Report S
Carrier RECEIVED
MAR 2 2 2016
CITY OF TIGARD
BUILDING DIVISION
SUBMITTAL
Project
11565 SW 67th AVE TIGARD
Date
Friday, March 4, 2016
Larry Goodroe
• Airefco, Inc
•
Table Of Contents
Project: -Untitled21 03/04/2016
Prepared By: Larry Goodroe 03:45PM
RTU-1 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
Unit Feature Sheet 11
Spec Sheet 12
Packaged Rooftop Builder 1.39z Page 2 of 12
RTU-1
Project: --Untitled2l 03/04/2016
Prepared By: Larry Goodroe 03:45PM
RTU-1
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
Spec Sheet
Packaged Rooftop Builder 1.39z Page 3 of 12
Unit Report For RTU-1
Project: -Untitled2l 03/04/2016
Prepared By:Larry Goodroe 03:45PM
Unit Parameters Dimensions(ft.in.)&Weight(lb.)*"
Unit Model. 48KCDA06A2A5-0A0A0 Unit Length: 6'2.375"
Unit Size. 06(5 Tons) Unit Width. 3'10.75"
Volts-Phase-Hertz. 208-3-60 Unit Height 3'5.375"
Heating Type. Gas "' Total Operating Weight: 607 lb
Duct Cfg• Vertical Supply/Vertical Return
Low Heat "' Weights and Dimensions are approximate. Weight does
Single Stage Compressor Models not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes.For exact
dimensions and weights,refer to appropriate product
• data catalog.
Lines and Filters
Return Air Filter Type. Throwaway
Return Air Filter Quantity. 4
Return Air Filter Size. 16 x 16 x 2
Unit Configuration
Medium Static Option Belt Drive
Al/Cu-AVCu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1-Year parts(std.)
5-Year compressor parts(std.)
10-Year heat exchanger-Aluminized(std.)
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number Description Quantity
48KCDA06A2A5-0A0A0 Rooftop Unit 1
Base Unit
Medium Static Option Belt Drive
None
•
Packaged Rooftop Builder 1.39z Page 4 of 12
•
•
•
Certified Drawing for RTU-1
Project:—Untdled2l 03/04/2016
Prepared By:Larry Goodroe 03:45PM
“lc, *11[3 r x.r 164 rmumma Rix riY:1 .11111.r -
1 DI**NTS 11 IA IKIIDV SIH31)M 60110 [33naAx.. [ wS�1m SSSaw 6 +Wu.,•moon
H I �631(3 DTII II[1EAS MIT ) 11 AXx[) A 1)IpNEI [MAKA
x 1H A'1'111'1"1'311?
E i)3 )11»
1.B [F01FI w 63.0111 HK 31 INII 1)111 14/ Cw31Ctq SIM
Nx 15 1S SFS I l? I1 Sx A I Ill•1353 IIS FM,1011 331131 ILL[
).y DlNtlq a III 1l* INII 111111 11121
311/N f1p5/131 hili lY 'lig I :•IHi NI MIN SONO ND[YY1
C 1 111.1533 DIA 6Aw[MUSS 7331
3 1A•3121 DIA 1¢331001x*3333*ARC
11011 1 3 3/1•.11 301(D*[*Al3*613
33-V
( 111.94 Il Y0 CD3*Ct1*
nit,,,, viv,x 3301
I 6 1 I/l'101 III POEN S3rk1 x3C1-*1
_ INN *1103111 ii661 _
(33110 K[[!f 03041 —'-- i rMl-101 001[[3331
*Ott-3[551 p11 i + 1x5[x31[3 64w1313 r*IIS(
•KCCSS "644[15[1 4 C64/M*ID1641,10101
Ilxl On- f 7 4
;UMMk0 _ _ - _ ` 1*FADES ,H[ 640"D*L[
KL[3516A[L CO*1i2 fll[ KC 11/3511111
I�I��� � IS-511 10111 ♦ 5 1/r• !N 113•111 II
-__ _- xl*AIAIP fill* HIM I • 3YI.1311,31)1 KIK,11/2 113.11
�D�1fU14 111111 .. , .. AIA I•• IN31 Ili•111 NS 1)116•IH II
BACK 64nF MI' I I C3 f Fmli�ixrai aii[i.lr i[ilui ana,
wla Er1a3 v1•a ur•
c^Iy ^h 2 III3 I1-J/1 • FOII 110[0.*»I/0 64 31K 6M
333* 1 .t •MAR au1* TAI I „ HOn IxxrKS ln•1rr i1w[3364
I [A NSEIO Ssler 'EI1112 Ili,,tv, 11646[i rllrl31
4.1 e
1 33/ /j f I IA
IVIII [)NII 111111 SEE 1»1 M[J 1 61/1Ilia I
I I I aASO QNI—^ �Fi 51j ft
-i 3-1i1
12911 •— IS51
3071
LK
iHl -(loot MOON Il-1/1--
ni
T., T� 111 1-II
f
loll
1111
'[*FCIIICK
1 El
I DfS(OMEt!
