 2311) 155°F(68°C) Red
and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5
UPRIGHT
(TY4131) 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A
3/4 NPT (TY4231)
Figure 12 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
RECESSED 155°F(68°C) Red
TY4231NT 175°F(79°C) Yellow 1,2,3,5 N/A
Figure 13 200°F(93°C) Green
286°F(141°C) Blue
135°F(57°C) Orange
PENDT
(TY 981) 155°F(68°C) Red
1/28 NPT and 175°F(79°C) Yellow 1,2,4,5,6 1,2,5
UPRIGHT 200°F(93°C) Green
(TY4831) 286°F(141°C) Blue
NOTES:
1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate
the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax
31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed
as Corrosion-Resistant Sprinklers.Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved
as a Corrosion-Resistant Sprinklers.
'Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable.
"Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable.
*'*Frame and Deflector only.Listings and approvals apply to color(Special Order).
N/A:Not Available
TABLE B -
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
w
c TFP171
Page 7 of 10
SPRINKLER FINISH
• K TYPE NATURAL CHROME SIGNAL LEAD
FACTOR BRASS PLATED WHITE COATED
PENDENT(TY1231)
and
2.8 UPRIGHT(TY1131) 175 PSI(12,1 BAR) N/A
1/2"NPT
RECESSED
PENDENT(TY1231)
PENDENT(TY2231)
and
UPRIGHT(TY2131)
4.2 175 PSI(12,1 BAR) N/A
1/2"NPT
RECESSED
PENDENT(TY2231)
PENDENT(TY3231) 175 PSI
and
UPRIGHT(TY3131) 250 PSI(17,2 BAR) (12,1 BAR)
5.6 OR 175 PSI(12,1 BAR) —
1/2"NPT (SEE NOTE 1)
RECESSED N/A
PENDENT(TY3231)
PENDENT(TY4231) 175 PSI
and
UPRIGHT(TY4131) (12,1 BAR)
8.0 ••-, 175 PSI(12,1 BAR)
3/4"NPT
RECESSED N/A
PENDENT(TY4231)
PENDENT(TY4931)
1/2"NPT UPRIGHand T(TY4831) 5 PSI
175 PSI(12,1 BAR) (121 BAR)
NOTES:
1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the
Listing by Underwriters Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York.
TABLE C
MAXIMUM WORKING PRESSURE
Care and corrosive products of combustion, but tion Service in accordance with local
have not operated,should be replaced requirements and/or national codes.
if they cannot be completely cleaned
Maintenance Care must be exercised to avoid dam-
by wiping the sprinkler with a cloth or
The TYCO Series TY-FRB must be by brushing it with a soft bristle brush. age to the sprinklers -before, during,
and after installation. Sprinklers dam-
maintained and serviced in accordance
Care must be exercised to avoid dam- aged by dropping, striking, wrench
with this section. thesprinklers- before, during,to sp e s twist/sli a e, or the like, must be
and after installation.Sprinklers dam- PP g
Before closing a fire protection system P � replaced. Also, replace any sprinkler
main control valve for maintenance aged by dropping, striking, wrench that has a cracked bulb or that has lost
work on the fire protection system twist/slippage, or the like, must be liquid from its bulb. (Ref. Installation
that it controls, obtain permission to replaced. Also, replace any sprinkler Section).
shut down the affected fire
Protection
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation Initial and frequent visual inspections of
systems from the proper authoritiesbq random samples are recommended for
and notify all personnel who may be Section.) s
affected by this action. The owner is responsible for the thecorrosion-resistantintegrity
ityof
o sprinklers atverifya
P the integrity of the corrosion-resistant
Absence of the outer piece of an inspection,testing,and maintenance of material of construction. Thereafter,
escutcheon, which is used to cover their fire protection system and devices annual inspections per NFPA 25 should
a clearance hole, can delay sprinkler in compliance with this document, as suffice.
operation in a fire situation. well as with the applicable standards
of the National Fire Protection Associa- Inspections of corrosion-resistant
Sprinklers which are found to be leak- tion (e.g., NFPA 25), in addition to the sprinklers are recommended at close
ing or exhibiting visible signs of corro- standards of any other authorities hav- range, instead of from the floor level
sion must be replaced. ing jurisdiction. Contact the installing per NFPA. Inspection at close range
Automatic sprinklers must never be contractor or sprinkler manufacturer can better determine the exact sprin-
painted, plated, coated, or other- regarding any questions. kler condition and the long-term integ-
wise altered after leavingthe factory. rity of the corrosion-resistant material,
Y Automatic sprinkler systems are rec- which can be affected by the corrosive
Modified sprinklers must be replaced. ommended to be inspected, tested, conditions present.