C 7 EIKI 1- - [*Slat 301 IIIDDO3 KORA
[ND 71:
i31FR
TAIL � K<E33 IA*LKEE53 [q)DFxA1F[ — —. S I *113 _1wr1164
K1091 I �• ]1D[KlNK Ix•Mll[ Ixfl SUMl11 IA •
Sf�
133 [D i _ L/ .Li __i3:
DI6431Fr /ivili= — ii i o• Rii� •. I,u3 w
sv
Ian 3064[ H trS 1-3/11 -3IB
1x1 / IS�HI 1101
14-//11 11111 11511
16 14
»-1»
111641 I6121 1.1 DA
/1 IU[i31t
nw
LEFT FRONT i2I. f 111111611
III
RIGHT
04-06 SINGLE ZONE ELECTRICAL 486(000281 r
I or 3 08-16-14 .4.4,44. 48KC COOLING MITH GAS HEAT -
Packaged Rooftop Builder 1.39z Page 5 of 12
I
•
•
Certified Drawing for RTU-1
Project:-Untitled2l 03/04/2016
Prepared By:Larry Goodroe 03:45PM
oi$10.11411 COMM NW COUP CNN, C f NNW
a88�I�,.nw,�A,1
NI) ■IPC KIWI CAI RING 31 WW1 ClIVENN III
IN. If. U3. N IN. K. (P. N 103 K. 1 I C
A w w 131 121 14 111 N IN 81 III II 31)10 INN IA 114 16211 11 1)1 1011
AIN N 142 IN 131 N III 51 III 14 16 M 1f 314 18311 IA 314 10211 N IN(M1
APC N 30) IN III II IN N 133 11 IA) M N 110 I0141 I)111 13111 H 1/113111
IN wW1 WINS r ICCIINSII!NI)`10 11PONNRI 1413 CAiNi Of
CORNER A CORNER B
0
•
I ft 110 �
CORNER D 'CORKER C
A 10P
y
mf l- R I NNR 1 'J
1110 - ft
00 =I 'tEl : 0o
TROOT
IBNC 04-06 SINGLE ZONE ELECTRICAL I8RCOOO281
:6? 09-16-IA 1w�- COOLING WITH GAS HEAT
Packaged Rooftop Builder 1.39z Page 6 of 12
•
•
Certified Drawing for RTU-1
Project:-Untitled2l 03/04/2016
Prepared By:Larry Goodroe 03:45PM
Service aearance
C
4 416 c
*NOY'
- ••". •-, A
(.2111,
LOCATON DIMENSION COMO-TIM
rrenn I1219 rent •lint examen<ts mounted on pmet
NI,Meowed.awnemence aide mew
18-in 4,451-mat
•ROCOMMentinl Mkt Clearance
12.t,(NZ rnron •Mermurn Marame
an 41067 rnrfn *Surface berme semen tc ouneed fn 4.,metal,masonry seal0
36-In(414mm Marfa.Wand meeker a-efectrIcaMme-coneuctve{e 5..vabod,fiberglass!