Sprinklers that have been exposed to and maintained by a qualified Inspec-
TFP171 .
Page 8 of 10
. 2-7/8"DIA. _ 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 6,4 mm
1/4"(6,4 mm) (12,7±3,2 mm) 1/4"
2-1/4"DIA. 2 1/4"DIA. ( )
/ FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
/ 1/8" f
(3,2 mm) (3 mm)
� 1 1 _
Z,41.1__
MOUNTING
' Ir f MOUNTING
SURFACE IP
SURFACE ii�I�. ����N.i.
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16'(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 6 FIGURE 7
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT
2-7/8'DIA. _ 2-7/8'DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 1/46,4 mm"
�-2-1/4"DIA. -y 2 1/4'DIA. ( )
/ FACE OF (57,2 mm) MOUNTING / FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
411_
/ 1/8" / 1/8"
(3,2 mm) (3,2 mm)
��_i ___I
Vir
, J 1 \
MOUNTING1�r .MOUNTINGSURFACE
SURFACE •
CLOSURE SERIES 1-1/4'(31,8 mm) CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 8 FIGURE 9
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT
s' TFP171
Page 9 of 10
2-7/8"DIA. - 2-7/8"DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm) 1/2±1/8` (73,0 mm) 1/2"(12,7 mm)
(15,9±6,4 mm) 1/4"(6,4 mm) (12,7±3,2 mm) 1/4"(6,4
2-1/4"DIA. 2-1/4"DIA. mm)
/ FACE OF (57,2 mm) MOUNTING / FACE OF F (57,2 mm) MOUNTING
SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
/ 1/8" / 1/8"
(3,2 mm) 20_ _ (3,2 mm)
�� f
\ ,,, MOUNTING ,�'
MOUNTING 4 ��_ SURFACE -
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm) CLOSURE SERIES 1-1/4'(31,8 mm)
TY-FRB 3/4"(19,1 mm) TY-FRB 1"(25,4 mm)
FIGURE 10 FIGURE 11
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT 5.6 K-FACTOR, 1/2 INCH NPT
-
2-7/8" DIA. 2-7/8"DIA.
-
(73,0 mm) 3/4"(19,1 mm) (73,0 mm) 1/2'(12,7 mm)
5/8±1/4" 1/2±1/8"
(15,9±6,4 mm) 2-1/4" DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4"DIA. 1/4"(6,4 mm)
/ (57,2 mm) MOUNTING / FACE OF (57,2 mm) 1 MOUNTING
FACE OF
' SPRINKLER PLATE SPRINKLER PLATE
FITTING FITTING
1/8' 1/8"
/ (3,2 mm) / (3,2 mm)
l r 7/;/
i.
ror,....
. mr.111 .4_7 1•- --..-=---e LI I I 7 7 7 7/: '
'�. MOUNTING
MOUNTING L_. MI Af SURFACE
SURFACE � 1
CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16'(33,3 mm)
TY-FRB 13/16"(20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 12 FIGURE 13
SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3M INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR,3M INCH NPT 8.0 K-FACTOR,3M INCH NPT
Gv WRENCH
RECESS
WRENCH RECESS
(END"A" USED FOR /!41
,/....
1/2"NPT MODELS)
• t
WRENCH RECESS
(END"B"USED FOR
3/4° NPT MODELS) PUSH WRENCH
• IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14 FIGURE 15
W-TYPE 6 SPRINKLER W-TYPE 7 RECESSED
WRENCH SPRINKLER WRENCH
TFP171
Page 10 of 10
P/N 57 - XXX - X - XXX
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C)
331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 155°F(68°C)
(RAL9010)'
340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C)
(RAL9003)
341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK
20G 200°F(93°C)
(RAL9005)"
370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C)
371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED
390 8.0K UPRIGHT(3/4"NPT) TY4131 *Eastern Hemisphere sales only.
**Available in only 2.8K,4.2K,and
391 8.0K PENDENT(3/4"NPT) TY4231 8.0K,155°F(68°C)and 200°F(93°C);
requires lead time to manufacture.
360 8.0K UPRIGHT(1/2"NPT) TY4831°
361 8.0K PENDENT(1/2"NPT) TY4931°
TABLE D
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB(Specify SIN),
(specify K-factor), (specify Pendent or
Upright) Sprinkler (specify) tempera-
ture rating, (specify) finish or coating,
P/N(specify from Table D)
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N(specify*)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
*Refer to Technical Data Sheet TFP770
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 194461 Telephone+1-215-362-0700
Copyright 0 2013 Tyco Fire Products,LP. All rights reserved. -two
TEFLON is trademark of The DuPont Corporation. Fire Protection Products