Special <heck for sources nf flue Ft-Meets webto 10-ft of ure fresh.<Mane hood
36-e 031a nuni •Side condensate dram a ased
1.1-In(4575001 •Patinemen deerance
46-n 0219-rrern •So Nue encharie amessolmatarherk surface,.cambusable metenel
42-es(1067 05,1 •Surface beim/sentwees poundal<at,mettstamsonre met another mrt)
36.514 WTI •Surkce babe*...cern ebednertlynoo-cmductsre(ea.wood,teseriMe
*Check Ion Mown*untts or beidefresh err Melees Minn 10-If ot thts mon
Smart
am outlet
110-113-Una not Magma forme aserheab Matradee Contact Appleation basmeemig for gmlence on am
awMaims plermne mereestabonmem or WrttC2116warces
Packaged Rooftop Builder 1.39z Page 7 of 12
. - .
Performance Summary For RTU-1
Project: -Untitled2l 03/04/2016
Prepared By: Larry Goodroe 03:45PM
Part Number:48KCDA06A2A5-0A0A0
ARI SEER. 14.10
Base Unit Dimensions
Unit Length. 74.4 in
Unit Width. 46.8 in
Unit Height 41.4 in
Operating Weight
Base Unit Weight 597 lb
Medium Static Option Belt Drive. 10 lb
Total Operating Weight. 607 lb
Unit
Unit Voltage-Phase-Hertz' 208-3-60
Air Discharge. Vertical
Fan Drive Type. Belt
Actual Airflow- 2000 CFM
Site Altitude 0 ft
Cooling Performance
Condenser Entering Air DB. 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB 67.0 F
Entering Air Enthalpy 31.44 BTU/lb
Evaporator Leaving Air DB. 58.6 F
Evaporator Leaving Air WEI. 57.3 F
Evaporator Leaving Air Enthalpy 24.57 BTU/Ib
Gross Cooling Capacity. 61.0 MBH
Gross Sensible Capacity' 46.23 MBH
Compressor Power Input 5.19 kW
Coil Bypass Factor 0.058
Heating Performance
Heating Airflow. 2000 CFM
Entering Air Temp. 70.0 F
Leaving Air Temp. 97.3 F
Gas Heating Input Capacity 72.0 MBH
Gas Heating Output Capacity 0.0/59.0 MBH
Temperature Rise. 27.3 F
Supply Fan
External Static Pressure' 0.50 in wg
Fan RPM. 1197
Fan Power 1.11 BHP
NOTE. Selected IFM RPM Range: 1035-1466
Electrical Data
Voltage Range. 187-253
Compressor#1 RLA• 15.9
Compressor#1 LRA• 110
Outdoor Fan Motor Qty: 1
Outdoor Fan FLA(ea). 1.4
Indoor Fan Motor Type. MED
- Indoor Fan Motor FLA. 8.4
Combustion Fan Motor FLA(ea). 0.48
Power Supply MCA. 30
Power Supply MOCP(Fuse or HACR): 45
Disconnect Size FLA. 30
Packaged Rooftop Builder 1.39z Page 8 of 12
Performance Summary For RTU-1
Project: -Untitled2l 03/04/2016
Prepared By: Larry Goodroe 03:45PM
Disconnect Size LRA. 185
• Electrical Convenience Outlet. None
Control Panel SCCR:5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels,db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 87.0 86.9 87.5
125 Hz 82.1 78.9 82.5
250 Hz 74.8 65.8 76.1
500 Hz 70.6 63.3 73.6
1000 Hz 67.2 62.7 71.3
2000 Hz 61.4 56.7 67.1
4000 Hz 63.1 52.5 64.1
8000 Hz 58.7 45.0 60.0
A-Weighted 74.0 68.7 77.0
Advanced Acoustics
0 r
1114, 1114
•0
Advanced Accoustics Parameters
1. Unit height above ground. 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground. 5.7 ft
4. Height of obstruction. 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction. 0.0 ft
Detailed Acoustics Information
Octave Band Center Freq.Hz 63 125 250 500 1k 2k 4k 8k Overall
A 87.5 82.5 76.1 73.6 71.3 67.1 64.1 60.0 89.2 Lw
B 61.3 66.4 67.5 70.4 71.3 68.3 65.1 58.9 76.7 LwA
C 55.1 50.1 43.7 41.2 38.9 34.7 31.7 27.6 56.8 Lp
D 28.934.0 35.1 38.0 38.9 35.9 32.7 26.5 44.3 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA
C Sound Pressure Levels at Specific Distance from Unit, Lp
D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA
Packaged Rooftop Builder 1.39z Page 9 of 12
1
Performance Summary For RTU-1
Project: -Untitled2l 03/04/2016
Prepared By: Larry Goodroe 03:45PM
Calculation methods used in this program are patterned after the ASHRAE Guide;other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space,an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
FanCurve
20 `,Boor + ���15100E0 ��
\ 15oo�n
18 \ R 2100fFM
161 \ \1CCRF14 N. `
..—.. N \
6 14 \, SOOBFP
c t:•••=,12
m
e 900RFM
en to II' 10 v
a -
V ce
N
c0
Cl) 700RPM
\ 30081#'
al
_ \\\ 2.00BAP
50:1111011.50BFP
_ ' 0.75919N .11, j‘, — 1 OOBFP \
cc 1 i rte I t I iv I I I < < i.
CO 03 06 09 12 15 18 21 24 27 30 33
Airbur(CFM-thousands)
RPM-1197 BHP=1.11 Maxin unRPM=2100MaxinunBHP=2.90
Note:Pleaseco ctapplicatianergineelingforselectionsoutsidetheshadedn gion.
SC-SystemCurveRP-RatedPoint
Packaged Rooftop Builder 1.39z Page 10 of 12
Project: --Untitled2l Unit Feature Sheet for RTU-1
03!0412016
Prepared By: Larry Goodroe 03:45PM
Barrie
.
el
WeatherMaker — 48KC
PACKAGED ROOFTOP GAS IIEATING/ELECTRIC COOLING UNITS-14 SEER
3.4.5 TONS
STANDARD FEATURES INCLUDE
•Piston 0R-410Ai WFC refrigerant
.,*..4,.. .;-,p� •Meets and exceeds ASI RAE 90.1 energy of ie
s rtcy levels
• Shoe compressors wept ntemMo
al e desk and overload protection
rs1& s r, s' r- •Singe-stage cooing cspaaty control
+..k 4 • ` •SEERS up tol40,EER's up to 12.0
t f• •Acutiarr refrigerant metering system
P rX .*. •Exclusive non-corrosive a composer condensate pan in accordance wan..a.0,,;
{
k �' 4'' AslitAE Standard 52,sloping Orman.side wcente dean
4' .'.`:„., • Standard cooling operation up to 115•F 146•C)and dower to 40•F Ii•C)
-dean to 25'F1-4'C)wen winter start ltd.
a • Pre-panted a ideror panels and primer-coated lir elor panels tested to
500 hours salt spray protection
•Fully nsuleted csbnret
•Exclusive IOC solid--'-'-control for onfioard degnosics with LED
!MN code designation bumrerconbol logic and energy saving indoor
tan actor steel
•Law Net models that meet Csifornd Ar QuakyMMnagwnent
h, Puron • induced draft gas heat combustor design
,., •Redundant gas vaireswen up Whip steges of heating
•Low pressure and high pressure match protected.
MAINTENANCE FEATURES:
•Access panels with easy grip handles
•Fnnovative easy startng.nostrp screws on unit access panels
•Two-meth dsposa6ne return writers and Topless filter access door
WEATHERMAKER SERIES •Direct Dive-ECU indoor motor rs standard with optional belt dare
sYSterns
WeatherMaker 48KC (14-SEER': omits are one-piece gas •TermnatWent faciatngulnae safety aloud troubleshooting and
heating,electric cooling units that are prewired and charged sipitied control box arrangement
withPurontR-410)refrigerant They are factory tested in both • Exclusive IOC soid-ststeconooltoeon-boaddsgnosticsweer LED
heating and cooling modes.and rated in accordance nth AHRI ermr code designation.burner corrhol loam and energy saving indoor
Standards 2102240. :WeatherMaker ends are designed m fan motor delay.
accordance with UL Standard 1995. and listed by the
INSTALLATION FEATURES:
Underwriters'Laboratories •Thnu-thabo tompowerentryrcapabiky
• Single point gas and electric conrection
•Ful perimeter base rad with built-in rigging adapters end fork slots
Approved and certMed by: •Feld convenable horn vertical to horizontal airflow
GM STANDARD WARRANTY:
• t0-yearheat exchanger-15-year stones steer option
• 5_,...
reor
C13 • Many optional upgrades also armee*OPTIONS INCLUDE BUT ARE NOT LOWED TO:
-'-•w•^" • PrenterLnk and RTU Open Mule Protocol DOC Cotrim
• Supply and Return Ali Smoke Detectors.high static motors
• Louvered condensercod guards
• Disconnect switch and convenience outlet options
• Stainless Steel heat exchange option
• Conoson resistant coil coating.
Certified to ISO 9001 • I•lgtn static motor option
• Patented Numidi-UiZer•adaptive dehunsditlsa on system.Thisoption
also includes Uotomesie 1 controls
• Hinged access panels
• Integrated econonwner system.Standard and Ultra Low Leak versions
For a cornptate 1st of options and accawones neferta the Product Data
Catalog foram unit.
Packaged Rooftop Builder 1.39z Page 11 of 12
Spec Sheet for RTU-1
Project: -Untitled2l 03/04/2016
Prepared By: Larry Goodroe 03:45PM
Packaged Rooftop Builder 1.39z Page 12 of 12
•
No Units Selected Part Number:
SUBMITTAL MicroMe ECD-SRT12SA-DWDS
FORM NO. 18486-2D 17/28/2015
Submitted To:
Company:
Job Name:
Notes: Economizer 30 lbs.,Hood 19 bs., Total 49 lbs.
A4ixed/Suppty air sensor.
44IField installed in the
FEATURES; indoor fan�1on•
PL6 Harness. ' (I) ,
Other=Ord options are amiable, Contact MMC. .• 4/ • hi // ...
• Internal ger driven dampers,96171114310 stowage and binding, Economizer controller. ' II
associated with standerd Abram.
• Designed specifically for disrhrge a_Pliraeore. ./ . --Al 16.9"
Easy to install. Easy to service. ��I�
•
• Priaty assembled manhood,with ainhum water entrainment ��
filters,for the outside porion of the hood. 401
• Uses standard titer access dor shipped with HVAC reit. 40
For factory installed tinged filler panel option Carrier ort nsrnber lii
CRPECONV003A00 or MMC part number 0840 -HDANGL
roust be ordered severaMey n addition to tre economizer.
•
Part number"ECD•SRTITA-HDOOR'tor Chassis 1 units. 4I\
Pan nmber"ECD-SRTyTA-HDOOR'tor Chasis2 unit. r,,,1 /
• Rer cod a sloped tor wader vHdt. Iv
• At harnesses and plugs needed are included. / \�\�`;� ' I
Direct coupled
Low ambient bckaA.
.40-1", !''r t
Honeywell corbW72el
s S,%i 7
economizer neyw eonbd syatssa. C I
•
. ... 4, a 0
acking
l To be removed prior to
Q Q .R !mental,gear drivarN • installation.
��,. i ] darnpers Outside air sensor
Haigh and law voltage plug ` (adjustable dry arts )-
Ivtodco.4s for propeller type
exhausts.power
THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MIROMETL'S WRITTEN CONSENT
MicroMett Corporation... Indianapolis Indiana—1-800-662-4822,Sparks Nevada—1-800-884-4662,Longview Texas—1-903-248-4800
•
•
ND Units Selected Part Number:
SUBMITTAL MicroMetl
ECD-SRT12SA-DWDS
FORM NO. 18486-1D 17/28/2015
Submitted To:
Company:
Job Name:
Notes: Not all options,configurations,controls,or product types,
are available with all sizes.
Options not shown may be available,contact factory.
PARTNUMBER - ECD - SRT12TA - DJDO - 0
t_
J....". _1 s 4-4-20 me catrd(Carrier DDC)
Economizer Internal Convenable(Through the End)-ECC F-0/A Flow Monitoring(Greentrol)
Ecenomizer Internal Daanaow-ECD M-Motorized relief(3 dmhg6®1'static)
Economizer Horizontal Extensa!Panel Mounted-ECE 5-Smoke Detector(Mum)
Economizer Memo!Horizontal-ECM e X-MFT style actuate((Beane only)
Economizer External Horizontal Ming Box-ECM
H Honeywell
faeloir-UML B-Beam
Small RoolTop-SA7 S-Siemens
Medium Rod Top-MET tla
D-Adjustable Dry Bub(0/A)
E-Enthalpy(0(A)
Chassis 1 and 2-12 F-Fixed Dry Bub
Chassis 2 Spurt Low Stake-52 X-Dtdererifel Dry Bub
Chassis 3 and 4-34 2-DMSr,nkal Enthalpy
Chassis 4 Special Low Static-S4 0-No Sensors
Chassis 5.05 1
Chassis 6 and 7.67 V4-Hdneywe6 Wr212A Logic Comeler
Chassis 6 and 6-69 s s J-Jade 1 Speed Indoor Fan
s 2-Jade 2 Speed Indoor Fan
Stardust production,no special compliance-S 1:B-Zip Base Module Only,1 or 2 Speed Indoor Fan
Damper Leakage,Ttle 24.2013,and AHRAE 90.1-2010-Ta a -Zip Base and Energy Module
Damper Leakage Vishtglon Stale Enemy Code-2012-Wa X-Zip Base,Energy Moore,and Cor maocation
module
tbalaioalmat No
Fist Level-A E0-Om Cords
It
may- D-Distribution
Economizers meet Title 24,2013,Prescriptive Section 140.4(e)4(a,b c,and h),de,t,and g when supplied with Note 3 controls,and
ASHRAE Standard 90.1-2010,Table 6.4.3.4.4 requirements.
S year parts and components warranty.Damper reliability and leakage.Relief.Sensor setpoint,reliability,calibration,and high limit.
2 Economizers meet Wasi gton State Energy Code,Commercial-2012,Section C402.4.5.2,Exception 4 for Unitary Packaged Equipment.
Motorized damper leakage.
• Economizers meet Title 24,2013,Mandatory Section 120.2 Economizer fault detection and diagnostic requirements.
4 Optional Energy Module required for use with CO2 or Power Exhaust.
✓ Only used with nm-current models.Current models TC,TCQ HC,HCQ LC,SC use'2'-lade 2 speed indoor fan option,even with 1 speed units.
4 Includes 500 ohm resistor and moles plug to connect with Carrier INAC unit.
THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MIROMETL'S WRITTEN CONSENT
MicroMetl Corporation... Indianapolis Indiana—1-800-662-4822,Sparks Nevada—1-800-884-4662,Longview Texas—1-903-248-4800
•
SUBMITTAL �.MicroMeti 48TC A04-48TC A07,48TCB04 B04-48TC
-5OTC BB0707,0 50TC A04-50TC A07,50TC Part Number:
0537-014A-00010
FORM NO.1174-1D I 8/4/2014
Submitted To:
Company:
Job Name: •
Notes: opening for dim 1 3/4"Alt.drain hole
the bottom electncal
connections
Knockdown CurbsBletop
.1 �I 1 16" corners
Full Perimeter 4.'
NOTES: '
• *Custom 1-heights Ate Available 201//
• 'Fully Insulated Penmeter Curbs Are Available And
Des- dDo With A suffix
• Hold' Down Brackets Are Available For Most Curbs 67 ale"
• Attach Ductwork Directly To Roof Curb Flange 11f Duet
Rest1 314"j 37 16OnIbp Of Curb i
• Any Posted Weight is Actual Weight.Not Shipping Weight r JlJ
• All Dividers&Supports ltPresent,Are Flush With lip Of
Curb ink.'ss Noted.
A
*Please Contact Factory For Pricing and Amiability
CROSS SECTION
FEATURES: OF CURB
2" kr--
• Ships Knockdown,Assembly I lardware Provided When
Needed
• Deck Pans When Factory Provided,Are Factor:Insulated
• Constructed OfGalvanized Steel 0537 Series Roofcurb Specifications lin Inches)
• (iasketing Package Provided MicroMeti Part Na Carrier Part No. A Weight
• Full Penmeter Wood Nailer Provided. 0537-008A-00010 8" 71 lbs
0537-011A-00010 11" 82 lbs
0537-014A-00010 CRRFCURBOO1 A02 14" 94 lbs
0537-018A-00010 18"
0537-024A-00010 CRRFCURBOO2A02 24" 131 lbs
THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MIROMETL'S WRITTEN CONSENT
MicroMetl Corporation... Indianapolis Indiana—1-800-662-4822,Sparks Nevada—1-800-884-4662,Longview Texas—1-903-248-4800